Attachment I WPB VAMC Security Record Docs.pdf

PDF 11 MB Posted

Attached to
Z1DA--FY22: NRM (PROJ: 548-22-109) INSTALL FIBER OPTICS AND SWITCHES FOR SECURITY CAMERAS (VA-22-00023048)
Solicitation number
36C24822Q0184
Issued by

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LOCATION:

BY:

SUBMISSION / DATE:

JL

C&O

Joseph, Lawrence & Co

Consulting Engineers 317 RIVEREDGE BLVD. SUITE 110. COCOA, Florida 32922 Tel: 321.972.4466 . www.jlceng.com . CA No. 32770

Space Coast

DRAWING

NUMBER DRAWING TITLE

--- COVER SHEET

3130 Seminole Road, Fort Pierce, FL 34951 Tel: 866-977-7555 | VenergyGroup.com

NOTE: THESE DOCUMENTS IN ADDITION TO THE CONTRACTOR PROVIDED

SUPPLEMENTARY INFORMATION CONSTITUTE THE RECORD

DOCUMENTS/AS-BUILTS FOR THIS PROJECT.

AutoCAD SHX Text

DRAWING INDEX

AutoCAD SHX Text E000

AutoCAD SHX Text

ELECTRICAL LEGEND

AutoCAD SHX Text E001

AutoCAD SHX Text

ELECTRICAL SPECIFICATIONS

AutoCAD SHX Text E100A

AutoCAD SHX Text

BASEMENT FLOOR PLAN - AREA A - ELECTRICAL

AutoCAD SHX Text E100B

AutoCAD SHX Text

BASEMENT FLOOR PLAN - AREA B - ELECTRICAL

AutoCAD SHX Text E101A

AutoCAD SHX Text

FIRST FLOOR PLAN - AREA A - ELECTRICAL

AutoCAD SHX Text E101B

AutoCAD SHX Text

FIRST FLOOR PLAN - AREA B - ELECTRICAL

AutoCAD SHX Text E102A

AutoCAD SHX Text

SECOND FLOOR PLAN - AREA A - ELECTRICAL

AutoCAD SHX Text E102B

AutoCAD SHX Text

SECOND FLOOR PLAN - AREA B - ELECTRICAL

AutoCAD SHX Text E103A

AutoCAD SHX Text

THIRD FLOOR PLAN - AREA A - ELECTRICAL

AutoCAD SHX Text E103B

AutoCAD SHX Text

THIRD FLOOR PLAN - AREA B - ELECTRICAL

AutoCAD SHX Text E104A

AutoCAD SHX Text

FORTH FLOOR PLAN - AREA A - ELECTRICAL

AutoCAD SHX Text E104B

AutoCAD SHX Text

FORTH FLOOR PLAN - AREA B - ELECTRICAL

AutoCAD SHX Text E105

AutoCAD SHX Text

FIFTH FLOOR PLAN - ELECTRICAL

AutoCAD SHX Text E106

AutoCAD SHX Text

SIXTH FLOOR PLAN - ELECTRICAL

AutoCAD SHX Text E107

AutoCAD SHX Text

SEVENTH FLOOR PLAN - ELECTRICAL

AutoCAD SHX Text E108

AutoCAD SHX Text

EIGHTH FLOOR PLAN - ELECTRICAL

AutoCAD SHX Text E109

AutoCAD SHX Text

NINTH FLOOR PLAN - ELECTRICAL

AutoCAD SHX Text E201

AutoCAD SHX Text

ELECTRICAL DETAILS

AutoCAD SHX Text

VA PROJECT #: 548-19-110

AutoCAD SHX Text

WPB VAMC - INSTALL BUILDING SECURITY CONTROLS

AutoCAD SHX Text

WEST PALM BEACH VA MEDICAL CENTER | 7305 N MILITARY TRL, RIVIERA BEACH, FL 33410

AutoCAD SHX Text

RECORD DOCUMENTS : 02/09/2021

GENERAL NOTES

DESCRIPTIONSYMBOL

1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE LATEST ADOPTED EDITION OF THE NATIONAL ELECTRICAL CODE

(NFPA 70), AND THE LATEST ADOPTED EDITION OF THE FLORIDA BUILDING CODE.

2. CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND COORDINATE WITH EXISTING EQUIPMENT PRIOR TO BIDDING.

3. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED

THIRD-PARTY TESTING AGENCY.

BUILDING:

4. INSTALLATION HEIGHT OF EQUIPMENT (TO CENTERLINE) ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE SHALL BE:

RECEPTACLE = 18"

CLOCK = 7'-6"

SWITCH = 44"

MODULAR JACK FOR WALL MOUNTED TELEPHONE = 52"

MODULAR TELEPHONE JACK = 18"

TELEVISION OUTLET = 84"

COMPUTER OUTLET = 18"

CALL SWITCH = 44"

REMOTE TEST STATION FOR DUCT DETECTOR = 52"

C = ABOVE COUNTER BACKSPLASH, COORDINATE WITH ARCHITECTURAL ELEVATIONS AND MILLWORK.

5. ALL CONDUIT AND WIRING SHALL BE CONCEALED IN WALLS OR ABOVE CEILINGS UNLESS NOTED OTHERWISE OR APPROVED BY THE ARCHITECT/ENGINEER. ALL DEVICE OUTLET BOXES SHALL BE RECESSED UNLESS NOTED OTHERWISE OR APPROVED BY THE ARCHITECT/ENGINEER. WHERE APPROVED OR NOTED SURFACE METAL RACEWAY AND DEVICE BOXES SHALL BE USED IN LIEU OF CONDUIT AND CONCEALED BOXES AT NO EXTRA COST TO THE OWNER.

6. ALL CONDUIT ROUTES SHOWN ARE APPROXIMATE ONLY. CONTRACTOR SHALL FIELD VERIFY FINAL ROUTE.

7. CONDUIT RUNS SHOWN ARE SCHEMATIC AND DO NOT INDICATE THE NECESSARY FITTINGS AND JUNCTION BOXES THAT

ARE INCLUDED IN THE SCOPE OF THE WORK.

8. CONTRACTOR SHALL PERMANENTLY IDENTIFY ALL WIRING WITH THE SOURCE AND CIRCUIT AT ALL ELECTRICAL EQUIPMENT, PULL AND JUNCTION BOXES AND ELECTRICAL TERMINATIONS PROVIDED OR ASSOCIATED WITH THIS

CONSTRUCTION.

9. CONTRACTOR SHALL PATCH AND REPAIR ALL DAMAGED SURFACES AND AREAS WHERE EQUIPMENT WAS REMOVED OR

MODIFIED, TO MATCH EXISTING CONDITIONS.

10. ALL ABANDONED AUDIO OR CONTROL CABLES SHALL BE REMOVED. ALL BOX OR EQUIPMENT OPENINGS SHALL BE CLOSED

WITH LISTED CLOSURE DEVICE AS APPROVED BY THE EQUIPMENT MANUFACTURER.

11. WHERE EXISTING EQUIPMENT OR MATERIALS ARE REMOVED OR CHANGED, ALL BRANCH CONDUITS WHICH NO LONGER ARE IN SERVICE, SHALL BE REMOVED AS DIRECTED BY THE ENGINEER. IF, IN THE COURSE OF THIS WORK, OUTLETS ARE COVERED UP OR OTHERWISE RENDERED INACCESSIBLE, ALL WIRING TO SAME SHALL BE REMOVED TO THE SOURCE. IF A CIRCUIT THAT MUST REMAIN IN SERVICE IS INTERRUPTED THEREBY, IT SHALL BE RECONNECTED BY THE MOST INCONSPICUOUS MEANS SO AS TO REMAIN OPERATIONAL, WITH THE SAME CAPACITY AS BEFORE. ALL BUILDING SURFACES DAMAGED, AND OPENINGS LEFT BY REMOVAL OF BOXES, PIPING OR OTHER EQUIPMENT SHALL BE REPAIRED BY THE CONTRACTOR. ALL HOLES LEFT IN JUNCTION BOXES, SWITCHES, PANELS, ETC. SHALL BE CLOSED.

12. ALL REUSABLE DEVICES, FIXTURES AND EQUIPMENT SHALL BECOME THE PROPERTY OF THE OWNER. ALL OTHER

SALVAGE AND DEBRIS SHALL BE REMOVED FROM THE PREMISES DAILY.

13. THIS CONTRACTOR SHALL FURNISH AND PROVIDE ALL DEMOLITION REQUIRED TO ACCOMMODATE THIS PROJECT

WHETHER INDICATED ON DRAWINGS, OR DIRECTED IN THE FIELD.

GROUNDING:

14. ALL METAL RACEWAYS, INCLUDING CONDUIT, WIRE TROUGHS, WIREMOLD, ETC., SHALL BE GROUNDED. ALL CONNECTIONS IN METAL RACEWAYS SHALL BE COMPLETED IN SUCH A MANNER AS TO MAINTAIN A CONTINUOUS PATH TO GROUND

THROUGHOUT THE ENTIRE LENGTH OF THE RACEWAY.

WIRING:

15. UNLESS NOTED OTHERWISE ON THE DRAWINGS OR ON THE EQUIPMENT WIRING SCHEDULE, EACH BRANCH CIRCUIT HOME RUN SHALL BE THREE (3) #12 AWG THHN/THWN (1 HOT, 1 NEUTRAL & 1 EQUIPMENT GROUND) IN 3/4" EMT CONDUIT.

PROTECT EACH CIRCUIT WITH A 20 AMPERE, 1-POLE OVERCURRENT DEVICE UNLESS NOTED OTHERWISE. COMBINED

NEUTRALS ARE NOT PERMITTED.

EXISTING DEVICES TO REMAIN:

16. UNLESS OTHERWISE NOTED:

a. ON DEMOLITION AND NEW WORK PLANS - DEVICES AND EQUIPMENT SHOWN IN LIGHT LINETYPE ARE EXISTING TO

REMAIN.

b. ON DEMOLITION PLANS - DEVICES AND EQUIPMENT SHOWN IN DARK LINETYPE ARE EXISTING TO BE REMOVED

c. ON NEW WORK PLANS - DEVICES AND EQUIPMENT SHOWN IN DARK LINETYPE ARE NEW.

ABBREVIATIONS

DESCRIPTIONSYMBOL

CH COUNTER HEIGHT

ELECTRIC WATER COOLEREWC

H.I.D.

COMPACT FLUORESCENT LAMPCFL

A

A/C

AC

AFF

AFG

AHU

AWG

C

CONC

COND

CU

DISC

ELEC

EM

EMS

EMT

EF

EX

FA

AMPERES

AIR CONDITIONING

ALTERNATING CURRENT

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

AMERICAN WIRE GAUGE

CONDUIT

CONCRETE

CONDUIT

COPPER

DISCONNECT

ELECTRICAL

EMERGENCY

ENERGY MANAGEMENT SYSTEM

ELECTRICAL METALLIC TUBING

EXHAUST FAN

EXISTING

FIRE ALARM

G

GFI

GND

J

KAIC

KVA

KW

NL

NEMA

NFPA

GROUND

GROUND FAULT INTERRUPTER

GROUND

O.C.

P

PNL

PVC

RM

RGS

SPEC

SS

TYP

UON

V

W

WP

FIRE ALARM ANNUNCIATOR PANELFAAP

ENCLOSED CIRCUIT BREAKERECB

I.G.

TVSS

ETR

HIGH INTENSITY DISCHARGE

GRC

HVAC

LTG

MCM

MCU

MH

N

NA

NF

NEC

NIC

GALVANIZED RIGID CONDUIT

JUNCTION

KILOVOLT-AMPERES

KILOWATT

LIGHTING

THOUSANDS OF CIRCULAR MILS

MASTER CONTROL UNIT

METAL HALIDE

NEUTRAL

NOT APPLICABLE

NON-FUSED

NATIONAL ELECTRICAL CODE

NOT IN CONTRACT

NIGHT LIGHT

NATIONAL FIRE PROTECTION ASSOCIATION

ON CENTER

POLE

PANELBOARD

POLYVINYL CHLORIDE

ROOM

RIGID GALVANIZED STEEL

SPECIFICATION

STAINLESS STEEL

TYPICAL

UNLESS OTHERWISE NOTED

VOLTS

WIRE

WEATHERPROOF

MOTOR CIRCUIT PROTECTIONMCP

ISOLATED GROUND

TRANSIENT VOLTAGE SURGE SUPPRESSION

O.F.C.I. OWNER FURNISHED CONTRACTOR INSTALLED

FIRE ALARM CONTROL PANELFACP -

NATIONAL ELECTRIC MANUFACTURERS ASSOCIATION

HEATING, VENTILATING, AND AIR CONDITIONING

(THOUSAND) AMPERE INTERRUPTING CAPACITY

EXISTING TO REMAIN

SYMBOLS SHOWN ON THIS ELECTRICAL LEGEND ARE FOR

REFERENCE PURPOSES ONLY. ALL OF THESE SYMBOLS MAY NOT BE

USED FOR THIS PROJECT.

NOTE:

PANELS

DESCRIPTIONSYMBOL

DESCRIPTIONSYMBOL

WIRING AND POWER

XXX

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

SECURITY ALARM CONTROL PANEL

MASTER CLOCK CONTROL PANEL

PUBLIC ADDRESS CONTROL PANEL

FAAP

FACP

SACP

PA

MC

MAIN DISTRIBUTION PANEL (SEE PANEL SCHEDULE)

AUTOMATIC TRANSFER SWITCH

NEW ELECTRICAL PANEL

ELECTRICAL SYSTEMS PANEL

SURGE PROTECTION DEVICESPD

MDP

SPD

TYPE X X

POWER LEG ONLY (NO SWITCH LEG BETWEEN ROOMS)

DISCONNECT SWITCH - WEATHERPROOF (NEMA 3R)

COMBINATION VARIABLE SPEED DRIVE AND DISCONNECT

WATER HEATER

HVP1-6

MAGNETIC MOTOR STARTER

COMBINATION FUSED DISCONNECT/

MOTOR WITH DESIGNATOR

MAGNETIC STARTER SWITCH

TIME CLOCK

MANUAL STARTER

START/STOP

HAND/OFF/AUTO

FUSED DISCONNECT SWITCH

VARIABLE SPEED DRIVE

SS

EF-1

M

WP

HOA

POWER POLE

PLUG MOLD

DISCONNECT SWITCH

JUNCTION BOX

COUNTER HEIGHT

COUNTER HEIGHTC

C

GROUND FAULT CIRCUIT INTERRUPTER

GROUND FAULT CIRCUIT INTERRUPTER

GROUND FAULT CIRCUIT INTERRUPTER

OCCUPANCY SENSOR SWITCH

SINGLE POLE WEATHERPROOF SWITCH

COUNTER HEIGHT (ABOVE COUNTER OR 42" AFF)

COUNTER HEIGHT (ABOVE COUNTER OR 42" AFF)

COUNTER HEIGHT (ABOVE COUNTER OR 42" AFF)

ISOLATED GROUNDIG

SPECIAL RECEPTACLE

QUADRAPLEX RECEPTACLE

ISOLATED GROUND

WEATHERPROOF

C

IG

WP

GFI

EWC

C

WEATHERPROOF

ISOLATED GROUND

WEATHERPROOF

DUPLEX RECEPTACLE

SINGLE RECEPTACLE

GFI

WP

C

IG

WP

GFI

SINGLE POLE KEYED SWITCH

THREE WAY TOGGLE SWITCH

TWO POLE TOGGLE SWITCH

SINGLE POLE TOGGLE SWITCH

OS

K

(NONE)

WP

SWITCH

MANUAL MOTOR CONTROLLER W/O OVERLOADSM

RECESSED FLOOR MOUNTED DUPLEX RECEPTACLE

SURFACE-MOUNTED FLOOR DUPLEX RECEPTACLE

CEILING-MOUNTED DUPLEX RECEPTACLE

LOWER CASE LETTERS INDICATES SWITCHING DESIGNATIONS, QUANTITY OF LETTERS EQUAL

QUANTITY OF GANGED SWITCHES

ELECTRIC WATER COOLER, COORDINATE LOCATION WITH PLUMBING CONTRACTOR

BRANCH CIRCUIT HOME RUN WITH PANEL NAME AND CIRCUIT NUMBER, QUANTITY OF

ARROWHEADS DENOTES QUANTITY OF BRANCH CIRCUITS

BRANCH CIRCUIT WIRING, PROVIDE QUANTITIES OF CONDUCTORS REQUIRED FOR CIRCUITING

AND SWITCHING INDICATED

S abcS

J

HALF SWITCHED DUPLEX RECEPTACLE

(FURNISHED UNDER DIV 15 UNLESS NOTED OTHERWISE)

ELECTRIC UNIT HEATER

TYPE "K" TRANSFORMER

MUSHROOM HEAD PUSH BUTTON

RELAY

GROUND ROD

TRANSFORMER

(EMERGENCY STOP)

WIRE IN CONDUIT CONCEALED BELOW SLAB OR GRADE

ELECTRICAL LEGEND

E-000

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

M :\P ro je ct S er ve r\P ro je ct s\

\J

LS

C

.0

.0

- V en er gy G ro up

, V

AM

C W

PB

B ui ld in g

Se cu rit y

C on tro ls

In st al la tio n

- W es t P al m B ea ch

, F L\

D ra w in gs \E le ct ric al

\E -0

.d w g

2/ 9/

:2

0:

P M

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseENGINEER OF RECORD STAMPCONTRACTOR

321 4 5 6 7 8 9 10

WPB VAMC - INSTALL BUILDING

SECURITY CONTROLS

West Palm Beach VA Medical Center

548-19-110

Project Director

Revisions: Date:

ELECTRICAL ENGINEER:

LAWRENCE M. STOFF

P.E. #: 78586

Blake Lawrence Suddeth P.E. #: 69060

Blake Lawrence Suddeth P.E. #: 69060

BLS LMSMay 14th, 2020

1JL

C&O

Joseph, Lawrence & Co

Consulting Engineers 317 RIVEREDGE BLVD. SUITE 110. COCOA, Florida 32922 Tel: 321.972.4466 . www.jlceng.com . CA No. 32770

Space Coast

100% CONSTRUCTION

DOCUMENTS

3130 Seminole Road, Fort Pierce, FL 34951 Tel: 866-977-7555 | VenergyGroup.com

RECORD DOCUMENTS 02/09/21

LOW VOLTAGE DEVICES

DESCRIPTIONSYMBOL

CAMERA TYPE / VIEW ANGLE

ACCESS CONTROL DEVICE (KEYPAD,CARD READER, FAB READER OR SIMILAR)

SECURITY CAMERA

DOME / 180° / 360°

CR

AutoCAD SHX Text

ATS

AutoCAD SHX Text

XXX

AutoCAD SHX Text

TC

AutoCAD SHX Text

WH

AutoCAD SHX Text

VSD

AutoCAD SHX Text

VSD

AutoCAD SHX Text

PP

AutoCAD SHX Text T

AutoCAD SHX Text

UH

AutoCAD SHX Text T

AutoCAD SHX Text K

R

ELECTRICAL SPECIFICATIONS

E-001

ELECTRICAL SPECIFICATIONS

I. GENERAL REQUIREMENTS:

A. DO ALL WORK IN COMPLIANCE WITH THE LATEST ADOPTED EDITION (BY THE VA) OF THE BUILDING CODE, NFPA 70 AND NFPA 101 , AND THE REGULATIONS OF THE LOCAL UTILITY TELEPHONE, CABLE TELEVISION AND POWER UTILITY COMPANIES. OBTAIN AND PAY FOR ANY AND ALL REQUIRED PERMITS, INSPECTIONS, CERTIFICATES OF INSPECTIONS AND APPROVAL, AND THE LIKE, AND DELIVER SUCH

CERTIFICATES TO THE ENGINEER.

B. THE CONTRACTOR SHALL FURNISH, PERFORM, OR OTHERWISE PROVIDE ALL LABOR (INCLUDING, BUT NOT

LIMITED TO, ALL PLANNING, PURCHASING, PAINTING, TRANSPORTING, RIGGING, HOISTING,

STORING, INSTALLING, TESTING, CHASING, CHANNELING, CUTTING, TRENCHING, EXCAVATING AND BACKFILLING), COORDINATION, FIELD VERIFICATION, EQUIPMENT INSTALLATION, SUPPORT, AND SAFETY, SUPPLIES, AND MATERIALS NECESSARY FOR THE CORRECT INSTALLATION OF COMPLETE AND FUNCTIONAL ELECTRICAL SYSTEMS (AS DESCRIBED OR IMPLIED BY THESE SPECIFICATIONS

AND THE APPLICABLE DRAWINGS).

C. ALL DRAWINGS AND SPECIFICATIONS ON THE PROJECT ARE COMPLEMENTARY, EACH TO ALL OTHER

SETS, AND THEY SHALL BE USED IN COMBINATION FOR THE EXECUTION OF THIS WORK.

DIVISION 16 WORK SHOWN ON ANY ONE SET OF DRAWINGS, INCLUDING ALL ARCHITECTURAL

DRAWINGS, MECHANICAL, PLUMBING AND FIRE PROTECTION DRAWINGS FOR GENERAL WORK AND

EQUIPMENT, AND DIVISION 16 WORK CALLED FOR UNDER ANY SECTION OF THE PROJECT

SPECIFICATIONS, SHALL BE CONSIDERED AS INCLUDED IN THIS WORK UNLESS SPECIFICALLY

EXCLUDED BY INCLUSION IN SOME OTHER BRANCH OF THE WORK. THIS SHALL INCLUDE

ROUGHING-IN FOR CONNECTIONS AND EQUIPMENT AS CALLED FOR OR INFERRED. THE

CONTRACTOR SHALL CHECK ALL DRAWINGS AND SPECIFICATIONS FOR THE PROJECT AND SHALL BE

RESPONSIBLE FOR THE INSTALLATION OF ALL DIVISION 16 WORK.

D. THE CONTRACTOR SHALL CAREFULLY CHECK THE DRAWINGS AND SPECIFICATIONS OF ALL OTHER

TRADES AND DIVISIONS BEFORE INSTALLING ANY OF HIS WORK. HE SHALL IN ALL CASES

CONSIDER THE WORK OF ALL OTHER TRADES, AND SHALL COORDINATE HIS WORK WITH THEM SO THAT THE BEST ARRANGEMENTS OF ALL EQUIPMENT, PIPING, CONDUIT, DUCTS, ROUGH-IN, ETC., CAN BE OBTAINED.

E. LOCATIONS DESIGNATED FOR OUTLETS, SWITCHES, DEVICES, EQUIPMENT, ETC., ARE

APPROXIMATE AND FINAL LOCATIONS SHALL BE VERIFIED IN THE FIELD. CONTRACTOR SHALL

LOCATE ALL DEVICES UP TO 5 FEET IN ANY DIRECTION AS DIRECTED BY OWNER AND PER CODE.

WHERE INSTRUCTIONS OR NOTES ARE INSUFFICIENT TO CONVEY THE INTENT OF THE DESIGN,

CONSULT THE OWNER PRIOR TO BIDDING AND INSTALLATION.

F. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING AND COORDINATING THE LOCATIONS OF DEVICES TO BE USED AND COORDINATING THE FINAL LOCATIONS OF ELECTRICAL EQUIPMENT WITH MILLWORK, SINKS, BENCHES, COUNTERS AND SHELVING PRIOR TO BIDDING AND INSTALLATION.

ALL DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER.

G. DIVISION 16 CONTRACTOR SHALL HAVE HAD EXPERIENCE OF AT LEAST THE SAME SIZE AND SCOPE AS THIS PROJECT, ON AT LEAST TWO OTHER PROJECTS WITHIN THE LAST FIVE YEARS IN

ORDER TO BE QUALIFIED TO BID THIS PROJECT.

H. CONTRACTOR SHALL AND DOES HEREBY WARRANT ALL MATERIALS AND EQUIPMENT FURNISHED UNDER THIS SECTION OF THE SPECIFICATIONS TO BE FREE FROM DEFECTS AND TO FUNCTION OR OPERATE SATISFACTORILY FOR ONE YEAR AFTER FINAL ACCEPTANCE OF THE WORK, AND THAT ANY

ITEMS NOT MEETING THIS REQUIREMENT WILL BE MADE GOOD BY HIM WITHOUT COST TO

OWNER, PROVIDED SUCH DEFECTS OR FAILURES ARE NOT DUE TO ABUSE, NEGLECT, OR LACK OF

REASONABLE AND ORDINARY MAINTENANCE.

I. ALL WORK SHALL BE EXECUTED IN A WORKMANSHIP MANNER DISPLAYING A NEAT

MECHANICAL APPEARANCE UPON COMPLETION.

J. BALANCE TOTAL PHASE LOADS IN EACH ELECTRICAL PANEL TO A VALUE WITHIN 10% OF EACH OTHER.

K. THE CONTRACTOR SHALL PROVIDE ADEQUATE PROTECTION, WHEREVER WORK IS TO BE

PERFORMED IN FINISHED/OCCUPIED SPACES, TO PREVENT DAMAGE TO ADJACENT AREAS,

EQUIPMENT, OR FURNISHINGS; TO PREVENT ACCIDENTAL INJURY TO BUILDING OCCUPANTS AND THE PUBLIC; TO PREVENT THE SPREADING OF DUST, DIRT, DEBRIS, AND MOISTURE FROM THE

AREA WHERE WORK IS BEING PERFORMED; AND TO PREVENT DUST, DIRT, DEBRIS, AND

MOISTURE FROM GETTING ON OR IN THE BUILDING OCCUPANT'S FURNISHINGS OR EQUIPMENT.

L. THE CONTRACTOR SHALL REPAIR, AT NO COST TO THE OWNER, ANY DAMAGE DONE BY HIMSELF

OR HIS EMPLOYEES. HE SHALL ALSO BE RESPONSIBLE FOR ALL CUTTING AND PATCHING

REQUIRED TO PROPERLY INSTALL HIS WORK. THIS SHALL ALSO INCLUDE THE PATCHING OF EXISTING ROADWAYS (PAVED OR IMPROVED), PARKING AREAS, SIDEWALKS, WALLS, STAIRS, MECHANICAL WORK, CURBS, GUTTERS, ETC., CUT TO INSTALL WORK PROVIDED BY THE CONTRACTOR. PATCH

WORK SHALL COMPLY WITH THE APPLICABLE SECTIONS OF THESE SPECIFICATIONS AND SHALL

MATCH THE EXISTING FINISHES.

M. UPON COMPLETION OF WORK, THE ENTIRE WIRING SYSTEM SHALL BE TESTED, AND SHALL BE SHOWN TO BE IN PROPER WORKING CONDITION IN ACCORDANCE WITH INTENT OF SPECIFICATIONS AND DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO HAVE ALL SYSTEMS

READY FOR OPERATION AND TO HAVE AN ELECTRICIAN AVAILABLE TO OPERATE SAME IN

ACCORDANCE WITH AND UNDER THE SUPERVISION OF THE INSPECTION REPRESENTATIVE OF THE ENGINEER. THE CONTRACTOR SHALL BE AVAILABLE TO ASSIST IN REMOVAL OF PANEL FRONTS, ETC., TO PERMIT INSPECTION AS REQUIRED.

N. IN ACCORDANCE WITH DIVISION 1 AND THE CONDITIONS OF THE CONTRACT, THE CONTRACTOR SHALL PROVIDE AND KEEP UP TO DATE A COMPLETE RECORD SET OF CONSTRUCTION "AS-BUILTS"

BLUELINE PRINTS WHICH SHALL BE CORRECTED DAILY, AND SHALL SHOW EVERY CHANGE FROM

THE ORIGINAL CONTRACT DRAWINGS, INCLUDING ADDENDA AND CHANGE ORDERS IN

ACCORDANCE WITH GENERAL REQUIREMENTS AND SPECIAL CONDITIONS. THIS SET OF

PRINTS SHALL BE KEPT ON THE JOB SITE, AND SHALL BE USED ONLY AS A RECORD SET. THIS SHALL NOT BE CONSTRUED AS AUTHORIZATION FOR THE CONTRACTORS TO MAKE CHANGES IN THE

LAYOUT WITHOUT DEFINITE INSTRUCTION IN EACH CASE.

II. ELECTRICAL SCOPE:

A. FURNISHING AND INSTALLATION OF POWER SYSTEMS, AND AUXILIARY SYSTEMS AS SHOWN

OR HEREIN SPECIFIED.

B. CONNECTION OF ALL EQUIPMENT REQUIRING ELECTRICAL CONNECTION, MENTIONED IN THIS

DIVISION OR SHOWN ON DRAWINGS, WHETHER FURNISHED BY DIVISION 16 OR UNDER

OTHER DIVISIONS, OR FURNISHED BY OWNER.

C. FURNISHING AND INSTALLATION OF OUTLET BOXES, CONDUIT RACEWAYS, FOR A TELEPHONE AND DATA RACEWAY DISTRIBUTION SYSTEM. (TELEPHONE AND DATA HARDWARE, AS WELL AS WIRING AND SOFTWARE

IS NOT INCLUDED.)

D. THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR CONTACTING THE OFFICES OF ALL LOCAL AND/OR STATE AUTHORITIES HAVING JURISDICTION OVER THIS PROJECT IN ORDER TO SCHEDULE ALL REQUIRED INSPECTIONS AND OBTAIN ALL NECESSARY PERMITS, ETC. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER OF ALL SCHEDULED INSPECTIONS AT LEAST TWO WEEKS IN ADVANCE OF THE

SCHEDULED DATE.

E. THE CONTRACTOR SHALL REPLACE ANY DEFECTIVE MATERIALS, EQUIPMENT, OR WORKMANSHIP WITHOUT

COST TO THE OWNER WITHIN THE STIPULATED GUARANTEED PERIOD.

F. IT SHALL BE THE RESPONSIBILITY OF THE DIVISION 16 CONTRACTOR TO HAVE ALL SYSTEMS READY FOR OPERATION AND TO HAVE AN ELECTRICIAN AVAILABLE FOR ALL INSPECTIONS. THE CONTRACTOR SHALL PROVIDE PERSONNEL TO ASSIST IN REMOVAL OF PANEL FRONTS, ETC. TO PERMIT INSPECTION AS

REQUIRED.

G. SUBMIT TO THE ARCHITECT/ENGINEER PROMPTLY AFTER AWARD OF CONTRACT AND PRIOR TO

PURCHASING, SIX COPIES OF MANUFACTURER'S SHOP DRAWINGS IN ACCORDANCE WITH

DIVISION 1, SECTION 01300 - SUBMITTALS FOR THE FOLLOWING ITEMS. ALL SHOP DRAWINGS OF A SPECIFIC ITEM OR SYSTEM SHALL BE MADE IN ONE SUBMITTAL AND WITHIN TEN DAYS AFTER AWARD OF CONTRACT.

1. PANELBOARDS 4. DISCONNECT SWITCHES

2. SUPPORTS 5. CONDUIT

3. WIRING DEVICES 6. WIRE

H. COMPLETED WIRING SYSTEMS SHALL BE FREE FROM SHORT CIRCUITS AND AFTER COMPLETION, PERFORM TESTS FOR INSULATION RESISTANCE IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE. ALL WIRING SYSTEMS SHALL BE COMPLETELY AND TOTALLY "SAFED"

DURING CONSTRUCTION. ONLY QUALIFIED PERSONNEL SHALL HANDLE ELECTRICAL SYSTEMS.

