API 653 Out-of-Service Inspection Report Andrews AFB, Maryland
US Army Corps of Engineers Omaha District
API 653 Out-of-Service Inspection Report
Andrews AFB Facility 3474
Tank 2 US Army Corps of Engineers Center of Expertise for Petroleum, Oils and Lubricants
(USACE POL-MCX)
2/5/2018
Table of Contents
ACRONYMS AND ABBREVIATIONS
GENERAL SUMMARY
INSPECTION DATE
PREVIOUS INSPECTION DATES
RECOMMENDED FUTURE INSPECTION DATES
GENERAL TANK INFORMATION
A. GENERAL PROJECT INFORMATION
1. API 653 Inspection
2. Site Information
B. TANK INSPECTION COMMENTS
1. Tank Construction
2. Tank Foundation
3. Cathodic Protection
4. Tank Bottom
5. Tank Shell
6. Fixed Roof
7. Tank Appurtenances
a. Tank Shell
b. Fixed Roof
c. Gauging
d. Level Alarms
e. Stairs and Platforms
f. Grounding and Bonding
8. Tank Coating
9. Fire Protection System
10. Secondary Containment
11. Internal Floating Roof
C. OBSERVATIONS AND RECOMMENDATIONS
1. MANDATORY REPAIRS per API 653, UFC 3-460-01, or AW 78-24-27 Standards
2. RECOMMENDED REPAIRS to Fully Comply with API 653, UFC 3-460-01, or AW 78-24-27 Standards
3. RECOMMENDED REPAIRS as Part of Regular Maintenance
D. INSPECTION INTERVALS
1. Routine In-service Inspection
2. External (In-Service) Inspection
3. Ultrasonic Thickness Inspection
4. Internal (Out-of-Service) Inspection
APPENDIX A: ENGINEERING CALCULATIONS AND DRAWINGS
Drawing 01 Bottom Layout
Table 1: Tank Bottom Ultrasonic Thickness Readings
Table 2: Tank Bottom Critical Zone Ultrasonic Thickness Readings
Tank Bottom Service Life Evaluation
API 653 Appendix B Settlement Evaluation
Table 3: Tank Bottom Elevation Measurements
Drawing 02: Shell Layout
Table 4: Shell Plate Ultrasonic Thickness Readings
Shell Service Life Evaluation
Out-of-Roundness Evaluation
Drawing 03: Fixed Roof Layout
Table 5: Fixed Roof Ultrasonic Thickness Readings
Roof Life Evaluation
Table 6: Nozzle and Appurtenances
Table 7: Dry Film (Coating) Thickness
APPENDIX B: API 653 CHECKLISTS FOR TANK INSPECTIONS
APPENDIX C: PHOTOGRAPHS
ACRONYMS AND ABBREVIATIONS
AFB Air Force Base
API American Petroleum Institute
ATG Automatic Tank Gauge
BBL Barrel
BMP Best Management Practice
COMAR Code of Maryland Regulations
DB&B Double Block and Bleed
HHLA High-High Level Alarm
HLA High Level Alarm
HLCV High Level Control Valve
IAW In Accordance With
ICCP Impressed Current Cathodic Protection
IFR Internal Floating Roof
LLA Low Level Alarm
LLLA Low-Low Level Alarm
MFL Magnetic Flux Leakage
NDT Non-Destructive Testing
NFPA National Fire Protection Association
OOS Out-of-Service
SG Specific Gravity
UFC Unified Facilities Criteria
USACE United States Army Core of Engineers
UTT Ultrasonic Thickness Testing
VT Visual Testing
W/ With
W/O Without
GENERAL SUMMARY
POND was under contract to the United States Army of Engineers (USACE), Omaha District, to provide an out-of-service (OOS) American Petroleum Institute (API) 653 tank inspection, provide a hydrostatic test of the tank containment, and replace the internal floating roof primary and secondary seals with double wiper seals on Tank 2
(Facility 3474), at Andrews Air Force Base (AFB) located in Joint Base Andrews, Maryland.
The OOS API 653 inspection was performed 30-31 January, 2018 in accordance with (IAW) API 653, 5th Edition.
Results of this inspection and testing activities identified recommended repairs and upgrades required to comply with API 650/653, Unified Facilities Criteria (UFC) 3-260-01/3-460-03, AW 78-24-27, Code of Maryland
Regulations (COMAR), and industry standards.
Contained in this report is a detailed account of the tank inspection, non-destructive testing (NDT) methods, and conclusions derived from the inspection and testing activities. Findings from this inspection are further detailed in
Section B of this report. Recommended repairs and upgrades identified in Section B are further classified and listed in Section C of this report.
INSPECTION DATE
API Out-of-Service Inspection Date: 30-31 January, 2018 Equipment Used:
Manufacturer: MFE Enterprises Tank Floor Scanner Model Number: MFE 2412 Mark III Calibration Method: Function Plate with Known Defect
Manufacturer: GE Krautkramer Ultrasonic Thickness Gauge with Topcoat Model Number: DMS GO+ Calibration Method: 1-point Calibration
Manufacturer: Fisher Technologies Dry Film Thickness Gauge Model Number: Dual Scope MPOR Calibration Method: Calibration to Known Thickness Standard
Manufacturer: Johnson Self-Leveling Rotary Laser Level Model Number: 40-6515 Calibration Method: Self-Leveling
Inspector(s):
John Cronin Andrew Morrissette
PREVIOUS INSPECTION DATES
API Out-of-Service (Internal) Inspection Date: Unknown API In-Service (External) Inspection Date: Unknown
RECOMMENDED FUTURE INSPECTION DATES
Routine In-Service: Monthly API 653 Out-of-Service (Internal): 31 January 2028 API In-Service (External) w/o UTT: 31 January 2023 w/ UTT: 31 January 2033
NOTE:
IAW UFC 3-460-03, New Summary Sheet, Unification Issues, the Air Force requires tanks above 20,000 gallons in capacity to be cleaned on a ten (10) year cycle. Coating along the shell-to-bottom weld is in poor condition displaying disbondment from the shell and allowing water ingress due to tank sweating. Integrity of this weld could not be inspected due to the presence and condition of the coating. Based on the significance of the integrity of this weld, it is recommended to maintain a ten (10) year inspection interval to further evaluate the coating and weld integrity.
John Cronin, EIT Andrew Morrissette Brian W. Lunsford, P.E.
Integrity Engineer Integrity Engineer Program Manager / Integrity Engineer
API 653 Inspector # 77554 API 653 Inspector #28526
GENERAL TANK INFORMATION
ITEM DESCRIPTION
Owner U.S. Air Force
Location Andrews AFB
Facility Number 3474
Tank Number 2
State / Country Maryland / United States
City Joint Base Andrews
Inspection Date 30-31 January, 2018
Tank Manufacturer Witherup Fabrication and Erection, Inc.
Design Standard API 650, 10th Edition, Revision B
Date of Construction 2005
Tank Contents JET-A (F-24) (SG = 0.85)
Tank Diameter 31’-0”
Tank Height 41’-3”
Design Liquid Level 37’-7”
Tank Capacity 5,000 Barrels (BBL) – 210,000 Gallons
Foundation Concrete Ring Wall
Construction
Bottom Cone Down / Lap-Welded Steel Plates
Shell Butt-Welded Steel Plates / Five (5) Shell Courses
Floating Roof Aluminum Honeycomb Pan / Double Wiper Seal System
Fixed Roof Lap-Welded Steel Plates / Cone-Up / Self-Supported
Material
Bottom Carbon Steel
Shell A-36 MOD Carbon Steel
Floating Roof Aluminum
Fixed Roof Carbon Steel
Cathodic Protection Impressed Current Cathodic Protection (ICCP) System
Interior Coating System Unknown (Assumed Epoxy Based)
Exterior Coating System Unknown (Assumed Epoxy Based)
Level Gauging Enraf Automatic Tank Gauge (ATG)
Overfill Protection High Level Control Valve (HLCV) and HLCV Shut-Off Switch / Four (4) Overflow Vents
Piping Product Receipt 8” Carbon Steel
Main Suction 12” Carbon Steel
Water Draw-Off 1 ½” Carbon Steel
Low Suction 4” Carbon Steel
Level Alarms High Level Alarm (HLA), High-High Level Alarm (HHLA), Low Level Alarm (LLA), and Low-Low Level Alarm (LLLA)
A. GENERAL PROJECT INFORMATION
1. API 653 Inspection
An OOS API 653 inspection was performed 30-31 January, 2018 on Tank 2 (Facility 3474). Results of this inspection identified recommended repairs and upgrades required to comply with API 650/653, UFC 3-460-01/3-460-03, AW 78-24-27, and industry standards.
2. Site Information
Andrews Air Force Base is the airfield portion of Joint Base Andrews which is under the jurisdiction of the United States Air Force. In 2009, Andrews Air Force Base merged with Naval Air Facility
Washington to form Joint Base Andrews. Andrews is the home base of two Boeing VC-25A aircraft with the call sign Air Force One when the president is on board, that serve the President of the United States.
The host unit at Andrews is the 11th Wing, assigned to the Air Force District of Washington. It is responsible for maintaining emergency reaction rotary-wing airlift and other National Capital Region contingency response capabilities critical to national security; and for organizing, training, equipping and deploying combat-ready forces for Air and Space Expeditionary Forces.
B. TANK INSPECTION COMMENTS
1. Tank Construction
Tank 2 (Facility 3474) is a welded, steel, single-wall, JET-A (F-24), vertical aboveground storage tank.
The tank was constructed in 2005 by Witherup Fabrication and Erection, Inc. IAW API 650 10th Edition, Revision B. Tank 2 is 31’-0” in diameter and 41’-3” high with a nominal capacity of 5,000 BBL.
Construction drawings were not available for review. The facility possesses strapping charts for the tank. Strapping charts are provided in 1” increments with a separate column for calculating values within 1/16” increments.
2. Tank Foundation
Tank 2 rests on a concrete ring wall foundation. The tank chime-to-ring wall interface is provided with sealant in good overall condition displaying only minor signs cracking and staining. Sealant provided at the tank ring wall-to-containment interface is in poor condition and exhibits signs of voids, cracking, disbondment, and vegetation growth. A settlement evaluation was performed during the inspection. No signs of settlement were noted. See Appendix A for settlements results.
3. Cathodic Protection
The tank is cathodically protected from soil-side corrosion by an ICCP system.
4. Tank Bottom
The tank bottom is of cone-down construction with lap-welded carbon steel plates. The tank bottom was examined using magnetic flux leakage (MFL), ultrasonic thickness testing (UTT), and visual testing
(VT) methods. The MFL bottom scan revealed no indications of top-side or soil-side indications. Five
(5) UTT measurements were taken on each bottom plate. One (1) UTT reading was taken every 2 feet around the tank perimeter within the tank bottom critical zone.
UTT readings revealed no significant metal loss on bottom plates. VT was performed along the bottom plate lap-welds and the bottom-to-shell weld. Coating along the shell-to-bottom weld displays disbondment. Due to possible sweating of the tank during change in temperatures throughout the day, moisture may seep behind the coating and come in contact with the shell-to-bottom weld. VT examination of the shell-to-bottom weld was limited due to the presence and condition of the internal coating. Two (2) anti-rotation cables are attached to the bottom via square-cornered attachments.
Square corners present stress risers that could affect the integrity of the weld. The tank is currently equipped with a 29” diameter, 9” deep center sump. Coating provided for the center sump displays minor signs of failure and deterioration. Widespread pitting was observed throughout the tank bottom.
Maximum pit depth was found to be 0.035”. This value is within the maximum tolerance allowed by
API. At the time of the inspection, pitting was coated and inactive. Pitting may have been limited to impurities and inclusions in the coating, caused by improper application or incorrect surface preparation.
Refer to Drawing 01, “Bottom Layout” for the bottom plate layout and Table 1, “Tank Bottom Ultrasonic
Thickness Readings” and Table 2, “Tank Bottom Critical Zone Ultrasonic Thickness Readings” in
Appendix A for bottom plate UTT readings.
5. Tank Shell
The tank shell is equipped with five (5) butt-welded A-36 MOD steel shell courses. Shell plates were examined using UTT and VT methods. Nine (9) UTT measurements were taken on each plate of the 1st shell course. Nine (9) UTT measurements were taken on the 2nd through 5th shell course using the spiral staircase for access. UTT readings indicated no significant metal loss. The tank shell is not provided with a National Fire Protection Association (NFPA) emergency responder diamond. Conduit provided for the HLCV shutoff and visible alarm system is supported along the tank shell via-stitch welded connections. Stitch-welding creates a crevice between the shell and support. Crevice corrosion and weep staining was observed during the inspection at the interstice.
Refer to Drawing 02, “Shell Rollout” and Table 4, “Shell Plate Ultrasonic Thickness Readings” in
Appendix A for the shell plate layout and UTT readings.
6. Fixed Roof
The self-supported fixed roof is of cone-up construction with fully coated lap-welded steel plates. Fixed roof plates were examined using UTT and VT methods. Five (5) UTT measurements were taken on each fixed roof plate. UTT readings indicated no significant metal loss on the fixed roof plates.
Refer to Drawing 03, “Fixed Roof Layout” and Table 5, “Fixed Roof Ultrasonic Thickness Readings” in
Appendix A for plate location and UTT readings.
7. Tank Appurtenances
a. Tank Shell
Shell nozzles consist of three (3) 36” manways, one (1) 8” receipt, two (2) 1 ½” HLCV shut-off switch penetrations, two (2) 1 ½” high level alarm penetrations, two (2) low level alarm (2) penetrations, one (1) 12” main suction, one (1) 4” low suction, and one (1) 1 ½” water draw-off line. Shell nozzles and reinforcement pads were examined using UTT and VT methods. Four (4)
UTT reading were taken on each nozzle with a welded connection in each of four (4) quadrants
(0°, 90°, 180°, and 270°). One (1) UTT reading was taken on each reinforcement pad. UTT readings indicated no significant metal loss. Tell-tale holes provided for reinforcement pads are open to the atmosphere. The main suction and receipt piping is not provided standard military labeling. Crossover piping provided for the receipt and main suction lines are provided with sight flow indicators. Sight flows are no longer used in this application as they present potential leak paths. Coating provided for the main suction and receipt crossover piping, HLA, HHLA, HLCV shutoff, and the LLA displays flaking, corrosion staining, and deterioration. The HLA, HHLA, HLCV, and LLA are provided with threaded connections. The low suction line is provided with a 4” threaded connection proceeding the cam lock connection. UFC limits the use of threaded connections as they may not provide an adequate seal. The water draw-off line is provided with a ball valve at the tank skin location. Double block and bleed (DB&B) valves should always be used at the skin location as a ball valve may not provide adequate isolation during maintenance and inspection activities.
The internal main suction line extends half the tank radius; however, does not turn down towards the tank bottom. Neither the main suction nor low suction piping is provided with U-bolt attachments to limit lateral movement of the internal piping.
Refer to Drawing 02, “Shell Rollout” and Table 6, “Nozzles and Appurtenances” in Appendix A for nozzle location and data.
b. Fixed Roof
Fixed roof nozzles consist of two (2) 2 ½” anti-rotation cables, one (1) 36” manway with an 8” gauge hatch and internal access ladder, one (1) 6” Enraf automatic tank gauge (ATG) with an attached VITO temperature/water probe, one (1) 72” x 24” hatch, two (2) 2 ½” pan ground cables, one (1) 4” cap, one (1) 24” center vent, and one (1) 1 ½” tape level gauge penetration.
Fixed roof nozzles and reinforcement pads were examined using UTT and VT methods. Four (4)
UTT reading were taken on each nozzle with a welded connection in each of four (4) quadrants
(0°, 90°, 180°, and 270°). One (1) UTT reading was taken on each reinforcement pad. UTT readings indicated no significant metal loss on nozzles and associated reinforcement pads. The
Enraf ATG nozzle is equipped with carbon steel bolts that exhibit corrosion. The VITO temperature/water probe is provided in the same stilling well and riser as the Enraf ATG. To accurately gauge water levels within the tank, the VITO temperature/water probe should be placed as close to the tank sump as feasible. A cap located on a 1” pipe extruding the Enraf ATG riser is severely corroded exhibiting surface corrosion with metal loss.
Refer to Drawing 03, “Fixed Roof Layout” and Table 6, “Nozzles and Appurtenances” in
Appendix A for nozzle location and data.
c. Gauging
The tank is provided with an Enraf ATG system for automatic tank gauging. The Enraf ATG has a fill height label stating 33’-0”, while the strapping charts state the safe fill height as 34’-0”. The
Enraf ATG shares the same riser and stilling well as the VITO temperature/water probe. Manual gauging is performed through the gauging hatch located on the fixed roof manway. Neither the
Enraf ATG nor manual gauging hatch stilling wells are fully slotted. Stilling wells provided for the manual gauging hatch and Enraf ATG are attached directly to well guides at the tank bottom.
If the tank begins to settle, this configuration may cause icreased stress at the tank bottom. The tank is provided with a Shand and Jurs float gauge for gauging the tank volume from the ground level.
d. Level Alarms
The tank is equipped with shell-mounted independent level alarms in the high, high-high, low, and low-low level positions. The tank is provided with a HLCV shutoff for overfill protection.
e. Stairs and Platforms
The tank is provided with a spiral staircase with three (3) platforms. The first platform as for access to MW3 and the internal floating roof (IFR). The second platform is for level alarm access and maintenance. The third platform is for access to the fixed roof.
f. Grounding and Bonding
The tank is equipped with four (4) grounding lugs and cables that are in good overall condition with no signs of damage or detachment.
8. Tank Coating
All exterior and internal surfaces of the tank are coated. Coating was in good overall condition with only minor signs of failure located primarily on nozzles, appurtenances, and in the center sump with the exception of the shell-to-bottom weld which displayed disbondment.
9. Fire Protection System
For internal fire protection, Tank 2 is provided with a full contact aluminum honeycomb IFR.
10. Secondary Containment
Tank 2 is located within a concrete containment dike. Control joints for the concrete dike floor exhibit damaged (voids, cracking, disbondment, and vegetation growth) sealant. Minor signs of cracking and spalling were observed throughout the containment dike floor. Based on year of construction of the tank, it could be assumed a flexible membrane liner is provided under the tank containment; however, due to lack of as-built or construction drawings this could not be verified. In the event of a spill, the containment dike can hold approximately 40,000 BBLs. This value is approximately 127% greater than the maximum capacity of the tank.
A leak test was performed by Dark Horse on the containment dike drainage system. The leak test consisted of filling the dike drain to 3 7/16” below the drain grate and holding this volume for approximately 2 hours and 15 minutes. At the end of this time interval there was no change in height from the drain grate.
11. Internal Floating Roof
The tank is provided with an aluminum honeycomb (IFR. The IFR was provided with foam log primary and secondary seals. The foam log seals were replaced with a double wiper seal system as part of this inspection. The IFR was examined using VT methods. No gross defects nor damage were noted. The IFR is provided with six (6) support legs. Each support leg is provided with a landing pad that are sealed to the tank bottom. Two (2) mounting clips for the IFR anti-rotation cables are welded directly to the tank bottom and not provided with a fully seal welded base plate.
C. OBSERVATIONS AND RECOMMENDATIONS
The following subsections outline the itemized tank repairs/upgrades. Repairs and upgrades shall be completed IAW API 653, UFC 03-460-01, requirements and best engineering practice.
1. MANDATORY REPAIRS per API 653, UFC 3-460-01, or AW 78-24-27 Standards
Mandatory repairs represent items that require immediate attention, in order to prevent imminent risk to system operators, equipment integrity, or the adjacent environment. The tank should remain OOS until these repairs are completed.
There are no mandatory repairs required to return the tank to service.
2. RECOMMENDED REPAIRS to Fully Comply with API 653, UFC 3-460-01, or AW 78-24-27
Standards
Recommended repairs represent items that should be addressed in a timely manner in order to prevent future potential risks to system operators, equipment integrity, or the adjacent environment. These items may be required by Federal, State and Local Codes or by Military Criteria.
a. Tank Chime Sealant
OBSERVATION: Sealant provided for the tank chime displays cracking and staining.
CODE REFERENCE: UFC 3-460-03 SECTION 8-4.1.B
RECOMMENDATION: Provide approximately 5 linear feet of sealant repair at the tank chime-to-ring wall interface.
b. Pipeline Labeling
OBSERVATION: Piping within the containment dike is not provided with standard military labeling.
CODE REFERENCE: UFC 3-460-01, 2-18
RECOMMENDATION: Provide MIL-STD-161H labeling and flow arrows on the receipt and main suction line.
c. Ring Wall Control Joint
OBSERVATION: The tank ring wall-to-containment interface exhibits voids, cracking, disbondment, and vegetation growth.
CODE REFERENCE: UFC 3-460-03 SECTION 8-10.2.2 (C)
RECOMMENDATION: Provide approximately 100 linear feet (100%) of sealant repair at the tank ring wall-to-containment interface with a flexible, UV protective, and fuel resistant sealant.
d. Control Joint Sealant
OBSERVATION: Sealant provided for control joints located in the containment dike exhibit voids, cracking, disbondment, and vegetation growth.
CODE REFERENCE: UFC 3-460-03 SECTION 8-10.2.2 (C)
RECOMMENDATION: Provide approximately 50 linear feet of sealant repair at control joints within the containment dike with a flexible, UV protective, and fuel resistant sealant.
e. Containment Floor Cracking
OBSERVATION: Cracking was observed throughout the containment dike floor.
CODE REFERENCE: UFC 3-460-03 SECTION 8-10.2.2 (C)
RECOMMENDATION: Provide approximately 25 linear feet of sealant to cracking located throughout the containment dike.
f. Containment Floor Spalling
OBSERVATION: Spalling and damage was observed throughout the containment dike floor.
CODE REFERENCE: UFC 3-460-03 Section 8-10.2.2 (B)
RECOMMENDATION: Repair concrete dike floor. Existing floor exhibits approximately 10 ft2 of spalling and damage.
g. Emergency Responder Diamond
OBSERVATION: The tank is not provided with an emergency responded diamond.
CODE REFERENCE: UFC 3-460-01 2-18 (C)
RECOMMENDATION: Provide emergency responder diamond in accordance with NFPA 704.
h. Coating Failure
OBSERVATION: Coating provided for various piping, nozzles, and appurtenance displays flaking, corrosion staining, and deterioration.
CODE REFERENCE: UFC 3-460-03, Section 8-3.1
RECOMMENDATION: Provide approximately 12 ft2 of coating repair at the following piping, nozzles, and appurtenances:
• Main suction crossover piping – 2 ft2
• Receipt crossover piping – 2 ft2
• HLA, HHLA, and high level control valve (HLCV) shutoff switch – 2 ft2
• LLA and LLLA – 3 ft2
• Center sump – 1 ft2
i. Low Suction Piping
OBSERVATION: The low suction line is provided with 4” threaded piping. Threaded piping is not recommended for piping larger than 2”.
CODE REFERENCE: UFC 3-460-01, 7-5.2 (a)
RECOMMENDATION: Replace 1 linear foot of threaded piping located on the 4” low suction line.
j. Water Draw-Off Line
OBSERVATION: The water draw-off line is provided with a ball valve at the skin location. Ball valves may not provide adequate isolation during maintenance and inspection operations.
CODE REFERENCE: UFC 3-460-01, Table 8-1 (Z)
RECOMMENDATION: Replace 1” ball valve with a 1” DB&B valve on the water draw-off line.
k. Internal Shell-to-Bottom Weld
OBSERVATION: Coating along the shell-to-bottom weld displayed cracking and disbondment.
CODE REFERENCE: UFC 3-460-03, Section 8-3.2
RECOMMENDATION: Recoat 100 ft2 (100%) of internal shell-to-bottom weld.
l. Sight Flow Indicators
OBSERVATION: Sight flow indicators are located in crossover piping for the main suction and receipt line. Sight flow indicators are no longer used in this application as they present potential leak paths.
CODE REFERENCE: UFC 3-460-01 9-3.5.1
RECOMMENDATION: Remove two (2) sight flow indicators located in the crossover piping provided for the receipt and main suction lines.
m. HLA, HHLA, HLCV, LLA, and LLLA
OBSERVATION: Piping provided for the HLA, HHLA, HLCV, LLA, and LLLA and provided with threaded connections.
CODE REFERENCE: UFC 3-460-01, 7-5.2 (b)
RECOMMENDATION: Either replace the HLA, HHLA, HLCV, LLA, and LLLA piping with welded/flanged connections or seal weld existing threaded connections.
n. VITO Temperature/Water Probe
OBSERVATION: The VITO temperature/water probe shares a nozzle riser and stilling well with the Enraf ATG.
CODE REFERENCE: UFC 3-460-01, Table 8-1 (S) / DLA-E ATG Policy
RECOMMENDATION: Provide the VITO temperature/water probe with an 8” riser and 6” fully slotted stilling well as close to the center sump as feasible.
o. Enraf ATG Fasteners
OBSERVATION: Fasteners provided for the Enraf ATG flanges display coating failure and surface corrosion.
CODE REFERENCE: UFC 3-460-01, 9-8 (f)
RECOMMENDATION: Replace sixteen (16) corroded fasteners located in the Enraf ATG flange.
p. Main Suction Internal Piping
OBSERVATION: Internal piping provided for the main suction line does not turn down, and is not provided with an anti-vortex plate.
CODE REFERENCE: AW 78-24-27, D.08 (4)
RECOMMENDATION: Provide the 12” main suction line with a short radius elbow and anti-vortex plate.
q. Tell-Tale Hole
OBSERVATION: Tell-tale holes provided for nozzle reinforcement pads are opened to the atmosphere allowing water ingress, and place for insects nesting.
CODE REFERENCE: UFC 3-460-03, 8-9.13.4.1
RECOMMENDATION: Provide a heavy lithium grease to all nozzle reinforcement pad tell-tale holes to prevent water ingress.
r. Gauging Stilling Wells
OBSERVATION: Stilling wells provide for the Enraf ATG and manual gauging hatch are partially slotted, with slots only running up to initial 4 ft of the stilling well.
CODE REFERENCE: UFC 3-460-01, Table 8-1 (R)/(S) / DLA-E ATG Policy
RECOMMENDATION: Fully slot stilling wells provided for the manual gauging hatch and Enraf
ATG.
s. Anti-Rotation Cable
OBSERVATION: Two (2) anti-rotation cables are attached directly to the tank bottom via square corner attachments.
CODE REFERENCE: API 653 Figure 9-13
RECOMMENDATION: Provide two (2) circular bearing plates for both anti-rotation cables.
t. U-bolt
OBSERVATION: The main suction and low suction lines are not provided with U-bolts, used to limit lateral movement of the piping during regular operations.
CODE REFERENCE: AW 78-24-27, D.08 (6)
RECOMMENDATION: Provide one (1) stainless steel u-bolt restraint with loosened nuts for both the internal main suction and low suction line. Internal piping must be allowed to move vertically with the tank bottom.
u. Attached Stilling Wells
OBSERVATION: Stilling wells provided for the manual gauging hatch and Enraf ATG are attached directly to well guides. This attachment may cause severe damage to the tank bottom should the tank begin to settle.
CODE REFERENCE: AW 78-24-27, D.08 (6)
RECOMMENDATION: Rework stilling wells for the manual gauging hatch and Enraf ATG by removing welds attaching the stilling wells to well guides.
3. RECOMMENDED REPAIRS as Part of Regular Maintenance
Recommended repairs represent items that should be addressed in a timely manner in order to prevent future potential risks to system operators, equipment integrity, or the adjacent environment.
a. Conduit Support
OBSERVATION: Conduit supports provided for the HLCV and visible alarm conduit is stitch-welded. Crevice corrosion and staining was observed between the conduit-to-shell interfaces.
CODE REFERENCE: BMP
RECOMMENDATION: Provide sealant or fully weld eighteen (18) stitch-welded conduit supports provided for both the HLCV conduit and the visible alarm conduit.
b. Fill Height
OBSERVATION: A white label is placed on the Enraf ATG stating a fill height of 33’-0” while the strapping charts list the safe fill height as 34’-0”.
CODE REFERENCE: BMP
RECOMMENDATION: Correct safe fill limit shown on the Enraf ATG display.
c. Pipe Cap
OBSERVATION: Cap located on piping extruding from the Enraf ATG riser displays significant surface corrosion with noticeable metal loss.
CODE REFERENCE: BMP
RECOMMENDATION: Replace corroded cap located on the 1” pipe extruding from the Enraf ATG riser.
D. INSPECTION INTERVALS
Intervals between tank inspections (both internal and external) should be determined by the tank service history, corrosion rates, and regulatory requirements. Corrosion rates can only be determined when a comparison is made between measurements taken over an interval of time. In this case, corrosion rates were determined based on the assumed nominal thicknesses and actual thickness measurements taken during this inspection.
1. Routine In-service Inspection
Facility personnel shall perform a visual inspection of the tank exterior surfaces, containment, and associated piping. Gross defects, leaks, shell distortions, signs of settlement, and corrosion should all be monitored along with the foundation condition (including tank chime-to-foundation interface), coating, and appurtenances.
Interval: Monthly
2. External (In-Service) Inspection
An API certified inspector shall perform this inspection every five (5) years or RCA/4N years (where
RCA is the difference between the measured shell thickness and the minimum required thickness and N is the shell corrosion rate) whichever is less. This inspection includes inspection requirements of the routine in-service inspection as well as a visual inspection of the tank grounding system (shunts and cables) for damage.
Interval: Five (5) years; January 2023
3. Ultrasonic Thickness Inspection
An external UT inspection of the tank shell and roof (if applicable) shall be performed by an API certified inspector every fifteen (15) years or RCA/4N, whichever is less. The UT inspection may be performed in conjunction with the external inspection.
Interval: Fifteen (15) years; January 2033
4. Internal (Out-of-Service) Inspection
An API certified inspector shall perform the internal inspection every 20 years or ½ remaining life of the tank bottom, whichever is less. This inspection includes a visual inspection of the tank interior surfaces and associated piping and an evaluation of the tank bottom via NDT methods. Since UFC requires tank cleaning every ten (10) years, it is recommended to perform the next internal inspection at this date to further evaluate the shell-to-bottom weld.
Interval: Ten (10) years; January 2028
APPENDIX A: ENGINEERING CALCULATIONS AND DRAWINGS
21 3
8 9 10 11
12 13 14
NOTES:
1. REFER TO TABLE 1, "TANK BOTTOM PLATE ULTRASONIC
THICKNESS READINGS" IN APPENDIX A FOR INDIVIDUAL BOTTOM
PLATE UTT READINGS.
2. REFER TO TABLE 2, "TANK BOTTOM CRITICAL ZONE ULTRASONIC
THICKNESS READINGS" IN APPENDIX A FOR CIRCUMFERENTIAL
UTT READINGS.
3. REFER TO TABLE 6, "NOZZLES AND APPURTENANCES", IN
APPENDIX A FOR NOZZLE DATA.
C O
N T
R A
C T
N
O
F I L
E
N
A M
E
D W
N
B
Y
C K
D
B
Y
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F I L
E
N
U M
B E
R
S I Z
E
S U
B M
I T
T E
D
B
Y
P L
S
A
L E
P
L O
T
D
A T
E
D A
T E
M A
R K
D E
S C
R I P
T I O
N
D E
L I V
E R
Y
O
R D
E R
SHEET
IDENTIFICATION
D A
T E
A P
P R
SHEET OF
N T
S
N A
W
F
F
X
P a r k w a y
L a n e
S u i t e
P e a c h t r e e
C o r n e r s
G
A
P h o n e
F a x
J O
B
N
O
J G
C
K B
B
N A
TANK INFORMATION
TANK NO. (FACILITY NO.): 2 (3474)
MANUFACTURER: WITHERUP FABRICATION AND ERECTION, INC.
YEAR BUILT: 2005
TANK DIAMETER: 31'-0"
TANK HEIGHT: 41'-3"
MAX FILL CAPACITY: 5,000 BBLS
PRODUCT: JET-A (F-24)
PRODUCT SPECIFIC GRAVITY: 0.85
GPS COORDINATES: N 38° 48' 56.16"
W 76° 51' 28.67"
U S
A C
E
O M
A H
A
D
I S
T R
I C
T
J O
I N
T
B
A S
E
A
N D
R E
W S
M
A R
Y L
A N
D
A N
D R
E W
S
A
F B
T A
K
L
A Y
O U
T
N A
W
F
D
J R
D
ANTI-ROTATION
CABLE (TYP. 2)
LADDER
LOW SUCTION
(N7)
WATER
DRAW-OFF
(N9)
STRIKER PLATE FOR IFR
SUPPORT LEG (TYP. 6)
RECEIPT
(N10)
MAIN SUCTION
(N8)
MW2
MW1
PIPE SUPPORT
(TYP. 4)
ENRAF ATG
STILLING WELL
(N12)
MANUAL
GAUGING HATCH
STILLING WELL
(MW4)
SUMP DETAIL
0.499"
0.483" 0.498"
0.499"
0' 9"
0.483"
0.515"
0.484"
0.517"
0.483"
2' 5"
.XXX"
LEGEND
- UTT READING
- COATING FAILURE
B O
T T
M
Y
O U
T
PIPE SUPPORT
(TYP. 3)
Table 1: Tank Bottom Ultrasonic Thickness Readings
Plate 1 Plate 2 Plate 3 Plate 4 Plate 5
.306 .306 .316 .315 .307 .305 .309 .305 .302 .302
.303 .316 .304 .315 .303
.306 .305 .310 .316 .306 .305 .312 .315 .304 .302
Avg. .305 .315 .305 .311 .303
Plate 6 Plate 7 Plate 8 Plate 9 Plate 10
.309 .306 .303 .304 .301 .303 .302 .312 .310 .306
.311 .304 .305 .317 .304
.308 .309 .300 .301 .301 .303 .310 .313 .304 .307
Avg. .309 .302 .303 .311 .306
Plate 11 Plate 12 Plate 13 Plate 14
.306 .312 .299 .301 .311 .311 .304 .304
.317 .303 .313 .306
.316 .314 .305 .312 .314 .303 .306 .305
Avg. .313 .304 .310 .305 Thickness reading in inches.
Average tank bottom thickness reading: 0.307” Refer to Drawing 01, Bottom Layout, for plate layout.
Table 2: Tank Bottom Critical Zone Ultrasonic Thickness Readings
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32
.300 .306 .302 .307 .319 .323 .320 .313 .310 .299 .307 .311 .310 .309 .309 .309 .319
34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66
.319 .320 .309 .309 .310 .307 .309 .312 .303 .306 .300 .303 .316 .319 .314 .316 .317
68 70 72 74 76 78 80 82 84 86 88 90 92 94 96
.306 .311 .309 .308 .304 .302 .313 .315 .314 .318 .311 .306 .309 .306 .301
Thickness readings are in inches.
Average tank bottom critical zone plate thickness reading: 0.310” Refer to Drawing 01, Bottom Layout, for plate layout and UTT reading locations.
0’ = directly below manway opening.
Thickness readings were taken within 3” of the shell-to-bottom weld proceeding clockwise around the tank.
STORAGE TANK FLOOR EVALUATION
Date 01/31/2018
MINIMUM REMAINING THICKNESS (MRT) CALCULATIONS
File No Report No Client Inspector Tank No Temp (degF)
Andrews AFB Tank 2
(3474) USACE Omaha
John Cronin
(POND)
Tank 2 (3474)
Liner CP Protec 50mil Liner RPB Ca Shell tmin
Shell tnom D H
Yes Yes No N/A 0.188 0.101 0.250 31.000 37.583
Where;
Ca = corrosion allowance, in (inch).
MRT = minimum remaining thickness at the end of interval Or. This value must meet the requirements of Table 4-1 and sections 2.4.7.4 and 2.4.8.
Or = In-service interval of operation (years to next internal inspection) not to exceed that allowed by 4.4.2.
RTbc = minimum remaining thickness from bottom side corrosion after repairs.
RTip = minimum remaining thickness from internal corrosion after repairs.
StPr = maximum rate of corrosion not repaired on the top side. StPr = 0 for coated areas of the bottom.
The expected life of the must equal or exceed Or to use StPr = 0.
tmin = minimum allowable thickness in accordance with requirements of Table 4-1 and sections 2.4.7.4 and 2.4.8.
to = bottom plate original thickness.
UPr = maximum rate of corrosion on the bottom side. To calculate the corrosion rate, use the minimum remaining thickness after repairs. Assume a linear rate based on the age of the tanks. UPr = 0 for areas that have effec D = nominal diameter of tank, in (ft), H =Height, in (ft), from the bottom of the 1st shell course to the maximum allowable fill height S=Stresses are calculated from 2.6(H-1)DG/SE.
GENERAL PLATES-AFTER INSPECTION / REPAIRS
Age to RTbc RTip UPr StPr Or MRT tmin Results
13 0.313 0.307 0.307 0.00000 0.00000 20 0.307 0.100 ACCEPTABLE
PLATES IN CRITICAL ZONE (3") - AFTER INSPECTION / REPAIRS
Age to RTbc RTip UPr StPr Or MRT tmin Results
13 0.313 0.310 0.310 0.00000 0.00000 20 0.310 0.100 ACCEPTABLE
croninj Typewritten Text Nominal thickness was assumed to be 0.3125" (5/16").
API-653 APPENDIX B SHELL SETTLEMENT EVALUATION
(para. B.2.2.4)
Report No Client Inspector Vessel Date Andrews AFB Tank
2 (3474) USACE Omaha John Cronin (POND) Tank 2 (3474) 02/06/2018
Base Elev Max Elev Elev
FT 0.458 0.479 0.021 R^2 = 0.960
IN 5.496 5.748 0.252
API-653 APPENDIX B SHELL SETTLEMENT EVALUATION
Report No.: Andrews AFB Tank 2 (3474)
D H Roof Type L 1st Crs Plt Spec Y E
31 41.3 F 9.74 A 36 36000 29000000
Where:
D = Tank Diameter, in ft H = Tank Height, in ft Roof Type: F = fixed, O = Open L = Arc length between measurement points, in ft (32' max) (greatest dist. allowed based on even # of points) Y = Yield strength of shell 1st course , in pounds per Sq.Inch (psi) E - Young's modulus, in pounds per Sq.Inch (psi)
= Angle theta at elevation point, in degrees PE = Predicted elevation, in ft Ui = Measured out-of-plane settlement in relation to a cosine curve, in ft Si = Deflection, in ft, (out-of-plane distortion) Smax = Maximum allowed deflection, in ft, (out-of-plane distortion)
Smax =((L^2*Y*11)/2*(E*H)) = 0.016
Point Elevation PE Ui Si Results
1 0.458 0 0.460 -0.002 0.002 SAT
2 0.458 36 0.465 -0.007 -0.005 SAT
3 0.469 72 0.472 -0.003 0.000 SAT
4 0.479 108 0.477 0.002 0.003 SAT
5 0.479 144 0.479 0.000 -0.002 SAT
6 0.479 180 0.477 0.002 0.003 SAT
7 0.469 216 0.472 -0.003 0.000 SAT
8 0.458 252 0.465 -0.007 -0.005 SAT
9 0.458 288 0.460 -0.002 0.002 SAT
10 0.458 324 0.458 0.000 0.002 SAT
Table 3: Tank Bottom Elevation Measurements
Point Arc Length (ft.) 0'-2" 10'-0" 15'-0"
1 0.00 .458 1.083 1.271
2 9.74 .458 1.042 1.271
3 19.48 .469 1.000 1.271
4 29.22 .479 .948 1.271
5 38.96 .479 1.052 1.260
6 48.69 .479 1.063 1.271
7 58.43 .469 1.010 1.271
8 68.17 .458 .854 1.271
9 77.91 .458 OBS 1.271
10 87.65 .458 1.000 1.271
Point 1 is located at Manway 1 and subsequent points are measured clockwise circumferentially every 9.74’.
8'-0"
8'-0"
8'-0"
8'-0"
9'-3"
5-1 5-2 5-3 5-4
4-1 4-2 4-3 4-4
3-1 3-2 3-3 3-4
2-1 2-2 2-3 2-4
1-1 1-2 1-3 1-4 1-5
NOTES:
1. REFER TO TABLE 5, "SHELL PLATE ULTRASONIC THICKNESS READINGS", IN APPENDIX A FOR
INDIVIDUAL SHELL PLATE UTT READINGS.
2. REFER TO TABLE 6, "NOZZLES AND APPURTENANCES", IN APPENDIX A FOR NOZZLE DATA.
C O
N T
R A
F I L
E
N
A M
E
D W
N
B
Y
C K
D
B
Y
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F I L
E
N
U M
B E
R
S I Z
E
S U
B M
I T
T E
D
B
Y
P L
S
A
L E
P
L O
T
D
A T
E
D A
T E
M A
R K
D E
S C
R I P
T I O
N
D E
L I V
E R
Y
O
R D
E R
SHEET
IDENTIFICATION
D A
T E
A P
P R
SHEET OF
N T
S
N A
W
F
F
P a r k w a y
L a n e
S u i t e
P e a c h t r e e
C o r n e r s
G
A
P h o n e
F a x
J O
B
N
O
J G
C
K B
B
N A
TANK INFORMATION
TANK NO. (FACILITY NO.): 2 (3474)
MANUFACTURER: WITHERUP FABRICATION AND ERECTION, INC.
YEAR BUILT: 2005
TANK DIAMETER: 31'-0"
TANK HEIGHT: 41'-3"
MAX FILL CAPACITY: 5,000 BBLS
PRODUCT: JET-A (F-24)
PRODUCT SPECIFIC GRAVITY: 0.85
GPS COORDINATES: N 38° 48' 56.16"
W 76° 51' 28.67"
U S
A C
E
O M
A H
A
D
I S
T R
I C
T
J O
I N
T
B
A S
E
A
N D
R E
W S
M
A R
Y L
A N
D
A N
D R
E W
S
A
F B
T A
K
Y
O U
T
N A
W
F
D
J R
D
N5
N6
N1
N2
N3
N4
MW1
S H
E L
L
R
O L
L O
U T
MW2
N7
N8
N9
N10
MW3
CONDUIT SUPPORT
(TYP. 6)
CONDUIT SUPPORT (TYP. 8)
CONDUIT SUPPORT (TYP. 14)
TAPE LEVEL GAUGE SUPPORT (TYP. 4)
SPIRAL
STAIRCASE
(TYP.)
GROUNDING CABLE
(TYP. 4)
PERIMETER HANDRAIL
TANK FOUNDATION
OVERFLOW PORT
(TYP.4)
Table 4: Shell Plate Ultrasonic Thickness Readings
Roof
Shell Course
Plate 5-1 Plate 5-2 Plate 5-3 Plate 5-4
.277 .266 .280
.269 .265 .275 N/A N/A N/A
.267 .261 .278
Avg. .271
Circumferential Weld C5
Shell Course
Plate 4-1 Plate 4-2 Plate 4-3 Plate 4-4
.284 .285 .309
.288 .295 .288 N/A N/A N/A
.294 .274 .300
Avg. .291
Circumferential Weld C4
Shell Course
Plate 3-1 Plate 3-2 Plate 3-3 Plate 3-4
.304 .270 .277
.286 .271 .283 N/A N/A N/A
.284 .271 .302
Avg. .266
Circumferential Weld C3
Shell Course
Plate 2-1 Plate 2-2 Plate 2-3 Plate 2-4
.274 .285 .297
N/A N/A N/A .270 .284 .285
.269 .278 .285
Avg. .281
Circumferential Weld C2
Shell Course
Plate 1-1 Plate 1-2 Plate 1-3 Plate 1-4 Plate 1-5
.276 .284 .288 .286 .296 .310 .306 .309 .276 .288 .310 .279 .288 .292 .280
.285 .283 .282 .282 .283 .308 .305 .321 .287 .289 .297 .278 .274 .284 .277
.281 .280 .279 .290 .279 .285 .298 .317 .271 .296 .281 .275 .275 .298 .276
Avg. .282 .291 .299 .288 .283
Circumferential Weld C1
Thickness readings are in inches.
Shell Course 1 Average: 0.289” Shell Course 2 Average: 0.281” Shell Course 3 Average: 0.266” Shell Course 4 Average: 0.291” Shell Course 5 Average: 0.271” Refer to Drawing 02, Shell Rollout, for shell layout.
SHELL MINIMUM THICKNESS CALCULATIONS
Tank Shell Minimum Thickness and Remaining Life Calculations Date 02/06/2018
File No. Report No. Client Tank No. Temp. (degF) Initials
1908 Andrews AFB Tank 2 (3474)
USACE Omaha Tank 2 (3474) John Cron tmin = 2.6(H-1)DG
SE
Where:
H = The height above the bottom of the course of study to the maximum liquid level height of the product, in ft. For corroded or pitted areas, H = the height from the bottom of the corroded or pitted area to the maximum liquid level height of the product, in ft.
tmin = The calculated minimum acceptable shell thickness, in inch (cannot be less than
0.10 inch for any course). The minimum acceptable shell thickness allowed by API-653 and STI-SP001 for tank size, in inch .
D = Nominal diameter of tank, in ft.
G = Highest specific gravity of the contents (including test water if tank will, or may, be tested in the future).
S = Maximum allowable stress, in psi. For welded tanks; use the smaller of 0.80Y of 0.429T for bottom and second course or the smaller of 0.88Y or 0.472T for all other courses. For riveted tanks; S = 21000 psi. For STI Tank Inspections S = 26000 psi (E = 1)
Y = Specified minimum yield strength of the plate, in psi; use 30000 psi if not known (N/A for riveted tanks).
T = The smaller of the specified minimum tensile strength of the plate or 80000 psi; use 55000 psi if not known (N/A for riveted tanks).
E = Original joint efficiency for the tank. For welded tanks; use API-653, Table 2-1 ; use E =
1.0 when evaluating the retirement thickness in a corroded plate, when away from welds or joints by at least the greater of one inch or twice the plate thickness. For riveted tanks; use E = 1.0 for shell plates greater than 1 inch away from rivets; use the value of E from API- 653 Table 2-1 when within 1 inch of rivets. For STI Tank Inspections E = 1 where S = 26000 psi.
D (ft) 31 G 0.85 E 1.00 Fill Height (ft) 37.6
Material Crs H (ft) H (ft) S (psi) tmin (inch) Course 1 A 36 9.25 37.6 24900 0.101 Course 2 A 36 8 28.3 24900 0.100 Course 3 A 36 8 20.3 27400 0.100 Course 4 A 36 8 12.3 27400 0.100 Course 5 A 36 8 4.3 27400 0.100
SHELL REMAINING LIFE CALCULATIONS
Tank Shell Minimum Thickness and Remaining Life Calculations Date 02/06/2018
File No. Report No. Client Tank No. Temp. (degF) Initials
1908 Andrews AFB Tank 2 (3474)
USACE Omaha Tank 2 (3474) John Cron
Ca = tact-tmin = Remaining Corrosion Allowance (inch) Cr = tprev-tact / Y = Corrosion Rate (inch/Yr) RL = Ca / Cr = Remaining Life (year)
Y = 13 = Tank age (year)
Where:
Ca = Remaining corrosion allowance of the shell course under consideration, in inch.
Cr = Corrosion rate of the shell course under consideration, in inch per year.
FHc = Calculated fill Height = (SEtact/2.6DG+1) + (product height below course of interest), in ft.
tact = Minimum thickness measurement of the shell course under consideration, as recorded at the time of inspection, in inch.
tmin = minimum required thickness of shell course, at the maximum allowable fill height, in inch.
tprev = previous thickness measurement of shell course under consideration, as recorded at last inspection or nominal thickness if no previous thickness measurements, in inch.
RL = Estimated remaining life of the shell course under consideration, in year.
Y = Time span between thickness readings or age of the tank if nominal thickness is used for tprev, in year.
tprev tact tmin Ca Cr RL FHc Course 1 0.250 0.289 0.101 0.188 0.0000 >40 106.04 Course 2 0.250 0.281 0.100 0.181 0.0000 >40 112.38 Course 3 0.250 0.266 0.100 0.166 0.0000 >40 124.63 Course 4 0.250 0.291 0.100 0.191 0.0000 >40 142.63 Course 5 0.250 0.271 0.100 0.171 0.0000 >40 142.63
1ST SHELL COURSE (0'-3"):
16'-2"
MW2
1ST SHELL COURSE (3'-0"):
1ST SHELL COURSE (6'-0"):
30'-11
30'-11
30'-11
MW1
30'-10
31'-
30'-11
MW2
MW1
MW2
MW1
30'-10
30'-11
30'-11
Table 5: Fixed Roof Ultrasonic Thickness Readings
Plate 1 Plate 2 Plate 3 Plate 4 Plate 5
.295 .293 .288 .275 .298 .298 .294 .288 .289 .286
.300 .274 .297 .288 .301
.294 .284 .271 .281 .291 .295 .282 .292 .297 .283
Avg. .293 .278 .296 .289 .291
Plate 6 Plate 7 Plate 8 Plate 9 Plate 10
.293 .308 .305 .289 .281 .304 OBS OBS .290 .291
.286 .299 .297 OBS .300
.286 .298 .291 .285 .298 .291 OBS OBS .281 .293
Avg. .294 .294 .294 .291 Thickness readings are in inches.
Average fixed roof plate thickness reading: 0.291”
OBS - Obstructed
Refer to Drawing 03, Fixed Roof Layout, for fixed roof layout and UTT reading locations.
