B01 Attachment J03-c Drawings for Arapahoe.pdf

PDF 3 MB Posted

Attached to
Billings Area (Poplar, MT / Pryor, MT / Arapahoe, WY) Generator Project
Solicitation number
75H70125R00039
Issued by

About this file

This document is a set of final construction drawings for an emergency generator project at the Arapahoe Health Center in Arapahoe, Wyoming. The drawings, prepared by Short Elliott Hendrickson, Inc. (SEH) for the Indian Health Service (IHS), detail the electrical, mechanical, and gas piping systems for installing a 150kW Cummins natural gas generator. The drawings include comprehensive technical specifications such as a site plan, electrical one-line diagram, grounding details, generator concrete slab design, and gas piping schematics. Key technical details include a 208V, 3-phase generator with a generator docking station, new electrical panels, gas meter modifications, and specific installation requirements for the generator enclosure and associated infrastructure.

The drawings specify precise technical requirements for the generator installation, including a new equipment pad, grounding system, gas piping connections, and electrical system integration. The project involves connecting the generator to the existing electrical system through an automatic transfer switch (ATS), installing a new panel 'LS', and routing gas and electrical connections with specific conduit and conductor specifications. The drawings provide detailed notes on installation methods, code compliance, coordination requirements, and technical specifications for electrical, mechanical, and gas systems, ensuring a comprehensive and compliant emergency generator installation for the Arapahoe Health Center.

View the file

Other files

File Type Posted
B05 Amdnment A0005-75H70125R00039 Billings Area Generator project.pdf PDF
B05 Amdnment A0004-75H70125R00039 Billings Area Generator project.pdf PDF
B05 Amdnment A0003-75H70125R00039 Billings Area Generator project.pdf PDF
B01 RFP 75H70125R00039 Revised by A0003.pdf PDF
B01 RFP 75H70125R00039 Revised by A0002.pdf PDF
B05 Amdnment A0002-75H70125R00039 Billings Area Generator project.pdf PDF
B05 Amdnment A0001-75H70125R00039 Billings Area Generator project.pdf PDF
B01 Attachment J06 IHS IEE Representation Form.pdf PDF
B01 Attachment J02-c Specification Vol I for Pryor.pdf PDF
B01 Attachment J02-a Specification Vol I for Verne E Gibbs.pdf PDF
B01 Attachment J04 Company Specialized Experience Form Construction.pdf PDF
B01 Attachment J02-f Specification Vol II for Arapahoe.pdf PDF
B01 Attachment J01-c Wage Determination WY20250009 Fremont County 2025 03 14 .pdf PDF
B01 Attachment J01-b Wage Determination MT20250056 Big Horn County 2025 03 14.pdf PDF
B01 Attachment J05 Past Performance Questionnaire.docx DOCX document
B01 RFP 75H70125R00039.pdf PDF
B01 Attachment J03-a Drawings for Verne E Gibbs.pdf PDF
B01 Attachment J07 Self Performed Calculation Sheet.docx DOCX document
B01 Attachment J02-d Specification Vol II for Pryor.pdf PDF
B01 Attachment J01-a Wage Determination MT20250050 Roosevelt County 2025 03 14.pdf PDF
B01 Attachment J03-b Drawings for Pryor.pdf PDF
B01 Attachment J02-e Specification Vol I for Arapahoe.pdf PDF
B01 Attachment J02-b Specification Vol II for Verne E Gibbs.pdf PDF
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VICINITY MAP DRAWING INDEX PROJECT DIRECTORY

LOCATION MAP

1/

/2

:5 1:

A

M

INDIAN HEALTH SERVICE

ARAPAHOE HEALTH CENTER

EMERGENCY GENERATOR

14 Great Plains Rd, Arapahoe, WY 82510

FINAL CONSTRUCTION DRAWINGS

R

Building a Better World for All of Us

R

SEH Project

Checked By

Drawn By

Project Status Issue Date

This drawing is an instrument of service and shall remain the property of SEH, Inc. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of

SEH, Inc.

Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH, Inc.

C O

P Y

R

IG

H T

Architect

Structural Engineer

Mechanical Engineer

Electrical Engineer

Owner

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Indian Health Service (IHS) 1301 Young St., Ste. 840 Dallas, TX 75202 214.767.5255

1/

/2

:5 1:

A

M

COVER SHEET

G

A R

A P

A H

O E

H E

A L

T H

C E

N T

E R

E M

E R

G E

N C

Y G

E N

E R

A T

O R

G re at

P la in s

R d, A ra pa ho e, W

Y

169805

J.SOPATA

M.MASSA

IN

D

IA

N

H E

A L

T H

S E

R V

IC

E

FINAL CONSTRUCTION

DRAWINGS

01.12.2024

OWNER

PROJECT

LOCATION

PROJECT

LOCATION

INDIAN HEALTH SERVICE (IHS)

DEPARTMENT OF HEALTH AND HUMAN SERVICES

DIVISION OF ENGINEERING SERVICES

1301 YOUNG STREET, STE. 840

DALLAS, TX 75202

GENERAL

G 000 COVER SHEET

ARCHITECT / MEP

SHORT ELLIOTT HENDIRCKSON, INC (SEH)

2000 SOUTH COLORADO BLVD., STE. 6000

DENVER, CO 80222

MAIN: 800.490.4966

CONTACT: MATTHEW MASSA, PROJECT MANAGER

MMASSA@SEHINC.COM

ELECTRICAL

E001 ELECTRICAL TITLE SHEET

E201 ELECTRICAL PLAN

E401 ELECTRICAL ONE-LINE DIAGRAM

E601 ELECTRICAL DETAILS

MECHANICAL / PLUMBING

P001 MECHANICAL SYMBOLS AND ABBREVIATIONS

P111 PLUMBING PLANS - GAS

Revision Issue

Rev. # Description Date

J03-c Drawings for Arapahoe

1P 1 POLE (2P, 3P, 4P, ETC.)

A AMPERE

AC ABOVE COUNTER OR AIR

CONDITIONER

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPENER

AF AMP FRAME

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT

INTERRUPTER

AHU AIR HANDLING UNIT

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

AMPL AMPLIFIER

ANNUN ANNUNCIATOR

APPROX APPROXIMATELY

AQ-STAT AQUASTAT

ARCH ARCHITECT, ARCHITECTURAL

AS AMP SWITCH

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BATT BATTERY

BD BOARD

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

C CONDUIT

CAB CABINET

CAT CATALOG

CATV CABLE TELEVISION

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CLG CEILING

COMB COMBINATION

CMPR COMPRESSOR

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

CONV CONVECTOR

CP CIRCULATING PUMP

CRT CATHODE-RAY TUBE

CT CURRENT TRANSFORMER

CTR CENTER

CU COPPER

DCP DOMESTIC WATER CIRCULATING PUMP

DEPT DEPARTMENT

DET DETAIL

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DPR DAMPER

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EP ELECTRIC PNEUMATIC

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXH EXHAUST

EXP EXPLOSION PROOF

FA FIRE ALARM

FABP FIRE ALARM BOOSTER POWER

SUPPLY PANEL

FACP FIRE ALARM CONTROL PANEL

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FU FUSE

FUDS FUSED SAFETY DISCONNECT SWITCH

GA GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTOR

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP BD GYPSUM BOARD

HOA HANDS-OFF-AUTOMATIC SWITCH

HORIZ HORIZONTAL

HP HORSEPOWER

HPF HIGH POWER FACTOR

HT HEIGHT

HTG HEATING

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

HWP HYDRONIC WATER PUMP

IC INTERRUPTING CAPACITY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

I/W INTERLOCK WITH

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LOC LOCATE OR LOCATION

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MAX MAXIMUM

MAG.S MAGNETIC STARTER

M/C MOMENTARY CONTACT

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDC MAIN DISTRIBUTION CENTER

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MMS MANUAL MOTOR STARTER

MOA MULTIOUTLET ASSEMBLY

MSP MOTOR STARTER PANELBOARD

MSBD MAIN SWITCHBOARD

MT MOUNT

MT.C EMPTY CONDUIT

MTS MANUAL TRANSFER SWITCH

MTR MOTOR, MOTORIZED

N.C. NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT

SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

N.O. NORMALLY OPEN

NPF NORMAL POWER FACTOR

NTS NOT TO SCALE

OH OVERHEAD

OL OVERLOADS

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PE PNEUMATIC ELECTRIC

PED PEDESTAL

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

PP POWER POLE

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QUAN QUANTITY

RCPT RECEPTACLE

REQD REQUIRED

RM ROOM

RSC RIGID STEEL CONDUIT

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SHT SHEET

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

SPKR SPEAKER

SP SPARE

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

S/S STOP/START PUSHBUTTONS

STA STATION

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

ELECTRICAL ABBREVIATIONS LIST

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TL TWIST LOCK

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TTC TELEPHONE TERMINAL CABINET

TV TELEVISION

TVTC TELEVISION TERMINAL CABINET

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UT UNDERGROUND TELEPHONE

UTIL UTILITY

UV UNIT VENTILATOR OR

ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VDT VIDEO DISPLAY TERMINAL

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT

W/ WITH

WG WIRE GUARD

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

∠ ANGLE

@ AT

▲ DELTA

' FEET

" INCHES

# NUMBER

Ø PHASE

C CENTER LINE

P PLATE

A2

E d

ELECTRICAL SYMBOL NOTES

b

FIXTURE TYPE

SWITCH DESIGNATION

CIRCUIT NUMBER

FIXTURE TYPE

CHEVRON DIRECTION

SHADE = EXIT FACE

CIRCUIT NUMBER

CIRCUIT NUMBER

SWITCH IDENTIFICATION

SYMBOLSYMBOL SYMBOL

ELECTRICAL SYMBOL LEGEND

J

2 POLE SINGLE THROW SW.

SINGLE POLE SW.

DIMMER SWITCH

MOMENTARY CONTACT SWITCH

OCCUPANCY SENSOR SWITCH

SINGLE RECEPT.

TIME DELAY SWITCH

SPLIT DUPLEX RECEPT.

QUADPLEX RECEPT.

DUPLEX RECEPT.

RECEPT ON EMERGENCY CKT (DUPLEX SHOWN)

ISOLATED GROUND RECEPT (DUPLEX SHOWN)

RECEPT ON DROP CORD (DUPLEX SHOWN)

RECEPT ON CORD REEL (DUPLEX SHOWN)

FLOOR RECEPT. (DUPLEX SHOWN)

KEYED SW.

SW. W/PILOT

3-WAY SW.

4-WAY SW.

DESCRIPTION

WALL MOUNTED FLOODLIGHT (TYPE DENOTED)

POLE MOUNTED LIGHT (TYPE DENOTED)

RECESSED LIGHT (TYPE DENOTED)

SURFACE LIGHT (TYPE DENOTED)

EXIT SIGN (TYPE DENOTED)

SUSPENDED OR PENDANT LIGHT (TYPE DENOTED)

TRACK AND TRACK LIGHT (TYPES DENOTED)

SURFACE LINEAR LIGHT (TYPE DENOTED)

STRIP LIGHT (TYPE DENOTED)

EMERGENCY BATTERY LIGHT (TYPE DENOTED)

RECESSED LINEAR LIGHT (TYPE DENOTED)

POLE MOUNTED FLOODLIGHT (TYPE DENOTED)

QUADRAPLEX PLEX RECEPTACLE

ON EMERGENCY CIRCUIT

LIGHT FIXTURE ON EMERGENCY CIRCUIT

CIRCUIT BREAKER PANEL

DASHED SYMBOL INDICATES REMOVED

HALFTONE SYMBOL INDICATES EXISTING

LIGHT LEVEL SENSOR - TYPE DENOTED

PHOTOCELL

SAFETY DISC. SW. (FUSED)

SAFETY DISC. SW. (NON-FUSED)

COMB. MOTOR STARTER (FUSED)

POWER OR DISTRIBUTION PANEL

MOTOR (SEE SCHEDULE)

TRANSFORMER (TYPE DENOTED)

STATIC GROUND RECEPTACLE (TYPE DENOTED)

SPECIAL RECEPT. OR CONN. (SEE SCHEDULE)

JUNCTION BOX (FLOOR MOUNTED)

GROUND ROD (PLAN VIEW)

LIGHTNING PROTECTION AIR TERMINAL

CLOCK (TYPE DENOTED)

POWER POLE (OPEN OFFICE STYLE)

MULTIOUTLET ASSEMBLY (TYPE DENOTED)

DESCRIPTION

UTILITY SERVICE POWER POLE (SITE)

OCCUPANCY SENSOR - TYPE DENOTED

COMBINATION TELEPHONE/DATA OUTLET

INFORMATION OUTLET (TYPE DENOTED)

TELEPHONE OUTLET (TYPE DENOTED)

DESCRIPTION

WIRELESS ACCESS POINT

CARD READER

SECURITY

SYSTEMS

FIRE ALARM

JUNCTION BOX (WALL MOUNTED)

CR

C

POWERLIGHTING

SYMBOL

TELEPHONE OUTLET (TYPE DENOTED)

DESCRIPTION

SYSTEMS

SYMBOL DESCRIPTIONSYMBOL DESCRIPTION

INSTRUMENTATION

MANUAL MOTOR STARTER SWITCH

WEATHER PROOF SWITCH

TIMER SWITCH

D P

K

OS

M

W P

MC

T

TD

OS

LS

P

WAP

DOOR CONTACTDC

MOTION DETECTORMD

CCTV

CCTV-PTZ

* = * FACP (FIRE ALARM CONTROL PANEL)

FAA (FIRE ALARM ANNUNCIATOR)

FAGM (FIRE ALARM GRAPHIC MAP)

PACP (PRE-ACTION CONTROL PANEL)

* =* F (MANUAL PULL STATION)

FD (FIRE DAMPER)

F/S (FIRE/SMOKE DAMPER)

SD (SMOKE DAMPER)

M (MAGNETIC DOOR HOLDER)

RT (REMOTE TEST STATION & PILOT LIGHT)

V (VISUAL)

I OR Z (INDIVIDUAL ADDRESSABLE MODULE)

WHERE X:

C (CONTROL TYPE)

M (MONITOR TYPE)

S (SUPERVISORY)

* =* F (FLOW SWITCH)

T (TAMPER SWITCH)

P/V (POST INDICATOR VALVE)

* =* A (AUDIBLE)

H (HORN)

AV (AUDIBLE & VISUAL)

WHERE X:

X (CANDELA RATING)

* = D (DUCT DETECTOR)

H (HEAT)

S (SMOKE)

F (FLAME DETECTOR)

IR (INFRA-RED)

MF (MULTI SPECTRUM FLAME)

S (SMOKE DETECTOR)

I (IONIZATION)

P (PHOTOELECTRIC)

H (HEAT DETECTOR)

R (RATE OF RISE)

F (FIXED TEMPERATURE)

WIRING AND GROUNDING

XX =XX PS (PRESSURE SWITCH)

SV (SOLENOID VALVE)

LS (LIMIT SWITCH)

L (FLOAT SWITCH)

FS (FLOW SWITCH)

FD (FLOOR FLOOD FLOAT SWITCH)

T (THERMOSTAT)

MV (MOTORIZED VALVE)

XX =XX PT (PRESSURE TRANSMITTER)

LT (LEVEL TRANSMITTER)

LE (LEVEL ELEMENT)

FT (FLOW TRANSMITTER)

FM (FLOW METER ELEMENT)

TT (TEMPERATURE TRANSMITTER)

AT (ANALYZER)

MV (MODULATING MOTORIZED VALVE)

AE (ANALYZER ELEMENT)

CONDUIT EXPOSED

CONDUIT CONCEALED

CONDUIT CAPPED

CONDUIT CONTINUED

GROUND CONDUCTOR

OH OVERHEAD ELECTRICAL LINE

EE DIRECT BURIED CONDUIT

XX-1

P

P

J

J

J

SYSTEM

DESIGNATION

EQUIPMENT

DESIGNATION

EMERGENCY

UNINTERRUPTIBLE POWER SOURCE

NORMAL

U

LPE-102

E

(BLANK)

PANEL NUMBER

FLOOR OF STRUCTURE

3Ø4W. 208Y/120V

3Ø4W, 480Y/277V

EQUIPMENT DESIGNATION

SYSTEMS DESIGNATION

LP

PP

CODE

CODE

P3Ø3W. 480

L1Ø3W. 240/120V

PANELBOARD IDENTIFICATION

R

Building a Better World for All of Us

R

SEH Project

Checked By

Drawn By

Project Status Issue Date

This drawing is an instrument of service and shall remain the property of SEH, Inc. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH, Inc.

Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH, Inc.

C O

P Y

R

IG

H T

Architect

Structural Engineer

Mechanical Engineer

Electrical Engineer

Owner

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Indian Health Service (IHS) 1301 Young St., Ste. 840 Dallas, TX 75202 214.767.5255

1/

/2

:2 1:

A

M

ELECTRICAL TITLE SHEET

E001

A R

A P

A H

O E

H E

A L

T H

C E

N T

E R

E M

E R

G E

N C

Y G

E N

E R

A T

O R

G re at

P la in s

R d, A ra pa ho e, W

Y

169805

J.SOPATA

J.SEILER

IN

D

IA

N

H E

A L

T H

S E

R V

IC

E

100% CONSTRUCTION

DRAWINGS

1.11.2024

Revision Issue

Rev. # Description Date

1/11/2024

FINAL CONSTRUCTION

DRAWINGS

01.12.2024

J

E P

O

KEYNOTES

1. APPROXIMATE LOCATION OF ELECTRICAL ROOM AND 'MDP'.

2. 120/208V 3 PHASE 150KW NATURAL GAS GENERATOR, CUMMINS MODEL # C150N6 OR

APPROVED EQUIVALENT, TO BE HOUSED WITHIN A WALK-IN ENCLOSURE. COORDINATE

GAS SUPPLY WITH NATURAL GAS UTILITY.

3. GENERATOR DOCKING STATION, TRYSTAR SBDS-6 OR APPROVED EQUIVALENT. WALL

OR PAD MOUNT OUTSIDE OF GENSET ENCLOSURE FOR EASE OF ACCESS.

4. EXISTING SERVICE ENTRY DISCONNECT.

5. LOCATE ATS 'OS' ON NEW EQUIPMENT PAD.

6. GENERATOR ANNUNCIATOR PANEL TO BE LOCATED IN A READILY OBSERVED

LOCATION AT A REGULAR WORK STATION.

7. GROUND ROD.

8. #2/0 AWG CU GROUND RING BURIED NO LESS THAN 30" BELOW GROUND. CONNECT TO

BUILDING MAIN GROUNDING ELECTRODE SYSTEM.

9. JUNCTION BOX REQUIRED FOR CONTROLS CABLING FROM GENSET TO ATS AND

REMOTE GENERATOR ANNUNCIATOR PANEL. CONTRACTOR TO COORDINATE EXACT

MOUNTING LOCATION.

10. REMOTE WEATHERPROOF EMERGENCY STOP GENERATOR PUSH BUTTON.

CONTRACTOR TO COORDINATE EXACT MOUNTING LOCATION.

11. 208V SINGLE PHASE LOAD CENTER 'GP'. CONTRACTOR SHALL PROVIDE A 60A SINGLE

PHASE CIRCUIT TO PANEL GP FROM AN EXISTING PANEL WITH AVAILABLE SPACE

FROM INSIDE THE MAIN BUILDING. USE 3- #4 CU & 1- #8 CU GND IN 1 1/4" CONDUIT. ALL

GENERATOR, ENCLOSURE, & DOCKING STATION ACCESSORY LOADS TO BE

CONNECTED TO PANEL GP.

12. LOCATE ATS 'EM' ON NEW EQUIPMENT PAD.

13. LOCATE NEW PANEL 'LS' IN ELECTRIC ROOM. PROVIDE MLO 42 CIRCUIT PANEL WITH 10

SPARE 20A SINGLE POLE BREAKERS AND 32 PREPARED SPACES. CONTRACTOR SHALL

FIELD VERIFY APPROPRIATE PANEL MOUNTING LOCATION. IF NO SPACE IS AVAILABLE

IN ELECTRIC ROOM MOUNTING LOCATION SHALL BE COORDINATED BETWEEN

CONTRACTOR, OWNER, AND ENGINEER.

14. FUSED SWITCH FOR ATS 'EM' 100A/100A/3P/3R.

15. FUSED SWITCH FOR ATS 'OS' 450A/450A/3P/3R.

16. WEATHERPROOF WIREWAY.

17. EXTERIOR EQUIPMENT PAD.

X

SITE POWER GENERAL NOTES

A. ALL WORK SHALL COMPLY WITH THE 2020 NATIONAL ELECTRIC CODE, NATIONAL,

STATE, AND LOCAL CODES.

B. ALL EXISTING CONDITIONS MAY NOT BE DETAILED ON THE DRAWINGS. CONTRACTOR

SHALL FIELD VERIFY EXISTING EQUIPMENT AND CIRCUITRY AT THE SITE AND MAKE ALL

NECESSARY CHANGES REQUIRED BASED ON EXISTING CONDITIONS FOR PROPER

INSTALLATION OF WORK.

C. COORDINATE ALL ELECTRICAL SERVICE INTERRUPTION AND REQUIREMENTS WITH THE

LOCAL ELECTRICAL UTILITY & FACILITY MANAGEMENT.

D. CONTRACTOR MUST LOCATE ALL UNDERGROUND UTILITIES PRIOR TO ANY

EXCAVATION WORK.

E. COORDINATE ALL EQUIPMENT LOCATIONS AND REQUIREMENTS PRIOR TO ROUGH IN.

F. MAKE ALL FINAL ELECTRICAL CONNECTIONS TO EQUIPMENT REQUIRING ELECTRICAL

CONNECTIONS. THIS SHALL INCLUDE BUT NOT BE LIMITED TO ALL MECHANICAL

EQUIPMENT INCLUDED IN THIS PROJECT.

G. ALL EXTERIOR CIRCUITS SHALL BE #10AWG CONDUCTORS, AT A MINIMUM, FOR THE

ENTIRE LENGTH OF THE CIRCUIT.

APPROXIMATE LOCATION OF

ELECTRICAL ROOM AND 'MDP'

7 7

R

Building a Better World for All of Us

R

SEH Project

Checked By

Drawn By

Project Status Issue Date

This drawing is an instrument of service and shall remain the property of SEH, Inc. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH, Inc.

Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH, Inc.

C O

P Y

R

IG

H T

Architect

Structural Engineer

Mechanical Engineer

Electrical Engineer

Owner

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Indian Health Service (IHS) 1301 Young St., Ste. 840 Dallas, TX 75202 214.767.5255

1/

/2

:2 1:

A

M

ELECTRICAL PLAN

E201

A R

A P

A H

O E

H E

A L

T H

C E

N T

E R

E M

E R

G E

N C

Y G

E N

E R

A T

O R

G re at

P la in s

R d, A ra pa ho e, W

Y

169805

J.SOPATA

J.SEILER

IN

D

IA

N

H E

A L

T H

S E

R V

IC

E

100% CONSTRUCTION

DRAWINGS

1.11.2024

1/16" = 1'-0"

ELECTRICAL SITE PLAN

APPROXIMATE ELEVATION OF SITE: 5094'

LOCAL ELECTRIC UTILITY: HIGH PLAINS POWER

NORTH

Revision Issue

Rev. # Description Date

1/11/2024

FINAL CONSTRUCTION

DRAWINGS

01.12.2024

G

EXISTING SECONDARY

PANEL

'D'

