Attachment2 - Specification_Exhibits.pdf

PDF 1 MB Posted

Attached to
HELENA NATIONAL FOREST - Solar System Install on Existing Well
Solicitation number
1240LU26Q0107
Issued by

About this file

This is a submittal data document for a solar-powered submersible pump system (Model 3 SQF-3, Reference Number 95027333) designed for water production applications.

The system is sized for Helena, Montana (latitude 46.5889°N, longitude -112.0385°W) to produce 700 US gallons per day with a peak flow requirement. Key specifications include: a total annual water production of 909 cubic meters (658 US GPD average daily production), solar array configuration of 2 modules in series rated at 0.43 kW and 76 volts with fixed mounting at a 47-degree tilt angle, and a submersible pump rated at 2.3 US GPM at 333.4 feet total head under typical solar radiation conditions of 800 W/m². The pump materials are stainless steel (DIN W.-Nr. 1.4301, AISI 304) for the pump housing, impeller (EN 1.4301), motor, rotor, and stator with EPDM seals. The system includes 82 feet of 14 AWG pump cable with 2.9 percent cable loss and 320 feet of polyethylene riser pipe with total friction losses of 3.448 feet. The dimensional drawing indicates an overall length of 48 5/8 inches with an 8mm (5/16-inch) port connection and 1-inch NPT discharge. AC backup power requirements are 0.656 HP minimum output, producing 2.73 US GPM at 115V or 2.75 US GPM at 230V. Monthly water production varies from 192 US GPD in December to 993 US GPD in July, with the system achieving an average water production rate of 5.8 liters per watt per day.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Exhibit A.2 Page 1 - 5

Project:

Reference Number:

95027333 3 SQF-3

Q

[US GPM]

3.0

2.5

2.0

1.5

1.0

0.5

Company name:

Created by:

Phone:

Email:

Date:

Client:

Client Number:

Contact:

3 SQF-3 eta

0.46 0.50 0.54 0.58 P1 [kw]

0. 0 ::!-::-:c:--i��ZE.fl'..-:'1,!l....-+�-:----r-::.-::--r--::--,---.--,......---r---,---r---+----.---r-::.-::--r--r---.--,......---r---,---r----r----.---.----r---.,..l. 0

0 0.02 0.06 0.10 0.14 0.18 0.22 0.26 0.30 0.34 0.38 0.42

Q = 2.27 US GPM

P1 = 0.339 kW Pumped liquid = Water

H = 333.4 ft Eta pump+motor = 42 % Density = 62.29 lb/ft3

95027333 3 SQF-3

08(5/16") co co

• • • 1 • • •

15/1

Note! All units are in [in] unless others are stated.

1"NPT

II

Disclaimer: This simplified dimensional drawing does not show all details.

Company name:

Created by:

Phone:

Email:

Date:

Client:

Client Number:

Contact:

95027333 3 SQF-3

Flow: 700US GPD () Month for sizing: July Static lift above ground: 1 0 ft Dynamic water level: 320 ft Sun tracking: No (fixed) Location: Helena, Montana, United States Latitude: 46.5889 DD, Longitude: -112.0385 DD

Water production, Peak flow and Price Total water production per year: 909 m•

Avg. water production per day: 658 US GPO Average water production per watt per day: 5.8 I/Wp/day

Solar module configuration:

Number of solar modules in series: 2, in parallel:

Solar array rated power: 0.43 kW Solar array rated volts: 76 V Sun tracking: No (fixed) Tilt angle: 47 deg.

AC power (backup) - water production Recommended minimum output: 0.656 HP AC 115 V: Produces: 2. 73 US GPM AC 230 V: Produces: 2.75 US GPM

System performance - monthly average

Company name:

Created by:

Phone:

Email:

Date:

Client:

Client Number:

Pump: 3 SQF-3, 1 x 95027333 Solar module: 2 x SPM220W COPY

Typical performance at solar radiation 800 W/m2

Flow: 2.3 US GPM Total head: 333.4 ft

Cables and pipes:

Pump cable length: 82 ft Pump cable size: 14 AWG Total cable loss: 2.9 %

Material, riser pipe: PEH Pipe length of riser pipe: 320 ft Total friction losses: 3.448 ft

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Water production [US GPO]

Energy production Solar [kWh/day]

Radiation horizontal [kWh/m2 day]

Radiation tilt [kWh/m2 day]

Avg. Temp. [°F]

295 534 747 790 824 852 993 935 828 594 305 192

0.9 1.4

1.1 2.0

1.9 2.1

3.3 4.4

2.1 2.2

5.3 5.8

2.6

6.6

2.4

5.4

2.1

3.9

1.6

2.3

0.9

1.2

0.7

0.8

2.2 3.4 4.5 4.8 5.0 5.2 6.0 5.7 5.0 3.7 2.2 1.7

21.6 22.5 27.7 35.1 44.4 51.6 60.6 59.4 50.2 37.4 27.3 20.5

Data location: Latitude: 47 DD, Longitude: -113 DD

Accessory is missing 92799796

Water production - monthly Water production - daily: July

1,000

US GPO

F M A M J

Month

A s 0 N D

2.4 US GPM

2.2

2.0

1.8

1.6

1.4

1.2

1.0

0.8

0 1 2 3 4 5 6 7 8 9 11 13 15 17 19 21

Time of Day

Installation and Input

Pump Curve a

(USGPMJ

3 SOF·3 eta

Q = 2.27 US GPM

H = 333.4 ft P1 = 0.339 kW Eta pump+motor = 42 % Pumped liquid= Water 70 Density= 62.29 lb/IP

Company name:

Created by:

Phone:

Email:

Date:

Client:

Client Number:

Sizing Results

Water production, Peak flow and Price

Total water production per year: 909 m•

Avg. water production per day: 658 US GPD

Average water production per watt per day: 5.8 I/Wp/day

Solar module configuration:

Number of solar modules in series: 2, in parallel:

Solar array rated power: 0.43 kW

Solar array rated volts: 76 V

Sun tracking: No (fixed)

Tilt angle: 47 deg.

Typical performance at solar radiation 800 W/m2

Flow: 2.3 US GPM

Total head: 333.4 ft

Cables and pipes:

Pump cable length: 82 ft

Pump cable size: 14 AWG

Total cable loss: 2.9 %

Material, riser pipe: PEH

Pipe length of riser pipe: 320 ft

Total friction losses: 3.448 ft

Location: Helena, Montana, United States Latitude: 46.5889 DD, Longitude: -112.0385 DD

Dimensional Drawing

08(5/16")

File details come from the government source that posted it. Updated .