AST ATMOSPHERIC STORAGE TANK FIXED ROOF EVALUATION
MINIMUM THICKNESS, REMAINING LIFE, PRESSURE CALCULATIONS
Date 02/06/2018
File No Report No Client Inspector Tank No Temp(degF)
Andrews AFB Tank 2
(3474) USACE Omaha John Cronin (POND) Tank 2 (3474)
Where;
Ca = remaining corrosion allowance of the tank component under consideration, in inch (t act - t min).
Cr = corrosion rate of the tank component under consideration, in inch per year (t prev - t act / Y).
oz = unit of measurement, (weight, in ounces, per square inch), (16 oz per pound) psi = unit of measurement, (weight, in pounds, per square inch) RL = estimated remaining life of the tank component under consideration, in year (Ca / Cr).
t act = actual thickness measurement of the tank component under consideration, as recorded at the time of inspection, in inch.
t min = minimum required thickness of tank component, at the design MAWP at the design temperature (200 degF for atm AST's), in inch (greater of psi/wt or 0.090").
t nom = design nominal thickness of tank component under consideration, in inch.
t prev = previous thickness measurement of the tank component under consideration, as recorded at last inspection or nominal thickness if no previous thickness measurements, in inch.
t yn = thickness of the tank component under consideration at the next inspection at twice the calculated corrosion rate, in inch (t act - (2*Cr*Yn).
wt = weight of plate per cubic inch.
wc = unit of measurement, (height, in inch, of water column bearing on 1 Sq.Inch area), (27.7 wc per pound) Y = time span between thickness readings or age of the tank component if tnom is used for tprev, in year.
Yn = estimated time span to next inspection of the tank component under consideration, in year.
ROOF PLATES - REMAINING LIFE
Y t prev (inch) t act (inch) t min (inch) Cr (inch/Yr) Ca (inch) RL
13 0.313 0.291 0.090 0.00169 0.201 119 croninj Typewritten Text Nominal thickness was assumed to be 0.3125" (5/16").
Table 6: Nozzle and Appurtenances
Nozzle Nozzle Size
(Diameter or Width/Height)
Repad Shape
RepadSize (W X H)
Repad Thickness
Nozzle Thickness
H1 H2
Nozzle Location (Measured circumferentially from Manway A)
Notes 0° 90° 180° 270°
MW1 36" B 6'-0" .298 .425 .413 .410 - 3'-3" 0'-6" 0' Manway
N1 1 1/2" - - - TH TH TH TH 39'-10" - 9'-6" HHLA
N2 1 1/2" - - - TH TH TH TH 36'-1" - 9'-6" HLA
N3 1 1/2" - - - TH TH TH TH 39'-4" - 12'-9" HLCV Shutoff
N4 1 1/2" - - - TH TH TH TH 37'-8" - 12'-9" HLCV Shutoff
N5 1 1/2" - - - TH TH TH TH 3'-0" - 12'-9" LLA
N6 1 1/2" - - - TH TH TH TH 1'-6" - 12'-9" LLLA
MW2 36" B 6'-0" .261 .410 .412 .390 .408 3'-8" 0'-6" 49'-0" Manway
N7 4" B 1'-0" .273 .303 .329 .313 .323 0'-10" 0'-4" 61'-3" Low Suction
N8 12" B 2'-2" .275 .532 .526 .515 .535 1'-5" 0'-5" 65'-1" Main Suction
MW3 36" B 6'-0" .283 .419 .399 .394 .399 9'-4" 6'-4" 79'-0" Manway
N9 1 1/2" - - - .251 - - - 0'-6" - 87'-0" Water Draw-Off
N10 8" B 1'-7" .271 .530 .498 .533 - 1'-6" 0'-9" 89'-7" Receipt
N11 2 1/2" - - - TH TH TH TH Fixed Roof Anti-Rotation Cable
MW4 36" B 4'-6" .273 .265 .242 .255 .257 Fixed Roof Manway w/ 8" Gauge Hatch
N12 6" B 1'-3" .290 .267 .273 .289 .262 Fixed Roof Enraf ATG / VITO Temp/Water Probe
N13 72" x 24" - - - .414 .435 .403 .424 Fixed Roof Hatch
N14 2 1/2" - - - TH TH TH TH Fixed Roof Pan Ground
N15 4" B 0'-9" .372 .267 .270 .278 .276 Fixed Roof Cap
N16 24" B 2'-9" .235 .276 .283 .280 .296 Fixed Roof Center Vent
N17 2 1/2" - - - TH TH TH TH Fixed Roof Pan Ground
N18 2 1/2" - - - TH TH TH TH Fixed Roof Anti-Rotation Cable
N19 1 1/2" - - - TH TH TH TH Fixed Roof Shand and Jurs Tape Level Gauge
Thickness measurements are in inches.
H1 = C/L of pipe to edge of roof or chime H2 = Edge of tank or chime to nearest weld toe.
TH = Threaded Repad Shapes:
Table 7: Dry Film (Coating) Thickness
External Shell Coating Thickness
Average Standard Deviation Number of Readings Minimum Maximum
12.380 2.879 23 8.169 20.000
Internal Shell Coating Thickness
27.450 5.998 14 18.700 36.950
Bottom Coating Thickness
16.270 4.130 15 9.624 24.970
Fixed Roof Coating Thickness
15.200 3.546 13 12.330 23.860
Readings are represented in mils.
APPENDIX B: API 653 CHECKLISTS FOR TANK INSPECTIONS
Tank In-Service Inspection Checklist
Item Completed
X
B.1.1 Foundation a Measure foundation levelness and bottom elevations (see Annex B for extent of measurements).
X
B.1.1.1 Concrete Ring a Inspect for broken concrete, spalling, and cracks, particularly under backup bars used in welding butt-welded annular rings under the shell.
X b Inspect drain openings in ring, back of waterdraw basins and top surface of ring for indications of bottom leakage.
X c Inspect for cavities under foundation and vegetation against bottom of tank. X d Check that runoff rainwater from the shell drains away from tank. X e Check for settlement around perimeter of tank. X
B.1.1.2 Asphalt a Check for settling of tank into asphalt base which would direct runoff rain water under the tank instead of away from it.
N/A b Look for areas where leaching of oil has left rock filler exposed, which indicates hydrocarbon leakage.
N/A
B.1.1.3 Oiled Dirt or Sand a Check for settlement into the base which would direct runoff rain water under the tank rather than away from it.
N/A
B.1.1.4 Rock a
Presence of crushed rock under the steel bottom usually results in severe underside corrosion. Make a note to do additional bottom plate examination (ultrasonic, hammer testing, or turning of coupons) when the tank is out of service.
N/A
B.1.1.5 Site Drainage a Check site for drainage away from the tank and associated piping and manifolds. X b Check operating condition of the dike drains. X
B.1.1.6 Housekeeping a Inspect the area for buildup of trash, vegetation, and other inflammables buildup. X
B.1.1.7 Cathodic Protection a Review cathodic protection potential readings. X
B.1.2 Shells
B.1.2.1 External Visual Inspection a Visually inspect for paint failures, pitting, and corrosion. X
Item Completed
X b Clean off the bottom angle area and inspect for corrosion and thinning on plate and weld.
X c Inspect the bottom-to-foundation seal, if any. X
B.1.2.2 Internal (Floating Roof Tank) a Visually inspect for grooving, corrosion, pitting, and coating failures. N/A
B.1.2.3 Riveted Shell Inspection a Inspect external surface for rivet and seam…