225A

120/

208V

3Ø,4W

EXISTING UTILITY

TRANSFORMER

500A/3P

ATS 'OS' 800A,

208V, 3PHASE,

4-POLE, 65KAIC

EXISTING

SERVICE

DISCONNECT

PANEL 'MDP', 800A, 120/208V, 3Ø, 4W

225A/3P 225A/3P 225A/3P 225A/3P

PANEL

'F'

225A

120/

208V

3Ø,4W

PANEL

'G'

225A

120/

208V

3Ø,4W

PANEL

'H'

225A

120/

208V

3Ø,4W

PANEL

'I'

225A

120/

208V

3Ø,4W

PANEL

'C'

225A

120/

208V

3Ø,4W

PANEL

'B'

225A

120/

208V

3Ø,4W

PANEL

'A'

225A

120/

208V

3Ø,4W

JJJ

350A/3P 150A/3P

PANEL

'J'

225A

120/

208V

3Ø,4W

150A/3P

PANEL

'K'

225A

120/

208V

3Ø,4W

110A/3P

112.5KVA

208:

480Y/277

X-RAY

MACHINE

208:240

BUCK/BOOST

TRANSFORMER

CIRCUIT

SOURCE

UNKOWN

X-RAY

TABLE

450A/3P

GENERATOR DOCKING STATION

208V, 600A, 3Ø, 4W

GENERATOR

150KW, 120/208V, 3Ø, 4W

#1/0AWG

FEEDER SCHEDULE

3 RUNS (4 #300 KCMIL CU & 1 #1/0 AWG CU GND) 2 1/2"C

2 RUNS (4 #4/0 AWG CU & 1 #2 AWG CU GND) 2 1/2"C

30A/3P

SPD

NEW

1"C TO REMOTE ANNUNCIATOR1"C - 6 #14AWG, TO GENERATOR CONTROLLER

FEEDER FOR PANEL GP: 1 1/4"C - 3#4AWG, 1#8AWG TO NEAREST

EXISTING PANEL.PROVIDE 60A, 2-POLE BREAKER IN EXISTING PANEL.

100A/3P

NEW

ATS 'EM' 100A,

208V, 3Ø, 4-POLE

22KAIC

1"C - 6 #14AWG TO

GENERATOR

CONTROLLER

FROM

'MDP'

PANEL

'LS'

100A

120/

208V

3Ø,4W

22KAIC

100A/100A/ 3P/3R

1 RUN (4 #1 AWG CU & 1 #8 AWG CU GND) 1 1/2"C03

ATS 'EM'

WP

WIREWAY

450A/450A/ 3P/3R

EXISTING SECONDARY

PANEL

'D'

225A

120/

208V

3Ø,4W

EXISTING UTILITY

TRANSFORMER

500A/3P

EXISTING

SERVICE

DISCONNECT

PANEL 'MDP', 800A, 120/208V, 3Ø, 4W

225A/3P 225A/3P 225A/3P 225A/3P

PANEL

'F'

225A

120/

208V

3Ø,4W

PANEL

'G'

225A

120/

208V

3Ø,4W

PANEL

'H'

225A

120/

208V

3Ø,4W

PANEL

'I'

225A

120/

208V

3Ø,4W

PANEL

'C'

225A

120/

208V

3Ø,4W

PANEL

'B'

225A

120/

208V

3Ø,4W

PANEL

'A'

225A

120/

208V

3Ø,4W

JJJ

350A/3P 150A/3P

PANEL

'J'

225A

120/

208V

3Ø,4W

150A/3P

PANEL

'K'

225A

120/

208V

3Ø,4W

110A/3P

112.5KVA

208:

480Y/277

X-RAY

MACHINE

208:240

BUCK/BOOST

TRANSFORMER

CIRCUIT

SOURCE

UNKOWN

X-RAY

TABLE

KEYNOTES

1. DISCONNECT EXISTING SERVICE CONDUCTORS FROM SERVICE.

DISCONNECT AND EXTEND TO NEW ATS.

2. CONTRACTOR TO FIELD VERIFY MDP HAS SPACE FOR NEW 100A 3

POLE BREAKER FOR PANEL 'LS'. IF CONTRACTOR DETERMINES MDP

DOES NOT HAVE SPACE CONTRACTOR SHALL COORDINATE WITH

ENGINEER FOR ALTERNATE INSTALLATION.

3. EMERGENCY SYSTEMS OVERCURRENT PROTECTIVE DEVICES

(OCPDS), SHALL BE SELECTIVELY COORDINATED WITH ALL SUPPLY

SIDE AND LOAD SIDE OCPDS. SELECTION OF OCPDS SHALL BE

DOCUMENTED BY THE SUPPLIER OR CONTRACTOR PER 700.32 AND

SHALL BE SUBMITTED WITH THE SHOP DRAWINGS.

X

R

Building a Better World for All of Us

R

SEH Project

Checked By

Drawn By

Project Status Issue Date

This drawing is an instrument of service and shall remain the property of SEH, Inc. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH, Inc.

Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH, Inc.

C O

P Y

R

IG

H T

Architect

Structural Engineer

Mechanical Engineer

Electrical Engineer

Owner

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Indian Health Service (IHS) 1301 Young St., Ste. 840 Dallas, TX 75202 214.767.5255

1/

/2

:2 1:

A

M

ELECTRICAL ONE-LINE DIAGRAM

E401

A R

A P

A H

O E

H E

A L

T H

C E

N T

E R

E M

E R

G E

N C

Y G

E N

E R

A T

O R

G re at

P la in s

R d, A ra pa ho e, W

Y

169805

J.SOPATA

J.SEILER

IN

D

IA

N

H E

A L

T H

S E

R V

IC

E

100% CONSTRUCTION

DRAWINGS

1.11.2024

NOT TO SCALE

ONE LINE DIAGRAM - NEW

NOT TO SCALE

ONE LINE DIAGRAM - EXISTING

Revision Issue

Rev. # Description Date

1/11/2024

FINAL CONSTRUCTION

DRAWINGS

01.12.2024

ENGINE-

GENERATOR SET

NOTE: GROUNDING SYSTEM TO GO IN BEFORE COMMON SLAB

KEYNOTES:

1. BOND TO FRAME GROUNDING POINT

AND GENERATOR GROUND BUS.

2. SIZE GROUNDING CONDUCTORS PER

NEC.

3. GROUND ROD (TYP). EXOTHERMIC

WELD ALL CONNECTIONS OF

CONDUCTORS TO GROUND RODS.

4. TO SERVICE GROUND POINT. SIZE PER

NEC TABLE 250.66.

CHAMFER EDGES

CJ

NOTES

- PROVIDE SLAB ON GRADE CONTROL JOINT PER DETAIL.

- COORDINATE SLAB LOCATION AND ORIENTATION WITH CIVIL.

- REFER TO ELECTRICAL PLANS AND SPECIFICATIONS FOR ADD'L NOTES & DETAILS.

- CONTRACTOR SHALL VERIFY DIMENSIONS AND ALL OTHER REQUIREMENTS.

BLOCKOUT FOR CONDUIT

BANK - VERIFY SIZE

AND LOCATION

CONC. SLAB

CLASS 5

GRANULAR 100%

STANDARD PROCTOR

TOPSOIL

12" SLAB ON GRADE

w/#5 @ 12" TOP & BOT

PLAN DIMENSION AS REQ'D

FOR EQUIPMENT (COORDINATE W/APPROVED SHOP DRAWINGS)

P L A

N D

IM

E

N S

IO

N

A S

R E

Q 'D

F O

R E

Q U

IP

M

E N

T

C O

O R

D

IN

A T

E W

/A P

P R

O V

E D

S H

O P

D R

A W

IN

G

S

12" ALL AROUND

PERIMETER OF

GENERATOR HOUSING

V E

R

U .N

.O

#5 TOP AND BOTTOM

ADD'L

REINFORCEMENT AT

SLAB OPENING(S)

78" MAX.

