Attachment B - Approved for Const Project Drawings - 03.17.26.pdf

PDF 31 MB Posted

Attached to
Enterprise Hall Elevator Modernization
Solicitation number
IFB-127890
Issued by
Fairfax County, Virginia

About this file

This is a set of approved construction project drawings for the Enterprise Hall Elevator Modernization project at George Mason University in Fairfax, Virginia, involving the Office of the University Building Official (OUBO). The project consists of the modernization of three hydraulic elevators in the Enterprise Hall classroom and office building, with Elevators #1 and #2 comprising a 5-stop elevator bank and Elevator #3 a 3-stop elevator. Modernization work includes renovations of the elevator pit, replacement of elevator doors, upgrades to new interior stainless steel panels, lighting, and call buttons, and all necessary modifications to bring the elevators into compliance with current code requirements. The project is classified as a Level II Alteration per the Virginia Uniform Statewide Building Code (VUSBC) 2021 Edition, and work will be conducted in two phases to maintain building occupancy and elevator access to all floors during construction. The drawing set includes comprehensive plans and details across multiple disciplines: general, architectural, mechanical, plumbing, electrical, telecom, fire alarm, and sprinkler systems, with sheets indexed for floor plans at various elevator locations and levels, reflected ceiling plans, interior elevations, sections, details, and schedules.

The project is governed by the VUSBC 2021 Edition, Virginia State Fire Prevention Code 2021 Edition, Higher Education Capital Outlay (HECO) 2023 Edition, and the George Mason University Design Manual 2013 Edition. The compliance path for accessibility follows ADA-SO-Title II with technical standards per the 2010 ADA Standards for Accessible Design and AI 17.1-2017. The building is exempt from the High Performance Building Act compliance because renovation costs do not exceed 50% of the building's value, and must comply with Virginia Energy Conservation Code (VECC) Sections C402 through C405 and C408. The drawings were approved for construction on March 11, 2026, with an electronic approval stamp from the same date. The existing structure is a sprinklered, non-high-rise building originally constructed under the VUSBC 2021 Use & Occupancy Classification with a sprinklered construction type.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONCRETE

BRICK

CMU

GROUT

STEEL

WOOD LUMBER

FINISH LUMBER

PLYWOOD

GYPSUM WALLBOARD

BATT INSULATION

RIGID INSULATION

AREAS

OF WORK

ROOM NAME &

NUMBER

PARTITION TYPEDOOR TYPE

# WINDOW TYPE

LEVEL MARKER

KEYNOTE

SECTION REFERENCE

SECTION NUMBER

SHEET NUMBER WHERE

DETAIL IS LOCATED

SHEET NUMBER WHERE

DETAIL IS REFERENCED

FROM

DETAIL REFERENCE

DETAIL NUMBER

SHEET NUMBER

WHERE SECTION IS

REFERENCED FROM

SHEET NUMBER WHERE

SECTION IS LOCATED

ELEVATION REFERENCE

ELEVATION NUMBER

SHEET NUMBER WHERE

ELEVATION IS REFERENCED

FROM SHEET NUMBER WHERE

ELEVATION IS LOCATED

INTERIOR ELEVATION

ELEVATION NUMBER

SHEET NUMBER WHERE

ELEVATION IS LOCATED

SECTION NUMBER

SHEET NUMBER WHERE

SECTION IS LOCATED

Name

NAME

PROJECT LOCATION

O

X R D

EXISTING TO REMAIN

EXISTING TO BE DEMOLISHED

NEW CONSTRUCTION

I-

236 / MAIN ST

US 50

I-66

O

X R D

PROJECT LOCATION

US 29

BRIDGE RD

CH

AI

N

General

G0.01 Cover Sheet

G1.01 Egress, Occupancy & Fire Resistance Rating Plan

PH1.01 Phasing Plan

Architectural

AD1.01 Partial Demolition Floor Plan - Elev #1 & #2

AD1.02 Partial Demolition Floor Plan - Elevator #3

AD1.03 Partial Demo RCP - Elev #1 & #2

AD1.04 Partial Demo RCP - Elevator #3

AD4.01 Demo Int Elevations, Sections, and Details - Elevator #1 & #2

AD4.02 Demo Int Elevations, Sections, and Details - Elevator #3

A1.01 Partial Floor Plans - Elev #1 & #2

A1.02 Partial Floor Plans - Elevator #3

A1.03 Partial RCP - Elevator #1 & #2

A1.04 Partial RCP - Elevator #3

A4.01 Interior Elevations, Wall Sections, and Details - Elevator #1 & #2

A4.02 Interior Elevations, Wall Sections, and Details - Elevator #3

A5.01 Partition Type and Rath Wiring Diagram

A5.02 UL Details

Mechanical

M-001 Cover Sheet - Mechanical

M-101 Partial Demolition Floor Plans Elevator #1 & #2 - Mechanical

M-102 Partial Demolition Floor Plans Elevator #3 - Mechanical

M-201 Partial New Work Floor Plans Elevator #1 & #2 - Mechanical

M-202 Partial Demolition Floor Plan Elevator #3 - Mechanical

M-203 Site Plan New Work, Mechanical

M-301 Details - Mechanical

M-401 Schedules - Mechanical

Plumbing

P-001 Cover Sheet - Plumbing

P-201 Partial New Work Floor Plans - Elevator #1 & #2

P-202 Partial New Work Floor Plans - Elevator #3

Electrical

E-001 Cover Sheet - Electrical

E-101 Partial Demolition Floor Plans - Elevator #1 & #2

E-102 Partial Demolition Floor Plans - Elevator #3

E-201 Partial Lighiting Floor Plans - Elevator #1 & #2

E-202 Partial Power Floor Plans - Elevator #1 & #2

E-203 Partial Lighiting Floor Plans - Elevator #3

E-204 Partial Power Floor Plans - Elevator #3

E-205 Site Plan - Electrical

E-401 Power Riser Diagram

E-501 Panel Schedules - Electrical

Telecom

T-001 Cover Sheet - Telecom

T-201 Partial New Work Floor Plans - Elevator #1 & #2

T-202 Partial New Work Floor Plans - Elevator #3

Fire Alarm

FA0.01 Reference Sheet - Fire Alarm

FA1.00 Elev #1 & #2 Lower Floor Plans - Fire Alarm

FA1.01 Elev & #2 Level 1-4 Floor Plans - Fire Alarm

FA1.02 Elev #3 Lower Level Floor Plans - Fire Alarm

FA1.03 Elev #3 First Floor Plans - Fire Alarm

FA1.04 Elev #3 Second Floor Plans - Fire Alarm

FA5.01 Detail Sheet - Fire Alarm

Sprinkler

FX0.01 Reference Sheet - Sprinkler

FX1.00 Elev #1 & #2 Lower Floor Plans - Sprinkler

FX1.01 Elev & #2 Level 1-4 Floor Plans - Sprinkler

FX1.02 Elev #3 Lower Level Floor Plans - Sprinkler

FX1.03 Elev #3 First Floor Plans - Sprinkler

FX1.04 Elev #3 Second Floor Plans - Sprinkler

FX5.01 Detail Sheet - Sprinkler

SHEET INDEX

GMU Enterprise Hall

Elevator Modernization Project Code: 247-242012

4400 University Drive Fairfax, Virginia 22030

LAE

WN

O M

M O

OF

I

NI

G

RI

H V

E C TCRA

MICHAEL DETOMO

Lic. No. 15799

T

C

A

IH T

Consultants

703.684.5994

333 North Fairfax Street

Alexandria, Virginia 22314

Seal

Key Plan

Drawing

Revisions

Date

Project No.

Sheet No.

OUBO Submission 09/26/2025

Submission Set coleanddenny.com

PC No.: 247-242012

Permit Electronic Approval Stamp

03/11/2026

03/11/2026

20011.22

4400 University Drive Fairfax, Virginia 22030

G0.01

Cover Sheet

GMU Enterprise Hall Elevator Modernization

APPLICABLE CODES

MATERIALS

DRAWING SYMBOLS

CODE SUMMARY

LOCATION MAP

ABBREVIATIONS

PHASING

# NUMBER

& AND

@ AT

ACP ACOUSTICAL CEILING PANEL

AFF ABOVE FINISH FLOOR

ALT ALTERNATIVE

ALUM ALUMINUM

ASTM AMERICAN SOCIETY OF TESTING &

MATERIALS

BD BUILDING

BOT BOTTOM

CJ CONTROL JOINT

CLG CEILING

CLOS CLOSET

CMU CONCRETE MASONRY UNIT

CONC CONCRETE

CONT CONTINUOUS

CPT CARPET

CT CERAMIC TILE

DEMO DEMOLITION

DF DRINKING FOUNTAIN

DIA DIAMETER

DN DOWN

DS DOWNSPOUT

EF EXHAUST FAN

EIFS EXTERIOR INSULATION FINISHING SYSTEM

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATOR

EQ EQUAL

EQUIP EQUIPMENT

ETR EXISTING TO REMAIN

EXIST EXISTING

EXT EXTERIOR

FE FIRE EXTINGUISHER

FRT FIRE RETARDANT TREATED

FT FEET/FOOT

GA GAUGE

GALV GALVANIZED

GWB GYPSUM WALL BOARD

HDWR HARDWARE

HM HOLLOW METAL

HR HOUR

IN INCH

INSUL INSULATION

INT INTERIOR

JAN JANITOR'S CLOSET

JT JOINT

MAX MAXIMUM

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MO MASONRY OPENING

MTL METAL

N NORTH

NIC NOT IN CONTRACT

NO NUMBER

OC ON CENTER

PLAM PLASTIC LAMINATE

PLUMB PLUMBING

PLYWD PLYWOOD

PT PRESSURE TREATED

PTD PAINTED

PVC POLYVINYL CHLORIDE

RB RESILIENT BASE

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

RM ROOM

SCW SOLID CORE WOOD

SF SQUARE FOOT/FEET

SIM SIMILAR

SST STAINLESS STEEL

STOR STORAGE

STRUCT STRUCTURAL

THRU THROUGH

TOS TOP OF STEEL

TYP TYPICAL

UL UNDERWRITER'S LABORATORIES

UNO UNLESS NOTED OTHERWISE

VCT VINYL COMPOSITE TILE

VEST VESTIBULE

VIF VERIFY IN FIELD

VWC VINYL WALL COVERING

W/ WITH

WD WOOD

THE BUILDING CODE AUTHORITY IS THE OFFICE OF THE UNIVERSITY BUILDING OFFICIAL (OUBO) OF

GEORGE MASON UNIVERSITY (GMU).

THE BUILDING CODE FOR THIS PROJECT IS THE VIRGINIA UNIFORM STATEWIDE BUILDING CODE (VUSBC) 2021 EDITION, EFFECTIVE JANUARY 24, 2024. ALL WORK SHALL CONFORM TO THE BUILDING CODE.

THE PROJECT IS CLASSIFIED AS A LEVEL II ALTERATION PER SECTION 601 OF THE VIRGINIA EXISTING

BUILDING CODE, 2021 EDITION.

THE FIRE CODES FOR THIS PROJECT ARE THE VIRGINIA STATE FIRE PREVENTION CODE, 2021 EDITION.

THE HIGHER EDUCATION CAPITAL OUTLAY (HECO) 2023 EDITION APPLIES TO THIS PROJECT.

GEORGE MASON UNIVERSITY DESIGN MANUAL, 2013 EDITION

THE COMPLIANCE PATH FOR ACCESSIBILITY FOR THIS PROJECT IS ADASO-TITLE II. THE ADA STANDARD FOR SCOPE OF WORK IS CHAPTER 2 OF THE DOJ'S 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN (ASAD) DATED SEPTEMBER 16, 2010. THE ADA STANDARDS FOR TECHNICAL DESIGN ARE CHAPTERS | 8 THRU II OF STANDARDS FOR ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES AI 17.1-2017.

APPROVED MARCH 28, 2017.

THE PROJECT CONSISTS OF THE MODERNIZATION OF THREE HYDRAULIC ELEVATORS IN THE ENTERPRISE HALL CLASSROOM AND OFFICE BUILDING OF THE GEORGE MASON UNIVERSITY. ELEVATORS #1 & #2 IS A 5-STOP ELEVATOR BANK, AND ELEVATOR #3 IS A 3-STOP ELEVATOR. MODERNIZATION CONSISTS OF RENOVATIONS OF THE ELEVATOR PIT AND REPLACING ELEVATOR DOORS. THE ELEVATOR WILL ALSO BE UPGRADED WITH NEW INTERIOR STAINLESS STEEL INTERIOR PANELS, LIGHTING, AND CALL BUTTONS. ALL NECESSARY MODIFICATIONS SHALL BE MADE TO BRING THE ELEVATOR UP TO CURRENT CODE. WORK WILL BE CONDUCTED IN 2 PHASES SUCH THAT THE BUILDING WILL REMAIN OCCUPIED DURING CONSTRUCTION AND ELEVATOR ACCESS TO ALL

FLOORS SHALL BE MAINTAINED. SEE PHASING DIAGRAM AND NARRATIVE ON PH1.01

DESCRIPTION OF WORK

IN ACCORDANCE WITH THE HIGH PERFORMANCE BUILDING ACT, THE BUILDING IS EXEMPT FROM BUILDING IS EXEMPT FROM COMPLIANCE BECAUSE THE COST OF THE RENOVATIONS DOES NOT EXCEED 50% OF THE

VALUE OF THE BUILDING.

HIGH PERFORMANCE BUILDING ACT-

COMPLIANCE STATEMENT

IN ACCORDANCE WITH THE VIRGINIA ENERGY CONSERVATION CODE (VECC), THE BUILDING SHALL COMPLY WITH

VECC SECTIONS C402 THROUGH C405 AND C408.

VECC COMPLIANCE STATEMENT

ORIGINAL CODE BUILT UNDER:

ORIGINAL USE GROUP

ORIGINAL CONSTRUCTION TYPE:

VUSBC 2021 USE & OCC CLASSIFICATION

VUSBC 2021 CONSTRUCTION TYPE:

SPRINKLERED:

EXISTING BUILDING AREA:

EXISTING BUILDING HEIGHT:

NON-HIGH-RISE BUILDING PER <75'-0"

HIGHEST OCCUPIED FLOOR HEIGHT:

PROJECT AREA:

VUSBC 1990

A-3, B & E

IIA

A-3 & B

IIA

YES

101,200 GSF

6 STORIES, 86'-4"

70'-4"

3,250 SF

VICINITY MAP

ADDITIVE ITEM #1

PHASING

ALL WORK RELATED TO THE MODERNIZATION OF ELEVATOR #3 SHALL BE BID AS AN ADDITIVE ITEM.

THE PROJECT WORK WILL BE CONDUCTED IN 3 PHASES SUCH THAT THE BUILDING WILL REMAIN OCCUPIED DURING CONSTRUCTION AND ELEVATOR ACCESS TO ALL FLOORS SHALL BE MAINTAINED. EACH PHASE CONSISTS OF ONE ELEVATOR MODERNIZATION. SEE PH1.01 FOR PHASING PLAN AND NARRATIVE.

THE CONTRACTOR SHALL RETAIN THE NECESSARY DESIGN PROFESSIONALS LICENSED IN THE JURISDICTION OF THE PROJECT TO FULLY DESIGN AND DETAIL THE FOLLOWING DELEGATED DESIGN ITEMS. DELEGATED DESIGN SUBMITTALS SHALL INCLUDE SIGNED AND SEALED DRAWINGS AND CALCULATIONS AS NECESSARY:

1. SYSTEMS WITH SHOP DRAWING REVIEW & APPROVAL BY OUBO AFTER A/E REVIEW AND APPROVAL:

A. FIRE SUPPRESSION SYSTEMS

B. FIRE ALARM SYSTEMS

C. IN-BUILDING EMERGENCY COMMUNICATIONS INFRASTRUCTURE (RATH)

D. ELEVATOR CAB (ENGINEER SEAL NOT REQUIRED)

2. SYSTEMS WITH SHOP DRAWING REVIEW & APPROVAL BY THE A/E:

A. INTERIOR NON-LOAD BEARING METAL STUD WALLS

B. BOLTED AND WELDED STEEL CONNECTIONS

C. DUCTWORK SUPPORT HANGERS

D. PIPING SUPPORT HANGERS

E. ELEVATOR PIT LADDERS

DELEGATED DESIGN ITEMS

No. Revision Date 1 Response to Comments 11/20/2025

2 Response to Comments 02/09/2026

3 Response to Comments 03/11/2026

Revisions

Date

OUBO Submission 09/26/2025

Submission Set

03/11/2026

No. Revision Date 1 Response to Comments 11/20/2025

2 Response to Comments 02/09/2026

3 Response to Comments 03/11/2026

APPROVED FOR

CONSTRUCTION

Date = 03/17/2026

These construction documents have been examined in accordance with the 2021 Virginia Uniform Statewide Building Code (USBC). Submittals and/or shop drawings have not been provided or reviewed as part of this process.

The Registered Design Professional and/or Building/Tradesman Contractor shall be solely responsible for the correct installation and construction of all required systems in compliance with Federal, State, Local codes and manufacturing installation instructions. Request required special inspections and provide to A&E for review. Request inspections required by OUBO in accordance with OUBO policies and procedures. Any revisions that occur during the course of construction shall not be made to this set without the explicit permission of the OUBO in accordance with OUBO policies and procedures.

2-HR FIRE BARRIER

EGRESS STARTING POINT

POINT AT WHICH A CHOICE OF

TWO EXITS BECOMES AVAILABLE

REMAINING TRAVEL DISTANCE

(REMAINING TRAVEL DISTANCE +

COMMON PATH OF TRAVEL <300')

COMMON PATH OF TRAVEL (<100')

TYPE-B EGRESS LEGEND

AREAS

OF WORK

ELEC ROOM

LOBBY

KITCHENETTE

ELEV MACH

ROOM

LOBBY

47'

58'

113'

20'

TEL/

COMM

#1

ELEVATOR

#2

ELEVATOR

ELEV MACH

ROOM

#3

ELEVATOR

121'

66'

JAN CL

JAN CL

2-HR FIRE BARRIER

EGRESS STARTING POINT

POINT AT WHICH A CHOICE OF

TWO EXITS BECOMES AVAILABLE

REMAINING TRAVEL DISTANCE

(REMAINING TRAVEL DISTANCE +

COMMON PATH OF TRAVEL <250')

COMMON PATH OF TRAVEL (<75')

TYPE-A EGRESS LEGEND

LAE

WN

O M

M O

OF

I

NI

G

RI

H V

E C TCRA

MICHAEL DETOMO

Lic. No. 15799

T

C

A

IH T

Consultants

703.684.5994

333 North Fairfax Street

Alexandria, Virginia 22314

Seal

Key Plan

Drawing

Revisions

Date

Project No.

Sheet No.

OUBO Submission 09/26/2025

Submission Set coleanddenny.com

PC No.: 247-242012

Permit Electronic Approval Stamp

03/11/2026

03/11/2026

20011.22

4400 University Drive Fairfax, Virginia 22030

G1.01

Egress, Occupancy & Fire Resistance Rating Plan

GMU Enterprise Hall Elevator Modernization

1" = 10'-0"A1.03 G1.01

1 LOWER LEVEL EGRESS PLAN

0' 5' 10' 20'

SCALE: 1" = 10'

N

No. Revision Date

Revisions

Date

OUBO Submission 09/26/2025

Submission Set

03/11/2026

No. Revision Date 1 Response to Comments 11/20/2025

2 Response to Comments 02/09/2026

3 Response to Comments 03/11/2026

APPROVED FOR

CONSTRUCTION

Date = 03/17/2026

These construction documents have been examined in accordance with the 2021 Virginia Uniform Statewide Building Code (USBC). Submittals and/or shop drawings have not been provided or reviewed as part of this process.

