Attch_3__Inspection-Testing_List_1.pdf

PDF 392 KB Posted

Attached to
Northern California Area Office (NCAO) Fire Alarm Maintenance Services
Solicitation number
140R2026Q0116
Issued by

About this file

This is an Inspection & Testing Requirements attachment that details fire detection and alarm system maintenance procedures across multiple federal facilities. The document specifies inspection and testing frequencies for 10 facilities on annual and semi-annual schedules, and 6 facilities on monthly schedules. Facilities include J.F. Carr Powerplant, Keswick Office Building, Keswick Powerplant, Lewiston Powerplant, Shasta Dam, Shasta Maintenance Center, Shasta Powerplant, Spring Creek Powerplant, Trinity Powerplant, and Upper Vista House.

Maintenance actions are organized by component type and include inspections and tests for control equipment, transponders, alarm control units, Digital Alarm Communication Transmitters (DACT), secondary power supplies, batteries, remote annunciators, circuit integrity conductors, initiating devices (manual pull stations, smoke detectors, heat detectors, projected beam detectors, and duct detectors), alarm notification appliances, and supervising station alarm system receivers. All maintenance procedures reference either NFPA 72 standards (primarily Tables 14.3.1 and 14.4.3.2) or FIST 4-1 standards (Section 18.2). Annual frequencies dominate the requirements, with monthly testing limited to 30-second backup battery power function tests and supervising station alarm system receiver tests at powerplant locations. Semiannual inspections are specified for control equipment, batteries, remote annunciators, initiating devices, and notification appliances across all facilities.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Location Component Quantity Maintenance Action Reference/Method Frequency

J.F. Carr Powerplant All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually

J.F. Carr Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually

J.F. Carr Powerplant Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually

J.F. Carr Powerplant Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually

J.F. Carr Powerplant Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually

J.F. Carr Powerplant Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually

J.F. Carr Powerplant Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually

J.F. Carr Powerplant Batteries, all types within fire det & alarm sys 2 Inspect FIST 4-1, Section 18.2, row 5 Annually

J.F. Carr Powerplant 90-min Battery Discharge Test 1 Test FIST 4-1, Section 18.2, row 6 Annually

J.F. Carr Powerplant Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually

J.F. Carr Powerplant Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually

J.F. Carr Powerplant Initiating Device - Manual Pull Stations 4 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually

J.F. Carr Powerplant Initiating Device - Smoke Detectors 28 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually

J.F. Carr Powerplant Initiating Device - Projected Beam Detectors 2 Test NFPA 72, Table 14.4.3.2, line 17 (7) (f) Annually

J.F. Carr Powerplant Alarm Notification Appliances (strobe & horn/strobe) 29 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually

J.F. Carr Powerplant 30-sec Backup Battery Power Function Test 1 Test FIST 4-1, Section 18.2, row 3 Monthly

J.F. Carr Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually

J.F. Carr Powerplant Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually

J.F. Carr Powerplant Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually

J.F. Carr Powerplant Initiating Device - Manual Pull Stations 4 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually

J.F. Carr Powerplant Initiating Device - Smoke Detectors 28 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually

J.F. Carr Powerplant Initiating Device - Projected Beam Detectors 2 Inspect NFPA 72, Table 14.3.1, line 17 (10) Semiannually

J.F. Carr Powerplant Notification Appliances (strobe & horn/strobe) 29 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually

Keswick Office Building All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually

Keswick Office Building Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually

Keswick Office Building Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually

Keswick Office Building Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually

Keswick Office Building Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually

Keswick Office Building Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually

Keswick Office Building Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually

Keswick Office Building Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually

Keswick Office Building Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually

Keswick Office Building Initiating Device - Manual Pull Stations 8 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually

Keswick Office Building Initiating Device - Heat Detectors 2 Test NFPA 72, Table 14.4.3.2, line 17 (4)(a) Annually

Keswick Office Building Initiating Device - Smoke Detectors 52 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually

Keswick Office Building Initiating Device - Duct Detectors 6 Inspect NFPA 72, Table 14.3.1, line 17 (2)(b) Annually

Keswick Office Building Initiating Device - Duct Detectors 6 Test NFPA 72, Table 14.4.3.2, line 17 (7)(e) Annually

Keswick Office Building Alarm Notification Appliances (strobe & horn/strobe) 28 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually

Keswick Office Building Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually

Keswick Office Building Batteries 1 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually

Keswick Office Building Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually

Keswick Office Building Initiating Device - Manual Pull Stations 8 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually

Keswick Office Building Initiating Device - Heat Detectors 2 Inspect NFPA 72, Table 14.3.1, line 17 (6) Semiannually

Keswick Office Building Initiating Device - Smoke Detectors 52 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually

Attachment 3: Inspection & Testing Requirements

(Annual/Semi-Annual/Monthly) 10 facilities (Annually & Semi-Anually); 6 facilites (Monthly)

Keswick Office Building Initiating Device - Duct Detectors 6 Inspect NFPA 72, Table 14.3.1, line 17 (2)(a) Semiannually

Keswick Office Building Notification Appliances (strobe & horn/strobe) 28 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually

Keswick Powerplant All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually

Keswick Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually

Keswick Powerplant Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually

Keswick Powerplant Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually

Keswick Powerplant Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually

Keswick Powerplant Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually

Keswick Powerplant Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually

Keswick Powerplant Batteries, all types within fire det & alarm sys 8 Inspect FIST 4-1, Section 18.2, row 5 Annually

Keswick Powerplant 90-min Battery Discharge Test 1 Test FIST 4-1, Section 18.2, row 6 Annually

Keswick Powerplant Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually

Keswick Powerplant Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually

Keswick Powerplant Initiating Device - Manual Pull Stations 17 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually

Keswick Powerplant Initiating Device - Heat Detectors 1 Test NFPA 72, Table 14.4.3.2, line 17 (12) Annually

Keswick Powerplant Initiating Device - Smoke Detectors 60 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually

Keswick Powerplant Initiating Device - Projected Beam Detectors 3 Test NFPA 72, Table 14.4.3.2, line 17 (7) (f) Annually

Keswick Powerplant Initiating Device - Duct Detectors 10 Inspect NFPA 72, Table 14.3.1, line 17 (2)(b) Annually

Keswick Powerplant Initiating Device - Duct Detectors 10 Test NFPA 72, Table 14.4.3.2, line 17 (7)(e) Annually

Keswick Powerplant Alarm Notification Appliances (strobe & horn/strobe) 57 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually

Keswick Powerplant 30-sec Backup Battery Power Function Test 1 Test FIST 4-1, Section 18.2, row 3 Monthly

Keswick Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually

Keswick Powerplant Batteries 8 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually

Keswick Powerplant Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually

Keswick Powerplant Initiating Device - Manual Pull Stations 17 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually

Keswick Powerplant Initiating Device - Heat Detectors 1 Inspect NFPA 72, Table 14.3.1, line 17 (6) (9) Semiannually

Keswick Powerplant Initiating Device - Smoke Detectors 60 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually

Keswick Powerplant Initiating Device - Projected Beam Detectors 3 Inspect NFPA 72, Table 14.3.1, line 17 (10) Semiannually

Keswick Powerplant Initiating Device - Duct Detectors 10 Inspect NFPA 72, Table 14.3.1, line 17 (2)(a) Semiannually

Keswick Powerplant Notification Appliances (strobe & horn/strobe) 57 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually

Lewiston Powerplant All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually

Lewiston Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually

Lewiston Powerplant Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually

Lewiston Powerplant Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually

Lewiston Powerplant Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually

Lewiston Powerplant Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually

Lewiston Powerplant Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually

Lewiston Powerplant Batteries, all types within fire det & alarm sys 2 Inspect FIST 4-1, Section 18.2, row 5 Annually

Lewiston Powerplant 90-min Battery Discharge Test 1 Test FIST 4-1, Section 18.2, row 6 Annually

Lewiston Powerplant Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually

Lewiston Powerplant Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually

Lewiston Powerplant Initiating Device - Manual Pull Stations 2 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually

Lewiston Powerplant Initiating Device - Smoke Detectors 5 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually

Lewiston Powerplant Alarm Notification Appliances (strobe & horn/strobe) 3 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually

Lewiston Powerplant 30-sec Backup Battery Power Function Test 1 Test FIST 4-1, Section 18.2, row 3 Monthly

Lewiston Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually

Lewiston Powerplant Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually

Lewiston Powerplant Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually

Lewiston Powerplant Initiating Device - Manual Pull Stations 2 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually

Lewiston Powerplant Initiating Device - Smoke Detectors 5 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually

Lewiston Powerplant Notification Appliances (strobe & horn/strobe) 3 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually

Shasta Dam All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually

Shasta Dam Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually

Shasta Dam Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually

Shasta Dam Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually

Shasta Dam Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually

Shasta Dam Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually

Shasta Dam Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually

Shasta Dam Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually

Shasta Dam Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually

Shasta Dam Initiating Device - Manual Pull Stations 14 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually

Shasta Dam Initiating Device - Smoke Detectors 27 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually

Shasta Dam Alarm Notification Appliances (strobe & horn/strobe) 22 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually

Shasta Dam Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually

Shasta Dam Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually

Shasta Dam Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually

Shasta Dam Initiating Device - Manual Pull Stations 14 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually

Shasta Dam Initiating Device - Smoke Detectors 27 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually

Shasta Dam Notification Appliances (strobe & horn/strobe) 22 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually

Shasta Maintenance Center All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually

Shasta Maintenance Center Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually

Shasta Maintenance Center Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually

Shasta Maintenance Center Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually

Shasta Maintenance Center Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually

Shasta Maintenance Center Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually

Shasta Maintenance Center Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually

Shasta Maintenance Center Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually

Shasta Maintenance Center Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually

Shasta Maintenance Center Initiating Device - Manual Pull Stations 10 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually

Shasta Maintenance Center Initiating Device - Heat Detectors 8 Test NFPA 72, Table 14.4.3.2, line 17 (4)(a) Annually

Shasta Maintenance Center Initiating Device - Smoke Detectors 43 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually

Shasta Maintenance Center Initiating Device - Projected Beam Detectors 2 Test NFPA 72, Table 14.4.3.2, line 17 (7) (f) Annually

Shasta Maintenance Center Alarm Notification Appliances (strobe & horn/strobe) 33 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually

Shasta Maintenance Center Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually

Shasta Maintenance Center Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually

Shasta Maintenance Center Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually

Shasta Maintenance Center Initiating Device - Manual Pull Stations 10 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually

Shasta Maintenance Center Initiating Device - Heat Detectors 8 Inspect NFPA 72, Table 14.3.1, line 17 (6) Semiannually

Shasta Maintenance Center Initiating Device - Smoke Detectors 43 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually

Shasta Maintenance Center Initiating Device - Projected Beam Detectors 2 Inspect NFPA 72, Table 14.3.1, line 17 (10) Semiannually

Shasta Maintenance Center Notification Appliances (strobe & horn/strobe) 33 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually

Shasta Powerplant All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually

Shasta Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually

Shasta Powerplant Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually

Shasta Powerplant Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually

Shasta Powerplant Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually

Shasta Powerplant Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually

Shasta Powerplant Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually

Shasta Powerplant Batteries, all types within fire det & alarm sys 10 Inspect FIST 4-1, Section 18.2, row 5 Annually

Shasta Powerplant 90-min Battery Discharge Test 1 Test FIST 4-1, Section 18.2, row 6 Annually

Shasta Powerplant Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually

Shasta Powerplant Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually

Shasta Powerplant Initiating Device - Manual Pull Stations 24 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually

Shasta Powerplant Initiating Device - Heat Detectors 3 Test NFPA 72, Table 14.4.3.2, line 17 (12) Annually

Shasta Powerplant Initiating Device - Smoke Detectors 67 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually

Shasta Powerplant Initiating Device - Projected Beam Detectors 3 Test NFPA 72, Table 14.4.3.2, line 17 (7) (f) Annually

Shasta Powerplant Initiating Device - Duct Detectors 12 Inspect NFPA 72, Table 14.3.1, line 17 (2)(b) Annually

Shasta Powerplant Initiating Device - Duct Detectors 12 Test NFPA 72, Table 14.4.3.2, line 17 (7)(e) Annually

Shasta Powerplant Alarm Notification Appliances (strobe & horn/strobe) 95 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually

Shasta Powerplant Supervising Station Alarm System - Receiver 1 Inspect NFPA 72, Table 14.3.1, line 27 (2) Annually

Shasta Powerplant 30-sec Backup Battery Power Function Test 1 Test FIST 4-1, Section 18.2, row 3 Monthly

Shasta Powerplant Supervising Station Alarm System - Receiver 1 Test NFPA 72, Table 14.4.3.2, line 27 (1) (2) Monthly

Shasta Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually

Shasta Powerplant Batteries 10 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually

Shasta Powerplant Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually

Shasta Powerplant Initiating Device - Manual Pull Stations 24 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually

Shasta Powerplant Initiating Device - Heat Detectors 3 Inspect NFPA 72, Table 14.3.1, line 17 (6) (9) Semiannually

Shasta Powerplant Initiating Device - Smoke Detectors 67 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually

Shasta Powerplant Initiating Device - Projected Beam Detectors 3 Inspect NFPA 72, Table 14.3.1, line 17 (10) Semiannually

Shasta Powerplant Initiating Device - Duct Detectors 12 Inspect NFPA 72, Table 14.3.1, line 17 (2)(a) Semiannually

Shasta Powerplant Notification Appliances (strobe & horn/strobe) 95 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually

Spring Creek Powerplant All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually

Spring Creek Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually

Spring Creek Powerplant Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually

Spring Creek Powerplant Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually

Spring Creek Powerplant Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually

Spring Creek Powerplant Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually

Spring Creek Powerplant Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually

Spring Creek Powerplant Batteries, all types within fire det & alarm sys 2 Inspect FIST 4-1, Section 18.2, row 5 Annually

Spring Creek Powerplant 90-min Battery Discharge Test 1 Test FIST 4-1, Section 18.2, row 6 Annually

Spring Creek Powerplant Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually

Spring Creek Powerplant Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually

Spring Creek Powerplant Initiating Device - Manual Pull Stations 5 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually

Spring Creek Powerplant Initiating Device - Smoke Detectors 21 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually

Spring Creek Powerplant Initiating Device - Projected Beam Detectors 2 Test NFPA 72, Table 14.4.3.2, line 17 (7) (f) Annually

Spring Creek Powerplant Alarm Notification Appliances (strobe & horn/strobe) 24 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually

Spring Creek Powerplant 30-sec Backup Battery Power Function Test 1 Test FIST 4-1, Section 18.2, row 3 Monthly

Spring Creek Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually

Spring Creek Powerplant Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually

Spring Creek Powerplant Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually

Spring Creek Powerplant Initiating Device - Manual Pull Stations 5 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually

Spring Creek Powerplant Initiating Device - Smoke Detectors 21 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually

Spring Creek Powerplant Initiating Device - Projected Beam Detectors 2 Inspect NFPA 72, Table 14.3.1, line 17 (10) Semiannually

Spring Creek Powerplant Notification Appliances (strobe & horn/strobe) 24 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually

Trinity Powerplant All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually

Trinity Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually

Trinity Powerplant Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually

Trinity Powerplant Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually

Trinity Powerplant Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually

Trinity Powerplant Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually

Trinity Powerplant Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually

Trinity Powerplant Batteries, all types within fire det & alarm sys 2 Inspect FIST 4-1, Section 18.2, row 5 Annually

Trinity Powerplant 90-min Battery Discharge Test 1 Test FIST 4-1, Section 18.2, row 6 Annually

Trinity Powerplant Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually

Trinity Powerplant Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually

Trinity Powerplant Initiating Device - Manual Pull Stations 4 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually

Trinity Powerplant Initiating Device - Smoke Detectors 24 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually

Trinity Powerplant Initiating Device - Projected Beam Detectors 2 Test NFPA 72, Table 14.4.3.2, line 17 (7) (f) Annually

Trinity Powerplant Alarm Notification Appliances (strobe & horn/strobe) 27 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually

Trinity Powerplant 30-sec Backup Battery Power Function Test 1 Test FIST 4-1, Section 18.2, row 3 Monthly

Trinity Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually

Trinity Powerplant Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually

Trinity Powerplant Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually

Trinity Powerplant Initiating Device - Manual Pull Stations 4 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually

Trinity Powerplant Initiating Device - Smoke Detectors 24 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually

Trinity Powerplant Initiating Device - Projected Beam Detectors 2 Inspect NFPA 72, Table 14.3.1, line 17 (10) Semiannually

Trinity Powerplant Notification Appliances (strobe & horn/strobe) 27 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually

Upper Vista House All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually

Upper Vista House Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually

Upper Vista House Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually

Upper Vista House Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually

Upper Vista House Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually

Upper Vista House Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually

Upper Vista House Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually

Upper Vista House Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually

Upper Vista House Conductors - circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually

Upper Vista House Initiating Device - Manual Pull Stations 8 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually

Upper Vista House Initiating Device - Heat Detectors 2 Test NFPA 72, Table 14.4.3.2, line 17 (4)(a) Annually

Upper Vista House Initiating Device - Smoke Detectors 51 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually

Upper Vista House Initiating Device - Duct Detectors 6 Inspect NFPA 72, Table 14.3.1, line 17 (2)(b) Annually

Upper Vista House Initiating Device - Duct Detectors 6 Test NFPA 72, Table 14.4.3.2, line 17 (7)(e) Annually

Upper Vista House Alarm Notification Appliances (strobe & horn/strobe) 28 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually

Upper Vista House Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually

Upper Vista House Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually

Upper Vista House Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually

Upper Vista House Initiating Device - Manual Pull Stations 8 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually

Upper Vista House Initiating Device - Heat Detectors 2 Inspect NFPA 72, Table 14.3.1, line 17 (6) Semiannually

Upper Vista House Initiating Device - Smoke Detectors 51 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually

Upper Vista House Initiating Device - Duct Detectors 6 Inspect NFPA 72, Table 14.3.1, line 17 (2)(a) Semiannually

Upper Vista House Notification Appliances (strobe & horn/strobe) 28 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually