Acuvim-II-Advanced-Power-and-Energy-Meter-Datasheet.pdf

PDF 2 MB Posted

Attached to
Design-Build (DB) Barracks Initiative (Package #2), Marine Corps Base (MCB) Camp Lejeune, North Carolina
Solicitation number
Not on record
Issued by

About this file

This document is a product datasheet for the Acuvim II Advanced Power & Energy Meter, a multifunction power monitoring device manufactured by Accuenergy. The meter is available in two models: Acuvim IIR (with data logging and time-of-use functionality) and Acuvim IIW (with added waveform capture and power quality event logging). Both models are available in LCD display panel mount or DIN rail transducer configurations and support multiple current input options including 5A/1A, 333mV, Rogowski coil, and 80mA/100mA/200mA inputs. Power supply options include 100–415Vac 50/60Hz with 100–300Vdc or 20–60Vdc low voltage DC.

The meter achieves ANSI C12.20 class 0.1 and IEC 62053-22 class 0.1s revenue-grade accuracy for energy measurement, with 0.1% accuracy across voltage, current, power, reactive power, apparent power, and frequency parameters. Key capabilities include IEC 61000-4-30 Class S compliant power quality measurements, four tariff time-of-use energy tracking, 512 samples per cycle measurement, 20ms Modbus refresh rates, 8MB onboard memory expandable to 8GB with the WEB2 module, and support for multiple communication protocols via optional modules including Modbus RTU/TCP, BACnet MS/TP and IP, IEC 61850, Ethernet, Wi-Fi, PROFIBUS, and EtherNet/IP. Optional I/O modules support digital inputs and outputs, relay outputs, pulse outputs, analog inputs and outputs, and up to 16 alarm configurations. The document includes detailed specifications, function lists, wiring diagrams for various configurations, and ordering information for the base meter and optional communication and I/O modules.

View the file

Other files

File Type Posted
AXM-WEB2-user-manual.pdf PDF
FX90 Cutsheet.pdf PDF
Simplex 4100ES.pdf PDF
Attachment 1 - Company Information.docx DOCX document
EC-BOS-9_SP Cutsheet.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Acuvim II Advanced Power & Energy Meter | Datasheet | 1

DESCRIPTION

Acuvim II Advanced Power & Energy Meter Datasheet

FEATURES

+ Revenue Grade: ANSI C12.20 class 0.1 & IEC 62053-22 class 0.1s.

+ 4th CT input to measure neutral current.

+ Dual Ethernet ports with both RSTP bridge daisy-chain mode and separately configurable network.

+ High-resolution frequency measurement utilizes a custom moving average filter with 0.001Hz and 10mHz accuracy. Window size ranges from 1 - 50 cycles, and update rate varies from 1 - 2 cycles.

+ Data logging available with 8MB onboard memory and expandable to 8GB with WEB2 module.

+ IEC 61000-4-30 Class S compliant power quality event measurements for Acuvim IIW.

+ High-speed update rate.

Fast Read mode offers a 20ms Modbus refresh rate, Fast Log is available at 100ms and 50ms intervals via Modbus RTU and TCP/IP.

+ Compatible with multiple CT output options including 5A mA, Accuenergy Rogowski coil, or 333mV.

+ Modbus-RTU & BACnet MS/ TP ready. Optional modules add support for multiple industrial protocols & interfaces such as Modbus- TCP/IP, BACnet-IP, IEC 61850 2nd Ed., Wi-Fi, & EtherNet/IP.

The Acuvim II Series advanced power and energy meter is a robust solution for power monitoring, kWh metering, power quality analysis, and more. This multifunction meter is engineered for easy integration into any project environment and is compatible with a wide array of plug-in expansion modules to facilitate communication on over 15 different industry-standard protocols.

Its two available form factors include a panel mount meter with a digital display and a DIN rail transducer configuration.

With IEC 61000-4-30 Class S compliant power quality analysis, Acuvim IIW can monitor key PQ events such as harmonics, voltage swells and more.

C12.20 .5 CLASS

NEW

NEW

NEW

NEW

NEW

NEW

EN55011

KEY FEATURES

Communication

+ Modbus RTU protocol and BACnet MS/TP via RS485 + Wi-Fi and Ethernet Communication Channels (Modbus TCP, BACnet IP, HTTP, SMTP, SNTP, HTTPs, Post, FTP)

+ PROFIBUS DP

+ Dual RJ45 ports with RSTP daisy-chain and two individually configurable Ethernet ports

Data Logging

+ Acuvim II meters offer three assignable historical logs and a real-time clock to record many metering parameters with accurate timestamping. Add the AXM WEB2 module to expand the memory to 8GB with an adjustable log size.

+ WEB2 module offers additional granularity to data logging such as 1 second interval timing and max/ min/average and instantaneous reading for real time parameters.

Fast Response

+ 512 samples per cycle for measurement, 100ms and 20ms Modbus refresh rate, and 100ms and 50ms options Fast Logging for real time parameters including Frequency and Active Power.

Flexible Current Transformer Options

+ The Acuvim II is directly compatible with Rogowski coils plus a variety of other current transformer outputs, including 5A, 1A, 80mA, 100mA, 200mA, and 333mV. All CTs are available from Accuenergy.

Power Quality Measurements

+ Acuvim IIW offers IEC 61000-4-30 Class S compliant power quality event measurements. It is designed for monitoring and diagnosing power quality issues to improve efficiency and reliability, and enhance overall system performance. Perfect for energy management systems, building automation systems, and more.

Time of Use

+ Users can assign up to four tariffs (sharp, peak, valley, & normal) to different time periods within a day. The Acuvim II meter will calculate and accumulate energy to different tariffs according to the meter’s internal clock and TOU settings.

Optional I/O Module

+ Expand Acuvim II I/O functionality by connecting an optional I/O module. A maximum of three modules can be used per meter. Digital input, digital output, pulse output, relay output, analog input, and analogue output I/O modules are available.

Alarms

+ Limits can be set for up to 16 indicated parameters with a specified time interval. Parameters that are over or under the setting limit and persist longer than the specified time interval will be recorded and trigger the Alarm DO. Choose from 80 available parameters.

APPLICATIONS

+ Submetering

+ Energy Storage, Microgrids, and VPPs

+ Power Generation

+ Load Banks

+ Building Automation

+ PDUs and Data Centers

+ Energy Management Systems

+ Substation and Distribution Systems

+ Transformer Monitoring

+ Measurement & Verification

Acuvim II Advanced Power & Energy Meter | Datasheet | 3

SPECIFICATIONS

Metering

PARAMETERS ACCURACY RESOLUTION RANGE

Voltage 0.1% 0.1V 10V~1000kV

Current 0.1% 0.1mA 5mA~50000A

Power 0.1% 1W -9999MW~9999MW

Reactive Power 0.1% 1var -9999Mvar~9999Mvar

Apparent Power 0.1% 1VA 0~9999MVA

Power Demand 0.1% 1W -9999MW~9999MW

Reactive Power Demand 0.1% 1var -9999Mvar~9999Mvar

Apparent Power Demand 0.1% 1VA 0~9999MVA

Power Factor 0.1% 0.001 -1.000~1.000

Frequency 0.001% 0.001Hz 45.00~65.00Hz

Energy

Primary 0.1 0.1% 0.1kWh 0-99999999.9kWh

Primary 0.001 0.1% 0.001kWh 0-999999.999kWh

Secondary 0.1% 0.001kWh 0-999999.999kWh

Reactive Energy

Primary 0.1 0.1% 0.1kvarh 0-99999999.9kvarh

Primary 0.001 0.1% 0.001kvarh 0-999999.999kvarh

Secondary 0.1% 0.001kvarh 0-999999.999kvarh

Apparent Energy

Primary 0.1 0.1% 0.1kVAh 0-99999999.9kVAh

Primary 0.001 0.1% 0.001kVAh 0-999999.999kVAh

Secondary 0.1% 0.001kVAh 0-999999.999kVAh

Harmonics 1.0% 0.10%

Phase Angle 2.0% 0.1° 0.0°~359.9°

Unbalance Factor 2.0% 0.10% 0.0%~100.0%

Running Time 0.01h 0~9999999.99h

Communication

Modbus-RTU or BACnet MS/TP

Modbus-RTU 2-Wire Shielded Twisted Pair Cable Connection 2400~115200 bps

SECOND RS-485 PORT

(OPTIONAL MODULE)

Same as the Primary RS485 port Baud Rate: 4800~38400 bps

ETHERNET

(OPTIONAL MODULE)

Ethernet 10M/100M BaseT

MODBUS-TCP/IP

DNP 3.0 V2 Over IP Level 2 IEC 61850 2nd Ed.