8"x 8"x 1/4"

ALUMINUM

BASE PLATE

1/2" DIA. ADHESIVE

ANCHORS (4 PER

BASE PLATE)

1/8" THICK ALUMINUM PLATE

FOR MOUNTING EQUIPMENT,

BOLTED TO CHANNELS

ALUMINUM ANGLE

BRACE, WELDED TO

CHANNEL AND BASE

PLATE

1.

NOTES:

USE STAINLESS STEEL FASTENERS AND HARDWARE.

DIMENSIONS AS NEEDED

DOUBLE 1-5/8 IN.

ALUMINUM STRUT

OR C4-5.4 ALUMINUM

CHANNEL

ATS

1/4" MAX

"T"

T/2

T/2 T/4

SAWCUT OR TOOLED JOINT WITHIN 18HRS OF CONC

PLACEMENT

REINFORCEMENT, SEE PLAN

NOTES:

1. CONTROL JOINT LOCATIONS SHALL BE (UNO):

- @ 15'-0" OC MAX

- PANELS NOT TO EXCEED 1.5:1 L:W ASPECT RATIO

- ALIGNED W/COLS WHERE POSSIBLE

- CENTERED ON INTERIOR MASONRY WALL OPENINGS

2. SEE DRAWINGS FOR SLAB THICKNESS

3. MAKE SAWCUTS PRIOR TO SHRINKAGE CRACKING OF THE SLAB

4. FILL JOINTS W/JOINT SEALER (UNO)

R

Building a Better World for All of Us

R

SEH Project

Checked By

Drawn By

Project Status Issue Date

This drawing is an instrument of service and shall remain the property of SEH, Inc. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH, Inc.

Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH, Inc.

C O

P Y

R

IG

H T

Architect

Structural Engineer

Mechanical Engineer

Electrical Engineer

Owner

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Indian Health Service (IHS) 1301 Young St., Ste. 840 Dallas, TX 75202 214.767.5255

1/

/2

:2 1:

A

M

ELECTRICAL DETAILS

E601

A R

A P

A H

O E

H E

A L

T H

C E

N T

E R

E M

E R

G E

N C

Y G

E N

E R

A T

O R

G re at

P la in s

R d, A ra pa ho e, W

Y

169805

J.SOPATA

J.SEILER

IN

D

IA

N

H E

A L

T H

S E

R V

IC

E

100% CONSTRUCTION

DRAWINGS

1.11.2024

NOT TO SCALE

GROUNDING DETAIL

NOT TO SCALE

GENERATOR CONCRETE SLAB DETAIL

NOT TO SCALE

SLAB ON GRADE CONTROL JOINT DETAIL

1" = 1'-0"

MOUNTING DETAIL

Revision Issue

Rev. # Description Date

1/11/2024

FINAL CONSTRUCTION

DRAWINGS

01.12.2024

ALL GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN

THIS SET. THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT

BE USED IN THIS SET OF DRAWINGS.

1. ALL WORK SHALL BE PERFORMED IN STRICT COMPLIANCE WITH THE MANUFACTURER'S

RECOMMENDATIONS AND CURRENT STATE BUILDING, PLUMBING, MECHANICAL, FUEL GAS, FIRE

AND ENERGY CODES, ALL LOCAL CODES, STANDARDS, AND REGULATIONS GOVERNING THE

WORK.

2. ALL CONTRACTORS SHALL FAMILIARIZE THEMSELVES WITH THE MECHANICAL DRAWINGS AND

SPECIFICATIONS PRIOR TO BID. PROVIDE ALL EQUIPMENT, MATERIALS, AND LABOR AS

REQUIRED FOR THE COMPLETE INSTALLATION FOR ALL WORK AS SHOWN AND PROVIDE FOR A

COMPLETE, OPERABLE SYSTEM. ALL WORK SHALL BE PERFORMED IN A CLEAN, RECTILINEAR

AND WORKMANLIKE MANNER.

3. THE DRAWINGS ARE DIAGRAMMATIC, INTENDED TO CONVEY THE SCOPE OF WORK AND TO

INDICATE THE GENERAL ARRANGEMENT AND APPROXIMATE ROUTING. CERTAIN BASIC ITEMS

SUCH AS OFFSETS, FITTINGS, ACCESS PANELS, HANGERS, AND SLEEVES MAY NOT BE SHOWN.

WHERE SUCH ITEMS ARE REQUIRED FOR PROPER INSTALLATION OF THE WORK, SUCH ITEMS

SHALL BE INCLUDED. CONTRACTOR SHALL VERIFY CONNECTIONS, CLEARANCES, AND SERVICES

PRIOR TO INSTALLATION.

4. COORDINATE FINAL LOCATIONS OF DUCTWORK, PIPING AND MECHANICAL EQUIPMENT WITH

OTHER TRADES PRIOR TO BEGINNING WORK TO AVOID INTERFERENCES WITH EQUIPMENT,

STRUCTURE, PIPING, LIGHTING, CONDUIT, ETC. PROVIDE OFFSETS AS REQUIRED TO MEET

SPACE REQUIREMENTS AND TO AVOID INTERFERENCES. NO PIPING SHALL BE RUN OVER THE

TOP OF ANY ELECTRICAL PANELS OR ELECTRICAL EQUIPMENT.

5. EQUIPMENT AND MATERIALS SHALL BE PROTECTED FROM WEATHER, PAINTING, PLASTER, ETC.

UNTIL THE PROJECT IS COMPLETE. DAMAGE FROM RUST, PAINT, SCRATCHES, ETC., SHALL BE

REPAIRED AS REQUIRED TO RESTORE EQUIPMENT TO ORIGINAL CONDITION AT NO COST TO

OWNER.

6. CONTRACTOR SHALL COORDINATE ALL WALL AND ROOF OPENINGS AS IT RELATES TO THEIR

WORK. CUTTING OF STRUCTURAL SUPPORT MEMBERS WILL NOT BE PERMITTED WITHOUT

PRIOR WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER. EXTENT OF CUTTING SHALL BE

MINIMIZED TO PROVIDE THE NEAT MINIMUM OPENING REQUIRED PATCHING SHALL MATCH

ADJACENT MATERIALS AND SURFACES.

7. TEMPORARY SHUT DOWNS OF MECHANICAL SYSTEMS, IF REQUIRED, SHALL BE COORDINATED

WITH THE OWNER IN ORDER TO MINIMIZE THE INTERRUPTIONS TO THE OWNER.

8. NO MECHANICAL SERVICES OR EQUIPMENT SHALL BE LOCATED OVER ELECTRICAL EQUIPMENT, ELEVATOR EQUIPMENT, OR TELEPHONE EQUIPMENT ROOM.

9. CONTRACTOR SHALL INSTALL AS MUCH OF THE NEW SYSTEM AS POSSIBLE, PRIOR TO

REMOVING EXITING SYSTEMS IN ORDER TO MINIMIZE THE AMOUNT OF DOWN TIME. REFER TO

SPECIFICATIONS.

MECHANICAL GENERAL NOTES

HWS HYDRONIC HOT WATER SUPPLY

HWR HYDRONIC HOT WATER RETURN

CHWS CHILLED WATER SUPPLY

CHWR CHILLED WATER RETURN

REF REFRIGERANT SUCTION / LIQUID

CD CONDENSATE

CW COLD WATER

H-CW HARD COLD WATER

S-CW SOFTENED COLD WATER

HW DOMESTIC HOT WATER

RHW RECIRCULATED HOT WATER

RO REVERSE OSMOSIS WATER

T TEMPERED EYEWASH WATER

G NATURAL GAS

NPW NON-POTABLE WATER

W1 POTABLE WATER

W2 NON-POTABLE WATER

W3 PLANT EFFLUENT

OSD OVERFLOW STORM DRAIN

SD STORM DRAIN

SAN SANITARY SEWER DRAIN

V VENT

CWV COMBINATION WASTE AND VENT

IW INDIRECT WASTE

PD PUMP DISCHARGE

HWS

HWR

CHWS

CHWR

REF

CD

H-CW

S-CW

RO

T G

NPW

W1 W2 W3

OSD

SD

SAN

V

CWV

IW

PD

HVAC SYMBOLS PLUMBING AND PIPING SYMBOLSGENERAL NOTES

MECHANICAL EQUIPMENT

AC AIR COMPRESSOR

ACC AIR COOLED CONDENSER

ACCH AIR COOLED CHILLER

AHU AIR HANDLING UNIT

AS AIR SEPARATOR

B BOILER

BC BOOSTER COIL (HOT WATER)

