CROSSGATE LANE
BR
OW
NS
BO
RO
R
D
BROW
NSBORO RD, US 42 WARRINGTON WAY
WATTERSON EXPRESSWAY
I - 264
SITE
LOCATION MAP
NO SCALE
TRUE NORTH
PROJECT CONSULTANTS
FOOD SERVICE & LAUNDRY DESIGN:
Ricca Design Studios Denver Technological Center 5325 South Valentia Way Greenwood Village, CO 80111 Al Moller T: (303) 221-0500
MATERIALS MANAGEMENT/ELEVATORS:
Lerch, Bates, Inc.
9780 S. Meridian Blvd., Suite 450 Englewood, CO. 80112 Steven Wuthrich T: (312) 386-7661
HARDWARE:
Jenosky Consulting, Inc.
43422 West Oaks Drive, #270 Novi, Michigan 48377-3300 Dave Jenosky T: (248) 496-7900
CMP SCHEDULING AND RISK ASSESSMENT:
RADIATION SHIELDING:
Diagnostic Physics, Inc.
P.O. Box 49587 Charlotte, NC 28277 Beth Franklin, DABR T: (704) 541-9628
CODE CONSULTING:
FP&C Consultants, Inc 1520 Main Street Indianapolis, IN 46224 Frank Van Overmeiren - President T: (317) 486-5188
MAGNETIC SHIELDING:
Vitatech Electromagnetics 115 Juliad Court, Suite 105 Fredericksburg, VA 22406 Louis S. Vitale, Jr. (COO) T: (540) 286-1984, Ext. #201
SUSTAINABLE ARCHITECTURE & ENGINEERING:
Guidon Design 2453 N Delaware Street Indianapolis, IN 46205 Luke Leising T: (317) 800-6388 x101
GEOTECHNICAL:
AMEC Environmental & Infrastructure 11003 Bluegrass Pkwy. Suite 690 Louisville, KY 40299 David Sawitzki, PE T: (502) 267-0700
SECURITY SYSTEMS:
Security Management and Integration Company Inc.
4940 Olympic Blvd Olympic Corporate Offices Erlanger, KY 41018 Cecil Avery T: (859) 372-6618
CIVIL ENGINEERING & LAND SURVEYING:
ClasSickle, Incorporate 4501 Bardstown Road Louisville, KY 40218 Anthony Sickles, PLS T: (502) 493-2722
PARKING DECK PLANNING:
CWConsulting, LLC 2429 Highpointe Drive Kalamazoo, MI 49008-2074 Carl Walker, PE T: (269) 217-7615
COST ESTIMATING:
U.S. Cost 600 Northpark Town Center 1200 Abernathy Road, NE Building 600, Suite 950 Atlanta, GA 30328 Louis Parkins T: (770) 481-1614
GRAPHICS/SIGNAGE:
Square Peg Design 1631 Telegraph Avenue Oakland, CA 94612 Jeffrey Padia T: (510) 596-8810
MEDICAL EQUIPMENT:
The Innova Group 9442 Capital of Texas Highway North Arboretum Plaza I, Suite 325 Austin, TX 78759 Chris Phillips T: (512) 346-8700
BLAST CONSULTANT:
Stone Security Engineering 315 Bleecker Street Suite 319 New York, NY 10014 Hollice Stone President T: (646) 649-3169
RENEWABLE ENERGY STUDY:
CMTA Engineering 110411 Metting Street Prospect, KY 40059 Tony Hans VP Principal T: (502) 326-3085
Crawford Consulting Services 239 Highland Avenue East Pittsburgh, PA 15112 Mary Crawford T: (412) 823-0400
URS Corporation 500 West Jefferson St.
Suite 1600 Louisville, KY 40202 T: (313.983.3600)
ARCHITECTURE - ENGINEERING: URS / SMITHGROUP JOINT VENTURE
SMITHGROUPJJR
500 West Jefferson St.
Suite 1600 Louisville, KY 40202 T: (313) 983-3600
VOLUME LEGEND
VOLUME 00
VOLUME LEGEND
INDEX SHEETS
GENERAL
LIFE SAFETY
CAMPUS COMPOSITES
COMMON ARCHITECTURAL SHEETS (ALL BUILDINGS)
SIGNAGE
VOLUME 10
SITE
VOLUME 20 - NOT USED
VOLUME 21 - NOT USED
VOLUME 30
VAMC - BUILDING ZONE B
ARCHITECTURE - EXTERIOR
CANOPIES
VOLUME 31
VAMC - BUILDING ZONE B
EQUIPMENT
FURNITURE
VOLUME 32
VOLUME 40
DOCK, LAUNDRY AND CUP - BUILDING ZONE C & D
ALL DISCIPLINES
VOLUME 50
NORTH PARKING STRUCTURE - BUILDING ZONE E
ALL DISCIPLINES
VOLUME 60
SOUTH PARKING STRUCTURE - BUILDING ZONE F
VOLUME 70
OUTBUILDINGS & MISCELLANEOUS STRUCTURES
MAINTENANCE BUILDING - BUILDING ZONE G1
GUARD HOUSES - BUILDING ZONES J1 & J2
WATER TOWER - BUILDING ZONE K1
ELECTRICAL SERVICE BUILDINGS - BUILDING ZONES L1 & L2
BUS SHELTER - BUILDING ZONE M1
PUMP HOUSE - BUILDING ZONE P1
VOLUME 33
VOLUME 37
VAMC - BUILDING ZONE B
ELECTRICAL SPECIAL SYSTEMS
TELECOMMUNICATIONS
FIRE ALARM
PHYSICAL SECURITY
VOLUME 36
VAMC - BUILDING ZONE B
POWER
LIGHTING
VOLUME 35
VAMC - BUILDING ZONE B
HVAC
VOLUME 34
VAMC - BUILDING ZONE B
FIRE PROTECTION
PLUMBING
VAMC - BUILDING ZONE B
ARCHITECTURE - INTERIOR
TRANSPORTATION
ELEVATORS
PNEUMATIC TUBE
GRAVITY CHUTES
VAMC - BUILDING ZONE B
STRUCTURAL
Pl ot
Da te:
th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
CONSTRUCTION DOCUMENTS -
URS | SMITHGROUP JOINT VENTURE
500 WEST JEFFERSON ST.
Suite 1600
LOUISVILLE, KY 40202
T 313.983.3600 F 313.983.3636 www.urscorp.com | www.smithgroupjjr.com
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management
B
A
C
D
E
F
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321 o n e si xt e e n th in c h o n e fo o t o n e th ir ty se c o n d th in c h o n e fo o t
PROJECT # 14576907/22200.000
OFFICE OF CONSTRUCTION & FACILITIES MANAGEMENT - CENTRAL REGION
3001 GREEN BAY ROAD
BUILDING 48
NORTH CHICAGO, IL 60064
T 224.610.3492
U.S. DEPARTMENT OF VETERANS AFFAIRS
SHEET INDEX ID:
USACE LOUISVILLE DISTRICT
600 DR. MARTIN LUTHER KING PLACE
LOUISVILLE, KY 40202
PHONE: 502-315-6766
FAX: 502-315-6195
CONTRACTING DIVISION
OrientationSeal
/27
/20
8:
:44 A
M
20NOV2020
GI00700
COVER SHEET - VOLUME 70
WJ MG
Louisville, Kentucky
REPLACEMENT VA MEDICAL CENTER
VA Project No. 603-320 USACE P2 No. 453413
700.01.1.GI-GI00700-Phase B-GENERAL
20NOV2020
Replacement VA Medical Center
Louisville, Kentucky 40222
PHASE B CERTIFIED FINAL
NOVEMBER 20, 2020
VOLUME 70 - OUTBUILDINGS & MISC STRUCTURES
VA Project No. 603-320 VA101CFM-P-0157 USACE P2 No. 453413
4906 Brownsboro Road
PHB CERTIFIED FINAL 20NOV2020
11/20/2020
ARIMS: 200A Disposition: Maintain for 15yrs after construction
03 December 2020
W912QR21R0008
As Awarded 17 August 2021
W912QR21C0027
As A w ar de d
A ug us t 2
W
2Q
R
C
/W
2Q
R
R
Pl ot
Da te:
th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
CONSTRUCTION DOCUMENTS -
URS | SMITHGROUP JOINT VENTURE
500 WEST JEFFERSON ST.
Suite 1600
LOUISVILLE, KY 40202
T 313.983.3600 F 313.983.3636 www.urscorp.com | www.smithgroupjjr.com
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management
B
A
C
D
E
F
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
TRUE NORTH
PROJECT NORTH
97 8654321 o n e si xt e e n th in c h o n e fo o t o n e th ir ty se c o n d th in c h o n e fo o t
PROJECT # 14576907/22200.000
OFFICE OF CONSTRUCTION & FACILITIES MANAGEMENT - CENTRAL REGION
3001 GREEN BAY ROAD
BUILDING 48
NORTH CHICAGO, IL 60064
T 224.610.3492
U.S. DEPARTMENT OF VETERANS AFFAIRS
SHEET INDEX ID:
USACE LOUISVILLE DISTRICT
600 DR. MARTIN LUTHER KING PLACE
LOUISVILLE, KY 40202
PHONE: 502-315-6766
FAX: 502-315-6195
CONTRACTING DIVISION
OrientationSeal
/5/
1:
:13 P
M
20NOV2020
GI01700
INDEX OF DRAWINGS VOLUME 70
Checker Designer
Louisville, Kentucky
REPLACEMENT VA MEDICAL CENTER
VA Project No. 603-320 USACE P2 No. 453413
700.01.1.GI-GI01700-Phase B-GENERAL
20NOV2020
INDEX OF DRAWINGS - GENERAL
SHEET NUMBER SHEET NAME
GENERAL
GI00700 COVER SHEET - VOLUME 70
GI01700 INDEX OF DRAWINGS VOLUME 70
STRUCTURAL
SF00000 GENERAL STRUCTURAL NOTES
ARCHITECTURE
AE0000 BUILDING AREA DESIGNATION PLAN - ARCHITECTURE
AE00001 ARCHITERCTURAL ABBREVIATIONS
AE00002 ARCHITECTURAL SYMBOLS
FIRE PROTECTION
FX0000 FIRE SUPPRESSION WATER SUPPLY PLAN
PLUMBING
PL0000 PLUMBING BUILDING AREA DESIGNATION PLAN
PL001 PLUMBING - GENERAL INFO
MECHANICAL
MH0000 MECHANICAL BUILDING AREA DESIGNATION PLAN
MH001 MECHANICAL GENERAL INFO
MH501 GENERAL MECHANICAL DETAILS
MH502 GENERAL MECHANICAL DETAILS
MH503 GENERAL MECHANICAL DETAILS
ELECTRICAL
EE000 ELECTRICAL BUILDING AREA DESIGNATION PLAN
EE001 ELECTRICAL SYMBOLS AND ABBREVIATIONS, PART 1
EE002 ELECTRICAL SYMBOLS AND ABBREVIATIONS, PART 2
EE003 ELECTRICAL SYMBOLS AND ABBREVIATIONS, PART 3
EE600MISC ELECTRICAL PANEL SCHEDULES
EE601MISC ELECTRICAL PANEL SCHEDULES
TECHNOLOGY
TC0000 TECHNOLOGY BUILDING AREA DESIGNATION PLAN
TC001 TECHNOLOGY SYMBOLS LEGEND
INDEX OF DRAWINGS - MAINTENANCE BUILDING
SHEET NUMBER SHEET NAME
STRUCTURAL
SF101G1 MAINTENANCE BUILDING - FOUNDATION & ROOF FRAMING PLANS
SF501G1 MAINTENANCE BUILDING - FOUNDATION & ROOF FRAMING SECTIONS AND DETAILS
ARCHITECTURE
AE101G1 MAINTENANCE BUILDING - FLOOR PLANS
AE2001G1 MAINTENANCE BUILDING - EXTERIOR ELEVATIONS & BUILDING SECTIONS
AE3201G1 MAINTENANCE BUILDING - WALL SECTIONS
AE5201G1 MAINTENANCE BUILDING - DETAILS
FIRE PROTECTION
FX101G1 MAINTENANCE BUILDING - FIRE SUPPRESSION
PLUMBING
PL101G1 MAINTENANCE - PLUMBING PLANS & SCHEDULES
PL102G1 FUEL ISLAND PLANS & DETAILS - PLUMBING
PL601G1 MAINTENANCE BUILDING - DETAILS & DIAGRAMS
MECHANICAL
MH101G1 MAINTENANCE BUILDING HVAC PLANS
ELECTRICAL
EE100G1 MAINTENANCE BUILDING - LIGHTING AND POWER FLOOR PLAN
EE700G1 MAINTENANCE BUILDING SINGLE LINE DIAGRAM
TECHNOLOGY
TC100G1 MAINTENANCE BUILDING - SYSTEMS FLOOR PLAN
FIRE ALARM
FA101G1 MAINTENANCE BUILDING - FIRE ALARM
INDEX OF DRAWINGS - GUARD HOUSES
SHEET NUMBER SHEET NAME
STRUCTURAL
SF101J1 GUARDHOUSE - FOUNDATION & ROOF FRAMING PLANS
SF501J1 GUARDHOUSE - FOUNDATION & ROOF FRAMING SECTIONS AND DETAILS
ARCHITECTURE
AE101J1 GUARD HOUSE FLOOR PLANS
AE2001J1 GUARD HOUSE EXTERIOR ELEVATIONS
AE3201J1 GUARD HOUSE EXTERIOR WALL SECTIONS
AE5201J1 GUARD HOUSE SECTION DETAILS
AE5301J1 GUARD HOUSE PLAN DETAILS
PLUMBING
PL101J1 GUARD HOUSE - PLUMBING PLANS, DETAILS, & SCHEDULES
MECHANICAL
MH101J1 GUARD HOUSES HVAC PLANS
ELECTRICAL
EE100J GUARD HOUSES - LIGHTING FLOOR PLANS
EE200J GUARD HOUSES - POWER FLOOR PLANS
EE700J GUARD HOUSES - SINGLE LINE DIAGRAM
TECHNOLOGY
TC100J GUARD HOUSES - SYSTEMS FLOOR PLANS
INDEX OF DRAWINGS - WATER TOWER
SHEET NUMBER SHEET NAME
PL100K1 ELEVATED WATER STORAGE TANK PLAN
PL100K2 GROUND STORAGE TANK PLAN & SECTION
PL300K1 ELEVATED WATER STORAGE TANK SECTIONS
PL700K WATER TOWER AND WATER TANK PROCESS FLOW DIAGRAM
ELECTRICAL
EE100K1 WATER TOWER ELECTRICAL PLAN
INDEX OF DRAWINGS - ELECTRICAL BUILDING EAST
SHEET NUMBER SHEET NAME
STRUCTURAL
SF101L1 ELECTRICAL BUILDING EAST - FOUNDATION & ROOF FRAMING PLANS
SF501L1 ELECTRICAL BUILDING EAST - FOUNDATION AND FRAMING SECTIONS AND DETAILS
ARCHITECTURE
AE101L1 ELECTRICAL BUILDING EAST - FLOOR PLANS
AE2001L1 ELECTRICAL BUILDING EAST - ELEVATIONS, BUILDING AND WALL SECTIONS
AE5201L1 ELECTRICAL BUILDING EAST - DETAILS
MECHANICAL
MH101L1 ELECTRICAL SERVICE BUILDING EAST HVAC PLANS
ELECTRICAL
EE100L1 ELECTRICAL SERVICE BUILDING EAST - LIGHTING AND POWER FLOOR PLAN
EE700L1 ELECTRICAL SERVICE BUILDINGS EAST AND WEST - SINGLE LINE DIAGRAMS
TECHNOLOGY
TC100L1 ELECTRICAL BUILDING EAST - SYSTEMS FLOOR PLAN
FIRE ALARM
FA101L1 ELECTRICAL BUILDING EAST - FIRE ALARM
INDEX OF DRAWINGS - ELECTRICAL BUILDING WEST
SHEET NUMBER SHEET NAME
STRUCTURAL
SF101L2 ELECTRICAL BUILDING WEST - FOUNDATION & ROOF FRAMING PLANS
SF501L2 ELECTRICAL BUILDING WEST - FOUNDATION & FRAMING SECTIONS & DETAILS
ARCHITECTURE
AE101L2 ELECTRICAL BUILDING WEST - FLOOR PLANS
AE2001L2 ELECTRICAL BUILDING WEST - ELEVATIONS, BUILDING AND WALL SECTIONS
AE5201L2 ELECTRICAL BUILDING WEST - DETAILS
MECHANICAL
MH101L2 ELECTRICAL SERVICE BUILDING WEST HVAC PLANS
ELECTRICAL
EE100L2 ELECTRICAL BUILDING WEST - LIGHTING AND POWER FLOOR PLAN
TECHNOLOGY
TC100L2 ELECTRICAL BUILDING WEST - SYSTEMS FLOOR PLAN
FIRE ALARM
FA101L2 ELECTRICAL BUILDING WEST - FIRE ALARM
INDEX OF DRAWINGS - BUS SHELTER
SHEET NUMBER SHEET NAME
STRUCTURAL
SF101M1 BUS SHELTER - STRUCTURAL PLANS, SECTIONS AND DETAILS
ARCHITECTURE
AE101M1 BUS SHELTER FLOOR PLANS, ELEVATIONS AND SECTIONS
AE5201M2 BUS SHELTER SECTION DETAILS
AE5202M2 BUS SHELTER PLAN DETAILS
ELECTRICAL
EE100M1 BUS SHELTER - LIGHTING FLOOR PLAN
INDEX OF DRAWINGS - PUMP HOUSE
SHEET NUMBER SHEET NAME
STRUCTURAL
SF101P1 PUMP HOUSE BUILDING - FOUNDATION & ROOF FRAMING PLANS
SF501P1 PUMP HOUSE BUILDING - FOUNDATION & ROOF FRAMING SECTIONS AND DETAILS
ARCHITECTURE
AE101P1 PUMP HOUSE - FLOOR PLANS
AE2001P1 PUMP BUILDING - ELEVATIONS, BUILDING & WALL SECTIONS
AE5201P1 PUMP BUILDING - DETAILS
FIRE PROTECTION
FX101P1 PUMP HOUSE - LEVEL1 FIRE SUPPRESSION
PLUMBING
PL101P1 PUMP HOUSE - PLUMBING PLAN, DIAGRAM, AND SCHEDULE
MECHANICAL
MH101P1 PUMP HOUSE HVAC PLANS
ELECTRICAL
EE100P1 PUMP HOUSE - LIGHTING FLOOR PLAN
EE200P1 PUMP HOUSE - POWER FLOOR PLAN
EE700P1 PUMP HOUSE - SINGLE LINE DIAGRAM
TECHNOLOGY
TC100P1 PUMP HOUSE - SYSTEM FLOOR PLAN
FIRE ALARM
FA101P1 PUMP HOUSE - FIRE ALARM
PHB CERTIFIED FINAL 20NOV2020
ARIMS: 200A Disposition: Maintain for 15yrs after construction
As A w ar de d
A ug us t 2
W
2Q
R
C
/W
2Q
R
R
ANCHORED VENEER LINTEL
OPENING SIZE LINTEL DESCRIPTION DIAGRAM
0'-0" TO 6'-0" L4X3 1/2X1/4 (LLV)
6'-0" TO 10'-0" L4X3-1/2X1/4 (LLV)
1. PROVIDE MINIMUM 4" BEARING EACH SIDE OF LINTEL
2. STEEL ANGLES TO BE HOT-DIP GALVANIZED
10'-0" TO 14'-0" L6X3-1/2X5/16 (LLV)
905 N. CAPITOL AVE. SUITE 100 INDIANAPOLIS, IN 46204
317.800.6388 WWW.GUIDONDESIGN.COM
P lo t D at e th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
CONSTRUCTION DOCUMENTS -
URS | SMITHGROUP JOINT VENTURE
500 WEST JEFFERSON ST.
Suite 1600
LOUISVILLE, KY 40202
T 313.983.3600
F 313.983.3636 www.urscorp.com | www.smithgroupjjr.com
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management
B
A
C
D
E
F
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321 o n e s ix te e n th in c h o n e fo o t o n e th ir ty s e c o n d th in c h o n e fo o t
PROJECT # 14576907/22200.000
OFFICE OF CONSTRUCTION & FACILITIES MANAGEMENT - CENTRAL REGION
3001 GREEN BAY ROAD
BUILDING 48
NORTH CHICAGO, IL 60064
T 224.610.3492
U.S. DEPARTMENT OF VETERANS AFFAIRS
SHEET INDEX ID:
USACE LOUISVILLE DISTRICT
600 DR. MARTIN LUTHER KING PLACE
LOUISVILLE, KY 40202
PHONE: 502-315-6766
FAX: 502-315-6195
CONTRACTING DIVISION
OrientationSeal
/2
8/
0:
:3
A M
20NOV2020
SF00000
GENERAL STRUCTURAL NOTES
MAV WJT
Louisville, kentucky
REPLACEMENT VA MEDICAL CENTER
VA Project No. 603-320 USACE P2 No. 453413
700.07.2.S1-SF00000-STRUCTURAL
20NOV2020
GENERAL
THE STRUCTURE HAS BEEN DESIGNED FOR THE IN-SERVICE LOADS ONLY. THE METHODS, MEANS, PROCEDURES, AND SEQUENCES OF CONSTRUCTION ARE THE RESPONSIBILITY OF THE CONTRACTOR. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER THE BUILDING IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND SEQUENCE TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS DURING ERECTION. THIS INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, TEMPORARY BRACING, GUYS, TIEDOWNS, ETC.
THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH CIVIL, ARCHITECTURAL, MECHANICAL, ELECTRICAL AND PLUMBING
DRAWINGS AND SPECIFICATIONS.
THE GENERAL NOTES ON THE DRAWINGS ARE TO BE USED IN CONJUNCTION WITH THE FULL WRITTEN MATERIAL SPECIFICATIONS (IF ANY) FOR THE PROJECT. IF A DISCREPANCY OCCURS BETWEEN THE NOTES AND THE FULL SPECIFICATIONS, THE MORE STRINGENT
REQUIREMENT SHALL APPLY.
NO PENETRATIONS THROUGH STRUCTURAL ELEMENTS, OTHER THAN THOSE SHOWN ON THE DRAWINGS, SHALL BE MADE WITHOUT THE
APPROVAL OF THE STRUCTURAL ENGINEER.
THE NOTES ON THIS SHEET APPLY TO VOLUME 70 STRUCTURAL SHEETS ONLY.
CONCRETE MIX DESIGN SUBMITTAL
THE CONTRACTOR SHALL SUBMIT FOR THE REVIEW OF THE STRUCTURAL ENGINEER A MIX DESIGN FOR EACH PROPOSED CLASS OF CONCRETE. EACH MIX DESIGN SHALL BE IDENTIFIED BY A MIX NUMBER OR OTHER UNIQUE IDENTIFICATION. THE CONTRACTOR SHALL NOT VARY FROM THE MIX DESIGNS NOR USE ANY CONCRETEOTHER THAN THE APPROVED MIX DESIGNS WITHOUT THE
APPROVAL OF THE
STRUCTURAL ENGINEER. MIX DESIGN SUBMITTALS SHALL INCLUDE THE FOLLOWING INFORMATION:
1. MIX DESIGN NUMBER OR UNIQUE IDENTIFICATION AND INTENDED LOCATION OF PLACEMENT.
2. CEMENT TYPE, PROPORTION AND NAME OF MANUFACTURER.
3. FLY ASH PROPORTION (WHEN USED), LABORATORY ANALYSIS CERTIFICATION, AND NAME AND LOCATION OF SUPPLIER.
4. COURSE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION OF SUPPLIER.
5. FINE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION OF SUPPLIER.
6. MIXING WATER PROPORTION AND SOURCE.
7. ADMIXTURE DOSAGES, PRODUCT NAME(S) AND MANUFACTURER NAME(S).
8. FIBER REINFORCEMENT DOSAGE (WHEN USED), PRODUCT NAME AND MANUFACTURER NAME.
9. DESIGN 28-DAY COMPRESSIVE STRENGTH (F'C).
10. DESIGN SLUMP RANGE.
11. DESIGN AIR-ENTRAINMENT (FOR CONCRETE REQUIRING ENTRAINED AIR).
12. STATISTICAL ANALYSIS OF LABORATORY STRENGTH TEST DATA IN ACCORDANCE WITH "STANDARD DEVIATION"
DETERMINATION OUTLINED IN ACI 318.
SHOP DRAWING SUBMITTALS
THE CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS TO ENABLE HIM TO FABRICATE, ERECT AND CONSTRUCT ALL PARTS OF THE WORK IN ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS. THESE SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT ONLY. THE CONTRACTOR IS
RESPONSIBLE FOR ALL DIMENSIONS, ACCURACY AND FIT OF WORK.
ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO THE STRUCTURAL ENGINEER. DRAWINGS SUBMITTED WITHOUT CONTRACTOR'S REVIEW WILL BE RETURNED UNCHECKED.
SUBMIT ELECTRONIC VERSIONS OF SHOP DRAWINGS. SUBMIT SHOP DRAWINGS IN PDF FORMAT.
SUBMIT SHOP DRAWINGS FOR EACH OF THE FOLLOWING ITEMS:
1. CONCRETE REINFORCEMENT
2. CONCRETE MASONRY REINFORCEMENT
3. STRUCTURAL STEEL (INCLUDING DESIGN CALCULATIONS SEALED BY A PROFESSIONAL ENGINEER
REGISTERED IN THE STATE WHERE THE PROJECT IS CONSTRUCTED FOR ALL CONNECTIONS NOT
SPECIFICALLY DETAILED ON THE DRAWINGS)
4. STEEL DECK
PRODUCT DATA SUBMITTALS
THE CONTRACTOR SHALL SUBMIT FOR APPROVAL PRODUCT DATA FOR THE SPECIFIC ITEMS LISTED BELOW. CONTRACTOR SHALL NOT USE PRODUCTS OTHER THAN THOSE SUBMITTED WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER.
MANUFACTURER'S TRADE NAMES AND NUMBERS USED HEREIN ARE ONLY TO IDENTIFY COLORS, FINISHES, TEXTURES, AND PATTERNS AS A BASIS OF DESIGN. PRODUCTS OF AUTHORIZED EQUAL MANUFACTURER'S EQUIVALENT TO COLORS, FINISHES, TEXTURES, AND PATTERNS OF MANUFACTURERS LISTED THAT MEET REQUIREMENTS OF TECHNICAL SPECIFICATIONS IN EVERY RESPECT MAY BE ACCEPTABLE WITH SUBMITTAL OF A COMPLETED SUBSTITUTION REQUEST CONTAINING ALL PRODUCT DATA, TESTING AND ACTUAL SAMPLES, AND UPON APPROVAL IN WRITING BY CONTRACTING OFFICER.
SUBMIT ELECTRONIC VERSIONS OF PRODUCT DATA IN PDF FORMAT TO THE STRUCTURAL ENGINEER AND COR FOR REVIEW.
1. FIBER REINFORCEMENT FOR CONCRETE
2. CONCRETE REINFORCEMENT
3. DIAMOND PLATE DOWELS FOR SLABS ON GRADE
4. CONCRETE CURING COMPOUND
5. CONCRETE JOINT SEALANT
6. WATER STOPS
7. MASONRY JOINT REINFORCEMENT
8. EXPANSION ANCHORS
9. ADHESIVE ANCHORS
10. NON-SHRINK GROUT
FOUNDATIONS
FOUNDATION EXCAVATIONS AND SOIL RELATED WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE GEOTECHNICAL REPORT
NUMBER 7382-13-3013 PREPARED BY AMEC DATED 12 SEPTEMBER 2014.
FOUNDATIONS HAVE BEEN DESIGNED BASED ON ASSUMED ALLOWABLE CAPACITIES INDICATED BELOW. CONTRACTOR SHALL ENGAGE A LICENSED GEOTECHNICAL ENGINEER TO REVIEW THE SOIL CONDITIONS AT THE SITE TO CONFIRM THE ALLOWABLE CAPACITIES PRIOR TO PLACEMENT OF THE FOUNDATIONS. CONFIRMATION OF THE ACCEPTABILITY OF THE SOILS SHALL BE REPORTED IN WRITING TO THE
STRUCTURAL ENGINEER.
ALLOWABLE NET BEARING PRESSURE = 3,000 PSF
IF ACTUAL ALLOWABLE CAPACITIES ARE FOUND TO BE LESS THAN THE ASSUMED VALUES, THE CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER IMMEDIATELY AND SHALL NOT PROCEED WITH FOUNDATION CONSTRUCTION WITHOUT REVIEW BY THE
STRUCTURAL ENGINEER.
FOUNDATION CONDITIONS NOTED DURING CONSTRUCTION, WHICH DIFFER FROM THOSE DESCRIBED IN THE GEOTECHNICAL REPORT, SHALL BE REPORTED TO THE STRUCTURAL ENGINEER AND GEOTECHNICAL ENGINEER BEFORE FURTHER CONSTRUCTION IS ATTEMPTED.
EXCAVATIONS FOR SPREAD FOOTINGS, COMBINED FOOTINGS, CONTINUOUS FOOTINGS AND MAT FOUNDATIONS SHALL BE PREPARED IN
ACCORDANCE WITH THE EARTHWORK SPEC.
BELOW-GRADE WALLS
DO NOT BACKFILL AGAINST BELOW-GRADE CONCRETE (OR MASONRY) WALLS UNTIL THE CONCRETE (OR MASONRY ASSEMBLAGE)
HAS REACHED ITS 28-DAY COMPRESSIVE STRENGTH.
WHERE BACKFILL IS REQUIRED ON BOTH SIDES OF BELOW-GRADE WALLS, BACKFILL EVENLY ON EACH SIDE OF EACH WALL TO
PREVENT UNBALANCED SOIL LOADS AGAINST THE WALL.
CONCRETE CONT.
WATER-REDUCING ADMIXTURES SHALL CONFORM TO ASTM C494.
AIR-ENTRAINING ADMIXTURES SHALL CONFORM TO ASTM C260 AND SHALL BE CERTIFIED BY THE MANUFACTURER TO BE COMPATIBLE
WITH OTHER ADMIXTURES.
CALCIUM CHLORIDE ADMIXTURES OR ADMIXTURES CONTAINING MORE THAN 0.1 PERCENT CHLORIDE IONS SHALL NOT BE USED.
IN COLD WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND PROTECTION OF CONCRETE SHALL BE PERFORMED IN
ACCORDANCE WITH THE LATEST EDITION OF ACI 306R, COLD WEATHER CONCRETING.
IN HOT WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND PROTECTION OF CONCRETE SHALL BE PERFORMED IN
ACCORDANCE WITH THE LATEST EDITION OF ACI 305R, HOT WEATHER CONCRETING.
USE OF CONSTRUCTION JOINTS AT LOCATIONS OTHER THAN THOSE INDICATED ON THE DRAWINGS SHALL BE SUBMITTED TO THE
STRUCTURAL ENGINEER FOR REVIEW.
SLUMP FOR PUMPED CONCRETE SHALL BE MEASURED AT POINT OF DISCHARGE.
NORMAL WEIGHT CONCRETE SHALL BE USED IN THE FOLLOWING AREAS AND SHALL
HAVE THE PROPERTIES AS SHOWN BELOW:
FOUNDATIONS
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 470 LB./CU. YD. (USE TYPE II SULFATE RESISTANT CEMENT)
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS
ADDED TO CONCRETE WITH 2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.48
6. MAXIMUM COARSE AGGREGATE SIZE: 1 1/2 INCHES
7. AIR CONTENT: N/A
FOUNDATION WALLS
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 470 LB./CU. YD. (USE TYPE II SULFATE RESISTANT CEMENT)
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS
ADDED TO CONCRETE WITH 2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.48
6. MAXIMUM COARSE AGGREGATE SIZE: 1 INCH
7. AIR CONTENT: N/A
SLABS ON GRADE
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 470 LB./CU. YD. (USE TYPE II SULFATE RESISTANT CEMENT)
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS
ADDED TO CONCRETE WITH 2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.48
6. MAXIMUM COARSE AGGREGATE SIZE: 1 INCH
7. AIR CONTENT: 6% +/- 1%
8. HIGH RANGE WATER REDUCING ADMIXTURE AND FIBER REINFORCING REQUIRED
SLABS ON STEEL DECK
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 470 LB./CU. YD.
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS
ADDED TO CONCRETE WITH 2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.48
6. MAXIMUM COARSE AGGREGATE SIZE: 1 INCH
7. AIR CONTENT: N/A
CONCRETE SLABS ON GRADE
SLABS ON GRADE SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE LATEST EDITION OF THE GUIDE FOR CONCRETE FLOOR AND
SLAB CONSTRUCTION (ACI 302.1R).
PLACE CONCRETE IN A MANNER SO AS TO PREVENT SEGREGATION OF THE MIX. DELAY FLOATING AND TROWELING OPERATIONS UNTIL THE CONCRETE HAS LOST SURFACE WATER SHEEN OR ALL FREE WATER. DO NOT SPRINKLE FREE CEMENT ON THE SLAB
SURFACE.
PROVIDE CURING OF CONCRETE SLABS IMMEDIATELY AFTER FINISHING USING A SPRAYED ON DISSIPATING-RESIN LIQUID CURING COMPOUND CONFORMING TO ASTM C309, UNLESS NOTED OTHERWISE. ALL SCUFFS OR ABRASIONS TO THE CURING MEMBRANE SHALL BE RECOATED DAILY. OTHER CURING METHODS MAY BE USED WITH APPROVAL BY THE STRUCTURAL ENGINEER.
SLABS ON GRADE SHALL BE PLACED TO ACHIEVE THE FOLLOWING MINIMUM TOLERANCES:
OVERALL VALUES: FF = 25
LOCAL VALUES: FF = 20
THE MINIMUM LOCAL AREA SHALL BE ANY BAY DEFINED BY COLUMN LINES.
UNLESS SHOWN OR NOTED OTHERWISE, PROVIDE CONTROL OR CONSTRUCTION JOINTS IN SLABS-ON-GRADE AT A MAXIMUM SPACING OF 36 TIMES THE SLAB THICKNESS. PROVIDE JOINTS AT ALL COLUMN LOCATIONS. LOCATE JOINTS TO ELIMINATE RE-ENTRANT CORNERS AND TO CREATE SQUARE OR RECTANGULAR SECTIONS WITH MAXIMUM LONG SIDE TO SHORT SIDE RATIO OF 1.5 TO 1.
CONTROL JOINTS IN SLABS ON GRADE SHALL NOT RECEIVE JOINT FILLER MATERIAL UNLESS NOTED OTHERWISE.
CONCRETE SLABS ON METAL DECK
UNLESS INDICATED OTHERWISE ON THE DRAWINGS, CONCRETE SLABS ON METAL DECK SHALL BE PLACED AS REQUIRED TO MAINTAIN
A CONSTANT SLAB [THICKNESS].
CONTRACTOR SHALL ALLOW FOR THE DEFLECTION OF THE FLOOR ASSEMBLY DUE TO THE WET WEIGHT OF THE CONCRETE WHEN CALCULATING CONCRETE QUANTITIES AND SHALL INCLUDE THE COST OF ALL REQUIRED SLAB-ON-DECK CONCRETE IN THE BID PRICE.
PRIOR TO PLACEMENT OF CONCRETE SLABS ON METAL DECK, THE CONTRACTOR SHALL CAREFULLY REVIEW THE ELEVATIONS OF THE STRUCTURAL STEEL FRAMING, INCLUDING CAMBERED MEMBERS, FOR CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS.
CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER OF ANY DISCREPANCIES (SUCH AS IMPROPER CAMBER, IMPROPER STEEL ELEVATIONS, ETC.) IMMEDIATELY AND SHALL NOT BEGIN CONCRETE PLACEMENT WITHOUT PRIOR REVIEW BY THE STRUCTURAL
ENGINEER.
ACTUAL CONCRETE SLAB THICKNESS SHALL NOT BE LESS THAN THE INDICATED NOMINAL THICKNESS AT ANY LOCATION. IF ANY CONDITION IS DISCOVERED THAT WOULD PREVENT PLACEMENT OF CONCRETE TO THE NOMINAL THICKNESS; CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER IMMEDIATELY AND SHALL NOT PROCEED WITH CONCRETE PLACEMENT WITHOUT PRIOR REVIEW
BY THE STRUCTURAL ENGINEER.
SLABS ON METAL DECK SHALL RECEIVE A SMOOTH TROWEL FINISH, AND BE PLACED TO ACHIEVE THE FOLLOWING MINIMUM
TOLERANCES:
OVERALL VALUES: FF = 25
LOCAL VALUES: FF = 20
PLACE CONCRETE IN A MANNER SO AS TO PREVENT SEGREGATION OF THE MIX. DELAY FLOATING AND TROWELING OPERATIONS UNTIL THE CONCRETE HAS LOST SURFACE WATER SHEEN OR ALL FREE WATER. DO NOT SPRINKLE FREE CEMENT ON THE SLAB SURFACE.
PROVIDE CURING OF CONCRETE SLABS IMMEDIATELY AFTER FINISHING USING A SPRAYED ON DISSIPATING-RESIN LIQUID CURING COMPOUND CONFORMING TO ASTM C309. ALL SCUFFS OR ABRASIONS TO THE CURING MEMBRANE SHALL BE RECOATED DAILY. OTHER
CURING METHODS MAY BE USED WITH APPROVAL BY THE STRUCTURAL ENGINEER.
REINFORCING STEEL
REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615 AND SHALL HAVE A MINIMUM YIELD STRENGTH OF 60,000
PSI.
REINFORCING BAR DETAILING, FABRICATING, AND PLACING SHALL CONFORM TO THE LATEST EDITION OF THE FOLLOWING STANDARDS:
ACI 301, ACI 315, ACI 318 AND ACI DETAILING MANUAL (SP66).
UNLESS A GREATER AMOUNT OF COVER IS INDICATED ON THE DRAWINGS, PROVIDE THE FOLLOWING MINIMUM CONCRETE COVER
OVER REINFORCEMENT AS FOLLOWS:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3 INCHES
#6 BARS AND LARGER EXPOSED TO EARTH OR WEATHER: 2 INCHES
#5 BARS AND SMALLER EXPOSED TO EARTH OR WEATHER: 1-1/2 INCHES
BEAM AND COLUMN TIES, STIRRUPS AND SPIRALS: 1-1/2 INCHES
ELEVATED SLAB BARS NOT EXPOSED TO EARTH OR WEATHER: 3/4 INCH
REINFORCING STEEL SHALL NOT BE TACK WELDED, WELDED, HEATED OR CUT UNLESS INDICATED ON THE CONTRACT DOCUMENTS OR
APPROVED BY THE STRUCTURAL ENGINEER.
WHERE LAP SPLICE LENGTHS ARE NOT SHOWN OR NOTED, PROVIDE A CLASS "B" LAP.
ALL 90 DEGREE AND 180 DEGREE BENDS SHOWN ON THE DRAWINGS SHALL BE STANDARD HOOKS, UNLESS NOTED OTHERWISE.
PROVIDE CORNER BARS OF SAME SIZE AND SPACING AS HORIZONTAL BARS AT CORNERS OF ALL WALLS AND GRADE BEAMS. LAP
SPLICE CORNER BARS WITH STRAIGHT BARS.
UNLESS OTHERWISE SHOWN OR NOTED, PROVIDE 2-#5 BARS (ONE EACH FACE) AROUND UNFRAMED OPENINGS IN CONCRETE WALLS AND GRADE BEAMS. PLACE BARS PARALLEL TO THE SIDES OF THE OPENING AND EXTEND 24" BEYOND CORNERS.
WELDABLE REINFORCING STEEL
REINFORCING STEEL WHICH IS TO BE WELDED SHALL CONFORM TO ASTM A706. WELDING OF REINFORCING STEEL, WHEN APPROVED BY THE STRUCTURAL ENGINEER, SHALL CONFORM TO THE LATEST EDITION OF AMERICAN WELDING SOCIETY STANDARD D1.4.
ELECTRODES FOR SHOP AND FIELD WELDING OF REINFORCING STEEL SHALL CONFORM TO ASTM A233, CLASS E90XX.
EPOXY-COATED REINFORCING STEEL
EPOXY COATED REINFORCING STEEL SHALL CONFORM TO ASTM A775 AND SHALL BE USED ONLY WHERE SHOWN OR
NOTED ON THE DRAWINGS.
WELDED WIRE FABRIC
WELDED WIRE FABRIC SHALL BE SMOOTH WIRE FABRIC CONFORMING TO ASTM A185. FABRIC SHALL BE SUPPLIED IN FLAT SHEETS AND
LAPPED A MINIMUM OF ONE SPACE PLUS 2 INCHES.
WELDED WIRE FABRIC SHALL BE PLACED AS FOLLOWS, UNLESS NOTED OTHERWISE:
SLABS ON GRADE: 2 INCHES DOWN FROM TOP OF SLAB.
SLABS ON METAL DECK: 3/4 INCH DOWN FROM TOP OF SLAB.
FIBER REINFORCEMENT
FIBER REINFORCEMENT SHALL BE 3/4" LONG, VIRGIN (NON-RECYCLED) NYLON OR POLYPROPYLENE FIBERS, INTRODUCED INTO THE CONCRETE MIX AT THE BATCH PLANT, IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. DOSAGE SHALL BE 1.5
POUNDS PER CUBIC YARD OF CONCRETE.
CONCRETE TESTING
MAKE ONE SET OF TEST CYLINDERS IN ACCORDANCE WITH ASTM C31 FOR EACH DAY'S POUR AND FOR EACH 100 CUBIC YARDS. EACH SET SHALL INCLUDE ONE SPECIMEN TESTED AT 7 DAYS, 2 SPECIMENS TESTED AT 28 DAYS AND ONE SPECIMEN RETAINED IN RESERVE TO BE TESTED AT THE DIRECTION OF THE STRUCTURAL ENGINEER. SPARE CYLINDER MAY BE DISCARDED 90 DAYS AFTER CASTING
UNLESS
DIRECTED OTHERWISE BY THE STRUCTURAL ENGINEER. THIS SET OF TEST CYLINDERS SHALL BE PROTECTED AGAINST FREEZING.
WHEN THE AMBIENT TEMPERATURE IS EXPECTED TO FALL BELOW 40 DEGREES DURING THE COURSE OF A CONCRETE POUR OR SUBSEQUENT CURING PROCESS, AN ADDITIONAL SET OF CONCRETE TEST CYLINDERS SHALL BE MADE AND TESTED. THESE CYLINDERS SHALL BE STORED IMMEDIATELY ADJACENT TO, AND CURED UNDER THE SAME CONDITIONS AS THE BUILDING CONCRETE. SPECIAL
CURING BOXES ARE NOT PERMITTED FOR THESE TEST CYLINDERS.
FORWARD COPIES OF TEST RESULTS TO THE ARCHITECT, STRUCTURAL ENGINEER, READY-MIX SUPPLIER AND CONTRACTOR WITHIN 24
HOURS AFTER TESTING.
MASONRY
CONCRETE MASONRY HAS BEEN DESIGNED IN ACCORDANCE WITH THE LATEST EDITION OF THE BUILDING CODE REQUIREMENTS FOR
CONCRETE MASONRY STRUCTURES (ACI 530).
CONCRETE MASONRY SHALL CONSIST OF HOLLOW UNITS CONFORMING TO THE REQUIREMENTS OF ASTM C90, WITH A MINIMUM NET AREA COMPRESSIVE STRENGTH OF 1900 PSI. CONCRETE MASONRY ASSEMBLAGES SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH
(F'M) OF 1,500 PSI AT 28 DAYS.
MORTAR SHALL BE TYPE S PROPORTIONED IN ACCORDANCE WITH ASTM C270.
GROUT FOR REINFORCED MASONRY SHALL BE PROPORTIONED IN ACCORDANCE WITH ASTM C476. COARSE AND FINE AGGREGATES SHALL CONFORM TO ASTM C404. USE COARSE GROUT FOR ALL GROUTING EXCEPT HIGH-LIFT POURS DEFINED BY ACI 530-05 TABLE
1.16.1, WHERE FINE GROUT SHALL BE USED.
PROVIDE 9-GAUGE GALVANIZED STEEL WIRE JOINT REINFORCEMENT IN ALL MASONRY CONSTRUCTION. REINFORCEMENT SHALL BE CONTINUOUS AND BE LAPPED EIGHT INCHES AT SPLICES. CUT REINFORCEMENT AT ALL CONTROL AND EXPANSION JOINTS. SPACE REINFORCEMENT AT 8" ON CENTER FOR PARAPETS AND BELOW GROUND FLOOR ELEVATION. ELSEWHERE SPACE REINFORCEMENT AT
16 INCHES ON CENTER.
BEAMS AND LINTELS SHALL BEAR A MINIMUM OF 8 INCHES ONTO SUPPORTING MASONRY, UNLESS NOTED OTHERWISE. BEARING FOR ALL BEAMS, LINTELS, JOISTS, ETC. SHALL BE GROUTED SOLID A MINIMUM OF ONE COURSE (8 INCHES) BELOW BEARING ELEVATION, UNLESS NOTED OTHERWISE.
EXPANSION ANCHORS
EXPANSION ANCHORS SHALL BE CARBON STEEL ANCHORS AS MANUFACTURED BY HILTI FASTENING SYSTEMS OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER AND SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
EXPANSION ANCHORS SHALL NOT BE INSTALLED IN CONCRETE UNTIL IT HAS ATTAINED ITS SPECIFIED MINIMUM 28 DAY COMPRESSIVE
STRENGTH.
ADHESIVE ANCHORS
ADHESIVE ANCHORS SHALL BE HILTI "HIT HY200" FOR SOLID SUBSTRATE AND HILTI "HIT HY70" FOR HOLLOW SUBSTRATE OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER, UNLESS NOTED OTHERWISE ON PLANS. ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S RECOMMENDATIONS BY INSTALLERS TRAINED BY THE MANUFACTURER'S
REPRESENTATIVE.
MINIMUM EMBEDMENT DEPTH SHALL BE 8 BOLT DIAMETERS UNLESS NOTED OTHERWISE.
NON-SHRINK GROUT
GROUT SHALL BE A NON-METALLIC, SHRINKAGE RESISTANT (WHEN TESTED IN ACCORDANCE WITH THE LATEST EDITION OF ASTM C827 OR CRD-C621), PREMIXED, NON-CORROSIVE, NON-STAINING PRODUCT CONTAINING PORTLAND CEMENT, SILICA SANDS, SHRINKAGE COMPENSATING AGENTS AND FLUIDITY IMPROVING COMPOUNDS. GROUT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH (F'C) OF
5,000 PSI IN 28 DAYS.
WATERSTOPS
SELF-EXPANDING STRIP WATER STOPS SHALL BE VOLCLAY WATERSTOP-RX 101 UNLESS NOTED OTHERWISE. INSTALL IN ACCORDANCE
WITH MANUFACTURER'S WRITTEN INSTRUCTIONS.
PVC WATERSTOPS
PROVIDE FACTORY MADE WATERSTOP FABRICATIONS FOR ALL CHANGES OF DIRECTION, INTERSECTIONS, AND TRANSITIONS
LEAVING ONLY STRAIGHT BUTT JOINT SPLICES FOR THE FIELD.
PROVIDE HOG RINGS OR GROMMETS SPACED AT 12 INCHES ON CENTER ALONG LENGTH OF WATERSTOP.
PROVIDE TEFLON COATED THERMOSTATICALLY CONTROLLED WATERSTOP SPLICING IRONS FOR FIELD BUTT SPLICES.
FIELD BUTT SPLICES SHALL BE HEAT FUSED WELDED USING A TEFLON COATED THERMOSTATICALLY CONTROLLED WATERSTOP SPLICING IRON AT APPROXIMATELY 380 DEGREES F. FOLLOW APPROVED MANUFACTURER RECOMMENDATIONS.
LAPPING OF WATERSTOP, USE OF ADHESIVES, OR SOLVENTS SHALL NOT BE ALLOWED.
CENTER WATERSTOP IN JOINT AND SECURE WATERSTOP IN CORRECT POSITION USING HOG RINGS OR GROMMETS SPACED AT 12
INCHES ON CENTER ALONG THE
LENGTH OF THE WATERSTOP AND WIRE TIE TO ADJACENT REINFORCING STEEL.
MASTIC COATING
MASTIC COATING FOR PROTECTION OF INDICATED ITEMS SHALL BE BITUMASTIC 50 COAL TAR MASTIC BY CARBOLINE OR EQUIVALENT SUBSTITUTE APPROVED BY THESTRUCTURAL ENGINEER. INSTALL AT LOCATIONS INDICATED ON DRAWINGS.
UNLESS NOTED OTHERWISE, APPLY MASTIC TO A COATING THICKNESS OF 18 MILS. PROVIDE FULL COVERAGE OVER ITEMS
INDICATED TO RECEIVE COATING.
STRUCTURAL STEEL CONT
STRUCTURAL STEEL THAT RECEIVES FINISH PAINT SHALL BE SHOP-PRIMED WITH A RUST-INHIBITING PRIMER, UNLESS NOTED OTHERWISE ON THE DRAWINGS. CONTRACTOR SHALL VERIFY PRIMER IS COMPATIBLE WITH FINISH COAT SYSTEM SPECIFIED BY
THE ARCHITECT. COORDINATE FINISH PAINTING REQUIREMENTS WITH THE ARCHITECT.
STRUCTURAL STEEL THAT IS NOT EXPOSED IN THE FINISHED CONSTRUCTION AND DOES NOT RECEIVE FINISH PAINT SHALL NOT BE
SHOP-PRIMED, UNLESS NOTED OTHERWISE ON THE DRAWINGS.
STRUCTURAL STEEL NOTED TO BE GALVANIZED SHALL BE HOT-DIP GALVANIZED IN CONFORMANCE WITH ASTM A123.
DO NOT PAINT OR GALVANIZE THE FOLLOWING SURFACES:
1. SURFACES TO BE WELDED.
2. SURFACES TO RECEIVE BOLTED SLIP-CRITICAL CONNECTIONS.
3. SURFACES TO RECEIVE SHEAR STUD CONNECTIONS.
4. SURFACES TO RECEIVE SPRAYED-ON FIREPROOFING.
ALL ABRASIONS TO GALVANIZED SURFACES OR SURFACES TO RECEIVE AN ARCHITECTURAL FINISH COAT SHALL BE TOUCHED-UP AFTER ERECTION IS COMPLETE. FOR PAINTED STEEL, USE A PRIMER EQUIVALENT TO THE SHOP PAINT. FOR GALVANIZED STEEL, USE A ZINC-RICH COLD-GALVANIZING PAINT.
DESIGN CONNECTIONS NOT SHOWN IN ACCORDANCE WITH THE ASD SPECIFICATION AND MANUAL OF STEEL CONSTRUCTION.
UNLESS NOTED OTHERWISE ON THE DRAWINGS, DESIGN BEAM CONNECTIONS NOT SHOWN, TO SUPPORT A MINIMUM OF A 10 KIP SHEAR REACTION. PROVIDE NO LESS THAN 2 BOLTS IN ANY SINGLE LINE OF BOLTS, UNLESS SPECIFICALLY INDICATED ON THE
DRAWINGS.
PROVIDE L4X4X1/4 FRAMED OPENINGS FOR ALL ROOF PENETRATIONS 12 INCHES OR LARGER ALONG ANY SIDE, UNLESS LARGER FRAMING IS INDICATED. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR PENETRATIONS. COORDINATE FRAMED OPENING
SIZES AND LOCATIONS WITH THE MECHANICAL AND PLUMBING CONTRACTORS.
GALVANIZE ALL EXPOSED STEEL.
STEEL ROOF DECK
PROVIDE AND ERECT STEEL DECK IN ACCORDANCE WITH THE LATEST EDITION OF THE STEEL DECK INSTITUTE'S SPECIFICATIONS
AND CODE OF STANDARD PRACTICE.
DECK MANUFACTURER SHALL PROVIDE ALL ROOF DECK ACCESSORIES, INCLUDING CLOSURES, SUPPLEMENTARY FRAMING, AND
SUMP PANS, WHETHER OR NOT SUCH ITEMS ARE DETAILED ON THE CONTRACT DOCUMENTS.
FASTEN ROOF DECK TO STEEL SUPPORTS AS INDICATED ON THE DRAWINGS. PERFORM WELDING IN ACCORDANCE WITH ANSI/AWS D1.3.
ROOF DECK SHALL BE INSTALLED IN A MINIMUM THREE SPAN CONDITION.
PROVIDE STEEL ROOF DECK WITH FINISH AS INDICATED ON THE DRAWINGS.
STEEL FLOOR DECK
PROVIDE AND ERECT STEEL DECK IN ACCORDANCE WITH THE LATEST EDITION OF THE STEEL DECK INSTITUTE'S SPECIFICATIONS AND
CODE OF STANDARD PRACTICE.
DECK MANUFACTURER SHALL PROVIDE ALL FLOOR DECK ACCESSORIES, SUCH AS EDGE FORMS, CLOSURES, FILLERS AND POUR STOPS FOR A COMPLETE INSTALLATION, WHETHER OR NOT SUCH ITEMS ARE DETAILED ON THE CONTRACT DOCUMENTS.
FASTEN FLOOR DECK TO STEEL SUPPORTS AS INDICATED ON THE DRAWINGS. PERFORM WELDING IN ACCORDANCE WITH ANSI/AWS D1.3.
STEEL FLOOR DECK IS INTENDED TO BE INSTALLED IN AN UNSHORED CONDITION UNLESS NOTED OTHERWISE. DECK SUPPLIER SHALL REVIEW ALL SPAN CONDITIONS AND CONFIRM THAT THE SUPPLIED PRODUCT IS SUFFICIENT TO SAFELY SUPPORT THE WET WEIGHT OF
CONCRETE AND ASSOCIATED CONSTRUCTION LIVE LOADS WITHOUT THE NEED FOR SHORING.
FLOOR DECK UNITS SHALL BE INSTALLED IN A MINIMUM THREE SPAN CONDITION.
PROVIDE INTERIOR STEEL FLOOR DECK WITH FINISH AS INDICATED ON THE DRAWINGS.
PROVIDE FLOOR DECK SUPPORTING EXTERIOR SLABS WITH A GALVANIZED FINISH IN ACCORDANCE WITH ASTM A924 G90.
CONCRETE ABOVE FLUTE MIIMUM REINFORCEMENT
2" 6X6~W1.4XW1.4
2 1/2" 6X6~W1.4XW1.4
3" 6X6~W1.4XW1.4
4" 6X6~W2.0XW2.0
DESIGN DATA
THE BUILDING STRUCTURE HAS BEEN DESIGNED IN ACCORDANCE WITH THE 2015 INTERNATIONAL BUILDING CODE.
SEE LOAD MAPS FOR FLOOR LOADING CRITERIA.
SNOW LOAD DESIGN DATA
1. GROUND SNOW LOAD (PG) = 15 PSF
2. LOW-SLOPE ROOF SNOW LOAD (PF) = 18 PSF
3. SNOW EXPOSURE FACTOR (CE) = 0.9
4. THERMAL FACTOR (CT) = 1.0
5. SNOW LOAD IMPORTANCE FACTOR (IS) = 1.2
WIND LOAD DESIGN DATA
1. BASIC WIND SPEED (3-SECOND GUST) = 120 MPH
2. WIND LOAD IMPORTANCE FACTOR (IW) = 1.0
3. WIND EXPOSURE = C
4. WIND DESIGN PRESSURE (P) = VARIES WITH HEIGHT AND LOCATION
5. INTERNAL PRESSURE COEFFICIENT (GCpi) = +/- 0.18
EARTHQUAKE DESIGN DATA
1. SHORT PERIOD SPECTRAL RESPONSE (SS) = 0.197
2. 1-SECOND SPECTRAL RESPONSE (S1) = 0.103
3. SEISMIC IMPORTANCE FACTOR (IE) = 1.5
4. SITE CLASSIFICATION = C
5. SHORT PERIOD SPECTRAL RESPONSE COEFFICIENT (SDS) = 0.135
6. 1-SECOND SPECTRAL RESPONSE COEFFICIENT (SD1) = 0.094
7. ANAYSIS PROCEDURE UTILIZED = EQUIVALENT LATERAL FORCE PROCEDURE
8. MAINTENANCE BUILDING:
A. BASIC STRUCTURAL SYSTEM / SEISMIC RESISTING SYSTEM: A2 – ORDINARY REINFORCED CONCRETE SHEAR WALLS
B. RESPONSE MODIFICATION COEFFICIENT (R) = 4.0
C. SEISMIC RESPONSE COEFFICIENT (CS) = 0.049
D. OCCUPANCY CATEGORY = II
E. SEISMIC DESIGN CATEGORY = B
9. SMOKING SHELTER:
A. BASIC STRUCTURAL SYSTEM / SEISMIC RESISTING SYSTEM: H - STEEL SYSTEMS NOT SPECIFICALLY DETAILED FOR
SEISMIC RESISTANCE, EXCLUDING CANTILEVER COLUMN SYSTEMS
B. RESPONSE MODIFICATION COEFFICIENT (R) = 3.0
C. SEISMIC RESPONSE COEFFICIENT (CS) = 0.068
D. OCCUPANCY CATEGORY = II
E. SEISMIC DESIGN CATEGORY = B
10. GUARD HOUSES:
A. BASIC STRUCTURAL SYSTEM / SEISMIC RESISTING SYSTEM: H - STEEL SYSTEMS NOT SPECIFICALLY DETAILED FOR
SEISMIC RESISTANCE, EXCLUDING CANTILEVER COLUMN SYSTEMS
B. RESPONSE MODIFICATION COEFFICIENT (R) = 3.0
C. SEISMIC RESPONSE COEFFICIENT (CS) = 0.053
D. OCCUPANCY CATEGORY = II
E. SEISMIC DESIGN CATEGORY = B
11. ELECTRICAL BUILDING EAST:
A. BASIC STRUCTURAL SYSTEM / SEISMIC RESISTING SYSTEM: A2 – ORDINARY REINFORCED CONCRETE SHEAR WALLS
B. RESPONSE MODIFICATION COEFFICIENT (R) = 4.0
C. SEISMIC RESPONSE COEFFICIENT (CS) = 0.059
D. OCCUPANCY CATEGORY = IV
E. SEISMIC DESIGN CATEGORY = C
12. ELECTRICAL BUILDING WEST:
A. BASIC STRUCTURAL SYSTEM / SEISMIC RESISTING SYSTEM: A2 – ORDINARY REINFORCED CONCRETE SHEAR WALLS
B. RESPONSE MODIFICATION COEFFICIENT (R) = 4.0
C. SEISMIC RESPONSE COEFFICIENT (CS) = 0.059
D. OCCUPANCY CATEGORY = IV
E. SEISMIC DESIGN CATEGORY = C
13. BUS SHELTERS:
A. BASIC STRUCTURAL SYSTEM / SEISMIC RESISTING SYSTEM: H - STEEL SYSTEMS NOT SPECIFICALLY DETAILED FOR
SEISMIC RESISTANCE, EXCLUDING CANTILEVER COLUMN SYSTEMS
B. RESPONSE MODIFICATION COEFFICIENT (R) = 3.0
C. SEISMIC RESPONSE COEFFICIENT (CS) = 0.079
D. OCCUPANCY CATEGORY = II
E. SEISMIC DESIGN CATEGORY = B
14. PUMP HOUSE:
A. BASIC STRUCTURAL SYSTEM / SEISMIC RESISTING SYSTEM: A2 – ORDINARY REINFORCED CONCRETE SHEAR WALLS
B. RESPONSE MODIFICATION COEFFICIENT (R) = 4.0
C. SEISMIC RESPONSE COEFFICIENT (CS) = 0.059
D. OCCUPANCY CATEGORY = IV
E. SEISMIC DESIGN CATEGORY = C
CONCRETE
REINFORCED CONCRETE HAS BEEN DESIGNED IN ACCORDANCE WITH THE BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE (ACI 318) AND COMMENTARY (ACI 318R).
