B01_140L6326Q0006_-_Attachment_02_-_Drawings.pdf
PDF 2 MB Posted
- Attached to
- FDO Exterior Door Canopies
- Solicitation number
- 140L6326Q0006
About this file
This is a set of architectural and structural construction documents for the FDO Entry Canopies project located at the Bureau of Land Management Fairbanks District Office in Fairbanks, Alaska. The project, issued November 30, 2023, with communication number 902304, involves the design and construction of three entry canopies with associated structural support systems. The work includes metal standing seam roofing (R-M2 assembly), structural steel components using HSS3X3X3/16 and HSS3X3X1/4 hollow structural sections conforming to ASTM A500 Grade C, concrete foundations with 4500 PSI compressive strength, and metal roof panels with pre-finished metal flashing and trim. The roof deck specifications call for 1.5-inch 16-gauge Type B steel roof deck fastened with #12 screws at flute button punch side seams spaced 12 inches on center. Foundation designs include sonotube foundations and anchor bolts per ASTM F1554 Grade 36, with concrete protection requirements specified for cold-weather construction in the Alaska climate.
Design criteria reference the 2021 International Building Code with ground snow load of 60 PSF, ultimate design wind speed of 110 MPH, and seismic design category D. Material specifications include metal roof panels from Metal Sales (Magna-Loc series) and sheet metal flashing and trim accessories, with colors and specific models to be determined. The documents contain detailed architectural information sheets (A001, A040, A210, A670) and structural plans (S001, S100, S200, S300) with foundation plans, framing plans, and architectural details for rake flashing, wall connections, and eave conditions. Design professionals include James D. Bartlett, AIA (Registered Professional Architect) and Peter A. Jacobsen, SE14544 (Registered Structural Engineer) from Design Alaska, with the Bureau of Land Management represented by Curt Fortenberry as the owner's representative.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 View Name 1/8" = 1'-0"A101
Room name
GENERAL SYMBOLS
NAME
NUMBER
SHEET LOCATION
SCALE
TRUE NORTH
GRID LINE
ROOM NAME
ROOM NUMBER
PLAN NORTH
REVISION
SEE DISCIPLINES FOR SPECIFIC SYMBOLS
PROJECT TEAM
OWNERS REPRESENTATIVE
BUREAU OF LAND MANAGEMENT
POINT OF CONTACT: CURT FORTENBERRY
222 UNIVERSITY AVENUE
FAIRBANKS, ALASKA 99709
DESIGNERS REPRESENTATIVE
DESIGN ALASKA
POINT OF CONTACT: JEFF PUTNAM
601 COLLEGE ROAD
FAIRBANKS, ALASKA 99701
VICINITY MAP
PROJECT
LOCATION
U N
IV
E
R S
IT
Y
A V
E N
U E
DNR ACCESS ROAD
ALASKA MAP
PACIFIC OCEAN
ARCTIC OCEAN
BERING
SEA
KODIAK
ARCTIC CIRCLE
SEWARD
SITKA
JUNEAU
HAINES
WHITEHORSE YT
DAWSON YT
HAINES
JCT
HOMER
ANCHORAGE
EAGLE
CORDOVA
VALDEZ
GLENNALLEN
TOK
NORTH
POLE
FAIRBANKS
NENANA
TANANA
CIRCLE
NOME
KOTZEBUE
UTQIAGVIK
(BARROW)
PRUDHOE BAY
U N
IT
E
D S
T A
T E
S
R U
S S
IA
U N
IT
E
D S
T A
T E
S C
A N
A D
A
PROJECT
LOCATION
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
30 NOV 2023
FDO ENTRY
CANOPIES
902304
AECC511
11/30/2023 11:33:28 AM
GENERAL
INFORMATION
G010
FDO ENTRY CANOPIES
FAIRBANKS, ALASKA
BUREAU OF LAND MANAGEMENT - FAIRBANKS DISTRICT OFFICE
ARCHITECTURAL
A001 ARCHITECTURAL INFORMATION
A040 ARCHITECTURAL SCHEDULES AND TYPES - MATERIAL
A210 ARCHITECTURAL PLANS - 1ST FLOOR - OVERALL
A670 ARCHITECTURAL DETAILS - EXTERIOR ROOF AND
CANOPY
GENERAL
G010 GENERAL INFORMATION
STRUCTURAL
S001 GENERAL STRUCTURAL NOTES
S100 CANOPY LOCATION PLAN
S200 STRUCTURAL PLANS
S300 STRUCTURAL DETAILS
CONCRETE
EARTH
PLYWOOD
MATERIAL LEGEND
NO ARCHITECTURAL WORK
THIS AREA
EXISTING
CONSTRUCTION DETAIL
ARCHITECTURAL SYMBOL LEGEND
150 SF
Room Name
DETAIL NAME
DETAIL NUMBER
SHEET LOCATION
DETAIL SCALE
TRUE NORTH
GRID LINE
ROOM NAME
ROOM NUMBER
PLAN NORTH
DETAIL NUMBER
SHEET LOCATION
SIMILAR
REVISION
SPOT ELEVATION
SEE OTHER DISCIPLINES FOR ADDITIONAL SYMBOLS
KEYED NOTE
DOOR TAG
A100
A100
EXTERIOR ELEVATION
SHEET LOCATION
DETAIL NUMBER
INTERIOR ELEVATION
SHEET LOCATION
DETAIL NUMBER
DETAIL NUMBER 4
A
BUILDING SECTION
DETAIL NUMBER
SHEET LOCATION
SIMILAR
WALL SECTION
WINDOW TYPE
ROOM AREA
1/8" = 1'-0" View Name
1/4" / 1'-0"
.SPOT SLOPE
101ROOM NUMBER
A101
SIM
A101
SIM
101A
1. SEE OTHER DISCIPLINES FOR ADDITIONAL ABBREVIATIONS.
2. SEE GENERAL SHEETS FOR CODE ABBREVIATIONS.
3. SEE ASSEMBLY TYPES FOR HYPHENATED ASSEMBLY TAGS
(I.E. C-A1, W01-3A, AND WX-3A).
4. SEE MATERIAL SCHEDULE FOR HYPHENATED MATERIAL TAGS
(I.E. ACT-1, CPT-1, AND RB-1).
5. SEE ROOM AND DOOR SCHEDULE FOR SPECIFIC RELEVANT
ABBREVIATIONS.
6. SOME ABBREVIATIONS LISTED BELOW MAY NOT BE USED IN
THIS PROJECT.