The Registered Design Professional and/or Building/Tradesman Contractor shall be solely responsible for the correct installation and construction of all required systems in compliance with Federal, State, Local codes and manufacturing installation instructions. Request required special inspections and provide to A&E for review. Request inspections required by OUBO in accordance with OUBO policies and procedures. Any revisions that occur during the course of construction shall not be made to this set without the

X XX X X

AREAS

OF WORK

ELEC ROOM

LOBBY

KITCHENETTE

ELEV MACH

ROOM

LOBBY

PROVIDE SAFETY NETTING HOISTWAY

SCREENING SUCH THAT THE PORTION

OF THE ELEVATOR HOISTWAY WHERE

THE WORK IS TO BE PERFORMED

SHALL BE FULLY SEPARATED

PHASE 1 PHASE 2

PHASE 1&2

PHASE 3

ADDITIVE

ITEM #1

PHASE 1, 2, & 3

PROVIDE 4'X3' GCVIF EXTERIOR

CONCRETE PAD FOR NEW CONDENSING

UNIT PER 2/PH1.01. SEE MECH.

PROVIDE 8'X3' GCVIF EXTERIOR

CONCRETE PAD FOR NEW CONDENSING

UNIT PER 2/PH1.01. SEE MECH.

THE PROJECT WORK WILL BE CONDUCTED IN 3 PHASES SUCH THAT THE BUILDING WILL REMAIN OCCUPIED DURING CONSTRUCTION

AND ELEVATOR ACCESS TO ALL FLOORS SHALL BE MAINTAINED.

PHASE 1

1. INSTALL HOISTWAY SAFETY NETTING SUCH THAT ELEVATOR #1 AND ELEVATOR #2 ARE SEPARATED WITHIN SHARED SHAFT

2. REMOVE EXISTING ELEVATOR MACHINE ROOM 033 / KITCHENETTE WALL 031

3. BUILD NEW ELEVATOR MACHINE ROOM 033 / KITCHENETTE WALL 031

4. REMOVE EXISTING ELEVATOR EQUIPMENT ASSOCIATED WITH ELEVATOR #1

5. INSTALL NEW ELEVATOR EQUIPMENT ASSOCIATED WITH ELEVATOR #1

6. PERFORM ALL WORK REQUIRED TO MODERNIZE ELEVATOR #1 SHAFT, CAB, AND LOBBY COMPONENTS

7. PROVIDE EXTERIOR CONCRETE PADS AND INSTALL NEW CONDENSING UNITS TO SERVE ELEV #1 & ELEV #2

8. INSTALL NEW FAN COIL UNITS IN MACHINE ROOM 033 FOR ELEV #1 & #2

9. REMOVE PARTIAL SUPPLY AIR DUCT TO ELEVATOR MACHINE ROOM 033 (SEE MECH)

10. CLOSE IN CEILING IN ELEVATOR MACHINE ROOM 033 AND KITCHENETTE 031 AS REQUIRED FOR ELEVATOR INSPECTION

PHASE 2

1. REMOVE EXISTING ELEVATOR EQUIPMENT ASSOCIATED WITH ELEVATOR #2

2. INSTALL NEW ELEVATOR EQUIPMENT ASSOCIATED WITH ELEVATOR #2

3. PERFORM ALL WORK REQUIRED TO MODERNIZE ELEVATOR #2 SHAFT, CAB, AND LOBBY COMPONENTS

4. CLOSE IN CEILING IN ELEVATOR MACHINE ROOM 033

PHASE 3 (ADDITIVE ITEM #1)

1. REMOVE EXISTING ELEVATOR EQUIPMENT ASSOCIATED WITH ELEVATOR #3

2. INSTALL NEW ELEVATOR EQUIPMENT ASSOCIATED WITH ELEVATOR #3

3. PERFORM ALL WORK REQUIRED TO MODERNIZE ELEVATOR #3 SHAFT, CAB, AND LOBBY COMPONENTS

4. PROVIDE EXTERIOR CONCRETE PAD AND INSTALL NEW CONDENSING UNIT

5. INSTALL NEW FAN COIL UNITS IN ELEVATOR MACHINE ROOM 022

6. CLOSE IN CEILING IN ELEVATOR MACHINE ROOM 022

PHASING NARRATIVE

JAN CL

JAN CL

TEL/

COMM

PHASE 1

PHASE 3

ADDITIVE ITEM #1

ELEV MACH

ROOM

1 1/2"

6"

3"

CAST IN PLACE CONCRETE EQUIPMENT PAD PER ASTM C387:

4,000 PSI @ 28 DAYS, REGULAR WEIGHT AGGREGATE, MAX

WATER TO CEMENT RATIO OF 0.45, 6% AIR-ENTRAINMENT

ADMIXTURE ADDED WITH A TOLERANCE OF ± 1.5%.

2" MIN COMPACTED

#57 BLUESTONE

6 MIL VAPOR

BARRIER

4" X 4" WELDED WIRE MESH

EQUIPMENT BASE

MECHANICALLY FASTEN TO PAD

WITH1/2" SS POST-INSTALLED BOLT AND

WASHER WITH ZINC INSERT AS NEEDED

LAE

WN

O M

M O

OF

I

NI

G

RI

H V

E C TCRA

MICHAEL DETOMO

Lic. No. 15799

T

C

A

IH T

Consultants

703.684.5994

333 North Fairfax Street

Alexandria, Virginia 22314

Seal

Key Plan

Drawing

Revisions

Date

Project No.

Sheet No.

OUBO Submission 09/26/2025

Submission Set coleanddenny.com

PC No.: 247-242012

Permit Electronic Approval Stamp

03/11/2026

03/11/2026

20011.22

4400 University Drive Fairfax, Virginia 22030

PH1.01

Phasing Plan

GMU Enterprise Hall Elevator Modernization

1" = 10'-0"A1.03 PH1.01

1 PHASING PLAN

1" = 1'-0"PH1.01

2 CONC PAD DETAIL

0' 5' 10' 20'

SCALE: 1" = 10'

N

No. Revision Date 1 Response to Comments 11/20/2025

Revisions

Date

OUBO Submission 09/26/2025

Submission Set

03/11/2026

No. Revision Date 1 Response to Comments 11/20/2025

2 Response to Comments 02/09/2026

3 Response to Comments 03/11/2026

APPROVED FOR

CONSTRUCTION

Date = 03/17/2026

These construction documents have been examined in accordance with the 2021 Virginia Uniform Statewide Building Code (USBC). Submittals and/or shop drawings have not been provided or reviewed as part of this process.

The Registered Design Professional and/or Building/Tradesman Contractor shall be solely responsible for the correct installation and construction of all required systems in compliance with Federal, State, Local codes and manufacturing installation instructions. Request required special inspections and provide to A&E for review. Request inspections required by OUBO in accordance with OUBO policies and procedures. Any revisions that occur during the course of construction shall not be made to this set without the

OF WORK

J K

AD4.01AD1.01

AD4.01

AD1.01 ---

MEN'S

TOILET

WOMEN'S

TOILET

#1

ELEVATOR

#2

ELEVATOR

LOBBY

KITCHENETTE

TEL/

COMM

ELEV MACH

ROOM

STAIR #2

AD4.017

S im

Sim

Sim

S im AD4.017

S im

Sim

Sim

S im

D-1

6'-9" D-2

D-1

AD1.01 AD1.01

AD1.03AD1.01

J K

AD4.01AD1.01

AD4.01

HYDRAULIC

PUMP #1

OIL

COOL

#1

ELEVATOR

CONTROLLER #1

STACKED ELEV

DISCONNECTS

- SEE ELEC

STACKED ELEV

CAB LIGHT

DISCONNECTS

- SEE ELEC

D U C

TL

E S

A C -1

A B O

V E

RATH

#1

H Y D R A U

LI

P O

W E R U

N

IT

C O

N

TR

O L

BATTERY

LOWERING

DEVICE #2MAINLINE

DISCS #2

RELOCATED CAB

LIGHT DISC #2

HALL BUTTON

INTERFACE #2

EXIST FA

PANEL ABOVE

STACKED OIL

MINDER AND

SUMP POWER -

SEE ELEC

HYDRAULIC POWER

UNIT #1

H Y D R A U

W E R U

N

IT

CONTROL #1

C O

N

TR

O L

BATTERY

LOWERING

DEVICE #2

STACKED

MAINLINE DISCS

#1TO BE DEMO'D

#2 TO REMAIN CAB LIGHT

DISC #1

RELOCATE

CAB LIGHT

DISC #2

HALL BUTTON

INTERFACE #1

HALL BUTTON

INTERFACE #2

FA PANEL TO REMAIN

CONDUIT CHASE

LAE

WN

O M

M O

OF

I

NI

G

RI

H V

E C TCRA

MICHAEL DETOMO

Lic. No. 15799

T

C

A

IH T

Consultants

703.684.5994

333 North Fairfax Street

Alexandria, Virginia 22314

Seal

Key Plan

Drawing

Revisions

Date

Project No.

Sheet No.

OUBO Submission 09/26/2025

Submission Set coleanddenny.com

PC No.: 247-242012

Permit Electronic Approval Stamp

03/11/2026

03/11/2026

20011.22

4400 University Drive Fairfax, Virginia 22030

AD1.01

Partial Demolition Floor Plan - Elev #1 & #2

GMU Enterprise Hall Elevator Modernization

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

KEYED DEMO NOTES

1/4" = 1'-0"AD1.01

1 PARTIAL LOWER LEVEL DEMO PLAN - ELEV #1 &#2

1/4" = 1'-0"AD1.01

2 PARTIAL DEMO PLAN LEVEL 1 THRU 4 - ELEV #1 & #2

N

1. REVIEW PHASING PLAN AND NARRATIVE ON PH1.01. DEMOLITION WORK RELATED TO

ELEVATOR #1 TO BE DONE IN A SEPARATE PHASE FROM WORK RELATED TO ELEVATOR #2

SUCH THAT ONE ELEVATOR REMAINS FULLY OPERATIONAL AT ALL TIMES. SEE ADDITIONAL

NOTES ON MEP SHEETS.

A. EXCEPTION: EXIST CAB LIGHT DISCONNECT FOR ELEVATOR #2 SHALL BE TEMPORARILY

RELOCATED LOWER IN PHASE ONE TO ALLOW FOR MOUNTING POSITION OF NEW

ELEVATOR #1 CONTROLLER. RELOCATED CAB LIGHT DISCONNECT FOR ELEVATOR #2

SHALL THEN BE FULLY DEMOLISHED IN PHASE TWO.

2. REMOVE OR REROUTE ALL CONDUIT, PIPES AND DUCTS NOT SERVING THE ELEVATOR

MACHINE ROOM EQUIPMENT.

3. PATCH ALL WALL PENETRATIONS AFTER REMOVAL. TOOTH IN MASONRY USING FULL BLOCKS

WHERE NECESSARY. MACHINE ROOM AND HOISTWAY WALLS ARE 2-HOUR RATED.

4. SEE SHEET A 5.01 FOR APPROVED UL PENETRATION DETAILS

5. RETAIN AND REFURBISH EXIST HYDRAULIC PIPING AS APPROPRIATE.

6. REPLACE ALL EXISTING HYDRAULIC FITTINGS.

7. REMOVE EXISTING ELEVATOR CONTROLLERS AND HYDRAULIC POWER UNITS TO BE REPLACED

WITH NON-PROPRIETARY UNITS - SEE MEP

MACHINE ROOM DEMOLITION NOTES

GENERAL DEMOLITION NOTES

1. ALL EXISTING DIMENSIONS AND CONDITIONS SHALL BE FIELD VERIFIED.

2. REPAIR EXISTING CONSTRUCTION TO REMAIN WHERE MECHANICAL, PLUMBING, FIRE PROTECTION, AND ELECTRICAL

WORK IS REMOVED TO MATCH EXISTING CONSTRUCTION.

3. WHERE MASONRY IS EXPOSED, TOOTH-IN NEW WORK WITH FULL-SIZE MASONRY UNITS.

4. PATCH AS REQUIRED TO ACCOMMODATE NEW MECHANICAL, PLUMBING, AND ELECTRICAL WORK.

REFER TO

ENGINEERING DRAWINGS. ALL NEW WORK SHALL BE CONCEALED UNLESS NOTED OTHERWISE.

5. PROTECT EXIT FLOOR & WALL FINISHES ADJACENT TO THE AREA OF WORK DURING CONSTRUCTION.

6. REQUIRED DEMOLITION SHALL NOT BE LIMITED TO THAT PORTION ON THE PLANS, BUT SHALL

INCLUDE ALL NECESSARY WORK (OR INCIDENTAL THERE TO) TO COMPLETE THE WORK IN

ACCORDANCE WITH THE CONTRACT DOCUMENTS.

D-1 PARTIAL DEMOLITION OF EXIST METAL STUD AND GWB WALL TO EXTENTS SHOWN

D-2 PARTIAL DEMOLITION OF EXIST 2-HR RATED CMU WALL TO EXTENTS SHOWN

1/2" = 1'-0"AD1.01

4 PHASE 2 - ELEV MACH ROOM DEMO PLAN

1/2" = 1'-0"AD1.01 AD1.01

3 PHASE 1 - ELEV MACH ROOM DEMO PLAN

No. Revision Date

Revisions

Date

OUBO Submission 09/26/2025

Submission Set

03/11/2026

No. Revision Date 1 Response to Comments 11/20/2025

2 Response to Comments 02/09/2026

3 Response to Comments 03/11/2026

APPROVED FOR

CONSTRUCTION

Date = 03/17/2026

These construction documents have been examined in accordance with the 2021 Virginia Uniform Statewide Building Code (USBC). Submittals and/or shop drawings have not been provided or reviewed as part of this process.

The Registered Design Professional and/or Building/Tradesman Contractor shall be solely responsible for the correct installation and construction of all required systems in compliance with Federal, State, Local codes and manufacturing installation instructions. Request required special inspections and provide to A&E for review. Request inspections required by OUBO in accordance with OUBO policies and procedures. Any revisions that occur during the course of construction shall not be made to this set without the

E F G

STAIR

#3

CLASSROOM

ELEV MACH

ROOM

#3

ELEVATOR

LOBBY

AD4.02AD1.02

AD4.022

AD1.02 AD1.02

AD4.025

S im 6

S im

Sim

Sim

E F G

WOMEN'S

TOILET

STAIR

#3

#3

ELEVATOR

LOBBY

COMM /

TELL

AD4.02AD1.02

AD4.023

MECH SHAFT

E F G

WOMEN'S

TOILET

#3

ELEVATOR

STIAR #3

COMM /

TEL208

LOBBY

AD4.02AD1.02

AD4.024

MECH SHAFT

H Y D R A U

W E R U

N

IT

C O

N

TR

O L

MAINLINE

DISC #3

CAB LIGHT

DISC #3

HALL BUTTON

INTERFACE #3

FA PANEL

CONDUIT

CHASE

BATTERY

LOWERING

DEVICE #3

AREAS

OF WORK

LAE

WN

O M

M O

OF

I

NI

G

RI

H V

E C TCRA

MICHAEL DETOMO

Lic. No. 15799

T

C

A

IH T

Consultants

703.684.5994

333 North Fairfax Street

Alexandria, Virginia 22314

Seal

Key Plan

Drawing

Revisions

Date

Project No.

Sheet No.

OUBO Submission 09/26/2025

Submission Set coleanddenny.com

PC No.: 247-242012

Permit Electronic Approval Stamp

ADDITIVE ITEM #1

02/09/2026

03/11/2026

20011.22

4400 University Drive Fairfax, Virginia 22030

AD1.02

Partial Demolition Floor Plan - Elevator #3

GMU Enterprise Hall Elevator Modernization

1/4" = 1'-0"AD1.02

1 PARTIAL LOWER LEVEL DEMO PLAN - ELEV #3

1/4" = 1'-0"AD1.02

2 PARTIAL FIRST FLOOR DEMO PLAN - ELEV #3

1/4" = 1'-0"AD1.02

3 PARTIAL SECOND FLOOR DEMO PLAN - ELEV #3

1/2" = 1'-0"AD1.02 AD1.02

4 ELEVATOR MACHINE ROOM DEMO PLAN

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

N

GENERAL DEMOLITION NOTES

1. ALL EXISTING DIMENSIONS AND CONDITIONS SHALL BE FIELD VERIFIED.

2. REPAIR EXISTING CONSTRUCTION TO REMAIN WHERE MECHANICAL, PLUMBING, FIRE PROTECTION, AND ELECTRICAL

WORK IS REMOVED TO MATCH EXISTING CONSTRUCTION.

3. WHERE MASONRY IS EXPOSED, TOOTH-IN NEW WORK WITH FULL-SIZE MASONRY UNITS.

4. PATCH AS REQUIRED TO ACCOMMODATE NEW MECHANICAL, PLUMBING, AND ELECTRICAL WORK. REFER TO

ENGINEERING DRAWINGS. ALL NEW WORK SHALL BE CONCEALED UNLESS NOTED OTHERWISE.

5. PROTECT EXIT FLOOR & WALL FINISHES ADJACENT TO THE AREA OF WORK DURING CONSTRUCTION.

6. REQUIRED DEMOLITION SHALL NOT BE LIMITED TO THAT PORTION ON THE PLANS, BUT SHALL INCLUDE ALL

NECESSARY WORK (OR INCIDENTAL THERE TO) TO COMPLETE THE WORK IN ACCORDANCE WITH THE CONTRACT

DOCUMENTS.

1. REVIEW PHASING PLAN AND NARRATIVE ON PH1.01. ALL WORK RELATED TO ELEVATOR #3

TO BE COMPLETED IN PHASE #3

2. REMOVE OR REROUTE ALL CONDUIT, PIPES AND DUCTS NOT SERVING THE ELEVATOR

MACHINE ROOM EQUIPMENT.

3. PATCH ALL WALL PENETRATIONS AFTER REMOVAL. TOOTH IN MASONRY USING FULL BLOCKS

WHERE NECESSARY. MACHINE ROOM AND HOISTWAY WALLS ARE 2-HOUR RATED.

4. SEE SHEET A 5.01 FOR APPROVED UL PENETRATION DETAILS

5. RETAIN AND REFURBISH EXIST HYDRAULIC PIPING AS APPROPRIATE.

6. REPLACE ALL EXISTING HYDRAULIC FITTINGS.

7. REMOVE EXISTING ELEVATOR CONTROLLERS AND HYDRAULIC POWER UNITS TO BE

REPLACED WITH NON-PROPRIETARY UNITS - SEE ELEC

MACHINE ROOM DEMOLITION NOTES

No. Revision Date

Revisions

Date

OUBO Submission 09/26/2025

Submission Set

03/11/2026

No. Revision Date 1 Response to Comments 11/20/2025

2 Response to Comments 02/09/2026

3 Response to Comments 03/11/2026

APPROVED FOR

CONSTRUCTION

Date = 03/17/2026

These construction documents have been examined in accordance with the 2021 Virginia Uniform Statewide Building Code (USBC). Submittals and/or shop drawings have not been provided or reviewed as part of this process.

The Registered Design Professional and/or Building/Tradesman Contractor shall be solely responsible for the correct installation and construction of all required systems in compliance with Federal, State, Local codes and manufacturing installation instructions. Request required special inspections and provide to A&E for review. Request inspections required by OUBO in accordance with OUBO policies and procedures. Any revisions that occur during the course of construction shall not be made to this set without the

AD4.01AD1.01

ELEV MACH

ROOM

TEL/

COMM

KITCHENETTE

MEN'S

TOILET

WOMEN'S

TOILET

#1

ELEVATOR

#2

ELEVATOR

LOBBY

STAIR #2

AD1.03AD1.01

AD4.01AD1.01

MEN'S

TOILET

STAIR #2

WOMEN'S

TOILET

LOBBY

#1

ELEVATOR

#2

ELEVATOR

AREAS

OF WORK

Lower Level

421' - 5"

First Floor

435' - 5"

REMOVE EXIST 2HR

RATED CMU WALL

EXIST 2HR RATED

CEILING ASSEMBLY

EXIST 90MIN RATED

ACCESS PANEL

REMOVE EXIST

FIRE DAMPER

REMOVE EXIST CONC LINTEL

EXIST DUCTWORK

REMOVE EXIST ACP

CEILING AND GRID

ELEV MACH

ROOM 031

KITCHENETTE

EXIST ACP TO BE REMOVED

AND REPLACED AS

REQUIRED FOR ACCESS TO

PERFORM THE WORK ABOVE

LAE

WN

O M

M O

OF

I

NI

G

RI

H V

E C TCRA

MICHAEL DETOMO

Lic. No. 15799

T

C

A

IH T

Consultants

703.684.5994

333 North Fairfax Street

Alexandria, Virginia 22314

Seal

Key Plan

Drawing

Revisions

Date

Project No.

Sheet No.

OUBO Submission 09/26/2025

Submission Set coleanddenny.com

PC No.: 247-242012

Permit Electronic Approval Stamp

03/11/2026

03/11/2026

20011.22

4400 University Drive Fairfax, Virginia 22030

AD1.03

Partial Demo RCP - Elev #1 & #2

GMU Enterprise Hall Elevator Modernization

1/4" = 1'-0"AD1.03

1 PARTIAL LOWER LEVEL DEMO RCP - ELEV #1 & #2

1/4" = 1'-0"AD1.03

2 PARTIAL DEMO RCP LEVEL 1 THRU 4 - ELEV #1 & #2

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

N

GENERAL DEMOLITION NOTES

1. ALL EXISTING DIMENSIONS AND CONDITIONS SHALL BE FIELD VERIFIED.

2. REPAIR EXISTING CONSTRUCTION TO REMAIN WHERE MECHANICAL, PLUMBING, FIRE PROTECTION, AND ELECTRICAL

WORK IS REMOVED TO MATCH EXISTING CONSTRUCTION.

3. WHERE MASONRY IS EXPOSED, TOOTH-IN NEW WORK WITH FULL-SIZE MASONRY UNITS.

4. PATCH AS REQUIRED TO ACCOMMODATE NEW MECHANICAL, PLUMBING, AND ELECTRICAL WORK. REFER TO

ENGINEERING DRAWINGS. ALL NEW WORK SHALL BE CONCEALED UNLESS NOTED OTHERWISE.

5. PROTECT EXIT FLOOR & WALL FINISHES ADJACENT TO THE AREA OF WORK DURING CONSTRUCTION.

6. REQUIRED DEMOLITION SHALL NOT BE LIMITED TO THAT PORTION ON THE PLANS, BUT SHALL INCLUDE ALL

NECESSARY WORK (OR INCIDENTAL THERE TO) TO COMPLETE THE WORK IN ACCORDANCE WITH THE CONTRACT

DOCUMENTS.

3/8" = 1'-0"AD1.01 AD1.03

3 PARTIAL DEMO SECTION ELEV MACH ROOM

No. Revision Date 2 Response to Comments 02/09/2026

Revisions

Date

OUBO Submission 09/26/2025

Submission Set

03/11/2026

No. Revision Date 1 Response to Comments 11/20/2025

2 Response to Comments 02/09/2026

3 Response to Comments 03/11/2026

APPROVED FOR

CONSTRUCTION

Date = 03/17/2026

These construction documents have been examined in accordance with the 2021 Virginia Uniform Statewide Building Code (USBC). Submittals and/or shop drawings have not been provided or reviewed as part of this process.

The Registered Design Professional and/or Building/Tradesman Contractor shall be solely responsible for the correct installation and construction of all required systems in compliance with Federal, State, Local codes and manufacturing installation instructions. Request required special inspections and provide to A&E for review. Request inspections required by OUBO in accordance with OUBO policies and procedures. Any revisions that occur during the course of construction shall not be made to this set without the

AD4.02AD1.02

STAIR

#3

CLASSROOM

ELEV MACH

ROOM

#3

ELEVATOR

LOBBY

WOMEN'S

TOILET

AD4.02AD1.02

WOMEN'S

TOILET

STAIR

#3

#3

ELEVATOR

LOBBY

COMM /

TELL

MECH SHAFT

AD4.02AD1.02

WOMEN'S

TOILET

#3

ELEVATOR

STIAR #3

COMM /

TEL

LOBBY

MECH SHAFT

AREAS

OF WORK

LAE

WN

O M

M O

OF

I

NI

G

RI

H V

E C TCRA

MICHAEL DETOMO

Lic. No. 15799

T

C

A

IH T

Consultants

703.684.5994

333 North Fairfax Street

Alexandria, Virginia 22314

Seal

Key Plan

Drawing

Revisions

Date

Project No.

Sheet No.

OUBO Submission 09/26/2025

Submission Set coleanddenny.com

PC No.: 247-242012

Permit Electronic Approval Stamp

ADDITIVE ITEM #1

02/09/2026

03/11/2026

20011.22

4400 University Drive Fairfax, Virginia 22030

AD1.04

Partial Demo RCP - Elevator #3

GMU Enterprise Hall Elevator Modernization

1/4" = 1'-0"AD1.04

1 PARTIAL LOWER LEVEL DEMO RCP - ELEV #3

1/4" = 1'-0"AD1.04

2 PARTIAL FIRST FLOOR DEMO RCP - ELEV #3

1/4" = 1'-0"AD1.04

3 PARTIAL SECOND FLOOR DEMO RCP - ELEV #3

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

N

GENERAL DEMOLITION NOTES

1. ALL EXISTING DIMENSIONS AND CONDITIONS SHALL BE FIELD VERIFIED.

2. REPAIR EXISTING CONSTRUCTION TO REMAIN WHERE MECHANICAL, PLUMBING, FIRE PROTECTION, AND ELECTRICAL

WORK IS REMOVED TO MATCH EXISTING CONSTRUCTION.

3. WHERE MASONRY IS EXPOSED, TOOTH-IN NEW WORK WITH FULL-SIZE MASONRY UNITS.

4. PATCH AS REQUIRED TO ACCOMMODATE NEW MECHANICAL, PLUMBING, AND ELECTRICAL WORK. REFER TO

ENGINEERING DRAWINGS. ALL NEW WORK SHALL BE CONCEALED UNLESS NOTED OTHERWISE.

5. PROTECT EXIT FLOOR & WALL FINISHES ADJACENT TO THE AREA OF WORK DURING CONSTRUCTION.

6. REQUIRED DEMOLITION SHALL NOT BE LIMITED TO THAT PORTION ON THE PLANS, BUT SHALL INCLUDE ALL

NECESSARY WORK (OR INCIDENTAL THERE TO) TO COMPLETE THE WORK IN ACCORDANCE WITH THE CONTRACT

DOCUMENTS.

No. Revision Date

Revisions

Date

OUBO Submission 09/26/2025

Submission Set

03/11/2026

No. Revision Date 1 Response to Comments 11/20/2025

2 Response to Comments 02/09/2026

3 Response to Comments 03/11/2026

APPROVED FOR

CONSTRUCTION

Date = 03/17/2026

These construction documents have been examined in accordance with the 2021 Virginia Uniform Statewide Building Code (USBC). Submittals and/or shop drawings have not been provided or reviewed as part of this process.

The Registered Design Professional and/or Building/Tradesman Contractor shall be solely responsible for the correct installation and construction of all required systems in compliance with Federal, State, Local codes and manufacturing installation instructions. Request required special inspections and provide to A&E for review. Request inspections required by OUBO in accordance with OUBO policies and procedures. Any revisions that occur during the course of construction shall not be made to this set without the

D-4

D-3

D-1

REMOVE COP PANEL

D-1

D-3

D-4

D-3

D-6

D-7

D-4

AREAS

OF WORK

Lower Level

421' - 5"

First Floor

435' - 5"

Second Floor

449' - 5"

Third Floor

463' - 5"

Fourth Floor

477' - 5"

Roof

491' - 5"

Pit #1

417' - 0 1/4"

D-1

D-2

D-12

D-8

D-11

TYP

D-10

D-9

D-8

D-11

TYP

D-10

D-9

D-3

D-7

D-4

LAE

WN

O M

M O

OF

I

NI

G

RI

H V

E C TCRA

MICHAEL DETOMO

Lic. No. 15799

T

C

A

IH T

Consultants

703.684.5994

333 North Fairfax Street

Alexandria, Virginia 22314

Seal

Key Plan

Drawing

Revisions

Date

Project No.

Sheet No.

OUBO Submission 09/26/2025

Submission Set coleanddenny.com

PC No.: 247-242012

Permit Electronic Approval Stamp

03/11/2026

03/11/2026

20011.22

4400 University Drive Fairfax, Virginia 22030

AD4.01

Demo Int Elevations, Sections, and Details - Elevator #1 & #2

GMU Enterprise Hall Elevator Modernization

1/4" = 1'-0"AD4.01

5 ELEV CAR 1 - DEMO RCP

1/4" = 1'-0"AD4.01

4 ELEV CAR 1 - DEMO FLOOR PLAN

1/4" = 1'-0"AD1.01 AD4.01

8 ELEV CAR 1 DOOR - DEMO ELEVATION

1/4" = 1'-0"AD1.01 AD4.01

6 ELEV CAR 1 - DEMO ELEVATION

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"1/4" = 1'-0"AD1.01 AD4.01

1 DEMO SECTION - ELEVATOR SHAFT #1 & #2

1/4" = 1'-0"AD1.01 AD4.01

2 LOWER LEVEL LOBBY ELEVATION

1/4" = 1'-0"AD1.01 AD4.01

3 LEVEL 1 THRU 4 LOBBY ELEVATION

1/4" = 1'-0"AD1.01 AD4.01

7 ELEV CAR - DEMO ELEVATION

GENERAL DEMOLITION NOTES

1. ALL EXISTING DIMENSIONS AND CONDITIONS SHALL BE FIELD VERIFIED.

2. REQUIRED DEMOLITION SHALL NOT BE LIMITED TO THAT PORTION ON THE PLANS, BUT SHALL INCLUDE ALL

NECESSARY WORK (OR INCIDENTAL THERE TO) TO COMPLETE THE WORK IN ACCORDANCE WITH THE

CONTRACT DOCUMENTS.

3. REMOVE FLOOR, AND CEILING FINISHES AND CONSTRUCTION AS INDICATED.

4. REPAIR EXISTING CONSTRUCTION TO REMAIN WHERE MECHANICAL, PLUMBING, FIRE PROTECTION, AND

ELECTRICAL WORK IS REMOVED TO MATCH EXISTING CONSTRUCTION.

D-1 REMOVE EXIST ELEVATOR CAR DOORS

D-2 REMOVE EXIST DOOR OPERATORS

D-3 REMOVE EXIST TILE FLOORING

D-4 REMOVE EXISTING CEILING AND LIGHTS

D-6 REMOVE EXIST HAND RAILS

D-7 REMOVE EXIST PLAM WALL PANELS

D-8 REMOVE EXIST HALL LANTERNS, PATCH AND PAINT EXCESS OPENING TO MATCH EXIST

D-9 REMOVE EXIST EGRESS SIGNAGE AND SAVE FOR REINSTALLATION

D-10 REMOVE EXIST UNUSED JBOX AND COVER PLATE, PATCH AND PAINT TO MATCH EXIST

D-11 REMOVE EXIST ELEVATOR CALL BUTTON, PATCH AND PAINT EXCESS OPENING TO MATCH EXIST

D-12 REMOVE EXIST PITT LADDER

KEYED DEMO NOTES

ELEV CAR DEMOLITION NOTES

1. RETAIN & REFURBISH CAR SLING, SAND AND PAINT

2. RETAIN & REFURBISH CAR SHELL

3. RETAIN & REFURBISH CAR PLATFORM

4. REMOVE AND REPLACE EXISTING ISOLATION PADS

5. REMOVE AND REPLACE EXISTING SUBFLOORING

No. Revision Date 1 Response to Comments 11/20/2025

Revisions

Date

OUBO Submission 09/26/2025

Submission Set

03/11/2026

No. Revision Date 1 Response to Comments 11/20/2025

2 Response to Comments 02/09/2026

3 Response to Comments 03/11/2026

APPROVED FOR

CONSTRUCTION

Date = 03/17/2026

These construction documents have been examined in accordance with the 2021 Virginia Uniform Statewide Building Code (USBC). Submittals and/or shop drawings have not been provided or reviewed as part of this process.

The Registered Design Professional and/or Building/Tradesman Contractor shall be solely responsible for the correct installation and construction of all required systems in compliance with Federal, State, Local codes and manufacturing installation instructions. Request required special inspections and provide to A&E for review. Request inspections required by OUBO in accordance with OUBO policies and procedures. Any revisions that occur during the course of construction shall not be made to this set without the

Lower Level

421' - 5"

First Floor

435' - 5"

Second Floor

449' - 5"

Third Floor

463' - 5"

G

Pit #3

417' - 4"

D-1

D-2

D-12

D-8

D-11

D-10

D-9

D-8

D-11

D-10

D-9

D-8

D-11

D-10

D-9

REMOVE COP PANEL

D-1

D-3

D-4

D-3

D-6

D-6

D-4

D-3

D-6

D-4

D-3

D-1

D-4

LAE

WN

O M

M O

OF

I

NI

G

RI

H V

E C TCRA

MICHAEL DETOMO

Lic. No. 15799

T

C

A

IH T

Consultants

703.684.5994

333 North Fairfax Street

Alexandria, Virginia 22314

Seal

Key Plan

Drawing

Revisions

Date

Project No.

Sheet No.

OUBO Submission 09/26/2025

Submission Set coleanddenny.com

PC No.: 247-242012

Permit Electronic Approval Stamp

ADDITIVE ITEM #1

02/09/2026

03/11/2026

20011.22

4400 University Drive Fairfax, Virginia 22030

AD4.02

Demo Int Elevations, Sections, and Details - Elevator #3

GMU Enterprise Hall Elevator Modernization

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

1/4" = 1'-0"AD1.02 AD4.02

1 DEMO SECTION - ELEVATOR SHAFT #3

1/4" = 1'-0"A1.02 AD4.02

2 LOWER LEVEL DEMO ELEVATION

1/4" = 1'-0"AD1.02 AD4.02

3 FIRST FLOOR DEMO ELEVATION

1/4" = 1'-0"AD1.02 AD4.02

4 SECOND FLOOR DEMO ELEVATION

1/4" = 1'-0"AD1.02 AD4.02

5 ELEV CAR DOOR - DEMO ELEVATION

1/4" = 1'-0"AD1.02 AD4.02

6 ELEV CAR - DEMO ELEVATION

1/4" = 1'-0"AD1.02 AD4.02

7 ELEV CAR - DEMO ELEVATION

1/4" = 1'-0"AD4.02

8 ELEV CAR - DEMO FLOOR PLAN

1/4" = 1'-0"AD4.02

9 ELEV CA - DEMO RCP

GENERAL DEMOLITION NOTES

1. ALL EXISTING DIMENSIONS AND CONDITIONS SHALL BE FIELD VERIFIED.

2. REQUIRED DEMOLITION SHALL NOT BE LIMITED TO THAT PORTION ON THE PLANS, BUT SHALL INCLUDE ALL

NECESSARY WORK (OR INCIDENTAL THERE TO) TO COMPLETE THE WORK IN ACCORDANCE WITH THE

CONTRACT DOCUMENTS.

3. REMOVE FLOOR, AND CEILING FINISHES AND CONSTRUCTION AS INDICATED.

4. REPAIR EXISTING CONSTRUCTION TO REMAIN WHERE MECHANICAL, PLUMBING, FIRE PROTECTION, AND

ELECTRICAL WORK IS REMOVED TO MATCH EXISTING CONSTRUCTION.

D-1 REMOVE EXIST ELEVATOR CAR DOORS

D-2 REMOVE EXIST DOOR OPERATORS

D-3 REMOVE EXIST TILE FLOORING

D-4 REMOVE EXISTING CEILING AND LIGHTS

D-6 REMOVE EXIST HAND RAILS

D-7 REMOVE EXIST PLAM WALL PANELS

D-8 REMOVE EXIST HALL LANTERNS, PATCH AND PAINT EXCESS OPENING TO MATCH EXIST

D-9 REMOVE EXIST EGRESS SIGNAGE AND SAVE FOR REINSTALLATION

D-10 REMOVE EXIST UNUSED JBOX AND COVER PLATE, PATCH AND PAINT TO MATCH EXIST

D-11 REMOVE EXIST ELEVATOR CALL BUTTON, PATCH AND PAINT EXCESS OPENING TO MATCH EXIST

D-12 REMOVE EXIST PITT LADDER

KEYED DEMO NOTES

ELEV CAR DEMOLITION NOTES

1. RETAIN & REFURBISH CAR SLING, SAND AND PAINT

2. RETAIN & REFURBISH CAR SHELL

3. RETAIN & REFURBISH CAR PLATFORM

4. REMOVE AND REPLACE EXISTING ISOLATION PADS

5. REMOVE AND REPLACE EXISTING SUBFLOORING

No. Revision Date 1 Response to Comments 11/20/2025

Revisions

Date

OUBO Submission 09/26/2025

Submission Set

03/11/2026

No. Revision Date 1 Response to Comments 11/20/2025

2 Response to Comments 02/09/2026

3 Response to Comments 03/11/2026

APPROVED FOR

CONSTRUCTION

Date = 03/17/2026

These construction documents have been examined in accordance with the 2021 Virginia Uniform Statewide Building Code (USBC). Submittals and/or shop drawings have not been provided or reviewed as part of this process.

The Registered Design Professional and/or Building/Tradesman Contractor shall be solely responsible for the correct installation and construction of all required systems in compliance with Federal, State, Local codes and manufacturing installation instructions. Request required special inspections and provide to A&E for review. Request inspections required by OUBO in accordance with OUBO policies and procedures. Any revisions that occur during the course of construction shall not be made to this set without the

J K

ELEV MACH

ROOM

TEL/

COMM

KITCHENETTE

MEN'S

TOILET

WOMEN'S

TOILET

#1

ELEVATOR

#2

ELEVATOR

LOBBY

STAIR #2

A4.01A1.01 A4.01

5' -0

6'-2"

A1.01 A1.01

EQ

EQ

A4.01

Sim

S im

Sim

S im A4.01

Sim

S im

Sim

S im

REF REF

A5.01A1.01

R-20

R-21

A1.03A1.01

A1.03A1.01

J K

MEN'S

TOILET

WOMEN'S

TOILET

STAIR #2

VV

TT

SS

RR

LOBBY

A4.01A1.01

A4.01

#1

ELEVATOR

#2

ELEVATOR

A5.01A1.01

HYDRAULIC

PUMP #1

OIL

COOL

#1

OIL

COOL

#2

ELEV

CONTROLLER #1

ELEV

CONTROLLER #2

HYDRAULIC

PUMP #2

STACKED ELEV

DISCONNECTS

- SEE ELEC

STACKED ELEV

CAB LIGHT

DISCONNECTS

- SEE ELEC

DUCTLESS

AC-2 ABOVE

D U C

TL

E

-1

A B O

V E

RATH

#2

RATH

#1

STACKED OIL

MINDER AND SUMP

POWER - SEE ELEC

A1.03A1.01

A1.03A1.01

R-1

R-2

R-4

R-5

R-6

R-7

R-1

R-2

R-3

R-4

R-5

R-6

R-7

A5.01A1.01

R-8R-8R-8 R-8

LAE

WN

O M

M O

OF

I

NI

G

RI

H V

E C TCRA

MICHAEL DETOMO

Lic. No. 15799

T

C

A

IH T

Consultants

703.684.5994

333 North Fairfax Street

Alexandria, Virginia 22314

Seal

Key Plan

Drawing

Revisions

Date

Project No.

Sheet No.

OUBO Submission 09/26/2025

Submission Set coleanddenny.com

PC No.: 247-242012

Permit Electronic Approval Stamp

03/11/2026

03/11/2026

20011.22

4400 University Drive Fairfax, Virginia 22030

A1.01

Partial Floor Plans - Elev #1 & #2

GMU Enterprise Hall Elevator Modernization

GENERAL NEW WORK NOTES

1. DIMENSIONS ARE TO FINISH FACE OF CONSTRUCTION UNLESS OTHERWISE INDICATED.

2. OUTSIDE OF DOOR JAMBS TO BE 4" FROM WALL INTERSECTION UNLESS OTHERWISE INDICATED.

3. PROVIDE NON-COMBUSTIBLE OR FIRE RETARDANT TREATED WOOD BLOCKING IN PARTITIONS WHERE

REQUIRED TO SUPPORT WALL MOUNTED ITEMS.

4. "TOOTH-IN" MASONRY WHERE ALTERING OR REPAIRING EXISTING MASONRY. MORTAR COLOR SHALL MATCH

EXISTING MORTAR.

R-1 RETAIN & REFURBISH EXISTING HYDRAULIC JACK ASSEMBLY, PROVIDE NEW SEALS

R-2 RETAIN & REFURBISH EXISTING HYDRAULIC OIL PIPING, PROVIDE NEW VICTAULIC FITTINGS, PAINT EXIST PIPE

R-3 RETAIN & REFURBISH EXISTING PIT CHANNEL, PAINT CHANNEL

R-4 INSTALL NEW PIT LADDER SUCH THAT EACH SIDE RAIL EXTENSION SHALL BE DESIGNED TO RESIST A SINGLE CONCENTRATED LOAD OF 100 POUNDS IN ACCORDANCE WITH VCC 1607.17 AND SECTION 4.5.4 OF ASCE 7.

R-5 PROVIDE NEW LED PIT LIGHTING WITH MIN OF 10FC - SEE ELEC

R-6 PROVIDE NEW SURFACE MOUNTED SUMP PUMP - SEE PLUMB

R-7 PROVIDE NEW NON-PROPRIETARY HOISTWAY DOOR OPERATING EQUIPMENT

R-8 SAND AND PAINT RETAINED EXIST RAILS

R-9 PROVIDE NEW LED LIGHT, PATCH AND REAPAIR EXIST GWB CEILING - SEE ELEC

R-10 INSTALL FLOOR DESIGNATIONS IN TACTLE CHARACTERS & BRAILLE ON BOTH JAMBS OF THE ELEV HOISTWAY

ENTRANCE PER 2017 ANSI 407.2.3.1

R-11 LOCATE HALL LANTERN W/ DIRECTIONAL SIGNAL CENTERED AT 72" MIN AFF - TYP

R-12 LOCATE FIRE FIGHTERS RECALL SWITCH ABOVE CALL BUTTONS

R-13 LOCATE HALL ELEVATOR CALL BUTTONS RECESSED FLUSH TO THE WALL WITH ENGRAVING AT 48" MAX TO THE

CENTERLINE OF HIGHEST OPERABLE PART - TYP

R-14 INSTALL ELEVATOR EMERGENCY POWER INDICATOR AT 76" MIN AFF

R-15 RETAIN AND PROVIDE NEW PAINT AT ENTRANCE DOORS

R-16 RETAIN AND PROVIDE NEW PAINT AT ENTRANCE FRAMES

R-17 PROVIDE NEW TEXTURED STAINLESS STEEL CAR DOORS

R-18 PROVIDE NEW 2X2 LAY-IN ACP AND GRID. COORDINATE WITH OWNER FOR ATTIC STOCK

R-19 PROVIDE NEW 2X4 FLOURESCENT TROFFER FIXTURE TO MATCH EXISTING CORRIDOR LIGHTS - SEE ELEC

R-20 PATCH AND REPAIR EXIST GWB WALL

R-21 PROVIDE NEW HOLLOW METAL FRAME FOR 3' X 7' CASED OPENING

KEYED REPAIR NOTES

1/4" = 1'-0"A1.01

1 PARTIAL LOWER LEVEL FLOOR PLAN - ELEV #1 & #2

1/4" = 1'-0"A1.01

PARTIAL FLOOR PLAN LEVEL

1 THRU 4 - ELEV #1 & #2

1/2" = 1'-0"A1.01 A1.01

3 ELEVATOR MACHINE ROOM PLAN

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

N

1/2" = 1'-0"A1.01

4 ELEVATOR #1 & #2 PIT

1. PROVIDE NEW SHUT OFF VALVE

2. PROVIDE NEW SCAVENGER PUMP

3. PROVIDE NEW CAR LANDING SYSTEM

4. PROVIDE NEW LIMIT SWITCHES

5. PROVIDE NEW VICTAULIC FITTINGS

SHAFT AND PIT NEW WORK NOTES

1. REVIEW PHASING PLAN AND NARRATIVE ON PH1.01. NEW WORK RELATED TO ELEVATOR #1 TO BE DONE IN A SEPARATE PHASE FROM NEW WORK RELATED TO ELEVATOR #2 SUCH THAT ONE ELEVATOR REMAINS

FULLY OPERATIONAL AT ALL TIMES. SEE ADDITIONAL NOTES ON MEP SHEETS.

2. SEE A5.01 FOR RATH WIRING DIAGRAM AND SHEETS T-001THRU T-202 FOR PLANS AND ADDITIONAL

INFORMATION ON THE ELEVATOR EMERGENCY TWO-WAY COMMUNICATION SYSTEM (RATH).

ELEVATOR MACHINE ROOM NOTES

No. Revision Date

Revisions

Date

OUBO Submission 09/26/2025

Submission Set

03/11/2026

No. Revision Date 1 Response to Comments 11/20/2025

2 Response to Comments 02/09/2026

3 Response to Comments 03/11/2026

APPROVED FOR

CONSTRUCTION

Date = 03/17/2026

These construction documents have been examined in accordance with the 2021 Virginia Uniform Statewide Building Code (USBC). Submittals and/or shop drawings have not been provided or reviewed as part of this process.

The Registered Design Professional and/or Building/Tradesman Contractor shall be solely responsible for the correct installation and construction of all required systems in compliance with Federal, State, Local codes and manufacturing installation instructions. Request required special inspections and provide to A&E for review. Request inspections required by OUBO in accordance with OUBO policies and procedures. Any revisions that occur during the course of construction shall not be made to this set without the

E F G

STAIR

#3

CLASSROOM

ELEV MACH

ROOM

#3

ELEVATOR

LOBBY

A4.02A1.02

A4.02 2

WOMEN'S

TOILET

A1.02 A1.02

A4.029

E F G

WOMEN'S

TOILET

STAIR

#3

#3

ELEVATOR

LOBBY

COMM /

TELL

A4.02A1.02

A4.02 3

MECH SHAFT

E F G

WOMEN'S

TOILET

#3

ELEVATOR

STIAR #3

COMM /

TEL208

LOBBY

A4.02A1.02

A4.02 4

MECH SHAFT

HYDRAULIC

PUMP #3

OIL COOL

#3

ELEV

CONTROLLER #3

OIL MINDER

CONTROLS

RATH BASE STATION

#3 - SEE TELE

D U C

TL

E

-3

A B O

V E

RELOCATED SHUNT

TRIP BREAKER

AC-3 CONDENSATE

REMOVAL PUMP

ELEVATOR CAB

POWER DISCONNECT

SUMP PUMP POWER

R-1

R-2

R-4

R-5 R-6

R-7

R-8

R-8

LAE

WN

O M

M O

OF

I

NI

G

RI

H V

E C TCRA

MICHAEL DETOMO

Lic. No. 15799

T

C

A

IH T

Consultants

703.684.5994

333 North Fairfax Street

Alexandria, Virginia 22314

Seal

Key Plan

Drawing

Revisions

Date

Project No.

Sheet No.

OUBO Submission 09/26/2025

Submission Set coleanddenny.com

PC No.: 247-242012

Permit Electronic Approval Stamp

ADDITIVE ITEM #1

02/09/2026

03/11/2026

20011.22

4400 University Drive Fairfax, Virginia 22030

A1.02

Partial Floor Plans - Elevator #3

GMU Enterprise Hall Elevator Modernization

GENERAL NEW WORK NOTES

1. DIMENSIONS ARE TO FINISH FACE OF CONSTRUCTION UNLESS OTHERWISE INDICATED.

2. OUTSIDE OF DOOR JAMBS TO BE 4" FROM WALL INTERSECTION UNLESS OTHERWISE

INDICATED.

3. PROVIDE NON-COMBUSTIBLE OR FIRE RETARDANT TREATED WOOD BLOCKING IN

PARTITIONS WHERE REQUIRED TO SUPPORT WALL MOUNTED ITEMS SUCH AS

TELEVISIONS, DIGITAL MEDIA PLAYERS, DRY ERASE BOARDS, SMART BOARDS, ETC. SEE

FLOOR PLAN. GC SHALL COORDINATE WITH OWNER FOR LOCATIONS OF BLOCKING. THE

OWNER SHALL PROVIDE THESE WALL MOUNTED DEVICES.

4. "TOOTH-IN" MASONRY WHERE ALTERING OR REPAIRING EXISTING MASONRY. MORTAR

COLOR SHALL MATCH EXISTING MORTAR.

R-1 RETAIN & REFURBISH EXISTING HYDRAULIC JACK ASSEMBLY, PROVIDE NEW SEALS

R-2 RETAIN & REFURBISH EXISTING HYDRAULIC OIL PIPING, PROVIDE NEW VICTAULIC FITTINGS, PAINT EXIST PIPE

R-3 RETAIN & REFURBISH EXISTING PIT CHANNEL, PAINT CHANNEL

R-4 INSTALL NEW PIT LADDER SUCH THAT EACH SIDE RAIL EXTENSION SHALL BE DESIGNED TO RESIST A SINGLE CONCENTRATED LOAD OF 100 POUNDS IN ACCORDANCE WITH VCC 1607.17 AND SECTION 4.5.4 OF ASCE 7.

