This is an Inspection & Testing Requirements attachment that details fire detection and alarm system maintenance procedures across multiple federal facilities. The document specifies inspection and testing frequencies for 10 facilities on annual and semi-annual schedules, and 6 facilities on monthly schedules. Facilities include J.F. Carr Powerplant, Keswick Office Building, Keswick Powerplant, Lewiston Powerplant, Shasta Dam, Shasta Maintenance Center, Shasta Powerplant, Spring Creek Powerplant, Trinity Powerplant, and Upper Vista House.
Maintenance actions are organized by component type and include inspections and tests for control equipment, transponders, alarm control units, Digital Alarm Communication Transmitters (DACT), secondary power supplies, batteries, remote annunciators, circuit integrity conductors, initiating devices (manual pull stations, smoke detectors, heat detectors, projected beam detectors, and duct detectors), alarm notification appliances, and supervising station alarm system receivers. All maintenance procedures reference either NFPA 72 standards (primarily Tables 14.3.1 and 14.4.3.2) or FIST 4-1 standards (Section 18.2). Annual frequencies dominate the requirements, with monthly testing limited to 30-second backup battery power function tests and supervising station alarm system receiver tests at powerplant locations. Semiannual inspections are specified for control equipment, batteries, remote annunciators, initiating devices, and notification appliances across all facilities.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Location Component Quantity Maintenance Action Reference/Method Frequency
J.F. Carr Powerplant All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually
J.F. Carr Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually
J.F. Carr Powerplant Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually
J.F. Carr Powerplant Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually
J.F. Carr Powerplant Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually
J.F. Carr Powerplant Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually
J.F. Carr Powerplant Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually
J.F. Carr Powerplant Batteries, all types within fire det & alarm sys 2 Inspect FIST 4-1, Section 18.2, row 5 Annually
J.F. Carr Powerplant 90-min Battery Discharge Test 1 Test FIST 4-1, Section 18.2, row 6 Annually
J.F. Carr Powerplant Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually
J.F. Carr Powerplant Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually
J.F. Carr Powerplant Initiating Device - Manual Pull Stations 4 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually
J.F. Carr Powerplant Initiating Device - Smoke Detectors 28 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually
J.F. Carr Powerplant Initiating Device - Projected Beam Detectors 2 Test NFPA 72, Table 14.4.3.2, line 17 (7) (f) Annually
J.F. Carr Powerplant Alarm Notification Appliances (strobe & horn/strobe) 29 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually
J.F. Carr Powerplant 30-sec Backup Battery Power Function Test 1 Test FIST 4-1, Section 18.2, row 3 Monthly
J.F. Carr Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually
J.F. Carr Powerplant Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually
J.F. Carr Powerplant Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually
J.F. Carr Powerplant Initiating Device - Manual Pull Stations 4 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually
J.F. Carr Powerplant Initiating Device - Smoke Detectors 28 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually
J.F. Carr Powerplant Initiating Device - Projected Beam Detectors 2 Inspect NFPA 72, Table 14.3.1, line 17 (10) Semiannually
J.F. Carr Powerplant Notification Appliances (strobe & horn/strobe) 29 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually
Keswick Office Building All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually
Keswick Office Building Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually
Keswick Office Building Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually
Keswick Office Building Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually
Keswick Office Building Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually
Keswick Office Building Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually
Keswick Office Building Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually
Keswick Office Building Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually
Keswick Office Building Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually
Keswick Office Building Initiating Device - Manual Pull Stations 8 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually
Keswick Office Building Initiating Device - Heat Detectors 2 Test NFPA 72, Table 14.4.3.2, line 17 (4)(a) Annually
Keswick Office Building Initiating Device - Smoke Detectors 52 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually
Keswick Office Building Initiating Device - Duct Detectors 6 Inspect NFPA 72, Table 14.3.1, line 17 (2)(b) Annually
Keswick Office Building Initiating Device - Duct Detectors 6 Test NFPA 72, Table 14.4.3.2, line 17 (7)(e) Annually
Keswick Office Building Alarm Notification Appliances (strobe & horn/strobe) 28 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually
Keswick Office Building Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually
Keswick Office Building Batteries 1 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually
Keswick Office Building Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually
Keswick Office Building Initiating Device - Manual Pull Stations 8 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually
Keswick Office Building Initiating Device - Heat Detectors 2 Inspect NFPA 72, Table 14.3.1, line 17 (6) Semiannually
Keswick Office Building Initiating Device - Smoke Detectors 52 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually
Attachment 3: Inspection & Testing Requirements
(Annual/Semi-Annual/Monthly) 10 facilities (Annually & Semi-Anually); 6 facilites (Monthly)