(E) EXISTING
ADA AMERICAN DISABILITIES ACT
AFF ABOVE FINISHED FLOOR
CFCI CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CFOI CONTRACTOR FURNISHED OWNER INSTALLED
CMU CONCRETE MASONRY UNIT
CONC CONCRETE
ELEC ELECTRICAL
FV FIELD VERIFY
GA GYPSUM ASSOCIATION
GYP GYPSUM BOARD
IBC INTERNATIONAL BUILDING CODE
INSUL INSULATION
ITSP INSULATED TRANSLUCENT SANDWICH PANEL
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MFSD MANUFACTURER'S STANDARD
MIN MINIMUM
NIC NOT IN CONTRACT
OC ON CENTER
OD OVERFLOW DRAIN
OFOI OWNER FURNISHED OWNER INSTALLED
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OSB ORIENTED STRAND BOARD
OTS OPEN TO STRUCTURE
PLY PLYWOOD
RD ROOF DRAIN
SIP STRUCTURAL INSULATED PANEL
SPEC SPECIFICATION
STC SOUND TRANSMISSION CLASS
STRUC STRUCTURAL
TBD TO BE DETERMINED
TYP TYPICAL
UL UNDERWRITERS LABORATORY
VTR VENT THROUGH ROOF
ARCHITECTURAL STANDARD ABBREVIATIONS
ARCHITECTURAL PROJECT SPECIFIC ABBREVIATIONS
NA NOT APPLICABLE
WX-A1
WALL ASSEMBLY CATEGORY - FUNCTION
WALL BUILDING ENVELOPE DESIGNATION
WALL ASSEMBLY MODIFIER
WALL ASSEMBLY CATEGORY - FUNCTION
PROJECTS MAY NOT INCLUDE ALL ASSEMBLY CATEGORIES.
• WF WALL - FOUNDATION
• WP WALL - PARAPET
• WX WALL - EXTERIOR
WALL BUILDING ENVELOPE DESIGNATION
• A EIFS / FOUNDATION
• B RAINSCREEN
• C IMP
• D OTHER
WALL ASSEMBLY MODIFIER
NUMBERS REPRESENT DESCRIPTIONS OF ASSEMBLY TYPES.
THE BELOW ARE COMMONLY USED EXAMPLES. SEE
ASSEMBLY TYPES FOR ADDITIONAL MODIFIERS.
• 1 TYPICAL
EXTERIOR ASSEMBLY TAG LEGEND - WALL
CX-B1
CEILING ASSEMBLY CATEGORY
CEILING ASSEMBLY MODIFIER
CEILING ASSEMBLY CATEGORY
PROJECTS MAY NOT INCLUDE ALL ASSEMBLY CATEGORIES.
• CX CEILING EXTERIOR
CEILING BUILDING ENVELOPE DESIGNATION
• A NOT USED
• B CAVITY INSULATED
• C NOT USED
• D OTHER
CEILING ASSEMBLY MODIFIER
NUMBERS REPRESENT DESCRIPTIONS OF ASSEMBLY
TYPES. THE BELOW ARE COMMONLY USED EXAMPLES.
SEE ASSEMBLY TYPES FOR ADDITIONAL MODIFIERS.
• 1 TYPICAL
EXTERIOR ASSEMBLY TAG LEGEND - CEILING
CEILING BUILDING ENVELOPE DESIGNATION
R-A1
ROOF ASSEMBLY CATEGORY - FUNCTION
ROOF ASSEMBLY MODIFIER
ROOF ASSEMBLY CATEGORY - FUNCTION
• R ROOF
• RS ROOF - SOFFIT
ROOF BUILDING ENVELOPE DESIGNATION
• A MEMBRANE
• B CAVITY INSULATED
• C IMP
• D OTHER
ROOF ASSEMBLY MODIFIER
NUMBERS REPRESENT DESCRIPTIONS OF ASSEMBLY
TYPES. THE BELOW ARE COMMONLY USED EXAMPLES.
SEE ASSEMBLY TYPES FOR ADDITIONAL MODIFIERS.
• 1 TYPICAL
EXTERIOR ASSEMBLY TAG LEGEND - ROOF
ROOF BUILDING ENVELOPE DESIGNATION
BUILDING ENVELOPE LEGEND
SEE EXTERIOR ASSEMBLY TYPES, EXTERIOR DETAILS,
MATERIAL SCHEDULE, AND SPECIFICATIONS FOR
ADDITIONAL INFORMATION. PROJECTS MAY NOT INCLUDE
ALL BUILDING ENVELOPE CATEGORIES.
DIRECTION
OF DRYING
BE-1 OR 2: FOUNDATION MEMBRANE
BE-4: INTERIOR AIR/VAPOR BARRIER
BE-5 OR 6: EXTERIOR AIR/WATER BARRIER
BE-7, 8, OR 9: ROOF UNDERLAY
BUILDING ENVELOPE COMPONENT
BUILDING ENVELOPE METAL FLASHING
DESCRIBES THE DIRECTION OF AIRFLOW IN A
VENTED OR VENTILATED ASSEMBLY
DESCRIBES THE DIRECTION AN ASSEMBLY
WILL DRY. PERMEABLE MATERIALS REQUIRED
TO DRY AS SHOWN
A. ARCHITECTURAL NOTES DESCRIBE WORK COMPRISING
THE ENTIRE ARCHITECTURAL DISCIPLINE.
B. SHEET NOTES DESCRIBE WORK COMPRISING THE ENTIRE
SHEET ON WHICH THE NOTES APPEAR INCLUDING
SHEETS ON WHICH THE NOTES ARE REFERENCED.
C. CONSTRUCTION DOCUMENTS ARE PREPARED FOR THE
PURPOSES OF COMMUNICATING DESIGN INTENT.
D. DRAWINGS ARE GRAPHIC REPRESENTATIONS CONVEYING
THE QUANTITATIVE EXTENT AND RELATIONSHIP BETWEEN
PROJECT ELEMENTS.
E. SPECIFICATIONS ARE WRITTEN REPRESENTATIONS
CONVEYING THE QUALITATIVE REQUIREMENTS OF
PROJECT ELEMENTS.
F. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A
COMPLETE AND FINISHED PRODUCT FULFILLING THE
INTENT OF THE CONSTRUCTION DOCUMENTS.
G. THE TERM 'NEW' MAY BE USED TO DISTINGUISH NEW
FROM EXISTING IN SOME INSTANCES. OMISSION OF THE
TERM 'NEW' IS NOT NECESSARILY AN INDICATION THAT
THE ELEMENT IS EXISTING.
H. THE TERM 'ALL' MAY BE USED TO CLARIFY SCOPE.
OMISSION OF THE TERM 'ALL' IS NOT NECESSARILY AN
INDICATION THAT THE SCOPE IS LIMITED.
I. SEE GENERAL CODE INFORMATION AND CODE PLAN.
J. PROVIDE CONSTRUCTION IN COMPLIANCE WITH OSHA.
K. COORDINATE ARCHITECTURAL WORK WITH
STRUCTURAL.
L. SEE STRUCTURAL FOR SPECIFIC INFORMATION
REGARDING LOAD BEARING MEMBERS, MECHANICAL
FASTENERS, MASTIC ADHESION, AND STRUCTURE.
M. FURNITURE IS SHOWN FOR COORDINATION PURPOSES
ONLY. FURNITURE IS OWNER FURNISHED AND OWNER
INSTALLED UNLESS NOTED OTHERWISE.
N. PATCH, REPAIR, AND REFINISH EXISTING SURFACES TO
REMAIN, AFFECTED BY WORK.
O. CONTRACTOR TO FIELD VERIFY DIMENSIONS SHOWN TO
EXISTING CONSTRUCTION PRIOR TO WORK. NOTIFY
ARCHITECT WHERE DISCREPANCIES ARE DISCOVERED.
P. DIMENSIONS AT EXISTING CONSTRUCTION ARE
MEASURED FROM FACE OF EXISTING FINISH UNLESS
NOTED OTHERWISE.
Q. DIMENSIONS AT NEW CONSTRUCTION ARE MEASURED
FROM FACE OF FRAMING UNLESS NOTED OTHERWISE.
R. CONFIRM DIMENSIONS INDICATED WITH 'FIELD VERIFY'
AND/ OR 'FV' PRIOR TO WORK.
S. DIMENSIONS INDICATED AS 'CLEAR' REQUIRE MINIMUM
CLEARANCE MEASURED TO FINISHED FACES, UNLESS
NOTED OTHERWISE.
T. DIMENSIONS INDICATED WITH '+/-' BRING THE
CONTRACTORS ATTENTION TO AREAS WITH FLEXIBILITY
GREATER THAN ADJACENT AREAS NOT OTHERWISE
INDICATED.
U. SEE SPECIFICATIONS FOR ALLOWABLE TOLERANCES.
V. CONFIRM MANUFACTURERS' INSTALLATION
INSTRUCTIONS CONFORM TO SPECIFIED TOLERANCES.
W. SEE DETAILS FOR DIMENSION AND LEVEL REFERENCE
POINTS.
ARCHITECTURAL NOTES
A001
A001
THIS REFERENCE INDICATES LOCATION OF INFORMATION IN A
TYPICAL PROJECT. THIS PROJECT MAY VARY FROM THE
REPRESENTATION BELOW. SEE THE SHEET INDEX FOR SPECIFIC
SHEET SEQUENCE.
A0 SHEETS INFORMATION, ASSEMBLIES, SCHEDULES
A1 SHEETS PHASING, EXISTING, DEMOLITION (NOT USED)
A2 SHEETS FLOOR AND ROOF PLANS
A3 SHEETS EXTERIOR ELEVATIONS (NOT USED)
A4 SHEETS SECTIONS (NOT USED)
A5 SHEETS VERTICAL CIRCULATION (NOT USED)
A6 SHEETS FIRE RESISTIVE AND EXTERIOR DETAILS
A7 SHEETS INTERIOR DESIGN PLANS (NOT USED)
A8 SHEETS INTERIOR ELEVATIONS (NOT USED)
A9 SHEETS INTERIOR DESIGN DETAILS (NOT USED)
THE TWO CHARACTER ALPHANUMERIC DESIGNATIONS REPRESENT
ALL SHEETS IN THE SERIES. FOR EXAMPLE, 'A1 SHEETS' DESCRIBES
A100 THROUGH A199.
ARCHITECTURAL SHEET SEQUENCE
1'-0"
1'-0"
GRID
1'-0"
CLEAR
8 3/8" 1'-0"
GRID TO GRID
GRID TO WALL
NEW WALL STUD TO
NEW WALL STUD
NEW WALL STUD TO
EXISTING WALL FINISH
EXISTING WALL FINISH TO
EXISTING WALL FINISH.
FIELD VERIFY.
REQUIRED CLEARANCE TO
FINISHED FACES, MINIMUM
UNLESS NOTED OTHERWISE
FIELD VERIFY EXISTING
CONDITIONS
1ST FLOOR
0'-0"
ARCHITECTURAL FLOOR LEVEL INDICATES
TOP OF STRUCTURAL FLOOR SURFACE. SEE
STRUCTURAL FOR LOCATION, SIZING, AND
COMPOSITION OF STRUCTURAL MEMBERS.
PER TYPE THIS DIAGRAM CLARIFIES DIMENSION
REFERENCE POINTS. SEE FLOOR
ASSEMBLY TYPES FOR ACTUAL
CONSTRUCTION.
FLOOR FINISH PER ROOM SCHEDULE
FLOOR PREPARATION PER SPECS
STRUCTURE/ SHEATHING PER STRUCTURAL
GRADE
- 0'-8"
ARCHITECTURAL GRADE LEVEL INDICATES
APPROXIMATE RELATIONSHIP BETWEEN
BUILDING AND GROUND SURFACE. SEE CIVIL
FOR GRADING, EXTERIOR WALKING
SURFACES, AND ACTUAL RELATIONSHIP
BETWEEN BUILDING AND GROUND SURFACE.
ROOF
12'-0"
PER TYPE
ARCHITECTURAL ROOF LEVEL INDICATES
TOP OF STRUCTURAL FRAMING /
SHEATHING / DECK. SEE STRUCTURAL
FOR LOCATION, SIZING, AND COMPOSITION
OF STRUCTURAL MEMBERS.
THIS DIAGRAM CLARIFIES DIMENSION
REFERENCE POINTS. SEE ROOF
ASSEMBLY TYPES FOR ACTUAL
CONSTRUCTION.
LOW SLOPE ROOF EXAMPLE SHOWN.
STEEP SLOPE MAY INDICATE TOP OF
WALL. COORDINATE WITH STRUCTURAL.
STRUCTURE / FRAMING / SHEATHING /
DECK PER STRUCTURAL
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
A K
AF AL
T S
TA
E
O
49 TH
S
JAMES D. BARTLETT
No. A10413
R E
G
IS
T
ERED
PROFESSIONAL
ARC
H
IT
E C
T
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
30 NOV 2023
FDO ENTRY
CANOPIES
902304
AECC511
30-NOV-2023
11/30/2023 8:50:38 AM
JB
JAC
ARCHITECTURAL
INFORMATION
A0011 1/2" = 1'-0"A001
1 INTERIOR DETAIL - TYPICAL - DIMENSION REFERENCE POINT CONVENTIONS
6" = 1'-0"A001
2 INTERIOR DETAIL - TYPICAL - LEVEL REFERENCE POINT CONVENTIONS
MATERIAL SCHEDULE NOTES
A. SEE EXTERIOR ELEVATIONS, CEILING PLANS, FINISH
PLANS, INTERIOR ELEVATIONS, AND ROOM SCHEDULE
FOR LOCATION OF FINISHES.
B. THE MATERIAL SCHEDULE PROVIDES A BASIS OF DESIGN.
SEE SPECIFICATIONS FOR PRODUCT INFORMATION,
PERFORMANCE CRITERIA, AND ACCEPTABLE
ALTERNATIVE MANUFACTURERS.
C. THE MATERIAL SCHEDULE IS ORGANIZED BY SPEC
NUMBER. MATERIALS WITH SPEC NUMBERS INCLUDING
'NA' PROVIDE A BASIS OF DESIGN WITH NO CORRELATING
SPEC SECTION.
D. SEE MATERIAL SCHEDULE INDEX BELOW TO QUICKLY
FIND THE SPEC NUMBER FOR MATERIALS ORGANIZED BY
TYPE.
MISCELLANEOUS
1. NOT USED
MATERIAL SCHEDULE REMARKS
SEE A001 FOR STANDARD ARCHITECTURAL ABBREVIATIONS
MATERIAL TYPES DEFINED IN MATERIAL SCHEDULE
MFSD MANUFACTURER'S STANDARD
SPEC SPECIFICATION
TYP TYPICAL
MATERIAL SCHEDULE ABBREVIATIONS
A. COMPOSITE WOOD AND AGRIFIBER PRODUCTS
(INCLUDING ASSOCIATED SUBSTRATE) MUST CONTAIN
NO ADDED UREA-FORMALDEHYDE.
B. CLEAR WOOD FINISHES, FLOOR COATINGS, STAINS,
PRIMERS, SEALERS, AND SHELLACS (INCLUDING TILE
SETTING ADHESIVE, AND GROUT) APPLIED TO INTERIOR
ELEMENTS MUST NOT EXCEED THE VOC CONTENT LIMITS
ESTABLISHED IN SCAQMD RULE 1113 AS OF 01 JAN 2004.
C. ADHESIVES, SEALANTS, AND SEALANT PRIMERS APPLIED
TO INTERIOR ELEMENTS MUST COMPLY WITH SCAQMD
RULE 1168 AS OF 01 JULY 2005. AEROSOL ADHESIVES
APPLIED TO INTERIOR ELEMENTS MUST COMPLY WITH
GREEN SEAL GS-36 AS OF 19 OCTOBER 2000.
D. HARD SURFACE FLOORING AND WALL BASE MUST BE
FLOORSCORE CERTIFIED.
E. CARPET MUST MEET GREEN LABEL PLUS
REQUIREMENTS. CARPET CUSHION MUST MEET GREEN
LABEL REQUIREMENTS.
F. ARCHITECTURAL PAINTS AND COATINGS APPLIED TO
INTERIOR ELEMENTS MUST NOT EXCEED THE VOC
CONTENT LIMITS ESTABLISHED IN GREEN SEAL
STANDARD GS-11 AS OF 20 MAY 1993.
LOW EMITTING
LE-
LE-
LE-
LE-
LE-
LE-
1 - TYPICAL
A. ASSEMBLIES ARE DIAGRAMS ONLY, DO NOT SCALE.
B. ASSEMBLIES DESCRIBE MATERIALS AND THEIR
RELATIONSHIP WITHIN A GIVEN CEILING, FLOOR, ROOF, OR
WALL. PENETRATIONS, JOINTS, FINISHES, AND
INTERSECTIONS BETWEEN ASSEMBLIES ARE NOT SHOWN.
C. SEE A0 SHEETS FOR ARCHITECTURAL NOTES, SHEET
SEQUENCE, AND ASSEMBLY TAG LEGENDS.
D. SEE FLOOR PLANS AND SECTIONS FOR ASSEMBLY
LOCATIONS.
E. SEE EXTERIOR DETAILS FOR ADDITIONAL INFORMATION.
F. SEE MATERIAL SCHEDULE FOR ADDITIONAL INFORMATION.
2 - FINISHES
A. SEE EXTERIOR ELEVATIONS FOR EXTERIOR FINISHES.
B. SEE MATERIAL SCHEDULE FOR FINISH INFORMATION.
3 - BUILDING ENVELOPE
A. SEE SPEC DIVISION 07 AND RELATED SPEC SECTIONS.
B. SEE A001 FOR BUILDING ENVELOPE LEGEND.
C. BARRIER / RETARDER CONTINUITY IS CRITICAL FOR THE
PERFORMANCE AND DURABILITY OF THE ASSEMBLY.
D. FLASHING, SEALING, AND INSULATING TRANSITION SPACES
ARE CRITICAL COMPONENTS OF WATER, AIR, AND THERMAL
BARRIER CONTINUITY.
E. WATER RESISTIVE BARRIER COMPONENTS MUST BE
INSTALLED IN A SHINGLE FASHION (WEATHER LAPPED),
FROM FOOTING TO ROOF, WITH SUFFICIENT OVERLAP AND
NO EXPOSED CORNERS. AVOID TRAPPING MOISTURE IN
TIGHT SPACES OR CREATING FLAT HORIZONTAL AREAS THAT
CAN COLLECT WATER.
F. NOTIFY ARCHITECT OF BUILDING ENVELOPE COMPONENT
SUBSTITUTIONS. SOME PRODUCTS CAN SIMULTANEOUSLY
ACT AS A WATER RESISTIVE BARRIER, AIR BARRIER, AND/ OR
A VAPOR RETARDER. SUBSTITUTING ASSEMBLY
COMPONENTS WITHOUT ARCHITECTS APPROVAL CAN
DRASTICALLY ALTER THE DURABILITY AND ENERGY
PERFORMANCE OF THE ASSEMBLY.
EXTERIOR ASSEMBLY NOTES
R-M2
ROOF - METAL STANDING SEAM
WHOLE ASSEMBLY THERMAL PERFORMANCE: N/A
INTERIOR
EXTERIOR
MTR-1
METAL DECK PER STRUCTURAL
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
A K
AF AL
T S
TA
E
O
49 TH
S
JAMES D. BARTLETT
No. A10413
R E
G
IS
T
ERED
PROFESSIONAL
ARC
H
IT
E C
T
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
30 NOV 2023
FDO ENTRY
CANOPIES
902304
AECC511
30-NOV-2023
11/30/2023 8:50:38 AM
JB
JAC
ARCHITECTURAL
SCHEDULES AND
TYPES - MATERIAL
A040
MATERIAL SCHEDULE
SPEC TYPE DESCRIPTION LOCATION
BASIS OF DESIGN REMARKS
TYPEMANUFACTURER MODEL COLOR
LOW
EMITTING MISCELLANEOUS
07 40 00 - THERMAL AND MOISTURE PROTECTION - ROOFING AND SIDING PANELS
07 41 13 MTR-1 METAL ROOF PANELS PER EXTERIOR ELEVATIONS METAL SALES MAGNA-LOC TO BE DETERMINED MTR-1
07 60 00 - THERMAL AND MOISTURE PROTECTION - FLASHING AND SHEET METAL
07 62 00 MTF-2 SHEET METAL FLASHING AND TRIM PER EXTERIOR ELEVATIONS METAL SALES ACCESSORIES AND TRIM TO BE DETERMINED MTF-2
MATERIAL INDEX
TYPE SPEC
MTF-2 07 62 00
MTR-1 07 41 13
A B C D E F G
A210
A210
A210
ARCHITECTURAL PLAN NOTES
A. SEE ARCHITECTURAL INFORMATION SHEETS FOR
ABBREVIATIONS, LEGENDS, SHEET SEQUENCE, AND
GENERAL NOTES FOR ARCHITECTURAL WORK.
B. SEE ARCHITECTURAL INFORMATION SHEETS FOR
ASSEMBLY TYPES.
C. ARCHITECTURAL OVERALL PLANS SHOW SPATIAL
RELATIONSHIPS FOR THE BUILDING AS A WHOLE.
CONSTRUCTION COMPONENTS MAY BE SIMPLIFIED OR
OMITTED FOR CLARITY.
D. ARCHITECTURAL ENLARGED PLANS SHOW FRAMING AND
LAYOUT INFORMATION NOT SHOWN ON PARTIAL PLANS.
E. SEE DOOR SCHEDULE FOR DOOR DETAIL CALLOUTS.
F. DIMENSION REFERENCE POINT CONVENTIONS.
A001
ARCHITECTURAL PLAN LEGEND
NO ARCHITECTURAL WORK THIS AREA
EXISTING WALL AND DOOR
B
2" / 1'-0"
A210
A670
A670
A670
119B
COLUMN BELOW
A210
A670
A670
A670
143B
COLUMN BELOW
D
A670
A210
A670
A670
145C
COLUMN BELOW
SHELF PER
STRUCTURAL
KEY PAD
COVERED
OUTLET
1ST FLOOR
0"
2" / 1'-0"
A670
A670
R-M2
SMOOTH
1ST FLOOR
0"
2" / 1'-0"
R-M2
A670
A670
SMOOTH
1ST FLOOR
0"
A670
A670
R-M2
SMOOTH
SHELF PER
STRUCTURAL
36"
2" / 1'-0"
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
A K
AF AL
T S
TA
E
O
49 TH
S
JAMES D. BARTLETT
No. A10413
R E
G
IS
T
ERED
PROFESSIONAL
ARC
H
IT
E C
T
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
30 NOV 2023
FDO ENTRY
CANOPIES
902304
AECC511
30-NOV-2023
11/30/2023 8:50:40 AM
JB
JAC
ARCHITECTURAL
PLANS - 1ST
FLOOR - OVERALL
A210
1" = 40'-0"A210
1 OVERALL PLAN - 1ST FLOOR
3/8" = 1'-0"A210
4 ENLARGED ROOF PLAN - CANOPY 3
3/8" = 1'-0"A210
3 ENLARGED ROOF PLAN - CANOPY 2
3/8" = 1'-0"A210
2 ENLARGED ROOF PLAN - CANOPY 1
3/8" = 1'-0"A210
7 EXTERIOR SECTION - CANOPY 3
3/8" = 1'-0"A210
6 EXTERIOR SECTION - CANOPY 2
3/8" = 1'-0"A210
5 EXTERIOR SECTION - CANOPY 1
EXTERIOR DETAIL NOTES
A. SEE FIRST SHEET IN SERIES FOR EXTERIOR DETAIL
NOTES.
PRE-FINISHED METAL FLASHING WITH DRIP
EDGE
FLASHING FASTENED TO SUPPORT PLATE AT
12" ON CENTER MAXIMUM
16 GAUGE SUPPORT PLATE FASTENED TO
DECKING AT 12" ON CENTER MAXIMUM
FIELD-FORM PANEL LEG 1 1/2" MINIMUM AND SEAL
TO SUPPORT PLATE WITH BUTYL SEALANT
FRAMING PER STRUCTURAL
R-M2
90 DEGREE COLD-FORMED STEEL ANGLE AS
REQUIRED TO SUPPORT RAKE FLASHING
16 GAUGE SUPPORT PLATE FASTENED TO
DECKING AT 12" ON CENTER MAXIMUM
SEE STRUCTURAL FOR FRAMING
STRUCT
GAP PER
R-M2
FASTEN TO SMOOTH
FACE CMU BLOCK
REGLET AND SEALANT
PRE-FINISHED METAL
FLASHING
S M
O O
T H
R O
U G
H
PRE-FINISHED METAL
FLASHING WITH DRIP EDGE
FIELD NOTCH AND HEM PANEL
1 1/2" MINIMUM
FRAMING PER STRUCTURAL
R-M2
OFFSET CLEAT FASTENED THROUGH
METAL FLASHING TO METAL DECK
OFFSET CLIP PER METAL
PANEL MANUFACTURER
PRE-FINISHED METAL FLASHING WITH
DRIP EDGE AND CONTINUOUS CLEAT
Z CLOSURE WITH BUTYL SEALANT
TAPE PER MANUF. FASTENED
THROUGH METAL PANEL TO
SUPPORT PLATE 12" OC MAX
FRAMING PER
STRUCTURAL
R-M2
FASTEN METAL FLASHING TO Z
CLOSURE AT 12" OC MAXIMUM
16 GA SUPPORT PLATE PER
METAL PANEL MANUF.
FASTENED TO METAL DECK
AT 12" OC MAX
OFFSET CLIP PER PANEL
MANUFACTURER
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
A K
AF AL
T S
TA
E
O
49 TH
S
JAMES D. BARTLETT
No. A10413
R E
G
IS
T
ERED
PROFESSIONAL
ARC
H
IT
E C
T
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
30 NOV 2023
FDO ENTRY
CANOPIES
902304
AECC511
30-NOV-2023
11/30/2023 8:50:41 AM
JB
JAC
ARCHITECTURAL
DETAILS -
EXTERIOR ROOF
AND CANOPY
A670
BUILDING ENVELOPE INDEX
TYPE BASIS OF DESIGN - PER MATERIAL SCHEDULE
BE-7 SLOPE SHIELD PLUS SA
3" = 1'-0"A670
1 EXTERIOR DETAIL - RAKE FLASHING
3" = 1'-0"A670
2 EXTERIOR DETAIL - WALL CONNECTION FLASHING
3" = 1'-0"A670
3 EXTERIOR DETAIL - LOW EAVE FLASHING
3" = 1'-0"A670
4 EXTERIOR DETAIL - HIGH EAVE FLASHING
C. CONCRETE
1. GENERAL:
A. ALL CAST-IN-PLACE CONCRETE SHALL HAVE THE FOLLOWING PROPERTIES:
a. A MINIMUM 28-DAY COMPRESSIVE STRENGTH (f'c) OF 4500 PSI.
b. MAXIMUM AGGREGATE SIZE OF 3/4".
c. CONCRETE SHALL CONTAIN 6% ±1.5% AIR ENTRAINMENT BY VOLUME.
d. MAXIMUM WATER TO CEMENT RATIO OF 0.45.
e. MAXIMUM SLUMP OF 8" AT TRUCK CHUTE DISCHARGE POINT.
f. EXTERIOR CONCRETE TO BE BROOM FINISHED.
B. CONCRETE SHALL BE TESTED FOR TEMPERATURE. SLUMP, AIR CONTENT AND STRENGTH
VERIFICATION IN ACCORDANCE WITH ASTM C 1064, ASTM C 143, ASTM C321, ASTM C31 & C39
RESPECTIVELY. TESTING FREQUENCY SHALL BE AS FOLLOWS:
a. 0-25 CY PER DAY: ONE TEST.
C. CONCRETE SHALL MEET ALL REQUIREMENTS OF ACI 301 SPECIFICATION FOR STRUCTURAL
CONCRETE BUILDINGS.
D. ALL PERMANENTLY EXPOSED CONCRETE EDGES TO BE CHAMFERED 3/4", UNO
E. DIMENSIONS SHOWN ON DRAWING SHALL SUPERCEDE THOSE SHOWN ON GENERAL NOTES.
2. REINFORCING:
A. REINFORCING BARS SHALL CONFORM TO ASTM A615 GRADE 60.
B. DETAIL REINFORCING BARS IN ACCORDANCE WITH THE ACI DETAILING MANUAL AND THE ACI
BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, LATEST EDITION.PROVIDE ALL
ACCESSORIES NECESSARY TO SUPPORT REINFORCING AT POSITIONS SHOWN ON THE DRAWINGS.
PROVIDE SUFFICIENT TIE BARS TO SUPPORT ALL REINFORCING.
C. CLEAR DISTANCE BETWEEN REINFORCING SHALL NOT BE LESS THAN 1.5 BAR DIAMETERS NOR LESS
THAN 1 1/2''.
D. PROVIDE REINFORCEMENT COVER AS FOLLOWS (ACI 7.7), UNLESS NOTED OTHERWISE ON
DRAWINGS:
a. CONCRETE POURED AGAINST EARTH ............................ 3" ±3/8"
b. CONCRETE EXPOSED TO EARTH OR WEATHER............. 1 1/2" ±3/8"
3. EMBEDDED ANCHORS:
A. ANCHOR BOLTS FOR STEEL COLUMNS SHALL BE ASTM F1554 GRADE 36 HEAVY HEX HEAD UNO.
ANCHOR BOLTS ARE TO BE ACCURATELY PLACED WITH SETTING TEMPLATES.
B. BOLTS SHALL EXTEND PAST FACE OF NUT BY AT LEAST ONE FULL THREAD.
4. COLD-WEATHER CONCRETE:
COLD WEATHER CONDITIONS EXIST WHEN AIR TEMPERATURE HAS FALLEN TO OR IS EXPECTED TO FALL BELOW 40°F DURING CONCRETE PLACEMENT OR STANDARD PROTECTION PERIOD OR AT ANYTIME DURING THE PROTECTION PERIOD. PROTECTION PERIOD DURATION AS OUTLINED BLOW. COMPLY WITH ACI 306.1, STANDARD SPECIFICATION FOR COLD WEATHER CONCRETING AND AS FOLLOWS:
A. SUBGRADE TO BE THAWED PRIOR TO CONCRETE PLACEMENT.
B. DO NOT PLACE CONCRETE ON FROZEN MATERIALS, ICE, SNOW, OR STANDING WATER.
C. DO NOT USE CALCIUM CHLORIDE, SALT, OR OTHER MATERIALS CONTAINING ANTIFREEZE AGENTS OR
CHEMICAL ACCELERATORS UNLESS OTHERWISE SPECIFIED AND APPROVED IN MIXTURE DESIGNS.
D. DO NOT USE FROZEN MATERIALS OR MATERIALS CONTAINING ICE OR SNOW IN THE CONCRETE
MIXTURE.
E. ALL MASSIVE EMBEDMENTS (STRUCTURAL STEEL EMBEDMENTS IN CONTACT WITH CONCRETE WITH
A CROSS-SECTIONAL AREA GREATER THAN 4 IN2) MUST BE ABOVE FREEZING BEFORE CONCRETE
PLACEMENT.
F. PROTECT CONCRETE DURING PLACEMENT AND THROUGHOUT THE PROTECTION PERIOD:
a. PROTECTION PERIOD DURATION IS THE MOST RESTRICTIVE OF THE FOLLOWING:
• 3 DAYS
• 5 DAYS FOR FOUNDATIONS AND THICKENED EDGE SLABS.
• UNTIL CONCRETE HAS REACHED A MINIMUM IN-PLACE COMPRESSIVE STRENGTH OF
3500 PSI.
b. MAINTAIN A MINIMUM CONCRETE TEMPERATURE OF 55°F DURING THE PROTECTION PERIOD.
c. DO NOT REMOVE SHORING OR FORMWORK DURING THE PROTECTION PERIOD.
d. DO NOT OVERHEAT AND DRY CONCRETE SURFACES DURING PROTECTION.
e. RECORD CONCRETE TEMPERATURE AT REGULAR TIME INTERVALS AT LEAST TWICE EVERY
24 HOURS.
f. PROTECTION TERMINATION REQUIREMENTS:
• FOLLOWING THE PROTECTION PERIOD GRADUALLY COOL CONCRETE SURFACE BY
THE FOLLOWING MAXIMUM COOLING RATE UNTIL THE CONCRETE SURFACE
TEMPERATURE IS WITHIN 20°F OF THE AMBIENT AIR TEMPERATURE.
1. SECTION THICKNESS LESS THAN 12".............................. 50°F PER 24 HOURS
2. SECTION THICKNESS 12" TO 36" ......................................40°F PER 24 HOURS
3. SECTION THICKNESS 36" TO 72" ......................................30°F PER 24 HOURS
4. SECTION THICKNESS GREATER THAN 72" .....................20°F PER 24 HOURS
G. FOR FLATWORK, USE LOW SLUMP CONCRETE TO MITIGATE PROBLEMS DUE TO BLEED WATER.
H. ALL WATER ADDED TO THE CONCRETE MIX SHALL NOT BE LESS THAN 55°F.
GENERAL STRUCTURAL NOTES
A. DESIGN CRITERIA
1. BUILDING CODE........................................................................................ 2021 IBC (INTERNATIONAL BUILDING CODE)
GOVERNING JURISDICTION.................................................................... STATE OF ALASKA
2. DEAD LOADS
ROOF SUPERIMPOSED DEAD LOAD........................................ 4 PSF
3. SNOW LOADS
GROUND SNOW LOAD Pg ........................................................ 60 PSF FLAT ROOF SNOW LOAD Pf .................................................... 50.4 PSF SNOW EXPOSURE FACTOR Ce .............................................. 1.0
SNOW LOAD IMPORTANCE FACTOR I .................................... 1.0
THERMAL FACTOR Ct .............................................................. 1.2
4. WIND LOADS
ULTIMATE DESIGN WIND SPEED VULT..................................... 110 MPH
NOMINAL DESIGN WIND SPEED VASD...................................... 85 MPH
RISK CATEGORY ....................................................................... II EXPOSURE ................................................................................. B
ROOFING DESIGN UPLIFT PRESSURE (ULT).......................... 25 PSF
5. SEISMIC LOADS
SS ............................................................................................... 0.996 S1 ............................................................................................... 0.38 SDS ............................................................................................. 0.80 SD1 ............................................................................................. N/A CS................................................................................................. 0.23 R................................................................................................... 3.5 SITE CLASS................................................................................. D (DEFAULT)
SEISMIC DESIGN CATEGORY.................................................. D
RISK CATEGORY ....................................................................... II IMPORTANCE FACTOR............................................................. 1.0 BASIC SEISMIC FORCE RESISTING SYSTEM........................ STEEL ORDINARY MOMENT FRAMES DESIGN BASE SHEAR............................................................... 0.2 KIPS (EA CANOPY) ANALYSIS PROCEDURE........................................................... EQUIVALENT LATERAL FORCE METHOD
B. FOUNDATION
1. FOUNDATION DESIGN IS BASED ON IBC TABLE 1806.2 PRESUMPTIVE LOAD-BEARING VALUES.
2. ALLOWABLE SOIL BEARING PRESSURE: 1500 PSF
D. STRUCTURAL STEEL
1. SQUARE/RECTANGULAR HOLLOW STRUCTURAL SECTIONS (HSS) SHALL CONFORM TO ASTM A500 GRADE C
(Fy = 50 KSI).
2. PLATES SHALL BE ASTM A36 (Fy = 36 KSI).
3. ALL STRUCTURAL STEEL SHALL BE DETAILED AND FABRICATED IN ACCORDANCE WITH THE LATEST EDITION
OF THE AISC STEEL CONSTRUCTION MANUAL.
4. NON-SHRINK GROUT SHALL BE 5,000 PSI DAYTON SUPERIOR 1107 ADVANTAGE GROUT OR EQUIVALENT.
5. BOLTED CONNECTIONS SHALL BE ACCOMPLISHED WITH TENSION-CONTROLLED HIGH-STRENGTH BOLTS
CONFORMING TO ASTM F3125 GRADE F1852 (A325-TC) IN STANDARD HOLES UNLESS NOTED OTHERWISE.
6. ALL BOLTED CONNECTIONS SHALL BE PRE-TENSIONED UNLESS NOTED OTHERWISE.
7. WELDING SHALL BE PERFORMED WITH E70XX ELECTRODES. WELDING SHALL BE DONE BY QUALIFIED
WELDERS AND SHALL CONFORM TO THE AWS D1.1 STRUCTURAL WELDING CODE-STEEL, LATEST EDITION.
ALL WELDS ARE INTENDED TO BE CONTINUOUS UNLESS NOTED OTHERWISE.
8. FIELD WELDS NOTED THROUGHOUT THE CONTRACT DOCUMENTS ARE ACCEPTABLE LOCATIONS FOR FIELD
WELDING AT THE CONTRACTOR'S OPTION. FIELD WELDS MAY BE PERFORMED IN THE SHOP.
E. STEEL DECK
1. STEEL DECK INSTALLATION SHALL COMPLY WITH ALL MANUFACTURER'S REQUIREMENTS AND THE STEEL
DECK INSTITUTE'S SPECIFICATIONS FOR FABRICATION AND ERECTION.
2. WELDING OF STEEL DECK IS TO BE DONE BY CERTIFIED WELDERS EXPERIENCED IN WELDING LIGHT GAUGE
STEEL DECK.
F. GENERAL
1. CONTRACTOR IS TO FIELD VERIFY ALL DIMENSIONS AND ELEVATIONS TO MATCH NEW CONSTRUCTION TO
EXISTING CONSTRUCTION.
2. THE STRUCTURAL CONSTRUCTION DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT
INDICATE THE METHOD OR SEQUENCE OF CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR AND PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION.
SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO: BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC. THE STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR THE CONTRACTOR'S MEANS, METHODS, TECHNIQUES, SEQUENCES FOR PROCEDURE OF CONSTRUCTION, OR THE SAFETY PRECAUTIONS AND THE PROGRAMS INCIDENT THERETO (NOR SHALL OBSERVATION VISITS TO
THE SITE INCLUDE INSPECTION OF THESE ITEMS).
3. STRUCTURAL DRAWINGS ARE A PORTION OF THE CONTRACT DOCUMENTS AND ARE INTENDED TO BE USED
WITH ARCHITECTURA DRAWINGS. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE
REQUIREMENTS FROM ARCHITECURAL DOCUMENTS INTO THEIR SHOP DRAWINGS AND WORK.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN AND IMPLEMENTATION OF ALL SCAFFOLDING, BRACING AND SHORING.
5. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON FRAMED CONSTRUCTION. LOADS SHALL
NOT EXCEED THE DESIGN SNOW LOAD.
6. DO NOT USE SCALED DIMENSIONS TAKEN FROM STRUCTURAL DRAWINGS. CONTACT STRUCTURAL
ENGINEER IF DIMENSIONAL INFORMATION IS MISSING.
7. ANY ENGINEERING DESIGN PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW SHALL BEAR THE SEAL OF
A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF ALASKA.
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
30 NOV 2023
FDO ENTRY
CANOPIES
902304
AECC511
11/30/2023 9:09:30 AM
PAJ
PAJ
GENERAL
STRUCTURAL
NOTES
S001
SPECIAL INSPECTIONS
WORK IS CONSIDERED CONSTRUCTION OF A MINOR NATURE PER
IBC 1701.2 EXCEPTION 1. SPECIAL INSPECTIONS ARE NOT REQUIRED.
A K
AF AL
T S
T A
E O
49 TH
S
Peter A. Jacobsen
No. SE14544
R E
G
IS
T
ERED
STRUCTURAL
EN
G
IN
E E
R
30-NOV-2023
A B C D E F G
CANOPY 1
CANOPY 3
CANOPY 2
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
30 NOV 2023
FDO ENTRY
CANOPIES
902304
AECC511
11/30/2023 9:09:32 AM
PAJ
PAJ
CANOPY
LOCATION PLAN
S100 3/32" = 1'-0"S100
1 CANOPY LOCATION PLAN
A K
AF AL
T S
T A
E O
49 TH
S
Peter A. Jacobsen
No. SE14544
R E
G
IS
T
ERED
STRUCTURAL
EN
G
IN
E E
S300
S300
KEY PAD ABOVE
EXTERIOR LIGHT
LOCATE AND AVOID/
RELOCATE BURIED
POWER AS REQUIRED
CANOPY 2 FOUNDATION PLAN
H S S3X
3X 3/
F
FACE OF (E) CMU
WALL AND FDN
3' - 4" (FIELD VERIFY)
H
SS
3X 3X
3/
8"
5' - 1"
(E) FOOTING BELOW
H
SS
3X 3X
3/
H
SS
3X 3X
3/
CANOPY 1 FOUNDATION PLAN
S300
EXTERIOR LIGHT
LOCATE AND AVOID/
RELOCATE BURIED
POWER AS REQUIRED
D
(E) FOOTING BELOW
(F
IE
L D
V E
R
IF
Y
S300
S300
KEY PAD ABOVE
CANOPY 3 FOUNDATION PLAN
H
SS
3X 3X
3/
H
SS
3X 3X
3/
H S S3X
3X 3/
H S S3X
3X 3/
B
8"
FACE OF (E) CMU
WALL AND FDN
3' - 4" (FIELD VERIFY) 6' - 1"
(F
IE
L D
V E
R
IF
Y
(E) FOOTING BELOW
CANOPY 2 FRAMING PLAN CANOPY 3 FRAMING PLAN
H S
S X
X
/1
H S
S X
X
/1
2"
/2
10" 4 1/2"5' - 1"
CANOPY 1 FRAMING PLAN
H S
S X
X
/1
H S
S X
X
/1
1 1/2" 16 GA TYPE B
STEEL ROOF DECK
FASTEN TO SUPPORTS
W/ #12 SCREWS EA FLUTE
BUTTON PUNCH SIDE
SEAMS @ 12" OC
4 1/2" 4 1/2"
/2
5' - 9"
S300
HSS3X3X3/16
2" 4 1/2"
HSS3X3X3/16
/2
10" 6' - 1"
FACE OF (E) CMU
WALL AND FDN
(E) SIDEWALK EDGE
(E) SIDEWALK EDGE
(E) SIDEWALK EDGE
S300
S300
S300
S300
S300
S300
S300
1 1/2" 16 GA TYPE B
STEEL ROOF DECK
FASTEN TO SUPPORTS
W/ #12 SCREWS EA FLUTE
BUTTON PUNCH SIDE
SEAMS @ 12" OC
1 1/2" 16 GA TYPE B
STEEL ROOF DECK
FASTEN TO SUPPORTS
W/ #12 SCREWS EA FLUTE
BUTTON PUNCH SIDE
SEAMS @ 12" OC
SIM
S300
SIM
HSS3X3X1/4
HSS3X3X1/4
HSS3X3X1/4
HSS3X3X1/4
H S
S X
X
/4
H S
S X
X
/4
5' - 9"
H
SS
3X 3X
3/
H
SS
3X 3X
3/
KEY PAD ABOVE
GUTTER DOWNSPOUT BELOW
CONFIGURE FOOTING TO CLEAR
H
SS
3X 3X
3/
H
SS
3X 3X
3/
S300
1' - 6"
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
30 NOV 2023
FDO ENTRY
CANOPIES
902304
AECC511
11/30/2023 9:09:32 AM
PAJ
PAJ
STRUCTURAL
PLANS
S200 1/2" = 1'-0"S200
1 STRUCTURAL PLANS
A K
AF AL
T S
T A
E O
49 TH
S
Peter A. Jacobsen
No. SE14544
R E
G
IS
T
ERED
STRUCTURAL
EN
G
IN
E E
1' - 6"
M
IN
(8) #5 VERT
#4 CLOSED TIES W/ 135
DEG HOOKS AS SHOWN
@ 8" OC W/ (2) TIES
WITHIN TOP 5" OF
FOUNDATION
1" CHAMFER
T.O. FDN TO MATCH T.O. SLAB
ADJACENT TO BUILDING
8" MIN PEA
GRAVEL
COMPACTED STRUCTURAL FILL
AROUND CONCRETE PIER
WRAP FOUNDATION W/ (2) LAYERS
MIN POLY SHEETING
ø 1' - 2
S300
3/4X6X6" BASE PLATE
ON 1" NON-SHRINK GROUT
W/ (4) 5/8"Ø ANCHOR BOLTS
EMBEDDED AS SHOWN
5/16
2"
TOP OF STEEL
EL = 8'-6"
10" 4 1/2"
8'-1" CANOPY 1
6' - 1" CANOPIES 2 AND 3
3/8" CONT PLATE (TYP)
3/16
3/16
ARCH
EXPOSED, TYP
TOP OF STEEL
EL = VARIES
1' - 0"
2"
4 1/2"5' - 1"
FILL GAP, TYP
3/16
ARCH
EXPOSED, TYP
3/8X7X7" BEARING
PLATE (TYP)
3/8X7X7" COLUMN
CAP PLATE (TYP)
1" TYP (4) 5/8"Ø BOLTS
3/16
3/16
T.O. FDN TO MATCH
SIDEWALK
8"
(E) FINISHED FLOOR
REFERENCE EL = 0'-0"
S300
SAW CUT SLAB (N/A @ SIM)
(2) #3X1'-0" ADHESIVE DOWELS EA SIDE
OF FOOTING EMBEDDED 3" IN (E)
SIDEWALK AND (E) CMU WALL
FINISH FOOTING SURFACE TO
MATCH (E) SIDEWALK
(2) #4 EA WAY
1' - 4" SQUARE
/2
L5X5X3/8X0'-5"
CHAMFER EDGES
FILL GAP
ARCH
EXPOSED
NOTE: SEE ARCH DRAWINGS
FOR SHELF LOCATION
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
30 NOV 2023
FDO ENTRY
CANOPIES
902304
AECC511
11/30/2023 9:09:33 AM
PAJ
PAJ
STRUCTURAL
DETAILS
S300
1" = 1'-0"S300
1 14" SONOTUBE FOUNDATION
1" = 1'-0"S300
4 BASEPLATE DETAIL
1" = 1'-0"S300
5 CANOPY ROOF FRAMING SECTION 1
1" = 1'-0"S300
6 CANOPY ROOF FRAMING SECTION 2
1" = 1'-0"S300
2 FOUNDATION ADJACENT TO EXISTING BUILDING
1" = 1'-0"S300
3 STEEL SHELF
A K
AF AL
T S
T A
E O
49 TH
S
Peter A. Jacobsen
No. SE14544
R E
G
IS
T
ERED
STRUCTURAL
EN
G
IN
E E
| G010 - GENERAL INFORMATION |
| A001 - ARCHITECTURAL INFORMATION |
| A040 - ARCHITECTURAL SCHEDULES AND TYPES - MATERIAL |
| A210 - ARCHITECTURAL PLANS - 1ST FLOOR - OVERALL |
| A670 - ARCHITECTURAL DETAILS - EXTERIOR ROOF AND CANOPY |
| S001 - GENERAL STRUCTURAL NOTES |
| S100 - CANOPY LOCATION PLAN |
| S200 - STRUCTURAL PLANS |
| S300 - STRUCTURAL DETAILS |