B_-_EA25WBM048_SPEC_Standards_Implementation_Guide_0.1.0_DRAFT.pdf
PDF 2 MB Posted
- Solicitation number
- RFP-DS-0149
- Issued by
- Los Angeles County, California
About this file
This is a Standards Implementation Guide prepared by Enterprise Automation for West Basin Municipal Water District located in Carson, California, detailing technical specifications and programming standards for a Process Control System (PCS). The document establishes standardized practices for implementing Derived Function Blocks (DFBs), Derived Data Types (DDTs), and System Platform Templates across PLC programming and HMI graphical interfaces. The guide covers 30 different DFB modules for controlling various devices including analog inputs and outputs, valves, motors, chemical pacing systems, discrete inputs and outputs, controllers, and communication modules. The implementation strategy emphasizes repeatable behavior across multiple projects through unified back-end PLC programming and front-end graphical interface standards, with detailed specifications for each device module including input/output parameters, alarm configurations, override functions, and operational modes for both remote and local equipment operation.
The document provides comprehensive technical specifications for device functionality, including analog alarm calculations with deadband and delay parameters, scaling formulas for input/output conversions, smoothing algorithms, and interlock condition management. Additional standards address communication protocols via OPC UA and NOC modules, common graphic symbols for HMI displays with customizable properties, and faceplate design guidelines. The guide is intended for use in conjunction with supplemental PLC Style Guide, HMI Style Guide, and Standards Operating Guide documents, all version 1.0.0. This Standards Implementation Guide version 0.1.0 became effective August 11, 2026, and was authored by Adrian Leon with review by Kaylee Halliday and Alex Coker. The document supports the Torrance Refinery Water Recycling Plant Programmable Logic Controller Replacements project being procured by West Basin Municipal Water District.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
West Basin Municipal Water District 17140 Avalon Blvd Carson, CA 90746 Phone: (310) 217-2411 www.WestBasinCA.gov
PCS Standards
Implementation Guide v.0.1.0
West Basin Municipal Water District
Document Standards Implementation Guide
Revision Number 0.1.0
Effective Date 8/11/2026
Author Adrian Leon
Reviewed by Kaylee Halliday, Alex Coker
Prepared By:
9050 Irvine Center Drive Irvine, CA 92618
(949) 769-6000 www.eaintegrator.com
Standards Implementation Guide v0.1.0 EA Project Number: EA25WBM048
17140 Avalon Blvd, Carson, CA 90746 Revision: 0.1.0 Tel 310-217-2411 Effective Date: 8/11/2026 www.WestBasinCA.Gov Page Number: 2 of 293
History Revision Date Description of Change Author Reviewed
0.1.0 8/11/2026 Draft release for client review AL KH, AC
Table of Contents 1 Overview
1.1 Purpose
1.2 Acronyms and Terms
1.3 Supplemental Documents
1.3.1 HMI Style Guide
1.3.2 PLC Style Guide
1.3.3 Standards Operating Guide
2 Implementation Strategy 3 Standard Operating Modes
3.1 Remote Operation
3.1.1 PCS Auto
3.1.2 PCS Manual
3.2 Local Operation
4 Device Standards
4.1 Derived Function Blocks (DFB)
4.1.1 DFB_AnalogAlarm
4.1.2 DFB_AnalogInput
4.1.3 DFB_AnalogOutput
4.1.4 DFB_AnalogRamp
4.1.5 DFB_AnalogValve
4.1.6 DFB_ChemicalPacing
4.1.7 DFB_ClockSync
4.1.8 DFB_CommRead
4.1.9 DFB_CommWrite
4.1.10 DFB_Conditions
4.1.11 DFB_DiscreteAlarm
4.1.12 DFB_DiscreteInput
4.1.13 DFB_DiscreteOutput
4.1.14 DFB_DiscretePOSValve
4.1.15 DFB_DiscretePulse
4.1.16 DFB_DiscreteValve
4.1.17 DFB_FixedMotor
4.1.18 DFB_FlowTotalizer
4.1.19 DFB_Intrusion
4.1.20 DFB_LeadLagController
4.1.21 DFB_PIDController
4.1.22 DFB_PulseTotalizer
www.WestBasinCA.Gov Page Number: 3 of 293
4.1.23 DFB_PWMController
4.1.24 DFB_RedundantTransmitter
4.1.25 DFB_RuntimeTotalizer
4.1.26 DFB_SeqAction
4.1.27 DFB_SeqCommand
4.1.28 DFB_SeqProgress
4.1.29 DFB_VFDMotor
4.1.30 DFB_ViewMotor
4.1.31 DFB_ViewValve
4.1.32 ClockSync (Section)
4.1.33 HotStandbyMgmt (Section)
4.1.34 PLCStatus (Section)
4.2 Derived Data Types (DDT)
4.2.1 DDT_AnalogInput
4.2.2 DDT_AnalogOutput
4.2.3 DDT_AnalogValve
4.2.4 DDT_ChemicalPacing
4.2.5 DDT_ClockSync
4.2.6 DDT_CommRead
4.2.7 DDT_CommWrite
4.2.8 DDT_Conditions
4.2.9 DDT_DiscreteInput
4.2.10 DDT_DiscreteOutput
4.2.11 DDT_DiscretePOSValve
4.2.12 DDT_DiscreteValve
4.2.13 DDT_FixedMotor
4.2.14 DDT_Intrusion
4.2.15 DDT_LeadLagController
4.2.16 DDT_PIDController
4.2.17 DDT_PLCStatus
4.2.18 DDT_PWMController
4.2.19 DDT_RedundantTransmitter
4.2.20 DDT_Sequence
4.2.21 DDT_Totalizer
4.2.22 DDT_VFDMotor
4.3 System Platform Templates
4.3.1 $AnalogInput
4.3.2 $AnalogModule
4.3.3 $AnalogOutput
4.3.4 $AnalogValve
4.3.5 $ChemicalPacing
4.3.6 $ClockSync
4.3.7 $Conditions
4.3.8 $DigitalModule
4.3.9 $DiscreteInput
4.3.10 $DiscreteOutput
4.3.11 $DiscretePOSValve www.WestBasinCA.Gov Page Number: 4 of 293
4.3.12 $DiscreteValve
4.3.13 $FixedMotor
4.3.14 $Intrusion
4.3.15 $LeadLagController
4.3.16 $PIDController
4.3.17 $PLCStatus
4.3.18 $PulseTotalizer
4.3.19 $PWMController
4.3.20 $RuntimeTotalizer
4.3.21 $RedundantTransmitter
4.3.22 $Sequence
4.3.23 $VFDMotor 5 Communication Standards
5.1 OPC UA Module
5.1.1 Module Settings
5.1.2 PLC Setup
5.1.3 System Platform Setup
5.2 NOC Module
5.2.1 Module Settings
5.2.2 PLC Setup
5.2.3 System Platform Setup
5.3 Monitoring Requirements
5.3.1 Communication Failure
6 Common Graphics
6.1 cmButton
6.1.1 Symbol Wizard Options
6.1.2 Custom Properties
6.2 cmBarChart
6.2.1 Symbol Wizard Options
6.2.2 Custom Properties
6.3 cmPieChart
6.3.1 Symbol Wizard Options
6.3.2 Custom Properties
6.4 cmStackedBars
6.4.1 Custom Properties
6.5 cmSetpoint
6.5.1 Symbol Wizard Options
6.5.2 Custom Properties
6.6 cmDisplayDiscrete
6.6.1 Symbol Wizard Options
6.6.2 Custom Properties
6.7 cmDisplayString
6.7.1 Symbol Wizard Options
6.7.2 Custom Properties
6.8 cmDisplayValue
6.8.1 Symbol Wizard Options
www.WestBasinCA.Gov Page Number: 5 of 293
6.8.2 Custom Properties
6.9 cmDisplayAlarm
6.9.1 Symbol Wizard Options
6.9.2 Custom Properties
6.10 cmFillBar
6.10.1 Symbol Wizard Options
6.10.2 Custom Properties
6.11 cmMeter
6.11.1 Symbol Wizard Options
6.11.2 Custom Properties
6.12 cmMultiAlarm
6.12.1 Symbol Wizard Options
6.12.2 Custom Properties
6.13 cmTrend
6.13.1 Symbol Wizard Options
6.13.2 Custom Properties
6.14 cmPolarStar
6.14.1 Symbol Wizard Options
6.14.2 Custom Properties
6.15 cmNavLink
6.15.1 Symbol Wizard Options
6.15.2 Custom Properties
6.16 cmDiscreteChannel
6.16.1 Symbol Wizard Options
6.16.2 Custom Properties
6.17 cmAnalogChannel
6.17.1 Symbol Wizard Options
6.17.2 Custom Properties
7 Creating New Faceplates
7.1 Faceplate Header
7.1.1 Configure the major heading (dark grey)
7.1.2 Configure the minor heading (light grey)
7.2 Main Content
7.2.1 Configure the main content box
7.3 Tabbed Content
7.3.1 Configure the tabbed content box
7.3.2 Configure the alarm displays with acknowledgement
www.WestBasinCA.Gov Page Number: 6 of 293
1 Overview
1.1 Purpose
This specification explains how to implement the PCS device standards developed for West Basin Municipal Water District (the District) by Enterprise Automation. This document outlines the steps to use these standards within PLC programming, and the steps to implement these standards into a System Platform galaxy. This document will also explain any optional configurations that can be changed to suit the needs of individual projects. These standards are intended for use with a suite of standards documentation that define PLC and HMI practices (see Supplemental Documents).
1.2 Acronyms and Terms
For the remainder of the document the following acronyms will be used.
Term Description
WBMWD, the District “West Basin Municipal Water District”
EA “Enterprise Automation” (Integrator)
HMI “Human Machine Interface”: The screens and graphics that Operators use to monitor and control an automated process
PLC
“Programmable Logic Controller”: The industrially hardened controllers that interface with the instrumentation, valves, pumps, etc., and control the automated processes (or simply collect information from any non-automated systems).
Device A term encompassing both the repeatable PLC code and the PCS integration (graphics, tags, historization, etc.) that represent a standardized unit of the system, i.e., “the Analog Valve device”
PCS Process Control System
DFB “Derived Function Block”: PLC code module for EcoStruxure Control Expert
DDT “Derived Data Type” www.WestBasinCA.Gov Page Number: 7 of 293
1.3 Supplemental Documents
1.3.1 HMI Style Guide
SPEC HMI Style Guide 1.0.0
1.3.2 PLC Style Guide
SPEC PLC Style Guide 1.0.0
1.3.3 Standards Operating Guide
SPEC Standards Operating Guide 1.0.0 www.WestBasinCA.Gov Page Number: 8 of 293
2 Implementation Strategy This document outlines the usage of pre-built Derived Function Blocks (DFB) with pre-built Derived Data Types (DDT) and System Platform Templates. Used in conjunction, these three elements produce standardized behavior for the control of a specific device.
Each DFB within this guide defines the specific behavior (logic) of a device. The DFB is responsible for handling user-input values from HMI, calculating changes of state/mode, and calculating alarms.
More generally, the DFB is responsible for determining the standard behavior of the device.
Each DDT provides a standard structure for holding data about the device. DDTs within this guide are designed for use with one or more standard DFBs. References in the PLC programming should not be made directly to the pins of the DFB, but instead to the equivalent DDT elements. The DDT also serves as a common interface for the System Platform template to read and write.
Each System Platform template provides the HMI-side handling of the device. The template defines alarm priorities, historization settings, and scripting for data handling. Importantly, the template also provides standardized graphics and faceplates that can be used within the HMI.
Used in conjunction, these three structures standardize the “back-end” programming as well as the “front-end” graphical interface of each device. This results in predictable and repeatable behavior over a large range of projects and sites.
www.WestBasinCA.Gov Page Number: 9 of 293
3 Standard Operating Modes
3.1 Remote Operation
A device in “Remote” mode refers to equipment that is acting on the commands from the PLC/HMI.
The physical equipment may be equipped with a Hand-Off-Auto (HOA) switch or a Local-Off-Remote (LOR) switch. When the switches are positioned for “Auto” and “Remote”, the device is considered in Remote mode since the equipment will respond to signals from the PCS and operate as programmed.
3.1.1 PCS Auto
PCS Auto mode is the normal mode of operation for devices controlled by PLC/HMI. PCS Auto allows the equipment to be controlled automatically by the PLC at any time. Commands are determined solely by the logic of the PLC and therefore will update whenever the PLC logic dictates.
3.1.2 PCS Manual
PCS Manual mode allows the equipment to be controlled by manual commands inputted from HMI.
These manual commands entered by an HMI user are followed regardless of the automatic operation of the PLC. Since the PLC will not be able to update the commands to respond to process changes (such as alarms), this mode is not intended as a typical mode of operation.
3.2 Local Operation
A device in “Local” mode refers to any equipment that is not in “Remote”. Local equipment may be configured for operation by any system that is not connected to the PCS (i.e., local control switches) or for no operation (i.e., locked out).
If the HOA switch or the LOR switch is positioned for “Off”, “Local”, or “Hand”, the device is considered to be in Local mode since the equipment will not respond to signals from the PCS. It cannot be expected that the equipment will follow the programmed behavior. Equipment may have physical or electrical interlocks that prevent the mechanism to operate under certain conditions. When these interlocks are active, the device is considered to be in Local mode since the equipment will not respond to signals from the PCS.
Many devices that are configured for Local operation will still provide feedback to the PLC/HMI, such as position feedback. As such, Local mode will not disable screen animations or state historization.
www.WestBasinCA.Gov Page Number: 10 of 293
4 Device Standards
4.1 Derived Function Blocks (DFB)
4.1.1 DFB_AnalogAlarm
The DFB_AnalogAlarm device is responsible for calculating the limit or deviation alarms associated with an analog value.
The block allows for up to four alarms: Low Low, Low, High, and High High. It is possible to disable/enable each of these four alarms independently. It is also possible to enable latching for the warning alarms (High, Low) separately from the shutdown alarms (High High, Low Low). The block will apply a delay and deadband to all alarms.
4.1.1.1 Value
Description: Analog input value (E.U.)
Connect To: (DDT_AnalogInput).Value
4.1.1.2 Target
Description: Target value for calculating deviation (E.U.)
Connect To: (DDT_AnalogInput).Target
4.1.1.3 HiHiSP
Description: High high alarm setpoint (E.U.)
Connect To: (DDT_AnalogInput).HiHiSP OR (DDT_AnalogInput).DevHiHiSP
4.1.1.4 HiSP
Description: High alarm setpoint (E.U.)
Halliday, Kaylee Typical for all, screenshots will be updated once standards are implemented www.WestBasinCA.Gov Page Number: 11 of 293
Connect To: (DDT_AnalogInput).HiSP OR (DDT_AnalogInput).DevHiSP
4.1.1.5 LoSP
Description: Low alarm setpoint (E.U.)
Connect To: (DDT_AnalogInput).LoSP OR (DDT_AnalogInput).DevLoSP
4.1.1.6 LoLoSP
Description: Low low alarm setpoint (E.U.)
Connect To: (DDT_AnalogInput).LoLoSP OR (DDT_AnalogInput).DevLoLoSP
4.1.1.7 AlmDeadbandSP
Description: Alarm deadband setpoint (E.U.)
Connect To: (DDT_AnalogInput).AlmDeadbandSP OR (DDT_AnalogInput).DevAlmDeadbandSP
4.1.1.8 AlmDelaySP
Description: Alarm delay timer setpoint (seconds)
Connect To: (DDT_AnalogInput).AlmDelaySP OR (DDT_AnalogInput).DevAlmDelaySP
4.1.1.9 DeviationMode
Description: Limit or Deviation alarm configuration (0 = limit mode, 1 = deviation mode)
Connect To: Constant (0 or 1)
If DeviationMode is set to 0, all alarms will be calculated as limit alarms.
If DeviationMode is set to 1, all alarms will be calculated as deviation alarms. Alarm tags should be appended with “Dev” to line up properly with the user-defined data type used for analog inputs with deviation alarms (e.g., “HiHiSP” “DevHiHiSP”).
4.1.1.10 HiHiDisable
Description: High high alarm disable (0 = alarm enabled, 1 = alarm disabled)
Connect To: PLC Logic OR Constant (0 or 1)
The input for this parameter should reflect all cases in which the alarm is disabled. Alarms should be disabled in situations where they do not provide a relevant indicator of the process health (e.g., disabling a flow alarm when the pump is not running).
4.1.1.11 HiDisable
Description: High alarm disable (0 = alarm enabled, 1 = alarm disabled) www.WestBasinCA.Gov Page Number: 12 of 293
The input for this parameter should reflect all cases in which the alarm is disabled. Alarms should be disabling a flow alarm when the pump is not running).
4.1.1.12 LoDisable
Description: Low alarm disable (0 = alarm enabled, 1 = alarm disabled)
The input for this parameter should reflect all cases in which the alarm is disabled. Alarms should be disabling a flow alarm when the pump is not running).
4.1.1.13 LoLoDisable
Description: Low low alarm disable (0 = alarm enabled, 1 = alarm disabled)
The input for this parameter should reflect all cases in which the alarm is disabled. Alarms should be disabling a flow alarm when the pump is not running).
4.1.1.14 LatchShutdown
Description: Shutdown alarm latch enable (0 = non-latching, 1 = latching)
This parameter should be set to true if the High High and Low Low alarms should remain on until reset by ResetReq, even after the alarm condition is cleared.
4.1.1.15 LatchWarning
Description: Warning alarm latch enable (0 = non-latching, 1 = latching)
This parameter should be set to true if the High and Low alarms should remain on until reset by ResetReq, even after the alarm condition is cleared.
4.1.1.16 OOSEnable
Description: Out-of-service enable/disable
Connect To: (DDT_AnalogInput).OOSEnable www.WestBasinCA.Gov Page Number: 13 of 293
If this device is out-of-service, all alarms are inactive.
4.1.1.17 ResetReq
Description: Alarm reset request
Connect To: (DDT_AnalogInput).ResetReq
This request is reset after it is received and processed by the DFB.
4.1.1.18 HiHiAlm
Description: High high alarm
Connect To: (DDT_AnalogInput).HiHiAlm OR (DDT_AnalogInput).DevHiHiAlm
This output is set when all of the following conditions are met for longer than AlmDelaySP:
1. Any of the following conditions are met:
A. DeviationMode is set to 0 (limit alarms) and Value is greater than HiHiSP
B. DeviationMode is set to 1 (deviation alarms) and Value is greater than Target by HiHiSP
2. HiHiDisable is not active
3. OOSEnable is not active
If LatchShutdown is set to 0, the output is reset when any of the following conditions are met:
A. DeviationMode is set to 0 (limit alarms) and Value is less than [HiHiSP – AlmDeadbandSP]
B. DeviationMode is set to 1 (deviation alarms) and Value is greater than Target by less than [HiHiSP + AlmDeadbandSP]
C. HiHiDisable is active
D. OOSEnable is active
If LatchShutdown is set to 1, the output is reset when ResetReq is sent from HMI.
www.WestBasinCA.Gov Page Number: 14 of 293
4.1.1.19 HiAlm
Description: High alarm
Connect To: (DDT_AnalogInput).HiAlm OR (DDT_AnalogInput).DevHiAlm
A. DeviationMode is set to 0 (limit alarms) and Value is greater than HiSP
B. DeviationMode is set to 1 (deviation alarms) and Value is greater than Target by HiSP
2. HiHiAlm is not active
3. HiDisable is not active
4. OOSEnable is not active
If LatchWarning is set to 0, the output is reset when any of the following conditions are met:
A. DeviationMode is set to 0 (limit alarms) and Value is less than [HiSP – AlmDeadbandSP]
B. DeviationMode is set to 1 (deviation alarms) and Value is greater than Target by less than [HiSP + AlmDeadbandSP]
C. HiHiAlm is active
D. HiDisable is active
E. OOSEnable is active
If LatchWarning is set to 1, the output is reset when ResetReq is sent from HMI (or while HiHiAlm is active).
www.WestBasinCA.Gov Page Number: 15 of 293
4.1.1.20 LoAlm
Description: Low alarm
Connect To: (DDT_AnalogInput).LoAlm OR (DDT_AnalogInput).DevLoAlm
A. DeviationMode is set to 0 (limit alarms) and Value is less than LoSP
B. DeviationMode is set to 1 (deviation alarms) and Value is less than Target by LoSP
2. LoLoAlm is not active
3. LoDisable is not active
4. OOSEnable is not active
If LatchWarning is set to 0, the output is reset when any of the following conditions are met:
A. DeviationMode is set to 0 (limit alarms) and Value is greater than [LoSP + AlmDeadbandSP]
B. DeviationMode is set to 1 (deviation alarms) and Value is less than Target by less than [LoSP - AlmDeadbandSP]
C. LoLoAlm is active
D. LoDisable is active
E. OOSEnable is active
If LatchWarning is set to 1, the output is reset when ResetReq is sent from HMI (or while LoLoAlm is active).
www.WestBasinCA.Gov Page Number: 16 of 293
4.1.1.21 LoLoAlm
Description: Low low alarm
Connect To: (DDT_AnalogInput).LoLoAlm OR (DDT_AnalogInput).DevLoLoAlm
A. DeviationMode is set to 0 (limit alarms) and Value is less than LoLoSP
B. DeviationMode is set to 1 (deviation alarms) and Value is less than Target by LoLoSP
2. LoLoDisable is not active
If LatchShutdown is set to 0, the output is reset when any of the following conditions are met:
A. DeviationMode is set to 0 (limit alarms) and Value is greater than [LoLoSP + AlmDeadbandSP]
B. DeviationMode is set to 1 (deviation alarms) and Value is less than Target by less than [LoLoSP - AlmDeadbandSP]
C. LoLoDisable is active
D. OOSEnable is active
If LatchShutdown is set to 1, the output is reset when ResetReq is sent from HMI.
4.1.1.22 ShutdownAlm
Description: General alarm indicating any active shutdown alarm
Connect To: (DDT_AnalogInput).ShutdownAlm OR (DDT_AnalogInput).DevShutdownAlm
This output is active if either HiHiAlm or LoLoAlm are active.
4.1.1.23 WarningAlm
Description: General alarm indicating any active warning alarm
Connect To: (DDT_AnalogInput).WarningAlm OR (DDT_AnalogInput).DevWarningAlm
This output is active if either HiAlm or LoAlm are active.
www.WestBasinCA.Gov Page Number: 17 of 293
4.1.2 DFB_AnalogInput
The DFB_AnalogInput device is used to scale the raw signal from the I/O module into engineering units. This block also has the ability to monitor and set a delay on a broken transmitter alarm. This block is typically used in conjunction with the analog alarm module and/or the flow totalizer module.
The scaling calculation allows for output smoothing and adjustable deadband. An override function allows users from the HMI to force the output value of the block.
4.1.2.1 Input
Description: Raw analog input (counts)
Connect To: (DDT_AnalogInput).Input
4.1.2.2 RackCommsLost
Description: Rack communication fault
Connect To: (DDT_PLCStatus).RackXX.CommsLost
This parameter should be linked to the CommsLost status for the PLC rack that is used for this I/O point.
www.WestBasinCA.Gov Page Number: 18 of 293
4.1.2.3 ModuleFault
Description: Module fault
Connect To: (DDT_PLCStatus).RackXX.ModuleStatus.Y
This parameter should be linked to the ModuleStatus bit for the I/O module that is used for this I/O
4.1.2.4 ChannelFault
Description: Channel fault
Connect To: (DDT_AnalogInput).ChannelFault
4.1.2.5 FaultDelay
Description: Fault alarm delay (seconds)
Connect To: Constant (> 0)
This parameter defines the duration (in seconds) that ChannelFault must be on before FaultAlm turns on.
4.1.2.6 AILoRng
Description: Out-of-range fault low setpoint (counts)
Connect To: (DDT_AnalogInput).AILoRng
4.1.2.7 AIHiRng
Description: Out-of-range fault high setpoint (counts)
Connect To: (DDT_AnalogInput).AIHiRng
4.1.2.8 AIMin
Description: Raw value minimum scale (counts)
Connect To: Constant
This parameter should match the raw input value at the minimum signal (e.g., 4mA). This value should match the configuration of the I/O card.
4.1.2.9 AIMax
Description: Raw value maximum scale (counts)
Connect To: Constant (≠ AIMin) www.WestBasinCA.Gov Page Number: 19 of 293
This parameter should match the raw input value at the maximum signal (e.g., 20mA). This value should match the configuration of the I/O card.
4.1.2.10 EUMin
Description: Output value minimum scale (E.U.)
This parameter defines the analog value (in engineering units) associated with the minimum signal AIMin.
4.1.2.11 EUMax
Description: Output value maximum scale (E.U.)
Connect To: Constant (≠ EUMin)
This parameter defines the analog value (in engineering units) associated with the maximum signal AIMax. This value typically is greater than EUMin but can be less if the transmitter is such that a higher electrical signal indicates a lower engineering value.
4.1.2.12 Deadband
Description: Output deadband range (≤ 0.0 to disable) (E.U.)
Connect To: Constant (> 0 if enabled)
This parameter defines a minimum change (in engineering units) that the input must change before the DFB’s output will update with the new value. A value of 0 disables the deadband feature.
The deadband feature is typically configured to remove insignificant figures from the analog tag.
Therefore, it is recommended to set this parameter to half the value of the least significant digit of the final value. For example, if “discharge pressure” is needed with two digits of precision (100.00 psig), set the deadband to 0.005 psig.
www.WestBasinCA.Gov Page Number: 20 of 293
4.1.2.13 SFactor
Description: Smoothing factor (0.0 < Factor < 1.0)
Connect To: Constant (> 0.0 and < 1.0 if enabled)
This parameter works with SRate to determine the smoothing behavior of the DFB.
Rather than matching the input instantaneously, the output will move a fraction of the distance between the current value and the new value. Then, after a delay equal to SRate, the value output will move that same fraction again (repeating indefinitely). SFactor defines this fraction. An SFactor close to 1 will result in fast response. An SFactor close to 0 will result in a very sluggish response.
If SFactor is set to a value greater than or equal to 1, or less than or equal to 0, smoothing is disabled.
4.1.2.14 SRate
Description: Smoothing rate (ms)
This parameter works with SFactor to determine the smoothing behavior of the DFB.
SRate determines the frequency of the smoothing calculation. The calculation will pause for a duration equal to SRate (milliseconds) before re-executing. Since this block is intended for use in a continuous task (see PLC Style Guide), it is important that SRate is set higher than the maximum scan time of the task (and also higher than the poll rate of the process variable input, if the input is read over a communications network).
If smoothing is disabled (see SFactor), this parameter will have no effect on the behavior of the block.
However even if smoothing is disabled, this parameter should be set to a positive value.
www.WestBasinCA.Gov Page Number: 21 of 293
4.1.2.15 OvrValue
Description: Override (forced) input value
Connect To: (DDT_AnalogInput).OvrValue
If OvrActive is not active, OvrValue is set to match the Value attribute.
If OvrActive is active, OvrValue is available as a setpoint on the HMI. The Value attribute will ignore all other calculations and is instead set to match OvrValue.
4.1.2.16 OvrActive
Description: Override (force) enable/disable
Connect To: (DDT_AnalogInput).OvrActive
4.1.2.17 OvrTime
Description: Override timeout (hours)
Connect To: (DDT_AnalogInput).OvrTime
4.1.2.18 OOSEnable
Connect To: (DDT_AnalogInput).OOSEnable
4.1.2.19 MinutePulse
Description: Input pulse once a minute
Connect To: (DDT_ClockSync).MinutePulse
This parameter is used to trigger the countdown for the override timeout. This is intended to be connected to the MinutePulse tag generated from DFB_ClockSync.
www.WestBasinCA.Gov Page Number: 22 of 293
4.1.2.20 Value
Description: Scaled and filtered analog value (E.U.)
Connect To: (DDT_AnalogInput).Value
This output is calculated by first applying the deadband to Input, then scaling Input to engineering units, then smoothing the result. The output is then overridden if OvrActive is active.
Deadband Calculation:
𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝑑𝑑𝐴𝐴𝐴𝐴 = 𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷 × �
𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴 − 𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴
𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸 − 𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸�
𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝑒𝑒𝐴𝐴𝐴𝐴 = �𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼 − 𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡�
If 𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝑒𝑒𝐴𝐴𝐴𝐴 ≥ 𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝑑𝑑𝐴𝐴𝐴𝐴 , set 𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡 = 𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼.
Otherwise, 𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡 remains unchanged.
Scaling Calculation:
𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠 = ��𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡 − 𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴�× �𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸−𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸
𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴−𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴
�� + 𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸
Smoothing Calculation:
𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑒𝑒𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠ℎ𝑒𝑒𝑒𝑒 =
𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑒𝑒𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠ℎ𝑒𝑒𝑒𝑒,𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝 + 𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆 (𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑒𝑒𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠 − 𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑒𝑒𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠ℎ𝑒𝑒𝑒𝑒,𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝)
Perform this calculation every SRate (milliseconds).
Override Calculation:
If OvrActive is not active, set 𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉 = 𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑒𝑒𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠ℎ𝑒𝑒𝑒𝑒
If OvrActive is active, set 𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉 = 𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂
Then restrict Value between EUMin and EUMax.
www.WestBasinCA.Gov Page Number: 23 of 293
4.1.2.21 FaultAlm
Description: I/O fault alarm
Connect To: (DDT_AnalogInput).FaultAlm
The output is active when all of the following conditions are met for longer than FaultDelay:
A. RackCommsLost is active
B. ModuleFault is active
C. ChannelFault is active
D. Input is less than AILoRng
E. Input is greater than AIHiRng
2. OOSEnable is not active
4.1.2.22 OvrAlm
Description: Override timeout alarm
Connect To: (DDT_AnalogInput).OvrAlm
This output is active when all of the following conditions are met for longer than OvrTime:
1. OvrActive is active
2. OOSEnable is not active
4.1.2.23 OvrHour
Description: Override alarm countdown hours left
Connect To: (DDT_AnalogInput).OvrHour
If OvrActive is active, this output indicates the number of hours remaining before the OvrAlm becomes active. The full time remaining can be read as a combination of OvrHour and OvrMin (e.g., 23:59 hours remain).
If OvrActive is not active, this output is set to 0.
www.WestBasinCA.Gov Page Number: 24 of 293
4.1.2.24 OvrMin
Description: Override alarm countdown minutes left
Connect To: (DDT_AnalogInput).OvrMin
If OvrActive is active, this output indicates the number of minutes remaining before OvrHour ticks down by one. The full time remaining can be read as a combination of OvrHour and OvrMin (e.g., 23:59 hours remain).
If OvrActive is not active, this output is set to 0.
www.WestBasinCA.Gov Page Number: 25 of 293
4.1.3 DFB_AnalogOutput
The DFB_AnalogOutput device is used to scale an analog command from the PLC logic into raw counts for the I/O card. This block also has the ability to monitor and set a delay on a broken transmitter alarm.
4.1.3.1 Command
Description: Output command (E.U.)
Connect To: (DDT_AnalogOutput).Command
4.1.3.2 RackCommsLost
4.1.3.3 ModuleFault
4.1.3.4 ChannelFault
Description: Channel fault
Connect To: (DDT_AnalogOutput).ChannelFault www.WestBasinCA.Gov Page Number: 26 of 293
4.1.3.5 FaultDelay
4.1.3.6 EUMin
Description: Command minimum scale (E.U.)
This parameter defines the analog value (in engineering units) associated with the minimum signal AOMin.
4.1.3.7 EUMax
Description: Command maximum scale (E.U.)
Connect To: Constant (≠EUMin)
This parameter defines the analog value (in engineering units) associated with the maximum signal AOMax. This value typically is greater than EUMin but can be less if the transmitter is such that a higher electrical signal indicates a lower engineering value.
4.1.3.8 AOMin
Description: Output minimum value (counts)
This parameter should match the raw output value at the minimum signal (e.g., 4mA). This value
4.1.3.9 AOMax
Description: Output maximum value (counts)
Connect To: Constant (≠AOMin)
This parameter should match the raw output value at the maximum signal (e.g., 20mA). This value www.WestBasinCA.Gov Page Number: 27 of 293
4.1.3.10 OOSEnable
Connect To: (DDT_AnalogOutput).OOSEnable
4.1.3.11 Output
Description: Raw analog output (counts)
Connect To: (DDT_AnalogOutput).Output
This output is calculated by scaling command to raw counts.
Scaling Calculation:
𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂 = �(𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶 − 𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸) × �
𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴 − 𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴
𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸 − 𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸��
+ 𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴
Then restrict Output between AOMin and AOMax.
4.1.3.12 FaultAlm
Connect To: (DDT_AnalogOutput).FaultAlm
This output is active when all of the following conditions are met for longer than FaultDelay:
A. RackCommsLost is active
B. ModuleFault is active
C. ChannelFault is active
2. OOSEnable is not active www.WestBasinCA.Gov Page Number: 28 of 293
4.1.4 DFB_AnalogRamp
The DFB_AnalogRamp device is used to linearly ramp an output variable towards a target by a specified rate. This is typically used to avoid sudden changes to the process control.
This DFB is used within DFB_PIDController, but is also available to use within any other logic in the
PLC.
4.1.4.1 Input
Description: Analog value to ramp (E.U.)
Connect To: PLC Logic
This parameter defines the target value of the ramp. As long as Output does not equal Input, the block will attempt to ramp Output towards Input.
4.1.4.2 Rate
Description: Value ramp rate (E.U./second)
Connect To: PLC Logic OR Constant (> 0)
This parameter defines the amount that Output will ramp every second.
4.1.4.3 Bypass
Description: Bypass enable/disable
Connect To: PLC Logic OR Always False
This parameter determines whether the Output will be ramped or whether ramping should be bypassed, and the value should be set straight to Input.
www.WestBasinCA.Gov Page Number: 29 of 293
4.1.4.4 Output
Description: Ramping output analog value
Connect To: PLC Tag or PLC Logic
This parameter represents the value that is being ramped towards Input.
This output is ramped by the following calculation:
If Rate > 0 and Bypass is inactive, every 100ms (1/10 second):
If Output < Input:
𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂 = min(𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂 +
𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅
, 𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼)
If Output > Input:
𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂 = max(𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂 −
𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅
, 𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼)
If Rate < 0 or Bypass is active:
Set Output = Input.
www.WestBasinCA.Gov Page Number: 30 of 293
4.1.5 DFB_AnalogValve
The DFB_AnalogValve device is responsible for handling any valve that accepts analog position commands rather than open/close (discrete) commands.
This DFB is intended for valves with one analog output for position command and one analog input for position feedback. The valve can optionally be configured with open and/or closed limit switches for further position confirmation. The valve can also optionally be configured with remote/local (discrete) feedback.
4.1.5.1 AutoSP
Description: PCS auto position command (%)
Connect To: (DDT_AnalogValve).AutoSP
4.1.5.2 Remote_Value
Description: Remote status discrete input (0 = local/off, 1 = remote)
Connect To: (DDT_AnalogValve).Remote.Value www.WestBasinCA.Gov Page Number: 31 of 293
4.1.5.3 Posn_Value
Description: Position feedback from field
Connect To: (DDT_AnalogValve).Posn.Value
If SimPosn is inactive, the Posn_Value will use the field analog input as feedback.
If SimPosn is active, Posn_Value will use the PosnCmd_Command as feedback.
4.1.5.4 Open_Value
Description: Open limit switch input
Connect To: (DDT_AnalogValve).Open.Value
If SimOpen is inactive, this parameter matches the physical limit switch.
If SimOpen is active, this parameter is active any time the valve position feedback is greater than [100 - OpenLSDeadband].
4.1.5.5 Closed_Value
Description: Closed limit switch input
Connect To: (DDT_AnalogValve).Closed.Value
If SimClosed is inactive, this parameter matches the physical limit switch.
If SimClosed is active, this parameter is active any time the valve position feedback is less than ClosedLSDeadband.
4.1.5.6 ExternalWarning
Description: External warning indication for the valve
Connect To: (DDT_AnalogValve).ExternalWarning
4.1.5.7 ExternalFault
Description: External fault indication for the valve
Connect To: (DDT_AnalogValve).ExternalFault www.WestBasinCA.Gov Page Number: 32 of 293
4.1.5.8 ManSP
Description: PCS manual position command (%)
Connect To: (DDT_AnalogValve).ManSP
If AutoMode is active, ManSP is set to match the PosnCmd_Command attribute.
If AutoMode is not active, ManSP is available as a setpoint on the HMI.
4.1.5.9 AutoReq
Description: PCS auto mode request, reset by PLC
Connect To: (DDT_AnalogValve).AutoReq
4.1.5.10 ManReq
Description: PCS manual mode request, reset by PLC
Connect To: (DDT_AnalogValve).ManReq
4.1.5.11 ResetReq
Description: Alarm reset request, reset by PLC
Connect To: (DDT_AnalogValve).ResetReq
4.1.5.12 SimPosn
Description: Enable simulated position feedback (0 = AI, 1 = simulate position)
Connect To: (DDT_AnalogValve).SimPosn
This parameter determines whether the block will simulate the position feedback.
4.1.5.13 SimOpen
Description: Enable simulated open limit switch (0 = DI, 1 = simulate limit switch)
Connect To: (DDT_AnalogValve).SimOpen
This parameter determines whether the valve will simulate the open limit switch.
www.WestBasinCA.Gov Page Number: 33 of 293
4.1.5.14 SimClosed
Description: Enable simulated closed limit switch (0 = DI, 1 = simulate limit switch)
Connect To: (DDT_AnalogValve).SimClosed
This parameter determines whether the valve will simulate the closed limit switch.
4.1.5.15 OpenLSDeadband
Description: Distance of feedback from max where open limit switch would be expected (%)
This parameter defines the distance from 100% (open) where the position feedback will trigger a simulated Open_Value.
4.1.5.16 ClosedLSDeadband
Description: Distance of feedback from min where closed limit switch would be expected (%)
This parameter defines the distance from 0% (closed) where the position feedback will trigger a simulated Closed_Value.
4.1.5.17 LSAlmDeadband
Description: Distance of command from limit switch region where limit switch would be unexpected (%)
This parameter defines the distance from the limit switch region where it would be unexpected to receive limit switch feedback. This is used to calculate unexpected open/closed alarms
For example, if the open limit switch triggers when the command is 0.1% away from the open region, this is expected behavior. If the open limit switch triggers when the command is 25% away from the limit switch, this is an alarm condition.
4.1.5.18 PosnDevSP
Description: Position difference before position deviation alarm (%)
Connect To: (DDT_AnalogValve).PosnDevSP
4.1.5.19 PosnDevTime
Description: Position deviation alarm delay timer setpoint (seconds)
Connect To: (DDT_AnalogValve).PosnDevTime www.WestBasinCA.Gov Page Number: 34 of 293
4.1.5.20 FailMoveTime
Description: Fail to open and close timer setpoint (seconds)
Connect To: (DDT_AnalogValve).FailMoveTime
4.1.5.21 UnxptdMoveTime
Description: Unexpected open and close timer setpoint (seconds)
Connect To: (DDT_AnalogValve).UnxptdMoveTime
4.1.5.22 Interlock_Met
Description: Interlock conditions are met and device is allowed to operate
Connect To: 1 or (DDT_AnalogValve).Interlock.Met
If a device does not have interlock conditions, this input should be set to 1.
If a device has an interlock, a DFB_Conditions block must be configured with this input connected to (DDT_AnalogValve).Interlock.Met.
4.1.5.23 InterlockPosition
Description: Interlock valve position (%)
Connect To: Constant (0 – 100%)
This parameter defines the valve’s position during an interlock condition.
4.1.5.24 OOSEnable
Connect To: (DDT_AnalogValve).OOSEnable
If this device is out-of-service, all alarms are inactive, AutoMode and AutoAvailable are cleared, and the position command is set to the OOSPosition value.
4.1.5.25 OOSPosition
Description: Out-of-service position (%)
Connect To: (DDT_AnalogValve).OOSPosition
4.1.5.26 PosnCmd_Command
Description: Position command to valve (%)
Connect To: (DDT_AnalogValve).PosnCmd.Command www.WestBasinCA.Gov Page Number: 35 of 293
This parameter determines the actual position command sent to the valve. This output will take different values depending on the mode of the valve.
Position Command calculation:
(Listed in order of priority, highest to lowest)
If Interlock is active, set PosnCmd_Command = InterlockPosition
If OOSEnable is active, set PosnCmd_Command = OOSPosition
If AutoMode is inactive, set PosnCmd_Command = ManSP
If AutoMode is active (lowest priority), set PosnCmd_Command = AutoSP
4.1.5.27 AutoMode
Description: PCS auto mode indication
Connect To: (DDT_AnalogValve).AutoMode
This parameter indicates that the valve is in PCS Auto mode.
This output is set by AutoReq (from HMI command).
This output is reset by ManReq or OOSEnable (from HMI command).