Keswick Office Building Initiating Device - Duct Detectors 6 Inspect NFPA 72, Table 14.3.1, line 17 (2)(a) Semiannually
Keswick Office Building Notification Appliances (strobe & horn/strobe) 28 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually
Keswick Powerplant All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually
Keswick Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually
Keswick Powerplant Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually
Keswick Powerplant Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually
Keswick Powerplant Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually
Keswick Powerplant Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually
Keswick Powerplant Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually
Keswick Powerplant Batteries, all types within fire det & alarm sys 8 Inspect FIST 4-1, Section 18.2, row 5 Annually
Keswick Powerplant 90-min Battery Discharge Test 1 Test FIST 4-1, Section 18.2, row 6 Annually
Keswick Powerplant Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually
Keswick Powerplant Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually
Keswick Powerplant Initiating Device - Manual Pull Stations 17 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually
Keswick Powerplant Initiating Device - Heat Detectors 1 Test NFPA 72, Table 14.4.3.2, line 17 (12) Annually
Keswick Powerplant Initiating Device - Smoke Detectors 60 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually
Keswick Powerplant Initiating Device - Projected Beam Detectors 3 Test NFPA 72, Table 14.4.3.2, line 17 (7) (f) Annually
Keswick Powerplant Initiating Device - Duct Detectors 10 Inspect NFPA 72, Table 14.3.1, line 17 (2)(b) Annually
Keswick Powerplant Initiating Device - Duct Detectors 10 Test NFPA 72, Table 14.4.3.2, line 17 (7)(e) Annually
Keswick Powerplant Alarm Notification Appliances (strobe & horn/strobe) 57 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually
Keswick Powerplant 30-sec Backup Battery Power Function Test 1 Test FIST 4-1, Section 18.2, row 3 Monthly
Keswick Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually
Keswick Powerplant Batteries 8 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually
Keswick Powerplant Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually
Keswick Powerplant Initiating Device - Manual Pull Stations 17 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually
Keswick Powerplant Initiating Device - Heat Detectors 1 Inspect NFPA 72, Table 14.3.1, line 17 (6) (9) Semiannually
Keswick Powerplant Initiating Device - Smoke Detectors 60 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually
Keswick Powerplant Initiating Device - Projected Beam Detectors 3 Inspect NFPA 72, Table 14.3.1, line 17 (10) Semiannually
Keswick Powerplant Initiating Device - Duct Detectors 10 Inspect NFPA 72, Table 14.3.1, line 17 (2)(a) Semiannually
Keswick Powerplant Notification Appliances (strobe & horn/strobe) 57 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually
Lewiston Powerplant All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually
Lewiston Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually
Lewiston Powerplant Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually
Lewiston Powerplant Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually
Lewiston Powerplant Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually
Lewiston Powerplant Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually
Lewiston Powerplant Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually
Lewiston Powerplant Batteries, all types within fire det & alarm sys 2 Inspect FIST 4-1, Section 18.2, row 5 Annually
Lewiston Powerplant 90-min Battery Discharge Test 1 Test FIST 4-1, Section 18.2, row 6 Annually
Lewiston Powerplant Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually
Lewiston Powerplant Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually
Lewiston Powerplant Initiating Device - Manual Pull Stations 2 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually
Lewiston Powerplant Initiating Device - Smoke Detectors 5 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually
Lewiston Powerplant Alarm Notification Appliances (strobe & horn/strobe) 3 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually
Lewiston Powerplant 30-sec Backup Battery Power Function Test 1 Test FIST 4-1, Section 18.2, row 3 Monthly
Lewiston Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually
Lewiston Powerplant Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually
Lewiston Powerplant Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually
Lewiston Powerplant Initiating Device - Manual Pull Stations 2 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually
Lewiston Powerplant Initiating Device - Smoke Detectors 5 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually
Lewiston Powerplant Notification Appliances (strobe & horn/strobe) 3 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually
Shasta Dam All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually
Shasta Dam Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually
Shasta Dam Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually
Shasta Dam Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually
Shasta Dam Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually
Shasta Dam Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually
Shasta Dam Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually
Shasta Dam Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually
Shasta Dam Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually
Shasta Dam Initiating Device - Manual Pull Stations 14 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually
Shasta Dam Initiating Device - Smoke Detectors 27 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually
Shasta Dam Alarm Notification Appliances (strobe & horn/strobe) 22 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually
Shasta Dam Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually
Shasta Dam Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually
Shasta Dam Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually
Shasta Dam Initiating Device - Manual Pull Stations 14 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually
Shasta Dam Initiating Device - Smoke Detectors 27 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually
Shasta Dam Notification Appliances (strobe & horn/strobe) 22 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually
Shasta Maintenance Center All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually
Shasta Maintenance Center Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually
Shasta Maintenance Center Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually
Shasta Maintenance Center Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually
Shasta Maintenance Center Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually
Shasta Maintenance Center Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually
Shasta Maintenance Center Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually
Shasta Maintenance Center Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually
Shasta Maintenance Center Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually
Shasta Maintenance Center Initiating Device - Manual Pull Stations 10 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually
Shasta Maintenance Center Initiating Device - Heat Detectors 8 Test NFPA 72, Table 14.4.3.2, line 17 (4)(a) Annually
Shasta Maintenance Center Initiating Device - Smoke Detectors 43 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually
Shasta Maintenance Center Initiating Device - Projected Beam Detectors 2 Test NFPA 72, Table 14.4.3.2, line 17 (7) (f) Annually
Shasta Maintenance Center Alarm Notification Appliances (strobe & horn/strobe) 33 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually
Shasta Maintenance Center Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually
Shasta Maintenance Center Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually
Shasta Maintenance Center Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually
Shasta Maintenance Center Initiating Device - Manual Pull Stations 10 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually
Shasta Maintenance Center Initiating Device - Heat Detectors 8 Inspect NFPA 72, Table 14.3.1, line 17 (6) Semiannually
Shasta Maintenance Center Initiating Device - Smoke Detectors 43 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually
Shasta Maintenance Center Initiating Device - Projected Beam Detectors 2 Inspect NFPA 72, Table 14.3.1, line 17 (10) Semiannually
Shasta Maintenance Center Notification Appliances (strobe & horn/strobe) 33 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually
Shasta Powerplant All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually
Shasta Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually
Shasta Powerplant Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually
Shasta Powerplant Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually
Shasta Powerplant Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually
Shasta Powerplant Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually
Shasta Powerplant Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually
Shasta Powerplant Batteries, all types within fire det & alarm sys 10 Inspect FIST 4-1, Section 18.2, row 5 Annually
Shasta Powerplant 90-min Battery Discharge Test 1 Test FIST 4-1, Section 18.2, row 6 Annually
Shasta Powerplant Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually
Shasta Powerplant Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually
Shasta Powerplant Initiating Device - Manual Pull Stations 24 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually
Shasta Powerplant Initiating Device - Heat Detectors 3 Test NFPA 72, Table 14.4.3.2, line 17 (12) Annually
Shasta Powerplant Initiating Device - Smoke Detectors 67 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually
Shasta Powerplant Initiating Device - Projected Beam Detectors 3 Test NFPA 72, Table 14.4.3.2, line 17 (7) (f) Annually
Shasta Powerplant Initiating Device - Duct Detectors 12 Inspect NFPA 72, Table 14.3.1, line 17 (2)(b) Annually
Shasta Powerplant Initiating Device - Duct Detectors 12 Test NFPA 72, Table 14.4.3.2, line 17 (7)(e) Annually
Shasta Powerplant Alarm Notification Appliances (strobe & horn/strobe) 95 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually
Shasta Powerplant Supervising Station Alarm System - Receiver 1 Inspect NFPA 72, Table 14.3.1, line 27 (2) Annually
Shasta Powerplant 30-sec Backup Battery Power Function Test 1 Test FIST 4-1, Section 18.2, row 3 Monthly
Shasta Powerplant Supervising Station Alarm System - Receiver 1 Test NFPA 72, Table 14.4.3.2, line 27 (1) (2) Monthly
Shasta Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually
Shasta Powerplant Batteries 10 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually
Shasta Powerplant Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually
Shasta Powerplant Initiating Device - Manual Pull Stations 24 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually
Shasta Powerplant Initiating Device - Heat Detectors 3 Inspect NFPA 72, Table 14.3.1, line 17 (6) (9) Semiannually
Shasta Powerplant Initiating Device - Smoke Detectors 67 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually
Shasta Powerplant Initiating Device - Projected Beam Detectors 3 Inspect NFPA 72, Table 14.3.1, line 17 (10) Semiannually
Shasta Powerplant Initiating Device - Duct Detectors 12 Inspect NFPA 72, Table 14.3.1, line 17 (2)(a) Semiannually
Shasta Powerplant Notification Appliances (strobe & horn/strobe) 95 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually
Spring Creek Powerplant All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually
Spring Creek Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually
Spring Creek Powerplant Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually
Spring Creek Powerplant Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually
Spring Creek Powerplant Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually
Spring Creek Powerplant Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually
Spring Creek Powerplant Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually
Spring Creek Powerplant Batteries, all types within fire det & alarm sys 2 Inspect FIST 4-1, Section 18.2, row 5 Annually
Spring Creek Powerplant 90-min Battery Discharge Test 1 Test FIST 4-1, Section 18.2, row 6 Annually
Spring Creek Powerplant Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually
Spring Creek Powerplant Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually
Spring Creek Powerplant Initiating Device - Manual Pull Stations 5 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually
Spring Creek Powerplant Initiating Device - Smoke Detectors 21 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually
Spring Creek Powerplant Initiating Device - Projected Beam Detectors 2 Test NFPA 72, Table 14.4.3.2, line 17 (7) (f) Annually
Spring Creek Powerplant Alarm Notification Appliances (strobe & horn/strobe) 24 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually
Spring Creek Powerplant 30-sec Backup Battery Power Function Test 1 Test FIST 4-1, Section 18.2, row 3 Monthly
Spring Creek Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually
Spring Creek Powerplant Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually
Spring Creek Powerplant Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually
Spring Creek Powerplant Initiating Device - Manual Pull Stations 5 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually
Spring Creek Powerplant Initiating Device - Smoke Detectors 21 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually
Spring Creek Powerplant Initiating Device - Projected Beam Detectors 2 Inspect NFPA 72, Table 14.3.1, line 17 (10) Semiannually
Spring Creek Powerplant Notification Appliances (strobe & horn/strobe) 24 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually
Trinity Powerplant All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually
Trinity Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually
Trinity Powerplant Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually
Trinity Powerplant Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually
Trinity Powerplant Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually
Trinity Powerplant Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually
Trinity Powerplant Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually
Trinity Powerplant Batteries, all types within fire det & alarm sys 2 Inspect FIST 4-1, Section 18.2, row 5 Annually
Trinity Powerplant 90-min Battery Discharge Test 1 Test FIST 4-1, Section 18.2, row 6 Annually
Trinity Powerplant Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually
Trinity Powerplant Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually
Trinity Powerplant Initiating Device - Manual Pull Stations 4 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually
Trinity Powerplant Initiating Device - Smoke Detectors 24 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually
Trinity Powerplant Initiating Device - Projected Beam Detectors 2 Test NFPA 72, Table 14.4.3.2, line 17 (7) (f) Annually
Trinity Powerplant Alarm Notification Appliances (strobe & horn/strobe) 27 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually
Trinity Powerplant 30-sec Backup Battery Power Function Test 1 Test FIST 4-1, Section 18.2, row 3 Monthly
Trinity Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually
Trinity Powerplant Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually
Trinity Powerplant Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually
Trinity Powerplant Initiating Device - Manual Pull Stations 4 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually
Trinity Powerplant Initiating Device - Smoke Detectors 24 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually
Trinity Powerplant Initiating Device - Projected Beam Detectors 2 Inspect NFPA 72, Table 14.3.1, line 17 (10) Semiannually
Trinity Powerplant Notification Appliances (strobe & horn/strobe) 27 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually
Upper Vista House All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually
Upper Vista House Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually
Upper Vista House Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually
Upper Vista House Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually
Upper Vista House Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually
Upper Vista House Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually
Upper Vista House Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually
Upper Vista House Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually
Upper Vista House Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually
Upper Vista House Initiating Device - Manual Pull Stations 8 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually
Upper Vista House Initiating Device - Heat Detectors 2 Test NFPA 72, Table 14.4.3.2, line 17 (4)(a) Annually
Upper Vista House Initiating Device - Smoke Detectors 51 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually
Upper Vista House Initiating Device - Duct Detectors 6 Inspect NFPA 72, Table 14.3.1, line 17 (2)(b) Annually
Upper Vista House Initiating Device - Duct Detectors 6 Test NFPA 72, Table 14.4.3.2, line 17 (7)(e) Annually
Upper Vista House Alarm Notification Appliances (strobe & horn/strobe) 28 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually
Upper Vista House Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually
Upper Vista House Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually
Upper Vista House Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually
Upper Vista House Initiating Device - Manual Pull Stations 8 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually
Upper Vista House Initiating Device - Heat Detectors 2 Inspect NFPA 72, Table 14.3.1, line 17 (6) Semiannually
Upper Vista House Initiating Device - Smoke Detectors 51 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually
Upper Vista House Initiating Device - Duct Detectors 6 Inspect NFPA 72, Table 14.3.1, line 17 (2)(a) Semiannually
Upper Vista House Notification Appliances (strobe & horn/strobe) 28 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually