About this file

This is a user manual for the AXM-WEB2 Series Ethernet communication modules designed for Accuenergy Acuvim II and Acuvim-L power meters. The document provides comprehensive installation, configuration, and operational guidance for the AXM-WEB2, AXM-WEB2-FOLC, and AXM-WEB2-D module variants, which offer dual Ethernet ports with Wi-Fi capability, fiber optic connectivity, or dual Ethernet-only configurations respectively. The modules support multiple communication protocols including Modbus-TCP, BACnet-IP, SNMP, DNP 3.0, IEC 61850, EtherNet/IP, MQTT, and Google IoT, enabling integration with various building automation and energy management systems. Key features include 100ms and 20ms response rates for real-time parameter monitoring, HTTPS web interface access with user role-based permissions, comprehensive metering data display (voltage, current, power, energy, harmonics, power quality), and support for up to 16 alarm channels with relay output control.

The manual details configuration procedures for network settings (IP addressing via static or DHCP), Modbus-TCP protocol implementation with specific function codes for reading/writing registers and controlling relay outputs, user management with customizable role-based access control, and extensive logging capabilities including trend logs, data logs, alarm logs, sequence-of-events logs, and waveform capture for power quality events. It covers optional I/O module configurations (AXM-IO1, AXM-IO2, AXM-IO3) for digital inputs/outputs, analog inputs/outputs, and relay control, firmware update procedures, and network diagnostics. Default settings establish Ethernet 1 at 192.168.1.254 (static) and Ethernet 2 via DHCP, with Wi-Fi access point mode at 192.168.100.1, all supporting secure remote access and integration with cloud-based monitoring through AcuCloud connectivity.

View the file

Other files

File Type Posted
Acuvim-II-Advanced-Power-and-Energy-Meter-Datasheet.pdf PDF
FX90 Cutsheet.pdf PDF
Simplex 4100ES.pdf PDF
Attachment 1 - Company Information.docx DOCX document
EC-BOS-9_SP Cutsheet.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AXM-WEB2 Series Acuvim II and Acuvim L Power Meters Users Manual www.accuenergy.com

II V: 2.1.4 Revised: September 2024

Copyright © 2024 V2.1.4

This manual may not be altered or reproduced in whole or in part by any means without the expressed written consent of Accuenergy.

1V: 2.1.4 Revised: September 2024

The information contained in this document is believed to be accurate at the time of publication, however, Accuenergy assumes no responsibility for any errors which may appear here and reserves the right to make changes without notice. Please ask the local representative for latest product specifications before ordering.

Please read this manual carefully before installation, operation and maintenance of the Acuvim II series meter. The following symbols in this manual are used to provide warning of danger or risk during the installation and operation of the meters.

Electric Shock Symbol: Carries information about procedures which must be followed to reduce the risk of electric shock and danger to personal health.

Safety Alert Symbol: Carries information about circumstances which if not considered may result in injury or death.

Prior to maintenance and repair, the equipment must be de-energized and grounded. All maintenance work must be performed by qualified, competent accredited professionals who have received formal training and have experience with high voltage and current devices.

Accuenergy shall not be responsible or liable for any damages or injuries caused by improper meter installation and/or operation.

2 V: 2.1.4 Revised: September 2024

Table of Contents

Chapter 1: Introduction to AXM-WEB2 Series Modules

1.1 Module Types

1.1.1 AXM-WEB2

1.1.2 AXM-WEB2-FOLC

1.1.3 AXM-WEB2-D

1.2 Functional Description of the Ethernet module

Chapter 2: Installation

2.1 Appearance and Dimensions

2.2 Installation Method

2.3 Cable Connection

2.4 Default Settings

2.5 Initializing

Chapter 3: Connection Method

3.1 Direct Connect to a Computer

3.2 Direct Connect to a Router/Switch

3.3 Connect through Wi-Fi

3.4 Description of Modbus-TCP Protocol

3.4.1 Protocol

3.4.2 Format of communication

Chapter 4: User Management

4.1 User Access Login

4.2 User Configuration

4.3 Role Configuration

4.4 Password Policy

4.5 Password Management

4.6 API Token Management

Chapter 5: Web Interface Readings and Parameter Settings

5.1 Dashboard

5.2 Metering web page

5.2.1 Basic Metering

5.2.2 Power & Energy

5.2.3 Min/Max

5.2.4 THD

5.2.5 Harmonics

5.2.6 Phase Angles

3V: 2.1.4 Revised: September 2024

5.2.7 Sequence

5.2.8 I/O

5.3 Logs

5.3.1 Trend Log

5.3.2 Trendlog Management

5.3.3 Data log

5.3.4 Alarm Log

5.3.5 SOE Log

5.3.6 Waveform Log

5.3.7 Event Log

5.4 About

5.5 Settings

5.5.1 Meter Settings

Chapter 6: Communications

6.1 Network

6.1.1 RSTP Protocol

6.1.2 VLAN

6.1.3 Network Settings

6.1.4 Default Routing Interface (Outbound Traffic)

6.2 IPv6

6.3 Certificate Management

6.4 Access Control

6.5 Email

6.6 Time/Date

6.7 Data Log

6.7.1 50ms Fast Log

6.7.2 100ms Fast Log

6.8 Post Channel

6.9 Waveform Post

6.10 AcuCloud

6.11 BACnet/IP

6.12 SNMP

6.13 DNP

6.14 IEC 61850

6.15 EtherNet/IP

6.16 MQTT

6.16.1 MQTT General Settings

6.16.2 MQTT Authentication

6.16.3 MQTT Encryption

4 V: 2.1.4 Revised: September 2024

6.16.4 Last Will & Testament

6.16.5 Top and Parameter Selection

6.17 Google IoT

6.18 Remote Access

6.19 Config Management

6.19.1 Backup Configuration

6.19.2 Export/Apply Configuration

6.19.3 Import Configuration

Chapter 7: Management

7.1 Parameter Reset

7.2 Reboot Meter & Communications Module

7.3 Reset to Factory

7.4 SSH

7.5 Debug Diagnostic

7.6 Diagnostic File

Chapter 8: Network Diagnostic

8.1 Network Status

8.2 Host Lookup

8.3 Connection Test

Chapter 9 Firmware Update

9.1 Module Firmware Update

9.1.1 Auto Firmware Update

9.1.2 Manual Update

9.1.3 Remote Update

9.2 Meter Firmware Update

9.2.1 Manual Update

9.2.2 Remote Update

9.3 Emergency Mode

5V: 2.1.4 Revised: September 2024

AXM-WEB2 for Acuvim II and Acuvim-L Series Power Meters

6 V: 2.1.4 Revised: September 2024

Chapter 1: Introduction to AXM-WEB2 Series Modules

The AXM-WEB2 series modules provide Ethernet, Wi-Fi, or fiber optics LC communication interface for Acuvim II and Acuvim-L series power meters. FOLC

The AXM-WEB2 series modules provide users with an industry leading 100ms and 20ms response rate via Modbus TCP that allow users to attain real time updates to key parameters such as voltage, current and power from the Acuvim II and Acuvim-L Series meter.

1.1 Module Types

AXM-WEB2 series has three available modules: the AXM-WEB2 module (dual Ethernet, Wi-Fi), the AXM-WEB2-FOLC module (1 fiber optic LC, 1 Ethernet, Wi-Fi), and the AXM-WEB2-D module (dual Ethernet).

1.1.1 AXM-WEB2

The AXM-WEB2 is equipped with two Ethernet ports for wired connections and Wi-Fi capability for wireless connectivity, providing a comprehensive networking solution for a wide range of applications.

Ethernet Interface: The dual Ethernet ports allow you to establish wired connections for robust and reliable data transfer. Connect your AXM-WEB2 to your network devices using standard RJ45 Ethernet cables to ensure seamless communication between devices.

Wi-Fi Connectivity: The integrated Wi-Fi feature provides the flexibility of wireless networking.

Easily connect your AXM-WEB2 to a Wi-Fi network for convenient wireless access and communication in environments where wired connections may be impractical.

1.1.2 AXM-WEB2-FOLC

The AXM-WEB2-FOLC features 1 fiber optics LC Interface and 1 Ethernet port, designed for specific applications requiring fast and reliable connectivity. This module includes 1 fiber optics LC interface and 1 Ethernet port for versatile connectivity.

Fiber Optics LC Interface: The Fiber Optic Link Connector (FOLC) connects the AXM-WEB2 FOLC to a fiber optic network. High-speed data transfer and reliable communication with this advanced optical connectivity option.

7V: 2.1.4 Revised: September 2024

Chapter 1: Introduction to AXM-WEB2 Series Modules

1.1.3 AXM-WEB2-D

The AXM-WEB2-D model features two Ethernet ports for establishing a reliable wired connections.

Ideal for applications where signal interference is a concern and the need to prioritize reliability and speed.

1.2 Functional Description of the Ethernet module

The AXM-WEB2 series module supports a wide range of communication protocols. Some of the more commonly used protocols are briefly explained below.

These series modules support the Modbus-TCP protocol. When connected to the Acuvim II or Acuvim-L series meter, it is a slave device that can only respond to queries. The default value for the Modbus Port is 502. The user defined range is 2000~5999.

The AXM-WEB2 series grant users the ability to send emails based on a time interval or from a triggered event using the SMPT protocol. It can send emails from an encrypted server and servers using different SMTP ports.

AXM-WEB2 series protocol supports the HTTPS protocol. It is used as a HTTPS server with the protocol default port value set to 443. Using the HTTPS protocol, the AXM-WEB2 series can send post requests to both HTTP and HTTPS servers.

The following are a list of all the protocols supported by the AXM-WEB2 module series:

•Modbus TCP
•IPv6
•RSTP
•BACnet-IP
•SNMP V2 , V3
•DNP 3.0 V2
•IEC 61850 1st & 2nd Edition
•SMTP, NTP, SNTP, PTP
•HTTP/HTTPs
•FTP
•SFTP
•Wi-Fi WPA, WPA2 Enterprise (AXM-WEB2, AXM-WEB2 FOLC models only)
•EtherNet/IP
•MQTT
•Google IoT

8 V: 2.1.4 Revised: September 2024

Chapter 2: Installation

2.1 Appearance and Dimensions

The dimensions in the following diagram are in millimeters.

Dimensions listed in the brackets are inches.

2.2 Installation Method

The AXM-WEB2, AXM-WEB2 FOLC, or AXM-WEB2-D module is linked to the Acuvim II or Acuvim-L series meter by a communication plug. Additional extended modules such as the I/O modules can be linked to the Acuvim series meter after a AXM-WEB2 series.

1.Remove cover from the back of the Acuvim series meter which will expose the socket.
2.Insert the installation clips to the grooves in the Acuvim series meter and then press the

AXM-WEB2 series module lightly to establish a linking between meter and module.

3. Tighten the installation screws.

WARNING: Do not Install the meter with power on. The module must be installed/ uninstalled while the meter is powered off to prevent injury or damage to the devices.

22.00 (0.866)

.0

(0 .8

.6

(2

.1

90.00 (3.543)

9V: 2.1.4 Revised: September 2024

Chapter 2: Installation

2.3 Cable Connection

The AXM-WEB2 uses two standard RJ45 connectors to access the Ethernet network. The mechanical and electrical characteristics of the connector are consistent with the requirements of

IEC 603-7.

Top View

Pin number Name Description

1 TX+ Transmit Data+ 2 TX- Transmit Data- 3 RX+ Receive Data+ 4 n/c Not connected 5 n/c Not connected 6 RX- Receive Data- 7 n/c Not connected 8 n/c Not connected

LED_L (Yellow): Displays the speed status. When the LED is on it indicates 100Mpbs, whiles an off LED represents a speed of 10Mbps.

LED_R (Green): Displays the link and activity status. When the LED is on it indicates the link status.

When the LED is flashing it indicates that there is activity.

10 V: 2.1.4 Revised: September 2024

2.4 Default Settings

The default settings in the Acuvim II series meter are as followed:

Ethernet 1 Ethernet 2 Wi-Fi (Access Point)

IP address 192.168.1.254 (Static)

DHCP (Dynamic IP address)

192.168.100.1 (static) Subnet Mask 255.255.255.0 255.255.255.0

Gateway 192.168.1.1 n/a DNS Server 1 8.8.8.8 n/a DNS Server 2 8.8.4.4 n/a Modbus Port 502 n/a

By default, Ethernet 2 is configured for DHCP allowing the network will dynamically assign its network properties. To view the Ethernet 2 IP address from the meter’s display the Acuvim II or Acuvim-L meter must be configured to the WEB2 protocol. The following explains how to change the meters protocol settings to work with the WEB2 series module:

2.5 Initializing

• Press the ‘H’ and ‘V/A’ buttons simultaneously on the Acuvim II or Acuvim-L series. Release the buttons and the meter will enter the meter selecting mode, as indicated by the flashing 'Meter' cursor.

• Press the 'P' or 'E' button to move the cursor to 'Setting'. Press 'V/A' button to enter the parameter setting mode. The device address page is the first page of the 'Setting' mode. It will show the Modbus address of the meter for a second before prompting for the password of the device.

• You will be required to type in a password in the ‘PASSWORD’ screen. Leave the password as default ‘0000’ and press ‘V/A’ to enter the parameter selection Mode.

11V: 2.1.4 Revised: September 2024

Chapter 2: Installation

• The cursor will be on ‘SYS’. Press ‘V/A’ on this screen to get to the system settings. This will show screen ‘S01 ADDR’.

•Press the 'E' button until you get to 'S37 PROTOCOL 2'. Select the 'WEB2' protocol.
•Press ‘V/A’ to modify the setting; the cursor should now flash.
•Press ‘P’ or ‘E’ to select 'WEB2'.
•Press ‘V/A’ to confirm the change.

12 V: 2.1.4 Revised: September 2024

Once the protocol 2 setting of the Acuvim II or Acuvim-L meter is configured for WEB2, users can now view all necessary settings in the meters NET settings.

Press the 'H' button to exit the system setting, you will be directed to the parameter selection screen.

Press the 'P' or 'E' button to move the cursor to 'NET' and press the 'V/A' button to enter the Ethernet module settings.

• The first page of the NET Settings will be the N01 DHCP setting. By default, this is configured to Manual. Setting this configuration to Auto will allow the router to assign the meter with an IP address, while manual will allow the user to configure the IP address. Press the 'V/A' button to enter edit mode. Press 'P' or 'E' to change the setting and press 'V/A' to confirm.

NOTE: If the DHCP is selected as Auto, the Ethernet module needs to be rebooted before it can be assigned with the new IP address.

13V: 2.1.4 Revised: September 2024

Chapter 2: Installation

• Press 'P' to get to "N02 IP address" This is the IP address for Ethernet 1 and can be used to access the web interface of the module. Users can configure the IP address if the DHCP is configured to Manual. Press 'V/A' to configure the IP address. The cursor of the first digit will begin to flash. Press the 'H' button to scroll through the digits, press the 'P' or 'E' to change the value of the flashing cursor and press 'V/A' to confirm.

• Press 'P' to get to "N03 Subnet Mask". Press 'V/A' to configure the subnet address. The cursor of the first digit will begin to flash. Press the 'H' button to scroll through the digits, press the 'P' or 'E' to change the value of the flashing cursor and press 'V/A' to confirm.

• Press 'P' to get to "N04 Gateway". Press 'V/A' to configure the gateway IP address. The cursor of the first digit will begin to flash. Press the 'H' button to scroll through the digits, press the 'P' or 'E' to change the value of the flashing cursor and press 'V/A' to confirm.

14 V: 2.1.4 Revised: September 2024

• Press 'P' to get to "N05 DNS Primary Server". Press 'V/A' to configure the DNS address. The cursor of the first digit will begin to flash. Press the 'H' button to scroll through the digits, press the 'P' or 'E' to change the value of the flashing cursor and press 'V/A' to confirm.

The DNS parameters must be set correctly to use the SMTP, FTP/HTTP Post and AcuCloud functions.

• Press 'P' to get to "N06 DNS Secondary Server". Press 'V/A' to configure the DNS address.

The cursor of the first digit will begin to flash. Press the 'H' button to scroll through the digits, press the 'P' or 'E' to change the value of the flashing cursor and press 'V/A' to confirm.

15V: 2.1.4 Revised: September 2024

Chapter 2: Installation

• Press 'P' to get to "N07 Modbus Port". Press 'V/A' to configure the Modbus Port. The cursor of the first digit will begin to flash. Press the 'H' button to scroll through the digits, press the 'P' or 'E' to change the value of the flashing cursor and press 'V/A' to confirm.

• Press 'P' to get to "N08 HTTP Port". Press 'V/A' to configure the HTTP Port. The cursor of the first digit will begin to flash. Press the 'H' button to scroll through the digits, press the 'P' or 'E' to change the value of the flashing cursor and press 'V/A' to confirm.

16 V: 2.1.4 Revised: September 2024

• Press 'P' to get to "N09 NET REST". After making any changes to the NET settings, users must reboot the Ethernet module from this page for the settings to take effect. Press 'V/A' to reboot the module, the cursor will begin to flash. Press the 'P' or 'E' button to change the setting to 'Reset' and press 'V/A' to confirm. The cursor will return to 'No' once the module has successfully reset.

• Press 'P' to get to "N11 Wi-Fi" This is the IP address of Wi-Fi and will be the IP address to access the web interface of the module by using Wi-Fi connection. This IP address cannot be modified from the meters display, it can only be configured on the meter’s web server.

17V: 2.1.4 Revised: September 2024

Chapter 2: Installation

• Press 'P' to get to 'N12 IP2'. This is the IP address for Ethernet port 2, it is preset as dynamic DHCP. A new IP address will be assigned to it when it is connected to the internet via Ethernet port 2.

18 V: 2.1.4 Revised: September 2024

Chapter 3: Connection Method

3.1 Direct Connect to a Computer

The AXM-WEB2 series can be connected to a computer using a crossover cable (standard 568A).

The AXM-WEB2 series module supports Modbus-TCP and HTTPS Functions for this method of connection.

To connect the meter directly to a computer, the computers IP must be within the same subnet as the meters IP address. The following steps outline how to change the computers IP using a Microsoft Windows OS:

•Manually connect the meter cable to the computer using a RJ45 Ethernet cable
•From the Windows OS screen, right click on the connection icon
•Select "Open Network Sharing Center"

• Click on the Change adapter options

19V: 2.1.4 Revised: September 2024

Chapter 3: Connection Method

• From the Network Connections window, right click on the icon with the local area connection and select properties

• Select the icon that says Internet Protocol Version 4 TCP/IP

20 V: 2.1.4 Revised: September 2024

• The Internet Protocol Version 4(TCP/IP) Properties box will pop up

• Click on ''Use the following IP address'' and enter in an IP number so that meter and computer are in the same local network range. For example, if the meter has IP address of 192.168.1.254, then the computer must be assigned with an IP 192.168.1.xxx, where xxx can be any number but cannot be the same as the value the meter has.

21V: 2.1.4 Revised: September 2024

Chapter 3: Connection Method

• Once you have entered in the IP address, press the Tab key on your keyboard until you hit the bottom and click OK

• Before selecting the OK button make note of the IP address you have assigned to the meter and then press OK.

NOTE: The meter and computer cannot have the same IP address, they must be different

3.2 Direct Connect to a Router/Switch

The AXM-WEB2 series can be connected to a router or switch using a patch cable. The DHCP can be configured to Auto to have the router automatically assign the meter with an IP address or the DHCP can be configured to Manual to set an IP address and network settings manually by the user.

AXM-WEB2 and AXM-WEB2-D has two Ethernet ports, Ethernet 1 is set to have the static DHCP, and Ethernet 2 is set to have the dynamic DHCP. Both Ethernet ports have the same functionalities, which can be used according to the requirements.

3.3 Connect through Wi-Fi

The AXM-WEB2 and AXM-WEB2 FOLC can be connected through Wi-Fi network.

By default, the AXM-WEB2 and AXM-WEB2 FOLC will be in Access Point mode with default IP address of 192.168.100.1. Ensure the device connecting to the communication modules has DHCP enabled, or it should be in the same subnet. The module will appear in the Wi-Fi network

22 V: 2.1.4 Revised: September 2024 as AXM-WEB2-WIFI-(serial number of module) as the SSID or name of the wireless network. By default, the network key or password will be ''accuenergy''.

• Once connected to the network, open an internet browser and type in the IP address of the Wi-Fi module: 192.168.100.1

• Log in to the web interface, the default username and password is 'admin'.

3.4 Description of Modbus-TCP Protocol

The Modbus-TCP protocol is used as one of the communication protocols in the AXM-WEB2 series.

The protocol establishes a master and slave connection in Ethernet. The master device(client) first sets up a TCP-IP link with slave device(server). The master device then sends a request to the slave device and the slave device in return sends a response to the master device. Figure below shows how the Modbus-TCP protocol works.

3.4.1 Protocol

3.4.1.1. Data Frame Format

MBAP Header Function Data

7x8 bits 8-bits Nx8 bits

3.4.1.2. Modbus Application Header (MBA Header) Field

Modbus application header field is the start of the data frame and consists of seven bytes.

Field Length Description

Transaction Identifier 2 Bytes Identification of a Modbus

Request/Response transaction Protocol Identifier 2 Bytes Modbus Protocol = 0

Length 2 Bytes Number of following bytes

Unit Identifier 1 Byte Slave address, in the range of 0-247 decimal

Modbus Client Modbus Server

Request Indication

ResponseCon�rmation

23V: 2.1.4 Revised: September 2024

Chapter 3: Connection Method

3.4.1.3. Function Field

The function code field of a message frame contains eight bits. Valid codes are in the range of 1-255. When a message is sent from a client to a server device, the function code field tells the server what kinds of action to perform.

Code Length Description

01 Read Relay Output Status Obtain current status of Relay Output 02 Read Digital Input (DI) Status Obtain current status of Digital Input 03 Read Data Obtain current binary value in one or more registers 05 Control Single Relay Output Force Relay to a state of On or OFF

16 Write Multiple Registers Place specific value into a series of consecutive multiple registers

3.4.1.4. Data Field

The data field is constructed using sets of two hexadecimal digits, in the range of 00 to FF. The data field of messages sent from a master to slave contains additional information which the slave must use to take the action defined by the function code. This can include information such as the register addresses, the quantity of registers to query and the count of the actual number of data bytes. For example, if the master requests a slave to read a group of holding registers (function code 03), the data field specifies the starting register and how many registers are to be read.

If the master needs to write data (function code 10 hexadecimal) to a group of registers in the slave, the data field specifies the starting register, how many registers to write, the count of data bytes to follow in the data field and the data to be written into the registers.

3.4.2 Format of communication

Explanation of frame

Transaction Identifier hi

Transaction Identifier lo

Protocol Identifier hi

Protocol Identifier lo

Length hi Length lo Unit Identifier

00H 00H 00H 00H 00H 06H 01H

Function Code Data Start Register hi

Data Start Register lo

Data # of Register hi

Data # of Register lo

03H 40H 00H 00H 48H

The meaning of each abbreviated field above is:

Transaction Identifier hi: High byte of transaction identifier

Transaction Identifier lo: Low byte of transaction identifier

24 V: 2.1.4 Revised: September 2024

Protocol Identifier hi: High byte of protocol identifier

Protocol Identifier lo: Low byte of protocol identifier

Length hi: High byte of length

Length lo: Low byte of length

Unit Identifier: Slave address

Fun: Function code

Data Start Register hi: High byte of starting register address

Data Start Register lo: Low byte of starting register address

Data # of Registers hi: High byte of number of registers

Data # of Registers lo: Low byte of number of registers

3.4.2.1 Read Status of Relay (Function code 01)

Function Code 1

This function code is used to read the relay output status in the Acuvim II or Acuvim-L series meter.

1=On 0=Off

There are 8 relay outputs in the Acuvim series meter and they start at address 0000H.

The following query is to read 2 relay output status of the Acuvim series address 1.

Query

Transaction Identifier hi

Transaction Identifier lo

Protocol Identifier hi

Protocol Identifier lo

Length hi Length lo Unit Identifier

00H 00H 00H 00H 00H 06H 01H

Fun Data Start Register hi

Data Start Register lo

Data # of Register hi

Data # of Register lo

01H 00H 00H 00H 02H

25V: 2.1.4 Revised: September 2024

Chapter 3: Connection Method

Response

The Acuvim series meter responds back with the MBAP header, function code, quantity of data bytes and the data.

An example of response to read the status of the first 2 relay outputs starting at 0000H is shown below. The status of relay output 1 and 2 is corresponds to the last 2 bits of data.

Relay 1: bit0 Relay 2: bit1

The content of the data is, 7 6 5 4 3 2 1 0

0 0 0 0 0 0 1 0

MSB LSB

(Relay 1 = OFF, Relay 2 = ON)

3.4.2.2 Read Status of DI (Function Code 02)

Function Code 2

1=On 0=Off

There are 28 DIs in the Acuvim II series meter starting at address 0000H.

The following query is to read 4 DI statuses of AXM-IO1 module with logic address of 1 in the Acuvim series meter.

Query

Transaction Identifier hi

Transaction Identifier lo

Protocol Identifier hi

Protocol Identifier lo

Length hi Length lo Unit Identifier

00H 00H 00H 00H 00H 06H 01H

Fun Data Start Register hi

Data Start Register lo

Data # of Register hi

Data # of Register lo

02H 00H 00H 00H 04H

The content of the data is, 7 6 5 4 3 2 1 0

0 0 0 0 0 0 1 0

26 V: 2.1.4 Revised: September 2024

7 6 5 4 3 2 1 0

MSB LSB

3.4.2.3 Read Status (Function Code 03)

Function Code 3

Query

This function allows the user to obtain the measurement results of the Acuvim series meter.

Below is an example to read 6 registers corresponding to the device clock of the meter, starting at 1040H.

Transaction Identifier hi

Transaction Identifier lo

Protocol Identifier hi

Protocol Identifier lo

Length hi Length lo Unit Identifier

00H 00H 00H 00H 00H 06H 01H

Fun Data Start Register hi

Data Start Register lo

Data # of Register hi

Data # of Register lo

03H 10H 40H 00H 06H

An example response is provided to read the time (2006-12-18 14:15:20).

Transaction Identifier hi

Transaction Identifier lo

Protocol Identifier hi

Protocol Identifier lo

Length hi Length lo Unit Identifier

00H 00H 00H 00H 00H 0FH 01H

Fun Byte count Data1 hi Data1 lo Data2 hi Data2 lo Data3 hi Data3 lo Data4 hi Data4 lo Data5 hi Data5 lo Data6 hi Data6 lo

03H 0CH 07H D6H 00H 0CH 00H 12H 00H 0EH 00H 0FH 00H 14H

3.4.2.4 Control Relay (Function Code05)

Function Code 5

Query

This function code enables the control of a single relay output in the Acuvim series meter. Any relay output in the Acuvimseries meter can be controlled on or off starting at 0000H.

Sending the data 'FF00H' will set they relay output on and sending '0000H' will turn it off; all other values are illegal and will not affect they relay output status.

27V: 2.1.4 Revised: September 2024

Chapter 3: Connection Method

The example below is a request to a Acuvim series meter to turn on relay output 1.

Transaction Identifier hi

Transaction Identifier lo

Protocol Identifier hi

Protocol Identifier lo

Length hi Length lo Unit Identifier

00H 00H 00H 00H 00H 06H 01H

Fun Data Start Register hi

Data Start Register lo

Data # of Register hi

Data # of Register lo

05H 00H 00H FFH 00H

Response

The normal response to the command request is to retransmit the message as received after the relay output status has been altered.

Transaction Identifier hi

Transaction Identifier lo

Protocol Identifier hi

Protocol Identifier lo

Length hi Length lo Unit Identifier

00H 00H 00H 00H 00H 06H 01H

Fun Data start reg hi Data start reg lo Value hi Value lo

05H 00H 00H FFH 00H

3.4.2.5 Preset/Reset Multi-Register (Function Code 16)

Function Code 16

Query

This function code allows the user to modify the contents of a register. The example below is a request to an Acuvim series meter with device address 1 to preset the CT1(500) and CT2(5) registers. The CT1 data address is 1008H and CT2 is at 1009H.

Transaction Identifier hi

Transaction Identifier lo

Protocol Identifier hi

Protocol Identifier lo

Length hi Length lo Unit Identifier

00H 00H 00H 00H 00H 0BH 01H

Fun Data start reg hi

Data start reg lo

Data #of reg hi

Data #of reg lo

Byte count

Value1 hi

Value1 lo

Value2 hi

Value2 lo

10H 10H 08H 00H 02H 04H 01H F4H 00H 05H

Response

The normal response to a preset Multi-Register request including the MBAP Header, function code, data start register and the number of registers is shown below.

28 V: 2.1.4 Revised: September 2024

Transaction Identifier hi

Transaction Identifier lo

Protocol Identifier hi

Protocol Identifier lo

Length hi Length lo Unit Identifier

00H 00H 00H 00H 00H 06H 01H

Fun Data start reg hi Data start reg lo Data #of reg hi Data #of reg lo

10H 10H 08H 00H 02H

29V: 2.1.4 Revised: September 2024

Chapter 4: User Management

The AXM-WEB2, AXM-WEB2 FOLC, and AXM-WEB2-D modules support the HTTPS protocol to allow for the use of a web interface. The user will need to access the AXM-WEB2 series web interface to configure the module and use its functions. The web interface allows for remote initial setup of the Acuvim II and Acuvim-L meters.

The AXM-WEB2 series web interface allows for different user access levels where multiple users and role configurations can be made.

To access the web interface the IP address for the WEB2 series module, either Ethernet 1, Ethernet 2 or a Wi-Fi IP address must be known.

4.1 User Access Login

Enter the correct IP address of the module in the search bar of the internet browser to access the web interface of the AXM-WEB2 series. The user will be redirected to a web page prompting to enter the User Name and the appropriate password for that user. It is recommended that no more than five users are logged in concurrently for this level to ensure optimal performance when using the web interface.

The default User Name is admin and the default password for this user name is also admin.

User Name: admin

Password: admin

Chapter 4: User Management

30 V: 2.1.4 Revised: September 2024

4.2 User Configuration

The AXM-WEB2 series supports the creation of different users for the web interface. Each user can be assigned different roles to determine what permissions and functions users will have when logged in. To access the user configuration page, click on the User Management tab and select User Configuration.

The user configuration table provides information regarding the user access level, such as the register date, expiration date and last login time. If the correct permission is available for the account, the user will have the option to lock an account, and edit and delete users.

NOTE: Users cannot lock or delete an account they are already signed into.

New users can be added with available options to enter an user name, password, role, and option to set the password policy. The role determines the type of access the user will have on the user level created. Users have the option to override the default password policy which is a set of rules for allowable passwords on the AXM-WEB2 series interface, this includes length and complexity of the password (capital letters, number, special characters, etc.).

31V: 2.1.4 Revised: September 2024

Chapter 4: User Management

4.3 Role Configuration

The Role Configuration page allows users to configure and create different roles for user levels.

These roles determine whether the user has edit, view or no access to certain features while logged onto the web interface. By default, there are two roles on the module, Admin and View.

The Admin role allows the user to view and configure all settings whereas the View role allows users to only view meter readings.

Reading Permissions: Allows users to either edit or view the meter readings, this includes all readings such as real time, energy, harmonics, demand, etc. This also includes access to data logs, trend logs, alarm logs and SOE logs.

Configuration Permissions: Allows users to edit or view the meter configurations such as the CT/ PT ratio, alarms, and communication settings.

Maintenance Permissions: Allows users to access Firmware updates, both module and meter firmware update options.

32 V: 2.1.4 Revised: September 2024

4.4 Password Policy

The Password Policy page provides users with a method to ensure that all passwords created follow specific criteria. The password policy lists specific details relating to the password that some users may find beneficial for security purposes. When creating a user password there is an option to override the password policy if necessary.

4.5 Password Management

The Password Management page allows users to change the password for each user levels created.

33V: 2.1.4 Revised: September 2024

Chapter 4: User Management

4.6 API Token Management

Provides users with the API token for the web interface. This token can be reset and a new one will be generated.

34 V: 2.1.4 Revised: September 2024

Chapter 5: Web Interface Readings and Parameter

Settings

5.1 Dashboard

In the Dashboard page, the user will find the navigation tabs to access different pages in the web interface such as 'Metering', 'Logs', and 'Settings'. The dashboard is the first page users will see once they have successfully logged in to the meters web interface.

The dashboard displays a summary from different groups of metering parameters such as 'Basic Metering', 'Power & Energy', 'THD' and 'Max Demand'. By clicking on the "Full Report" link under any one of these four metering parameter groups the user will be redirected to the web page containing the full parameter list supported by that specific group.

The dashboard also displays how long the AXM-WEB2 series module has been connected to the network since the last reboot of the module in the bottom left corner of the page.

The parameters on this page are updated every five seconds.

5.2 Metering web page

Click on the 'Metering' tab to select the different kinds of parameter readings. There are eight groups of metering parameter pages including "Basic Metering", "Power & Energy", "Min/Max", 'THD', 'Harmonics', "Phase Angles", ''Sequence'' and ''I/O''. Each web page shows data from the Acuvim II or Acuvim-L series meter.

35V: 2.1.4 Revised: September 2024

Chapter 5: Web Interface Readings and Parameter Settings

5.2.1 Basic Metering

The Basic Metering webpage includes the data of real-time parameters for the Acuvim II or Acuvim-L series meter. This includes the Line Voltages, Phase Voltages, Current, Neutral Current, Active, Reactive and Apparent Power, Power Factor, Frequency and Load type.

The parameters on this page are updated every one second.

The values displayed in this webpage will depend on the wiring configuration mode of the meter.

For example, if the meter is configured as '2LL' or '3LL' then the metering webpage will not display the phase readings, only the total values will be shown.

5.2.2 Power & Energy

The Power & Energy webpage will show the energy data for the Acuvim II or Acuvim-L series meter such as the Active and Reactive Energy that is consumed and delivered as well as the total and per phase Apparent Energy. This page also shows the different demand types measured by the Acuvim II or Acuvim-L meter such as the Active, Reactive, Apparent Power as well as the three phase Current demands.

The parameters in this webpage are updated every five seconds.

36 V: 2.1.4 Revised: September 2024

From the Power & Energy page, the user will have the option to edit and write new Energy values.

Simply click on the 'Manual Edit' button to edit the energy values.

This will be important for users who want to start and monitor energy accumulation at a determined kilowatt-hour reading. All energy parameters including individual phase, total, import, export, and net for the real, reactive and apparent energy support this feature.

5.2.3 Min/Max

The Min/Max page shows the maximum and minimum statistics that the meter has recorded since the lifetime of the meter or from the last reset of the min/max statistics. On this page, each parameter will show the maximum and minimum timestamped events that was recorded.

The parameters in this web page are updated every ten seconds.

37V: 2.1.4 Revised: September 2024

Chapter 5: Web Interface Readings and Parameter Settings

5.2.4 THD

The THD web page shows the power quality data such as the THD, THFF, Crest, and K Factor for both the voltage and current.

The parameters in this web page are updated every fifteen seconds.

5.2.5 Harmonics

The Harmonics web page will show the harmonics of the voltage and the current waveform being measured. It will display the harmonics of each phase in graphical and tabular format. Two drop-down lists is available to configure the harmonics data. First option allows the selection between voltage and current. Second option provides a choice between 2nd - 31st harmonics or 32nd - 63rd harmonics.

The parameters in this web page are updated every fifteen seconds.

38 V: 2.1.4 Revised: September 2024

5.2.6 Phase Angles

The Phase Angles web page will show the phase angles of the voltage and current waveform being measured which can be used for remote troubleshooting. This page provides a visual diagram of the phase angles with respect to the voltage connected to the Phase A voltage input.

The parameters in this web page are updated every ten seconds.

5.2.7 Sequence

The Sequence page will show the positive, negative and zero components of the voltage and current waveform being measured.

39V: 2.1.4 Revised: September 2024

Chapter 5: Web Interface Readings and Parameter Settings

The parameters in this web page are updated every ten seconds.

5.2.8 I/O

The I/O page displays the status of the I/O modules that are connected and their values depending on the module model connected to the meter. That is, the AXM-IO11 module will display the Relay Output status(on/off), DI status/counter. The I/O module can be configured in the general settings section of the web interface which is discussed later in the manual.

The parameters in this web page are updated every five seconds.

From the I/O readings page, users can perform the following functions depending on the I/O module being used:

IO Module Functions

AXM-IO1-1/2 • Read Digital Input Status or Digital Input Count value depending on the mode configured (Channels 1-6)

•Reset DI Counter back to 0 (Counters 1-6)
•Read the Relay Output Channel 1 and 2 Status ON/OFF
•Toggle Relay Output Channels 1 and 2 ON/OFF

NOTE: Relay must be configured for Control Mode for toggle function to work

AXM-IO2-1/2 • Read Digital Input Status or Digital Input Count value depending on the mode configured (Channels 1-4)

•Reset DI Counter back to 0 (Counters 1-4)
•Read value of the Analog Output Channels 1 and 2, either 4-20mA, 0-20mA, 0-5V,

1-5V signals

40 V: 2.1.4 Revised: September 2024

IO Module Functions

AXM-IO3-1/2 • Read Digital Input Status or Digital Input Count value depending on the mode configured (Channels 1-4)

•Reset DI Counter back to 0 (Counters 1-4)
•Read the Relay Output Channel 1 and 2 Status ON/OFF
•Toggle Relay Output Channels 1 and 2 ON/OFF
•Read value of the Analog Input channels 1 and 2, either 4-20mA, 0-20mA, 0-5V,

1-5V signals

NOTE: Relay must be configured for Control Mode for toggle function to work

5.3 Logs

Click on the 'Logs' navigation tab to visit the metering logs web pages.

There are six kinds of logs that can be viewed, they are "Trend Log", "Trend Log Management", "Data Log", "Alarm Log", "SOE Log", "Waveform Log"(Only available in Acuvim IIW model) and “Event Log”.

Each web page shows data from the Acuvim II or Acuvim-L series meter.

41V: 2.1.4 Revised: September 2024

Chapter 5: Web Interface Readings and Parameter Settings

5.3.1 Trend Log

The Trend Log web page includes the Realtime trend diagram and Energy trend diagram. The Realtime menu tab can be selected to show the trend log diagram for the following parameters phase voltage, line voltage, current, active power, reactive power, apparent power, and power factor for each phase as well as the totals. The Energy menu tab show the trend log for the imported and exported active energy, reactive energy, total energy, net energy, and apparent energy.

The data of the trend log can be previewed and downloaded as a .csv file by clicking the 'Data Review' and 'Data' icons on the right top side of the diagram. The trend log diagram can also be saved as an image by clicking the 'Image' icon.

5.3.1.1 Realtime

The real time parameters can be trended at different time intervals depending on the time frame selected. Listed below are the time intervals for each possible time frame setting:

Time Frame Time Intervals

Last 10 minutes 1 second

15 seconds

1 minute

Last 1 Hour 1 minute

Today 15 minutes

1 hour

Yesterday 15 minutes

1 hour

Last 7 days 15 minutes

1 hour

1 day

Last 30 days 1 hour

1 day

Last Month 1 hour

1 day

Custom Range Dependent on range specified

42 V: 2.1.4 Revised: September 2024

5.3.1.2 Energy

The Energy parameters can be trended at different time intervals depending on the Time Frame selected. The table below displays the time intervals:

Time Frame Time Intervals

Last 10 minutes 15 seconds

1 minute

Last 1 Hour 1 minute

Today 15 minutes

1 hour

Yesterday 15 minutes

1 hour

Last 7 days 15 minutes

1 hour

1 day

Last 30 days 1 hour

1 day

Last Month 1 hour

1 month

Custom Range Dependent on range specified

43V: 2.1.4 Revised: September 2024

Chapter 5: Web Interface Readings and Parameter Settings

5.3.1.3 Data Preview

The data preview allows the user to view the graphical data in tabular form.

User can also download this data into a CSV file for further examination.

5.3.2 Trendlog Management

The Trendlog Management page allows the user to download data from the meters database.

The Trendlog Management page acts as a backup to the data logs.

Log Param Type: Users can select which data they want to download from the meter. In the drop-down menu there is a timestamp range that shows the available data.

NOTE: Energy data will remain in meter database for up to 3-years, whereas all other metering data will

44 V: 2.1.4 Revised: September 2024 remain in the meter database for up to 1-month before overriding.

Log Param Type Detail: This setting allows users to modify what values they see in the data log.

Users can select the following parameter details:

•Instantaneous
•Minimum
•Maximum
•Average

Only the 'Real-time' and 'Demand' parameters support the minimum, maximum and average parameter type details. All other parameter types such as Energy, Power Quality, and IO only support the instantaneous values displayed in the data log.

The log file will be downloaded as a .gz file and will need to be unzipped to view the CSV file.

45V: 2.1.4 Revised: September 2024

Chapter 5: Web Interface Readings and Parameter Settings

5.3.2.1 Clear Logs

The clear logs function allows the user to clear and remove all metering data stored on the module database. This will allow users to clear all readings and historical data without resetting all features and functions. Users can find the clear logs function at the bottom of the Trendlog page.

To clear the logs, click on the "Clear Logs" button. A warning message is will notify the user that this action is permanent and cannot be reversed once done.

WARNING: Clear logs cannot be undone, once the trend log is cleared all data stored in the meter database is permanently deleted forever.

5.3.3 Data log

The Data Log web page includes all the data log files for the three different loggers, Acucloud, and 50/100ms loggers.

You can select each loggers by clicking the logger tab. After the logger is selected, the log file for this logger will show on the screen with the update time and file size. To download a file, click on the download icon to save the file in the computer. The data log will be saved as a compressed CSV file. To download multiple files as once. Check the box next to the data log files and click on the “Download Selected” button.

46 V: 2.1.4 Revised: September 2024

5.3.3.1 Deleting Data Logs

To delete the data logs users can check the box next to the data log file and click on the 'Delete Selected' button at the bottom of the page.

Users will be prompted by a window asking to confirm the data log delete.

WARNING: Deleting the data log is permanent, this cannot be undone once this action is performed.

5.3.4 Alarm Log

The Alarm Log web page provides the user with a summary of the alarm events that have occurred with the meter. It will show the status of up to sixteen (16) alarm events indicating the alarm ID, status, parameter, value that exceeded or falls below the threshold, and the timestamp of the alarm event.

Once all sixteen (16) alarm events are full, the newest alarm event will then wrap around to alarm 1.

The parameters in the alarm status web page are updated every ten seconds.