4.1.5.28 AutoAvailable
Description: Device ready for automatic operation indication
Connect To: (DDT_AnalogValve).AutoAvailable
This output is active when all of the following conditions are met:
1. Remote_Value is active
2. AutoMode is active
3. OOSEnable is not active
4. Interlock is not active
5. No summary alarms are active (external fault, unexpected open/close, fail to open/close)
4.1.5.29 PosnDevAlm
Description: Position deviation alarm
Connect To: (DDT_AnalogValve).PosnDevAlm
This output is active when all of the following conditions are met for longer than PosDevTime:
www.WestBasinCA.Gov Page Number: 36 of 293
3. |Posn_Value - PosnCmd_Command| > PosnDevSP
4.1.5.30 FailedToOpenAlm
Description: Valve failed to open alarm
Connect To: (DDT_AnalogValve).FailedToOpenAlm
This output is active when all of the following conditions are met for longer than FailMoveTime:
2. OOSEnable is not active
3. Any of the following conditions are met:
A. All of the following conditions are met:
1. Device was previously confirmed as closed
2. PosnCmd_Command > (ClosedLSDeadband + LSAlmDeadband)
3. Closed_Value is active
B. All of the following conditions are met:
1. Device was not previously confirmed as open
2. PosnCmd_Command = 100
3. Open_Value is not active
4.1.5.31 FailedToCloseAlm
Description: Valve failed to close alarm
Connect To: (DDT_AnalogValve).FailedToCloseAlm
This output is active when all of the following conditions are met for longer than FailMoveTime:
2. OOSEnable is not active
3. Any of the following conditions are met:
A. All of the following conditions are met:
1. Device was not previously confirmed as closed
2. PosnCmd_Command = 0
3. Closed_Value is not active
B. All of the following conditions are met:
1. Device was previously confirmed as open
2. PosnCmd_Command < (100 – OpenLSDeadband – LSAlmDeadband) www.WestBasinCA.Gov Page Number: 37 of 293
3. Open_Value is active
4.1.5.32 UnxptdOpenAlm
Description: Valve unexpected open alarm
Connect To: (DDT_AnalogValve).UnxptdOpenAlm
This output is active when all of the following conditions are met for longer than UnxptdMoveTime:
2. OOSEnable is not active
3. Any of the following conditions are met:
A. All of the following conditions are met:
1. Device was previously confirmed as closed
2. PosnCmd_Command = 0
3. Closed_Value is not active
B. All of the following conditions are met:
1. Device was not previously confirmed as open
2. PosnCmd_Command < (100 – OpenLSDeadband – LSAlmDeadband)
3. Open_Value is active
4.1.5.33 UnxptdCloseAlm
Description: Valve unexpected close alarm
Connect To: (DDT_AnalogValve).UnxptdCloseAlm
This output is active when all of the following conditions are met for longer than UnxptdMoveTime:
2. OOSEnable is not active
3. Any of the following conditions are met:
A. All of the following conditions are met:
1. Device was previously confirmed as open
2. PosnCmd_Command = 100
3. Open_Value is not active
B. All of the following conditions are met:
1. Device was not previously confirmed as closed
2. PosnCmd_Command > (ClosedLSDeadband + LSAlmDeadband) www.WestBasinCA.Gov Page Number: 38 of 293
3. Closed_Value is active
4.1.5.34 SummaryWarning
Description: Summary warning bit
Connect To: (DDT_AnalogValve).SummaryWarning
A. ExternalWarning is active
B. PosnDevAlm is active
2. OOSEnable is not active
4.1.5.35 SummaryAlm
Description: Summary alarm summary bit
Connect To: (DDT_AnalogValve).SummaryAlm
A. ExternalFault is active
B. FailToOpenAlm is active
C. FailToCloseAlm is active
D. UnxptdOpenAlm is active
E. UnxptdCloseAlm is active.
www.WestBasinCA.Gov Page Number: 39 of 293
4.1.6 DFB_ChemicalPacing
The DFB_ChemicalPacing device outputs open and closed loop calculations. For the open loop output, the block will calculate the pump’s required speed to meet the dose setpoint. For the closed loop output, this block will calculate the required flow rate required to meet the dose setpoint that can then be used with a controller block such as the PID controller.
This block also has the ability to trim the calculation based on an analyzer value. This option allows the PLC to fine-tune the pacing based on feedback values.
4.1.6.1 EnableCalc
Description: Enables flow output calculation
Connect To: (DDT_ChemicalPacing).EnableCalc
If the EnableCalc parameter is not active, the flow calculation is set to the OutputClampMin and the calculated flow will be set to 0.
If the EnableCalc parameter is active, the flow calculation is limited between the minimum and maximum values.
4.1.6.2 PacingFlow
Description: Chemical system pacing flow (MGD)
Connect To: (DDT_ChemicalPacing).PacingFlow
4.1.6.3 DoseSP
Description: Chemical system dose setpoint (mg/L)
Connect To: (DDT_ChemicalPacing).DoseSP www.WestBasinCA.Gov Page Number: 40 of 293
4.1.6.4 Background
Description: Background chemical (mg/L)
Connect To: (DDT_ChemicalPacing).Background
Not all chemical systems will use a background setpoint, setting this parameter to zero will effectively disable it within the calculation.
4.1.6.5 Demand
Description: Chemical demand (mg/L)
Connect To: (DDT_ChemicalPacing).Demand
Not all chemical systems will use a demand setpoint, setting this parameter to zero will effectively disable it within the calculation.
4.1.6.6 Concentration
Description: Chemical concentration (%)
Connect To: (DDT_ChemicalPacing).Concentration
4.1.6.7 SpecGrav
Description: Chemical specific gravity
Connect To: (DDT_ChemicalPacing).SpecGrav
4.1.6.8 ConversionFactor
Description: Units conversion constant
Connect To: (DDT_ChemicalPacing).ConversionFactor
4.1.6.9 MinFlow
Description: Minimum allowable value for the calculated flow (GPH)
Connect To: Constant
4.1.6.10 MaxFlow
Description: Maximum allowable value for the calculated flow (GPH)
Connect To: Constant
4.1.6.11 OutputClampMin
Description: Minimum allowable value for the speed output (%) www.WestBasinCA.Gov Page Number: 41 of 293
4.1.6.12 OutputClampMax
Description: Maximum allowable value for the speed output (%)
Connect To: Constant
4.1.6.13 EnableTrim
Description: Trim enable command (1 = enabled)
Connect To: (DDT_ChemicalPacing).EnableTrim
If EnableTrim is not active, the trim value is set to 0 (E.U.)
4.1.6.14 AnalyzerValue
Description: Analyzer feedback value (E.U.)
Connect To: (DDT_ChemicalPacing).AnalyzerValue
4.1.6.15 TrimSP
Description: Target trim setpoint (E.U.)
Connect To: (DDT_ChemicalPacing).TrimSP
4.1.6.16 TrimBumpSP
Description: Trim bump setpoint (mg/L)
Connect To: (DDT_ChemicalPacing).TrimBumpSP
4.1.6.17 MaxTrimSP
Description: Maximum trim amount (mg/L)
Connect To: (DDT_ChemicalPacing).MaxTrimSP
4.1.6.18 TrimDeadband
Description: Trim deadband setpoint (E.U.)
Connect To: (DDT_ChemicalPacing).TrimDeadband
4.1.6.19 TrimBumpDelay
Description: Trim bump delay (min)
Connect To: (DDT_ChemicalPacing).TrimBumpDelay www.WestBasinCA.Gov Page Number: 42 of 293
4.1.6.20 ReverseActing
Description: Reverses direction of bumps if enabled (1 = reverse acting, 0 = forward acting)
Connect To: Constant (1 or 0)
The direction of the trim is reversed if the reverse acting parameter is enabled. This means that trim will decrease the dose when the analyzer value is greater than the dose and increase when it is less than the dose. See the TrimValue section for more details.
4.1.6.21 SpeedOutput
Description: Chemical system speed output (%)
Connect To: (DDT_ChemicalPacing).SpeedOutput
The following calculation is used to determine the chemical system speed setpoint:
Calc. speed SP (%) =
𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶 𝐹𝐹𝐹𝐹𝐹𝐹𝐹𝐹
𝐌𝐌𝐌𝐌𝐌𝐌𝐌𝐌𝐌𝐌𝐌𝐌𝐌𝐌(GPH)
× 100%
4.1.6.22 CalculatedFlow
Description: Chemical system closed loop flow output (E.U.)
Connect To: (DDT_ChemicalPacing).CalculatedFlow
The following calculation is used to determine the chemical system flow setpoint:
Calc. flow SP (GPH) = System pacing flow × conversion factor × (Effective dose)
�𝐜𝐜𝐜𝐜𝐜𝐜𝐜𝐜. (%)
100 � × 𝐒𝐒.𝐆𝐆.
Effective Dose (mg/L) = 𝐃𝐃𝐃𝐃𝐃𝐃𝐃𝐃 − 𝐁𝐁𝐁𝐁𝐁𝐁𝐁𝐁𝐁𝐁𝐁𝐁𝐁𝐁𝐁𝐁𝐁𝐁𝐁𝐁 + 𝐃𝐃𝐃𝐃𝐃𝐃𝐃𝐃𝐃𝐃𝐃𝐃 ± Current Trim Value
4.1.6.23 EffectiveDose
Description: Chemical system calculated dose (mg/L)
Connect To: (DDT_ChemicalPacing).EffectiveDose www.WestBasinCA.Gov Page Number: 43 of 293
4.1.6.24 TrimValue
Description: Current total trim value (mg/L)
Connect To: (DDT_ChemicalPacing).TrimValue
The abbreviations in the calculations above refer to the following setpoints:
conversion factor = flow units conversion factor conc. = Chemical system concentration (%)
S.G. = Chemical system specific gravity
MaxFlow = Chemical system flow at 100% VFD flow
Trim Increment Conditions
The logic below describes when the trim value is incremented.
If all the following are true:
1. [Trim setpoint –analyzer value] is greater than the trim bump deadband for longer than the trim bump timer delay
2. The Trim value (E.U.) is less or equal to the absolute value of the (maximum trim value – trim bump setpoint)
3. The output value is less than the max allowable output
Then do the following:
1. Increment the trim value by the trim bump setpoint
2. Reset the trim bump timer
Trim Decrement Conditions
The logic below describes when the trim value is decremented.
If all the following are true:
1. [Analyzer value – trim setpoint] is greater than the trim bump deadband for longer than the trim bump timer delay
2. The Trim value (E.U.) is less or equal to the absolute value of the (maximum trim value – trim bump setpoint)
3. The output value is greater than negative of the max allowable output
Then do the following:
1. Decrement the trim value by trim bump setpoint
2. Reset the trim bump timer www.WestBasinCA.Gov Page Number: 44 of 293
4.1.7 DFB_ClockSync
The DFB_ClockSync device is used to synchronize the PLC clock time with a clock time from HMI.
This block also reports the current PLC clock time and produces single-scan pulses to be used for logic that requires precise or synchronized triggers. This block should be executed as part of the “ClockSync” standard section.
4.1.7.1 HourSP
Description: Hour setpoint from the HMI (0 - 23)
Connect To: (DDT_ClockSync).HourSP
4.1.7.2 MinuteSP
Description: Minute setpoint from the HMI (0 - 59)
Connect To: (DDT_ClockSync).MinuteSP
4.1.7.3 SecondSP
Description: Second setpoint from the HMI (0 - 59)
Connect To: (DDT_ClockSync).SecondSP
4.1.7.4 YearSP
Description: Year setpoint from the HMI (yyyy)
Connect To: (DDT_ClockSync).YearSP
4.1.7.5 MonthSP
Description: Month setpoint from the HMI (1-12)
Connect To: (DDT_ClockSync).MonthSP www.WestBasinCA.Gov Page Number: 45 of 293
4.1.7.6 DaySP
Description: Day setpoint from the HMI (01 - 31)
Connect To: (DDT_ClockSync).DaySP
4.1.7.7 SyncReq
Description: Request to synchronize the PLC clock to setpoints, reset by PLC
Connect To: (DDT_ClockSync).SyncReq
4.1.7.8 Hour
Description: Real-time PLC clock hour (0 - 23)
Connect To: (DDT_ClockSync).Hour
This output is always set equal to the PLC internal clock’s current hour (in 24-hour format).
4.1.7.9 Minute
Description: Real-time PLC clock minute (0 - 59)
Connect To: (DDT_ClockSync).Minute
This output is always set equal to the PLC internal clock’s current minute.
4.1.7.10 Second
Description: Real-time PLC clock second (0 - 59)
Connect To: (DDT_ClockSync).Second
This output is always set equal to the PLC internal clock’s current second.
4.1.7.11 Year
Description: Real-time PLC clock year (yyyy)
Connect To: (DDT_ClockSync).Year
This output is always set equal to the PLC internal clock’s current year.
4.1.7.12 Month
Description: Real-time PLC clock month (1-12)
Connect To: (DDT_ClockSync).Month www.WestBasinCA.Gov Page Number: 46 of 293
This output is always set equal to the PLC internal clock’s current month.
4.1.7.13 Day
Description: Real-time PLC clock day (01-31)
Connect To: (DDT_ClockSync).Day
This output is always set equal to the PLC internal clock’s current day.
4.1.7.14 DateTime
Description: Real-time PLC clock date and time (DT)
Connect To: (DDT_ClockSync).DateTime
4.1.7.15 TimeOfDay
Description: Real-time PLC clock time (TIME_OF_DAY)
Connect To: (DDT_ClockSync).TimeOfDay
4.1.7.16 DateYear
Description: Real-time PLC clock date (DATE)
Connect To: (DDT_ClockSync).DateYear
4.1.7.17 HourPulse
Description: One-scan pulse on the first scan of the hour
Connect To: (DDT_ClockSync).HourPulse
This output is active for one scan on the first scan of the new hour.
4.1.7.18 MinutePulse
Description: One-scan pulse on the first scan of the minute
This output is active for one scan on the first scan of the new minute.
4.1.7.19 SecondPulse
Description: One-scan pulse on the first scan of the second
Connect To: (DDT_ClockSync).SecondPulse www.WestBasinCA.Gov Page Number: 47 of 293
This output is active for one scan every second.
4.1.7.20 YearPulse
Description: One-scan pulse on the first scan of the year
Connect To: (DDT_ClockSync).YearPulse
This output is active for one scan on the first scan of the new year (on midnight of January 1st).
4.1.7.21 MonthPulse
Description: One-scan pulse on the first scan of the moth
Connect To: (DDT_ClockSync).MonthPulse
This output is active for one scan on the first scan of the new month (on midnight of the 1st).
4.1.7.22 DayPulse
Description: One-scan pulse on the first scan of the day
Connect To: (DDT_ClockSync).DayPulse
This output is active for one scan on the first scan of the new day (midnight).
www.WestBasinCA.Gov Page Number: 48 of 293
4.1.8 DFB_CommRead
The DFB_CommRead block is used to read an array of up to 100 holding registers from a remote device via Modbus.
4.1.8.1 Token
Description: Token controlling the execution order of the DFB_CommRead blocks.
Connect To: PLC logic
The DFB_CommRead block increments the Token number after execution.
4.1.8.2 ID
Description: ID of the block for the token system
This is a unique number to indicate the execution order of the block within the communication token system. If the Token matches the ID, the block executes the read message.
4.1.8.3 Enable
Description: Communication block enable/disable
If this is not active, the message will not be read, and the Token will be incremented.
4.1.8.4 DeviceAddress
Description: Path to remote device
Connect To: PLC Logic (ADDM block)
4.1.8.5 MbStartAddress
Description: Modbus holding register starting address www.WestBasinCA.Gov Page Number: 49 of 293
4.1.8.6 MbLength
Description: Number of…