SNMP V3

BACnet-IP HTTP/HTTPs Webserver HTTP/HTTPs, FTP data post

SMTP

MQTT

MV90

NTP

PROFIBUS

(OPTIONAL MODULE)

PROFIBUS-DP/V0 Protocol Work as PROFIBUS Slave, Baud Rate Adaptive, up to 12M Model 1: Input Bytes: 32, Output Bytes: 32 Model 2: Input Bytes: 64, Output Bytes: 2 PROFIBUS Standard According to EN 50170 Vol. 2

Input

CURRENT INPUTS (EACH CHANNEL)

Nominal Current Options 5A, 1A, 333mV, Rogowski Coil, 80mA/100mA/200mA

Metering Range 0-10A, 0-2A, 0-400mV, 0-400mV, 0-240mA

Pickup Current 5mA, 1mA, 0.25mV, 0.25mV, 0.15mA

Withstand 20Arms Continuous, 0.1% of Nominal 100Arms for 1 Second, Non-Recurring

Burden 0.05VA (Typical) @ 5A RMS

Accuracy 0.1% at Reading

VOLTAGE INPUTS (EACH CHANNEL)

Nominal Full Scale 480Vac L-N, 828Vac L-L

Withstand 1500Vac Continuous 2500Vac, 50/60Hz for 1 Minute

Input Impedance 2MΩ per Phase

Metering Frequency 45Hz~65Hz

Pickup Voltage 10Vac

Accuracy 0.1% at Reading

ENERGY ACCURACY

Active Class 0.1s (According to IEC 62053-22) Class 0.1 (According to ANSI C12.20)

Reactive Class 0.5s (According to IEC 62053-24)

HARMONIC RESOLUTION

Metered Value 63rd Harmonic

Acuvim II Advanced Power & Energy Meter | Datasheet | 4

SPECIFICATIONS

I/O Options

DIGITAL INPUT

Input Type Dry

Input Resistance 100kΩ

Input Voltage Range 20~160 Vac/dc

Input Current (Max) 2mA

Start Voltage 15V

Stop Voltage 5V

Pulse Frequency (Max) 100Hz, 50% Duty Ratio (5ms ON and 5ms OFF)

SOE Resolution 2ms

DIGITAL OUTPUT (DO) (PHOTO-MOS)

Voltage Range 0~250Vac/dc

Load Current 100mA (Max)

Output Frequency 25Hz, 50% Duty Ratio (20ms ON, 20ms OFF)

Isolation Voltage 2500Vac

RELAY OUTPUT (RO) (NO, Form A)

Switching Voltage (Max) 250Vac, 30Vdc

Load Current 5A (R), 2A (L)

Set Time 10ms (Max)

Contact Resistance 30mΩ (Max)

Isolation Voltage 2500Vac

Mechanical Life 1.5x107

ANALOG OUTPUT (AO)

Output Range 0~5V, 0~20mA 1~5V, 4~20mA Optional

Accuracy 0.50%

Temperature Drift 50ppm/°C Typical

Isolation Voltage 500Vdc

Open Circuit Voltage 15V

ANALOG INPUT (AI)

Input Range 0~5V, 0~20mA 1~5V, 4~20mA Optional

Accuracy 0.20%

Temperature Drift 50ppm/°C Typical

Isolation Voltage 500Vdc

POWER SUPPLY FOR DI (24 VDC)

Output Voltage 24Vdc

Output Current 42mA

Load (Max) 21 DIs

Control Power Universal AC or DC

AC/DC CONTROL POWER

Operating Range 100~415Vac, 50/60Hz; 100~300Vdc

Burden 5W

Frequency 50/60Hz

Withstand 3250Vac, 50/60Hz for 1 Minute

Installation Category III (Distribution)

LOW VOLTAGE DC CONTROL POWER (P2V3 Option Only)

Operating Range 20~60Vdc

Burden 5W

Operating Environment

Operating Temperature -25°C to 70°C -13°F to 158°F

Storage Temperature -40°C to 85°C -40°F to 176°F

Relative Humidity 5% to 95% Non-Condensing

Standard Compliance & Certifications

Measurement Standard IEC 62053-22;

ANSI C12.20; IEC61557-12

Environmental Standard IEC 60068-2, CE, RoHS

Safety Standard IEC 61010-1, UL 61010-1

EMC Standard

IEC 61000-4/-2-3-4-5-6-8-11, CISPR

22, IEC 61000-3-2, IEC 61000-6-2/4,

EN55011

Outlines Standard DIN 43700, ANSI C39.1

Protocol Conformance IEC 61850 2nd Ed.

BTL Listed for B-SA

Acuvim II Advanced Power & Energy Meter | Datasheet | 5

FUNCTION LIST

Function; Option; Blank NA

REAL TIME MEASURING Parameters Acuvim IIR Acuvim IIW

Phase Voltage V1, V2, V3, VInavg Line Voltage V12, V23, V31, VIIavg

Current I1, I2, I3, In, Iavg

Power P1, P2, P3, Psum

Reactive Power Q1, Q2, Q3, Qsum

Apparent Power S1, S2, S3, Ssum

Power Factor PF1, PF2, PF3, PF

Frequency F

Load Features L/C/R

Four Quadrant Powers Four Quadrant Powers

4-30 CLASS S READINGS

10/12 Cycle 150/180 Cycle 10 Minutes 2 Hours

F,V1,V2,V3,Vlnavg, V12,V23,V31,Vllavg, I1,I2,I3,In,Iavg, THD_V, THD_I, Unbalance Factor Sequence Readings Current Harmonic Amplitude Voltage Harmonic Amplitude

INDEPENDENT CHANNEL

System Phase Voltage V1, V2, V3, Vlnavg

System Line Voltage V12, V23, V31, Vllavg

System Frequency F

Current Ichannel1, Ichannel2, Ichannel3, Ichannel4, Isum_1avg, Isum_2avg

Power Pchannel1, Pchannel2, Pchannel3, Pchannel4, Psum_1, Psum_2

Reactive Power Qchannel1, Qchannel2, Qchannel3, Qchannel4, Qsum_1, Qsum_2

Apparent Power Schannel1, Schannel2, Schannel3, Schannel4, Ssum_1, Ssum_2

Power Factor PFchannel1, PFchannel2, PFchannel3, PFchannel4, PFsum_1, PFsum_2

Load Features Load Features

Four Quadrant Powers Four Quadrant Powers

Energy

Epchannel1_imp, Epchannel2_imp, Epchannel3_imp, Epchannel4_imp Epchannel1_exp, Epchannel2_exp, Epchannel3_exp, Epchannel4_exp Epsum1_imp, Epsum2_imp, Epsum1_exp, Epsum2_exp Epsum1_Totoal, Epsum2_Total, Epsum1_Net, Epsum2_Net

Reactive Energy

Eqchannel1_imp, Eqchannel2_imp, Eqchannel3_imp, Eqchannel4_imp, Eqchannel1_exp, Eqchannel2_exp, Eqchannel3_exp, Eqchannel4_exp, Eqsum1_imp, Eqsum2_imp, Eqsum1_exp, Eqsum2_exp, Eqsum1_Total, Eqsum2_Total, Eqsum1_Net, Eqsum2_Net

Apparent Energy Eschannel1, Eschannel2, Eschannel3, Eschannel4, Essum1, Essum2

Demand

Dmd_Pchannel1, Dmd_Pchannel2, Dmd_Pchannel3, Dmd_Pchannel4, Dmd_Qchannel1, Dmd_Qchannel2, Dmd_Qchannel3, Dmd_Qchannel4, Dmd_Schannel1, Dmd_Schannel2, Dmd_Schannel3, Dmd_Schannel4, Dmd_Psum1, Dmd_Psum2, Dmd_Qsum1, Dmd_Qsum2 Dmd_Ssum1, Dmd_Ssum2, Dmd_Ichannel1, Dmd_Ichannel2, Dmd_Ichannel3, Dmd_ Ichannel4

ENERGY

Active Energy Ep_imp, Ep_exp, Ep_total, Ep_net , Epa_imp, Epa_exp, Epb_imp, Epb_exp, Epc_imp, Epc_exp, Ep_q1, Ep_q2, Ep_q3, Ep_q4

Reactive Energy Eq_imp, Eq_exp, Eq_total, Eq_net, Eqa_imp, Eqa_exp, Eqb_imp, Eqb_exp, Eqc_imp, Eqc_exp

Apparent Energy Es_imp, Es_exp, Es_total, Es_net, Esa, Esb, Esc, Es_q1, Es_q2, Es_q3, Es_q4

DUAL SOURCE ENERGY

Energy to Generator Energy1_Generator, Energy2_Generator, Energy3_Generator

Energy to Grid Energy1_Grid, Energy2_ Grid, Energy3_Grid

Acuvim II Advanced Power & Energy Meter | Datasheet | 6

Function; Option; Blank NA

DEMAND

Current Demand Dmd_I1, Dmd_I2, Dmd_I3, Dmd_ In

Power Demand Dmd_Psum, Dmd_Qsum, Dmd_ Ssum

TIME

Real-Time Clock Year, Month, Day, Hour, Minute, Second

HOUR

Meter Running Time Hour

Load Running Time Hour

POWER QUALITY

Voltage Unbalance U_unbl Current Unbalance I_unbl Voltage THD THD_V1,THD_V2,THD_V3, THD_Vavg

Current THD THD_I1, THD_I2, THD_I3, THD_Iavg

Individual Harmonics Harmonics 2nd to 63rd (50Hz or60Hz)

Voltage Crest Factor Crest Factor

TIF THFF

Current K Factor K Factor

SEQUENCE

Voltage/Current Sequence Positive Sequence, Negative Sequence, Zero Sequence

Phase Order ABC, ACB

PHASE ANGLES

Voltage/Current Phase Angles Voltage Phase Angle, Current Phase Angle

STATISTICS

MAX with Time Stamp MIN with Time Stamp

Each Phase of V & I, Total of P, Q, S, PF & F, Demand of I1, I2, I3, IN, P, Q, & S, Each Phase THD of V & I, Unbalance Factor of V & I

ALARM

Over/Under Limit Alarm

V, I, P, Q, S, PF, V_THD & I_THD Each Phase and Total/Average, Unbalance Factor of V& I, Load Type, Analog and Digital Input of Each Channel, Demand of I1, I2, I3, P, Q & S, Reverse Phase Sequence

WAVEFORM CAPTURE

Voltage and Current Waveform

Trigger, Manual, DI change, Voltage Sag Voltage Swell Current Swell

4-30 CLASS S WAVEFORM CAPTURE

Class S Voltage and Current Waveform

Trigger, Manual, DI Change, Voltage Sag Voltage Swell Voltage Interrupt Current Swell

POWER QUALITY EVENT LOGGING

Power Quality Event with Time Stamp Voltage SAG and Fail, Current overflow, Phase Sequence Error

Acuvim II Advanced Power & Energy Meter | Datasheet | 7

Function; Option; Blank NA

4-30 CLASS S PQ EVENT

Class S Power Quality Event with Timestamp and Duration

Voltage Sag Voltage Swell Voltage Interrupt Unbalance Voltage Current Swell Unbalance Current Event Duration

DATA LOGGING

Data Logging 1 Data Logging 2 Data Logging 3 Data Logging 4

Frequency V1, V2, V3, VInavg V12, V23, V31, VIIavg I1, I2, I3, In, Iavg P1, P2, P3, Psum Q1, Q2, Q3, Qsum S1, S2, S3, Ssum Ep_imp, Ep_exp, Ep_total, Ep_net, Eq_imp, Eq_exp, Eq_total, Eq_net, Es_imp, Es_exp, Es_total, Es_net Epa_imp, Epa_exp, Epb_imp, Epb_exp, Epc_imp, Epc_exp Eqa_imp, Eqa_exp, Eqb_imp, Eqb_exp, Eqc_imp, Eqc_exp Esa_imp, Esa_exp, Esb_imp, Esb_exp, Esc_imp, Esc_exp

PF1, PF2, PF3, PF

U_unbl, I_unbl Load Type THD_V1, THD_V2, THD_V3, THD_Vavg THD_I1, THD_I2, THD_I3, THD_Iavg Harmonics 2nd to 63rd, Crest Factor, THFF, K Factor Sequence, phase angles DI counter, AI, AO Dmd P, Dmd Q, Dmd S, Dmd_I1, Dmd_I2, Dmd_I3

TIME OF USE

Energy/Max Demand TOU, 4 Tariffs, 12 Seasons, 14 Schedules

Daylight Saving Time Two Adjustable Formats

I/O MODULE

Switch Status (DI) Digital Input

Power Supply for DI 24V DC

Relay Output (RO) NO, Form A

Digital Output (DO) Photo-MOS

Pulse Output (PO) By Using DO

Analog Input (AI) 0 (4) – 20mA, 0 (1) – 5V

Analog Output (AO) 0 (4) – 20mA, 0 (1) – 5V

COMMUNICATION

RS485 Port, Half Duplex, Optical Isolated

Modbus-RTU/BACnet Protocol

Ethernet Module Modbus-TCP, HTTP, SMTP, SNTP, Modbus Gateway Passthrough

RS-485 Module Modbus-RTU Protocol

PROFIBUS Module PROFIBUS-DP/V0 Protocol

ONBOARD MEMORY SIZE

Memory Bytes 8MB 16MB (8MB Data Logging + 8MB Power Quality)

DISPLAY

LCD or DIN Rail

DIMENSIONS

96×96×64.3mm (Opening Size: 92 × 92mm)

Acuvim II Advanced Power & Energy Meter | Datasheet | 8

COMMUNICATION MODULES

Standard AXM

WEB2 FOLC

AXM

WEB2

AXM

WEB2-D

AXM

PROFI

AXM

RS485

Modbus-RTU

BACnet-MS/TP

DNP 3.0 V2 Over IP

IEC 61850 2nd Ed.

Modbus-TCP/IP

HTTP/HTTPS

Webserver

SMTP Email

SNMP V3

NTP Synchronization

EtherNet/IP

MQTT

RSTP

IPv6

HTTP/HTTPs Push

FTP Post sFTP Server

Datalogging 8MB 8GB 8GB 8GB

BACnet-IP

PROFIBUS

Wi-Fi

RJ45 Ports 1 2 2

Fiber Optics LC

Function; Option; Blank NA

IO MODULES

AXM-IO1 AXM-IO2 AXM-IO3

Digital Input (Dry) 6 4 4

Digital Output 2

Relay Output 2 2

Analogue Inputs 2

Analogue Outputs 2

Power Supply 24Vdc

Acuvim II Advanced Power & Energy Meter | Datasheet | 9

DIMENSIONS

I/O Module Dimensions

2.

.6 m m

3.54" (90.0mm)

0.77" (19.5mm)

Communication Module Dimensions

2.

.6 m m

3.54" (90.0mm)

0.87" (22.0mm)

DIN Mount Meter Dimensions External Display Module Dimensions

1. Display module is connected with a six-foot 10 pin RJ50 cable. If longer cable is needed, please specify that in the ordering statement.

2. Display module opening size and Acuvim II body openings are exactly the same size.

Note:

4.02" (102.0mm)

Cut-Out

3.

.0 m m

3.62" (92.0mm)

Cut-Out

Acuvim II Dimensions

Rear View Side View Front View Side View

Side ViewFront View Cut Out

3.

(9

6.

0m m

3.80" (96.0mm)

3.58" (91.0mm)

3.

(9

3.

5m m

1.91" (48.44mm)

3.

(8

9.

m m

3.51" (89.2mm)

2.

(5

5.

6m m

2.42" (61.4mm)

2.04" (51.7mm)

2.00" (50.9mm)

1.41" (35.9mm)

1.40" (35.5m m

3.

(9

6.

0m m

3.80" (96.0mm)

H P E V/A

3.

(9

1.

0m m

2.04" (51.7mm)

2.00" (50.9mm)

3.

(9

6.

0m m

3.80" (96.0mm)

3.58" (91.0mm)

3.

(9

3.

5m m

1.91" (48.44mm)

3.

(8

9.

m m

3.51" (89.2mm)

2.

(5

5.

6m m

2.42" (61.4mm)

2.04" (51.7mm)

2.00" (50.9mm)

1.41" (35.9mm)

1.40" (35.5m m

3.

(9

6.

0m m

3.80" (96.0mm)

H P E V/A

3.

(9

1.

0m m

2.04" (51.7mm)

2.00" (50.9mm)

3.

(9

6.

0m m

3.80" (96.0mm)

3.58" (91.0mm)

3.

(9

3.

5m m

1.91" (48.44mm)

3.

(8

9.

m m

3.51" (89.2mm)

2.

(5

5.

6m m

2.42" (61.4mm)

2.04" (51.7mm)

2.00" (50.9mm)

1.41" (35.9mm)

1.40" (35.5m m

3.

(9

6.

0m m

3.80" (96.0mm)

H P E V/A

3.

(9

1.

0m m

2.04" (51.7mm)

2.00" (50.9mm)

3.

(9

6.

0m m

3.80" (96.0mm)

3.58" (91.0mm)

3.

(9

3.

5m m

1.91" (48.44mm)

3.

(8

9.

m m

3.51" (89.2mm)

2.

(5

5.

6m m

2.42" (61.4mm)

2.04" (51.7mm)

2.00" (50.9mm)

1.41" (35.9mm)

1.40" (35.5m m

3.

(9

6.

0m m

3.80" (96.0mm)

H P E V/A

3.

(9

1.

0m m

2.04" (51.7mm)

2.00" (50.9mm)

3.

(9

6.

0m m

3.80" (96.0mm)

3.58" (91.0mm)

3.

(9

3.

5m m

1.91" (48.44mm)

3.

(8

9.

m m

3.51" (89.2mm)

2.

(5

5.

6m m

2.42" (61.4mm)

2.04" (51.7mm)

2.00" (50.9mm)

1.41" (35.9mm)

1.40" (35.5m m

3.

(9

6.

0m m

3.80" (96.0mm)

H P E V/A

3.

(9

1.

0m m

2.04" (51.7mm)

2.00" (50.9mm)

Acuvim II Advanced Power & Energy Meter | Datasheet | 10

WIRING DIAGRAMS

Typical Wiring With 5A/1A CTs

I/O Module Wiring

N GL

220Vac comV+

DOC

DOC

DO1

DO2

OUT

Power Supply

Relay Control

RO1

ROC

DO Type 10K

Pulse Output

Alarm Output

Buzzer

Terminal Block Terminal Block

A N

LINE

1A FUSE

1A FUSE1A FUSE

LOAD

Acuvim II

Acuvim II

DI1 DI2 DI3 DI4 DI5 DI6 DIC RO1 RO2 ROC V+ V-

Digital Input Relay Output VDC

Q F1

Q F2

Q F3

Q F4

Q F5

Q F6

DI1 DI2 DI3 DI4 DIC

Digital Input

Q F1

Q F2

Q F3

Q F4

Q F5

20-160Vac/dc

COM

V+

3 Element 4 Wire Wye (3LN, 3CT**) 3 Element 4 Wire Delta (3LL, 3CT) 3 Element 4 Wire Wye with PT (3LN, 3CT)

1 Element 2 Wire (1LN, 1CT)2 Element 3 Wire 1 Phase (1LL, 2CT)2 Element 3 Wire Delta with PT (2LL, 3CT)

AXM-IO1 AXM-IO2/IO3

Relay Output (RO) Wiring Energy Output (DO) Wiring

Note: *2CT configuration is optional only in 3 Phase 3 Wire system.

**Neutral CT is optional.

Acuvim II Acuvim II

Acuvim II

1A FUSE

1A FUSE1A FUSE

Terminal Block

LOAD

LOAD

LOAD

LOAD

LOAD

Acuvim II

A B C NLINELINELINE

LINE LINE

10 10 9 8 8 7 7 9

10 9 8 7

Acuvim II Advanced Power & Energy Meter | Datasheet | 11

Typical Wiring RCT/mV/mA Current Input

ACCESSORIES

DIN Rail Adapter

The AXM-DIN Rail Adapter is the easy way to mount the Acuvim II Series energy meter on either horizontal or vertical DIN rail. The adapter quickly secures to the meter and is compatible with all AXM communication modules as well as I/O options.

Protective Display Cover

The Protective Display Cover is designed for Acuvim II Series energy meters and other 96mm by 96mm display panel meters. Crucial in harsh environments, it increases the IP environmental rating of the meter's display to IP66 or NEMA 4X.

USB RS485 Converter

This plug-and-play USB to Serial RS485 Converter is designed to provide a convenient, reliable USB connection to the Acuvim II Series power meters and other serial devices.

WIRING DIAGRAMS

Note: *2CT configuration is optional only in 3 Phase 3 Wire system.

Terminal Block

LINE

1A FUSE

LOAD

I11

I12

I21

I22

I31

I32

VN V 3 V 2 V 1

I41

I42

3 Element 4 Wire Wye (3LN, 3CT**)

Terminal Block

LINE

1A FUSE

I11

I12

I21

I22

I31

I32

VN V 3 V 2 V 1

I41

I42

LOAD

3 Element 4 Wire Delta (3LL, 3CT)

Terminal Block

LINE

1A FUSE

LOAD

I11

I12

I21

I22

I31

I32

VN V 3 V 2 V 1

I41

I42

Terminal Block

LINE

1A FUSE

LOAD

I11

I12

I21

I22

I31

I32

VN V 3 V 2 V 1

I41

I42

2 Element 3 Wire 1 Phase (1LL, 2CT) 1 Element 2 Wire (1LN, 1CT)

Terminal Block

I11

I12

I21

I22

I31

I32

LINE

1A FUSE

VN V 3 V 2 V 1

LOAD

I41

I42

2 Element 3 Wire Delta (2LL, 3CT)

Terminal Block

LOAD

I11

I12

I21

I22

I31

I32

VN V 3 V 2 V 1

1A FUSE

I41

I42

3 Element 4 Wire Wye with PT (3LN, 3CT)

A B C N

A B C N

A B C

A N B A N

A B C

Acuvim II

Acuvim II

Acuvim II

Acuvim II

Acuvim II

Acuvim II

10 9 8 7 10 9 8 7 10 9 8 7

10 9 7 810 9 8 7

**Neutral CT is optional.

Acuvim II Advanced Power & Energy Meter | Datasheet | 12

Meter Model - Mounting Option - Current Input - Power Supply

Acuvim IIR:

Data logging, TOU

D: LCD Display (Panel Mount Meter/Transducer)

5A: 5A/1A (Input Field Selectable)

P1V3: 100~415Vac, 50/60Hz, 100~300Vdc

Acuvim IIW:

IIR + Waveform Capture and PQ Event Logging

M: DIN-Rail Mount Transducer without Display (Optional Remote Display Available) mV: 333mV and Rogowski Coil (Input Field Selectable) P2V3: 20~60Vdc mA: 80mA/100mA/200mA (Input Field Selectable)

Ordering Example: Acuvim-IIR-M-mV-P2V3

Acuvim-IIW-D-5A-P1V3

Accessories (Optional)

REM-DS2: Remote Display (Only for Acuvim II DIN-Rail Mount "M" option)

AXM-DIN: DIN Rail Adapter

IP66/NEMA4X: Environmental Protection Cover

USB-RS485: USB-to-RS485 Converter

Communication Module (Optional) - Protocols

AXM WEB2-FOLC:

IEC 61850 2nd Ed., Modbus-TCP, HTTP/HTTPs Webserver, SMTP Email, SNMP, HTTP/HTTPS Push, FTP Post, sFTP Server, BACnet-IP, Datalogging, Wi-Fi, Fiber Optics LC, Ethernet port, EtherNet/IP, MQTT, Modbus Gateway Passthrough

WEB2:

IEC 61850 2nd Ed., Modbus-TCP, HTTP/HTTPs Webserver, SMTP Email, SNMP, HTTP/ HTTPS Push, FTP Post, sFTP Server, BACnet-IP, Datalogging, Wi-Fi, Dual Ethernet Ports, EtherNet/IP, MQTT, Modbus Gateway Passthrough

WEB2-D:

IEC 61850 2nd Ed., Modbus-TCP, HTTP/HTTPs Webserver, SMTP Email, SNMP, HTTP/ HTTPS Push, FTP Post, sFTP Server, BACnet-IP, Datalogging, Dual Ethernet Ports, EtherNet/IP, MQTT, Modbus Gateway Passthrough

PROFI: PROFIBUS

RS485: Modbus-RTU

Ordering Example: AXM-RS485

AXM-WEB2-FOLC

ORDERING INFORMATION

Note:

Note:

1. Refer to the Communication table and I/O Module table.

2. A maximum of 3 modules may be attached to the meter. If a communication module is used (e.g. AXM-WEB2), it must be installed on the back FIRST before the other I/O modules are attached.

3. No more than 2 of the same I/O modules may be attached to the meter (e.g. two AXM-IO2). The same two I/O modules must have different logic numbers.

Logic numbers can be configured as either 1 or 2 through Acuview 2 or AXM-WEB2.

4. If Acuvim IIW uses DI to trigger a waveform capture, the I/O module logic number must be Module 1.

1. Accuenergy suggests using a USB-RS485 converter for configuration, and 3 CTs per three phase circuits.

2. All fields must be completed to create a part number.

3. Add “-S” after power supply for anti-tampering seal option.

Accuenergy Inc.

Los Angeles - Toronto - Pretoria

North America Toll Free: 1-877-721-8908 Web: www.accuenergy.com Email: marketing@accuenergy.com

Revision Date: January 2026 Version: 2.0.16 Specs Subject To Change Without Notice.

+ +I/O Module (Optional)

AXM-IO1 6 Digital Inputs, 2 Relay Outputs, 24Vdc Power Supply

AXM-IO2 4 Digital Inputs, 2 Digital Outputs, 2 Analog Outputs (0~5V or 1~5V, 0~20mA or 4~20mA)

AXM-IO3 4 Digital Inputs, 2 Relay Outputs, 2 Analog Inputs (0~5V or 1~5V, 0~20mA or 4~20mA)

Ordering Example: AXM-IO1

ISO 9001, 14001

& 45001 Certified

File details come from the government source that posted it. Updated .