47V: 2.1.4 Revised: September 2024

Chapter 5: Web Interface Readings and Parameter Settings

5.3.5 SOE Log

The SOE Log web page will display the Sequence of Event log for the enabled I/O module that is attached to the Acuvim II series meter with timestamps and will display the DI status for up to 20 SOE events.

The SOE log parameters are updated every ten seconds.

48 V: 2.1.4 Revised: September 2024

5.3.6 Waveform Log

The Waveform Log is available only on Acuvim IIW models of the Acuvim II series meter. This meter supports a waveform capture function that allows users to capture and record ten cycles before and after the triggering point whether it be a voltage sag, swell, or over current. The waveform log on the web interface allows users to view these waveforms whenever a power quality event has occurred. The log displays a table list of the waveform files, the time the waveform was updated, and the file size. The waveform file name includes the timestamp when the event occurred as well as the parameter name/event name that triggered the power quality event.

To view the waveform data click on the bar graph icon .

The waveform graph screen will have the option for users can select which voltage or current phase they want to view during the power quality event.

An image of the graph can be downloaded by clicking on the download icon .

Users can zoom into the graph for further detail by clicking on the magnify icon . The graph can be reset back by double clicking the button.

49V: 2.1.4 Revised: September 2024

Chapter 5: Web Interface Readings and Parameter Settings

Users can select 'Close' link to exit the waveform graph and return to the Waveform Log page.

Users can enable the manual waveform capture function by clicking on 'Manual Capture' button.

This will allow the user to manually capture voltage and current waveforms of the system being monitored. Once the waveform is capture it will take approximately 1-2 minutes to appear in the waveform log.

The file name for the manually captured waveform will include the timestamp the event occurred, and the text 'MANUAL' will be appended at the end of the file name.

50 V: 2.1.4 Revised: September 2024

In the Waveform Log page, the option to select and delete waveform files is available. Simply click on the check box next to the individual files to select it, alternatively ‘Select All’ can be checked to select all the files. Once all desired files are selected, click on “Delete Selected” to remove the files from the waveform log.

5.3.6.1 COMTRADE

The AXM-WEB2 series allows users to download the waveform data as a COMTRADE file.

COMTRADE is a file format for storing waveform data related to transient power system disturbances.

The file can be downloaded from the waveform log by clicking on the file name or by clicking on the button. Once downloaded the file can be read using a COMTRADE file reader where users can further analyze the waveform data provided from the meter.

5.3.7 Event Log

The AXM-WEB2 series provide the event log page for the user to track the activities of the module.

51V: 2.1.4 Revised: September 2024

Chapter 5: Web Interface Readings and Parameter Settings

The user can specify the event level and source by choosing the level and the source type.

To clear the event logs, click “Clear Event Log”. Then click “Yes” when prompted to continue. Users can also export the Event log where it can be exported as a .csv file.

5.4 About

The About menu tab located at the top right corner of the web interface allows users to view the Device Information page. This page provides users with information about the Acuvim II or Acuvim-L series meter and the AXM-WEB2 series module. The Device Information contains the model of the Acuvim II or Acuvim-L meter, serial number, firmware version and the meter addresses. It also contains the serial number, firmware version, hardware version and the MAC addresses of the AXM-WEB2 series module.

The disk usage field at the bottom of the device information page allows users to view the percentage of the memory that is used on the AXM-WEB2 series module.

52 V: 2.1.4 Revised: September 2024

5.5 Settings

5.5.1 Meter Settings

5.5.1.1 General Settings

The basic metering settings needed for installation and commissioning can be done from the web interface. To access these settings users can click on Settings and select the 'Meter' menu tab. On the metering tab users will see the 'General' tab from the submenu selected and the following page presented.

The general page allows users to configure the following settings:

Device Description: A description for the meter can be provided in this field and will be displayed on the Dashboard page.

53V: 2.1.4 Revised: September 2024

Chapter 5: Web Interface Readings and Parameter Settings

Voltage Wiring: Select the type of wiring that the meter will be monitoring from the modes in the drop down list.

Current Wiring: Select the number of CT's that will be connected to the meter to measure the current.

PT1: Enter the rated input of the potential transformer that is connected to the meter. Possible range is from 50 to 1,000,000V. By default, PT1 is 400.

PT2: Enter the rated output of the potential transformer. Possible range is from 50 to 400V. The default PT2 setting is 400.

NOTE: If the voltage input is connected directly to the meter and there are no potential transformer (PT) stepping down the voltage to the meter’s voltage input then the PT1 and PT2 settings can be left as the default value of 400.

CT1: Enter the rated input of the current transformer (CT) that is used with the meter. Possible ranges for the CT1 are from 1 to 50000A.

The default settings for CT1 are dependent on the current input type of the Acuvim II or Acuvim-L meter. The following table displays the default CT1 values for the different current input options.

Acuvim II Current Input Default CT1 Value

1A 1

5A 5

80mA/100mA/200mA 1

333mV 1

RCT 1000

54 V: 2.1.4 Revised: September 2024

CT2: Select the rated output of the current transformer from the drop down list. By default this setting is already configured.

NOTE: CT2 is configurable only for 5A and mA current inputs, 5A can be either 5A or 1A and mA can be either 80mA, 100mA or 200mA.

I4 Method: Represents the Neutral Current Value (I N Value) calculating method – The neutral current value can be configured as either Calculated or Measured.

•Calculated: If Calculated is selected, the I4 readings will be calculated based on IA, IB, IC.
•Measured: If Measured is selected, the I4 readings will be measured independently based

on the independent CT41 and CT42 values.

Real Time Reading: Select the mode of the readings for the meter when it is polled through Modbus. Default setting for the meter is Secondary mode, which will require some parameters to be scaled by a relationship. Configuring the meter in Primary mode does not require any scaling.

I A Direction: Represents the flow of direction for the Phase A current being measured, configure this setting to troubleshoot issues related to incorrect polarity of readings such as real power, power factor and other parameters.

I B Direction: Represents the flow of direction for the Phase B current being measured, configure this setting to troubleshoot issues related to incorrect polarity of readings such as real power, power factor and other parameters.

I C Direction: Represents the flow of direction for the Phase C current being measured, configure this setting to troubleshoot issues related to incorrect polarity of readings such as real power, power factor…

This is the start of the file's text. The full file is on GovTribe.