Attch 1 Salient Characteristics.pdf
PDF 271 KB Posted
- Attached to
- Coriolis Flow Measurement Instrument
- Solicitation number
- N0060426Q4077
About this file
This is a Statement of Work (SOW) for the procurement of a Coriolis Flow Measurement Instrument for Joint Base Pearl Harbor Hickam's (JBPHH) JB7 Fuel Department, intended for liquid fuel custody transfer applications.
The contractor must provide one Coriolis Flow Measurement Instrument consisting of a sensor and transmitter, plus shipping. The flow sensor requires 8" ASME B16.5 CL-150 RF, 316 stainless steel weld neck flanges and must be designed for kerosene-jet-diesel fluid with density 0.807 to 0.848 g/cc and viscosity 1.42 to 3.50 cSt. Operating specifications include a maximum allowable pressure of 219 psig (normal 20–100 psig), maximum temperature of 100°F (normal 85°F), maximum flow of 5,600 gpm with normal flow of 1,800–3,600 gpm, and a pressure drop not exceeding 15 psid at 3,600 gpm. The sensor must support bidirectional flow, full pipe operation in horizontal/straight orientation (tubes down), and achieve 0.05% mass flow and 0.0005 g/cc density calibration accuracy. The transmitter requires 18 to 28.8 VDC power (nominal 24 VDC), coated aluminum housing, and a local high-visibility graphic display showing lbm/hr, density, gpm with reference density, °F, total lbm, and total gal. The transmitter must feature local pushbutton or touchscreen interface for complete standalone configuration without external laptops or communicators, 100 ms update rate, self-diagnosis, totalizer display, non-volatile memory with automatic recovery, and on-board data historian with nominal one-year storage capacity. The system must support three independent communication channels: two configurable 4–20 mA channels with frequency and discrete output options, and one Modbus RS-485 channel. All equipment must be rated for outdoor tropical/marine environment installation in Hawaii and certified for Class I, Division 2, Group D hazardous locations. The contractor shall deliver three hard copies and one digital file each of Operations & Maintenance Manuals, Material Test Reports, Hydrostatic Test Reports, and Hazardous Area Certifications, with all documentation in English utilizing Imperial/U.S. customary units. Delivery is required within 8–10 weeks of award to JBPHH, JB7 Fuel Department, Bldg. 1757 Neosho Avenue, Pearl Harbor, HI 96860.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| N0060426Q4077 Q and A.pdf | ||
| Attch 2 P and Cs.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JB7 Fuel Department
Joint Base Pearl Harbor Hickam
Procurement of Coriolis Flow Measurement Instrument for Liquid Fuel Custody Transfer
1.0 Scope
JB7 Fuel Department is seeking a contractor who can provide a fully functioning Coriolis Flow Measurement
Instrument (Sensor and Transmitter) that meets all technical, environmental, and documentation requirements specified below.
2.0 Requirements
Item Product Description Qty Unit of Issue
1 Coriolis Flow Measurement Instrument (Sensor and Transmitter)
1 Each
2 Shipping 1 Each
The Contractor shall provide equipment meeting or exceeding the following minimum technical specifications. All measurements, displays, and documentation must utilize English language and Imperial/U.S. customary units.
2.1 Flow Sensor requires the following minimum salient characteristics:
Parameter Specification
Process Connections 8” ASME B16.5 CL-150 RF, 316 SS weld neck
Flange-to-Flange Distance No requirement
Industry Standard ASME B31.3
Fluid Liquid; Kerosene-Jet-Diesel
Density 0.807 to 0.848
Viscosity 1.42 to 3.50 cSt
Flash Point > 100°F
Two-Phase Flow No
Max Allowable Operating Press 219 psig
Normal Operating Pressure 20–100 psig
Maximum Temp 100°F
Normal Temp 85°F
Heat Trace No
Maximum Flow 5,600 gpm1
1 Maximum Flow occurs during backward direction of flow through the meter (not common).
Normal Flow 1,800–3,600 gpm2
Minimum Back Pressure > 15 psig downstream during normal flow conditions3
Acceptable dP Not to Exceed (NTE) 15 psid at 3,600 gpm
Orientation Horizontal/straight (tubes down)
Full Pipe Yes
Bidirectional Yes
Intended Use Custody transfer
Case Standard pressure containment
Conduit Stainless steel cable gland
Calibration 0.05% mass flow and 0.0005 g/cc density
Tagging TBD (To be provided at a later date)
2.2 Transmitter requires the following minimum salient characteristics:
Power 18 to 28.8 VDC (nominal 24 VDC)
Housing Coated aluminum
Mounting Integral to sensor, if available
Display Local high-visibility graphic display; lbm/hr, density, gpm w/ref density, °F, total lbm, total gal
Interface Local pushbutton (or touchscreen is acceptable); no external configurator, communicator, or laptop required for operation/setup4
Update Rate 100 ms
Conduit 1/2” NPT
Output Board Configurable from local display
2 Normal Flow occurs during forward direction of flow through the meter.
3 Minimum backpressure of 15 psig is during forward direction of flow through the meter; backpressure during backward direction of flow through the meter is typically 65 psig.
4 Transmitter shall utilize an integrated local display with physical operator buttons, magnetic switches, or equivalent that allow for complete standalone commissioning, ranging, and configuration directly from the device housing. Transmitter unit must be fully operational and field-configurable without the use of external laptops, handheld communicators, proprietary software, or a control system connection
Self-Diagnosis Required
Totalizer Display Required
Memory Non-volatile. Shall permanently retain all calibration, configuration, set-up, and user settings during total power loss. Device shall automatically recover exact configuration upon restart without requiring reconfiguration.
Data Historian On-board logging of key variables (flow, density, temp) and configuration changes; nominal 1-year of data storage capacity
2.3 Input/Output (I/O) Communications
The system must support a minimum of 3 active independent communication channels:
• Channel A: 4–20 mA, Frequency Output, Discrete Output, Configurable
• Channel B: 4–20 mA, Frequency Output, Discrete Output, Configurable
• Channel C: Modbus RS-485
3.0 Operating Environment & Approvals
• Location/Environment: The system must be rated and suitable for outdoor installation in a tropical/marine environment (Hawaii).
• Hazardous Area Approvals: The entire system (Sensor and Transmitter) must be certified for Class I, Division 2, Group D hazardous locations.
4.0 Deliverables & Documentation
The Contractor shall provide the following documentation upon delivery of the equipment. All documentation must be in the English language and utilize Imperial/U.S. customary units.
1. Operations & Maintenance Manuals: Three (3) hard copies, plus one (1) digital file.
2. Material Test Reports (MTR): Three (3) hard copies, plus one (1) digital file.
3. Hydrostatic Test Reports: Three (3) hard copies, plus one (1) digital file.
4. Hazardous Area Certifications: Three (3) hard copies, plus one (1) digital file.
5.0 Delivery Period
8-10 weeks upon receipt of award
6.0 Delivery Address
JBPHH, JB7 Fuel Department
Bldg. 1757 Neosho Avenue
Pearl Harbor, HI 96860
File details come from the government source that posted it. Updated .