AttachmentA_Storage Rack Anchorage Package.pdf
PDF 1 MB Posted
- Attached to
- MILL CREEK WAREHOUSE RACKING PROJECT
- Solicitation number
- S-10700-00000521
- Issued by
- Marion County, Oregon
About this file
The document consists of structural calculations and an attachment sketch for the storage rack anchorage requirements at the DAS Warehouse - Mill Creek located at 3455 Aumsville Highway, Salem, Oregon. The project involves the anchorage of a 2-shelf storage rack system with a rated load capacity of 4,000 pounds per shelf at elevations of 7.5 feet and 15 feet above the concrete slab. The calculations are based on seismic design criteria for a Risk Category II structure with a Seismic Design Category determined by the ATC Hazards tool. The attachment sketch depicts the required concrete screw anchor layout and details.
The related state and local contract opportunity is for the MILL CREEK WAREHOUSE RACKING PROJECT, which includes the breakdown and removal of the existing high bay steel storage rack system at the current site in Wilsonville, Oregon, and the relocation and reinstallation of the shelving components at the Mill Creek Corporate Center in Salem, Oregon. This project involves the Marion County and City of Salem jurisdictions.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 00000521_Bid_Tab.xls | XLS spreadsheet | |
| PrebidAttendees.pdf | ||
| 5255-0 Final.pdf | ||
| S-10700-00000521_NOITA.pdf | ||
| S-10700_00000521_Shelving_NVM.pdf | ||
| S-10700-00000521_Add001.pdf | ||
| S-10700-00000521_Add003.pdf | ||
| Addendum002~2.pdf | ||
| AttachmentB_MC WAREHOUSE PERMIT_STAMPED.pdf | ||
| _S-10700-00000521_Add004.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DAS WAREHOUSE – MILL CREEK
Storage Rack Anchorage
Structural Calculations
KPFF Project No. 10022100401
September 21, 2021
Submitted To:
SERA Architects 338 NW 5th Ave
Portland, OR 97209
Submitted By:
KPFF Consulting Engineers 111 SW Fifth Avenue, Suite 2600
Portland, OR 97204-3628
N
78836PE
13, OREGON
EXPIRES:
MAR
NE
G I
S T R U C T
02 0
REE
RU LA
T O B I N
KRAM
W.
CH
PROFESS I ONAL
DERETSI
GER
06-30-22
ATTACHMENT A
SKETCH SHOWING STORAGE RACK
ANCHORAGE REQUIREMENTS
PLAN
ELEVATION
LEG OF STORAGE RACK SYSTEM
(BY OTHERS)
SK-1 ANCHORAGE OF STORAGE RACK SYSTEM
BASE PLATE
3/8" x 5" x 0'-8"
(BY OTHERS)
(VERIFY SIZE)
LEG OF STORAGE RACK SYSTEM
(BY OTHERS)
BASE PLATE
(BY OTHERS)
(E) CONCRETE SLAB ON GRADE.
VERIFY 6" THICK, MIN.
CONCRETE SCREW ANCHOR,
REF. ELEVATION.
(4) TOTAL
(4) SIMPSON TITEN HD ANCHORS
1/2" DIAMETER
NOMINAL EMBED = 3.50"
INSTALL PER ICC-ESR 2713
DAS WAREHOUSE - MILL CREEK
3455 AUMSVILLE HIGHWAY, SALEM, OR
KPFF
09/21/2021
1" TYP., VERIFY
N
78836PE
13, OREGON
EXPIRES:
MAR
NE
G I
S T R U C T
02 0
REE
RU LA
T O B I N
KRAM
W.
CH
PROFESS I ONAL
DERETSI
GER
06-30-22
ANCHORAGE DESIGN IS BASED ON A 2-SHELF SYSTEM.
RATED LOAD CAPACITY OF EACH SHELF = 4,000 POUNDS.
ELEVATION OF SHELVES = 7'-6" & 15'-0" ABOVE CONCRETE SLAB.
NOTE: PROVIDE PERIODIC SPECIAL INSPECTIONS PER THE ANCHOR
ICC-ESR REPORT. FOR ONGOING INSTALLATIONS, PROVIDE INSPECTIONS
FOR 10% OF ANCHORS, EQUALLY DISTRIBUTED OVER THE DURATION OF
ANCHOR INSTALLATION.
SUPPORTING STRUCTRUAL
CALCULATIONS
DAS Mill Creek Warehouse -- Storage Rack Anchorage
The following calculations are for the anchorage of steel storage racks at the warehouse located at
3455 Aumsville Hwy, Salem, OR 97317 - Building 3
The calculations and associated sketches pertain only to the anchorage.
The design of the storage racks themselves are by others and beyond KPFF's scope.
Seismic Design Criteria:
SDS = 0.636 { per ATC Hazards }
R = 4.0 { ASCE 7-16, 15.5.3.3.1 }
I = 1.0 { I = 1.0 if NOT accessible to the public }
Ω0 = 2.0 { Required for ductile anchor design }
Geometry & Configurations:
Rack Length = 12.00 ft
Rack Depth = 3.67 ft
Shelf 1 Elevation = 7.50 ft above slab on grade
Shelf 2 Elevation = 15.00 ft above slab on grade
Shelf 1 Rated Capacity = 4,000 lbs
Shelf 2 Rated Capacity = 4,000 lbs
Base Plate Width = 5 in
Base Plate Length = 8 in
Base Plate Thick. = 0.375 in
No. of Bolt Holes = 4
Slab on grade thickness = 6 in
Anchor Bolt Spacing, X = 3 in
Anchor Bolt Spacing, Y = 6 in
Hole Diameter = 0.625 in
{ Use (4) 1/2" Anchors }
Design Forces for Fully Loaded and Partially Loaded Conditions (15.5.3.3.2) :
Condition 1 Condition 2
All Shelves Loaded to Top Shelf Only Loaded to
67% of Rated Capacity 100% Rated Capacity
Shelf 2, W = 2,680 lbs Shelf 2, W = 4,000 lbs
Shelf 1, W = 2,680 lbs Shelf 1, W = 0 lbs
Σ = 5,360 lbs Σ = 4,000 lbs
Vu = 0.159 W Vu = 0.159 W
Vu = 852 lbs Vu = 636 lbs
Vertical Distribution (15.5.3.3.3) : Vertical Distribution (15.5.3.3.3) :
% Vu Fx % Vu Fx
Shelf 2 = 66.7% 568 lbs Shelf 2 = 100.0% 636 lbs
Shelf 1 = 33.3% 284 lbs Shelf 1 = 0.0% 0 lbs
Σ = 852 lbs Σ = 636 lbs
Over-Turning Moment: Over-Turning Moment:
Mu = 10,653 lb-ft Mu = 9,540 lb-ft
Condition 1 Governs with:
Vu = 852 lbs per individual rack
Mu = 10,653 lb-ft per individual rack
Mu is resisted by a Tension / Compression Couple:
Tu = Cu = 2,905 lbs per individual rack
Shear is resisted equally by 4 legs:
Vu = 213 lbs per leg
Tension / Compression is resisted equally by 2 legs:
Tu = Cu = 1,453 lbs per leg
Gravity load is resisted equally by 4 legs:
Pgrav = 1,340 lbs per leg
Governing Load Case for Uplift / Tension is: 0.9 Pgrav +/- Ev +/- Emh
0.9 Pgrav = -1,206 lbs -- Down
Ev = 0.2 SDS Pgrav = 170 lbs -- Up
Emh = Ω0 Tu = 2,905 lbs -- Up
Net Uplift / Tension, Tu = 1,870 lbs per leg -- Up
Because the racks share vertical legs when they are adjacent to each other, double the above values.
Design each base connection for:
Vu = 426 lbs
Tu = 3,740 lbs
9/21/21, 12:18 PM ATC Hazards by Location https://hazards.atcouncil.org/#/seismic?lat=44.8983&lng=-122.9686&address= 1/2
Hazards by Location
Search Information
Coordinates: 44.8983, -122.9686
Elevation: 236 ft
Timestamp: 2021-09-21T19:18:32.537Z
Hazard Type: Seismic
Reference Document:
ASCE7-16
Risk Category: II
Site Class: D-default
Basic Parameters
Name Value Description
SS 0.795 MCER ground motion (period=0.2s)
S1 0.4 MCER ground motion (period=1.0s)
SMS 0.954 Site-modified spectral acceleration value
SM1 * null Site-modified spectral acceleration value
SDS 0.636 Numeric seismic design value at 0.2s SA
SD1 * null Numeric seismic design value at 1.0s SA
* See Section 11.4.8
Additional Information
Name Value Description
SDC * null Seismic design category
Fa 1.2 Site amplification factor at 0.2s
Fv * null Site amplification factor at 1.0s
CRS 0.88 Coefficient of risk (0.2s)
CR1 0.863 Coefficient of risk (1.0s)
PGA 0.368 MCEG peak ground acceleration
FPGA 1.232 Site amplification factor at PGA
PGAM 0.453 Site modified peak ground acceleration
TL 16 Long-period transition period (s)
236 ft
Map data ©2021 Google https://maps.google.com/maps?ll=44.8983,-122.9686&z=8&t=m&hl=en-US&gl=US&mapclient=apiv3
9/21/21, 12:18 PM ATC Hazards by Location https://hazards.atcouncil.org/#/seismic?lat=44.8983&lng=-122.9686&address= 2/2
SsRT 0.795 Probabilistic risk-targeted ground motion (0.2s)
SsUH 0.904 Factored uniform-hazard spectral acceleration (2% probability of exceedance in 50 years)
SsD 1.5 Factored deterministic acceleration value (0.2s)
S1RT 0.4 Probabilistic risk-targeted ground motion (1.0s)
S1UH 0.463 Factored uniform-hazard spectral acceleration (2% probability of exceedance in 50 years)
S1D 0.627 Factored deterministic acceleration value (1.0s)
PGAd 0.511 Factored deterministic acceleration value (PGA)
* See Section 11.4.8
The results indicated here DO NOT reflect any state or local amendments to the values or any delineation lines made during the building code adoption process. Users should confirm any output obtained from this tool with the local Authority Having Jurisdiction before proceeding with design.
Disclaimer Hazard loads are provided by the U.S. Geological Survey Seismic Design Web Services.
While the information presented on this website is believed to be correct, ATC and its sponsors and contributors assume no responsibility or liability for its accuracy. The material presented in the report should not be used or relied upon for any specific application without competent examination and verification of its accuracy, suitability and applicability by engineers or other licensed professionals. ATC does not intend that the use of this information replace the sound judgment of such competent professionals, having experience and knowledge in the field of practice, nor to substitute for the standard of care required of such professionals in interpreting and applying the results of the report provided by this website. Users of the information from this website assume all liability arising from such use. Use of the output of this website does not imply approval by the governing building code bodies responsible for building code approval and interpretation for the building site described by latitude/longitude location in the report.
https://earthquake.usgs.gov/ws/designmaps/
Company: Date: 9/21/2021
Engineer: Page: 1/5
Project:
Address:
Phone:
E-mail:
Anchor Designer™ Software Version 3.0.7845.0
1.Project information
Customer company:
Customer contact name:
Customer e-mail:
Comment:
Project description:
Location:
Fastening description:
2. Input Data & Anchor Parameters
General Design method:ACI 318-14 Units: Imperial units
Anchor Information:
Anchor type: Concrete screw Material: Carbon Steel Diameter (inch): 0.500 Nominal Embedment depth (inch): 3.500 Effective Embedment depth, hef (inch): 2.560 Code report: ICC-ES ESR-2713 Anchor category: 1 Anchor ductility: No hmin (inch): 5.42 cac (inch): 3.88 Cmin (inch): 1.75 Smin (inch): 3.00
Base Material Concrete: Normal-weight Concrete thickness, h (inch): 6.00 State: Cracked Compressive strength, f’c (psi): 3000 Ψc,V: 1.0 Reinforcement condition: B tension, B shear Supplemental reinforcement: Not applicable Reinforcement provided at corners: No Ignore concrete breakout in tension: No Ignore concrete breakout in shear: No Ignore 6do requirement: Not applicable Build-up grout pad: No
Base Plate Length x Width x Thickness (inch): 8.00 x 5.00 x 0.37 Yield stress: 36000 psi
Profile type/size: HSS4X2X1/4
Recommended Anchor Anchor Name: Titen HD® - 1/2"Ø Titen HD, hnom:3.5" (89mm) Code Report: ICC-ES ESR-2713
5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.comSimpson Strong-Tie Company Inc.
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
DAS Mill Creek Warehouse Storage Rack Anchorage
Engineer: Page: 2/5
Project:
Address:
Phone:
E-mail:
Anchor Designer™ Software Version 3.0.7845.0
Load and Geometry Load factor source: ACI 318 Section 5.3 Load combination: not set Seismic design: Yes Anchors subjected to sustained tension: Not applicable Ductility section for tension: 17.2.3.4.2 not applicable Ductility section for shear: 17.2.3.5.2 not applicable Ω0 factor: not set Apply entire shear load at front row: No Anchors only resisting wind and/or seismic loads: Yes
Strength level loads:
Nua [lb]: 3740 Vuax [lb]: 426 Vuay [lb]: 426 Mux [ft-lb]: 0 Muy [ft-lb]: 0 Muz [ft-lb]: 0
<Figure 1>
5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.comSimpson Strong-Tie Company Inc.
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Engineer: Page: 3/5
Project:
Address:
Phone:
E-mail:
Anchor Designer™ Software Version 3.0.7845.0
<Figure 2>
5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.comSimpson Strong-Tie Company Inc.
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Engineer: Page: 4/5
Project:
Address:
Phone:
E-mail:
Anchor Designer™ Software Version 3.0.7845.0
Shear load y, Vuay (lb)
Anchor Tension load, Nua (lb)
3. Resulting Anchor Forces
Shear load combined, √(Vuax)²+(Vuay)² (lb)
Shear load x, Vuax (lb)
935.01 106.5 150.6106.5
935.02 106.5 150.6106.5
935.03 106.5 150.6106.5
935.04 106.5 150.6106.5
426.0 426.0Sum 3740.0 602.5
Maximum concrete compression strain (‰): 0.00 Maximum concrete compression stress (psi): 0 Resultant tension force (lb): 3740 Resultant compression force (lb): 0 Eccentricity of resultant tension forces in x-axis, e'Nx (inch): 0.00 Eccentricity of resultant tension forces in y-axis, e'Ny (inch): 0.00 Eccentricity of resultant shear forces in x-axis, e'Vx (inch): 0.00 Eccentricity of resultant shear forces in y-axis, e'Vy (inch): 0.00
<Figure 3>
4. Steel Strength of Anchor in Tension (Sec. 17.4.1)
Nsa (lb) f fNsa (lb)
20130 0.65 13085
5. Concrete Breakout Strength of Anchor in Tension (Sec. 17.4.2)
Nb = kclaÖf’chef
1.5 (Eq. 17.4.2.2a) kc la f’c (psi) hef (in) Nb (lb)
17.0 1.00 3000 2.560 3814
0.75fNcbg =0.75f (ANc / ANco)Yec,NYed,NYc,NYcp,NNb (Sec. 17.3.1 & Eq. 17.4.2.1b) ANc (in2) ANco (in2) ca,min (in) Yec,N Yed,N Yc,N Ycp,N Nb (lb) f 0.75fNcbg (lb)
146.10 58.98 - 1.000 1.000 1.00 1.000 3814 0.65 4606
8. Steel Strength of Anchor in Shear (Sec. 17.5.1)
Vsa (lb) fgrout f fgroutfVsa (lb)
4790 1.0 0.60 2874
10. Concrete Pryout Strength of Anchor in Shear (Sec. 17.5.3) fVcpg = fkcpNcbg = fkcp(ANc / ANco)Yec,NYed,NYc,NYcp,NNb (Sec. 17.3.1 & Eq. 17.5.3.1b) kcp ANc (in2) ANco (in2) Yec,N Yed,N Yc,N Ycp,N Nb (lb) f fVcpg (lb)
2.0 146.10 58.98 1.000 1.000 1.000 1.000 3814 0.70 13226
5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.comSimpson Strong-Tie Company Inc.
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Engineer: Page: 5/5
Project:
Address:
Phone:
E-mail:
Anchor Designer™ Software Version 3.0.7845.0
11. Results
Interaction of Tensile and Shear Forces (Sec. 17.6.)
Tension Factored Load, Nua (lb) Design Strength, øNn (lb) Ratio Status
Steel 935 13085 0.07 Pass
Concrete breakout 3740 4606 0.81 Pass (Governs)
Shear Factored Load, Vua (lb) Design Strength, øVn (lb) Ratio Status
Steel 151 2874 0.05 Pass (Governs)
Pryout 602 13226 0.05 Pass
Interaction check Nua/fNn Vua/fVn Combined Ratio Permissible Status
Sec. 17.6..1 0.81 0.00 81.2% 1.0 Pass
1/2"Ø Titen HD, hnom:3.5" (89mm) meets the selected design criteria.
12. Warnings
- Per designer input, the tensile component of the strength-level earthquake force applied to anchors does not exceed 20 percent of the total factored anchor tensile force associated with the same load combination. Therefore the ductility requirements of ACI 318 17.2.3.4.2 for tension need not be satisfied – designer to verify.
- Per designer input, the shear component of the strength-level earthquake force applied to anchors does not exceed 20 percent of the total factored anchor shear force associated with the same load combination. Therefore the ductility requirements of ACI 318 17.2.3.5.2 for shear need not be satisfied – designer to verify.
- Designer must exercise own judgement to determine if this design is suitable.
- Refer to manufacturer’s product literature for hole cleaning and installation instructions.
5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.comSimpson Strong-Tie Company Inc.
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
| Calc-Cover |
| Storage Rack Geometry Sketch |
| DAS Mill Creek - Storage Rack Anchorage Excel Calcs |
| Ground Motions per ATC |
| Simpson Anchor Designer Output |