B08_Attach_2_Product_Information.pdf
PDF 21 MB Posted
- Attached to
- KALA-REPLACE HVAC AND HUMIDITY CONTROL SYSTEM IN T Federal contract opportunity
- Solicitation number
- 140P8226B0004
About this file
This document is a comprehensive product specification and operating manual for Mitsubishi Electric heat pump and air conditioning systems, along with an owner's manual for a Damp2Dry commercial dehumidifier.
The file contains detailed technical specifications for multiple HVAC units including the MXZ-SM60NL (60,000 BTU/H outdoor unit), MXZ-SM48NL (48,000 BTU/H outdoor unit), MSZ-GX30NL and MUZ-GX30NL (30,600 BTU/H wall-mounted system), MSZ-GX24NL (22,400 BTU/H wall-mounted unit), and MSZ-WR24NA and MUZ-WR24NA (24,000 BTU/H wall-mounted heat pump system). Specifications include cooling and heating capacities at various outdoor temperatures, efficiency ratings (SEER2, EER2, HSPF2, COP values), electrical requirements (208V/230V, 1-phase, 60Hz), refrigerant type (R454B or R410A), piping specifications, and operating temperature ranges. The systems feature INVERTER-driven compressors, multiple fan speeds, Wi-Fi connectivity, smart controls, and various protection systems. Accessories available include condensate pumps, wired and wireless controllers, mounting hardware, linesets, and optional defrost heaters. The Damp2Dry 310-pint commercial dehumidifier (Model 3PACD250) operates at 115V/60Hz with 1,130-watt input power, 515 CFM airflow, and 310 PPD dehumidification capacity at 90°F/90% RH, featuring automatic drainage, WiFi/Bluetooth connectivity, humidity control settings from 30-90%, and washable SUS304 filters. The dehumidifier manual includes comprehensive operating instructions, control panel features, error codes, troubleshooting guidance, and maintenance requirements.
View the file
Other files for this federal contract opportunity
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
MXZ-SM60NL
60,000 BTU/H HEAT PUMP OUTDOOR UNIT
Job Name:
System Reference: Date:
Specifications System Unit Type MXZ-SM60NL
Cooling at 95F1 (Non-Ducted // Mixed // Ducted)
Maximum Capacity Btu/h 60,000 // 60,000 // 60,000 Rated Capacity Btu/h 60,000 // 60,000 // 60,000 Minimum Capacity Btu/h 16,000 // 16,000 // 16,000 Maximum Power Input W 5,000 // 5,610 // 6,385 Rated Power Input W 5,000 // 5,610 // 6,385 Power Factor (208V) % 98.10 // 98.10 // 98.10 Power Factor (230V) % 98.10 // 98.10 // 98.10
Heating at 47F2 (Non-Ducted // Mixed // Ducted)
Maximum Capacity Btu/h 66,000 // 66,000 // 66,000 Rated Capacity Btu/h 66,000 // 66,000 // 66,000 Minimum Capacity Btu/h 13,500 // 13,500 // 13,500 Maximum Power Input W 4,720 // 5,230 // 5,865 Rated Power Input W 4,720 // 5,230 // 5,865 Power Factor (208V) % 98.10 // 98.10 // 98.10 Power Factor (230V) % 98.10 // 98.10 // 98.10
Heating at 17F3 (Non-Ducted // Mixed // Ducted)
Maximum Capacity Btu/h 65,000 // 65,000 // 65,000 Rated Capacity Btu/h 41,500 // 41,000 // 40,500 Maximum Power Input W 8,740 // 8,820 // 8,820 Rated Power Input W 4,195 // 4,450 // 4,750
Heating at 5F4 (Non-Ducted // Mixed // Ducted) Maximum Capacity Btu/h 46,500 // 46,500 // 46,500 Maximum Power Input W 6,815 // 7,175 // 7,575
Heating at -13F8 (Non-Ducted // Mixed // Ducted) Maximum Capacity Btu/h 30,000 // 30,000 // 30,000 Maximum Power Input W 6,765 // 6,765 // 6,765
Efficiency (Non-Ducted // Mixed // Ducted)
SEER21 20 // 18.20 // 16.40
EER21 12 // 10.70 // 9.40
HSPF2 (IV)2 10.50 // 10 // 9.50
COP at 47°F2 4.10 // 3.70 // 3.30 COP at 17°F at Maximum Capacity3 2.18 // 2.16 // 2.16 COP at 5°F at Maximum Capacity4 2 // 1.90 // 1.80 ENERGY STAR® Certified Yes // No // No
NOTES
1Cooling at 95°F (Indoor: 80°F DB, 67°F WB // Outdoor: 95°F DB, 75°F WB) 2Heating at 47°F (Indoor: 70°F DB, 60°F WB // Outdoor: 47°F DB, 43°F WB) 3Heating at 17°F (Indoor: 70°F DB, 60°F WB // Outdoor: 17°F DB, 15°F WB) 4Heating at 5°F (Indoor: 70°F DB, 60°F WB // Outdoor: 5°F DB, 4°F WB) 8Heating at -13°F (Indoor: 70°F DB, 60°F WB // Outdoor: -13°F DB, -14°F WB)
• Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
• A Maximum connected units reduced when PLA connected. Refer to manual for details
• B Branch box should be placed within the level between the outdoor unit and indoor units
• C 5°F DB - 115°F DB when optional wind baffles are installed For actual capacity performance based on indoor unit type and number of indoor units connected, please refer to MXZ Operational Performance.
Although the maximum connectable capacity is 130%, the outdoor unit cannot provide more than 100% of the rated capacity.
Please utilize this over capacity capability for load shedding or applications where it is known that all connected units will NOT be operating at the same time.
** Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):
• System cuts out in heating mode and automatically restarts at these temperatures.
GENERAL FEATURES
• Compatible with M- and P-Series and CITY MULTI® indoor units (branch box required for connection with M- and P-Series)
| • | Compressor overcurrent detection |
| • | Compressor thermal protection |
| • | Fan motor overheating/voltage protection |
| • | High pressure protection |
| • | INVERTER-driven compressor: Compressor generates the precise |
capacity needed to maintain a temperature set point.
• Quiet operation: Outdoor units are as quiet as a typical conversation, and most indoor units are whisper quiet.
• Seacoast protection: Seacoast protection on heat exchanger and base panel (rated for 2,000 hrs. in accordance with ASTM B117 testing)
• Thermal Differential 1°F
Specifications System Unit Type MXZ-SM60NL
Electrical
Electrical Power Requirements V AC / V AC, , Hz 208 / 230, 1, 60 Guaranteed Voltage Range V AC 198 - 253 Voltage: Indoor - Outdoor, S1-S2 V AC 230 Short-circuit Current Rating (SCCR) kA 5 Recommended Fuse/Breaker Size if Branch Box Powered by Outdoor Unit A 50
Recommended Fuse/Breaker Size without Branch Box or Branch Box Powered Separate A 40
MCA if Branch Box Powered by Outdoor Unit A 55 MOCP if Branch Box Powered by Outdoor Unit A 90 MCA without Branch Box or Branch Box Powered Separate A 45 MOCP without Branch Box or Branch Box Powered Separate A 80
Outdoor Unit
Fan Motor Output W 200+200 Defrost Method Reverse Cycle Blue Fin Heat Exchanger Coating Yes Sound Pressure Level, Cooling1 dB (A) 58 Sound Pressure Level, Heating2 dB (A) 59 Compressor Type Twin Rotary Compressor Model MRB53FEJMC-L Compressor Motor Output kW 4.1 Compressor Oil Type // Charge Type // oz RM68EH // 78 External Finish Color Munsell 3Y 7.8/1.1 Base Pan Heater Optional
Unit Dimensions (W x D x H) inch [mm] inch [mm] inch [mm] 41-11/32 [1,050] 13 [330] 52-11/16 [1,338]
Package Dimensions (W x D x H) inch [mm] inch [mm] inch [mm] 43 [1,090] 18 [450] 58-5/16 [1,480]
Unit Weight lbs [kg] 278 [126] Package Weight lbs [kg] 304 [138]
ODU Operating Temp. Range
Cooling Intake Air Temp (Maximum / MinimumC) °FDB 115 / 23 Cooling Thermal Lock-out / Re-start Temperatures °FDB N/A / N/A Heating Intake Air Temp (Maximum / Minimum) °FDB 70 / -13 Heating Thermal Lock-out / Re-start Temperatures** °FDB -24 / -14
Refrigerant Type R454B Pre-Charged Refrigerant Amount lbs, oz 6, 10
IDU Connection
Maximum Number of Connected IDU with Branch BoxA 8 Maximum Number of Connected IDU without Branch Box 12 Minimum Connected Capacity with Branch Box Btu/h 12,000 Minimum Connected Capacity without Branch Box Btu/h 30,000 Maximum connected capacity Btu/h 78,000
Piping
Liquid Pipe Size O.D. (Flared) inch [mm] 3/8 [9.52] Gas Pipe Size O.D. (Flared) inch [mm] 3/4 [19.05] Total Piping Length when using Branch Box ft [m] 492 [150] Total Piping Length without Branch Box ft [m] 492 [150] Maximum Height Difference*B, ODU above IDU ft [m] 164 [50] Maximum Height Difference*B, ODU below IDU ft [m] 131 [40] Maximum Height Difference*B, between branch boxes ft [m] 39 [12] Maximum Height Difference between IDU and IDU without branch box ft [m] 49 [15] Maximum Piping Length between ODU and Branch Box ft [m] 180 [55] Farthest Piping Length from ODU to IDU with Branch Box ft [m] 262 [80] Farthest Piping Length from ODU to IDU without Branch Box ft [m] 262 [80] Farthest Piping Length after Branch Box ft [m] 82 [25] Total Piping Length between Branch Boxes and IDU ft [m] 312 [95] Maximum Number of Bends for IDU 15
NOTES
1Cooling at 95°F (Indoor: 80°F DB, 67°F WB // Outdoor: 95°F DB, 75°F WB) 2Heating at 47°F (Indoor: 70°F DB, 60°F WB // Outdoor: 47°F DB, 43°F WB) 3Heating at 17°F (Indoor: 70°F DB, 60°F WB // Outdoor: 17°F DB, 15°F WB) 4Heating at 5°F (Indoor: 70°F DB, 60°F WB // Outdoor: 5°F DB, 4°F WB) 8Heating at -13°F (Indoor: 70°F DB, 60°F WB // Outdoor: -13°F DB, -14°F WB)
• Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
• A Maximum connected units reduced when PLA connected. Refer to manual for details
• B Branch box should be placed within the level between the outdoor unit and indoor units
• C 5°F DB - 115°F DB when optional wind baffles are installed For actual capacity performance based on indoor unit type and number of indoor units connected, please refer to MXZ Operational Performance.
Although the maximum connectable capacity is 130%, the outdoor unit cannot provide more than 100% of the rated capacity.
Please utilize this over capacity capability for load shedding or applications where it is known that all connected units will NOT be operating at the same time.
** Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):
• System cuts out in heating mode and automatically restarts at these temperatures.
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
SPECIFICATIONS: MXZ-SM60NL
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
OUTDOOR UNIT ACCESSORIES: MXZ-SM60NL
Mini-Split Wire
14 Gauge 4 wire Armored MiniSplit Cable250 ft roll SW144-250 14 Gauge 4 wire Armored MiniSplit Cable50 ft roll SW144-50 14 Gauge 4 wire MiniSplit Cable250 ft roll S144-250 14 Gauge 4 wire MiniSplit Cable50 ft roll S144-50 16 Gauge 4 wire Armored MiniSplit Cable250 ft roll SW164-250 16 Gauge 4 wire Armored MiniSplit Cable50 ft roll SW164-50 16 Gauge 4 wire MiniSplit Cable250 ft roll S164-250
Control Wire M-Net Control Wire 1000 Roll 16-AWG Standard Twisted Pair Shielded Jacketed- Plenum rated CW162S-1000 M-Net Control Wire 250 Roll 16-AWG Standard Twisted Pair Shielded Jacketed- Plenum rated CW162S-250
Branch Box
3 Port Branch Box PAC-LMA30BC 5 Port Branch Box PAC-LMA50BC Branch Box Enclosure BBE-1
Air Outlet Guide Air Outlet Guide 1 Piece PAC-SH96SG-E (two pieces are required)
Mounting Pad Condensing Unit Mounting Pad 24 x 42 x 3 ULTRILITE2 Centralized Drain Pan Centralized Drain Pan PAC-SH97DP-E
Port Adaptor
Adaptor 1/4 x 3/8 PAC-SJ87RJ-E Adaptor 12 x 38 PAC-SK88RJ-E Adaptor 12 x 58 PAC-SK89RJ-E Adaptor 38 x 12 ADP3812 Adaptor 38 x 58 PAC-SK90RJ-E
Alarm Kit Alarm Kit PAC-SL54AL-E Alarm Kit Interface PAC-IF55AL-E
Stand
18 Dual Fan Stand QSMS1802M 24 Dual Fan Stand QSMS2402M Condenser Wall Bracket QSWB2000M-1 Condenser Wall Bracket - Stainless Steel Finish QSWBSS Outdoor Unit 3-14 inch Mounting Base Pair - Plastic DSD-400P Outdoor Unit Stand 12 High QSMS1202M
Power Supplies & Auxiliary Components
3-Pin Wiring Harness PAC-715AD 5-Pin Wiring Harness PAC-725AD
Ball Valve
Refrigeration Ball Valve - 1/2 BV12FFSI2 Refrigeration Ball Valve - 1/4 BV14FFSI2 Refrigeration Ball Valve - 3/8 BV38FFSI2 Refrigeration Ball Valve - 5/8 BV58FFSI2
Control/Service Tool Maintenance Tool Interface PAC-USCMS-MN-1
Distribution pipe Brazed Connection MSDD-50BR-E Flare Connection MSDD-50AR2-E
Optional Defrost Heater Optional Defrost Heater PAC-SJ20BH-E Drain Socket Drain Socket PAC-SG60DS-E Air Deflector Vertical Air Deflector ADV-1 Snow/Rain Diverter SnowRain Diverter SRD-5 Hail Guards Hail Guard HG-A2
Wind Baffle Front Wind Baffle WB-PA3 (two pieces are required)
NOTES
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
METUS_2025-02_PROPIN
1340 Satellite Boulevard Suwanee, GA 30024 Toll Free: 800-433-4822 https://mitsubishicomfort.com
*1
*1
*1
OUTDOOR UNIT DIMENSIONS: MXZ-SM60NL
SPLIT-TYPE AIR CONDITIONERS
Español
Français
English OPERATING INSTRUCTIONS For user
• To use this unit correctly and safely, be sure to read these operating in-structions before use.
MANUAL DE INSTRUCCIONES Para los clientes
• Para utilizar esta unidad de forma correcta y segura, lea previamente estas instrucciones de funcionamiento.
NOTICE D’UTILISATION A l’attention des clients
• Pour avoir la certitude d’utiliser cet appareil correctement et en toute sécurité, veuillez lire cette notice d’instructions avant de mettre le clima-tiseur sous tension.
INDOOR UNIT
MSZ-WR18NA MSZ-WR24NA
JG79Y503H02_cover.indd 1 2019/05/13 17:50:06
En-1
● OPERATING INSTRUCTIONS ●
• Since rotating parts and parts which could cause an electric shock are used in this product, be sure to read these “Safety Precautions” before use.
• Since the cautionary items shown here are important for safety, be sure to observe them.
• After reading this manual, keep it together with the installation manual in a handy place for easy reference.
• Be sure to receive a guarantee card from your dealer and check that the purchased date and shop name, etc. are entered correctly.
Marks and their meanings WARNING : Incorrect handling could cause serious hazard, such as death, serious injury, etc. with a high probability.
CAUTION : Incorrect handling could cause serious hazard depending on the conditions.
Meanings of symbols used in this manual
: Be sure not to do.
: Be sure to follow the instruction.
: Never insert your fi nger or stick, etc.
: Never step onto the indoor/outdoor unit and do not put anything on them.
: Danger of electric shock. Be careful.
: Be sure to disconnect the power supply plug from the power outlet.
: Be sure to shut off the power.
SAFETY PRECAUTIONS
CONTENTS
� SAFETY PRECAUTIONS 1
� NAME OF EACH PART 3
� PREPARATION BEFORE OPERATION 4
� SELECTING OPERATION MODES 5
� FAN SPEED AND AIRFLOW DIRECTION ADJUSTMENT 6
� ECONO COOL OPERATION 6
� TIMER OPERATION (ON/OFF TIMER) 6
� CLEANING 7
� WHEN YOU THINK THAT TROUBLE HAS OCCURRED 8
� WHEN THE AIR CONDITIONER IS NOT GOING TO BE USED FOR A LONG TIME 9
� INSTALLATION PLACE AND ELECTRICAL WORK 9
� SPECIFICATIONS 9
WARNING
Do not connect the power cord to an intermediate point, use an extension cord, or connect multiple devices to a single AC outlet.
• This may cause overheating, fi re, or electric shock.
Make sure the power plug is free of dirt and insert it se-curely into the outlet.
• A dirty plug may cause fi re or electric shock.
Do not bundle, pull, or modify the power cord, and do not apply heat or place heavy objects on it.
• This may cause fi re or electric shock.
Do not turn the breaker OFF/ON or disconnect/connect the power plug during operation.
• This may create sparks, which can cause fi re.
• After the indoor unit is switched OFF with the remote con-troller, make sure to turn the breaker OFF or disconnect the power plug.
Do not expose your body directly to cool air for a prolonged length of time.
• This could be detrimental to your health.
The unit should not be installed, relocated, disassembled, altered, or repaired by the user.
• An improperly handled air conditioner may cause fi re, electric shock, injury, or water leakage, etc. Consult your dealer.
• If the power supply cord is damaged, it must be replaced by the manufacturer or its service agent in order to avoid a hazard.
When installing, relocating, or servicing the unit, make sure that no substance other than the specifi ed refrigerant (R410A) enters the refrigerant circuit.
• Any presence of foreign substance such as air can cause abnormal pressure rise and may result in explosion or injury.
• The use of any refrigerant other than that specifi ed for the system will cause mechanical failure, system malfunction, or unit breakdown. In the worst case, this could lead to a serious impediment to securing product safety.
This appliance is not intended for use by persons (includ-ing children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concern-ing use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
Do not insert your fi nger, a stick, or other objects into the air inlet or outlet.
• This may cause injury, since the fan inside rotates at high speeds during operation.
In case of an abnormal condition (such as a burning smell), stop the air conditioner and disconnect the power plug or turn the breaker OFF.
• A continued operation in the abnormal state may cause a malfunction, fi re, or electric shock. In this case, consult your dealer.
When the air conditioner does not cool or heat, there is a possibility of refrigerant leakage. In this case, consult your dealer. If a repair involves recharging the unit with refrigerant, ask the service technician for details.
• The refrigerant used in the air conditioner is safe. Normally, it does not leak. However, if refrigerant leaks and comes in contact with a heat source such as a fan heater, kerosene heater, or cooking stove, it will create a harmful gas.
The user should never attempt to wash the inside of the indoor unit. Should the inside of the unit require cleaning, contact your dealer.
• Unsuitable detergent may cause damage to plastic material inside the unit, which may result in water leakage. Should detergent come in contact with electrical parts or the motor, it will result in a malfunction, smoke, or fi re.
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for com-mercial use by lay persons.
JG79Y503H02_01En.indd 1 2019/03/18 16:55:25
En-2
SAFETY PRECAUTIONS
CAUTION
Do not touch the air inlet or the aluminum fi ns of the in-door/outdoor unit.
• This may cause injury.
Do not use insecticides or fl ammable sprays on the unit.
• This may cause a fi re or deformation of the unit.
Do not expose pets or houseplants to direct airfl ow.
• This may cause injury to the pets or plants.
Do not place other electric appliances or furniture under the indoor/outdoor unit.
• Water may drip down from the unit, which may cause damage or malfunction.
Do not leave the unit on a damaged installation stand.
• The unit may fall and cause injury.
Do not step on an unstable bench to operate or clean the unit.
• This may cause injury if you fall down.
Do not pull the power cord.
• This may cause a portion of the core wire to break, which may cause overheating or fi re.
Do not charge or disassemble the batteries, and do not throw them into a fi re.
• This may cause the batteries to leak, or cause a fi re or explo-sion.
Do not operate the unit for more than 4 hours at high hu-midity (80% RH or more) and/or with windows or outside door left open.
• This may cause the water condensation in the air conditioner, which may drip down, wetting or damaging the furniture.
• The water condensation in the air conditioner may contribute to growth of fungi, such as mold.
Do not use the unit for special purposes, such as storing food, raising animals, growing plants, or preserving preci-sion devices or art objects.
• This may cause deterioration of quality, or harm to animals and plants.
Do not expose combustion appliances to direct airfl ow.
• This may cause incomplete combustion.
Never put batteries in your mouth for any reason to avoid accidental ingestion.
• Battery ingestion may cause choking and/or poisoning.
Before cleaning the unit, switch it OFF and disconnect the power plug or turn the breaker OFF.
• This may cause injury, since the fan inside rotates at high speeds during operation.
When the unit will be unused for a long time, disconnect the power plug or turn the breaker OFF.
• The unit may accumulate dirt, which may cause overheating or fi re.
Replace all batteries of the remote controller with new ones of the same type.
• Using an old battery together with a new one may cause overheating, leakage, or explosion.
If the battery fl uid comes in contact with your skin or clothes, wash them thoroughly with clean water.
• If the battery fl uid comes in contact with your eyes, wash them thoroughly with clean water and immediately seek medical attention.
Ensure that the area is well-ventilated when the unit is oper-ated together with a combustion appliance.
• Inadequate ventilation may cause oxygen starvation.
Turn the breaker OFF when you hear thunder and there is a possibility of a lightning strike.
• The unit may be damaged if lightning strikes.
After the air conditioner is used for several seasons, per-form inspection and maintenance in addition to normal cleaning.
• Dirt or dust in the unit may create an unpleasant odor, con-tribute to growth of fungi, such as mold, or clog the drain pas-sage, and cause water to leak from the indoor unit. Consult your dealer for inspection and maintenance, which require specialized knowledge and skills.
Do not operate switches with wet hands.
• This may cause electric shock.
Do not clean the air conditioner with water or place an object that contains water, such as a fl ower vase, on it.
• This may cause fi re or electric shock.
Do not step on or place any object on the outdoor unit.
• This may cause injury if you or the object falls down.
For installation
WARNING
Consult your dealer for installing the air conditioner.
• It should not be installed by the user since installation requires specialized knowledge and skills. An improperly installed air conditioner may cause water leakage, fi re, or electric shock.
Provide a dedicated power supply for the air conditioner.
• A non-dedicated power supply may cause overheating or fi re.
Do not install the unit where fl ammable gas could leak.
• If gas leaks and accumulates around the unit, it may cause an explosion.
Ground the unit correctly.
• Do not connect the ground wire to a gas pipe, water pipe, lightning rod, or a telephone ground wire. Improper grounding may cause electric shock.
CAUTION
Install a Ground Fault Interrupt (GFI) circuit breaker depend-ing on the installation location of the air conditioner (such as highly humid areas).
• If the Ground Fault Interrupt (GFI) breaker is not installed, it may cause electric shock.
Ensure that the drain water is properly drained.
• If the drain passage is improper, water may drip down from the indoor/outdoor unit, wetting and damaging the furniture.
In case of an abnormal condition Immediately stop operating the air conditioner and consult your dealer.
IMPORTANT
Dirty fi lters cause condensation in the air conditioner which will con-tribute to the growth of fungi such as mold. It is therefore recommended to clean air fi lters every 2 weeks.
JG79Y503H02_01En.indd 2 2019/03/18 16:55:25
En-3
Operation indicator lamp
Remote control receiving section
Emergency operation switch Page 5
Air inlet (back and side)
Refrigerant piping
Drainage hose
Air outlet
Drain outlet
Horizontal vane
Air outlet
Air fi lter
Air inlet
Heat exchanger
Front panel
Outdoor unit
NAME OF EACH PART
Indoor unit Remote controller
Outdoor units may be different in appearance.
Air cleaning fi lter (Anti-allergy Enzyme Filter, option)
Display section
Signal transmitting section Distance of signal :
About 20 ft. (6 m)
Beep(s) is (are) heard from the indoor unit when the signal is received.
Operation display section
OFF/ON
(stop/operate) button
Temperature buttons Pages 4, 5
Operation select button
ECONO
COOL button
FAN speed control button
VANE control button Page 6
TIME set button
RESET button
TIMER mode select button
Only use the remote controller provided with the unit.
Do not use other remote controllers.
If two or more indoor units are installed in proximity to one another, an indoor unit that is not intended to be operated may respond to the remote controller.
JG79Y503H02_01En.indd 3 2019/03/18 16:55:26
En-4
Before operation: Insert the power supply plug into the power outlet and/or turn the breaker on.
Installing the remote controller batteries
PREPARATION BEFORE OPERATION
Changing temperature units (°F→°C) Unit is preset with °F.
1. Press RESET while the temperature but-tons are pressed.
• Press RESET gently using a thin instrument.
• To change temperature unit from °C to °F, press RESET.
• Make sure the polarity of the batteries is correct.
• Do not use manganese batteries and leaking batteries. The remote controller could malfunction.
• Do not use rechargeable batteries.
• Replace all batteries with new ones of the same type.
• Batteries can be used for approximately 1 year. However, batteries with expired shelf lives last shorter.
1. Remove the back lid.
3. Install the back lid.
2. Insert the negative pole of AAA alkaline batteries fi rst.
• Press RESET gently using a thin instrument.
If the RESET button is not pressed, the remote controller may not operate correctly.
4. Press RESET.
JG79Y503H02_01En.indd 4 2019/03/18 16:55:26
En-5
COOL mode Enjoy cool air at your desired temperature.
Note:
Do not operate COOL mode at very low outside temperatures (less than 14°F [-10°C]). Water condensed in the unit may drip and wet or damage furniture, etc.
DRY mode Dehumidify your room. The room may be cooled slightly.
Temperature cannot be set during DRY mode.
HEAT mode Enjoy warm air at your desired temperature.
Operation indicator lamp
Emergency operation When the remote controller cannot be used...
Emergency operation can be activated by pressing the emergency operation switch (E.O.SW) on the indoor unit.
Each time the E.O.SW is pressed, the operation changes in the following order:
Auto restart function If a power failure occurs or the main power is turned off during operation, “Auto restart function” automatically starts operation in the same mode as the one set with the remote controller just before the shutoff of the main power. When timer is set, timer setting is cancelled and the unit starts operation when power is resumed.
If you do not want to use this function, please consult the service repre-sentative because the setting of the unit needs to be changed.
SELECTING OPERATION MODES
Set temperature : 75°F (24°C) Fan speed : Medium Horizontal vane : Auto
Emergency COOL
Emergency HEAT
Stop
Note:
The fi rst 30 minutes of operation is test run. Temperature control does not work, and fan speed is set to High.
Operation indicator lamp The operation indicator lamp shows the operation state of the unit.
Indication Operation state Room temperature
The unit is operating to reach the set temperature
About 4°F (2°C) or more away from set temperature
The room temperature is approach-ing the set temperature
About 2 to 4°F (1 to 2°C) from set tem-perature
Lit Not lit
1 Press to start the operation.
2 Press to select operation mode. Each press changes mode in the following order:
3 Press or to set the temperature.
Each press raises or lowers the temperature by 1°F (1°C).
Press to stop the operation.
• The same setting is selected the next time by simply pressing .
(COOL)
(DRY)
(HEAT)
JG79Y503H02_01En.indd 5 2019/03/18 16:55:27
En-6
FAN SPEED AND
AIRFLOW DIRECTION ADJUSTMENT
Press to select fan speed. Each press changes fan speed in the following order:
• Two short beeps are heard from the indoor unit when set to AUTO.
Press to select airfl ow direction. Each press changes airfl ow direction in the following order:
• Two short beeps are heard from the indoor unit when set to AUTO.
Airflow direction
(AUTO) .........The vane is set to the most effi cient airfl ow direction. COOL/ DRY:horizontal position. HEAT:position (4).
(Manual) .......For efficient air conditioning, select the upper position for COOL/DRY, and the lower position for HEAT. If the position
(4) or (5) is selected during COOL/DRY, the vane automatically moves to the upward position after 0.5 to 1 hour to prevent any condensation from dripping.
(Swing) .........The vane moves up and down intermittently.
� To change the horizontal airfl ow direction.
Move the vertical vane manually before starting operation.
(AUTO) (Low) (Med.) (High) (Super High)
(AUTO) (1) (2) (3) (4) (5) (SWING)
ECONO COOL OPERATION
TIMER OPERATION (ON/OFF TIMER)
Press during COOL mode page 5 to start ECONO COOL operation.
The unit performs swing operation vertically in various cycle according to the temperature of the airflow. Set temperature is set 4°F (2°C) higher automatically.
Press again to cancel ECONO COOL operation.
• ECONO COOL operation also is cancelled when the VANE button is pressed.
What is “ECONO COOL”?
Swing air fl ow (change of air fl ow) makes you feel cooler than constant air fl ow.
So, even though the set temperature is automatically set 4°F (2°C) higher, it is possible to perform cooling operation with keeping comfort. As a result, energy can be saved.
1 Press during operation to set the timer.
Each press changes timer mode in the following order:
2 Press to set the time of timer.
Each press increases or decreases the set time by 1 hour.
Press until “TIMER RELEASE” is selected to release timer.
Note:
• ON and OFF timers can not be used in combination.
• If power failure occurs while ON/OFF timer is set, see page 5 “Auto restart function”.
(OFF TIMER) (ON TIMER)
TIMER
RELEASE
JG79Y503H02_01En.indd 6 2019/03/18 16:55:28
En-7
Instructions:
CLEANING
• Switch off the power supply or turn off the breaker before cleaning.
• Be careful not to touch the metal parts with your hands.
• Do not use benzine, thinner, polishing powder, or insecticide.
• Use only diluted mild detergents.
• Do not expose parts to direct sunlight, heat, or fi re to dry.
• Do not use water hotter than 120°F (50°C).
Front panel
1. Lift the front panel until a “click” is heard.
2. Hold the hinges and pull to remove as shown in the above illustration.
• Wipe with a soft dry cloth or rinse it with water.
• Do not soak it in water for more than two hours.
• Dry it well in shade before installing it.
3. Install the front panel by following the removal procedure in reverse. Close the front panel securely and press the positions indicated by the arrows.
Air fi lter
• Clean every 2 weeks
• Remove dirt by a vacuum cleaner, or rinse with water.
• Dry it well in shade before installing it.
Hinge Hole
Air cleaning fi lter (Anti-allergy Enzyme Filter, option) Back side of air fi lter Every 3 months:
• Remove dirt by a vacuum cleaner.
When dirt cannot be removed by vacuum cleaning:
• Soak the fi lter and its frame in lukewarm water before rinsing it.
• After washing, dry it well in shade.
Every year:
• Replace it with a new air cleaning fi lter for best performance.
• Parts Number MAC-408FT-E
Pull to remove from the air fi lter
Important
• Clean the fi lters regularly for best performance and to re-duce power consumption.
• Dirty fi lters cause condensation in the air conditioner which will contribute to the growth of fungi such as mold. It is therefore recommended to clean air fi lters every 2 weeks.
JG79Y503H02_01En.indd 7 2019/03/18 16:55:28
En-8
Even if these items are checked, when the unit does not recover from the trouble, stop using the air conditioner and consult your dealer.
Symptom Explanation & Check points Indoor Unit The unit cannot be operated. • Is the breaker turned on?
• Is the power supply plug connected?
• Is the ON timer set? Page 6
All LED lamps on the indoor unit are blinking.
• Are the horizontal vanes installed correctly?
The horizontal vane does not move.
• Are the horizontal vanes installed cor-rectly?
• Is the fan guard deformed?
The unit cannot be operated for about 3 minutes when restarted.
• This protects the unit according to instruc-tions from the microprocessor. Please wait.
Mist is discharged from the air outlet of the indoor unit.
• The cool air from the unit rapidly cools mois-ture in the air inside the room, and it turns into mist.
The swing operation of the HORIZONTAL VANE is suspended for a while, then restarted.
• This is for the swing operation of the HORI- ZONTAL VANE to be performed normally.
The airfl ow direction changes during operation.
The direction of the horizontal vane cannot be adjusted with the remote controller.
• When the unit is operated in COOL or DRY mode, if the operation continues with air blowing down for 0.5 to 1 hour, the direction of the airfl ow is automatically set to upward position to prevent water from condensing and dripping.
• In the heating operation, if the airfl ow tem-perature is too low or when defrosting is be-ing done, the horizontal vane is automatically set to horizontal position.
The operation stops for about 10 minutes in the heating operation.
• Outdoor unit is in defrost.
Since this is completed in max.10 minutes, please wait. (When the outside temperature is too low and humidity is too high, frost is formed.)
The unit starts operation by itself when the main power is turned on, but hasn’t received sign from the remote control-ler.
• These models are equipped with an auto re-start function. When the main power is turned off without stopping the unit with the remote controller and is turned on again, the unit starts operation automatically in the same mode as the one set with the remote control-ler just before the shutoff of the main power.
Refer to “Auto restart function”. Page 5
The indoor unit discolors over time.
• Although plastic turns yellow due to the infl u-ence of some factors such as ultraviolet light and temperature, this has no effect on the product functions.
Outdoor Unit The fan of the outdoor unit does not rotate even though the compressor is running.
Even if the fan starts to rotate, it stops soon.
• When the outside temperature is low dur-ing cooling operation, the fan operates intermittently to maintain suffi cient cooling capacity.
Water leaks from the outdoor unit.
• During COOL and DRY operations, pipe or pipe connecting sections are cooled and this causes water to condense.
• In the heating operation, water condensed on the heat exchanger drips down.
• In the heating operation, the defrosting operation makes ice forming on the outdoor unit melt and drip down.
White smoke is discharged from the outdoor unit.
• In the heating operation, vapor generated by the defrosting operation looks like white smoke.
Symptom Explanation & Check points Remote controller The display on the remote controller does not appear or it is dim. The indoor unit does not respond to the remote control signal.
• Are the batteries exhausted? Page 4
• Is the polarity (+, -) of the batteries correct?
• Are any buttons on the remote controller of other electric appliances being pressed?
Does not cool or heat The room cannot be cooled or heated suffi ciently.
• Is the temperature setting appropriate?
• Is the fan setting appropriate? Please change fan speed to High or Super High. Page 6
• Are the fi lters clean? Page 7
• Is the fan or heat exchanger of the indoor unit clean?
• Are there any obstacles blocking the air inlet or outlet of the indoor or outdoor unit?
• Is a window or door open?
• It may take a certain time to reach the setting temperature or may not reach that depending on the size of the room, the ambient tempera-ture, and the like.
The room cannot be cooled suffi ciently.
• When a ventilation fan or a gas cooker is used in a room, the cooling load increases, resulting in an insuffi cient cooling effect.
• When the outside temperature is high, the cooling effect may not be suffi cient.
The room cannot be heated suffi ciently.
• When the outside temperature is low, the heating effect may not be suffi cient.
Air does not blow out soon in the heating operation.
• Please wait as the unit is preparing to blow out warm air.
Airfl ow The air from the indoor unit smells strange.
• Are the fi lters clean? Page 7
• Is the fan or heat exchanger of the indoor unit clean?
• The unit may suck in an odor adhering to the wall, carpet, furniture, cloth, etc. and blow it out with the air.
Sound Cracking sound is heard. • This sound is generated by the expansion/ contraction of the front panel, etc. due to change in temperature.
“Burbling” sound is heard. • This sound is heard when the outside air is absorbed from the drain hose by turning on the range hood or the ventilation fan, making water fl owing in the drain hose to spout out.
This sound is also heard when the outside air blows into the drain hose in case the outside wind is strong.
Mechanical sound is heard from the indoor unit.
• This is the switching sound in turning on/off the fan or the compressor.
The sound of water fl owing is heard.
• This is the sound of refrigerant or condensed water fl owing in the unit.
Hissing sound is sometimes heard.
• This is the sound when the fl ow of refrigerant inside the unit is changed.
In the following cases, stop using the air conditioner and consult your dealer.
• When water leaks or drips from the indoor unit.
• When the upper operation indicator lamp blinks.
• When the breaker trips frequently.
• The remote control signal is not received in a room where an electronic ON/OFF type fl uorescent lamp (inverter-type fl uorescent lamp, etc.) is used.
• Operation of the air conditioner interferes with radio or TV reception. An ampli-fi er may be required for the affected device.
• When an abnormal sound is heard.
• When any refrigerant leakage is found.
WHEN YOU THINK THAT TROUBLE HAS OCCURRED
JG79Y503H02_01En.indd 8 2019/03/18 16:55:28
En-9
Installation place Avoid installing the air conditioner in the following places.
• Where there is much machine oil.
• Salty places such as the seaside.
• Where sulfi de gas is generated such as hot spring, sewage, waste water.
• Where oil is splashed or where the area is fi lled with oily smoke. (such as cooking areas and factories, in which the properties of plastic could be changed and damaged).
• Where there is high-frequency or wireless equipment.
• Where the air from the outdoor unit air outlet is blocked.
• Where the operation sound or air from the outdoor unit brothers the house next door.
• The mounting height of indoor unit 5.9 ft. to 7.5 ft. (1.8 m to 2.3 m) is recom-mended. If it is impossible, please consult your dealer.
Electrical work
• Provide an exclusive circuit for the power supply of the air conditioner.
• Be sure to observe the breaker capacity.
If you have any questions, consult your dealer.
INSTALLATION PLACE AND
ELECTRICAL WORK
SPECIFICATIONS
To prevent the effects of a fl uorescent lamp, keep as far apart as possible.
wall, etc.
Inverter-type fl uorescent lamp
Keep a space to prevent the pic-ture distortion or the noise.
3 ft. (1 m) or more
Radio
4 in. (100 mm) or more
For the optimum effi ciency and to extend the life time of using, the outdoor unit should be installed in a well-ventilated dry place.
TV
Cordless phone or Portable phone
10 ft.
(3 m) or more
3 ft. (1 m) or more
The installation location of the outdoor unit should be at least 10 ft. (3 m) away from the antennas for TV sets, radios, etc. In areas where the reception is weak, provide greater space between the outdoor unit and the antenna of the affected device if operation of the air conditioner interferes with radio or TV reception.
1 Set to the highest temperature in manual COOL mode, and operate for 3 to 4 hours. Page 5
• This dries the inside of the unit.
• Moisture in the air conditioner contributes to favorable conditions for growth of fungi, such as mold.
2 Press to stop the operation.
3 Turn off the breaker and/or disconnect the power sup-ply plug.
4 Remove all batteries from the remote controller.
When using the air conditioner again:
1 Clean the air fi lter. Page 7
2 Check that the air inlet and outlet of the indoor and outdoor units are not blocked.
3 Check that the ground wire is connected correctly.
4 Refer to the “PREPARATION BEFORE OPERATION”, and follow the instructions. Page 4
WHEN THE AIR CONDITIONER IS NOT
GOING TO BE USED FOR A LONG TIME
(WR18/WR24)
8/20 in.
(200/500 mm) or more
Guaranteed operating range Indoor Outdoor
Cooling Upper limit
90°F (32.2°C) DB 115°F (46.1°C) DB
73°F (22.8°C) WB —
Lower limit
67°F (19.4°C) DB 32°F (0°C) DB
57°F (13.9°C) WB —
Heating Upper limit
80°F (26.7°C) DB 75°F (23.9°C) DB
— 65°F (18.3°C) WB
Lower limit
70°F (21.1°C) DB 5°F (-15°C) DB
— 4°F (-15.6°C) WB
Note:
1. The guaranteed operating range value is for 1:1 System Application.
2. If the outdoor temperature is below the lower limit of guaranteed operating range, the outdoor unit may stop operation until the outdoor temperature exceeds the lower limit.
DB : Dry Bulb WB : Wet Bulb
JG79Y503H02_01En.indd 9 2019/03/18 16:55:29
Sp-1
• Puesto que este producto tiene piezas rotatorias y piezas que pueden pro-vocar descargas eléctricas, lea atentamente las “Medidas de seguridad” antes de usarlo.
• Tome las precauciones aconsejadas en este manual, ya que son impor-tantes para una utilización segura del producto.
• Después de leer este manual, guárdelo a mano junto con el manual de instalación para poder recurrir a él con facilidad.
• Asegúrese de recibir la garantía de su distribuidor y comprobar que contie-ne la fecha de compra, el nombre del establecimiento, etc. correctos.
Indicaciones y sus signifi cados
ATENCIÓN: Una manipulación incorrecta podría conllevar con toda probabilidad un peligro grave, por ejemplo, de muerte o de heridas graves.
CUIDADO: Una manipulación incorrecta podría conllevar, según las condiciones, un peligro grave.
Símbolos utilizados en este manual y su signifi cado
: Asegúrese de no hacerlo.
: Siga las instrucciones estrictamente.
: No introduzca nunca los dedos ni objetos, etc.
: No se suba a la unidad interior/exterior ni ponga nada encima.
: Peligro de descarga eléctrica. Tenga cuidado.
: Asegúrese de desconectar el enchufe de alimentación de la toma de corriente.
: Asegúrese de desconectar la corriente.
MEDIDAS DE SEGURIDAD
ÍNDICE
ATENCIÓN
No conecte el cable de alimentación a un punto intermedio;
utilice una alargadera o conecte varios dispositivos a una sola toma de CA.
• Podría causar sobrecalentamiento, fuego o descarga eléctrica.
Asegúrese que el enchufe no tiene polvo e insértelo de forma segura en la toma de corriente.
• Si el enchufe está sucio puede provocar fuego o una des-carga eléctrica.
No enrolle ni cambie ni tire del cable de alimentación, y no aplique calor ni coloque objetos pesados sobre el mismo.
• Podría causar fuego o una descarga eléctrica.
No accione el disyuntor OFF/ON ni desconecte/conecte el enchufe de alimentación durante el funcionamiento.
• Podría generar chispas y originar un fuego.
• Una vez que la se apaga la unidad interior con el controlador remoto, asegúrese de que coloca el disyuntor en OFF o que desconecta el enchufe de alimentación.
Evite la exposición directa de la piel al aire frío durante un periodo de tiempo prolongado.
• Puede ser perjudicial para la salud.
El usuario no debe instalar, cambiar de sitio, desmontar, alterar ni reparar la unidad.
• Si no se maneja correctamente, el acondicionador de aire puede causar fuego, descarga eléctrica, lesiones, escape de agua, etc. Consulte con su distribuidor.
• Si el cable de alimentación está dañado, deberá ser susti-tuido por el fabricante o su agente de mantenimiento para evitar cualquier riesgo.
Al instalar, reubicar o reparar la unidad, asegúrese de que en el circuito de refrigeración no entra ninguna otra sustan-cia que no sea el refrigerante especifi cado (R410A).
• La presencia de cualquier otra sustancia extraña, como aire por ejemplo, puede provocar una elevación anómala de la presión, una explosión o daños corporales.
• El uso de un refrigerante distinto al especifi cado por el sis-tema ocasionará fallos mecánicos, malfuncionamiento del sistema o averías en la unidad. En el peor de los casos, esto podría llegar a ser un serio impedimento para garantizar el uso seguro del producto.
Este aparato no debe ser utilizado por personas (incluidos niños) que presenten una discapacidad física, sensorial o mental así como aquellos que dispongan de la experiencia o el conocimiento, a menos que lo hagan bajo la super-visión o instrucción relativa al uso del aparato por una persona responsable de su seguridad.
Se debe supervisar a los niños para garantizar que no jueguen con el aparato.
No introduzca los dedos, palos, etc. en las entradas/sa-lidas de aire.
• Podría causar daños, puesto que el ventilador del interior gira a alta velocidad durante el funcionamiento.
En caso de que se produzca una condición anómala (como olor a quemado), pare el aparato y desconecte el enchufe de alimentación o coloque el disyuntor en OFF.
• Si se prolonga el funcionamiento en la condición anómala puede producirse un fallo, fuego o una descarga eléctrica.
En tal caso, consulte a su distribuidor.
Cuando el acondicionador de aire no enfría o no calienta, es posible que haya una fuga del refrigerante. En tal caso, consulte a su distribuidor. Si una reparación exige la recar-ga de la unidad con refrigerante, solicite más información al técnico de servicio.
• El refrigerante que se usa en el acondicionador de aire es seguro. Normalmente no tiene fugas. Ahora bien, si hay fuga de refrigerante y éste entra en contacto con una fuente de calor como un calentador de ventilador, un calentador de parafi na o un horno de cocina, generará gases perjudicia-les.
El usuario nunca debería intentar lavar el interior de la unidad interior. Si el interior de la unidad requiere limpieza, póngase en contacto con el distribuidor.
• Un detergente inadecuado puede provocar daños a los ma-teriales plásticos del interior de la unidad, lo que puede tener como consecuencia pérdidas de agua. Si el detergente entra en contacto con las partes eléctricas del motor, provocará mal funcionamiento, humo o fuego.
Este equipo se ha diseñado para ser utilizado por usua-rios expertos o cualifi cados en comercios, industrias ligeras y granjas, o para su uso comercial por personas no expertas.
� MEDIDAS DE SEGURIDAD 1
� NOMBRE DE LAS PARTES 3
� PREPARACIÓN ANTES DE LA PUESTA EN MARCHA 4
� SELECCIÓN DE MODOS DE FUNCIONAMIENTO 5
� VELOCIDAD DEL VENTILADOR Y AJUSTE DE LA DIRECCIÓN DEL AIRE 6
� FUNCIÓN DE REFRIGERACIÓN ECONÓMICA (ECONO COOL) 6
� FUNCIONAMIENTO DEL TEMPORIZADOR (ACTIVACIÓN/DESACTIVACIÓN DEL TEMPORIZADOR) 6
� LIMPIEZA 7
� SI CREE QUE HA OCURRIDO ALGÚN PROBLEMA 8
� CUANDO EL ACONDICIONADOR DE AIRE NO SE VAYA A UTILIZAR DURANTE MUCHO TIEMPO 9
� LUGAR DE INSTALACIÓN Y TRABAJO ELÉCTRICO 9
� ESPECIFICACIONES 9
JG79Y503H02_02Es.indd 1 2019/03/18 16:56:14
Sp-2
● MANUAL DE INSTRUCCIONES ●
MEDIDAS DE SEGURIDAD
CUIDADO
No toque la entrada de aire ni la aleta de aluminio de la unidad interior/exterior.
• Podría hacerse daño.
No eche insecticidas ni pulverizadores infl amables sobre la unidad.
• Podrían provocar incendios o deformaciones de la unidad.
Evite la exposición directa de animales domésticos o plantas al fl ujo de aire.
• Puede causar daños a los animales y las plantas.
No coloque otros electrodomésticos o muebles debajo de la unidad interior/exterior.
• Podría gotear agua desde la unidad, que podría causar daños o hacer que funcionara mal.
No instale la unidad en un soporte roto.
• La unidad podría caer y causar daños.
Mientras limpia o hace funcionar la unidad, no tenga los pies en una superfi cie inestable.
• Si se cayera, podría hacerse daño.
No tire del cable de alimentación.
• Podría hacer que se rompa parte del núcleo del cable, lo que puede causar sobrecalentamiento o fuego.
No cargue ni desarme las pilas y no las arroje al fuego.
• Podría provocar fugas en las pilas, o causar fuego o una explosión.
La unidad no debe estar en funcionamiento más de 4 horas en condiciones de humedad elevada (80% de humedad relativa o superior) y/o con la puerta de entrada o las ven-tanas abiertas.
• Esto podría causar un descenso en la condensación de agua en el acondicionador de aire que podría humedecer o dañar el mobiliario.
• La condensación de agua en el acondicionador de aire podría contribuir a la formación de hongos, como el moho.
No use la unidad para fi nes especiales, como para alma-cenar alimentos, criar animales, cultivar plantas o guardar dispositivos de precisión u objetos de arte.
• Podría deteriorar la calidad o causar daños a los animales y plantas.
Evite la exposición directa de aparatos de combustión al fl ujo de aire.
• Podría interrumpir la combustión.
Para evitar una ingestión accidental, no coloque las pilas en su boca bajo ningún concepto.
• La ingestión de las pilas puede causar asfi xia y/o envenena-miento.
Antes de limpiar la unidad, apáguela y desconecte el cable de alimentación o coloque el disyuntor en OFF.
• Podría causar daños, puesto que el ventilador del interior gira a alta velocidad durante el funcionamiento.
Si la unidad va a dejar de usarse un tiempo prolongado, desconecte el cable de alimentación o coloque el disyuntor en OFF.
• La unidad puede acumular polvo y provocar sobrecalenta-miento o fuego.
Sustituya las pilas del controlador remoto por otras nuevas de la misma clase.
• La utilización de una pila usada junto con una nueva puede causar sobrecalentamiento, provocar una fuga o producir una explosión.
Si el líquido de la pila entra en contacto con la piel o la ropa, lávelas a fondo con agua limpia.
• Si el líquido de la pila entra en contacto con los ojos, lávelos a fondo con agua limpia y acuda a un médico de inmediato.
Asegúrese de que la zona está bien ventilada cuando la unidad esté en funcionamiento junto con un aparato de combustión.
• Una ventilación inadecuada puede originar falta de oxígeno.
Coloque el disyuntor en OFF si oye truenos y hay posibilidad de que caigan rayos.
• La unidad puede resultar dañada si cae algún rayo.
Tras varias estaciones con el acondicionador de aire en funcionamiento, efectúe una inspección y el mantenimiento además de la limpieza habitual.
• Si hay polvo o suciedad en la unidad se puede producir un olor desagradable, contribuir al crecimiento de hongos, como el moho, o bien bloquear el conducto de drenaje, lo que hace que gotee agua de la unidad interior. Consulte con su distribuidor sobre la inspección y el mantenimiento, puesto que exigen conocimientos y capacidades especializadas.
ATENCIÓN
Pida a su distribuidor que instale el aire acondicionado.
• No debe instalarlo el usuario, puesto que requiere conocimien-tos y capacidades especializadas. Si no se instala correcta-mente, puede provocar fugas, fuego o descargas eléctricas.
Dedique una toma de alimentación en exclusiva al acondi-cionador de aire.
• Si no se utiliza una toma de alimentación en exclusiva, pueden producirse sobrecalentamiento o fuego.
No instale la unidad donde pueda haber fugas de gas infl amable.
• Si hay una fuga de gas y éste se acumula cerca de la unidad, podría producirse una explosión.
Conecte la unidad a una toma a tierra.
• No conecte el cable de tierra a una tubería de gas, tubería de agua, pararrayos o cable de tierra de un teléfono. Si no, podría producirse una descarga eléctrica.
CUIDADO
Instale un disyuntor de pérdidas de tierra en función del lugar de instalación del aire acondicionado (por ejemplo, áreas muy húmedas).
• Si no instala el disyuntor de pérdidas de tierra, podrían pro-ducirse descargas eléctricas.
Asegúrese de que se drena correctamente el agua de drenaje.
• Si el conducto de drenaje no es correcto, el agua podría caer desde la unidad interior/exterior, causando humedad y daños en el mobiliario.
Si se produce una condición anómala Pare de inmediato el acondicionador de aire y consulte a su distribuidor.
No utilice los mandos con las manos mojadas.
• Podría producirse una descarga eléctrica.
No limpie el acondicionador de aire con agua ni coloque sobre él un objeto que contenga agua, como un fl orero.
• Podría causar fuego o una descarga eléctrica.
No se suba a la unidad exterior ni coloque ningún objeto encima.
• Si se cayera usted o el objeto, podría haber daños.
Para la instalación
IMPORTANTE
Los fi ltros sucios pueden provocar condensación en el acondiciona-dor de aire que contribuye a la formación de…