R-5 PROVIDE NEW LED PIT LIGHTING WITH MIN OF 10FC - SEE ELEC

R-6 PROVIDE NEW SURFACE MOUNTED SUMP PUMP - SEE PLUMB

R-7 PROVIDE NEW NON-PROPRIETARY HOISTWAY DOOR OPERATING EQUIPMENT

R-8 SAND AND PAINT RETAINED EXIST RAILS

R-9 PROVIDE NEW LED LIGHT, PATCH AND REAPAIR EXIST GWB CEILING - SEE ELEC

R-10 INSTALL FLOOR DESIGNATIONS IN TACTLE CHARACTERS & BRAILLE ON BOTH JAMBS OF THE ELEV HOISTWAY

ENTRANCE PER 2017 ANSI 407.2.3.1

R-11 LOCATE HALL LANTERN W/ DIRECTIONAL SIGNAL CENTERED AT 72" MIN AFF - TYP

R-12 LOCATE FIRE FIGHTERS RECALL SWITCH ABOVE CALL BUTTONS

R-13 LOCATE HALL ELEVATOR CALL BUTTONS RECESSED FLUSH TO THE WALL WITH ENGRAVING AT 48" MAX TO THE

CENTERLINE OF HIGHEST OPERABLE PART - TYP

R-14 INSTALL ELEVATOR EMERGENCY POWER INDICATOR AT 76" MIN AFF

R-15 RETAIN AND PROVIDE NEW PAINT AT ENTRANCE DOORS

R-16 RETAIN AND PROVIDE NEW PAINT AT ENTRANCE FRAMES

R-17 PROVIDE NEW TEXTURED STAINLESS STEEL CAR DOORS

R-18 PROVIDE NEW 2X2 LAY-IN ACP AND GRID. COORDINATE WITH OWNER FOR ATTIC STOCK

R-19 PROVIDE NEW 2X4 FLOURESCENT TROFFER FIXTURE TO MATCH EXISTING CORRIDOR LIGHTS - SEE ELEC

R-20 PATCH AND REPAIR EXIST GWB WALL

R-21 PROVIDE NEW HOLLOW METAL FRAME FOR 3' X 7' CASED OPENING

KEYED REPAIR NOTES

1/4" = 1'-0"A1.02

1 PARTIAL LOWER LEVEL FLOOR PLAN - ELEV #3

1/4" = 1'-0"A1.02

2 PARTIAL FIRST FLOOR PLAN - ELEV #3

1/4" = 1'-0"A1.02

3 PARTIAL SECOND FLOOR PLAN - ELEV #3

1/2" = 1'-0"A1.02 A1.02

4 ELEVATOR MACHINE ROOM PLAN

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

N

1/2" = 1'-0"A1.02

5 ELEVATOR #3 PIT

1. PROVIDE NEW SHUT OFF VALVE

2. PROVIDE NEW SCAVENGER PUMP

3. PROVIDE NEW CAR LANDING SYSTEM

4. PROVIDE NEW LIMIT SWITCHES

5. PROVIDE NEW VICTAULIC FITTINGS

SHAFT AND PIT NEW WORK NOTES

09/26/2025

1. REVIEW PHASING PLAN AND NARRATIVE ON PH1.01. ALL WORK RELATED TO ELEVATOR #3 TO BE

COMPLETED IN PHASE #3. SEE ADDITIONAL NOTES ON MEP SHEETS.

2. SEE A5.01 FOR RATH WIRING DIAGRAM AND SHEETS T-001THRU T-202 FOR PLANS AND ADDITIONAL

INFORMATION ON THE ELEVATOR EMERGENCY TWO-WAY COMMUNICATION SYSTEM (RATH).

ELEVATOR MACHINE ROOM NOTES

No. Revision Date

Revisions

Date

OUBO Submission 09/26/2025

Submission Set

03/11/2026

No. Revision Date 1 Response to Comments 11/20/2025

2 Response to Comments 02/09/2026

3 Response to Comments 03/11/2026

APPROVED FOR

CONSTRUCTION

Date = 03/17/2026

These construction documents have been examined in accordance with the 2021 Virginia Uniform Statewide Building Code (USBC). Submittals and/or shop drawings have not been provided or reviewed as part of this process.

The Registered Design Professional and/or Building/Tradesman Contractor shall be solely responsible for the correct installation and construction of all required systems in compliance with Federal, State, Local codes and manufacturing installation instructions. Request required special inspections and provide to A&E for review. Request inspections required by OUBO in accordance with OUBO policies and procedures. Any revisions that occur during the course of construction shall not be made to this set without the

ELEV MACH

ROOM

TEL/

COMM

KITCHENETTE

MEN'S

TOILET

WOMEN'S

TOILET

#1

ELEVATOR

#2

ELEVATOR

LOBBY

STAIR #2

A4.01A1.01

R-9

R-9

TYP (11)

R-18

R-19 R-18

A1.03A1.01

A1.03A1.01

MEN'S

TOILET

#1

ELEVATOR

#2

ELEVATOR

STAIR #2

WOMEN'S

TOILET

LOBBY

A4.01A1.01

R-9

TYP (11)

AREAS

OF WORK

Lower Level

421' - 5"

First Floor

435' - 5"

NEW 2HR RATED CEILING

ASSEMBLY PER UL-I506

OR SIMILAR TO EXTEND

THE RATED CEILING TO

THE NEW RATED WALL

EXIST 2HR RATED

CEILING ASSEMBLY

EXIST ACP TO BE REMOVED

AND REPLACED AS

REQUIRED FOR ACCESS TO

PERFORM THE WORK ABOVE

2 HR HORIZ SHAFT

WALL DUCT AND

CEILING ASSEMBLY -

SEE WHI 694-0300

ON A5.02

A1.03A1.01

KITCHENETTE

ELEV MACH

ROOM

EXIST 90MIN RATED

ACCESS PANEL

Lower Level

421' - 5"

A1.03A1.01

ELEV MACH

ROOM031

KITCHENETTE

CORRIDOR

NEW 2HR RATED CEILING

ASSEMBLY PER UL-I506

OR SIMILAR TO EXTEND

THE RATED CEILING TO

THE NEW RATED WALL

PROVIDE NEW FIRE DAMPER

AND ASSOCIATED

ACCESORIES WHERE

EXISTING DUCT PENETRATES

NEW RATED WALL

ENCLOSURE - SEE MECH

EXIST 24X16 DUCT TO

REMAIN - SEE MECH

EXIST 44X16 DUCT TO

REMAIN - SEE MECH

LAE

WN

O M

M O

OF

I

NI

G

RI

H V

E C TCRA

MICHAEL DETOMO

Lic. No. 15799

T

C

A

IH T

Consultants

703.684.5994

333 North Fairfax Street

Alexandria, Virginia 22314

Seal

Key Plan

Drawing

Revisions

Date

Project No.

Sheet No.

OUBO Submission 09/26/2025

Submission Set coleanddenny.com

PC No.: 247-242012

Permit Electronic Approval Stamp

03/11/2026

03/11/2026

20011.22

4400 University Drive Fairfax, Virginia 22030

A1.03

Partial RCP - Elevator #1 & #2

GMU Enterprise Hall Elevator Modernization

1/4" = 1'-0"A1.03

1 PARTIAL LOWER LEVEL RCP - ELEV #1 & #2

1/4" = 1'-0"A1.03

2 PARTIAL RCP LEVEL 1 THRU 4 - ELEV #1 & #2

GENERAL NEW WORK NOTES

1. DIMENSIONS ARE TO FINISH FACE OF CONSTRUCTION UNLESS OTHERWISE INDICATED.

2. OUTSIDE OF DOOR JAMBS TO BE 4" FROM WALL INTERSECTION UNLESS OTHERWISE INDICATED.

3. PROVIDE NON-COMBUSTIBLE OR FIRE RETARDANT TREATED WOOD BLOCKING IN PARTITIONS

WHERE REQUIRED TO SUPPORT WALL MOUNTED ITEMS SUCH AS TELEVISIONS, DIGITAL MEDIA

PLAYERS, DRY ERASE BOARDS, SMART BOARDS, ETC. SEE FLOOR PLAN. GC SHALL COORDINATE

WITH OWNER FOR LOCATIONS OF BLOCKING. THE OWNER SHALL PROVIDE THESE WALL MOUNTED

DEVICES.

4. "TOOTH-IN" MASONRY WHERE ALTERING OR REPAIRING EXISTING MASONRY. MORTAR COLOR

SHALL MATCH EXISTING MORTAR.

R-1 RETAIN & REFURBISH EXISTING HYDRAULIC JACK ASSEMBLY, PROVIDE NEW SEALS

R-2 RETAIN & REFURBISH EXISTING HYDRAULIC OIL PIPING, PROVIDE NEW VICTAULIC FITTINGS, PAINT EXIST PIPE

R-3 RETAIN & REFURBISH EXISTING PIT CHANNEL, PAINT CHANNEL

R-4 INSTALL NEW PIT LADDER SUCH THAT EACH SIDE RAIL EXTENSION SHALL BE DESIGNED TO RESIST A SINGLE CONCENTRATED LOAD OF 100 POUNDS IN ACCORDANCE WITH VCC 1607.17 AND SECTION 4.5.4 OF ASCE 7.

R-5 PROVIDE NEW LED PIT LIGHTING WITH MIN OF 10FC - SEE ELEC

R-6 PROVIDE NEW SURFACE MOUNTED SUMP PUMP - SEE PLUMB

R-7 PROVIDE NEW NON-PROPRIETARY HOISTWAY DOOR OPERATING EQUIPMENT

R-8 SAND AND PAINT RETAINED EXIST RAILS

R-9 PROVIDE NEW LED LIGHT, PATCH AND REAPAIR EXIST GWB CEILING - SEE ELEC

R-10 INSTALL FLOOR DESIGNATIONS IN TACTLE CHARACTERS & BRAILLE ON BOTH JAMBS OF THE ELEV HOISTWAY

ENTRANCE PER 2017 ANSI 407.2.3.1

R-11 LOCATE HALL LANTERN W/ DIRECTIONAL SIGNAL CENTERED AT 72" MIN AFF - TYP

R-12 LOCATE FIRE FIGHTERS RECALL SWITCH ABOVE CALL BUTTONS

R-13 LOCATE HALL ELEVATOR CALL BUTTONS RECESSED FLUSH TO THE WALL WITH ENGRAVING AT 48" MAX TO THE

CENTERLINE OF HIGHEST OPERABLE PART - TYP

R-14 INSTALL ELEVATOR EMERGENCY POWER INDICATOR AT 76" MIN AFF

R-15 RETAIN AND PROVIDE NEW PAINT AT ENTRANCE DOORS

R-16 RETAIN…