MIXING, TRANSPORTING, AND PLACING OF CONCRETE SHALL CONFORM TO THE LATEST EDITION OF THE SPECIFICATIONS FOR STRUCTURAL CONCRETE (ACI 301). READY-MIXED CONCRETE SHALL CONFORM TO THE REQUIREMENTS OF ASTM C94.
IN CASE OF A DISCREPANCY, THE PLANS AND SPECIFICATIONS SHALL GOVERN.
CEMENT SHALL CONFORM TO ASTM C150, TYPE I, UNO.
FLY ASH SHALL CONFORM TO ASTM C618, CLASS C OR F. THE RATIO OF THE AMOUNT (BY WEIGHT) OF FLY ASH TO TOTAL CEMENTITIOUS
MATERIALS IN THE MIX SHALL NOT EXCEED 25 PERCENT.
NORMAL WEIGHT AGGREGATES SHALL CONFORM TO ASTM C33.AGGREGATES AND SCMs SHALL BE TESTED SEPERATELY IN ACCORDANCE WITH ASTM C1567. THE TYPES OF AGGREGATES SHALL BE EVALUATED IN A COMBINATION WHICH MATCHES THE CONTRACTORS' PROPOSED MIX DESIGN (INCLUDING CLASS F FLY ASH OR GROUND GRANULATED BLAST FURNACE (GGBF) SLAG. ASR
TESTING SHOULD BE REQUIRED FOR EVERY MIX DESIGN SUBMITTED.
STRUCTURAL STEEL
STRUCTURAL STEEL DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO THE ANSI/AISC 360 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, LATEST EDITION WITH AMENDMENTS, AND THE AISC 303 CODE OF STANDARD PRACTICE FOR
STEEL BUILDINGS AND BRIDGES, LATEST EDITION WITH AMENDMENTS.
STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992, 50 KSI.
STRUCTURAL STEEL PLATES AND ROLLED SHAPES OTHER THAN WIDE-FLANGE SHAPES SHALL CONFORM TO ASTM A36, UNLESS
NOTED OTHERWISE.
STRUCTURAL STEEL TUBING SHALL CONFORM TO ASTM A500, GRADE B.
STRUCTURAL PIPE SHALL CONFORM TO ASTM A53, GRADE B.
ANCHOR RODS SHALL CONFORM TO ASTM F1554, GRADE 36, UNLESS NOTED OTHERWISE.
STEEL STUDS SHALL CONFORM TO ASTM A108.
BOLTED CONNECTIONS SHALL CONFORM TO THE SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS, APPROVED BY THE RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS OF THE ENGINEERING FOUNDATION. BOLTED CONNECTIONS FOR STRUCTURAL STEEL MEMBERS SHALL BE MADE WITH 3/4" DIAMETER A325 BOLTS, UNLESS NOTED OTHERWISE.
BOLTED CONNECTIONS SHALL BE TIGHTENED TO THE SNUG TIGHT CONDITION, EXCEPT BOLTED CONNECTIONS IN BRACE
ELEMENTS ARE TO BE FULLY PRETENSIONED WITH CLASS A FAYING SURFACES.
WELDING PROCEDURES SHALL CONFORM TO THE LATEST EDITION OF THE AMERICAN WELDING SOCIETY'S STRUCTURAL WELDING
CODE FOR STEEL ANSI/AWS D1.1.
WELDED CONNECTIONS USING ASTM A992 STEEL AS A BASE METAL SHALL BE MADE WITH E70XX LOW HYDROGEN ELECTRODES.
UNLESS OTHERWISE SHOWN OR NOTED ON THE DRAWINGS, OTHER WELDED CONNECTIONS MAY BE MADE WITH STANDARD E70XX
ELECTRODES.
INDICATES DIRECTION OF DECK SPAN
PHB CERTIFIED FINAL 20NOV2020
ARIMS: 200A Disposition: Maintain for 15yrs after construction
As A w ar de d
A ug us t 2
W
2Q
R
C
/W
2Q
R
R
B1 B2 B3
B4 B5 B6
C2 D1
G1
J1
J2
K2
L1
L2
M1
D2
C1
E1 E2
E3 E4
F1 F2
F3 F4
B1E
B4E
B4F
N1 N2
P1
K1
BUILDING AREA LEGEND
A NOT USED
B VA MEDICAL CENTER (VAMC)
C DOCK LAUNDRY FACILITY
D CENTRAL UTILITY PLANT (CUP)
E NORTH PARKING STRUCTURE
F SOUTH PARKING STRUCTURE
G MAINTENANCE BUILDING
H NOT USED
I NOT USED
J GUARD HOUSES
K WATER TOWER & WATER TANK
L ELECTRICAL SERVICE BUILDINGS
M BUS SHELTER
N COVERED WALKWAYS
P PUMP HOUSE
SHEET NUMBER LEGEND
A E 1 01 B1
DISCIPLINE DESIGNATOR
G GENERAL
H HAZARDOUS MATERIALS
V SURVEYING/MAPPING
B GEOTECHNICAL
C CIVIL
L LANDSCAPE
S STRUCTURAL
A ARCHITECTURAL
I INTERIORS
Q EQUIPMENT
F FIRE PROTECTION
P PLUMBING
D PROCESS
M MECHANICAL
E ELECTRICAL
T TELECOMM
LEVEL 2 DESIGNATOR - ARCH
GENERAL:
I INFORMATION
C CONTRACTURAL
R RESOURCE
SHEET TYPE DESIGNATOR
0 GENERAL
1 PLANS
1C REFLECTED CEILING PLANS
2 ELEVATIONS
3 SECTIONS
4 LARGE-SCALE VIEWS
5 DETAILS
6 SCHEDULES & DIAGRAMS
7 USER DEFINED
8 USER DEFINED
9 3D REPRESENTATIONS
BUILDING LEVEL
XX VARIES AT NON-PLANS
00 GROUND LEVEL
01 LEVEL 1
1i LEVEL 1i
02 LEVEL 2
03 LEVEL 3
04 LEVEL 4
4i LEVEL 4i
05 LEVEL 5
06 LEVEL 6
07 LEVEL 7
08 LEVEL 8
09 LEVEL 9
10 LEVEL 10
*OMIT LEADING "0" AT REFLECTED CEILING PLANS
KEY PLAN AREA / ZONE
KEY PLAN AREA AS DESIGNATED BY:
ON THIS PLAN
LETTER DENOTES KEY PLAN AREA
NUMBER DENOTES KEY PLAN ZONE
USE 01, 02 ETC FOR DRAWINGS
IN A SEQUENCE FOR NON-PLANS
B1
ARCHITECTURAL:
D DEMO
S SITE
E ELEMENTS
I INTERIORS
F FINISHES
G GRAPHICS
INTERIORS:
D DEMO
N DESIGN
F FURNISHINGS
G GRAPHICS
EQUIPMENT:
A ATHLETIC
B BANK
C CANTEEN
D DOCK
E EDUCATIONAL
F FOOD SERVICE
H HOSPITAL
L LABORATORY
M MAINTENANCE
P PARKING LOT
R CANTEEN RETAIL
S SITE
T TEXTILE CARE
(LAUNDRY)
V VIDEO
SHEET NUMBER LEGEND (NON-PLAN)
A E 3 1 01 B
DISCIPLINE DESIGNATOR
G GENERAL
H HAZARDOUS MATERIALS
V SURVEYING/MAPPING
B GEOTECHNICAL
C CIVIL
L LANDSCAPE
S STRUCTURAL
A ARCHITECTURAL
I INTERIORS
Q EQUIPMENT
F FIRE PROTECTION
P PLUMBING
D PROCESS
M MECHANICAL
E ELECTRICAL
T TELECOMM
LEVEL 2 DESIGNATOR - ARCH
GENERAL:
I INFORMATION
C CONTRACTURAL
R RESOURCE
SHEET TYPE DESIGNATOR
0 GENERAL
1 NOT USED
2 ELEVATIONS
3 SECTIONS
4 LARGE-SCALE VIEWS
5 DETAILS
6 SCHEDULES & DIAGRAMS
7 USER DEFINED
8 USER DEFINED
9 3D REPRESENTATIONS
SHEET TYPE SUB SERIES
1-9 INDICATES SUB SERIES TYPE
AS REQUIRED
SHEET SEQUENCE
01-99
ARCHITECTURAL:
D DEMO
S SITE
E ELEMENTS
I INTERIORS
F FINISHES
G GRAPHICS
INTERIORS:
D DEMO
N DESIGN
F FURNISHINGS
G GRAPHICS
EQUIPMENT:
A ATHLETIC
B BANK
C CANTEEN
D DOCK
E EDUCATIONAL
F FOOD SERVICE
H HOSPITAL
L LABORATORY
M MAINTENANCE
P PARKING LOT
R CANTEEN RETAIL
S SITE
T TEXTILE CARE
(LAUNDRY)
V VIDEO
KEY PLAN AREA
A NOT USED
B VA MEDICAL CENTER (VAMC)
C LAUNDRY FACILITY
D CENTRAL UTILITY PLAN (CUP)
E NORTH PARKING STRUCTURE
F SOUTH PARKING STRUCTURE
G MAINTENANCE BUILDING
H SMOKING SHELTERS
I NOT USED
J GUARD HOUSES
K WATER TOWER
L ELECTRICAL SERVICE BUILDINGS
M BUS SHELTER
Pl ot
Da te:
