AttachmentAPumpSchedule.pdf
PDF 146 KB Posted
- Solicitation number
- S141033-vCurrent
- Issued by
- Suffolk County, Woburn City, Massachusetts
About this file
This document is an Attachment A Pump Schedule for a project by the Massachusetts Water Resources Authority (MWRA). It provides detailed specifications for 17 pumps to be installed at the Administration Building location, including information on the pump model numbers, horsepower, flow rates, pressure, head, efficiency, suction/discharge pressure, and motor frame size. The pumps are to be provided by the vendor Emerson Swan Inc., with the motors manufactured by U.S. Electric, operating at 480V, 60Hz. The pump schedule was determined based on a test conducted on October 27, 1994.
The document outlines the technical requirements for the pumps, which will likely be part of a larger state or local contract opportunity. No other details about the contract are provided, such as the overall project scope, procurement process, response dates, or contract term. The document appears to be a technical specification sheet that would be included as an attachment to a solicitation for the pump installation project.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| TechicalSpecsSection15806.pdf | ||
| RFB.pdf | ||
| TechnicalSpecsSection15170.pdf | ||
| S141033-vCurrent_OD.xlsx | XLSX spreadsheet | |
| AttachmentBTechnicalSpecsExistingPump.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment A Pump Schedule
II
No. MWRA I.D. # Serial # Model #
HP GPM PSI Head Feet
Eff.
Suction/Disc.
psi
Motor Frame
1 FA:HW.CP-1/P A939AV06V127R046F-A FM4010 20 500 49 105 76 12/60 284T
2 FA:HW.CP-2/P A939AV06V127R046F-B FM4010 20 500 49 110 76 11/59 284T
3 FA:HW.CP-3/P B522AV0820418-A FM4010 25 600 45 110 74 25/69 284T
4 FA:HW.CP-4/P B522AV0820418-D FM4010 25 600 45 105 74 25/69 284T
5 FA:CW.CP-1/P G69298M03W0420254F FM3007 10 520 13 30 46. 39/52 215T
6 FA:CW.CP-2/P G69298M03W0420254F FM3007 10 520 13 30 46 39/52 215T
7 FA:CW.CP-3/P G69298M03W0420254F FM3007 10 520 13 30 46 39/52 215T
8 FA:CW.CP-4/P G69298M03W0420254F FM3007 10 520 13 30 46 39/52 215T
9 FA:CW.CP-5/P B522AV08V204018-B FM4010 25 855 35 80 76 42/76 284T
10 FA:CW.CP-6/P B522AV08V204018-B FM4010 25 855 35 80 76 42/76 284T
11 FA:CW.CP-7/P B522AW01V352R047-A FM3013 25 480 48 110 60 26/72 284T
12 FA:CW.CP-8/P B522AW01V352R047-B FM3013 25 480 48 110 60 26/72 284T
13 FA:CW.CP-9/P W02W005R208F-A FM2510 10 180 45 105 56 28/72 215T
14 FA:CW.CP-10P W02W005R208F-B FM2510 10 180 45 105 56 28/72 215T
15 FA:HIS.CP-1/P G69300W03W0420262F FM4008 15 600 22 50 74 22/43 254T
16 FA:HIS.CP-2/P G69300W03W0420262F FM4008 15 600 22 50 74 22/43 254T
17 FA:HIS.CP-3/P G69300W03W0420262F FM4008 15 600 22 50 74 22/43 254T
Manufacturer: TACO
Location: Administration Building
Vendor: Emerson Swan Inc.
Motor: U.S. Electric
Volts: 480
60 HZ
Efficiency: determined by pump test conducted on 10-27-94
File details come from the government source that posted it. Updated .