CH CHILLER

CHWC CHILLED WATER COIL

CHWP CHILLED WATER PUMP

CP CONDENSATE PUMP

CRU COMPUTER ROOM UNIT

CT COOLING TOWER

CUH CABINET UNIT HEATER

CWP CONDENSER WATER PUMP

DBP DOMESTIC WATER BOOSTER PUMP

DCP DOMESTIC WATER CIRC. PUMP

DSF DESTRATIFICATION FAN

DG DOOR GRILLE

DL DRUM LOUVER

DRP DOMESTIC RECIRCULATION PUMP

DS DUCT SILENCER

DU DEHUMIDIFICATION UNIT

DXC DX COIL

EBB ELECTRIC BASE BOARD HEATER

ECH ELECTRIC COVE HEATER

EDH ELECTRIC DUCT HEATER

EF EXHAUST FAN

EG EXHAUST GRILLE

EHMD ELECTRIC HUMIDIFIER

ERV ENERGY RECOVERY VENTILATOR

ET EXPANSION TANK

EUH ELECTRIC UNIT HEATER

EVAP REMOTE EVAPORATOR

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WALL HEATER

EWH ELECTRIC WATER HEATER

F FURNACE

FCU FAN COIL UNIT

FP FIRE PUMP

FTR FINNED TUBE RADIATION

GHMD GAS FIRED HUMIDIFIER

GI GREASE INTERCEPTOR

GRH GAS FIRED RADIANT HEATER

GRV GRAVITY ROOF VENTILATOR

GUH GAS FIRED UNIT HEATER

HB HOSE BIBB

HP HEAT PUMP UNIT (AIR-AIR)

HS HAND SINK

HWC HW CONVECTOR

HWHC HOT WATER HEATING COIL

HWUH HOT WATER UNIT HEATER

HX HEAT EXCHANGER

HYD WALL HYDRANT

L LAVATORY

L LOUVER

LBG LINEAR BAR GRILLE

MAU MAKEUP AIR UNIT

P PUMP

PRV POWER ROOF VENTILATOR

RTU ROOFTOP AIR HANDLING UNIT

RCP RECIRCULATING PUMP

RD ROUND DIFFUSER

RG RETURN GRILLE

RTF RETURN FAN

RTU ROOFTOP UNIT

RV ROOF VENT

SD SLOT DIFFUSER

SEP SEWAGE EJECTOR PUMP

SF SUPPLY FAN

SG SUPPLY GRILLE

SP SUMP PUMP

TF TRANSFER FAN

TG TRANSFER GRILLE

UH UNIT HEATER

UV UNIT VENTILATOR

VAV VAV BOX (WITH OR WITHOUT COIL)

VP VACUUM PUMP

WH WATER HEATER

WS WATER SOFTENER

ABV ABOVE

AC AIR CONDITIONING

AD AREA DRAIN

ADD ADDENDUM

AFF ABOVE FINISHED FLOOR

AFUE ANNUAL FUEL UTILIZATION EFF.

ALT ALTERNATE

AP ACCESS PANEL

APD AIR PRESSURE DROP

ARCH ARCHITECT/ARCHITECTURAL

BCO BUILDING CLEANOUT

BFF BELOW FINISHED FLOOR

BLW BELOW

BTU BRITISH THERMAL UNITS

BTUH BTU PER HOUR

CAP CAPACITY

CB CATCH BASIN

CC COOLING COIL

CFM CUBIC FEET PER MINUTE

CLG CEILING

CO CLEAN OUT

D DEGREE

DB DRY BULB

DIA DIAMETER

DN DOWN

E, EX EXISTING

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

ELEC ELECTRICAL

EQUIP EQUIPMENT

EWT ENTERING WATER TEMP.

F DEGREES FAHRENHEIT

FCO FLOOR CLEAN OUT

FD FLOOR DRAIN

FD FIRE DAMPER

FDV FIRE DEPARTMENT VALVE

FL FLOOR

FPM FEET PER MINUTE

FS FLOOR SINK

FSD FIRE SMOKE DAMPER

FT FEET

FT HD FEET OF HEAD

FTR FIN TUBE RADIATION

GA GAUGE

GAL GALLON

GC GENERAL CONTRACTOR

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

HB HOSE BIB

HP HORSE POWER

IN INCH

INV INVERT

LAT LEAVING AIR TEMPERATURE

GENERAL ABBREVIATIONS

LB POUND

LB/HR POUNDS PER HOUR

LWT LEAVING WATER TEMPERATURE

MAT MIXED AIR TEMPERATURE

MAX MAXIMUM

MBH THOUSAND BTUH

MCF THOUSAND CUBIC FEET

MD MOTORIZED DAMPER

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MTR MOTOR

MUA MAKE-UP AIR

NC NOISE CRITERIA

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

O OXYGEN

Ø ROUND

OA OUTSIDE AIR

ORD OVERFLOW ROOF DRAIN

PD PRESSURE DROP

PIV POST INDICATOR VALVE

PLBG PLUMBING

PRESS PRESSURE

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

RA RETURN AIR

RD ROOF DRAIN

RH RELATIVE HUMIDITY

RM ROOM

RPM REVOLUTIONS PER MINUTE

SA SUPPLY AIR

SD SMOKE DAMPER

SF SQUARE FOOT

SP STATIC PRESSURE

T THERMOSTAT

TD TEMPERATURE DROP

TDR TRENCH DRAIN

TEMP TEMPERATURE

TYP TYPICAL

UG UNDERGROUND

V VENT

VAC VACUUM

VTR VENT THROUGH ROOF

WB WET BULB

WC WATER COLUMN

WCO WALL CLEAN OUT

WG WATER GAUGE

WPD WATER PRESSURE DROP

1 REVISION NUMBER

REVISION CLOUD

PLAN KEYNOTE

CONTINUATION SYMBOL

ROOM

NAME

ROOM NAME AND NUMBER

CONNECT TO EXISTING

NUMBER OF DETAIL ON SHEET

SHEET WHERE DETAIL APPEARS

RETURN AIR DUCT UP/DOWN

SUPPLY AIR DUCT UP/DOWN

EXHAUST AIR DUCT UP/DOWN

12/6

RETURN AIR/EXHAUST AIR GRILLE

MD

TURNING VANES

FLEXIBLE DUCT

MOTORIZED DAMPER

VD

LINEAR DIFFUSER

TEMPERATURE SENSOR / THERMOSTAT

FIRE DAMPER

HUMIDISTAT

VOLUME DAMPER

SMOKE DAMPER

SUPPLY AIR DIFFUSER

FIRE/SMOKE DAMPER

SPEED SWITCH

FD

SD

FSD

M

C02 CO2 SENSOR

CEILING RADIATION DAMPERCRD

RECTANGULAR DUCT SIZE TAG (WIDTH / HEIGHT)

12ø ROUND DUCT SIZE TAG (DIAMETER)

XXX-1

MECHANICAL EQUIPMENT TAG

EQUIPMENT TYPE (SEE

TABLE BELOW)

EQUIPMENT

NUMBER

EXISTING PIPE TO BE REMOVED

EXISTING PIPE TO REMAIN

NEW CONSTRUCTION

UNDERGROUND PIPING

BS BEAUTY SINK

BT BATH TUB

DF DRINKING FOUNTAIN

DW DISHWASHER

EW EYE WASH STATION

EWC ELECTRIC WATER COOLER

FDC FIRE DEPARTMENT CONN.

GD GARBAGE DISPOSAL

HB HOSE BIBB

HS HAND SINK

L LAVATORY

LS LAB SINK

LT LAUNDRY TUB

MB MOP BASIN

SH SHOWER

SK SINK

SS SAFETY SHOWER

SSEW SAFETY SHOWER EYE WASH

SSK SERVICE SINK

UR URINAL

W LAUNDRY WASHER BOX

WC WATER CLOSET

WDF WASH DOWN FAUCET

WDR WASH DOWN REEL

WF WASH FOUNTAIN

WH WALL HYDRANT

WO WALL OUTLET (LAMB'S TONGUE)

PLUMBING FIXTURES

XXX-1

PLUMBING FIXTURE TAG

FIXTURE TYPE (SEE TABLE

BELOW AND PLUMBING

FIXTURE SCHEDULE)

FIXTURE

NUMBER

CD

DG

DL

EG

L

LBG

RD

RG

SD

SG

TG

CEILING DIFFUSER

DOOR GRILLE

DRUM LOUVER

EXHAUST GRILLE

LOUVER

LINEAR BAR GRILLE

ROUND DIFFUSER

RETURN GRILLE

SLOT DIFFUSER

SUPPLY GRILLE

TRANSFER GRILLE

CD1 8"

200 CFM

TYPICAL SUPPLY DIFFUSER TAG

DIFFUSER

MARK

DUCT CONNECTION SIZE

AIRFLOW

TYPICAL GRILLE TAG

RG1 8/8

200 CFM

GRILLE MARK

GRILLE SIZE

AIRFLOW

ABBREVIATIONS

AIR DEVICES TAGS

1. PIPE OPENINGS THROUGH FIRE RATED WALLS SHALL BE CAULKED WITH AN INTUMESCENT

MATERIAL.

2. EXCAVATE UNDER FLOOR TRENCH, INSTALL PIPING AND BACK FILL WITH CLEAN SAND.

COMPACT AND REPLACE FLOOR TO MATCH EXISTING.

3. PIPING SHOWN IS SCHEMATIC TO SHOW SIZES AND GENERAL LOCATIONS. ROUTE PIPING AS

REQUIRED FOR CLEARANCE WITH STRUCTURAL CONDITIONS.

4. INSTALL PIPING TO MAINTAIN HEADROOM, CONSERVE SPACE, AND NOT INTERFERE WITH USE

OF SPACE. GROUP PIPING WHERE PRACTICAL AT COMMON ELEVATIONS. ROUTE PIPING IN A

RECTILINEAR, ORDERLY MANNER AND MAINTAIN GRADIENT. ROUTE PIPING PARALLEL AND

PERPENDICULAR TO WALL IN CEILING SPACE.

5. COORDINATE ROUGH-IN AND FINAL LOCATIONS OF NEW AND RELOCATED PIPING WITH

EXISTING LIGHTING. STRUCTURE, PROCESS, PIPING AND DUCTWORK, ETC. PROVIDE OFFSETS

AN/OR EASEMENTS AS REQUIRE TO AVOID CONFLICTS WITH WORK OF ALL OTHER TRADES.

6. INSTALL PIPING TO ALLOW FOR EXPANSION AND CONTRACTION WITHOUT STRESSING PIPE,

JOINTS OR CONNECTION PIPING.

7. PROVIDE CLEARANCE IN HANGERS AND FROM STRUCTURE AND OTHER EQUIPMENT FOR

INSTALLATION OF INSULATION AND ACCESS TO VALVES AND FITTINGS.

8. ROUGH-IN AND CONNECT ALL PLUMBING TO FIXTURES AND EQUIPMENT FURNISHED AND

INSTALLED BY OTHERS.

9. PROVIDE SHUT-OFF VALVES AT ALL EQUIPMENT AND ALL BRANCH PIPING OFF OF THE MAINS.

PLUMBING GENERAL NOTES

1. FABRICATE AND SUPPORT ALL DUCTWORK IN ACCORDANCE WITH SMACNA HVAC DUCT

CONSTRUCTION STANDARDS, METAL AND FLEXIBLE, CURRENT EDITION.

2. ALL DUCTWORK IS SHOWN IN SCHEMATIC FORM. NOT ALL RISES AND DROPS ARE SHOWN.

PROVIDE OFFSETS AS REQUIRED TO MEET SPACE REQUIREMENTS AND TO AVOID

INTERFERENCES WITH OTHER TRADES.

3. ELBOWS SHALL BE SQUARE ELBOWS CONSTRUCTED WITH TURNING VANES. RADIUS ELBOWS

WITH CENTERLINE RADIUS OF NOT LESS THAN 1.5 TIMES THE DUCT WIDTH MAY BE USED

WHERE SPACE CONDITIONS PERMIT OR WHERE INDICATED ON DRAWINGS.

4. ALL BRANCH DUCT TAPS SHALL BE CONICAL FITTINGS ON ROUND MAINS AND SHALL BE 45 DEG

ENTRY FITTINGS ON RECTANGULAR MAINS.

5. MAXIMUM LENGTH OF FLEXIBLE DUCT SHALL NOT EXCEED 5'-0" FLEXIBLE DUCT SHALL BE

METALFLEX FLEXIBLE DUCT WITH 1" EXTERNAL FIBERGLASS INSULATION AND VAPOR BARRIER

JACKET.

6. MANUAL VOLUME DAMPERS SHALL BE PROVIDED ON ALL RETURN, SUPPLY AND EXHAUST

BRANCH DUCTS.

7. SUPPORT ALL DUCTWORK, EQUIPMENT, ETC., FROM TOP CHORD OF BAR JOISTS OR STEEL

FRAMING BEAMS.

8. ALL DUCTWORK IN CHEMICAL STORAGE ROOMS SHALL BE FIBERGLASS (FRP) WITH

FIBERGLASS HANGERS AND HARDWARE.

9. ALL DUCT SIZES SHOWN ARE CLEAR INSIDE DIMENSIONS. INCREASE SHEET METAL SIZE TO

ACCOMMODATE DUCT LINER AS REQUIRED BY THE SPECIFICATIONS.

10. ALL SHEET METAL CONNECTIONS AND JOISTS SHALL BE SEALED TO SMACNA CLASS A.

11. DIFFUSER, GRILLE, AND REGISTER LOCATIONS. SHALL BE COORDINATED WITH THE

ARCHITECT'S REFLECTED CEILING PLANS AND ELECTRICAL LIGHTING PLAN.

12. CHANGE DUCT SIZES GRADUALLY. LIMIT SLOPES FOR TRANSITIONS TO A MAXIMUM OF 1 INCH

CHANGE IN WIDTH FOR EVERY 3 INCHES OF LENGTH OF APPROXIMATELY 15 DEG. A MAXIMUM

OF 30 DEG IS ACCEPTABLE DIRECTLY ADJACENT TO EQUIPMENT.

HVAC GENERAL NOTES

ELBOW DOWN

TEE DOWN

TEE UP

ELBOW UP

CAPPED OR PLUGGED PIPE

3-WAY CONTROL VALVE

2-WAY CONTROL VALVE

PRESSURE REDUCING VALVE

BACKFLOW PREVENTER

FIN-TUBE RADIATION

BARE PIPE IN CABINET

FIN-TUBE RADIATION IN CABINET

CABINET ONLY

PUMP

BALANCING VALVE

DRAIN VALVE

PIPE THERMOMETER

PRESSURE GAUGE

RELIEF VALVE

STOP VALVE

GLOBE VALVE

BUTTERFLY VALVE

CHECK VALVE

PIPE PITCH DOWN

GATE VALVE

BALL VALVE

PIPE EXPANSION JOINT

STRAINER

PIPE ANCHOR

UNION

FLUID FLOW

OR

SCHEMATIC SYMBOLS

GENERAL MECHANICAL SYMBOLS

NOTE

FLOOR DRAIN SYMBOL

FLOOR SINK SYMBOL

STORM DRAIN SYMBOL

DRAIN TAGS

X" XX-1

DRAIN

CONNECTION

SIZE

DRAIN TYPE (SEE TABLE

BELOW AND PLUMBING

FIXTURE SCHEDULE)

AD AREA DRAIN

DW DISHWASHER

FD FLOOR DRAIN

FS FLOOR SINK

FFD FUNNEL FLOOR DRAIN

ORD OVERFLOW ROOF DRAIN

OSD OPEN SIGHT DRAIN

RD ROOF DRAIN

TD TRENCH DRAIN

TTFD TELL-TALE FLOOR DRAIN

MECHANICAL SHEET INDEX

S

H

T

R

Building a Better World for All of Us

R

SEH Project

Checked By

Drawn By

Project Status Issue Date

This drawing is an instrument of service and shall remain the property of SEH, Inc. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH, Inc.

Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH, Inc.

C O

P Y

R

IG

H T

Architect

Structural Engineer

Mechanical Engineer

Electrical Engineer

Owner

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Indian Health Service (IHS) 1301 Young St., Ste. 840 Dallas, TX 75202 214.767.5255

1/

/2

9:

:4

A

M

MECHANICAL SYMBOLS AND

ABBREVIATIONS

P001

A R

A P

A H

O E

H E

A L

T H

C E

N T

E R

E M

E R

G E

N C

Y G

E N

E R

A T

O R

G re at

P la in s

R d, A ra pa ho e, W

Y

169805

M.MASSA

C.ELSNER

IN

D

IA

N

H E

A L

T H

S E

R V

IC

E

100% CONSTRUCTION

DRAWINGS

01.12.2024

P001 MECHANICAL SYMBOLS AND ABBREVIATIONS

P111 PLUMBING PLANS - GAS

Revision Issue

Rev. # Description Date

FINAL CONSTRUCTION

DRAWINGS

J

E P

O

4" G

4" G

4" G

4" G

3" G (E)

ARAPAHOE HEALTH CENTER

CUMMINS 125KW NATURAL GAS

GENERATOR MODEL #C150N6

2" G (E)

4"

GAS

METER

RUN GAS PIPING ABOVE

GROUND TO GENERATOR

G

NOTES:

GAS METER & REGULATOR SHALL BE BY THE LOCAL GAS COMPANY.

ALL COSTS WILL BE INCURRED BY THE PLUMBING CONTRACTOR.

GAS MAIN,

SEE PLAN

12" (MIN.) DIRT LEG

TO GENERATOR, SEE PLAN.

CAPPED TEST TEE

PRESSURE REGULATOR,

SEE PLAN FOR DEMAND

SHUT-OFF VALVE

M M

EMERGENCY GENERATOR NUMBERED NOTES:

PREFABRICATED GENERATOR ENCLOSURE PROVIDED BY GENERATOR MANUFACTURER INCLUDES THE FOLLOWING (TYP.)

1. EMERGENCY GENERATOR

2. SPRING ISOLATORS

3. EXHAUST FLUE ROOF THIMBLE

4. MUFFLER

5. MUFFLER HANGERS

6. EXHAUST FLUE

7. EXHAUST FLUE RAIN CAP

8. EXHAUST FLUE FLEX CONNECTION

9. DUCT TRANSITION AND FLEX CONNECTION

10. EXHAUST AIR DUCTWORK

11. EXHAUST AIR DAMPER PER NFPA 99

12. OUTSIDE AIR DAMPER PER NFPA 99

13. CONCRETE HOUSEKEEPING PAD

14. OUTSIDE AIR LOUVER

15. EXHAUST AIR LOUVER

4"

NEW 4"

ISOLATION VALVE

OUTSIDE OF

BUILDING

GRADE

GAS METER

3079 MBH @ 2 PSI MAX

3665 CFH (840 BTU/CF)

300 FT DEVELOPED LENGTH

CONTRACTOR SHALL FIELD

COORDINATE CONNECTION SIZES

G

EXISTING

GAS METER

TO BE REPLACED PER

LOCAL UTILITY

REQUIREMENTS

NEW GENERATOR

1608.6 MBH

1915.0 SCFH

4"

3" (E)

TO BUILDING:

1470 MBH

1750 CFH

(ESTIMATED

MAX. DEMAND)

2" G (E) FROM MAIN

FUEL SHUT-OFF SOLENOID

FACTORY-MOUNTED ON GENERATOR

INSTALL FLEXIBLE FUEL LINE

(FURNISHED WITH GENERATOR)

PROVIDE PRIMARY GAS PRESSURE

REGULATOR

NATURAL GAS AT 6 TO 13 IN. W.C. INLET

PRESSURE

PROVIDE LOCKABLE MANUAL GAS

SHUT-OFF VALVE

SECONDARY GAS REGULATOR AND GAUGE,

FURNISHED WITH GENERATOR

CARBURETOR, FACTORY-MOUNTED ON

GENERATOR

TO GENERATOR ENGINE

GAS PRESSURE GAUGE WITH PETCOCK (0-15"

WATER COLUMN)

PROVIDE 4" GAS PIPING FROM REGULATOR TO

CONNECTION ON GENERATOR

INSTALL DRY FUEL FILTER (STRAINER)

FURNISHED WITH GENERATOR

R

Building a Better World for All of Us

R

SEH Project

Checked By

Drawn By

Project Status Issue Date

This drawing is an instrument of service and shall remain the property of SEH, Inc. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH, Inc.

Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH, Inc.

C O

P Y

R

IG

H T

Architect

Structural Engineer

Mechanical Engineer

Electrical Engineer

Owner

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Short Elliott Hendrickson, Inc.

2000 South Colorado Boulevard Tower One, Suite 6000 Denver, Colorado 80222 720.540.6800

Indian Health Service (IHS) 1301 Young St., Ste. 840 Dallas, TX 75202 214.767.5255

1/

/2

9:

:4

A

M

PLUMBING PLANS - GAS

P111

A R

A P

A H

O E

H E

A L

T H

C E

N T

E R

E M

E R

G E

N C

Y G

E N

E R

A T

O R

G re at

P la in s

R d, A ra pa ho e, W

Y

169805

M.MASSA

C.ELSNER

IN

D

IA

N

H E

A L

T H

S E

R V

IC

E

100% CONSTRUCTION

DRAWINGS

01.12.2024

16' 32'8'0 1/16" = 1'-0"P111

1 PLUMBING GAS PLAN-01

NOT TO SCALEP111

4 GAS METER

NOT TO SCALEP111

2 EMERGENCY GENERATOR SCHEMATIC

NOT TO SCALEP111

3 NATURAL GAS PIPING SCHEMATIC

A. ALL EXISTING CONDITIONS ARE NOT COMPLETELY

DETAILED. CONTRACTOR SHALL SURVEY THE SITE AND

MAKE ALL NECESSARY CHANGES REQUIRED BASED ON

EXISTING CONDITIONS FOR PROPER INSTALLATION OF

NEW WORK.

B. CONTRACTOR SHALL LOCATE ALL UNDERGROUND

UTILITIES PRIOR TO EXCAVATION WORK.

C. COORDINATE CHANGES TO NATURAL GAS SERVICE LINE

FROM MAIN TO NEW GAS METER WITH LOCAL UTILITY.

D. ALL DEMOLISHED WORK SHALL BECOME THE PROPERTY

OF THE CONTRACTOR. CONTRACTOR SHALL REMOVE AND

DISPOSE OF ALL DEMOLISHED WORK OFF SITE IN AN

ACCEPTABLE AND SAFE MANNER.

E. ROUGH-IN AND FINAL CONNECT ALL FIXTURES,

EQUIPMENT, ETC.

F. CONTRACTOR SHALL INVESTIGATE SITE CONDITIONS AND

SUBMIT SHOP DRAWINGS FOR THE GAS SERVICE

MODIFICATIONS.

GENERAL NOTES

NOT TO SCALEP111

5 GAS CONNECTION TO EQUIPMENT

Revision Issue

Rev. # Description Date

FINAL CONSTRUCTION

DRAWINGS

Sheets
E001 - ELECTRICAL TITLE SHEET
E201 - ELECTRICAL PLAN
E401 - ELECTRICAL ONE-LINE DIAGRAM
E601 - ELECTRICAL DETAILS

File details come from the government source that posted it. Updated .