th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
CONSTRUCTION DOCUMENTS -
URS | SMITHGROUP JOINT VENTURE
500 WEST JEFFERSON ST.
Suite 1600
LOUISVILLE, KY 40202
T 313.983.3600 F 313.983.3636 www.urscorp.com | www.smithgroupjjr.com
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management
B
A
C
D
E
F
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321 o n e si xt e e n th in c h o n e fo o t o n e th ir ty se c o n d th in c h o n e fo o t
PROJECT # 14576907/22200.000
OFFICE OF CONSTRUCTION & FACILITIES MANAGEMENT - CENTRAL REGION
3001 GREEN BAY ROAD
BUILDING 48
NORTH CHICAGO, IL 60064
T 224.610.3492
U.S. DEPARTMENT OF VETERANS AFFAIRS
SHEET INDEX ID:
USACE LOUISVILLE DISTRICT
600 DR. MARTIN LUTHER KING PLACE
LOUISVILLE, KY 40202
PHONE: 502-315-6766
FAX: 502-315-6195
CONTRACTING DIVISION
OrientationSeal
/26
/20
4:
:07 P
M
20NOV2020
AE0000
BUILDING AREA DESIGNATION PLAN -
ARCHITECTURE
WJ MG
Louisville, Kentucky
REPLACEMENT VA MEDICAL CENTER
VA Project No. 603-320 USACE P2 No. 453413
0.01.08 MISC-AE0000-ARCHITECTURAL
20NOV2020
SCALE: NOT TO SCALE1 BUILDING AREA DESIGNATION PLAN
PHB CERTIFIED FINAL 20NOV2020
ARIMS: 200A Disposition: Maintain for 15yrs after construction
As A w ar de d
A ug us t 2
W
2Q
R
C
/W
2Q
R
R
A LABEL CLASS A DOOR
A/C AIR CONDITION
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAMA AMERICAN ARCHITECTURAL
MANUFACTURERS ASSOCIATION
AB ANCHOR BOLT
ABC AGGREGATE BASE COURSE
AC ASBESTOS CEMENT OR ASPHALTIC
CONCRETE
ACI AMERICAN CONCRETE INSTITUTE
ACS DR ACCESS DOOR
ACS FLR ACCESS FLOOR
ACS PNL ACCESS PANEL
ACST ACOUSTIC
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES ACT
ADC AUTOMATIC DOOR CLOSER
ADDL ADDITIONAL
ADDN ADDITION
ADH ADHESIVE
ADJ ADJACENT, ADJOINING, OR ADJUSTABLE
ADMIN ADMINISTRATION
ADB AUTOMATIC DOOR BOTTOM
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
AGA AMERICAN GAS ASSOCIATION
AGC ASSOCIATED GENERAL CONTRACTORS
AGGR AGGREGATE
AHJ AUTHORITY HAVING JURISDICTION
AHR ANCHOR
AHU AIR HANDLING UNIT
AIA AMERICAN INSTITUTE OF ARCHITECTS
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
ALT ALTERNATE
ALT NO ALTERNATE NUMBER
ALUM ALUMINUM
AMP AMPERE
AMT AMOUNT
ANOD ANODIZE
ANSI AMERICAN NATIONAL STANDARDS
INSTITUTE
ANT ANTENNA
APA AMERICAN PLYWOOD ASSOCIATION
APPD APPROVED
APPROX APPROXIMATE
APT APARTMENT
AR AS REQUIRED
ARCH ARCHITECT
ASB ASBESTOS
ASI ARCHITECT'S SUPPLEMENTAL
INSTRUCTION
ASKLR AUTOMATIC SPRINKLER
ASPH ASPHALT
ASSN ASSOCIATION
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
ATCH ATTACHMENT
ATM AUTOMATIC TELLER MACHINE
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AVE AVENUE
AVG AVERAGE
AW ACID WASTE
AWI ARCHITECTURAL WOODWORKING
INSTITUTE
AWPA AMERICAN WOOD PRESERVERS'
ASSOCIATION
AWS AMERICAN WELDING SOCIETY
AWT ACOUSTICAL WALL TREATMENT
B LABEL CLASS B DOOR
B PL BASE PLATE
BALC BALCONY
BAT BATTEN
BB BULLETIN BOARD
BD BOARD
BD FT BOARD FEET (FOOT)
BEV BEVEL
BHMA BUILDER'S HARDWARE
MANUFACTURER'S ASSOCIATION
BI FLD DR BIFOLDING DOORS
BITUM BITUMINOUS
BKG BACKING
BLD BUILD
BLDG BUILDING
BLKT BLANKET
BLVD BOULEVARD
BM BEAM OR BENCHMARK
BOT BOTTOM
BR BEDROOM
BRCG BRACING
BRDG BRIDGING
BRDG JST BRIDGING JOIST
BRG BEARING
BRG PL BEARING PLATE
BRKT BRACKET
BRZ BRONZE
BSMT BASEMENT
BTWN BETWEEN
BU BUSHEL
BUR BUILT-UP ROOFING
C CELSIUS CHANNEL
C CHANNEL CELSIUS
C CONC CAST CONCRETE
C LABEL CLASS C DOOR
C TO C CENTER TO CENTER
CAB CABINET
CAC CEILING ATTENUATION CLASS
CB CATCH BASIN OR CORNER BEAD
CBB CEMENTITIOUS (BACKER) BOARD
CC CUBIC CENTIMETER
CCTV CLOSED CIRCUIT TELEVISION
CCW COUNTERCLOCKWISE
CD CONSTRUCTION DOCUMENTS OR
CONTRACT DOCUMENTS
CEM CEMENT
CEM PLAS CEMENT PLASTER
CER CERAMIC
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR
INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER
INSTALLED
CFLG COUNTERFLASHING
CFM CUBIC FEET PER MINUTE
CFMF COLD-FORMED METAL FRAMING
CFS CUBIC FEET PER SECOND
CG CENTER OF GRAVITY OR CORNER GUARD
CGSFU CERAMIC GLAZED STRUCTURAL FACING
UNITS
CH BD CHALKBOARD
CHEM CHEMICAL
CHFR CHAMFER
CHK CHECK
CI CAST IRON
CIP CAST-IN-PLACE
CIR CIRCLE
CIRC CIRCULAR
CJ CONSTRUCTION JOINT OR CONTROL
JOINT
CL CENTER LINE
CLDG CLADDING
CLG CEILING
CLG HT CEILING HEIGHT
CLR CLEAR
cm² SQUARE CENTIMETER cm ³ CUBIC CENTIMETER
CM CONSTRUCTION MANAGEMENT
CMU CONCRETE MASONRY UNIT
CNR CORNER
CNTR COUNTER
CO CARBON MONOXIDE, CERTIFICATE OF
OCCUPANCY, CLEANOUT, OR COMPANY
CO₂ CARBON DIOXIDE
COL COLUMN
COM COMMON
COMB COMBINATION, COMBINED
COMM COMMUNICATION
COMP COMPONENT
CONC CONCRETE
CONC FLR CONCRETE FLOOR
COND CONDENSER OR CONDITION
CONF CONFERENCE
CONN CONNECT
CONSTR CONSTRUCTION
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CORR CORRIDOR
CPM CRITICAL PATH METHOD
CPRS COMPRESSIBLE
CPT CARPET
CRS COLD ROLLED STEEL
CRSI CONCRETE REINFORCING STEEL
INSTITUTE
CSB CONCRETE SPLASH BLOCK
CSG CASING
CSI CONSTRUCTION SPECIFICATIONS
INSTITUTE
CSK COUNTER SUNK
CSMT CASEMENT
CSWK CASEWORK
CT CERAMIC TILE
CTB CERAMIC TILE BASE
CTF CERAMIC TILE FLOOR
CTG COATING
CTR CENTER CONTOUR
CTRL CONTROL
CTV CABLE TELEVISION
CU…