The document clarifies contractor responsibilities for the canopy installation project. The contractor is responsible for verifying all existing utilities, lights, and power locations; however, the contractor is not responsible for furnishing or installing new canopy-mounted lighting or electrical devices. If existing exterior lights or buried power must be relocated to accommodate column footers, the contractor shall notify the contracting officer for resolution. Existing keypads will not require relocation. For the gutter downspout at Canopy 1 locations, which is identified as a faux downspout, the contractor must remove it if the canopy structure creates a conflict, then patch, repair, and repaint the existing block to match. The gutter downspout near Canopy 2 is not affected by the work. Additionally, Canopies 1, 2, and 3 serve as emergency exits during normal business hours; the contractor must verify alternate egress paths for building occupants and provide interior and directional signage. Work outside normal hours is permitted when requested in writing and approved based on the nature of the work and government staff availability. The government will provide general utility routing information via Sheet ES-1 attached to the amendment but does not provide detailed as-built or utility locate information. Unknown conditions affecting the work require notification to the contracting officer for resolution.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BLM Alaska - 140L6326Q0006 – Amendment 02
FDO Exterior Door Canopies
Questions & Answers
1. Question: Are existing exterior light fixtures intended to remain in place, be protected, relocated, or replaced under this contract?
Answer: Existing exterior light and buried power may be relocated, if necessary, as required for column footers. The Contractor shall verify lights and power locations and utility locations. Contractor shall notify the contracting officer to resolve.
2. Question: Is the contractor responsible for furnishing and installing any new canopy/awning-mounted lighting or electrical devices?
Answer: No.
3. Question: Is electrical relocation work (conduit, conductors, keypad relocation, lighting relocation, buried power modifications, etc.) part of the contractor’s base scope, or is the contractor only responsible for locating and avoiding existing utilities?
Answer: Contractor shall verify all existing utilities. See Answer to Question 1 above.
Existing Keypads will not require to be relocated.
4. Question: If electrical relocation is required, will Government direction/design be provided?
Answer: See Answer to Question 1 above. Existing Keypads will not require to be relocated.
5. Question: The drawings indicate an existing gutter/downspout condition near Canopy #2 with note to configure footing accordingly. Please clarify whether the contractor is expected to relocate, modify, reconnect, or otherwise alter existing gutter/downspout components as part of the base bid, or if the intent is only to avoid interference during footing placement.
Answer: Gutter downspout at canopy 1 locations is a faux downspout. If the canopy structure is in conflict the contractor will remove the existing spout, the existing block will be patched, repaired and repainted to match existing. The gutter downspout near Canopy 2 is not affected by the work.
6. Question: Please confirm whether any restrictions, phasing requirements, access maintenance requirements, or after-hours work requirements apply to installation at active building entrances during construction.
BLM Alaska - 140L6326Q0006 – Amendment 02
Answer: The canopy 1, 2 and 3 are emergency exits for the facility during normal business hours. Contractor to verify alternate paths of egress for building occupants for exit path under construction. Interior signage and directional signage to the employees will be provided by contractor. The contract allows for work outside of normal working hours, when requested in writing ahead of time. Approval of the request is depending on the nature of the work at that time and if needed, government staff availability.
7. Question: Please confirm whether any known underground utility information, as-built information, or utility locates will be provided by the Government, particularly at canopy footing locations where excavation is required.
Answer: See Sheet ES-1 attached to this amendment. Drawing indicates general routing of utilities.
8. Question: Should it be discovered that the light fixtures need to be moved, will this be handled via a change order?
Answer: If an unknown condition is found affecting the work, and additional work is needed, notify the contracting officer for resolution.
9. Question: Should it be discovered that the keypads need to be moved, will this be handled via a change order?
Answer: Existing Keypads will not require to be relocated.