Attachment J.1 Fac 3035 - Insp Report - Apr 2019.pdf
PDF 2 MB Posted
- Attached to
- POL Tank Inspection - ADR - JB Andrews
- Solicitation number
- W9128F23Q0015
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Transmittal/Review/Approval DATE
TITLE Fill in Project Title/Location HereCONTRACT NO
TO SUBMITTAL NO. PEC SECTION
FILE NAME
FROM (CONTRACTOR)
Add Del
ENCL.
NO.
NO. OF
COPIES
DESCRIPTION ARA SCHEDULE ACTIVITY NO. CQC CODE
DATE NEEDED BY:
TRANSMITTED FOR: CLARIFICATION VARIANCESELECTION RECORDAPPROVAL
SIGNATURE:
FROM:
SIGNATURE:
For review/comment ( ) copies of enclosures forwarded. RETURN WITHIN ( ) WORKING DAYS, unless submittal is for record/info purposes only and there are no adverse comments.
DATE:
TO:
Received By (Print Name & Sign) /Date/Time:
Received By (Print Name & Sign) /Date/Time:
CONTRACTOR'S REPRESENTATIVE NAME/TITLE
TO:FROM:
DATE:
RECOMMEND:
APPROVAL/ACCEPTANCE, subject to contract requirements
APPROVAL/ACCEPTANCE, as noted, subject to contract requirements
RETURN for correction and resubmission
DISAPPROVAL
REVIEWED AND PROCEED
REMARKS:
copies of encls retained
SIGNATURE:
Received By (Print Name & Sign) /Date/Time:
FROM: TO (CONTRACTOR) / ATTENTION:
DATE:
Enclosure(s) is (are):
APPROVED/ACCEPTED, subject to contract requirements
APPROVED/ACCEPTED, as noted, subject to contract requirements
RETURNED for correction and resubmission
DISAPPROVED
NOT REVIEWED
RECEIVED FOR RECORD
REMARKS:
BY DIRECTION OF THE CONTRACTING OFFICER
SIGNATURE
Copy to: Contract File (w/encls) ConRep/ET (w/encls) CME (w/encls) copies of encls returned
Received By (Print Name & Sign) /Date/Time:
File Name:
Attachment
JB Andrews Tank 10 Final Inspection Report 08/09/2019
W9128F-17-D-0021 / TO W9128F18F0327 SPCC Aboveground Storage Tank Inspections ADR, MRT, NGH, WST
EEI USACE 015 N/A
1 1 JB Andrews Tank 10 Final Inspection Report Attachment D 60
James Hall, Project Manager
1 10
US Army Corps of Engineers Omaha District
API 653 In-Service Inspection Report
Joint Base Andrews, Maryland Facility No. 3035
Tank No. 10
US Army Corps of Engineers Center of Expertise for Petroleum, Oils and Lubricants
(USACE POL-MCX)
August 2019
API 653 In-Service Inspection Report Joint Base Andrews, MD
Table of Contents
ACRONYMS AND ABBREVIATIONS
GENERAL SUMMARY
INSPECTION DATE
STATE REGULATIONS
PREVIOUS INSPECTION DATES
RECOMMENDED FUTURE INSPECTION DATES (CALCULATIONS SHALL BE PROVIDED)
GENERAL TANK INFORMATION
A. GENERAL PROJECT INFORMATION
1. API 653 Inspection
2. Site Information
B. TANK INSPECTION COMMENTS
1. Tank Construction
2. Tank Evaluation Items
C. FINDINGS AND RECOMMENDATIONS
1. MANDATORY REPAIRS per API 653, UFC 3-460-01, or AW 78-24-27 Standards
2. REQUIRED REPAIRS to Fully Comply with API 653, UFC 3-460-01, or AW 78-24-27 Standards
3. RECOMMENDED REPAIRS as Part of Regular Maintenance Long-Term Repairs
APPENDIX A: ENGINEERING CALCULATIONS AND DRAWINGS
NDE DATA
ENGINEERING CALCULATIONS TANK DRAWING
OSHA ACCESS STRUCTURE REPORT
APPENDIX B: API 653 CHECKLISTS FOR TANK INSPECTIONS
APPENDIX C: PHOTOGRAPHS
ACRONYMS AND ABBREVIATIONS
API American Petroleum Institute
ASME American Society of Mechanical Engineers
ASNT American Society of Non-Destructive Testing
ATG Automatic Tank Gauge
BBL Barrel
CFR Code of Federal Regulations
CP Cathodic Protection
DFT Dry Film Thickness
HLA High Level Alarm
HLCS High Level Control Shutoff
HHLA High-High Level Alarm
LLA Low Level Alarm
LLLA Low-Low Level Alarm
MFL Magnetic Flux Leakage
MT Magnetic Particle Testing
NACE National Association of Corrosion Engineers
NDT Non-Destructive Testing
NFPA National Fire Protection Association
PSI Pounds per Square Inch
PT Penetrant Testing
P/V Pressure/Vacuum
RP Recommended Practice
PST Product Saver Tank
RT Radiography Testing
TML Thickness Measurement Location
TRV Thermal Relief Valve
UFC Unified Facilities Criteria
UFGS Unified Facilities Guide Specifications
ULS Ultra Low Sulfur
UT Ultrasonic Testing
VT Visual Testing
GENERAL SUMMARY
Enterprise Engineering Inc. (EEI) was retained by the United States Army Corps of Engineers (USACE), Omaha District, under Contract No. W9128F-17-D-0021 Delivery Order W9128F18F0327 to perform an in-service (IS) API 653 inspection of Tank 10 (Facility 3035) at Joint Base Andrews, Maryland.
The IS API 653 inspection was performed during April 29 to 30 2019 in accordance with the applicable portions of API Standard 653, UFC 3-460-01, UFC 3-460-03 and the Statement of Work (SOW).
Tank 10 is a field erected, vertical, aboveground storage tank. The tank was constructed in 1960. The nominal tank diameter is 42.5 feet and the shell height is 38 feet. The tank is of welded construction with butt-welded shell plates and lap-welded floor plates. The tank has a self-supported steel shed roof and an internal steel floating roof.
The nominal shell capacity is 10,000 Bbls. The tank is currently in Jet Fuel A (F-24) service. The tank name plate indicates tank repairs were performed in 2004 by Totltest, Inc. to provide a second bottom.
This inspection has determined that no mandatory repairs are required.
INSPECTION DATE
API In-Service (External) Inspection Date: 29 to 30 April 2019
Equipment Used:
Manufacturer: Olympus Model Number: 38DL Plus Calibration Method: 2-point calibration using a single material standard
Manufacturer: Positector Dry Film Thickness (DFT) Gauge Model Number: 6000 Calibration Method: Calibration to know thickness standard
Inspector(s):
James E. Hall, P.E.
Matthew C. McGowan Sierra C. Kuun
STATE REGULATIONS
State Regulation for API In-Service Tank Inspections N/A State Regulation for API Out-of-Service Tank Inspections N/A
Maryland does not regulate inspection of aboveground storage tanks.
PREVIOUS INSPECTION DATES
API Out-of-Service (Internal) Inspection Date: June 2014 (including floor scan) API In-Service (External) Inspection Date: 2004
RECOMMENDED FUTURE INSPECTION DATES (CALCULATIONS SHALL BE PROVIDED)
API Out-of-Service (Internal) Inspection Date: June 2034 (Taken from 2014 Inspection Report) API In-Service (External) Inspection Date: April 2024 (5 Years)
James E. Hall, P.E.
Project Manager Enterprise Engineering Inc.
API 653 Certified Inspector No. 46418
GENERAL TANK INFORMATION
ITEM DESCRIPTION
Owner U.S. Air Force Location Joint Base Andrews Facility Number 3035 Tank Number 10 State / Country Maryland / United States City Camp Springs Inspection Date 29 to 30 April 2019 Tank Manufacturer Unknown Design Standard API Standard 12C Date of Construction 1960 Tank Contents Jet A (F-24) Tank Serial Number None present Tank Diameter 42’-6” Shell Height 38’-10” Product Height 35’-11” Tank Capacity 10,000 BBLS (Nominal) / 9,788 BBLS (Gross) Foundation Concrete Ringwall
Construction
Bottom Lap welded Shell Butt-welded / 6 courses Floating Roof Lap welded Fixed Roof Steel shed roof
Material
Bottom Steel / Unknown grade Shell Steel / Unknown grade Floating Roof Steel / Unknown grade Fixed Roof Steel / Unknown grade
Cathodic Protection Impressed
Interior Coating System Floor: Thin-film epoxy Shell: Thin-film epoxy Roof: Thin-film epoxy
Exterior Coating System Shell: Thin-film epoxy Roof: Thin-film epoxy
Level Gauging Varec tape gauge system ENRAF ATG system
Overfill Protection High level shut off valve on Fill piping Piping Receipt 6-inch Carbon steel Issue 10-inch Carbon steel Low Suction 4-inch Carbon steel
Water Draw-Off Two 2-inch drain in shell Carbon steel
Level Alarms Scully high-high, high, low and low-low level alarms; ENRAF ATG alarms Type of Internal Floating Roof Lap welded
A. GENERAL PROJECT INFORMATION
1. API 653 Inspection EEI performed an IS API 653 inspection on Tank 10 (Facility 3035) 29 to 30 April 2019. Results of this inspection identified required repairs to comply with API 650, API 653, UFC 3-460-01, UFC 3-460-03, AW 78-24-27 and industry standards and recommended repairs as part of regular maintenance.
2. Site Information Joint Base Andrews is located in Maryland. The base is home to Air Force District of Washington's 11th Wing -- the base's host wing -- with several partner units on base including Air Mobility Command's 89th Airlift Wing, Air Force Reserve Command's 459th Air Refueling Wing, D.C. Air National Guard's 113th Wing, the Naval Air Facility, and Army and Marine Corps detachments.
B. TANK INSPECTION COMMENTS
1. Tank Construction Tank 10 (Facility 3035) is a field erected, vertical, aboveground storage tank. The tank was constructed in 1960. The nominal tank diameter is 42 feet 6 inches and the shell height is 38 feet 10 inches. The tank is of welded construction with butt-welded shell and lap welded floor plates. The tank has a self-supported steel shed roof and an internal steel floating roof. The nominal shell capacity is 10,000 Bbls.
The design liquid level is 35-feet 11-inches. The tank is currently in Jet A service.
2. Tank Evaluation Items Refer to Appendix A for a discussion of the tank evaluation items. The information has been provided in a tabular format for reference.
C. FINDINGS AND RECOMMENDATIONS
The following subsections outline the tank repairs/upgrades. Repairs and upgrades shall be completed in accordance with API requirements and best engineering practice.
1. MANDATORY REPAIRS per API 653, UFC 3-460-01, or AW 78-24-27 Standards Mandatory repairs represent items that require immediate attention, in order to prevent imminent risk to system operators, equipment integrity, or the adjacent environment. The tank should remain out of service until these repairs are completed.
No mandatory repairs were identified.
2. REQUIRED REPAIRS to Fully Comply with API 653, UFC 3-460-01, or AW 78-24-27 Standards Short-term Repairs that directly relate to the long-term preservation of the asset. Short-term repairs represent items that should be addressed in a timely manner in order to prevent future potential risks to system operators, equipment integrity, or the adjacent environment. These items may be required by Federal, State and Local Codes or by Military Criteria.
a. Tank Handrail OBSERVATION: A section of platform handrail at the top of the spiral stairs has been removed and sections of Unistrut are bolted in its place.
REFERENCE: OSHA 29 CFR 1910
RECOMMENDATION: Remove sections of Unistrut and provide top and mid rails to match existing handrail.
b. Tank Labelling OBSERVATION: The tank product stenciling is failing.
REFERENCE: AW 78-24-27 Sheet D.13, Detail 3
RECOMMENDATION: Remove failed stenciling and provide stenciling in accordance with MIL-STD 161G.
c. Manway Covers OBSERVATION: The tank manway covers are not equipped with davits.
REFERENCE: AW 78-24-27 Sheet D.10, Detail 3
RECOMMENDATION: Remove manway hinges and provide davits in accordance with AW 78-24-27.
3. RECOMMENDED REPAIRS as Part of Regular Maintenance Long-Term Repairs Long-term Repairs that directly relate to repair/upgrade of an asset to bring it up to the current standard from the standard at time of construction. Long-term Repairs represent items that should be addressed in a timely manner in order to prevent future potential risks to system operators, equipment integrity, or the adjacent environment.
a. Exterior Coating Failure OBSERVATION: Coating failure and corrosion was observed on the tank valves, flanges, stair platform framing and appurtenances.
REFERENCE: UFC 3-460-03 ¶8-3.1
RECOMMENDATION: Provide surface preparation and recoat.
b. Coating failure on Piping OBSERVATION: Coating failure and corrosion was observed on the fill and issue piping and pipe supports within the containment dike.
REFERENCE: UFC 3-460-03 ¶8-3.1
RECOMMENDATION: Provide surface preparation and recoat. Approximately 200 LF of 10-inch piping, 175 LF of 6-inch piping, and 24 pipe supports.
c. Organic growth OBSERVATION: Organic growth was observed on the exterior shell and exterior piping.
REFERENCE: UFC 3-460-03 ¶8-3.1
RECOMMENDATION: Pressure wash the tank shell and piping.
d. Secondary Containment Sealant OBSERVATION: The tank is located within a concrete containment area. Locations of unsealed cracks were observed at isolated locations.
REFERENCE: UFC 3-460-03, ¶8-10.2
RECOMMENDATION: Repair cracks by routing and providing jet fuel resistant sealant.
Approximately 50 LF of cracks.
e. Roof Perimeter Screens OBSERVATION: Several locations of the roof perimeter bird screens are missing.
REFERENCE: Usual and customary engineering practices.
RECOMMENDATION: Provide additional sections of screen. Approximately 30 LF of screen.
f. High-level control valve tubing supports OBSERVATION: The high-level control valve tubing is not properly supported above the valve.
REFERENCE: Usual and customary engineering practices.
RECOMMENDATION: Provide an additional support for the tubing.
g. Corrosion at high-level valve tubing supports OBSERVATION: Corrosion was observed at the carbon steel HLCV tubing supports.
REFERENCE: AW 78-24-27 Sheet D.10, Detail 5 and usual and customary engineering practices.
RECOMMENDATION: Replace carbon steel tubing clamps with stainless steel cushioned clamps.
Approximately 30 clamps.
h. Corrosion at electrical conduit supports OBSERVATION: Corrosion was observed at the carbon steel electrical conduit supports.
REFERENCE: AW 78-24-27 Sheet D.10, Detail 5 and usual and customary engineering practices
RECOMMENDATION: Replace carbon steel tubing clamps with stainless steel cushioned clamps.
Approximately 10 clamps.
i. Receipt pressure relief loop OBSERVATION: The pressure relief loop at the receipt valve contains carbon steel relief valve, piping, and flanges, which have coating failure and corrosion.
REFERENCE: AW 78-24-27 Detail 4 on Sheet D.10.
RECOMMENDATION: Replace relief valve, piping, and flanges with a stainless-steel relief valve, piping, and flanges.
j. Issue pressure relief loop OBSERVATION: The pressure relief loop at the issue valve contains carbon steel piping and flanges, which have coating failure and corrosion.
REFERENCE: AW 78-24-27 Detail 4 on Sheet D.10.
RECOMMENDATION: Replace piping and flanges with stainless-steel.
k. Tank ground wire OBSERVATION: One tank ground wire below the tank stairs has detached from the original floor extension.
REFERENCE: AW 78-24-27 Sheet ED.02
RECOMMENDATION: Reattach ground wire.
l. Testing OBSERVATION: The tank is equipped with an ENRAF ATG system, high level control valve, and an independent level alarm system.
REFERENCE: UFC 3-460-03 Appendix C
RECOMMENDATION: Test ATG system, level alarm switches, and overfill prevention devices as part of the on-going maintenance program.
APPENDIX A: ENGINEERING CALCULATIONS AND DRAWINGS
NDE DATA
ENGINEERING CALCULATIONS
TANK DRAWING
OSHA ACCESS STRUCTURE REPORT
Tank No.: 10 Location: Joint Base Andrews EEI Project No.: 9364 Performed By: JEH, MCM, SCK Date: 29-30 April 2019
Revised April 2019
Shell Course No. Reading No. UT Reading (Inches)
Coating Thickness at Same Location (Mils)
1 0.241 22.10 1 2 0.243 20.90
3 0.245 28.90 4 0.242 24.10 5 0.241 32.90 6 0.240 32.00
Average 0.242 26.82 1 0.236 18.10
2 2 0.238 21.90 3 0.241 20.50 4 0.241 24.10 5 0.239 19.30 6 0.235 17.60
Average 0.238 20.25 1 0.234 19.50
3 2 0.254 19.90 3 0.254 18.50 4 0.252 20.70 5 0.246 26.60 6 0.246 21.70
Average 0.248 21.15 1 0.243 20.60
4 2 0.247 21.00 3 0.247 18.20 4 0.251 15.80 5 0.246 18.20 6 0.238 26.20
Average 0.245 20.00
Form 07 Shell: Exterior UT & Coating
Enterprise Engineering, Inc. Form 07 Shell Exterior-UT&Coat
EEI Project No.: 9364 Performed By: JEH, MCM, SCK Date: 29-30 April 2019
Revised April 2019
Shell Course No. Reading No. UT Reading (Inches)
Coating Thickness at Same Location (Mils)
Form 07 Shell: Exterior UT & Coating
1 0.236 19.70 5 2 0.247 16.70
3 0.247 20.30 4 0.245 18.40 5 0.241 20.60 6 0.238 22.90
Average 0.242 19.77 1 0.254 29.40
6 2 0.253 27.80 3 0.254 23.20 4 0.250 24.00 5 0.249 22.10 6 0.248 22.00
Average 0.251 24.75 Rim Angle (3 locations) 1 0.370
2 0.369 3 0.368
Average 0.369
Coating Thickness Average 22.12 (all courses) Minimum 15.80
Maximum 32.90
Highlight Minimum UT Reading Per Course
Enterprise Engineering, Inc. Form 07 Shell Exterior-UT&Coat
EEI Project No.: 9364 Performed By: JEH, MCM, SCK Date: 29-30 April 2019
Revised April 2019
UT Equipment :
Vertical Welds Reading No.
UT Reading 6"-12" From Tank Bottom
(Inches)
1V-1 1 0.245
2 0.245
3 0.243
1V-2 4 0.243
1V-2 1 0.250
2 0.251
3 0.249
1V-3 4 0.248
1V-3 1 0.259
2 0.260
3 0.257
1V-4 4 0.253
1V-4 1 0.485
2 0.486
3 0.489
1V-5 4 0.491
1V-5 1 0.257
2 0.255
3 0.253
1V-6 4 0.251
1V-6 1 0.257
2 0.259
3 0.255
1V-7 4 0.252
1V-7 1 0.254
2 0.253
3 0.250
1V-8 4 0.247
1V-8 1 0.243
2 0.239
3 0.239
1V-9 4 0.234
1V-9 1 0.496
2 0.498
3 0.499
1V-1 4 0.499 Average 0.304 Minimum 0.234 Maximum 0.499
Form 08 Shell: Exterior 1st Course UT
Olympus 38 DL Plus
Note: Shell plate is thickened with tapered edges
Enterprise Engineering, Inc. Form 08 Shell Ext-1st Course UT
EEI Project No.: 9364 Performed By: JEH, MCM, SCK Date: 29-30 April 2019
Revised April 2019
Nozzle/ Manhole Reading No.
Nozzle (Inches)
Reinf. Plate (Inches)
Cover (Inches)
1 0.496 0.499 0.815 2 0.497 0.499 0.816 3 0.496 0.497 0.815
Average 0.496 0.498 0.815 1 0.520 - - 2 0.508 - - 3 0.524 - -
Average 0.517 - - 1 0.438 0.496 - 2 0.446 0.499 - 3 0.433 0.498 -
Average 0.439 0.498 - 1 0.493 0.489 0.815 2 0.495 0.491 0.815 3 0.497 0.492 0.815
Average 0.495 0.491 0.815 1 0.218 - - 2 0.209 - - 3 0.215 - -
Average 0.214 - - 1 0.213 - - 2 0.205 - - 3 0.224 - -
Average 0.214 - - 1 0.320 0.243 - 2 0.349 0.243 - 3 0.340 0.243 -
Average 0.336 0.243 -
Water Draw-Off 1
Water Draw-Off 2
Low Suction
Form 11 External Shell Manhole/Nozzle: UT
Manhole 1
Issue
Receipt
Manhole 2
Enterprise Engineering, Inc. Form 11 Shell MH-Nozzle UT
EEI Project No.: 9364 Performed By: JEH, MCM, SCK Date: 29-30 April 2019
Revised April 2019
Reading No. Clockwise Distance from MH-1 UT Reading
(Inches)
Coating Thickness at Same Location
(Mils)
Floor Projection Distance (Inches)
1 0'-0" 0.271 32.00 1.375
2 13'-4" 0.306 22.80 1.750
3 26'-6" 0.304 21.70 1.000
4 40'-1" 0.304 29.40 1.250
5 53'-0" 0.303 33.40 1.125
6 66'-6" 0.306 25.50 1.500
7 80'-2" 0.304 29.90 1.625
8 93'-0" 0.278 27.40 1.500
9 106'-6" 0.295 24.80 1.500
10 120'-0" 0.307 35.50 1.375 Average 0.298 28.24 1.400 Minimum 0.271 21.70 1.000 Maximum 0.307 35.50 1.750
Form 16 Floor: Projection UT & Coating
1. Record data at each first course vertical shell joint for tanks with 10 or more joints.
2. Record data at a minimum of 10 equally spaced locations for tanks with less than 10 vertical shell welds.
Enterprise Engineering, Inc. Form 16 Floor Projection
TANK EVALUATION CALCULATIONS VERSION 8.02 TANK EVALUATION
REL 9/15/2007 EXP 5/1/2045 #####
INPUT DATA REV 6/14/2019
(Highlighted values are input data)
PROJECT: PREPARED BY: SCK
LOCATION: DATE: 05/01/19
EEI PROJECT NO.:
CHECKED BY: JEH
TANK NO. DATE: 08/08/19
TANK DATA: GENERAL
NEW / EXISTING Existing
YEAR BUILT 1960
TANK DATA: PHYSICAL PROPERTIES
FOUNDATION
TYPE OF FOUNDATION Ringwall (INPUT Ringwall, Earth, Concrete Confining Ring, etc.)
TANK ANCHORED (YES OR NO) NO
NUMBER OF ANCHORS N =
DIAMETER OF BOLT CIRCLE d = FT DIAMETER OF ANCHOR BOLTS dB = INCHES
SPACING OF ANCHOR BOLTS S= FT
AISC Bolt Allowable Stresses
ANCHOR BOLT YIELD STRENGTH Fyab = KSI Material Fyab Fu Fnv Fvbolt = Fnv / W A36 36.00 58.00 Not listed use Fvbolt = 10.00
ANCHOR BOLT SHEAR STRENGTH Fvbolt = KSI A307 36.00 60.00 27.00 Fvbolt = 13.50
A320 L7 105.00 125.00 Not listed use Fv = 0.17(Fu) = 21.25 W = 2.00 for Allowable Stress Design
COEFFICIENT OF FRICTION
BETWEEN TANK AND μ = 0.40 (μ max = 0.4 PER API 650 E.7.6., USE SMALLER μ
FOUNDATION BASED ON FOUNDATION CONSIDERATIONS)
FLOOR
MATERIAL Unknown
FLOOR THICKNESS tF = 0.2980 INCHES
FLOOR CORROSION ALLOWANCE CAfloor = INCHES
FLOOR THICKNESS
BELOW SHELL tb = INCHES
ANNULAR PLATE (YES/NO) NO
ANNULAR PLATE THICKNESS tann = INCHES
ANNULAR PLATE WIDTH Ls = FT
YIELD STRENGTH OF FLOOR
PLATE BELOW SHELL FBY = 30,000 PSI
In-Service API 653 Inspection JB Andrews, MD
ENTERPRISE ENGINEERING, INC. Printed: 8/8/2019 Input Data - Page 1
File: App A Tank 10 Calcs 1 Tank Evaluation 8.02 REV 06-14-19
INPUT DATA REV 6/14/2019
(Highlighted values are input data)
PROJECT: PREPARED BY: SCK
LOCATION: DATE: 05/01/19
EEI PROJECT NO.:
CHECKED BY: JEH
TANK NO. DATE: 08/08/19
In-Service API 653 Inspection JB Andrews, MD
TANK DATA: PHYSICAL PROPERTIES
SHELL
DIAMETER D = 42.500 FT
SHELL CORROSION ALLOWANCE CAshell = INCHES
OVERFLOW PORTS = None (Input YES if overflow ports are present, input NONE if no overflow ports)
TOP OF SHELL TO BOTTOM
OF OVERFLOW PORT Hop = 0.000 FT (Input 0 if no overflow ports)
TYPE OF SHELL JOINTS Butt Welded (Input BUTT WELDED, LAP WELDED, or RIVETED)
USE JOINT EFFICIENCY PER API 650 FOR NEW TANK, PER API 653 FOR EXISTING TANK
COURSE HEIGHT THICKNESS JOINT MATERIAL YIELD ALLOWABLE STRESS
NO. h t EFFICIENCY STRESS PRODUCT HYDROTEST
FT INCHES E Fy Sd St
PSI PSI PSI
BOTTOM COURSE 1 6.021 0.2400 0.85 Unknown 30000 23600 26000
2 7.500 0.2380 0.85 Unknown 30000 23600 26000 3 7.438 0.2480 0.85 Unknown 30000 26000 27000 4 7.458 0.2450 0.85 Unknown 30000 26000 27000 5 7.438 0.2420 0.85 Unknown 30000 26000 27000 6 2.333 0.2510 0.85 Unknown 30000 26000 27000
RIM ANGLE 0.000 0.3690
SHELL HEIGHT Hs = 38.188 FT
ENTERPRISE ENGINEERING, INC. Printed: 8/8/2019 Input Data - Page 2
INPUT DATA REV 6/14/2019
(Highlighted values are input data)
PROJECT: PREPARED BY: SCK
LOCATION: DATE: 05/01/19
EEI PROJECT NO.:
CHECKED BY: JEH
TANK NO. DATE: 08/08/19
In-Service API 653 Inspection JB Andrews, MD
TANK DATA: PHYSICAL PROPERTIES
ROOF AND ROOF FRAMING
ROOF SLOPE THETA = 5.00 DEG
ROOF THICKNESS tR = 0.1000 INCHES ROOF CORROSION ALLOWANCE CAroof = INCHES
WEIGHT OF ROOF FRAMING rF = 5.000 PSF (if unknown, use 5 psf) WEIGHT OF RIM ANGLE rA = 4.900 LB/LF
ROOF FRAMING SYSTEM 0 (Input 0 no interior columns or 1 single center column with simple span radial rafters only or 2 single center column with simple span radial trusses only or 3 single center column with trusses and framing or 4 center column with perimeter columns)
(Leave cell blank if framing system 3 is NOT selected)
(Leave cell blank if framing system 3 is NOT selected) (Leave cell blank if framing system 3 is NOT selected) (Leave cell blank if framing system 3 is NOT selected)
COLUMN
NUMBER WEIGHT
COLUMN SIZE OF COLUMNS (LB/LF)
CENTER NONE 0 0.0 (If no interior columns, INNER COLUMNS NONE 0 0.0 input NONE in "SIZE" column OUTER COLUMNS NONE 0 0.0 input 0.0 in "NO. of COLUMNS" and "COLUMN WEIGHT" column)
RADIAL DISTANCE
TO OUTER COLUMN R2 = 0 FT (Input 0 if no radial columns)
APPURTENANCES
WEIGHT OF STAIRS, PIPING, ETC. 2 % (Input weight as a percentage of total weight of tank.
Input 2% if unknown)
FLOATING PAN/ROOF
WT OF FLOATING PAN/ROOF Wpan = 10.87 K (Input weight of floating pan/roof, Input 0 if no pan/roof) (Petrex aluminum honeycomb pans weigh 0.717 psf)
COMMENT: Indicate here whether roof slope is assumed, calculated, or based on record drawings
ENTERPRISE ENGINEERING, INC. Printed: 8/8/2019 Input Data - Page 3
INPUT DATA REV 6/14/2019
(Highlighted values are input data)
PROJECT: PREPARED BY: SCK
LOCATION: DATE: 05/01/19
EEI PROJECT NO.:
CHECKED BY: JEH
TANK NO. DATE: 08/08/19
In-Service API 653 Inspection JB Andrews, MD
TANK DATA: LIQUID STORAGE
FILL HEIGHT Hf = 35.917 FT (Fill height can also be the design liquid level)
PRODUCT STORAGE Jet A (Input product storage service.
Example: GASOLINE, JP-4, JP-5, JP-8, DIESEL, WATER)
SPECIFIC GRAVITY G = 0.840 Specific gravities of various liquids product G
Gasoline 0.730 JP-4 0.751 to 0.802 JP-5 0.788 to 0.845 JP-8 0.775 to 0.840 Diesel (F-76) 0.830 to 0.860 Water 1.000 Jet-A 0.775 to 0.840
TANK DATA: LOADS
DIFFERENTIAL SETTLEMENT
TOLERANCE OF
FLOATING PAN SEAL Rtol = 4 INCHES (Input N/A if no floating pan)
DIFFERENTIAL SETTLEMENT DELTA = 0.00 FT (High point EL - Low point EL) (Input 0 if no data)
ROOF LIVE LOAD
ROOF LIVE LOAD PLL = 20 PSF REF: API 650 5.2.1.f
SNOW LOAD
CODE: ASCE 7-10
NOTE: FOR MILITARY PROJECTS USE UFC 3-301-01 FOR GROUND SNOW LOAD DATA
GROUND SNOW DATA UFC (Enter ASCE or UFC) GROUND SNOW Pg = 25 PSF UFC 03-301-01 EXPOSURE FACTOR Ce = 1 ASCE 7-10 TABLE 7-2 THERMAL FACTOR Ct = 1.2 ASCE 7-10 TABLE 7-3
IMPORTANCE FACTOR I = 1 ASCE 7-10 TABLE 1.5-2
ROOF SNOW LOAD PER
LOCAL BUILDING CODE PfLocal Code = PSF
ENTERPRISE ENGINEERING, INC. Printed: 8/8/2019 Input Data - Page 4
INPUT DATA REV 6/14/2019
(Highlighted values are input data)
PROJECT: PREPARED BY: SCK
LOCATION: DATE: 05/01/19
EEI PROJECT NO.:
CHECKED BY: JEH
TANK NO. DATE: 08/08/19
In-Service API 653 Inspection JB Andrews, MD
TANK DATA: LOADS
WIND LOAD
CODE: API 650 12th EDITION ADDENDUM 3
NOTES
1. ASCE 7-10 WIND VELOCITIES HAVE LRFD LOAD FACTORS AND RISK CATEGORIES BUILT IN. API 650 USES
WORKING STRESS AND PERMITS USE OF ASCE 7-05 OR ASCE 7-10.
THIS SPREADSHEET USES ASCE 7-10.
2. API 650 WIND LOAD AND VELOCITY PRESSURE IN SECTION 5.2.1(k)(1) ARE BASED ON ASCE 7 EXPOSURE C, IMPORTANCE FACTOR OF 1.00.
3. PER API 650 5.2.1.k, WIND PRESSURES MAY BE DETERMINED IN ACCORDANCE WITH ASCE 7.
4. TO ADJUST THE VELOCITY PRESSURE ON THE TANK SHELL AND ROOF FOR WIND OVERTURNING, ENTER THE
EXPOSURE CATEGORY AND IMPORTANCE FACTOR.
5. STIFFENER EVALUATION IS BASED ON API 650 WHICH USES EXPOSURE CATEGORY C, IMPORTANCE FACTOR OF 1
6. FOR MILITARY PROJECTS USE UFC 3-301-01 FOR BASIC WIND SPEED.
RISK CATEGORY III ASCE 7-10 Table 1.5.1 or UFC 3-301-01 EXPOSURE CATEGORY C ASCE 7-10 sect 26.6 (B, C, D) BASIC WIND SPEED DATA UFC (Enter ASCE of UFC)
BASIC WIND SPEED V = 120 MPH UFC 3-301-01
USE API 650 WIND PRESSURES
MODIFIED FOR WIND SPEED (YES/NO) No API 650 5.2.1(k)
(NOTE: API wind pressures are for Exposure C)
DESIGN INTERNAL PRESSURE Pid = 0.00 PSF OPERATING PRESSURE Pi = 0.00 PSF Enter 0 if no internal pressure INTERNAL PRESSURE FACTOR Fp = 0.40 F = Ratio of operating pressure to design pressure, not less than 0.4
FILL HEIGHT FOR ALLOWABLE Applies to anchored tank only SHELL COMPRESSION Hfwind = 0.000 FT (For worse case use Hf = 0 FT for empty tank)
ENTERPRISE ENGINEERING, INC. Printed: 8/8/2019 Input Data - Page 5
INPUT DATA REV 6/14/2019
(Highlighted values are input data)
PROJECT: PREPARED BY: SCK
LOCATION: DATE: 05/01/19
EEI PROJECT NO.:
CHECKED BY: JEH
TANK NO. DATE: 08/08/19
In-Service API 653 Inspection JB Andrews, MD
TANK DATA: LOADS
SEISMIC LOAD
CODE: API 650 12th EDITION, ADDENDUM 3 ANNEX E
SEISMIC USE GROUP (I, II, III) = III API 650 E.3.1
SITE GROUND MOTION (API 650 E.4.1 MAPPED ASCE METHOD)
SHORT PERIOD (0.2 S)
ACCELERATION Ss = 0.1200 %g ASCE 7 FIG 22-1, 22-3, 22-5, and 22-6
1.0 S PERIOD
ACCELERATION S1 = 0.0500 %g ASCE 7 FIG 22-2, 22-4, 22-5, and 22-6
REGIONAL- DEPENDENT
TRANSITIONAL PERIOD TL = 8.00 SEC ASCE 7 FIG 22-12 THROUGH 22-16
SITE CLASS = D ASCE 7 CHAPTER 20 AND API 650 E.4.4
SITE MODIFICATION COEFFICIENTS (ASCE 7 AND API 650 E.4.4)
Fa = 1.60 API 650 ANNEX E TABLE E.1
Fv = 2.40 API 650 ANNEX E TABLE E.2
TANK MATERIAL Steel
TANK MATERIAL MODULUS
OF ELASTICITY E = ######## PSI
Hf/D = 0.8451
COEFFICIENT FOR
IMPULSIVE PERIOD Ci = 6.07 API 650 ANNEX E FIGURE E.1 (BASED ON Hf/D)
SCALING FACTOR FROM MCE TO
DESIGN LEVEL SPECTRAL
ACCELERATIONS Q= 2/3 (Q = 2/3 FOR ASCE -7 METHODS. FOR MILITARY
DESIGN OF ESSENTIAL FACILITIES, Q = 3/4)
COEFFICIENT TO ADJUST FROM
5% TO 0.5% DAMPING K = 1.5 K = 1.5 UNLESS SPECIFIED OTHERWISE
ENTERPRISE ENGINEERING, INC. Printed: 8/8/2019 Input Data - Page 6
INPUT DATA REV 6/14/2019
(Highlighted values are input data)
PROJECT: PREPARED BY: SCK
LOCATION: DATE: 05/01/19
EEI PROJECT NO.:
CHECKED BY: JEH
TANK NO. DATE: 08/08/19
In-Service API 653 Inspection JB Andrews, MD
TANK DATA: SHELL CORROSION ANALYSIS
DEPTH OF CORRODED AREAS IN SHELL
AT SHELL VERTICAL WELDS = Xw INCH (Input 0.0 if no corrosion or leave blank if no input)
AWAY FROM SHELL VERTICAL
WELDS BY 1 INCH OR 2t = Xs INCH (Input 0.0 if no corrosion or leave blank if no input)
COURSE Xw Xs
NO. INCH INCH
ENTERPRISE ENGINEERING, INC. Printed: 8/8/2019 Input Data - Page 7
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
TANK DIFFERENTIAL SETTLEMENT
Hd
Hs Hf
DELTA allow
ALLOWABLE RIGID BODY TILT
BASED ON HOOP STRESS AT BOTTOM OF FIRST COURSE
ALLOWABLE TILT DELTA allow = [ (4S x 12 (t - CA) x E)/(G x Gw x D) ] - 2 (Hf-1)
ALLOW HOOP STRESS, 1ST COURSE S = 23,600 PSI
1ST COURSE THICKNESS t = 0.24 INCH
SHELL CORROSION ALLOWANCE CA = 0.0000 INCH
1ST COURSE JOINT EFFICIENCY E = 0.85
SPECIFIC GRAVITY OF CONTENTS G = 0.840 Jet A UNIT WEIGHT OF WATER Gw = 62.4 LB/FT3
TANK DIAMETER D = 42.50 FT
HEIGHT OF SHELL Hs = 38.19 FT
FILL HEIGHT Hf = 35.92 FT FREEBOARD Hd = Hs - Hf = 2.27 FT
FOR Jet A Service
DELTA allow = [(4(23600) x 12(0.24 - ) x 0.85) / (0.84x62.4x42.5)] -2( 35.917- 1) = 33.90 FT
ENTERPRISE ENGINEERING, INC. Printed: 8/8/2019 Settlement - Page 8
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
TANK DIFFERENTIAL SETTLEMENT
ALLOWABLE RIGID BODY TILT
BASED ON OVERFLOWING
ALLOWABLE TILT DELTA allow = 2(Hd)
HEIGHT OF SHELL Hs = 38.19 FT
TOP OF SHELL TO BOT
OF OVERFLOW PORT Hop = 0.00 FT
HEIGHT TO BOTTOM
OF OVERFLOW PORT Hp = Hs - Hop = N/A FT Tank does not have overflow ports
FILL HEIGHT Hf = 35.92 FT
FREEBOARD Hd = 2.27 FT
DELTA allow = 2 ( 2.271 ) = 4.54 FT
BASED ON TOLERANCE OF FLOATING ROOF/PAN
ALLOWABLE TILT DELTA allow = 2 x SQR[Rtol x D]
FLOATING PAN SEAL TOLERANCE Rtol = 4 INCH
TANK DIAMETER D = 42.50 FT
DELTA allow = 2 SQR( 4/12 x 42.5 ) = 7.53 FT
ALLOWABLE RIGID BODY TILT SUMMARY
AT FILL HEIGHT = 35.917 FT
ALLOWABLE SETTLEMENT BASED ON OVERFLOWING CRITERIA GOVERNS
DELTA allow = 4.54 FT
EVALUATE ACTUAL DIFFERENTIAL SETTLEMENT
DIFFERENTIAL SETTLEMENT DELTA actual = 0.00 FT ALLOWABLE TILT DELTA allow = 4.54 FT
DELTA actual = 0 FT < DELTA allow = 4.54 FT PASSES CRITERIA
ENTERPRISE ENGINEERING, INC. Printed: 8/8/2019 Settlement - Page 9
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
DEAD LOAD
TANK DIAMETER D = 42.50 FT
HEIGHT OF SHELL Hs = 38.19 FT
SHELL
WT/COURSE = [ 0.490 KCF (t/12)(h)(PI)(D) ]
COURSE HEIGHT THICKNESS WEIGHT
NO. h t
FT INCH K
1 6.021 0.240 7.88 2 7.5 0.238 9.73 3 7.438 0.248 10.06 4 7.458 0.245 9.96 5 7.438 0.242 9.81 6 2.333 0.251 3.19
RIM ANGLE 0.65
Wshell = 51.29 K = 51.29 K
WT/LF = (Wshell) / (πD) = 51.29 / [(3.142) (42.5)] = 0.384 K/LF
WEIGHT OF RIM ANGLE rA = 4.9 LB/LF
Wrim angle = [(rA/1000) (π) (D)] = 4.9/1000 x 3.142 x 42.5 = 0.65 K
FLOOR
FLOOR THICKNESS tF = 0.298 INCH
WT = [490 PCF (tF/12) (π) ((D2/4)]/1000 = 490 x ( 0.298 / 12 ) x 3.142 x ((42.5)^2 ) / 4 )] /1000 = 17.26 K
SUBTOTAL = 68.55 K
ENTERPRISE ENGINEERING, INC. Printed: 8/8/2019 Dead Load - Page 10
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
DEAD LOAD
PREVIOUS PAGE SUBTOTAL = 68.55 K
ROOF
ROOF PLATE tR = 0.1 INCH
WT = [490 PCF (tR/12) (π) ((D2/4)]/1000 = [490 x ( 0.1 / 12 ) x 3.142 x ((42.5) ^2 ) / 4 )] /1000 = 5.79 K
ROOF FRAMING WEIGHT rF = 5 PSF
WT = (rF/1000) (π) [((D2)/4] = 5 / 1000 x 3.142 x[ ( ( 42.5 ) ^2 ) /4 ] = 7.09 K
12.89 K = 12.89 K
INTERIOR COLUMNS
COLUMN SIZE NUMBER HEIGHT COLUMN TOTAL
OF WEIGHT WEIGHT
COLS
FT LB/LF K
CENTER NONE 0 0 0.00 0.00
INNER COLUMNS NONE 0 0 0.00 0.00
OUTER COLUMNS NONE 0 0 0.00 0.00
0.00 = 0.00 K
APPURTENANCES AND MISCELLANEOUS WEIGHT
STAIRS, PIPING, MISC. WT = 2% OF FOLLOWING LOADS:
SHELL WT = 51.29 K
ROOF WT = 12.89 K
TOTAL = 64.18 K
MISC WT = (2%) (64.18) = 1.28 K
TOTAL WEIGHT OF TANK = 82.72 K
ENTERPRISE ENGINEERING, INC. Printed: 8/8/2019 Dead Load - Page 11
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
DEAD LOAD
WEIGHT OF ROOF SUPPORTED BY SHELL
10.63 FT R1 = 10.63 FT
21.25 FT R2 = 0.00 FT
R = 21.25 FT
TOTAL WEIGHT OF ROOF
ROOF PLATE WTOTAL ROOF PL = 5.79 K
FRAMING WTOTAL FRAMING = 7.09 K
12.89 K = 12.89 K
ROOF DEAD LOAD SUPPORTED BY INTERIOR COLUMNS
Tank roof is not supported by interior columns, roof is supported by shell.
Therefore, entire roof dead load is supported by the shell.
0.00 K
ROOF DEAD LOAD SUPPORTED BY SHELL
K
WROOF PL ON SHELL= 5.79
WFRAMING ON SHELL= 7.09
12.89 K
WT/LF = (WROOF ON SHELL) / (πD) =12.89 / [( 3.142 ) ( 42.5)] = 0.097 K/LF
ENTERPRISE ENGINEERING, INC. Printed: 8/8/2019 Dead Load - Page 12
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
ROOF LIVE LOAD
ROOF LIVE LOAD PLL = 20 PSF
10.63 FT R1 = 10.63 FT
21.25 FT R2 = 0.00
R = 21.25 FT
TOTAL ROOF LIVE LOAD
TOTAL ROOF LIVE LOAD = (PLL / 1000) (π) (D2/4) = (20 / 1000) x 3.142 x ( (42.5 ^2) / 4) = 28.37 K
ROOF LIVE LOAD SUPPORTED BY INTERIOR COLUMNS
Tank roof is not supported by interior coulumns, roof is supported by shell.
Therefore, entire roof live load is supported by the shell.
ROOF LIVE LOAD SUPPORTED BY SHELL
WLL ON SHELL = = 28.37 K
WLL = WLL ON SHELL / (π) (D) = 28.37 / (3.14 ) ( 42.5 ) = 0.213 K/FT
TANK CL
CL OUTER COL
ENTERPRISE ENGINEERING, INC. Printed: 8/8/2019 Roof Live Load - Page 13
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
SNOW LOAD
CODE: ASCE 7-10
FLAT ROOF SNOW Pf = (0.7) Ce Ct Is Pg PSF EQ. 7.3-1 PfMIN = (I) Pg for Pg <= 20 PSF PfMIN = (20) (I) for Pg > 20 PSF
GROUND SNOW Pg = 25 PSF UFC 3-301-01 EXPOSURE FACTOR Ce = 1 ASCE 7-10 TABLE 7-2 THERMAL FACTOR Ct = 1.2 ASCE 7-10 TABLE 7-3 IMPORTANCE FACTOR Is = 1 ASCE 7-10 TABLE 1.5-2
Pf = (0.7)1) (1.2) (1) (25) = 21.00 PSF
Pg > 20, THEREFORE Pfmin = (20) (Is) = 20.00 PSF
Pf > Pfmin
ASCE Pf GOVERNS OVER ASCE PFmin
Pf = 21.00 PSF
ROOF SNOW LOAD PER LOCAL BUILDING CODE
PfLocal Code = 0 PSF
PfLocal Code < ASCE Pf
ASCE Pf GOVERNS OVER PfLocal Code
ROOF SNOW LOAD = 21.00 PSF
10.63 FT R1 = 10.63 FT
21.25 FT R2 = 0.00 FT
R = 21.25 FT
TOTAL SNOW WEIGHT
TOTAL SNOW WEIGHT = (Pf / 1000) (π) (D2/4) = (21 / 1000) x 3.142 x ( (42.5 ^2) / 4) = 29.79 K
ENTERPRISE ENGINEERING, INC. Printed: 8/8/2019 Snow - Page 14
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
SNOW LOAD
ROOF SNOW LOAD SUPPORTED BY INTERIOR COLUMNS
Tank roof is not supported by interior coulumns, roof is supported by shell.
Therefore, entire snow weight is supported by the shell.
ROOF SNOW LOAD SUPPORTED BY SHELL
WSNOW ON SHELL = = 29.79 K
WSN = WSNOW ON SHELL / (π) (D) = 29.79 / (3.14 ) ( 42.5 ) = 0.22 K/FT
ENTERPRISE ENGINEERING, INC. Printed: 8/8/2019 Snow - Page 15
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
WIND LOAD EVALUATION: UN-ANCHORED TANK
CODE: API 650 AND ASCE 7-10
RISK CATEGORY = III
EXPOSURE CATEGORY = C
BASIC WIND SPEED V = 120 MPH From UFC 3-01-01 BASIC WIND SPEED x 0 .78 V = 93.6 MPH Modified per API 650 12th Ed sect 5.2.1.k.1
USE API 650 EXPOSURE C WIND PRESSURES
MODIFIED FOR WIND SPEED (YES/NO) = No
TANK PARAMETERS
TANK DIAMETER D = 42.50 FT
ROOF SLOPE = 5.00 DEG = 0.0873 RAD
MEAN ROOF HT = (1/2)(D/2)(TAN THETA = 0.93 FT
SHELL HEIGHT Hs = 38.19 FT
MEAN ROOF HEIGHT ABOVE GROUND = 39.12 FT
TO DETERMINE λ, USE MEAN ROOF HEIGHT = 40 FT
INTERNAL PRESSURE = 0.00 PSF
TANK ANCHORED = NO
FILL HEIGHT Hf = 35.92 FT THICKNESS OF FLOOR BELOW SHELL ta = 0.0000 INCHES YIELD STRENGTH OF FLOOR BELOW SHELL Fby = 30000.00 PSI
API 650 WIND PRESSURE (BASED ON EXPOSURE C, BASIC WIND SPEED = 120 MPH)
DESIGN WIND PRESSURE ON VERTICAL PROJECTED AREA OF CYLINDRICAL SURFACES, API 650 5.2.1(k)(1)
PSHELL = (18) (V/120)^2 = 10.95 PSF
DESIGN WIND PRESSURE ON HORIZONTAL PROJECTED AREA OF CONICAL OR DOUBLY CURVED SURFACES, API 650 5.2.1(k)(1)
PROOF = (30)(V/120)^2 = 18.25 PSF
WIND PRESSURE ADJUSTMENT FACTOR FOR HEIGHT AND EXPOSURE - ASCE 7-10 FIG 28.6-1
ADJUSTMENT FACTOR FOR HEIGHT AND EXPOSURE, λ
MEAN ROOF
HEIGHT B C D
15 1.00 1.21 1.47 20 1.00 1.29 1.55 25 1.00 1.35 1.61 30 1.00 1.40 1.66 35 1.05 1.45 1.70 40 1.09 1.49 1.74 45 1.12 1.53 1.78 50 1.16 1.56 1.81 55 1.19 1.59 1.84 60 1.22 1.62 1.87 λ = 1.49 MEAN ROOF HEIGHT = 39.12 FT, EXPOSURE C λ AT SITE = 1.49 MEAN ROOF HEIGHT = 39.12 FT, EXPOSURE C
EXPOSURE
ENTERPRISE ENGINEERING, INC. PRINTED: 8/8/2019
Wind Unanchored Tank - PAGE 16
FILE: App A Tank 10 Calcs 1 Tank Evaluation 8.02 REV 06-14-19
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
WIND LOAD EVALUATION: UN-ANCHORED TANK
ADJUSTED WIND PRESSURES FOR HEIGHT AND EXPOSURE
ADJUSTED PSHELL = (λ AT SITE / λ) (PSHELL)
= (1.49 / (1.49) (10.95) 10.95 PSF
ADJUSTED PROOF = (λ AT SITE / λ) (PROOF)
= (1.49 / (1.49) (18.25) 18.25 PSF
WIND OVERTURNING MOMENT
PROJECTED AREA OF SHELL
ASHELL = (D)(Hs) = (42.5) (38.188 = 1,622.99 SF
PROJECTED AREA OF ROOF
AROOF = π (D)^2/4 = π (42.5)^2 /4 = 1,418.63 SF
WIND FORCE ON SHELL
FwSHELL = (ADJUSTED PSHELL) (ASHELL) = (10.95) (1622.99) / 1000 = 17.77 K
WIND UPLIFT FORCE ON ROOF
FwROOF = (ADJUSTED PROOF) (AROOF) = (18.25) (1418.63) / 1000 = 25.89 K
OVERTURNING MOMENT FROM EXTERNAL WIND PRESSURE ON SHELL AND ROOF
Mw = (FwSHELL)(Hs/2) + (FwROOF)(D/2)
= (17.77) (38.188/2) + (25.89) (42.5/2) = 889.59 K-FT
OVERTURNING MOMENT FROM EXTERNAL WIND PRESSURE ON SHELL
Mws = (FwSHELL)(Hs/2)
= (17.77) (38.19/2) = 339.37 K-FT
INTERNAL PRESSURE OVERTURNING MOMENT
INTERNAL PRESSURE FORCE UPLIFT ON ROOF
FpiROOF = (INTERNAL PRESSURE) (AROOF) = (0) (1418.63) / 1000 = 0.00 K
OVERTURNING MOMENT FROM INTERNAL PRESSURE
Mpi = (FpiROOF)(D/2)
= (0) (42.5/2) = 0.00 K-FT
ENTERPRISE ENGINEERING, INC. PRINTED: 8/8/2019
Wind Unanchored Tank - PAGE 17
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
WIND LOAD EVALUATION: UN-ANCHORED TANK
RESISTANCE TO OVERTURNING (API 650 5.11.2)
RESISTANCE TO OVERTURNING CRITERIA
CASE 1: 0.6Mw + Mpi < MDL/1.5 + MDLR
CASE 2: Mw + FP(Mpi) < (MDL +MF)/2 + MDLR
CASE 3: Mws + FP(Mpi) < MDL/1.5 + MDLR
UNANCHORED TANK MUST SATISFY BOTH CRITERIA
DEAD LOAD RESISTING MOMENT
SHELL WEIGHT = 51.29 K
WEIGHT OF ROOF ON SHELL = 5.79 K
WEIGHT OF ROOF FRAMING
SUPPORTED BY SHELL = 7.09 K
WEIGHT OF ROOF PLATE + FRAMING
SUPPORTED BY SHELL = 12.89 K
RESISTING MOMENT FROM DEAD LOAD
MDL = (SHELL WEIGHT)(D/2)
= (51.29) (42.5/2) = 1,089.89 K-FT
MDLR = (ROOF + FRAMING WEIGHT)(D/2)
= (12.89) (42.5/2) = 273.82 K-FT
INTERNAL FLUID RESISTING MOMENT
WEIGHT OF LIQUID RESISTING OVERTURNING
PER API 650 5.11.2 UNANCHORED TANKS, THE WEIGHT OF LIQUID RESISTING OVERTURNING IS BASED ON
ONE HALF THE DESIGN LIQUID HEIGHT AND A SPECIFIC GRAVITY OF 0.70 .
FILL HEIGHT Hf = 35.92 FT wL = 4.67 ta [(Fby)(Hf)]^0.5 LB PER LF OF CIRCUMFERENCE ta = THICKNESS OF BOTTOM PLATE UNDER SHELL LESS CORROSION ALLOWANCE ta = tb - CAfloor
TANK DOES NOT HAVE AN ANNULAR PLATE, USE FLOOR THICKNESS BELOW SHELL tb to DETERMINE ta tb = 0.0000 INCHES FLOOR THICKNESS BELOW SHELL ta = 0 - 0 = 0.2980 INCHES
Hs
DEAD LOAD
LIQUID HOLD DOWN
WEIGHT WL
D/2
WIND
INTERNAL PRESSURE
Hs/2
WIND LOAD ON
MOMENT ABOUT
SHELL TO
BOTTOM JOINT
ENTERPRISE ENGINEERING, INC. PRINTED: 8/8/2019
Wind Unanchored Tank - PAGE 18
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
WIND LOAD EVALUATION: UN-ANCHORED TANK
INTERNAL FLUID RESISTING MOMENT
WEIGHT OF LIQUID RESISTING OVERTURNING
TANK DOES NOT HAVE AN ANNULAR PLATE, USE THICKNESS OF FLOOR BELOW SHELL TO DETERMINE
WEIGHT OF LIQUID RESISTING OVERTURNING
SPACE RESERVED FOR TANK WITH ANNULAR PLATE
SPACE RESERVED FOR TANK WITH ANNULAR PLATE
ta = 0.2980 INCHES wL = 4.67 (0.298) SQRT[(30000) (35.917)] 1,444.59 lb/lf
ENTERPRISE ENGINEERING, INC. PRINTED: 8/8/2019
Wind Unanchored Tank - PAGE 19
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
WIND LOAD EVALUATION: UN-ANCHORED TANK
INTERNAL FLUID RESISTING MOMENT
WEIGHT OF LIQUID RESISTING OVERTURNING
WEIGHT OF LIQUID (HOLD DOWN WEIGHT)
WL = LESSER OF 0.45(Hf)D OR (wL)(πD)
0.45(Hf)D = 0.45 (35.917) (42.5) = 686.91 K (wL)(πD) = (1444.59) (π) (42.5) / 1000 = 192.88 K GOVERNS
WL = 192.88 K
RESISTING MOMENT FROM INTERNAL LIQUID
MF = (WL)(D/2)
= (192.88) (42.5 /2) = 4,098.70 K-FT
RESISTANCE TO OVERTURNING (API 650 5.11.2)
CASE 1: 0.6Mw + Mpi < MDL/1.5 + MDLR
0.6Mw + Mpi = 0.6 (889.59) +0 = 533.76 K-FT
MDL/1.5 + MDLR= (1089.89)/1.5 + 273.82 = 1,000.42 K-FT
533.76 < 1,000.42 PASS CRITERIA
CASE 2: Mw + FP(Mpi) < (MDL +MF)/2 + MDLR
Mw + FP(Mpi) = (889.59) + (0.4) (0) = 889.59 K-FT
(MDL +MF)/2 + MDLR = (1089.89 + 4098.7)/2 + (273.82) = 2,868.12 K-FT
889.59 < 2,868.12 PASS CRITERIA
CASE 3: Mws + FP(Mpi) < MDL/1.5 + MDLR
Mws + FP(Mpi) = (339.37) + (0.4) (0) = 339.37 K-FT
MDL/1.5 + MDLR= (1089.89)/1.5 + 273.82 = 1,000.42 K-FT
339.37 < 1,000.42 PASS CRITERIA
MINIMUM LIQUID HEIGHT TO RESIST OVERTURNING (APPLIES TO CASE 2 ONLY)
Mw + FP(Mpi) = (MDL +MF)/2 + MDLR MF = 2[Mw + Fp(Mpi) - MDLR] - MDL = (WL)(D/2) WL = {2[Mw + Fp(Mpi) - MDLR] - MDL} / (D/2) = 6.67 K WL = (wa)(πD) wa = [WL / (πD)] (1000 LB/K) = 49.92 LB/LF wa = 4.67 ta [(Fby)(Hf)]^0.5 Hf = (wa / 4.67 tb)^2 / (Fby) = #DIV/0! FT
ENTERPRISE ENGINEERING, INC. PRINTED: 8/8/2019
Wind Unanchored Tank - PAGE 20
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
WIND LOAD EVALUATION: UN-ANCHORED TANK
RESISTANCE TO SLIDING
WIND BASE SHEAR
V = 17.77 K (WIND FORCE ON SHELL)
SLIDING RESISTANCE
Vs = μ(Ws + Wr + Wf + Wp)
COEFFICIENT OF FRICTION μ = 0.40 SHELL WEIGHT Ws = 51.29 K ROOF WEIGHT Wr = 12.89 K FLOOR WEIGHT Wf = 17.26 K FILL HEIGHT Hf = 35.92 FT CONTENTS WEIGHT Wp = (πD^2/4)(62.4)(G)(Hf)
Wp = [(π) (42.5)^2 / 4] (62.4)(0.84) (35.92)/10 = 2,670.74 K
FOR EMPTY TANK
Hf = 0 FT
Wp = [(π) (42.5)^2 / 4] (62.4)(0.84) (0)/1000 = 0.00 K
Vs = (0.4) (51.29 + 12.89 + 17.26 + 0) = 32.58 K
Vs = 32.58 K > V = 17.77 K
FOR EMPTY TANK SLIDING RESISTANCE CRITERIA SATISFIED
MINIMUM PRODUCT HEIGHT REQUIRED TO SATISFY SLIDING RESISTANCE
V = Vs
V = μ(Ws + Wr + Wf + Wp)
Wp = (V / μ) - (Ws + Wr + Wf) = (πD^2/4)(62.4)(G)(Hf)
Hf min = [(V / μ) - (Ws + Wr + Wf)] / [(πD^2/4)(62.4)(G)]
Hf min = [(17.77 / 0.4) - (51.29 + 12.89 + 17.26)] {1000 / [(π) (42.5^2) / 4) (62.4) (0.84)] }
Hf min = < 0 FT
SUMMARY
1. TANK MEETS RESISTANCE TO OVERTURNING CRITERIA
2. TANK MEETS SLIDING RESISTANCE CRITERIA
COMMENT: Tank is adequate to resist all wind loads.
ENTERPRISE ENGINEERING, INC. PRINTED: 8/8/2019
Wind Unanchored Tank - PAGE 21
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
SHELL STIFFENER REQUIREMENTS
EVALUATION CRITERIA
API 650 CRITERIA, Sec. 5.9.6
TRANSFORMED SHELL HEIGHT
TRANSFORMED SHELL HEIGHT Htr = SUM(Wtr) FT TRANSFORMED SHELL COURSE HEIGHT Wtr = SQRT [ ( tTOP / t )5 ] x W
COURSE HEIGHT = W FT
THICKNESS OF TOP COURSE = tTOP INCH
COURSE t W Wtr
NO INCH FT FT
1 0.240 6.021 6.735 2 0.238 7.5 8.566 3 0.248 7.438 7.665 4 0.245 7.458 7.923 5 0.242 7.438 8.149 6 0.251 2.333 2.333
Htr = 41.37 FT
3-SECOND GUST DESIGN WIND VELOCITY
V = 120 MPH From ASCE 7-10 or UFC 3-01-01 V = 93.6 MPH Modified per API 650 12th Ed sect 5.2.1.k.1
MAXIMUM HEIGHT OF UNSTIFFENED SHELL
H1 = 600,000 ( tTOP ) SQRT [ ( tTOP / D )^3 ] (120 / V)^2
H1 = 600,000 x ( 0.251 x SQRT[ ( 0.251 / 42.5)^3 )] (120 /93.6)^2 = 112.35 FT
SHELL STIFFENER REQUIREMENTS
H1 = 112.35 FT > Htr = 41.37 FT
INTERMEDIATE SHELL STIFFENERS NOT REQUIRED
ENTERPRISE ENGINEERING, INC. Printed: 8/8/2019 Shell Stiffeners - Page 22
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
SHELL STIFFENER REQUIREMENTS
MAXIMUM WIND VELOCITY WITHOUT SHELL STIFFENERS
H1 > Htr
SET H1 = Htr
600,000 (tTOP) SQR [( tTOP / D)^3] (120/V)^2 = Htr
SOLVING FOR V:
Vmax = 120 / { SQRT [ Htr / (600,000 ( tTOP) SQRT ( tTOP / D)^3)
Vmax = 120 / { SQRT [ 41.371 / (600,000 ( 0.251) SQRT ( 0.251 / 42.5 )^3} = 154.24 MPH
ENTERPRISE ENGINEERING, INC. Printed: 8/8/2019 Shell Stiffeners - Page 23
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
SEISMIC EVALUATION: UN-ANCHORED TANK
TANK PARAMETERS
DIAMETER D = 42.50 FT
SHELL HEIGHT Hs = 38.19 FT WEIGHT OF SHELL Ws = 51.29 K PRODUCT STORAGE = Jet A
FILL HEIGHT H = 35.92 FT
PRODUCT SPECIFIC GRAVITY G = 0.840
TYPE OF FOUNDATION = Ringwall
TANK ANCHORED = NO
TANK HAS ANNULAR PLATE = NO
E.3 PERFORMANCE BASIS
SEISMIC USE GROUP SUG = III
IMPORTANCE FACTOR I = 1.5 API 650 ANNEX E TABLE E.5
E.4 SITE GROUND MOTION
E.4.2 MAPPED ASCE METHOD
Ss = 0.1200 %g S1 = 0.0500 %g
TL = 8.00 SEC
So = 0.4Ss = 0.0480 %g
E.4.6 SITE CLASS
SITE CLASS = D
E.4.5 SITE MODIFICATION COEFFICIENTS
Fa = 1.60 Fv = 2.40
ASCE 7 ADJUSTED MCE SPECTRAL RESPONSE ACCELERATION PARAMETERS
Sms = (Fa) (Ss) = 0.1920 Sm1 = (Fv) (S1) = 0.1200
SCALING FACTOR FROM MCE TO DESIGN LEVEL SPECTRAL ACCELERATIONS
Q = 2/3
ASCE 7 DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS
SDS = Q (Sms) = 0.1280 SD1 = Q (Sm1) = 0.0800
ENTERPRISE ENGINEERING, INC. PRINTED: 8/8/2019
Seismic Unanchored Tank - PAGE 24
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
SEISMIC EVALUATION: UN-ANCHORED TANK
E.4 SITE GROUND MOTION
E.4.5 STRUCTURAL PERIOD OF VIBRATION
IMPULSIVE NATURAL PERIOD
Ti = (1 / 27.8) [Ci (Hf) / SQRT (tu / D)] [ SQRT (р) / SQRT (E)] E.4.5.1-1a
Ci = 6.0735318 FIGURE E.1 Hf = 35.92 FT Ws = 51.29 K tu = EQUIVALENT UNIFORM THICKNESS OF TANK SHELL, INCHES tu = 12 Ws / [(Hs) (Π) (D) (0.490 K/FT3)] tu = (12) (51.29) / [(38.188) (Π) (42.5) (0.4 = 0.246 INCHES p = 52.416 LB/FT3 DESITIY OF FLUID IN TANK (Jet A)
E = 29000000 PSI ELASTIC MODULUS OF TANK MATERIAL
Ti = (1 / 27.8) [(6.07353176470588) (35.917) / SQRT (0.246 / 42.5)] [SQRT (52.416 / 29000000)] Ti = 0.139 SEC
CONVECTIVE (SLOSHING) PERIOD, Tc
Ks = 0.578 / [tanh(3.68Hf/D)]^0.5 E.4.5.2-2c = 0.578 / [tanh(3.68(35.917)/42.5)]^0.5 = 0.5792
Tc = Ks(D)^0.5 E.4.5.2-2b
= 0.58(42.5)^5 = 3.776 SEC
E.5.1.1 RESPONSE MODIFICATION FACTORS
TABLE E.4 RESPONSE MODIFICATION FACTORS FOR ASD METHODS
ANCHORAGE SYSTEM Rwi (IMPULSIVE) Rwc (CONVECTIVE)
1 SELF-ANCHORED 3.5 2
2 MECHANICALLY ANCHORED 4 2
ANCHORAGE SYSTEM = SELF-ANCHORED
Rwi = 3.5 Rwc = 2
E.4.6.1 SPECTRAL ACCELERATION COEFFICIENTS
IMPULSIVE SPECTRAL ACCELERATION PARAMETER, Ai
Ai = SDS (I/Rwi) E4.6.1-1 Ai MIN > 0.007 E4.6.1-2 FOR S1 > 0.6: Ai > 0.5S1(I/Rwi) E4.6.1-3
S1 = 0.0500 < 0.6 CRITERIA BASED ON S1 DOES NOT GOVERN
SDS (I/Rwi) = 0.128 (1.5 / 3.5) = 0.055 GOVERNS
Ai MIN > 0.007 Ai = 0.055
Ai = 0.055
ENTERPRISE ENGINEERING, INC. PRINTED: 8/8/2019
Seismic Unanchored Tank - PAGE 25
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
SEISMIC EVALUATION: UN-ANCHORED TANK
E.4 SITE GROUND MOTION
E.4.6.1 SPECTRAL ACCELERATION COEFFICIENTS
CONVECTIVE SPECTRAL ACCELERATION PARAMETER, AC
FOR Tc < TL
Ac = KSD1(1/Tc)(I(/Rwc) < Ai E.4.6.1-4
K = 1.5 K = COEFFICIENT TO ADJUST FROM 5% TO 0.5% DAMPING,
K = 1.5 UNLESS SPECIFIED OTHERWISE
FOR Tc > TL
Ac = KSD1(TL/Tc2)(I/Rwc) < Ai E4.6.1-5
Tc = 3.78 SEC
TL = 8.00 SEC
Tc < TL E4.6.1-4 GOVERNS
Ac = 1.5(0.08) (1/3.78) (1.5/2) = 0.024 < Ai
Ac = 0.024
ENTERPRISE ENGINEERING, INC. PRINTED: 8/8/2019
Seismic Unanchored Tank - PAGE 26
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
SEISMIC EVALUATION: UN-ANCHORED TANK
E.6 DESIGN
DESIGN / EVALUATION PARAMETERS
WEIGHT OF TANK FLOOR Wf = 17.26 K WEIGHT OF SHELL Ws = 51.29 K
WT OF ROOF AND FRAMING = 12.89 K
WT OF FLOATING PAN/ROOF Wpan = 10.87 K
ROOF SNOW LOAD = 29.79 K
TOTAL WEIGHT OF ROOF INCLUDING
FRAMING AND 10% OF BALANCED
ROOF DESIGN SNOW LOAD Wr = 15.86 K API 650 E2.2
PRODUCT STORAGE = Jet A FILL HEIGHT Hf = 35.917 FT
PRODUCT SPECIFIC GRAVITY G = 0.84
WEIGHT OF CONTENTS Wp = π (D^2 / 4) (Hf) Уw (G) / 1000
= π (42.5^2 / 4) (35.917) (62.4) (0.84) / 1000 = 2,670.74 K
E.6.1.1 EFFECTIVE WEIGHT OF PRODUCT
IMPULSIVE WEIGHT Wi
FOR D/H > 1.333
Wi = {tanh [0.866 (D/H)] / 0.866 (D/H)} Wp E.6.1.1-1
FOR D/H < 1.333
Wi = [1.00 - 0.218 (D/H)] Wp E.6.1.1-2
D/H = 1.183 < 1.333 E.6.1.1-2 GOVERNS
Wi = [1.00 - 0.218 (42.5/35.917)] 2670.74 = 1,981.81 K
CONVECTIVE (SLOSHING) WEIGHT Wc
Wc = 0.230 (D/H) tanh(3.67H/D) Wp E.6.1.1-3
Wc = 0.230 (42.5/35.917) tanh[(3.67) 35.917/42.5] 2670.7= 723.92 K
ENTERPRISE ENGINEERING, INC. PRINTED: 8/8/2019
Seismic Unanchored Tank - PAGE 27
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
SEISMIC EVALUATION: UN-ANCHORED TANK
E.6 DESIGN
E.6.1.2.1 CENTER OF ACTION FOR RINGWALL OVERTURNING MOMENT
THE RINGWALL MOMENT, Mrw, IS THE PORTION OF THE TOTAL OVERTURNING MOMENT THAT ACTS AT THE BASE OF THE TANK SHELL PERIMETER. THIS MOMENT IS USED TO DETERMINE LOADS ON A RINGWALL FOUNDATION, THE TANK ANCHORAGE FORCES, AND TO CHECK THE LONGITUDINAL SHELL COMPRESSION.
HEIGHT TO THE CENTER OF THE IMPULSIVE FORCE Wi
Xi = HEIGHT FROM BOTTOM OF SHELL TO CENTER OF IMPULSIVE FORCE Wi
FOR D/H > 1.333
Xi = 0.375H E.6.1.2.1-1
FOR D/H < 1.333
Xi = [0.5 -0.094(D/H)] H E6.1.2.1-2
D/H = 1.183 < 1.333 E.6.1.2.1-2 GOVERNS
Xi = [0.5-0.094(42.5/35.917)] = 13.964 FT
HEIGHT TO THE CENTER OF THE CONVECTIVE FORCE WC
Xc = HEIGHT FROM BOTTOM OF SHELL TO CENTER OF CONVECTIVE FORCE Wc
Xc = [1.0 - {(cosh(3.67H/D) -1) / ((3.67H/D) sinh(3.67H/D)) } ] H E.6.1.2.1-3
Xc = [1.0 - {(cosh((3.67) (35.917/42.5)) -1) / ((3.67) (35.917/42.5) sinh((3.67) (35.917/42.5)) } ] (35.917)
Xc = 25.334 FT
ENTERPRISE ENGINEERING, INC. PRINTED: 8/8/2019
Seismic Unanchored Tank - PAGE 28
REV 6/14/2019
PROJECT: In-Service API 653 Inspection PREPARED BY: SCK LOCATION: JB Andrews, MD DATE: 5/1/2019
EEI PROJECT NO: 9364
CHECKED BY: JEH
TANK NO: 10 DATE: 08/08/19
SEISMIC EVALUATION: UN-ANCHORED TANK
E.6 DESIGN
E.6.1.2.2 CENTER OF ACTION FOR SLAB OVERTURNING MOMENT
THE SLAB MOMENT, Ms, IS THE TOTAL OVERTURNING MOMENT ACTING ACROSS THE ENTIRE TANK BASE CROSS SECTION. THIS OVERTURNING MOMENT IS USED TO DESIGN SLAB AND PILE CAP FOUNDATIONS.
HEIGHT TO THE CENTER OF THE IMPULSIVE FORCE Wi
Xis = HEIGHT FROM BOTTOM OF SHELL TO CENTER OF…