E. MOUNTING HEIGHTS ARE APPROXIMATE. THE EXACT LOCATIONS AND MOUNTING HEIGHTS SHALL BE DETERMINED ON THE JOB AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE WITH ALL TRADES TO INSURE CORRECT INSTALLATION, I.E., OVER COUNTERS IN OR ABOVE BACK-SPLASHES, IN BLOCK WALLS, TILE, AND OTHER SPECIFIC CONSTRUCTION FEATURES. LOCATION OF OUTLETS MOUNTED IN BUILT-INS, MILLWORK, AND CABINETRY SHALL BE VERIFIED. OUTLETS MOUNTED IN KICK OR TOE SPACES SHALL BE MOUNTED HORIZONTALLY. OUTLET BOXES SHALL BE MOUNTED TO PREVENT DEVICE PLATE FROM OVERLAPPING BACKSPLASH, TRIM, TILE, ETC. LOCATE SO DEVICE PLATE WILL LAY FLAT

AGAINST SURFACE COMPLETELY AROUND THE PERIMETER OF PLATE.

F. OUTLETS, OTHER THAN THOSE COORDINATED WITH COUNTER TOPS, SHELVES, AND CABINETS, SHALL BE LOCATED WITH THE CENTER LINE OF OUTLET BOXES THE FOLLOWING DISTANCE ABOVE THE FINISHED

FLOOR, UNLESS OTHERWISE INDICATED:

1. RECEPTACLES, GENERAL: 1'-6" AFF

2. TELEPHONE OUTLETS: 1'-6" AFF

3. SWITCHES, GENERAL: 4'-0" AFF

V. RACEWAYS

A. SHALL BE GALVANIZED OUTSIDE AND INSIDE BY HOT DIPPING. E.M.T. SHALL BE ELECTRO-

GALVANIZED. CONDUITS SHALL BE AS MANUFACTURED BY REPUBLIC, PITTSBURGH STANDARD,

WHEATLAND, TRIANGLE, ALLIED, OR YOUNGSTOWN.

B. SHALL BE STANDARD THREADED TYPE, GALVANIZED OUTSIDE AND INSIDE BY HOT DIPPING.

THREADLESS AND CLAMP TYPE NOT ACCEPTABLE. SHALL BE AS MANUFACTURED BY RACO,

EFCOR, OR APPLETON.

C. SHALL BE STEEL THREADED COMPRESSION TYPE. ALL COUPLINGS AND CONNECTORS SHALL BE EFCOR OR RACO. PRESSURE INDENTED TYPE CONNECTORS OR CAST METAL WILL NOT BE APPROVED FOR

ANY LOCATION.

D. CONNECTORS SHALL HAVE PLASTIC INSULATED THROAT INSERTS.

E. THE USE OF METAL CLAD CABLE IS ACCEPTABLE IN LOCATIONS AS ACCEPTED BY THE NEC AND ALL LOCAL

JURISDICTIONAL CODES.

F. STEEL METAL CLAD CABLE, TYPE MC, EMPLOYING CIRCUIT CONDUCTORS #12 SOLID TO #2 AWG, SOLID OR

STRANDED COPPER WITH THHN INSULATION, AN INSULATED GREEN GROUNDING CONDUCTOR AND

GALVANIZED STEEL INTERLOCKED ARMOR CLADDING. THE CABLES SHALL BE SUITABLE FOR USE IN DRY LOCATIONS AT TEMPERATURES NOT EXCEEDING 90° C ON AD CIRCUITS UP TO 600 VOLTS IN ACCORDANCE WITH N.E.C., ARTICLE 334. THE CABLE SHALL BE ONE AND TWO HOUR FIRE RATED PER ANSI/UL 1479 FOR USE

IN WALL, CEILING AND FLOOR ASSEMBLIES.

G. FLEXIBLE METALLIC CONDUIT RACEWAYS MAY BE USED TO CONNECT HVAC UNITS LOCATED IN

INTERIOR MECHANICAL AREAS. MINIMUM SIZE 3/4".

H. CONDUIT SHALL BE SIZED IN ACCORDANCE WITH THE LATEST NATIONAL ELECTRICAL CODE EXCEPT THAT NO CONDUIT SHALL BE SMALLER THAN 3/4" UNLESS OTHERWISE NOTED. CONDUIT SHALL BE SIZED LARGER THAN REQUIRED ABOVE WHEN SO SHOWN ON THE DRAWINGS OR WHEN REQUIRED BY LOCAL CODE.

I. ANY CONDUIT STUBBED OUT FOR FUTURE SHALL BE CAPPED WITH A PLASTIC CAP AND MARKED WITH A 2" MINIMUM RED METAL TAG WHICH IDENTIFIES CONDUIT ORIGIN. CONDUITS STUBBED UP ABOVE GRADE OR ROOF SHALL BE TAGGED ON THE CONDUIT. CONDUIT STUBBED OUT BELOW GRADE SHALL BE TAGGED ON NEAREST BUILDING WALL, CURB, ETC., DIRECTLY OVER THE CONDUIT RUN. ALL EMPTY

CONDUITS SHALL HAVE PULL WIRES.

VI. SCHEDULE 40 RIGID PVC:

A. CONDUIT SHALL BE COMPOSED OF POLYVINYLCHLORIDE AND SHALL BE UL RATED TYPE 40 FOR

USE WITH 90EC RATED CONDUCTORS. CONDUIT SHALL CONFORM TO NEMA STANDARDS AND

APPLICABLE SECTIONS OF NEC.

B. INSTALLATION OF RIGID NON-METALLIC CONDUIT SHALL COMPLY WITH ARTICLE 347 OF THE

NATIONAL ELECTRICAL CODE (NFPA 70) AND THESE SPECIFICATIONS.

C. PROVIDE A CONTINUOUS, INSULATED, GROUNDING CONDUCTOR IN EVERY RIGID, NON-METALLIC

RACEWAY EVEN IF NOT SHOWN ON THE DRAWINGS. THE GROUNDING CONDUCTOR SHALL BE

CONNECTED TO GROUND AT EACH END OF THE RACEWAY IN ACCORDANCE WITH ARTICLE 250 OF

THE NATIONAL ELECTRICAL CODE (NFPA 70).

D. WHERE RIGID NON-METALLIC CONDUIT TRANSITIONS TO METALLIC CONDUIT, THE LOCATION OF THE

TRANSITION SHALL BE UNDERGROUND.

E. NO PVC CONDUIT SHALL BE RUN EXPOSED, OR ABOVE GRADE.

VII. WIRE AND CABLE 600 VOLT:

A. CONDUCTORS SHALL HAVE CURRENT CARRYING CAPACITIES AS PER NEC AND WITH 600 VOLT

INSULATION, #12 AVERAGE MINIMUM FOR 20 AMP CIRCUITS AND #14 FOR 15 AMP CIRCUITS

EXCEPT FOR CONTROLS, AND FIXTURE WIRE. CONDUCTORS SHALL BE COPPER.

B. #12 AND #10 SHALL BE SOLID, TYPE THW/THWN INSULATION.

C. #8 AND LARGER, AND ANY SIZE TO MOTORS SHALL BE STRANDED TYPE THW.

D. SHALL BE MADE WITH T & B STA-KON WIRE JOINTS, PT SERIES, COMPLETE WITH INSULATING

CAPS AND INSTALLED WITH WT161 TOOL OR WT2000 TOOL, IDEAL SUPER-NUTS (NOT WIRE

NUTS), IDEAL WING NUTS, OR BUCHANAN ELEC. PRODUCTS B CAP OR SERIES 2000 PRES-

SURE CONNECTORS COMPLETE WITH NYLON SNAP-ON INSULATORS AND INSTALLED WITH C24

PRESSURE TOOL.

E. ALL JOINTS AND SPLICES IN WIRE SHALL BE MADE WITH APPROVED SOLDERLESS CONNECTORS, AND COVERED SO THAT INSULATION IS OWNER APPROVED EQUAL TO CONDUCTOR INSULATION.

SPLICES SHALL NOT BE PERMITTED IN CONTROL, SECURITY, FIRE ALARM, TELEVISION OR

COMMUNICATIONS SYSTEMS, OR WHERE OTHERWISE NOTED. SPLICING OF WIRE OR CABLES WILL

NOT BE ALLOWED BELOW GRADE, INCLUDING IN BOXES BELOW GRADE.

F. BOTH CONDUCTORS AND CONDUITS SHALL BE CONTINUOUS FROM OUTLET TO OUTLET.

G. IN INSTALLING THE MAIN ELECTRICAL SERVICE, ADDITIONAL SLACK CONDUCTORS SHALL BE

PROVIDED AND TERMINATED AS REQUIRED BY ELECTRIC UTILITY FOR CONNECTION TO THEIR

EQUIPMENT. FIELD COORDINATE WITH UTILITY PRIOR TO INSTALLING CONDUCTORS.

H. IN INSTALLING PARALLEL CONDUCTORS IT IS MANDATORY THAT ALL CONDUCTORS MAKING UP THE

FEEDER BE EXACTLY THE SAME LENGTH, THE SAME SIZE AND THE SAME TYPE OF CONDUCTOR

WITH THE SAME INSULATION. FURTHER, EACH GROUP OF CONDUCTORS MAKING UP A PHASE OR

NEUTRAL MUST BE BONDED AT BOTH ENDS IN AN APPROVED MANNER.

I. CONDUCTOR SIZES INDICATED ON CIRCUIT HOMERUNS OR IN PANELBOARD SCHEDULES SHALL BE

INSTALLED OVER THE ENTIRE LENGTH OF THE CIRCUIT UNLESS NOTED OTHERWISE ON THE

DRAWINGS.

J. CONDUCTORS SHALL BE CONTINUOUS AND UNSPLICED WHERE INSTALLED IN CONDUIT. SPLICES SHALL OCCUR ONLY WITHIN WIRING TROUGHS, WIREWAYS, JUNCTION BOXES, OUTLET BOXES, OR EQUIPMENT ENCLOSURES WHERE SUFFICIENT ADDITIONAL ROOM IS PROVIDED FOR ALL SPLICES.

K. EACH BRANCH CIRCUIT AND FEEDER CONDUCTOR SHALL BE COLOR CODED. FOR CONDUCTOR

SIZES THRU NO. 6 AWG, THE INSULATION SHALL BE OF THE COLOR AS INDICATED BELOW. COLOR CODE SHALL BE STRICTLY ADHERED TO. FOR CONDUCTOR SIZES NO. 4 AWG AND LARGER, COLOR

CODED PHASE TAPE MAY BE APPLIED COMPLETELY AROUND THE CONDUCTOR INSULATION

WITHIN 8" OF EACH END OF THE CONDUCTOR AND IN EACH PULL OR JUNCTION BOX OR WHENEVER

CONDUCTORS ARE PHYSICALLY EXPOSED TO VIEW. GROUNDING CONDUCTORS AND GROUNDED

CONDUCTORS SHALL HAVE INSULATION COLOR AS INDICATED FOR SIZES THROUGH #6 AWG.

120/208 V, 3PHASE,4W

PHASE A, COLOR: BLACK

PHASE B, COLOR: RED

PHASE C, COLOR: BLUE

NEUTRAL, COLOR: WHITE

GROUND, COLOR: GREEN

I. BEFORE ROUGH-IN OF CIRCUITRY OR CONNECTING TO EQUIPMENT, FURNISHED UNDER THIS DIVISION, ANY OTHER DIVISION, OR BY THE OWNER, THE CONTRACTOR SHALL VERIFY THE ELECTRICAL

CHARACTERISTICS AND REQUIREMENTS OF THE EQUIPMENT BEING FURNISHED AND FOR THAT SPECIFIED AND

SHOWN ON THE DRAWINGS AND PROVIDE FOR PROPER ROUGH-IN AND CONNECTION.

J. THE ELECTRICAL CIRCUITS, COMPONENTS, AND CONTROLS FOR ALL EQUIPMENT ARE SELECTED AND SIZED, BASED ON THE EQUIPMENT SPECIFIED. IF SUBSTITUTIONS AND/OR EQUIVALENT EQUIPMENT ARE FURNISHED, IT SHALL BE THE RESPONSIBILITY OF ALL PARTIES CONCERNED, INVOLVED IN, AND FURNISHING THE SUBSTITUTE AND/OR EQUIVALENT EQUIPMENT TO VERIFY AND COMPARE THE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF THAT FURNISHED TO THAT SPECIFIED AND/OR SHOWN. IF GREATER CAPACITY OR MORE MATERIALS OR LABOR IS REQUIRED FOR THE ROUGH-IN, CIRCUITRY OR CONNECTIONS THAN FOR THE ITEM SPECIFIED AND PROVIDED FOR, THEN IT SHALL BE THE RESPONSIBILITY OF THE PARTIES INVOLVED IN PROVIDING THE SUBSTITUTE AND/OR EQUIVALENT ITEMS OF EQUIPMENT TO PROVIDE ALL COMPENSATION FOR ADDITIONAL CHARGES MADE FOR THE PROPER ROUGH-IN, CIRCUITRY AND CONNECTIONS FOR THE EQUIPMENT FURNISHED. NO ADDITIONAL CHARGES ABOVE THE BASE BID SHALL BE ALLOWED FOR SUCH REVISIONS.

K. EXCAVATION FOR UNDERGROUND ELECTRICAL STRUCTURES: CONFORM TO ELEVATIONS AND

DIMENSIONS SHOWN WITHIN A TOLERANCE OF PLUS OR MINUS 0.10'; PLUS A SUFFICIENT

DISTANCE TO PERMIT PLACING AND REMOVAL OF CONCRETE FORMWORK, INSTALLATION OF

SERVICES, OTHER CONSTRUCTION, AND FOR INSPECTION.

L. TRENCHING: EXCAVATE TRENCHES FOR ELECTRICAL INSTALLATIONS AS FOLLOWS:

1. EXCAVATE TRENCHES TO THE UNIFORM WIDTH, SUFFICIENTLY WIDE TO PROVIDE AMPLE WORKING ROOM AND A MINIMUM OF 6" TO 9" CLEARANCE ON BOTH SIDES OF RACEWAYS AND EQUIPMENT.

2. EXCAVATE TRENCHES TO DEPTH INDICATED OR REQUIRED.

3. LIMIT THE LENGTH OF OPEN TRENCH TO THAT IN WHICH INSTALLATIONS CAN BE MADE AND THE

TRENCH BACKFILLED WITHIN THE SAME DAY.

4. WHERE ROCK IS ENCOUNTERED, CARRY EXCAVATION BELOW REQUIRED ELEVATION AND BACKFILL

WITH A LAYER OF CRUSHED STONE OR GRAVEL PRIOR TO INSTALLATION OF RACEWAYS AND

EQUIPMENT. PROVIDE A MINIMUM OF 6" OF STONE OR GRAVEL CUSHION BETWEEN ROCK BEARING

SURFACE AND ELECTRICAL INSTALLATIONS.

M. THE CONTRACTOR SHALL PROVIDE ALL INSERTS FOR THE SUPPORT OF DIVISION 16

EQUIPMENT TO BE PLACED IN CONCRETE OR THROUGH CONCRETE SLABS AS CONSTRUCTION

PROGRESSES. HE SHALL PROVIDE ALL MISCELLANEOUS HANGING AND SUPPORTING HARDWARE. ALL ELECTRICAL WORK IS TO BE CONCEALED IN OR BUILT INTO GENERAL CONSTRUCTION SHALL BE PLACED AS CONSTRUCTION PROGRESSES. FAILURE OF THE CONTRACTOR TO COORDINATE WORK WITH OTHER TRADES AND THE PROJECT CONSTRUCTION PROGRESS SHALL MAKE HIM RESPONSIBLE FOR ALL COST OF CUTTING AND PATCHING, AS REQUIRED TO INSTALL WORK. NO STRUCTURAL MEMBER, MASONRY CONSTRUCTION OR

FINISHED WORK SHALL BE CUT OR ALTERED WITHOUT PRIOR WRITTEN APPROVAL BY THE

ARCHITECT/ENGINEER. CONTRACTOR SHALL FIRE RATE ALL PENETRATIONS THROUGH ALL FIRE RATED SLABS

OR WALLS PER THE INTENDED RATING.

N. THE CONTRACTOR SHALL SUPPLY AND SET INTO PLACE ALL WALL SLEEVES FOR CONDUITS

AND CEILING INSERTS FOR HANGERS IN AREAS OF NEW CONSTRUCTION AS BUILDING CONSTRUCTION PROGRESSES. INSTALL EQUIPMENT NOTED TO BE CONCEALED IN WALLS BEFORE WALLS ARE CONSTRUCTED IN

ORDER THAT WALLS MAY BE CONSTRUCTED AROUND CONDUITS, ENCLOSURES, ETC.

O. METALLIC MATERIALS SHALL BE PROTECTED AGAINST CORROSION. EQUIPMENT ENCLOSURES SHALL BE GIVEN RUST-INHIBITING TREATMENT AND STANDARD FINISH BY MANUFACTURER. ALUMINUM SHALL NOT BE USED ON CONTACT WITH EARTH, AND, WHERE CONNECTED TO DISSIMILAR METAL, SHALL BE PROTECTED BY SUITABLE FITTINGS AND TREATMENT. ALL FERROUS METALS SUCH AS ANCHORS, BOLTS, BRACES, BOXES, BODIES, CLAMPS, FITTINGS, GUARDS, NUTS, PINS, RODS, SHIMS, THIMBLES, WASHERS, AND MISCELLANEOUS PARTS, NOT OF STAINLESS STEEL OR NONFERROUS MATERIALS, SHALL BE HOT-DIPPED GALVANIZED.

P. ALL CONDUITS STUBBED OUT FOR FUTURE USE SHALL HAVE A PULL WIRE INSTALLED, A PLASTIC CAP

INSTALLED AND BE IDENTIFIED AS TO THE CONDUIT ORIGIN.

Q. THE RESPONSIBILITY FOR ANY CUTTING OF CONSTRUCTION WHICH IS REQUIRED FOR THE INSTALLATION OF DIVISION 16 WORK, SHALL BE BY THE CONTRACTOR. THE CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES AND THE OWNER BEFORE ANY CUTTING AND OBTAIN APPROVAL FROM THE ARCHITECT/ENGINEER

PRIOR TO ANY CUTTING. ALL PATCHING AND FINISHING SHALL BE BY THE CONTRACTOR.

R. WHERE OPENINGS OR HOLES ARE CUT IN CONSTRUCTION AND THE CUTTING BREAKS ELECTRICAL CIRCUITRY OR CONTROL CIRCUITRY CONDUIT AND WIRING, THEN IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REROUTE THE CIRCUITRY CONDUIT AND REWIRING AND TO COMPLETE THE CIRCUITRY AS REQUIRED AND AS APPROVED BY THE ARCHITECT/ENGINEER. TEMPORARY COMPLETION SHALL BE PROVIDED

WHERE NECESSARY BEFORE THE PERMANENT REROUTING AND COMPLETION WORK IS FINISHED.

S. ANY PENETRATIONS OF FIRE OR SMOKE RATED ASSEMBLIES MADE BY THIS CONTRACTOR IN VERTICAL OR HORIZONTAL CONSTRUCTION SHALL BE SEALED AND PROTECTED BY THIS CONTRACTOR IN ORDER TO MAINTAIN THE ESTABLISHED FIRE RATING WITH METHODS AS APPROVED BY THE AUTHORITY HAVING

JURISDICTION.

III. IDENTIFICATION:

A. IDENTIFICATION NAMEPLATES SHALL BE LAMINATED PLASTIC, SECURED TO EQUIPMENT WITH TWO

SCREWS.

B. EACH PANELBOARD AND SWITCHBOARD SHALL BE EQUIPPED WITH A PERMANENT PLASTIC NAMEPLATE

WITH 1/2" MINIMUM LETTERS, SECURELY FASTENED TO THE DEVICE.

C. EACH INDIVIDUALLY MOUNTED CIRCUIT BREAKER, SWITCH, TRANSFER SWITCH, MOTOR STARTER, LIGHTING CONTACTOR, TRANSFORMER AND/OR ANY OTHER CONTROL OR PROTECTIVE DEVICE INCLUDING EQUIPMENT DISCONNECT SWITCHES SHALL BE EQUIPPED WITH A PERMANENT PLASTIC NAMEPLATE WITH 1/2"

MINIMUM LETTERS.

D. PANELBOARDS SHALL HAVE TYPEWRITTEN DIRECTORIES. ALL CIRCUITS TO BE IDENTIFIED BY DEVICES SERVED AND ROOM NUMBERS (I.E., LIGHTING ROOM 216). HANDWRITTEN DIRECTORIES WILL NOT BE ALLOWED.

E. EACH JUNCTION BOX CABINET OR WIREWAY LARGER THAN 6" X 6" SHALL BE EQUIPPED WITH A

PLASTIC NAMEPLATE WITH 1/2" MINIMUM LETTERS INDICATING THE SYSTEM ENCLOSED.

F. ALL SYSTEMS JUNCTION BOXES AND CONDUIT SHALL BE COLOR CODED INSIDE AND OUTSIDE OF THE BOX

PRIOR TO THE INSTALLATION OF CONDUCTORS PER THE FOLLOWING:

1. CCTV SYSTEM: GREEN

2. TELEPHONE DATA SYSTEM: BLUE

3. FIRE ALARM SYSTEM: RED

G. ENTIRE BOX INSIDE AND OUT, INCLUDING COVER, SHALL BE PAINTED PRIOR TO INSTALLING CONDUCTORS.

IV. WIRING DEVICES:

A. SWITCHES AND RECEPTACLES IN LOBBIES, CORRIDORS OR COMMERCIAL SPACES, UNFINISHED AND MECHANICAL SPACES SHALL BE 20 AMP COMMERCIAL GRADE 125 VAC. GRAY IN COLOR WITH STAINLESS STEEL

COVERPLATES.

B. WEATHERPROOF RECEPTACLES SHALL BE GFCI TYPES WITH GASKETED STAINLESS STEEL KEY LOCKABLE FLIP COVER TYPE COVERPLATES. SURGE SUPPRESSION TYPE OUTLETS IN MDFS AND IDFS SHALL BE HUBBELL

#83625 (BLUE) OR EQUAL.

C. RECEPTACLES PROVIDED FOR ATTACHMENT OF CORD AND PLUG EQUIPMENT SHALL BE HEAVY DUTY, SPECIFICATION GRADE, NON-INTERCHANGEABLE, FLUSH MOUNTED TYPES OF THE PROPER NEMA

CONFIGURATION TO SERVE THE EQUIPMENT. NEMA CONFIGURATIONS SHALL BE VERIFIED PRIOR TO INSTALLATION OF CIRCUIT CONDUCTORS. CONTRACTOR TO PROVIDE ALL CONNECTION, WIRING, PIGTAILS FOR

DISHWASHERS, COOKING RANGES, OVENS AND GARBAGE DISPOSALS.

D. ALL DEVICES SHALL HAVE PROPER PLATES, CARPET FLANGES, TRIMS, RINGS, ESCUTCHEONS, ETC., AS MANUFACTURED BY SAME MANUFACTURER AS DEVICES. ANY TELEPHONE OR OTHER OUTLET WHICH IS NOT EQUIPPED WITH A PLATE FURNISHED BY OTHERS SHALL HAVE ONE PROVIDED BY THIS CONTRACTOR. DEVICE

PLATES SHALL BE COLOR AND TYPE AS SHOWN BELOW.

1. FINISHED SPACES DECORA LINE:

a. WOOD SURFACES - BLACK

b. BANQUETTES - BLACK

c. FRP & METAL PANEL - GRAY DEVICES W/ STAINLESS STEEL COVERS

2. UNFINISHED OR INDUSTRIAL OR COMMERCIAL TYPE SPACES:

a. GRAY DEVICES

b. STAINLESS STEEL OR STAMPED GALVANIZED STEEL ON SURFACE MOUNTED BOXES

c. STAINLESS STEEL PLATES ON FLUSH MOUNTED BOXES

VIII. GROUNDING:

A. THIS SECTION DEALS WITH THE GROUNDING OF SERVICE EQUIPMENT, TRANSFORMERS, NON- CURRENT CARRYING CONDUCTIVE SURFACES OF EQUIPMENT, METAL BUILDING, STRUCTURES AND

OTHER EQUIPMENT.

B. ALL GROUNDING CONNECTIONS SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND ALL LOCAL CODES AND REQUIREMENTS. SUCH CODES SHALL BE CONSIDERED MINIMUM

REQUIREMENTS AND THE INSTALLATION OF THE GROUNDING SYSTEM

SHALL INSURE FREEDOM FROM DANGEROUS SHOCK EXPOSURE AND SHALL PROVIDE A LOW IMPEDANCE GROUND FAULT PATH TO PERMIT OPERATION OF OVERCURRENT AND GROUND FAULT PROTECTIVE DEVICES.

C. ALL SERVICE AND EQUIPMENT GROUNDING CONDUCTORS, AND BONDING JUMPERS SHALL BE INSULATED COPPER, TYPE THHN, THWN, OR THW CONDUCTORS (UNLESS NOTED OTHERWISE) AND SHALL BE SIZED IN ACCORDANCE WITH THE APPLICABLE PORTIONS OF ARTICLES 250 AND 517 OF THE NATIONAL ELECTRICAL CODE. GROUNDING CONDUCTORS #6 AWG AND SMALLER SHALL HAVE A GREEN COLOR INSULATION. ALL GROUNDING CONDUCTORS #4 AWG AND LARGER SHALL BE ADEQUATELY IDENTIFIED WITH A GREEN TRACER AND/OR GREEN COLORED TAPE AT EACH END OF THE GROUNDING CONDUCTOR AND AT EACH PULLBOX OR

OTHER ACCESSIBLE LOCATION.

D. THE MAIN SERVICE GROUNDING ELECTRODE SYSTEM SHALL CONSIST OF THE FOLLOWING ITEMS BONDED TOGETHER BY THE GROUNDING ELECTRODE CONDUCTORS IN ACCORDANCE WITH NEC ARTICLE 250, PART H:

1. THE MAIN UNDERGROUND COLD WATER PIPE, IF METAL, NEC 250- 81(A)

2. METAL FRAME OF BUILDING WHERE AVAILABLE, NEC 250-81(B)

3. CONCRETE ENCASED ELECTRODE, NEC 250-81(C)

4. THE BUILDING LIGHTNING PROTECTION SYSTEM.

E. THE NEUTRAL CONDUCTOR SHALL BE GROUNDED AT THE SERVICE ENTRANCE MAIN DISCONNECT, AND AT

EACH SEPARATELY DERIVED SYSTEM ONLY PER NEC ARTICLE 250.

F. A #4 INSULATED COPPER CONDUCTOR INSTALLED IN 3/4" CONCEALED CONDUIT SHALL BE CONNECTED FROM THE BUILDING GROUNDING ELECTRODE SYSTEM TO EACH BUILDING TELEPHONE TERMINAL/DATA IDF TERMINAL BOARDS, OR CABINETS, FIRE ALARM CONTROL CABINETS, CCTV SYSTEM CABINETS, EMS CABINETS, AND SECURITY SYSTEM CABINETS. TERMINATE ON AN APPROPRIATELY SIZED (8) TERMINAL MULTI-CONDUCTOR CONNECTION GROUNDING LUG LOCATED WITHIN CABINET OR ON TERMINAL BOARDS.

IX. PANELBOARDS:

A. PANELBOARDS SHALL BE DEAD FRONT TYPE AND SHALL BE IN ACCORDANCE WITH UNDERWRITERS' LABORATORIES, INC., STANDARD FOR PANELBOARDS AND ENCLOSING CABINETS AND SO LABELED.

B. PANELBOARDS SHALL BE FACTORY ASSEMBLED WITH BRANCH BREAKERS ARRANGED AS SHOWN IN SCHEDULES. BREAKERS SHALL BE NUMBERED VERTICALLY BEGINNING TOP LEFT. BREAKER NUMBERS SHALL BE PERMANENTLY ATTACHED TO TRIM. PANEL SHALL BE MINIMUM 20" WIDE OR 16" FOR RESIDENTIAL LOAD

CENTERS, UNLESS SPECIFICALLY NOTED OTHERWISE.

C. ANY SPECIAL REQUIREMENTS ON THE DRAWINGS OR SCHEDULES, SUCH AS GROUND FAULT PROTECTION, ARC-FAULT CIRCUIT BREAKERS, INCREASED INTERRUPTING CAPACITY, SHUNT TRIP TYPE CIRCUIT BREAKER, FEED THRU PANELBOARDS, ETC., SHALL SUPERSEDE THESE SPECIFICATIONS, BUT ONLY INSOFAR AS THAT

PARTICULAR REQUIREMENT IS CONCERNED AND AS INDICATED.

D. WIRING IN PANELBOARD GUTTERS SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER. WIRING SHALL

BE GROUPED INTO NEAT BUNDLES AND SECURED WITH NYLON TIE WRAPS.

E. PROVIDE TYPE WRITTEN DIRECTORIES FOR EACH PANELBOARD INDICATING THE LOAD SERVED.

X. LIGHTING FIXTURES:

A. LIGHTING FIXTURES SHALL BE FURNISHED AS SHOWN ON DRAWINGS AND IN THE LIGHTING FIXTURE SCHEDULE. IT SHALL SPECIFICALLY BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY EXACT TYPE CEILING AND RECESSING DEPTH OF ALL RECESSED FIXTURES AND TO FURNISH THE MOUNTING TRIMS AND ACCESSORIES OF THE SPECIFIED AND/OR APPROVED FIXTURES FOR THE CEILING TO BE INSTALLED.

LIGHTING FIXTURES SHALL BE PROVIDED WITH JOINER PLATES, END CAPS, RETAINING CLIPS, PLASTER FRAMES, HOUSINGS, AND ALL OTHER ACCESSORIES REQUIRED FOR A COMPLETE INSTALLATION.

B. ALL FIXTURES SHALL BE EQUIPPED WITH LAMPS UNLESS OTHERWISE NOTED. LAMPS SHALL BE INSTALLED NEW, IMMEDIATELY PRIOR TO FINAL INSPECTION, AND SHALL NOT BE USED FOR CONSTRUCTION.

C. FIXTURE CATALOG NUMBER REPRESENTS BASIC LUMINARY SIZE, TYPE, QUALITY AND CONFIGURATION.

ACCESSORIES SHALL BE FURNISHED WITH EACH UNIT AS REQUIRED FOR A COMPLETE FINISHED INSTALLATION. BASIC ACCESSORIES SHALL INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING:

1. JOINING PLATES, END CAPS, RETAINING CLIPS, ETC.

2. TRIMS FOR RECESSED FIXTURES.

3. FIXTURE STEMS AND CANOPIES FINISHED TO MATCH FIXTURES.

4. SPECIAL MOUNTING BRACKETS, TENONS, SLIP FILTERS, CONCRETE BASES, POLES, ANCHOR

BOLTS, JUNCTION BOXES, AND STANCHIONS FOR ALL EXTERIOR LIGHTING FIXTURES. PROVIDE

ALL WEATHERPROOFING FOR ALL LIGHTING FIXTURES TO BE INSTALLED IN EXTERIOR

LOCATIONS.

D. STRUCTURAL SUPPORT OF ALL FIXTURES SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.

E. THE SYSTEM GROUNDING CONDUCTOR SHALL BE SECURED TO EACH FIXTURE BODY BY MEANS OF A

BONDING SCREW.

F. OWNER/DEVELOPER WILL HAVE RIGHT TO RELOCATE LIGHTING FIXTURES OR LIGHTING SWITCHES WITHIN 72" OF LOCATION SHOWN ON FIRST WALK-THROUGH AT NO ADDITIONAL EXPENSE. COORDINATE THE

WALK-THROUGH PRIOR TO THE INSTALLATION OF THE WIRING.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

M :\P ro je ct S er ve r\P ro je ct s\

\J

LS

C

.0

.0

- V en er gy G ro up

, V

AM

C W

PB

B ui ld in g

Se cu rit y

C on tro ls

In st al la tio n

- W es t P al m B ea ch

, F L\

D ra w in gs \E le ct ric al

\E -0

.d w g

2/ 9/

:2

0:

P M

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseENGINEER OF RECORD STAMPCONTRACTOR

321 4 5 6 7 8 9 10

WPB VAMC - INSTALL BUILDING

SECURITY CONTROLS

West Palm Beach VA Medical Center

548-19-110

Project Director

Revisions: Date:

ELECTRICAL ENGINEER:

LAWRENCE M. STOFF

P.E. #: 78586

Blake Lawrence Suddeth P.E. #: 69060

Blake Lawrence Suddeth P.E. #: 69060

BLS LMSMay 14th, 2020

JL

C&O

Joseph, Lawrence & Co

Consulting Engineers 317 RIVEREDGE BLVD. SUITE 110. COCOA, Florida 32922 Tel: 321.972.4466 . www.jlceng.com . CA No. 32770

Space Coast

100% CONSTRUCTION

DOCUMENTS

3130 Seminole Road, Fort Pierce, FL 34951 Tel: 866-977-7555 | VenergyGroup.com

RECORD DOCUMENTS 02/09/21

1 2 3 4 5 6 7 161514

DIETETICS SERVICE

PHARMACY SERVICE

16151413 131118 12

1131049.893 4 5 6 7 81 2

7.9 8.8 9.7 113 122 131

M6

L6

K8

K2

J2

134 136

L9

L7

L2

7.2 7.6

L9

L7

L2

K9

R-3

R-5 R-5

R-4

R-5

K9

S-1

S-2

S-3

S-4

S-5

LIFT 1

LIFT 2

LIFT 3

P - 1

P - 2

P - 3 P - 4

P - 5

P - 6

S-9

BB-111

BB-116 BB-118

BB-111

BB-C1

BB-239

BB-253

BB-115

BB-104

BB-102

BB-113

BB-111

BB-111

BB-112

BB-111

BB-251

BB-C1

BB-C1

BB-C1

BB-C1

BB-213 BB-212 BB-212A BB-C1

BB-212BBB-215 BB-237

BB-217A

BB-217

BB-251

BB-251

BB-255

BB-257

BB-251

BB-252

BB-241

BC-247

BB-248

BB-245

BB-243A

BB-249

BB-254

BB-251

BB-251

BB-259

BB-258

BB-251BB-256

BB-336

BB-334BB-332

BB-C3

BB-324A

BB-235

BB-219B

BB-219

BB-C2

OFFICE

BB-219A

BB-233

BB-251

BB-232

BB-234

BB-251

BB-236 BB-238

BB-242

BB-241

BB-243

BB-225

BB-223

BB-221A

BB-221

BB-322

BB-C3

BB-324BB-312

BB-314

BB-312ABB-307

BB-316BB-121

MECHANICAL

LIQUID

SUPPLY

SYSTEM

ELECT

HAC

STOREAGE

CART

WASHER

AREA

RECEIVING

PROCESSING AREA

SORTING & WASHING AREA

FOREMAN

TEXTILE

CARE

ASS'T

MNGR

REST & LUNCH AREA

HAC

MEN'S

LOCKER

WOMEN'S

LOCKER

ASSEMBLY

DISTRIBUTION

CORR.

CORRIDOR

CORRIDOR

CORR.

CORR.

CORR.

VEST.

CORR.

LINEN

HOLED

LOADING

DOCKS #7

LOADING

DOCKS

DOCK 8

ADMIN.

SUPP.

ASSIST.

MECH. ROOM

LOUNDRY

STORAGE

BB-117

IV & CHEMO

PREP

IV COMPOUND

CHEMO

COMPOUND

BB-118

BB-119

COMPOUND

CHEMO

ANTE-ROOMANTE-ROOM

IV

COMPOUND

BB-120

R-4R-3

V

B

B

R-5 R-5

R-4

R-4

R-5

V

V

V

V

V

V V

V V V

V

VV

V

(TYP.)

(TYP.)1

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

CR

CR

CR

CR

CR

DOME

DOME

DOME

360°

360°

DOME

BASEMENT FLOOR PLAN - AREA A

- ELECTRICAL

E-100A

KEY NOTES:

1. NEW CAMERA LOCATION AS PROVIDED BY THE VA. COORDINATE EXACT LOCATION WITH THE VA AND CAMERA

INSTALLER. CAMERA TYPE AND SYSTEM SPECIFICATIONS SHALL BE PER LOW VOLTAGE/CAMERA SYSTEMS INSTALLER. ELECTRICAL CONTRACT SCOPE SHALL BE TO PROVIDE CONDUIT AND WIRING WITHIN THE INTERSTITIAL SPACE TO LOCATION SHOWN AND TERMINATE ABOVE CEILING OF THE SPACE WITH A JUNCTION BOX. THE LOW VOLTAGE/CAMERA CONTRACTOR IS RESPONSIBLE TO INSTALL THE CAMERA SYSTEM.

2. CONDUIT MAIN SHALL BE INSTALLED WITHIN INTERSTITIAL SPACE ABOVE EACH FLOOR AND WITH EXISTING CABLE TRAYS. CONDUIT ROUTING SHOWN WAS COORDINATED WITH AS-BUILT DOCUMENTED EXISTING CABLE TRAY APPROXIMATE LOCATIONS/ROUTING, BUT SHALL BE FIELD VERIFIED BY THE CONTRACTOR. SIZING WILL BE

PREDICATED ON CAMERA WIRING NEEDS AND BY THE CONTRACTOR.

3. CONDUIT BRANCH FROM MAIN TO CAMERA LOCATION/ JUNCTION BOX SHALL BE RUN IN EMT CONDUIT IN INTERSTITIAL SPACE. COORDINATE ROUTING WITH EXISTING CONDITIONS AND EQUIPMENT IN INTERSTITIAL

SPACE.

4. LOW VOLTAGE CONTRACTOR SHALL REPLACE, ONE FOR ONE, EXISTING ACCESS CONTROLS DEVICES WHERE INDICATED. RETAIN EXISTING POWER FOR USE WITH NEW DEVICE AS ABLE. CONTRACTOR IS RESPONSIBLE TO EXTEND OR PROVIDE NEW POWER FOR ACCESS CONTROL DEVICES IF EXISTING POWER IS NOT ABLE TO BE

REUSED. COORDINATE WITH THE OWNER FOR SPECIFICATIONS AND TYPE OF DEVICE.

5. EXISTING IT ROOM TO HOUSE CAMERA SYSTEM CONTROLLER, SWITCH AND HEAD END. COORDINATE WITH

OWNER AND LOW VOLTAGE/CAMERA CONTRACTOR.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

M :\P ro je ct S er ve r\P ro je ct s\

\J

LS

C

.0

.0

- V en er gy G ro up

, V

AM

C W

PB

B ui ld in g

Se cu rit y

C on tro ls

In st al la tio n

- W es t P al m B ea ch

, F L\

D ra w in gs \E le ct ric al

\E -1

.d w g

2/ 9/

:1

9:

P M

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseENGINEER OF RECORD STAMPCONTRACTOR

321 4 5 6 7 8 9 10

WPB VAMC - INSTALL BUILDING

SECURITY CONTROLS

West Palm Beach VA Medical Center

548-19-110

Project Director

Revisions: Date:

ELECTRICAL ENGINEER:

Blake Lawrence Suddeth P.E. #: 69060

Blake Lawrence Suddeth P.E. #: 69060

BLS LMSMay 14th, 2020

JL

C&O

Joseph, Lawrence & Co

Consulting Engineers 317 RIVEREDGE BLVD. SUITE 110. COCOA, Florida 32922 Tel: 321.972.4466 . www.jlceng.com . CA No. 32770

Space Coast

100% CONSTRUCTION

DOCUMENTS

3130 Seminole Road, Fort Pierce, FL 34951 Tel: 866-977-7555 | VenergyGroup.com

RECORD DOCUMENTS 02/09/21

GENERAL NOTES:

A. DO NOT SCALE ELECTRICAL DRAWINGS FOR ANY DIMENSIONS.

B. ALL WORK SHALL COMPLY WITH THE LATEST VA ADOPTED EDITION OF THE NATIONAL ELECTRIC CODE, NATIONAL, STATE AND LOCAL CODES.

C. ALL EXISTING ELECTRICAL SYSTEMS SHALL REMAIN AS IS UNLESS OTHERWISE NOTED. ANY BUILDING COMPONENT DAMAGE CREATED FROM CONSTRUCTION TO ACCOMPLISH THE SCOPE OF WORK PROVIDED WITHIN THESE DOCUMENTS SHALL BE REPAIRED BACK TO THE ORIGINAL CONDITION PRIOR TO COMPLETING

CONSTRUCTION.

D. CAMERA QUANTITIES AND LOCATIONS PROVIDED BY THE VA AND THE LOW VOLTAGE SYSTEMS DESIGNER.

AS SUCH, CAMERA LOCATIONS ARE SHOWN FOR REFERENCE. EXACT LOCATIONS, CAMERA SYSTEM SPECIFICATIONS AND TYPES SHALL BE COORDINATED WITH THE LOW VOLTAGE/CAMERA SYSTEMS

INSTALLING CONTRACTOR/VENDOR.

E. ALL CONDUIT MAINS SHALL BE ROUTED WITHIN CABLE TRAYS LOCATED IN THE INTERSTITIAL SPACE ABOVE EACH LEVEL. CONDUIT ROUTING SHOWN WAS COORDINATED WITH AS-BUILT DOCUMENTED EXISTING CABLE TRAY LOCATIONS/ROUTING, BUT SHALL BE FIELD VERIFIED BY THE CONTRACTOR TO ENSURE AS-BUILT DOCUMENTATION IS ACCURATE. IF ANY FIELD CONDITION IS FOUND THAT DEVIATES FROM THIS PLAN, OR THAT AFFECTS THE SCOPE OF WORK DEPICTED WITHIN THESE DOCUMENTS, THE CONTRACTOR SHALL INFORM THE ENGINEER IN WRITING PRIOR TO COMMENCING WORK. IF EXISTING CABLE TRAYS, CONDUITS, RACEWAYS...ETC. DO NOT HAVE CAPACITY FOR ADDITIONAL CABLING, THE CONTRACTOR SHALL PROVIDE NEW CABLE TRAYS, CONDUITS, RACEWAYS...ETC. AS NEEDED FOR TO ACCOMMODATE NEW PROJECT

CABLING.

F. CONDUIT SIZING SHALL BE PER CONTRACTOR AND LOW VOLTAGE VENDOR AND BASED ON ACTUAL WIRING

NEEDS AND WIRE SIZES REQUIRED BY THE SPECIFIC CAMERA SYSTEM INSTALLED.

G. HEAD END EQUIPMENT TO BE HOUSED ON BASEMENT LEVEL WITHIN EXISTING IT ROOM. COORDINATE WITH

OWNER AND LOW VOLTAGE/CAMERA VENDOR.

AutoCAD SHX Text %%uSUPPLY SERV. WAREHOUSE

AutoCAD SHX Text

%%UADMIN. OFFICES/CUBICALS

AutoCAD SHX Text %%uSUPPLY PROCCESSING & DIST.

AutoCAD SHX Text P.B.

AutoCAD SHX Text P.B.

AutoCAD SHX Text

MATCHLINE - SHEET E100A

AutoCAD SHX Text

MATCHLINE - SHEET E100B

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

BASEMENT FLOOR PLAN - AREA A - ELECTRICAL

1/16" = 1'-0"

17161514

D

E

F

G8

H

DIETETICS SERVICE

PHARMACY SERVICE

17161514

G

C

C

B

A

A

26 27

E8

E

B2

A6

A4

X X

X X

X X

X X

X X

X

26 27

E8

E

B2

A6

A4

18 182 19 191 196 198 20 21208 212205 22219 23 24 25 26 2718 182 19 191 196 198 20 21208 212205 22219 23 24 25 26 27

M

L

K6

K

L

H2

J2

M6

L6

K8

K2

J2

L9

L7

L2

K9

BB -123

BB-121

BB-125

BB-121BB-111

BB-116 BB-118

BB-111

BB-C1

BB-239

BB-253

BB-111

BB-251

BB-251

BB-251

BB-255

TELECOMM

BB-263

BB-257

BB-251

BB-252

BB-241

BC-247

BB-248

BB-245

BB-243A

BB-249

BB-254

BB-251

BB-251

BB-259

BB-258

BB-251BB-256

BB-338

BB-336

BB-334BB-332

BB-C3

BB-324A

BC-314

BC-316

BC-324

BC-314

BC-312

S-6 S-7 S-8

BB -C4

BC - 304

BC - 302

BB-C3 BC-C3

BC- C3

BC- 202A

BC- 218

BC - 261

BC - 202

BIOMEDICAL

ENGINEER

BC - 212

BC-203 A

BC - 203

BC - 261 A

BB - 121

BC - C1

BC - C1

BC - 101

BC - C1

BC - 103 A

BC - 101 A

BC - 103

BC - 211

BC - 213

BC - 213 A

BC - 213 B

BC-211A

BC - 242

BC - 202

BC - 216

BC - 214

BC- 215

BC- 215 A

BC- 231D BC- 231E

BC - 322

BC - 334 BC - 336

BC- 240A

BC- 240

BC - 338 BC - 340

BC - C3

BC - 360 B BC - 360 A

BC - 360

BC - 352

BC - 351 BC - 354

BC - 356 BC - 358

BC - 257

EOC

BC - 255

BC - 264

FACILITIES

PLANNING

BC - 253

BC - 239 BC - 257

BC - 250

BC - C3

BC - 248 BC - 247 BC - 262

BC - 245

BC - 246

BC - 244

BC - 243

BC -241 B

BC -241 A

BC-260

BC -261

BC -263

BC -265

BC

C

BC - C4

BC -241

BC - C6

BC

C

P - 7

FUTURE

BC- C1

P - 8 P - 9

P - 10

BC - 113

BC - 115

BC - 111

BC - 111

INFORMATION

SECURITY

OFFICER

BC - 112

BC - C1

BC - C3

CB -44

BC - C2

OPERATIONS STORAGE

N2 MANIFOLD

N2O MANIFOLD

FIRE PUMP RM.

MECHANICAL

AIR COMPRESSOR &

VACUUM PUMPS

DOMESTIC WATER

PUMP RM.

MECHANICAL

BOILER ROOM

FPL SWITCH ROOM

ELECTRICAL

SWITCH GEAR ROOM

CHILLER ROOM

A/C SHOP

BB - 122

BC-111A

BC - 342

BC - 245A

MECH.

CLOSET

BC-318

OFFICE

BC - 114B

STORAGE

BC - 114A

IRMS

STOR.

BC - 114CELEC

CLOSET

BC-114D

BC - 114 IRMS (IT)

BB-117

IV & CHEMO

PREP

IV COMPOUND

CHEMO

COMPOUND

BB-118

BB-119

COMPOUND

CHEMO

ANTE-ROOMANTE-ROOM

IV

COMPOUND

BB-120

(MEZZANINE ABOVE)

(LANDING)

FENCED AREA

OFFICE OFFICE

OFFICE OFFICE

J

F

E

A

D

H4

M

L

K6

K

DOMESTIC

WATER ROOM

MEDICAL

GAS ROOM

BC- 231

BC- 231CBC- 231B

BC- 231A

6' -0

" C

LR

BC - 266

BB - 121A

ELEC

CLOSET

BG-130

PREP RM

BG - 113

PREP RM

BG - 112

PREP RM

BG - 111

EXIT CORRIDOR

BG - 110

WAITING

ROOM

BG - 109

CLEAN

UTIL.

BG - 115

PATIENT

TOILET

BG - 114

CHIEF

TECH.

BG - 117

CORRIDOR

BG - 107

HOLD

ROOM

BG - 118

HOLD

ROOM

BG - 119

READING

ROOM

BG - 120

MRI

CONTROL

ROOM

BG - 121

MRI

SCANNING

ROOM

BG - 122

MRI

SCANNING

ROOM

BG - 123

RECOVERY

AND

SCREENING

BG - 128

LINEN

ALCOVE

BG - 127

MRI

SYSTEM

COMPONENT

ROOM

BG - 106

K-4386ANGLESEYC_TOILETSVITREOUS CHINA

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.) 180°

CR

CR

CR

CR

CR

360°

360°

DOME

DOME

DOME

DOME

BASEMENT FLOOR PLAN - AREA B

- ELECTRICAL

E-100B

KEY NOTES:

GENERAL NOTES:

1. NEW CAMERA LOCATION AS PROVIDED BY THE VA. COORDINATE EXACT LOCATION WITH THE VA AND CAMERA INSTALLER. CAMERA TYPE AND SYSTEM SPECIFICATIONS SHALL BE PER LOW VOLTAGE/CAMERA SYSTEMS INSTALLER. ELECTRICAL CONTRACT SCOPE SHALL BE TO PROVIDE CONDUIT AND WIRING WITHIN THE INTERSTITIAL SPACE TO LOCATION SHOWN AND TERMINATE ABOVE CEILING OF THE SPACE WITH A JUNCTION BOX. THE LOW VOLTAGE/CAMERA CONTRACTOR IS RESPONSIBLE TO INSTALL THE CAMERA SYSTEM.

2. CONDUIT MAIN SHALL BE INSTALLED WITHIN INTERSTITIAL SPACE ABOVE EACH FLOOR AND WITH EXISTING CABLE TRAYS. CONDUIT ROUTING SHOWN WAS COORDINATED WITH AS-BUILT DOCUMENTED EXISTING CABLE TRAY APPROXIMATE LOCATIONS/ROUTING, BUT SHALL BE FIELD VERIFIED BY THE CONTRACTOR. SIZING WILL BE

PREDICATED ON CAMERA WIRING NEEDS AND BY THE CONTRACTOR.

3. CONDUIT BRANCH FROM MAIN TO CAMERA LOCATION/ JUNCTION BOX SHALL BE RUN IN EMT CONDUIT IN INTERSTITIAL SPACE. COORDINATE ROUTING WITH EXISTING CONDITIONS AND EQUIPMENT IN INTERSTITIAL

SPACE.

4. LOW VOLTAGE CONTRACTOR SHALL REPLACE, ONE FOR ONE, EXISTING ACCESS CONTROLS DEVICES WHERE INDICATED. RETAIN EXISTING POWER FOR USE WITH NEW DEVICE AS ABLE. CONTRACTOR IS RESPONSIBLE TO EXTEND OR PROVIDE NEW POWER FOR ACCESS CONTROL DEVICES IF EXISTING POWER IS NOT ABLE TO BE

REUSED. COORDINATE WITH THE OWNER FOR SPECIFICATIONS AND TYPE OF DEVICE.

A. DO NOT SCALE ELECTRICAL DRAWINGS FOR ANY DIMENSIONS.

B. ALL WORK SHALL COMPLY WITH THE LATEST VA ADOPTED EDITION OF THE NATIONAL ELECTRIC CODE, NATIONAL, STATE AND LOCAL CODES.

C. ALL EXISTING ELECTRICAL SYSTEMS SHALL REMAIN AS IS UNLESS OTHERWISE NOTED. ANY BUILDING COMPONENT DAMAGE CREATED FROM CONSTRUCTION TO ACCOMPLISH THE SCOPE OF WORK PROVIDED WITHIN THESE DOCUMENTS SHALL BE REPAIRED BACK TO THE ORIGINAL CONDITION PRIOR TO COMPLETING

CONSTRUCTION.

D. CAMERA QUANTITIES AND LOCATIONS PROVIDED BY THE VA AND THE LOW VOLTAGE SYSTEMS DESIGNER.

AS SUCH, CAMERA LOCATIONS ARE SHOWN FOR REFERENCE. EXACT LOCATIONS, CAMERA SYSTEM SPECIFICATIONS AND TYPES SHALL BE COORDINATED WITH THE LOW VOLTAGE/CAMERA SYSTEMS

INSTALLING CONTRACTOR/VENDOR.

E. ALL CONDUIT MAINS SHALL BE ROUTED WITHIN CABLE TRAYS LOCATED IN THE INTERSTITIAL SPACE ABOVE EACH LEVEL. CONDUIT ROUTING SHOWN WAS COORDINATED WITH AS-BUILT DOCUMENTED EXISTING CABLE TRAY LOCATIONS/ROUTING, BUT SHALL BE FIELD VERIFIED BY THE CONTRACTOR TO…

This is the start of the file's text. The full file is on GovTribe.