Acuvim-II-Advanced-Power-and-Energy-Meter-Datasheet.pdf
PDF 2 MB Posted
- Attached to
- Design-Build (DB) Barracks Initiative (Package #2), Marine Corps Base (MCB) Camp Lejeune, North Carolina
- Solicitation number
- Not on record
About this file
This document is a product datasheet for the Acuvim II Advanced Power & Energy Meter, a multifunction power monitoring device manufactured by Accuenergy. The meter is available in two models: Acuvim IIR (with data logging and time-of-use functionality) and Acuvim IIW (with added waveform capture and power quality event logging). Both models are available in LCD display panel mount or DIN rail transducer configurations and support multiple current input options including 5A/1A, 333mV, Rogowski coil, and 80mA/100mA/200mA inputs. Power supply options include 100–415Vac 50/60Hz with 100–300Vdc or 20–60Vdc low voltage DC.
The meter achieves ANSI C12.20 class 0.1 and IEC 62053-22 class 0.1s revenue-grade accuracy for energy measurement, with 0.1% accuracy across voltage, current, power, reactive power, apparent power, and frequency parameters. Key capabilities include IEC 61000-4-30 Class S compliant power quality measurements, four tariff time-of-use energy tracking, 512 samples per cycle measurement, 20ms Modbus refresh rates, 8MB onboard memory expandable to 8GB with the WEB2 module, and support for multiple communication protocols via optional modules including Modbus RTU/TCP, BACnet MS/TP and IP, IEC 61850, Ethernet, Wi-Fi, PROFIBUS, and EtherNet/IP. Optional I/O modules support digital inputs and outputs, relay outputs, pulse outputs, analog inputs and outputs, and up to 16 alarm configurations. The document includes detailed specifications, function lists, wiring diagrams for various configurations, and ordering information for the base meter and optional communication and I/O modules.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| AXM-WEB2-user-manual.pdf | ||
| FX90 Cutsheet.pdf | ||
| Simplex 4100ES.pdf | ||
| Attachment 1 - Company Information.docx | DOCX document | |
| EC-BOS-9_SP Cutsheet.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Acuvim II Advanced Power & Energy Meter | Datasheet | 1
DESCRIPTION
Acuvim II Advanced Power & Energy Meter Datasheet
FEATURES
+ Revenue Grade: ANSI C12.20 class 0.1 & IEC 62053-22 class 0.1s.
+ 4th CT input to measure neutral current.
+ Dual Ethernet ports with both RSTP bridge daisy-chain mode and separately configurable network.
+ High-resolution frequency measurement utilizes a custom moving average filter with 0.001Hz and 10mHz accuracy. Window size ranges from 1 - 50 cycles, and update rate varies from 1 - 2 cycles.
+ Data logging available with 8MB onboard memory and expandable to 8GB with WEB2 module.
+ IEC 61000-4-30 Class S compliant power quality event measurements for Acuvim IIW.
+ High-speed update rate.
Fast Read mode offers a 20ms Modbus refresh rate, Fast Log is available at 100ms and 50ms intervals via Modbus RTU and TCP/IP.
+ Compatible with multiple CT output options including 5A mA, Accuenergy Rogowski coil, or 333mV.
+ Modbus-RTU & BACnet MS/ TP ready. Optional modules add support for multiple industrial protocols & interfaces such as Modbus- TCP/IP, BACnet-IP, IEC 61850 2nd Ed., Wi-Fi, & EtherNet/IP.
The Acuvim II Series advanced power and energy meter is a robust solution for power monitoring, kWh metering, power quality analysis, and more. This multifunction meter is engineered for easy integration into any project environment and is compatible with a wide array of plug-in expansion modules to facilitate communication on over 15 different industry-standard protocols.
Its two available form factors include a panel mount meter with a digital display and a DIN rail transducer configuration.
With IEC 61000-4-30 Class S compliant power quality analysis, Acuvim IIW can monitor key PQ events such as harmonics, voltage swells and more.
C12.20 .5 CLASS
NEW
NEW
NEW
NEW
NEW
NEW
EN55011
KEY FEATURES
Communication
+ Modbus RTU protocol and BACnet MS/TP via RS485 + Wi-Fi and Ethernet Communication Channels (Modbus TCP, BACnet IP, HTTP, SMTP, SNTP, HTTPs, Post, FTP)
+ PROFIBUS DP
+ Dual RJ45 ports with RSTP daisy-chain and two individually configurable Ethernet ports
Data Logging
+ Acuvim II meters offer three assignable historical logs and a real-time clock to record many metering parameters with accurate timestamping. Add the AXM WEB2 module to expand the memory to 8GB with an adjustable log size.
+ WEB2 module offers additional granularity to data logging such as 1 second interval timing and max/ min/average and instantaneous reading for real time parameters.
Fast Response
+ 512 samples per cycle for measurement, 100ms and 20ms Modbus refresh rate, and 100ms and 50ms options Fast Logging for real time parameters including Frequency and Active Power.
Flexible Current Transformer Options
+ The Acuvim II is directly compatible with Rogowski coils plus a variety of other current transformer outputs, including 5A, 1A, 80mA, 100mA, 200mA, and 333mV. All CTs are available from Accuenergy.
Power Quality Measurements
+ Acuvim IIW offers IEC 61000-4-30 Class S compliant power quality event measurements. It is designed for monitoring and diagnosing power quality issues to improve efficiency and reliability, and enhance overall system performance. Perfect for energy management systems, building automation systems, and more.
Time of Use
+ Users can assign up to four tariffs (sharp, peak, valley, & normal) to different time periods within a day. The Acuvim II meter will calculate and accumulate energy to different tariffs according to the meter’s internal clock and TOU settings.
Optional I/O Module
+ Expand Acuvim II I/O functionality by connecting an optional I/O module. A maximum of three modules can be used per meter. Digital input, digital output, pulse output, relay output, analog input, and analogue output I/O modules are available.
Alarms
+ Limits can be set for up to 16 indicated parameters with a specified time interval. Parameters that are over or under the setting limit and persist longer than the specified time interval will be recorded and trigger the Alarm DO. Choose from 80 available parameters.
APPLICATIONS
+ Submetering
+ Energy Storage, Microgrids, and VPPs
+ Power Generation
+ Load Banks
+ Building Automation
+ PDUs and Data Centers
+ Energy Management Systems
+ Substation and Distribution Systems
+ Transformer Monitoring
+ Measurement & Verification
Acuvim II Advanced Power & Energy Meter | Datasheet | 3
SPECIFICATIONS
Metering
PARAMETERS ACCURACY RESOLUTION RANGE
Voltage 0.1% 0.1V 10V~1000kV
Current 0.1% 0.1mA 5mA~50000A
Power 0.1% 1W -9999MW~9999MW
Reactive Power 0.1% 1var -9999Mvar~9999Mvar
Apparent Power 0.1% 1VA 0~9999MVA
Power Demand 0.1% 1W -9999MW~9999MW
Reactive Power Demand 0.1% 1var -9999Mvar~9999Mvar
Apparent Power Demand 0.1% 1VA 0~9999MVA
Power Factor 0.1% 0.001 -1.000~1.000
Frequency 0.001% 0.001Hz 45.00~65.00Hz
Energy
Primary 0.1 0.1% 0.1kWh 0-99999999.9kWh
Primary 0.001 0.1% 0.001kWh 0-999999.999kWh
Secondary 0.1% 0.001kWh 0-999999.999kWh
Reactive Energy
Primary 0.1 0.1% 0.1kvarh 0-99999999.9kvarh
Primary 0.001 0.1% 0.001kvarh 0-999999.999kvarh
Secondary 0.1% 0.001kvarh 0-999999.999kvarh
Apparent Energy
Primary 0.1 0.1% 0.1kVAh 0-99999999.9kVAh
Primary 0.001 0.1% 0.001kVAh 0-999999.999kVAh
Secondary 0.1% 0.001kVAh 0-999999.999kVAh
Harmonics 1.0% 0.10%
Phase Angle 2.0% 0.1° 0.0°~359.9°
Unbalance Factor 2.0% 0.10% 0.0%~100.0%
Running Time 0.01h 0~9999999.99h
Communication
Modbus-RTU or BACnet MS/TP
Modbus-RTU 2-Wire Shielded Twisted Pair Cable Connection 2400~115200 bps
SECOND RS-485 PORT
(OPTIONAL MODULE)
Same as the Primary RS485 port Baud Rate: 4800~38400 bps
ETHERNET
(OPTIONAL MODULE)
Ethernet 10M/100M BaseT
MODBUS-TCP/IP
DNP 3.0 V2 Over IP Level 2 IEC 61850 2nd Ed.
SNMP V3
BACnet-IP HTTP/HTTPs Webserver HTTP/HTTPs, FTP data post
SMTP
MQTT
MV90
NTP
PROFIBUS
(OPTIONAL MODULE)
PROFIBUS-DP/V0 Protocol Work as PROFIBUS Slave, Baud Rate Adaptive, up to 12M Model 1: Input Bytes: 32, Output Bytes: 32 Model 2: Input Bytes: 64, Output Bytes: 2 PROFIBUS Standard According to EN 50170 Vol. 2
Input
CURRENT INPUTS (EACH CHANNEL)
Nominal Current Options 5A, 1A, 333mV, Rogowski Coil, 80mA/100mA/200mA
Metering Range 0-10A, 0-2A, 0-400mV, 0-400mV, 0-240mA
Pickup Current 5mA, 1mA, 0.25mV, 0.25mV, 0.15mA
Withstand 20Arms Continuous, 0.1% of Nominal 100Arms for 1 Second, Non-Recurring
Burden 0.05VA (Typical) @ 5A RMS
Accuracy 0.1% at Reading
VOLTAGE INPUTS (EACH CHANNEL)
Nominal Full Scale 480Vac L-N, 828Vac L-L
Withstand 1500Vac Continuous 2500Vac, 50/60Hz for 1 Minute
Input Impedance 2MΩ per Phase
Metering Frequency 45Hz~65Hz
Pickup Voltage 10Vac
Accuracy 0.1% at Reading
ENERGY ACCURACY
Active Class 0.1s (According to IEC 62053-22) Class 0.1 (According to ANSI C12.20)
Reactive Class 0.5s (According to IEC 62053-24)
HARMONIC RESOLUTION
Metered Value 63rd Harmonic
Acuvim II Advanced Power & Energy Meter | Datasheet | 4
SPECIFICATIONS
I/O Options
DIGITAL INPUT
Input Type Dry
Input Resistance 100kΩ
Input Voltage Range 20~160 Vac/dc
Input Current (Max) 2mA
Start Voltage 15V
Stop Voltage 5V
Pulse Frequency (Max) 100Hz, 50% Duty Ratio (5ms ON and 5ms OFF)
SOE Resolution 2ms
DIGITAL OUTPUT (DO) (PHOTO-MOS)
Voltage Range 0~250Vac/dc
Load Current 100mA (Max)
Output Frequency 25Hz, 50% Duty Ratio (20ms ON, 20ms OFF)
Isolation Voltage 2500Vac
RELAY OUTPUT (RO) (NO, Form A)
Switching Voltage (Max) 250Vac, 30Vdc
Load Current 5A (R), 2A (L)
Set Time 10ms (Max)
Contact Resistance 30mΩ (Max)
Isolation Voltage 2500Vac
Mechanical Life 1.5x107
ANALOG OUTPUT (AO)
Output Range 0~5V, 0~20mA 1~5V, 4~20mA Optional
Accuracy 0.50%
Temperature Drift 50ppm/°C Typical
Isolation Voltage 500Vdc
Open Circuit Voltage 15V
ANALOG INPUT (AI)
Input Range 0~5V, 0~20mA 1~5V, 4~20mA Optional
Accuracy 0.20%
Temperature Drift 50ppm/°C Typical
Isolation Voltage 500Vdc
POWER SUPPLY FOR DI (24 VDC)
Output Voltage 24Vdc
Output Current 42mA
Load (Max) 21 DIs
Control Power Universal AC or DC
AC/DC CONTROL POWER
Operating Range 100~415Vac, 50/60Hz; 100~300Vdc
Burden 5W
Frequency 50/60Hz
Withstand 3250Vac, 50/60Hz for 1 Minute
Installation Category III (Distribution)
LOW VOLTAGE DC CONTROL POWER (P2V3 Option Only)
Operating Range 20~60Vdc
Burden 5W
Operating Environment
Operating Temperature -25°C to 70°C -13°F to 158°F
Storage Temperature -40°C to 85°C -40°F to 176°F
Relative Humidity 5% to 95% Non-Condensing
Standard Compliance & Certifications
Measurement Standard IEC 62053-22;
ANSI C12.20; IEC61557-12
Environmental Standard IEC 60068-2, CE, RoHS
Safety Standard IEC 61010-1, UL 61010-1
EMC Standard
IEC 61000-4/-2-3-4-5-6-8-11, CISPR
22, IEC 61000-3-2, IEC 61000-6-2/4,
EN55011
Outlines Standard DIN 43700, ANSI C39.1
Protocol Conformance IEC 61850 2nd Ed.
BTL Listed for B-SA
Acuvim II Advanced Power & Energy Meter | Datasheet | 5
FUNCTION LIST
Function; Option; Blank NA
REAL TIME MEASURING Parameters Acuvim IIR Acuvim IIW
Phase Voltage V1, V2, V3, VInavg Line Voltage V12, V23, V31, VIIavg
Current I1, I2, I3, In, Iavg
Power P1, P2, P3, Psum
Reactive Power Q1, Q2, Q3, Qsum
Apparent Power S1, S2, S3, Ssum
Power Factor PF1, PF2, PF3, PF
Frequency F
Load Features L/C/R
Four Quadrant Powers Four Quadrant Powers
4-30 CLASS S READINGS
10/12 Cycle 150/180 Cycle 10 Minutes 2 Hours
F,V1,V2,V3,Vlnavg, V12,V23,V31,Vllavg, I1,I2,I3,In,Iavg, THD_V, THD_I, Unbalance Factor Sequence Readings Current Harmonic Amplitude Voltage Harmonic Amplitude
INDEPENDENT CHANNEL
System Phase Voltage V1, V2, V3, Vlnavg
System Line Voltage V12, V23, V31, Vllavg
System Frequency F
Current Ichannel1, Ichannel2, Ichannel3, Ichannel4, Isum_1avg, Isum_2avg
Power Pchannel1, Pchannel2, Pchannel3, Pchannel4, Psum_1, Psum_2
Reactive Power Qchannel1, Qchannel2, Qchannel3, Qchannel4, Qsum_1, Qsum_2
Apparent Power Schannel1, Schannel2, Schannel3, Schannel4, Ssum_1, Ssum_2
Power Factor PFchannel1, PFchannel2, PFchannel3, PFchannel4, PFsum_1, PFsum_2
Load Features Load Features
Four Quadrant Powers Four Quadrant Powers
Energy
Epchannel1_imp, Epchannel2_imp, Epchannel3_imp, Epchannel4_imp Epchannel1_exp, Epchannel2_exp, Epchannel3_exp, Epchannel4_exp Epsum1_imp, Epsum2_imp, Epsum1_exp, Epsum2_exp Epsum1_Totoal, Epsum2_Total, Epsum1_Net, Epsum2_Net
Reactive Energy
Eqchannel1_imp, Eqchannel2_imp, Eqchannel3_imp, Eqchannel4_imp, Eqchannel1_exp, Eqchannel2_exp, Eqchannel3_exp, Eqchannel4_exp, Eqsum1_imp, Eqsum2_imp, Eqsum1_exp, Eqsum2_exp, Eqsum1_Total, Eqsum2_Total, Eqsum1_Net, Eqsum2_Net
Apparent Energy Eschannel1, Eschannel2, Eschannel3, Eschannel4, Essum1, Essum2
Demand
Dmd_Pchannel1, Dmd_Pchannel2, Dmd_Pchannel3, Dmd_Pchannel4, Dmd_Qchannel1, Dmd_Qchannel2, Dmd_Qchannel3, Dmd_Qchannel4, Dmd_Schannel1, Dmd_Schannel2, Dmd_Schannel3, Dmd_Schannel4, Dmd_Psum1, Dmd_Psum2, Dmd_Qsum1, Dmd_Qsum2 Dmd_Ssum1, Dmd_Ssum2, Dmd_Ichannel1, Dmd_Ichannel2, Dmd_Ichannel3, Dmd_ Ichannel4
ENERGY
Active Energy Ep_imp, Ep_exp, Ep_total, Ep_net , Epa_imp, Epa_exp, Epb_imp, Epb_exp, Epc_imp, Epc_exp, Ep_q1, Ep_q2, Ep_q3, Ep_q4
Reactive Energy Eq_imp, Eq_exp, Eq_total, Eq_net, Eqa_imp, Eqa_exp, Eqb_imp, Eqb_exp, Eqc_imp, Eqc_exp
Apparent Energy Es_imp, Es_exp, Es_total, Es_net, Esa, Esb, Esc, Es_q1, Es_q2, Es_q3, Es_q4
DUAL SOURCE ENERGY
Energy to Generator Energy1_Generator, Energy2_Generator, Energy3_Generator
Energy to Grid Energy1_Grid, Energy2_ Grid, Energy3_Grid
Acuvim II Advanced Power & Energy Meter | Datasheet | 6
Function; Option; Blank NA
DEMAND
Current Demand Dmd_I1, Dmd_I2, Dmd_I3, Dmd_ In
Power Demand Dmd_Psum, Dmd_Qsum, Dmd_ Ssum
TIME
Real-Time Clock Year, Month, Day, Hour, Minute, Second
HOUR
Meter Running Time Hour
Load Running Time Hour
POWER QUALITY
Voltage Unbalance U_unbl Current Unbalance I_unbl Voltage THD THD_V1,THD_V2,THD_V3, THD_Vavg
Current THD THD_I1, THD_I2, THD_I3, THD_Iavg
Individual Harmonics Harmonics 2nd to 63rd (50Hz or60Hz)
Voltage Crest Factor Crest Factor
TIF THFF
Current K Factor K Factor
SEQUENCE
Voltage/Current Sequence Positive Sequence, Negative Sequence, Zero Sequence
Phase Order ABC, ACB
PHASE ANGLES
Voltage/Current Phase Angles Voltage Phase Angle, Current Phase Angle
STATISTICS
MAX with Time Stamp MIN with Time Stamp
Each Phase of V & I, Total of P, Q, S, PF & F, Demand of I1, I2, I3, IN, P, Q, & S, Each Phase THD of V & I, Unbalance Factor of V & I
ALARM
Over/Under Limit Alarm
V, I, P, Q, S, PF, V_THD & I_THD Each Phase and Total/Average, Unbalance Factor of V& I, Load Type, Analog and Digital Input of Each Channel, Demand of I1, I2, I3, P, Q & S, Reverse Phase Sequence
WAVEFORM CAPTURE
Voltage and Current Waveform
Trigger, Manual, DI change, Voltage Sag Voltage Swell Current Swell
4-30 CLASS S WAVEFORM CAPTURE
Class S Voltage and Current Waveform
Trigger, Manual, DI Change, Voltage Sag Voltage Swell Voltage Interrupt Current Swell
POWER QUALITY EVENT LOGGING
Power Quality Event with Time Stamp Voltage SAG and Fail, Current overflow, Phase Sequence Error
Acuvim II Advanced Power & Energy Meter | Datasheet | 7
Function; Option; Blank NA
4-30 CLASS S PQ EVENT
Class S Power Quality Event with Timestamp and Duration
Voltage Sag Voltage Swell Voltage Interrupt Unbalance Voltage Current Swell Unbalance Current Event Duration
DATA LOGGING
Data Logging 1 Data Logging 2 Data Logging 3 Data Logging 4
Frequency V1, V2, V3, VInavg V12, V23, V31, VIIavg I1, I2, I3, In, Iavg P1, P2, P3, Psum Q1, Q2, Q3, Qsum S1, S2, S3, Ssum Ep_imp, Ep_exp, Ep_total, Ep_net, Eq_imp, Eq_exp, Eq_total, Eq_net, Es_imp, Es_exp, Es_total, Es_net Epa_imp, Epa_exp, Epb_imp, Epb_exp, Epc_imp, Epc_exp Eqa_imp, Eqa_exp, Eqb_imp, Eqb_exp, Eqc_imp, Eqc_exp Esa_imp, Esa_exp, Esb_imp, Esb_exp, Esc_imp, Esc_exp
PF1, PF2, PF3, PF
U_unbl, I_unbl Load Type THD_V1, THD_V2, THD_V3, THD_Vavg THD_I1, THD_I2, THD_I3, THD_Iavg Harmonics 2nd to 63rd, Crest Factor, THFF, K Factor Sequence, phase angles DI counter, AI, AO Dmd P, Dmd Q, Dmd S, Dmd_I1, Dmd_I2, Dmd_I3
TIME OF USE
Energy/Max Demand TOU, 4 Tariffs, 12 Seasons, 14 Schedules
Daylight Saving Time Two Adjustable Formats
I/O MODULE
Switch Status (DI) Digital Input
Power Supply for DI 24V DC
Relay Output (RO) NO, Form A
Digital Output (DO) Photo-MOS
Pulse Output (PO) By Using DO
Analog Input (AI) 0 (4) – 20mA, 0 (1) – 5V
Analog Output (AO) 0 (4) – 20mA, 0 (1) – 5V
COMMUNICATION
RS485 Port, Half Duplex, Optical Isolated
Modbus-RTU/BACnet Protocol
Ethernet Module Modbus-TCP, HTTP, SMTP, SNTP, Modbus Gateway Passthrough
RS-485 Module Modbus-RTU Protocol
PROFIBUS Module PROFIBUS-DP/V0 Protocol
ONBOARD MEMORY SIZE
Memory Bytes 8MB 16MB (8MB Data Logging + 8MB Power Quality)
DISPLAY
LCD or DIN Rail
DIMENSIONS
96×96×64.3mm (Opening Size: 92 × 92mm)
Acuvim II Advanced Power & Energy Meter | Datasheet | 8
COMMUNICATION MODULES
Standard AXM
WEB2 FOLC
AXM
WEB2
AXM
WEB2-D
AXM
PROFI
AXM
RS485
Modbus-RTU
BACnet-MS/TP
DNP 3.0 V2 Over IP
IEC 61850 2nd Ed.
Modbus-TCP/IP
HTTP/HTTPS
Webserver
SMTP Email
SNMP V3
NTP Synchronization
EtherNet/IP
MQTT
RSTP
IPv6
HTTP/HTTPs Push
FTP Post sFTP Server
Datalogging 8MB 8GB 8GB 8GB
BACnet-IP
PROFIBUS
Wi-Fi
RJ45 Ports 1 2 2
Fiber Optics LC
Function; Option; Blank NA
IO MODULES
AXM-IO1 AXM-IO2 AXM-IO3
Digital Input (Dry) 6 4 4
Digital Output 2
Relay Output 2 2
Analogue Inputs 2
Analogue Outputs 2
Power Supply 24Vdc
Acuvim II Advanced Power & Energy Meter | Datasheet | 9
DIMENSIONS
I/O Module Dimensions
2.
.6 m m
3.54" (90.0mm)
0.77" (19.5mm)
Communication Module Dimensions
2.
.6 m m
3.54" (90.0mm)
0.87" (22.0mm)
DIN Mount Meter Dimensions External Display Module Dimensions
1. Display module is connected with a six-foot 10 pin RJ50 cable. If longer cable is needed, please specify that in the ordering statement.
2. Display module opening size and Acuvim II body openings are exactly the same size.
Note:
4.02" (102.0mm)
Cut-Out
3.
.0 m m
3.62" (92.0mm)
Cut-Out
Acuvim II Dimensions
Rear View Side View Front View Side View
Side ViewFront View Cut Out
3.
(9
6.
0m m
3.80" (96.0mm)
3.58" (91.0mm)
3.
(9
3.
5m m
1.91" (48.44mm)
3.
(8
9.
m m
3.51" (89.2mm)
2.
(5
5.
6m m
2.42" (61.4mm)
2.04" (51.7mm)
2.00" (50.9mm)
1.41" (35.9mm)
1.40" (35.5m m
3.
(9
6.
0m m
3.80" (96.0mm)
H P E V/A
3.
(9
1.
0m m
2.04" (51.7mm)
2.00" (50.9mm)
3.
(9
6.
0m m
3.80" (96.0mm)
3.58" (91.0mm)
3.
(9
3.
5m m
1.91" (48.44mm)
3.
(8
9.
m m
3.51" (89.2mm)
2.
(5
5.
6m m
2.42" (61.4mm)
2.04" (51.7mm)
2.00" (50.9mm)
1.41" (35.9mm)
1.40" (35.5m m
3.
(9
6.
0m m
3.80" (96.0mm)
H P E V/A
3.
(9
1.
0m m
2.04" (51.7mm)
2.00" (50.9mm)
3.
(9
6.
0m m
3.80" (96.0mm)
3.58" (91.0mm)
3.
(9
3.
5m m
1.91" (48.44mm)
3.
(8
9.
m m
3.51" (89.2mm)
2.
(5
5.
6m m
2.42" (61.4mm)
2.04" (51.7mm)
2.00" (50.9mm)
1.41" (35.9mm)
1.40" (35.5m m
3.
(9
6.
0m m
3.80" (96.0mm)
H P E V/A
3.
(9
1.
0m m
2.04" (51.7mm)
2.00" (50.9mm)
3.
(9
6.
0m m
3.80" (96.0mm)
3.58" (91.0mm)
3.
(9
3.
5m m
1.91" (48.44mm)
3.
(8
9.
m m
3.51" (89.2mm)
2.
(5
5.
6m m
2.42" (61.4mm)
2.04" (51.7mm)
2.00" (50.9mm)
1.41" (35.9mm)
1.40" (35.5m m
3.
(9
6.
0m m
3.80" (96.0mm)
H P E V/A
3.
(9
1.
0m m
2.04" (51.7mm)
2.00" (50.9mm)
3.
(9
6.
0m m
3.80" (96.0mm)
3.58" (91.0mm)
3.
(9
3.
5m m
1.91" (48.44mm)
3.
(8
9.
m m
3.51" (89.2mm)
2.
(5
5.
6m m
2.42" (61.4mm)
2.04" (51.7mm)
2.00" (50.9mm)
1.41" (35.9mm)
1.40" (35.5m m
3.
(9
6.
0m m
3.80" (96.0mm)
H P E V/A
3.
(9
1.
0m m
2.04" (51.7mm)
2.00" (50.9mm)
Acuvim II Advanced Power & Energy Meter | Datasheet | 10
WIRING DIAGRAMS
Typical Wiring With 5A/1A CTs
I/O Module Wiring
N GL
220Vac comV+
DOC
DOC
DO1
DO2
OUT
Power Supply
Relay Control
RO1
ROC
DO Type 10K
Pulse Output
Alarm Output
Buzzer
Terminal Block Terminal Block
A N
LINE
1A FUSE
1A FUSE1A FUSE
LOAD
Acuvim II
Acuvim II
DI1 DI2 DI3 DI4 DI5 DI6 DIC RO1 RO2 ROC V+ V-
Digital Input Relay Output VDC
Q F1
Q F2
Q F3
Q F4
Q F5
Q F6
DI1 DI2 DI3 DI4 DIC
Digital Input
Q F1
Q F2
Q F3
Q F4
Q F5
20-160Vac/dc
COM
V+
3 Element 4 Wire Wye (3LN, 3CT**) 3 Element 4 Wire Delta (3LL, 3CT) 3 Element 4 Wire Wye with PT (3LN, 3CT)
1 Element 2 Wire (1LN, 1CT)2 Element 3 Wire 1 Phase (1LL, 2CT)2 Element 3 Wire Delta with PT (2LL, 3CT)
AXM-IO1 AXM-IO2/IO3
Relay Output (RO) Wiring Energy Output (DO) Wiring
Note: *2CT configuration is optional only in 3 Phase 3 Wire system.
**Neutral CT is optional.
Acuvim II Acuvim II
Acuvim II
1A FUSE
1A FUSE1A FUSE
Terminal Block
LOAD
LOAD
LOAD
LOAD
LOAD
Acuvim II
A B C NLINELINELINE
LINE LINE
10 10 9 8 8 7 7 9
10 9 8 7
Acuvim II Advanced Power & Energy Meter | Datasheet | 11
Typical Wiring RCT/mV/mA Current Input
ACCESSORIES
DIN Rail Adapter
The AXM-DIN Rail Adapter is the easy way to mount the Acuvim II Series energy meter on either horizontal or vertical DIN rail. The adapter quickly secures to the meter and is compatible with all AXM communication modules as well as I/O options.
Protective Display Cover
The Protective Display Cover is designed for Acuvim II Series energy meters and other 96mm by 96mm display panel meters. Crucial in harsh environments, it increases the IP environmental rating of the meter's display to IP66 or NEMA 4X.
USB RS485 Converter
This plug-and-play USB to Serial RS485 Converter is designed to provide a convenient, reliable USB connection to the Acuvim II Series power meters and other serial devices.
WIRING DIAGRAMS
Note: *2CT configuration is optional only in 3 Phase 3 Wire system.
Terminal Block
LINE
1A FUSE
LOAD
I11
I12
I21
I22
I31
I32
VN V 3 V 2 V 1
I41
I42
3 Element 4 Wire Wye (3LN, 3CT**)
Terminal Block
LINE
1A FUSE
I11
I12
I21
I22
I31
I32
VN V 3 V 2 V 1
I41
I42
LOAD
3 Element 4 Wire Delta (3LL, 3CT)
Terminal Block
LINE
1A FUSE
LOAD
I11
I12
I21
I22
I31
I32
VN V 3 V 2 V 1
I41
I42
Terminal Block
LINE
1A FUSE
LOAD
I11
I12
I21
I22
I31
I32
VN V 3 V 2 V 1
I41
I42
2 Element 3 Wire 1 Phase (1LL, 2CT) 1 Element 2 Wire (1LN, 1CT)
Terminal Block
I11
I12
I21
I22
I31
I32
LINE
1A FUSE
VN V 3 V 2 V 1
LOAD
I41
I42
2 Element 3 Wire Delta (2LL, 3CT)
Terminal Block
LOAD
I11
I12
I21
I22
I31
I32
VN V 3 V 2 V 1
1A FUSE
I41
I42
3 Element 4 Wire Wye with PT (3LN, 3CT)
A B C N
A B C N
A B C
A N B A N
A B C
Acuvim II
Acuvim II
Acuvim II
Acuvim II
Acuvim II
Acuvim II
10 9 8 7 10 9 8 7 10 9 8 7
10 9 7 810 9 8 7
**Neutral CT is optional.
Acuvim II Advanced Power & Energy Meter | Datasheet | 12
Meter Model - Mounting Option - Current Input - Power Supply
Acuvim IIR:
Data logging, TOU
D: LCD Display (Panel Mount Meter/Transducer)
5A: 5A/1A (Input Field Selectable)
P1V3: 100~415Vac, 50/60Hz, 100~300Vdc
Acuvim IIW:
IIR + Waveform Capture and PQ Event Logging
M: DIN-Rail Mount Transducer without Display (Optional Remote Display Available) mV: 333mV and Rogowski Coil (Input Field Selectable) P2V3: 20~60Vdc mA: 80mA/100mA/200mA (Input Field Selectable)
Ordering Example: Acuvim-IIR-M-mV-P2V3
Acuvim-IIW-D-5A-P1V3
Accessories (Optional)
REM-DS2: Remote Display (Only for Acuvim II DIN-Rail Mount "M" option)
AXM-DIN: DIN Rail Adapter
IP66/NEMA4X: Environmental Protection Cover
USB-RS485: USB-to-RS485 Converter
Communication Module (Optional) - Protocols
AXM WEB2-FOLC:
IEC 61850 2nd Ed., Modbus-TCP, HTTP/HTTPs Webserver, SMTP Email, SNMP, HTTP/HTTPS Push, FTP Post, sFTP Server, BACnet-IP, Datalogging, Wi-Fi, Fiber Optics LC, Ethernet port, EtherNet/IP, MQTT, Modbus Gateway Passthrough
WEB2:
IEC 61850 2nd Ed., Modbus-TCP, HTTP/HTTPs Webserver, SMTP Email, SNMP, HTTP/ HTTPS Push, FTP Post, sFTP Server, BACnet-IP, Datalogging, Wi-Fi, Dual Ethernet Ports, EtherNet/IP, MQTT, Modbus Gateway Passthrough
WEB2-D:
IEC 61850 2nd Ed., Modbus-TCP, HTTP/HTTPs Webserver, SMTP Email, SNMP, HTTP/ HTTPS Push, FTP Post, sFTP Server, BACnet-IP, Datalogging, Dual Ethernet Ports, EtherNet/IP, MQTT, Modbus Gateway Passthrough
PROFI: PROFIBUS
RS485: Modbus-RTU
Ordering Example: AXM-RS485
AXM-WEB2-FOLC
ORDERING INFORMATION
Note:
Note:
1. Refer to the Communication table and I/O Module table.
2. A maximum of 3 modules may be attached to the meter. If a communication module is used (e.g. AXM-WEB2), it must be installed on the back FIRST before the other I/O modules are attached.
3. No more than 2 of the same I/O modules may be attached to the meter (e.g. two AXM-IO2). The same two I/O modules must have different logic numbers.
Logic numbers can be configured as either 1 or 2 through Acuview 2 or AXM-WEB2.
4. If Acuvim IIW uses DI to trigger a waveform capture, the I/O module logic number must be Module 1.
1. Accuenergy suggests using a USB-RS485 converter for configuration, and 3 CTs per three phase circuits.
2. All fields must be completed to create a part number.
3. Add “-S” after power supply for anti-tampering seal option.
Accuenergy Inc.
Los Angeles - Toronto - Pretoria
North America Toll Free: 1-877-721-8908 Web: www.accuenergy.com Email: marketing@accuenergy.com
Revision Date: January 2026 Version: 2.0.16 Specs Subject To Change Without Notice.
+ +I/O Module (Optional)
AXM-IO1 6 Digital Inputs, 2 Relay Outputs, 24Vdc Power Supply
AXM-IO2 4 Digital Inputs, 2 Digital Outputs, 2 Analog Outputs (0~5V or 1~5V, 0~20mA or 4~20mA)
AXM-IO3 4 Digital Inputs, 2 Relay Outputs, 2 Analog Inputs (0~5V or 1~5V, 0~20mA or 4~20mA)
Ordering Example: AXM-IO1
ISO 9001, 14001
& 45001 Certified
File details come from the government source that posted it. Updated .