(b)_0001_Annex_1_20260608.pdf
PDF 158 KB Posted
- Solicitation number
- W912PF26QA042
About this file
This document is Annex 1 to a Statement of Requirements detailing line items and technical specifications for Work Order HB442895J, which involves the repair and supply of medium voltage SF6 breakers and related electrical equipment for substations at Caserma Del Din.
The procurement encompasses seven contract line items (CLINs) totaling multiple ABB brand electrical components. CLIN 0001 requires one ESS-K switchgear unit (24kV, 630A, 16kA) with integrated metering and feeder components. CLIN 0002 specifies one BLDG #55 CEP switchgear (24kV, 630A, 16kA) with 27 integrated circuit breaker components. CLIN 0003 calls for three BLDG #55 CEP switchgear units operating at 11kV with generator and transformer feeder capability. CLIN 0004 requires 13 ESS-N(S)-n switchgear units (24kV) with ring and transformer feeder configurations. CLIN 0005 specifies one ESS-S-7 switchgear (24kV) with five integrated feeder components. CLIN 0006 calls for one ESS-S-9 switchgear (24kV) with riser and transformer feeder components. CLIN 0007 requires eight ABB REF620 medium voltage protection relay units.
All items must meet mandatory requirements including: applicable commercial warranty documentation, Technical Manuals for operation, parts, and maintenance provided in English and Italian (preferably on DVD or CD in industry/manufacturer standard format), and CE (European Conformity) certification. Non-compliance with CE certification requirements will result in rejection. All equipment must include accessories necessary for complete installation per industry standards. Additional technical specifications are referenced in Annexes 2 and 3 for all CLINs and Annex 4 for CLIN 0007.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W.O. HB442895J - Repair MV SF6 breakers in all electrical substations - Caserma Del Din
Annex 1 - Details for each item
Statement of Requirements for all items:
1) Any applicable commercial warranty that was quoted as included with the equipment.
2) Technical Manual Operator - English and Italian (preferred if in DVD or CD).
Industry/Manufacturer standard format is acceptable.
3) Technical Manual Parts English and Italian (preferred if in DVD or CD).
Industry/Manufacturer standard format is acceptable.
4) Technical Manual Maintenance English and Italian (preferred if in DVD or CD). Industry/Manufacturer standard format is acceptable.
5) The equipment must be CE (European Conformity) or it will be rejected due to not meeting the technical specifications.
Clin Description Unit Quantity
Supply of ABB (Brand Name) medium voltage electrical panel:
Switchgear ESS-K, 24kV 630A 16kA, Composed by:
1 SFV metering, 6A;
1 WBC Feeder Line 1, 630A;
1 WBC Feeder Line 2, 630A;
1 WBC Incoming DC, 630A, Including all the accessories necessary to complete the work according to the rule of the art.
For further technical information, please refer to Annexes 2 and 3, which form an integral part of the technical specifications set out in
CLIN 0001.
Each 1
Supply of ABB (Brand Name) medium voltage electrical panel:
1 Switchgear BLDG #55 CEP, 24kV 630A 16kA Composed by:
1 DRC Incoming 1, 630 A 1 SFV Metering 1, 6 A 1 SDC Bypass 1, 630 A
1 WBS DDI 1, 630 A
1 DRS Riser 1, 630 A 1 SDC Bypass 2, 630 A 1 WBC Ring Feeder 1, 630 A 1 WBC Ring Feeder 2, 630 A 1 WBC Feeder 3 (TR4), 630 A 1 WBS Bus Tie 1, 630 A 1 DRS Riser 1, 630 A 1 SFV Busbar Metering, 6 A 1 WBC Feeder 1 (BESS), 630 A 1 WBC Feeder 2 (TR5), 630 A 1 WBC Feeder 3 TR Load Bank, 630 A 1 WBC Generator Feeder 1, 630 A 1 WBC Generator Feeder 2, 630 A 1 WBC Generator Feeder 3, 630 A 1 WBS Bus Tie 2, 630 A 1 DRS Riser 2, 630 A 1 WBC Ring Feeder 3, 630 A 1 WBC Ring Feeder 4, 630 A
1 WBS DDI 2, 630 A
1 DRS Riser 1 1, 630 A 1 SFV Metering 2, 6 A 1 DRC Incoming 2, 630 A
Including all the accessories necessary to complete the work according to the rule of the art. For further technical information, please refer to Annexes 2 and 3, which form an integral part of the technical specifications set out in CLIN 0002.
Switchgear BLDG #55 CEP 11kV, 630A 16kA, composed by:
1 SDC Incoming Generator, 630 A 1 SFV Metering, 6 A 1 SDC Transformer Feeder, 630 A
Including all the accessories necessary to complete the work according to the rule of the art.
For further technical information, please refer to Annexes 2 and 3, which form an integral part of the technical specifications set out in
CLIN 0003.
Each 3
Supply of ABB (Brand Name) medium voltage electrical panel:
Switchgear ESS-N(S)-n, 24kV 630A 16kA, composed by:
1 WBC Ring Feeder 1, 630 A 1 WBC Ring Feeder 2, 630 A 1 WBC Transformer Feeder 1, 630 A 1 WBC Transformer Feeder 2, 630 A
Including all the accessories necessary to complete the work according to the rule of the art. For further technical information, please refer to Annexes 2 and 3, which form an integral part of the technical specifications set out in CLIN 0004.
Each 13
Switchgear ESS-S-7, 24kV 630A 16kA, composed by:
1 WBC Ring Feeder 1, 630 A 1 WBC Ring Feeder 2, 630 A 1 WBC Line_TR Feeder 1, 630 A 1 WBC Line_TR Feeder 2, 630 A 1 WBC Line_TR Feeder 3, 630 A
Including all the accessories necessary to complete the work according to the rule of the art.
For further technical information, please refer to Annexes 2 and 3, which form an integral part of the technical specifications set out in
CLIN 0005.
Switchgear ESS-S-9, 24kV 630A 16kA, composed by:
1 DRC Riser, 630 A 1 WBC Transformer Feeder, 630 A
Including all the accessories necessary to complete the work according to the rule of the art.
For further technical information, please refer to Annexes 2 and 3, which form an integral part of the technical specifications set out in
CLIN 0006.
Each 1
Supply of ABB (Brand Name) Medium voltage protection relay, type
REF620.
Including all the accessories necessary to complete the work according to the rule of the art.
For further technical information, please refer to Annexes 2, Annex 3 and Annex 4, which form an integral part of the technical specifications set out in CLIN 0007.
Each 8
File details come from the government source that posted it. Updated .