Attachment H - Mason Fire Watch Guidelines.pdf

PDF 213 KB Posted

Attached to
Enterprise Hall Elevator Modernization
Solicitation number
IFB-127890
Issued by
Fairfax County, Virginia

About this file

This is a Fire Watch Guide document issued by George Mason University's Risk, Safety, & Resilience department, specifically the Emergency Management & Fire Safety (EM&FS) division, establishing procedures for fire watch implementation when fire suppression or fire alarm systems are out of service or compromised. The guide applies to all university employees and contractors performing work in George Mason University-owned buildings and mandates compliance with the Virginia Statewide Fire Prevention Code (SFPC) 901.7 and National Fire Protection Association (NFPA) 72 standards. Fire watch requirements are determined on a case-by-case basis considering the extent of system interruption, building use, expected occupancy, and anticipated duration. Two categories of fire watch are defined: One Day Fire Watch, which terminates at the end of a work shift when systems are restored, and Long Term Fire Watch, which extends across multiple shifts or overnight and requires fire watch coverage during all occupied hours. The guide was most recently updated in March 2025 and represents the seventh version since its initial publication in January 2011.

Responsibilities for establishing and conducting fire watches are divided among Facilities Project Managers, Facilities Inspectors, Facilities Management Supervisors, and other facilities personnel who oversee buildings where system failures occur, with EM&FS responsible for fire watches during systems tests, maintenance, or repairs conducted by EM&FS. Fire watch personnel must post signage, conduct hourly patrols of affected areas, maintain activity logs using the Fire Watch Checklist, remain proficient in fire alarm and suppression system operation, have immediate access to 911 emergency services, and possess fire extinguishing equipment and training. Personnel assigned to fire watch duty cannot perform other concurrent tasks and must notify building occupants to evacuate using verbal warnings, air horns, whistles, or other notification devices if fire or smoke is detected. For Long Term Fire Watches, a coordinated meeting between Facilities Management and EM&FS must occur before implementation, and the State Fire Marshal must be notified when any fire watch is initiated.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Risk, Safety, & Resilience Fire Watch Guide 08/2022

FIRE WATCH GUIDE

Version Date Comments 1 January, 2011 Initial Fire Watch Guide 2 May 2013 Routine review 3 November, 2015 Update code citation - SFPC 2012 4 July, 2017 Routine review 5 July, 2019 Routine review 6 August, 2022 Routine review 7 March 2025 Routine review

A. INTRODUCTION

The Virginia Statewide Fire Prevention Code (SFPC) 901.7 and National Fire Protection Association (NFPA) 72 mandate that a “fire watch” be implemented whenever a fire suppression or fire alarm system is out of service or compromised. Notification must be made to Risk, Safety, & Resilience- Emergency Management & Fire Safety (EM&FS) when a fire suppression or fire alarm system is out of service, under repair, or otherwise inoperable to determine if a fire watch is warranted.

B. SCOPE

This Guide applies to all George Mason employees and contractors performing work in university-owned buildings. Fire watch requirements for system outages and impairments will be determined on a case-by-case basis taking into consideration the extent of the interruption, building use, number of expected occupants, and expected duration of the interruption. Upon notification of a fire suppression or fire alarm outage, EM&FS is responsible for determining the appropriate type of fire watch.

One Day Fire Watch: A fire watch that can be terminated at the end of the work shift;

all alarm and suppression systems are restored to normal operations when the works shift is complete.

Long Term Fire Watch: A fire watch that extends across multiple work shifts or overnight to accommodate complex or lengthy systems repairs, maintenance, or upgrades.

During a Long Term Fire Watch, fire watch must be conducted during all hours that the building is occupied.

C. RESPONSIBILITIES

Facilities Project Managers, Facilities Inspectors, Facilities Management Supervisors, or other facilities management personnel (i.e., Housing and Residence Life, Student Centers, or Intercollegiate Athletics, etc.) are responsible for establishing a fire watch for the buildings

03/2025 which they oversee whenever a system fails or maintenance and/or repairs are necessary.

Emergency Management & Fire Safety (EM&FS) will be responsible for conducting a fire watch during any scheduled fire alarm or fire suppression system test, maintenance, or repair, conducted or coordinated by EM&FS. These agencies are responsible for ensuring that the fire watch is conducted in accordance with the procedures outlined in this guide.

Emergency Management & Fire Safety -

• Emergency Management & Fire Safety is responsible for overseeing fire watch procedures conducted in university buildings to include inspection of fire watch operations and fire watch logs maintained by employees and contractors responsible for conducting fire watch.

• Emergency Management & Fire Safety (EM&FS) will advise George Mason University Facilities Management or Facilities Administration personnel on fire watch procedures whenever a Long Term Fire Watch is warranted.

• Notify State Fire Marshal when a Fire Watch is implemented.

Facilities Management and Facilities Administration

• Facilities Management and Facilities Administration are responsible for coordinating a meeting with EM&FS whenever a Long Term Fire Watch is warranted. This meeting (virtual or physical) must take place before fire watch may be implemented.

D. NOTIFICATION

One Day Fire Watch Whenever scheduled repairs demand that a fire suppression or fire alarm system be taken out of service, notification must be made by submitting an outage request to Facilities Management Customer Service.

Long Term Fire Watch When it is discovered that a fire suppression or fire alarm system is inoperable due to damage, utility failure, system failure, or operates improperly, EM&FS must be notified. Additionally, a meeting with EM&FS must occur to discuss the severity of the outage, responsible parties for fire watch, and plans for rectification of the issue. When reporting such an outage, include the following information:

• Location of the system,

• System(s) impacted and corresponding areas of coverage,

• Anticipated duration of the outage,

• Suspected reason for the outage if know, and

• Name and contact information.

E. PROCEDURES

03/2025

Every fire watch is different in regards to scope and scale. In general, fire watch should be conducted in areas of a building that have an impaired fire safety system. If there are any questions about the scope and/or scale of a fire watch, Emergency Management & Fire Safety should be consulted.

All Long Term Fire Watch requires a meeting with Emergency Management & Fire Safety to discuss scope and duties of the personal conducting fire watch.

A fire watch is defined as, “the assignment of a qualified person or persons for the express purpose of notifying the fire department, the building occupants, or both of an emergency;

preventing a fire from occurring; extinguishing small fires; or protecting the public from fire or life safety dangers”. The responsibilities of an individual assigned to fire watch duty is to fulfill the intent of NFPA-72 as follows:

• Notify occupants to evacuate when there is a fire in the building.

• Notify 911 to initiate emergency personnel response.

• Activate fire protection systems (if available and operational) in order to release door holders, close smoke dampers, and shut down fans.

• The persons performing this type of fire watch are not to be permitted to perform any other duties (SFPC 901.7). Emergency Management & Fire Safety are to be responsible for determining the procedures to be followed for each specific circumstance.

Individuals assigned to fire watch duty are responsible for the following:

1. Post signage (Appendix A) throughout the building to notify occupants that a fire watch is being conducted and the appropriate response if a fire or smoke is discovered.

2. Have an understanding of basic fire prevention and fire extinguishment techniques.

3. Be proficient in the operation of the fire alarm and suppression system the area(s) impacted by the outage.

4. Have an understanding of and the ability (i.e., access to a phone, cell phone, or radio) to immediately contact 911 in case of an emergency or fire.

5. Conduct a routine and thorough walk of all locations impacted by the system outage at least once per hour.

6. Note the location of portable fire extinguishers.

7. Notifying occupants to evacuate the building in the event of a fire by verbal warning, whistle, horn, or other notification device.

8. Fire watch personnel are to have fire extinguishing equipment readily available and be trained in its use.

9. Maintain a log of activities, findings, and incidents throughout the fire watch using the

Fire Watch Checklist (see Appendix B).

10. Remove fire watch signage once the fire watch is complete.

11. Witness and acknowledge that both the fire suppression and alarm systems are fully operation and back online with notification made to University Police Dispatch prior to leaving the facility.

03/2025

Appendix A: Fire Watch Sign

Attention Occupants

F I R E W A T C H I N

P R O G R E S S

Fire alarm or sprinkler system is out-of-service for repairs, construction, or maintenance.

Qualified individuals are conducting a continuous tour of common areas to provide smoke and/or fire detection. Please be alert to evidence of smoke or fire. Contact 911 immediately if fire is seen or suspected.

Evacuate the building immediately upon hearing an air horn, whistle, or other alert.

03/2025

Appendix B: Fire Watch Checklist

Fire Watch Checklist

Building: Date:

Expected Duration System Outage (include days and/or hours):

Means of Notifying Building Occupants (i.e. verbal command, whistle, horn):

Fire Watch Personnel

1st Watch Hours: Name: Phone Number:

2nd Watch Hours: Name: Phone Number:

3rd Watch Hours: Name: Phone Number:

Area(s) That Require a Fire Watch

Building:

Floor: Area:

Floor: Area:

Floor: Area:

Floor: Area:

Fire Watch Patrol Log: Patrol of affected areas must be conducted at least hourly

Time 1 Time 7 Time 13

Time 2 Time 8 Time 14

Time 3 Time 9 Time 15

Time 4 Time 10 Time 16

Time 5 Time 11 Time 17

Time 6 Time 12 Time 18

Comments

Project Completion Date: Signature: