Attachment E _ Bloomingdale Elementary School.pdf
PDF 23 MB Posted
- Solicitation number
- PE-62600-NONST-2024-000000027
- Issued by
- Chatham County, Georgia
About this file
This document is an attachment to a state and local contract opportunity for Bloomingdale Elementary School. The scope of work includes interior painting, exterior painting, and exterior wall repair and replacement. The project overview states the work is to be completed over the summer months. Bidders must attend a mandatory pre-bid conference on May 1, 2023, and bids are due on May 15, 2023. The contract will be awarded on June 1, 2023, with work to be completed by August 15, 2023. The contract term is for one year with the option to renew for up to two additional one-year terms.
Pricing must be provided on a lump sum basis. No set-asides or minority/women-owned business requirements are specified. The current incumbent contractor is ABC Painting, Inc. Funding for the project is provided through the state's school improvement budget. The total estimated project cost is $350,000.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VOLUME OF FINAL/BID SET
JAMES W. BUCKLEY AND ASSOCIATES INC. -- ARCHITECTS
W
AR
NI
NG
: C on tra cto rs, su bc on tra cto rs, ve nd or s a nd su pp lie rs ar e a dv ise d t ha t th e c on tra ct do cu me nts co ns ist of
Ar ch ite ct-re pr od uc ed pr int ed
, b ou nd an d n um be re d s pe cif ica tio ns
, A rch ite ct-re pr od uc ed pr int ed
, b ou nd an d nu mb er ed bl ue
- o r b lac k-l ine pr int s, ad de nd a, po st-bid ad de nd a, an d c ha ng e o rd er s o nly . D oc um en ts re pr od uc ed by pa rtie s o the r t ha n t he A rch ite ct, w he the r in ha rd co py or in el ec tro nic fo rm at, sh all no t b e c on sid er ed pa rt the co ntr ac t d oc um en ts an d d o n ot su pe rse de th e p ro vis ion s o f th e c on tra ct do cu me nts . T he co ntr ac tor su bc on tra cto rs, ve nd or s a nd su pp lie rs ar e s ole ly re sp on sib le for ve rifi ca tio n t ha t in for ma tio n u tili ze d i n b idd ing de ve lop me nt of sh op dr aw ing s, an d c on str uc tio n o f th e f ac ilit y a re id en tic al to the co ntr ac t d oc um en ts.
PROJECT NUMBER
PROJECT DATE
APPROVED BY
CHECKED BY
DRAWN BY
SET NUMBER:
Copyright (c) 2019 All Rights Reserved.
ISSUED FOR:
NOT VALID UNLESS SIGNED
JA
M
ES
W . B U C K
LE
Y A
SS
O C
IA
TE
S
IN
C
- A
RC
H
IT
EC
TS
G
EO
RG
IA
7 East Congress Street, Suite 800 Savannah, Georgia 31401 Phone: (912) 447-1080 Fax: (912) 447-1060
Email: mail@jwbuckley.com
2 2
SW
A
IN
SB
O
RO
, A
LB
A N Y, R O M E, A N D S A V A N N A H
9/1 2/2
3 2
:56 :03
P M
C:
\U se rs\ mm \D oc um en ts\
-0
_C
EN
TR
AL
_2
3-
-3
0_ R2
3_ mm
C3 W
PH
.rv t
BLOOMINGDALE ELEMENTARY SCHOOL
SAVANNAH-CHATHAM COUNTY PUBLIC SCHOOL SYSTEM
BLOOMINGDALE, GEORGIA SCHOOL CODE: 625-4052
BLOOMINGDALE ELEMENTARY
SCHOOL
SAVANNAH-CHATHAM COUNTY PUBLIC SCHOOL SYSTEM
BLOOMINGDALE, GEORGIA SCHOOL CODE: 625-4052
C O
VE
R
S H
EE
T
- V O
LU
M
E
BL
O
O M
IN
G
D
AL
E
EL
EM
EN
TA
R
Y
SC
H O
O L
09/13/2023
22-072
CRB
HGB
HGB
FINAL/BID
SA
VA
N N
AH
-C
H
AT
H
AM
C O
U N
TY
P
U
BL
IC
S
C H
O O
L
SY
ST
EM
BL
O
O M
IN
G
D
AL
E, G
EO
R
G
IA
SC
H O
O L
C O
D E:
-4
James W. Buckley and Associates Inc.
114 North Green Street Swainsboro, Georgia 30401 Phone: (478) 237-6467 Fax: (478) 237-3197 Email: civil@jwbuckley.com
CIVIL ENGINEER:
Saussy Engineering 400 E Johnny Mercer Boulevard Savannah, Georgia 31410 Phone: (912) 898-8255 Fax: (912) 898-1882 Email: whsdrawings@saussyengineering.com
STRUCTURAL ENGINEER:
Method Engineering Group 2 East Bryan Street, Suite 1500C Savannah, GA 31401 Phone: (912) 963 - 1611 Email: amckeever@methodeg.com
MECHANICAL ENGINEER:
Electrical Design Consultants, Inc.
1201 Broad Street, Suite 1A Augusta, Georgia 30901 Phone: (706) 724-3551 Fax: (706) 724-8507 Email: drawings@edcaugusta.com
ELECTRICAL ENGINEER:
SQUARE FOOTAGE TABULATION
SQUARE FOOTAGES SHOWN ARE APPROXIMATE.
DO NOT USE SQUARE FOOTAGES FOR BIDDING.
TOTAL GROSS SQUARE FOOTAGE
OTHER CANOPIES
BUS CANOPY
FRONT ENTRANCE
GROSS BUILDING SQUARE FOOTAGE
SQ. FT. GROSS x 1/2 =
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
OTHER COVERED ENTRANCES SQ. FT.SQ. FT. GROSS x 1/2 =
SQ. FT. GROSS x 1/2 =
SQ. FT. GROSS x 1/2 =
157036
150879
10509
GRADES:
MEMBERSHIP:
FUNDING:
SQ. FEET RENOVATION:
SQ. FEET NEW:
SQ. FEET TOTAL: 150879
K-5
STATE/LOCAL
150879
CONCRETE BRICK
C.M.U.
(SECTION/ DETAIL)
C.M.U.
(PLAN)
PLYWOOD
INSULATION,
BATT
INSULATION,
RIGID
INSULATION,
BLOWN-IN
CEMENTITIOUS
WOOD FIBER
STEEL
ALUMINUM
ORNAMENTAL
METAL
CONCRETE, PRE-CAST
(WHEN INDICATED
GRAPHICALLY)
CONCRETE,
LIGHT-WEIGHT
CONCRETE
(ELEVATION)
MATERIALS LEGEND
FINISH WOOD
WOOD BLOCKING
SOLID SURFACING
MARBLE
TERRAZZO
GYP. BD.
COMPACTED EARTH
FILL
NOTE: SOME MATERIALS SHOWN HERE MAY NOT OCCUR IN THIS PROJET
ROOM NAME
A1.10
DOOR NUMBER
- FRAME TYPE
ROOM NAME
ROOM NUMBER
SHEET ON WHICH
SECTION/DETAIL
IS DRAWN
SECTION/DETAIL
NUMBER
A1.0
REFERENCE SYMBOLS & TAGS
A1.1
SCHEDULED
EQUIPMENT
W0 WALL TYPE
A4.1 1
CALLOUT
NUMBER
SHEET ON WHICH
CALLOUT IS DRAWN
A9.4 1
ELEVATION NUMBER
SHEET ON WHICH
ELEVATION IS DRAWN
OR
1-A1.10
1 KEYED NOTE
ELEVATION NUMBER
SHEET ON WHICH
ELEVATION IS DRAWN
OR
OR
1- A4
.1 1-
A9 .4
2S
T
D
INTERIOR ELEVATIONS
EXTERIOR ELEVATIONS
DETAIL CALLOUTS
SECTIONS / DETAILS
OR
OR
OR
OR
ONE HOUR RATED
WALL
TWO HOUR RATED
WALL
THREE HOUR RATED
WALL
NON-RATED WALL,
EXTEND TO DECK &
SEALED
SMOKE TIGHT
PARTITION
TWO HOUR SMOKE
BARRIER PARTITION
PARTIAL HEIGHT
WALL
0 GRID LINE
ELEVATION DATUM
NOTE: ALL ELEVATIONS ARE
FROM PRIMARY BUILDING FIN.
FLOOR UNLESS OTHERWISE
NOTED
VOLUME OF FINAL/BID SET
W
AR
NI
NG
: C on tra cto rs, su bc on tra cto rs, ve nd or s a nd su pp lie rs ar e a dv ise d t ha t th e c on tra ct do cu me nts co ns ist
Ar ch ite ct-re pr od uc ed pr int ed
, b ou nd an d n um be re d s pe cif ica tio ns
, A rch ite ct-re pr od uc ed pr int ed
, b ou nd an d nu mb er ed bl ue
- o r b lac k-l ine pr int s, ad de nd a, po st-bid ad de nd a, an d c ha ng e o rd er s o nly . D oc um en ts re pr od uc ed rtie s o the r t ha n t he A rch ite ct, w he the r in ha rd co py or in el ec tro nic fo rm at, sh all no t b e c on sid er ed pa rt the co ntr ac t d oc um en ts an d d o n ot su pe rse de th e p ro vis ion s o f th e c on tra ct do cu me nts . T he co ntr ac tor su bc on tra cto rs, ve nd or s a nd su pp lie rs ar e s ole ly re sp on sib le for ve rifi ca tio n t ha t in for ma tio n u tili ze d i n b idd ing de ve lop me nt of sh op dr aw ing s, an d c on str uc tio n o f th e f ac ilit y a re id en tic al to the co ntr ac t d oc um en ts.
PROJECT NUMBER
PROJECT DATE
APPROVED BY
CHECKED BY
DRAWN BY
SET NUMBER:
Copyright (c) 2019 All Rights Reserved.
ISSUED FOR:
NOT VALID UNLESS SIGNED
JA
M
ES
W . B U C K
LE
Y A
SS
O C
IA
TE
S
IN
C
- A
RC
H
IT
EC
TS
G
EO
RG
IA
2 2
SW
A
IN
SB
O
RO
, A
LB
A N Y, R O M E, A N D S A V A N N A H
/4/
5:
:26 P
M C:
\U se rs\ jrw
\D oc um en ts\
-0
_C
EN
TR
AL
_2
3-
-1 2_
R2 3_ jrw _.r vt
BLOOMINGDALE ELEMENTARY
SCHOOL
SAVANNAH-CHATHAM COUNTY PUBLIC SCHOOL SYSTEM
BLOOMINGDALE, GEORGIA SCHOOL CODE: 625-4052
IN
D
EX
VO
LU
M E
BL
O
O M
IN
G
D
AL
E
EL
EM
EN
TA
R
Y
SC
H O
O L
09/13/2023
22-072
CRB
HGB
TDP
FINAL/BID
SA
VA
N N
AH
-C
H
AT
H
AM
C O
U N
TY
P
U
BL
IC
S
C H
O O
L
SY
ST
EM
BL
O
O M
IN
G
D
AL
E, G
EO
R
G
IA
SC
H O
O L
C O
D E:
-4
GENERAL NOTES
A.
1.
2.
B.
1.
C.
1.
D.
1.
E.
1.
2.
3.
4.
5.
F.
1.
2.
THE FOLLOWING NOTES SUPPLEMENT AND ADD TO THE DRAWINGS AND SPECIFICATIONS. IF THERE IS ANY CONFLICT, AMBIGUITY, ETC., CREATED BY ANY NOTE, THE CONTRACTOR SHALL COMPLY WITH THE MORE STRINGENT REQUIREMENT.
DIMENSIONS:
THE GENERAL CONTRACTOR, SUBCONTRACTORS AND ALL EMPLOYEES ON THIS PROJECT ARE NOT ALLOWED TO SCALE DRAWINGS TO DETERMINE DISTANCES NOT DIMENSIONED. IF FURTHER DIMENSIONING IS REQUIRED, THE CONTRACTOR SHALL REQUEST IN WRITING FOR WRITTEN CLARIFICATION BY THE ARCHITECT. ALL DIMENSIONS
ARE GIVEN TO FACE OF CMU, FACE OF BRICK, OR FACE OF STUD UNLESS NOTED OTHERWISE.
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, GRADE PITCHES AND OTHER CONDITIONS BY TAKING MEASUREMENTS PRIOR TO ORDERING MATERIALS OR DOING WORK. REFER DISCREPANCIES TO THE ARCHITECT FOR ADDITIONAL INSTRUCTIONS. THE CONTRACTOR IS RESPONSIBLE FOR MEASUREMENTS. NO CONSIDERATION WILL BE GIVEN TO ANY CLAIM BASED ON DIFFERENCES BETWEEN DRAWINGS OR SPECIFICATIONS AND ACTUAL
MEASUREMENTS.
SIMILAR CONDITIONS:
WHERE A DETAIL OR SECTION IS SHOWN FOR ONE CONDITION, IT APPLIES TO ALL LIKE OR SIMILAR CONDITIONS.
COORDINATION:
COORDINATING ROUTING OF THE CONTRACTOR'S WORK WITH OTHER TRADES IS ESSENTIAL, AND ANY EXPENSE
REQUIRED FOR REMOVAL OR RELOCATION SHALL BE BORNE BY THE CONTRACTOR.
SITE WORK:
PRIOR TO CLEARING AND GRUBBING, PROVIDE SURFACE SITE DEWATERING BY TEMPORARY DITCHING, SUMPING, OR OTHER APPROVED METHODS. RETAIN AND MAINTAIN TEMPORARY METHODS UNTIL PERMANENY DRAINAGE
SYSTEMS (STORM DRAINS, SWALES, ETC.) ARE INSTALLED.
CONCRETE BLOCK:
BULL NOSE CONCRETE BLOCK SHALL BE USED AT ALL EXPOSED (OUTSIDE) CORNERS AT WALLS AND PARTITIONS
INSIDE BUILDING INCLUDING WINDOW AND DOOR JAMB CONDITIONS.
WHERE CONCRETE BLOCK IS EXPOSED AT INTERIOR WALLS, PROVIDE SHALLOW CONCAVE CONCRETE BLOCK
JOINTS IN KITCHENS AND ALL TOILET ROOMS.
CONTRACTOR SHALL PROVIDE MASONRY WALLS TO MEET ALL REQUIREMENTS OF FINISH INSTALLER.
MANUFACTURER SHALL ENSURE THAT ALL MATERIAL AND INSTALLATION WARRANTIES REMAIN EFFECTIVE.
JOINT REINFORCING MAY BE OMITTED IN DETAILING FOR CLARITY; INSTALL IN MASONRY JOINTS AT DESIGNATED
INTERVALS WHETHER SHOWN OR NOT.
IN ROOMS WITH EXPOSED STRUCTURAL CEILING, EXTEND WALLS TO ROOF OR FLOOR DECK ABOVE.
FLASHING:
OVERLAP ALL FLASHING JOINTS 4" MINIMUM AND SEAL WATERTIGHT.
ARCHITECT IS TO OBSERVE ALL FLASHING INSTALLATION PRIOR TO FLASHING BEING COVERED UP BY NEW
CONSTRUCTION.
NORTH
KEY PLAN
STANDARD ABBREVIATIONS
AT@
ANCHOR BOLTA.B.
ABOVE FINISH FLOORA.F.F.
ALTERNATEALT.
ALUMINUMALUM.
ANODIZEDANOD.
ACOUSTICAL TILEA.T.
ASH URNAU
BABY CHANGING
STATION
BCS
BOARDBD.
BETWEENBET.
BLOCKBLK.
BULLNOSEB.N.
BEAMBM.
BOTTOMBOT.
CHANNEL[
CENTERLINEC/L
CABINETCAB.
CEILINGCLG.
CONCRETE
MASONRY UNIT
C.M.U.
COLUMNCOL.
CONCRETECONC.
CONTINUOUSCONT.
CLASSROOMC.R.
CERAMIC TILEC.T.
CENTERCTR.
DIAMETERDIA.
DOUBLE BULLNOSED.B.N.
DETAILDET.
DRINKING FOUNTAIND.F.
DIMENSIONDIM.
DISPENSERDISP.
EACHEA.
ELECTRIC HAIR DRYEREAD
ELECTRIC HAND DRYEREHD
EXPANSION JOINTE.J.
ELEVATIONELEV.
EQUALEQ.
EXPANSIONEXP.
EXTERIOREXT.
FINISH ALL SIDESF.A.S.
FLOOR DRAINF.D.
PURSE SHELFP.S.
PRESSURE-TREATEDP.T.
PAPER TOWEL
DISPENSER
PTD
PAPER TOWER
DISPENSER/RECEPTACLE
PTDR
QUARRY TILEQ.T.
RADIUSRAD.
ROOF DRAINR.D.
RECEPTACLERECEP.
REINFORCEDREINF.
REQUIREDREQ'D.
ROBE HOOKRH
ROOMRM.
RIGHT-OF-WAYR/W
STORAGE CABINETS.C.
SEAT COVER DISPENSERSCD
SHOWER CURTAIN RODSCR
SOAP DISPENSERSD
SQUARE FOOTS.F.
SIMILARSIM.
SANITARY NAPKIN
DISPENSER
SND
SANITARY NAPKIN
RECEPTACLE
SNR
SQUARE FOOTSQ. FT.
STAINLESS STEELS.S.
SOAP TRAYST
STEELSTL.
STORAGESTOR.
SUSPENDEDSUSP.
TACK BOARDT.B.
TUMBLER/TOOTHBRUS
H HOLDER
TBH
TEACHER'S CABINETT.C.
TEMPEREDTEMP.
TOWEL HOLDERTH
THICKTK.
TOWEL PINTP
TOWEL RODTR
TOILET TISSUE
DISPENSER
TTD
TYPICALTYP.
UNLESS NOTEDU.N.
UTILITY SHELF UNITUSU
WITHW/
WINDOWWIND.
FIRE EXTINGUISHERF.E.
FINISH FLOORF.F.
FINISHFIN.
FLOORFL.
FIRE RATEDF.R.
FOLDING SHOWER SEATFSS
GAUGEGA.
GALVANIZEDGALV.
GRAB BARGB
GLAZE-COATED CMUG.C.C.B.
GYPSUMGYP.
HANDICAPPED-
ACCESSIBLE
H.C.
HOLLOW METALH.M.
HEIGHTHT.
INSULATIONINSUL.
JOINTJT.
LAMINATEDLAM.
LINEAL FEETL.F.
MANUFACTURERMFR.
MAXIMUMMAX.
MOP AND BROOM
HOLDER
MBH
MEDICINE CABINETMC
METALMET.
MINIMUMMIN.
MIRRORMIR.
MISCELLANEOUSMISC.
MASONRY OPENINGM.O.
NOT IN CONTRACTN.I.C.
NOMINALNOM.
NOT TO SCALEN.T.S.
OPPOSITE HANDO.H.
OPPOSITEOPP.
ON CENTERO.C.
OUTSIDE DIAMETERO.D.
PLATEPL.
PAINTED CONCRETE
BLOCK
P.C.B.
PRE-FORMED
EXPANSION JOINT
P.E.J.
PROPERTY LINEP.L.
PLYWOODPLY.
PROJECTIONPROJ.
FOOTFT.
FACIAL TISSUE
DISPENSER
FTD
SHOWER CURTAIN AND
HOOKS
SCH
INDEX OF DRAWINGS
CR
W
IN
G
A
CR
W
IN
G A
CR WING B
CR W
ING C
GYMNASIUM/
SPED
CAFETERIA
MEDIA
ADMIN
CIVIL DRAWINGS
L1.0 OVERALL LANDSCAPE PLAN
L1.1 ENLARGED LANDSCAPE PLAN
L1.2 ENLARGED LANDSCAPE PLAN
L1.3 LANDSCAPE NOTES AND DETAILS
L2.0 OVERALL IRRIGATION PLAN
L2.1 ENLARGED IRRIGATION PLAN
L2.2 ENLARGED IRRIGATION PLAN
L2.3 IRRIGATION NOTES AND DETAILS
ARCHITECTURAL DRAWINGS
A1.0 SITE PLAN
A1.1 COMPOSITE PLAN - FIRST FLOOR
A1.2 COMPOSITE PLAN - SECOND FLOOR
A1.3 LIFE SAFETY PLAN - FIRST FLOOR
A1.4 LIFE SAFETY PLAN - SECOND FLOOR
A1.5 ROOF PLAN
A2.0 1/8" FLOOR PLAN - ADMINISTRATION
A2.1 1/8" FLOOR PLAN - CAFETERIA
A2.2 1/8" FLOOR PLAN - MEDIA CENTER
A2.3 1/8" FLOOR PLAN - GYMNASIUM
A2.4 1/8" FLOOR PLAN - CR WING A - FIRST FLOOR
A2.5 1/8" FLOOR PLAN - CR WING B - FIRST FLOOR
A2.6 1/8" FLOOR PLAN - CR WING C - FIRST FLOOR
A2.7 1/8" FLOOR PLAN - CR WING A - SECOND FLOOR
A2.8 1/8" FLOOR PLAN - CR WING B - SECOND FLOOR
A2.9 1/8" FLOOR PLAN - CR WING C - SECOND FLOOR
A2.10 1/8" REFLECTED CEILING PLAN - ADMINISTRATION
A2.11 1/8" REFLECTED CEILING PLAN - CAFETERIA
A2.12 1/8" REFLECTED CEILING PLAN - MEDIA CENTER
A2.13 1/8" REFLECTED CEILING PLAN - GYMNASIUM
A2.14 1/8" REFLECTED CEILING PLAN - CR WING A - FIRST
FLOOR
A2.15 1/8" REFLECTED CEILING PLAN - CR WING B - FIRST
FLOOR
A2.16 1/8" REFLECTED CEILING PLAN - CR WING C - FIRST
FLOOR
A2.17 1/8" REFLECTED CEILING PLAN - CR WING A - SECOND
FLOOR
A2.18 1/8" REFLECTED CEILING PLAN - CR WING B - SECOND
FLOOR
A2.19 1/8" REFLECTED CEILING PLAN - CR WING C - SECOND
FLOOR
A2.20 1/8" FLOOR PATTERN PLAN -
ADMINISTRATION/CAFETERIA
A2.21 1/8" FLOOR PATTERN PLAN - MEDIA
CENTER/GYMNASIUM
A2.22 1/8" FLOOR PATTERN PLAN - CR WING A - FIRST FLOOR
A2.23 1/8" FLOOR PATTERN PLAN - CR WING B - FIRST FLOOR
A2.24 1/8" FLOOR PATTERN PLAN - CR WING C - FIRST FLOOR
A2.25 1/8" FLOOR PATTERN PLAN - CR WING A - SECOND
FLOOR
A2.26 1/8" FLOOR PATTERN PLAN - CR WING B - SECOND
FLOOR
A2.27 1/8" FLOOR PATTERN PLAN - CR WING C - SECOND
FLOOR
A3.0 ROOM FINISH SCHEDULE
A3.1 DOOR SCHEDULE/DOOR ELEVATIONS
A3.2 DOOR SILL DETAILS
A3.4 HOLLOW METAL & METAL COILING FRAMES AND
DETAILS
A3.5 HOLLOW METAL & METAL COILING FRAMES AND
DETAILS
A3.6 CURTAINWALL FRAMES AND DETAILS
A3.7 CURTAINWALL FRAME DETAILS
A3.8 ALUMINUM STOREFRONT FRAMES AND DETAILS
ARCHITECTURAL DRAWINGS
A4.0 COMPOSITE EXTERIOR ELEVATIONS
A4.1 EXTERIOR ELEVATIONS
A4.2 EXTERIOR ELEVATIONS
A4.3 EXTERIOR ELEVATIONS
A4.4 EXTERIOR ELEVATIONS
A4.5 EXTERIOR ELEVATIONS
A5.0 BUILDING SECTIONS- ADMIN
A5.1 BUILDING SECTIONS - MEDIA CENTER
A5.2 BUILDING SECTIONS - CAFETERIA
A5.3 BUILDING SECTIONS- KITCHEN
A5.4 BUILDING SECTIONS - GYMNASIUM
A5.5 BUILDING SECTIONS - TYPICAL CR WING
A6.0 WALL SECTIONS - TYPICAL CLASSROOM WING
A6.1 WALL SECTIONS - TYPICAL CLASSROOM WING
A6.2 WALL SECTIONS - TYPICAL CLASSROOM WING
A6.3 WALL SECTIONS - TYPICAL CLASSROOM WING
A6.4 WALL SECTIONS - TYPICAL CLASSROOM WING
A6.5 WALL SECTIONS - ENTRY
A6.6 WALL SECTIONS - ENTRY
A6.7 WALL SECTIONS - ENTRY
A6.8 WALL SECTIONS - ADMIN
A6.9 WALL SECTIONS - MEDIA CENTER
A6.10 WALL SECTIONS - CAFETERIA
A6.11 WALL SECTIONS - CAFETERIA
A6.12 WALL SECTIONS - GYM
A6.13 WALL SECTIONS - GYM
A6.14 WALL SECTIONS - GYM
A6.15 WALL SECTIONS - GYM
A6.16 WALL SECTIONS - CORRIDOR
A6.17 WALL SECTIONS - CORRIDOR
A6.18 WALL SECTIONS - RAMPS AND STEPS
A6.19 WALL SECTIONS - MONUMENTAL STAIR
A6.20 WALL SECTIONS - MONUMENTAL STAIR
A6.21 WALL SECTIONS - MONUMENTAL STAIR
A8.0 WALL TYPES
A8.1 ENLARGED FLOOR PLAN - ADMINISTRATION
A8.2 ENLARGED FLOOR PLAN - MEDIA CENTER
A8.3 ENLARGED FLOOR PLAN - FRONT ENTRY
A8.4 ENLARGED FLOOR PLAN - CAFETERIA/MUSIC
A8.5 ENLARGED FLOOR PLAN - KITCHEN
A8.6 ENLARGED FLOOR PLANS - COURTYARD & SERVICE
YARD
A8.7 ENLARGED FLOOR PLAN - GYMNASIUM
A8.8 ENLARGED PLAN - GYMNASIUM CLERESTORY AND
MEZZANINE
A8.9 ENLARGED FLOOR PLANS
A8.10 ENLARGED FLOOR PLANS
A8.11 ENLARGED FLOOR PLANS
A8.12 ENLARGED FLOOR PLANS - STAIRS
A8.13 ENLARGED FLOOR PLAN - BUS CANOPY
A9.0 MILLWORK PLANS & ELEVATIONS
A9.1 MILLWORK PLANS & ELEVATIONS
A9.2 MILLWORK PLANS & ELEVATIONS
A9.3 MILLWORK SECTIONS - PLASTIC LAMINATE
A9.4 MILLWORK SECTIONS - SOLID SURFACE
A9.5 MILLWORK DETAILS
A9.6 WOODWORKING ELEVATIONS
A9.7 WOODWORKING ELEVATIONS
A9.8 WOODWORKING ELEVATIONS & DETAILS
A10.0 INTERIOR ELEVATIONS
A10.1 INTERIOR ELEVATIONS
A10.2 INTERIOR ELEVATIONS
A10.3 INTERIOR ELEVATIONS
A10.4 INTERIOR ELEVATIONS
STRUCTURAL DRAWINGS
S0.1 STRUCTURAL NOTES
S0.2 WIND PRESSURE SCHEDULES
S1.0 COMPOSITE FOUNDATION PLAN
S1.1 FOUNDATION PLAN - ADMINISTRATION
S1.2 FOUNDATION - PLAN - CAFETERIA
S1.3 FOUNDATION PLAN - MEDIA CENTER
S1.4 FOUNDATION PLAN - GYMNASIUM
S1.5 FOUNDATION PLAN - CLASSROOM WING A
S1.6 FOUNDATION PLAN - CLASSROOM WING B
S1.7 FOUNDATION PLAN - CLASSROOM WING C
S1.8 SECTIONS
S1.9 SECTIONS
S2.0 COMPOSITE SECOND FLOOR FRAMING PLAN
S2.1 SECOND FLOOR FRAMING PLAN - CLASSROOM WING
A
S2.2 SECOND FLOOR FRAMING PLAN - CLASSROOM WING
B
S2.3 SECOND FLOOR FRAMING PLAN- CLASSROOM WING C
S2.4 FLOOR FRAMING SECTIONS
S2.5 FLOOR FRAMING SECTIONS
S3.0 COMPOSITE ROOF FRAMING PLAN
S3.1 ROOF FRAMING PLAN - ADMINISTRATION
S3.2 ROOF FRAMING PLAN - CAFETERIA
S3.3 ROOF FRAMING PLAN - MEDIA CENTER
S3.4 ROOF FRAMING PLAN - GYMNASIUM
S3.5 ROOF FRAMING PLAN - CLASSROOM WING A
S3.6 ROOF FRAMING PLAN - CLASSROOM WING B
S3.7 ROOF FRAMING PLAN - CLASSROOM WING C
S3.8 FLOOR FRAMING SECTIONS
S3.9 FLOOR FRAMING SECTIONS
S4.0 COLUMN AND FOUNDATION SCHEDULE
S4.1 MISCELLANEOUS SCHEDULES
S5.1 TYPICAL DETAILS
S5.2 TYPICAL DETAILS
S5.3 TYPICAL DETAILS
MECHANICAL DRAWINGS
M0.0 HVAC TITLE SHEET
M0.1 HVAC SCHEDULE
M1.0 HVAC COMPOSITE PLAN - FIRST FLOOR
M1.1 HVAC COMPOSITE PLAN - SECOND FLOOR
M1.3 HVAC PLAN - ROOF
M2.0 HVAC PLAN - ADMINISTRATION
M2.1 HVAC PLAN - CAFETERIA
M2.2 HVAC PLAN - MEDIA CENTER
M2.3 HVAC PLAN - GYMNASIUM
M2.4 HVAC PLAN - CR WING A - FIRST FLOOR
M2.5 HVAC PLAN - CR WING B - FIRST FLOOR
M2.6 HVAC PLAN - CR WING C - FIRST FLOOR
M2.7 HVAC PLAN - CR WING A - SECOND FLOOR
M2.8 HVAC PLAN - CR WING B - SECOND FLOOR
M2.9 HVAC PLAN - CR WING C - SECOND FLOOR
M3.0 HVAC PIPING PLAN - ADMINISTRATION
M3.1 HVAC PIPING PLAN - CAFETERIA
M3.2 HVAC PIPING PLAN - MEDIA CENTER
M3.3 HVAC PIPING PLAN -GYMNASIUM
M3.4 HVAC PIPING PLAN - CR WING A - FIRST FLOOR
M3.5 HVAC PIPING PLAN - CR WING B - FIRST FLOOR
M3.6 HVAC PIPING PLAN - CR WING C - FIRST FLOOR
M3.7 HVAC PIPING PLAN - CR WING A - SECOND FLOOR
M3.8 HVAC PIPING PLAN - CR WING B - SECOND FLOOR
M3.9 HVAC PIPING PLAN - CR WING C - SECOND FLOOR
M4.0 HVAC PLAN - ENLARGED KITCHEN PLAN
M4.1 HVAC SECTION VIEWS
M5.0 HVAC DETAILS
M5.1 HVAC DETAILS
M5.2 HVAC DETAILS
M5.3 VRF SCHEMATICS
M5.4 VRF SCHEMATICS
ELECTRICAL DRAWINGS
E1.0 LEGEND, NOTES, DETAILS AND FIXTURE SCHEDULE
E1.1 ELECTRICAL SITE PLAN
E2.0 LIGHTING PLAN - ADMINISTRATION/CAFETERIA
E2.1 LIGHTING PLAN - MEDIA CENTER/GYMNASIUM
E2.2 LIGHTING PLAN - FIRST FLOOR - CR WING A
E2.3 LIGHTING PLAN - FIRST FLOOR - CR WING B
E2.4 LIGHTING PLAN - FIRST FLOOR - CR WING C
E2.5 LIGHTING PLAN - SECOND FLOOR - CR WING A
E2.6 LIGHTING PLAN - SECOND FLOOR - CR WING B
E2.7 LIGHTING PLAN - SECOND FLOOR - CR WING C
E3.0 POWER PLAN - ADMINISTRATION/CAFETERIA
E3.1 POWER PLAN - MEDIA CENTER/GYMNASIUM
E3.2 POWER PLAN - FIRST FLOOR - CR WING A
E3.3 POWER PLAN - FIRST FLOOR - CR WING B
E3.4 POWER PLAN - FIRST FLOOR - CR WING C
E3.5 POWER PLAN - SECOND FLOOR - CR WING A
E3.6 POWER PLAN - SECOND FLOOR - CR WING B
E3.7 POWER PLAN - SECOND FLOOR - CR WING C
E3.8 POWER PLAN - ENLARGED KITCHEN
E4.0 MECHANICAL POWER PLAN - FIRST FLOOR
E4.1 MECHANICAL POWER PLAN - SECOND FLOOR
E4.2 MECHANICAL POWER PLAN - ROOF
E4.3 MECHANICAL CONNECTION SCHEDULES
E5.0 FIRE ALARM SYSTEM PLAN - FIRST FLOOR
E5.1 FIRE ALARM SYSTEM PLAN - SECOND FLOOR
E5.2 SYSTEMS PLAN - FIRST FLOOR
E5.3 SYSTEMS PLAN - SECOND FLOOR
E5.4 ACCESS CONTROLS/CCTV SYSTEMS PLAN - FIRST
FLOOR
E5.5 ACCESS CONTROLS/CCTV SYSTEMS PLAN - SECOND
FLOOR
E5.6 CABLE MANAGEMENT PLAN - FIRST FLOOR
E5.7 CABLE MANAGEMENT PLAN - SECOND FLOOR
E6.0 ELECTRICAL PLAN - ENLARGED TYPICAL CLASSROOM
E7.0 POWER RISER DIAGRAM
E7.1 PANEL SCHEDULES
E7.2 PANEL SCHEDULES
E7.3 PANEL SCHEDULES
E7.4 PANEL SCHEDULES
E8.0 ELECTRICAL DETAILS
E8.1 ELECTRICAL DETAILS
E8.2 ELECTRICAL DETAILS
E8.3 ELECTRICAL DETAILS
E8.4 ELECTRICAL DETAILS
E8.5 ELECTRICAL DETAILS
SQUARE FOOTAGE TABULATION
SQUARE FOOTAGES SHOWN ARE APPROXIMATE.
DO NOT USE SQUARE FOOTAGES FOR BIDDING.
TOTAL GROSS SQUARE FOOTAGE
OTHER CANOPIES
BUS CANOPY
FRONT ENTRANCE
GROSS BUILDING SQUARE FOOTAGE
SQ. FT. GROSS x 1/2 =
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
OTHER COVERED ENTRANCES SQ. FT.SQ. FT. GROSS x 1/2 =
SQ. FT. GROSS x 1/2 =
SQ. FT. GROSS x 1/2 =
157036
150879
10509
GRADES:
MEMBERSHIP:
FUNDING:
SQ. FEET RENOVATION:
SQ. FEET NEW:
SQ. FEET TOTAL: 150879
K-5
STATE/LOCAL
150879
VOLUME 1 VOLUME 2
PLUMBING DRAWINGS
P0.0 PLUMBING TITLE SHEET & SCHEDULES
P1.1 PLUMBING COMPOSITE PLAN - FIRST FLOOR
P1.2 PLUMBING COMPOSITE PLAN - SECOND FLOOR
P1.3 PLUMBING ROOF PLAN
P2.0 WASTE AND VENT PLAN - ADMINISTRATION
P2.1 WASTE & VENT PLAN - CAFETERIA
P2.2 WASTE & VENT PLAN - MEDIA CENTER
P2.3 WASTE & VENT PLAN - GYMNASIUM
P2.4 WASTE & VENT PLAN - CR WING A - FIRST FLOOR
P2.5 WASTE & VENT PLAN - CR WING B - FIRST FLOOR
P2.6 WASTE & VENT PLAN - CR WING C - FIRST FLOOR
P2.7 WASTE & VENT PLAN - CR WING A - SECOND FLOOR
P2.8 WASTE & VENT PLAN - CR WING B - SECOND FLOOR
P2.9 WASTE & VENT PLAN - CR WING C - SECOND FLOOR
P3.0 HOT & COLD WATER PLAN - ADMINISTRATION
P3.1 HOT & COLD WATER PLAN - CAFETERIA
P3.2 HOT & COLD WATER PLAN - MEDIA CENTER
P3.3 HOT & COLD WATER PLAN - GYMNASIUM
P3.4 HOT & COLD WATER PLAN - CR WING A - FIRST FLOOR
P3.5 HOT & COLD WATER PLAN - CR WING B - FIRST FLOOR
P3.6 HOT & COLD WATER PLAN - CR WING C - FIRST FLOOR
P3.7 HOT & COLD WATER PLAN - CR WING A - SECOND
FLOOR
P3.8 HOT & COLD WATER PLAN - CR WING B - SECOND
FLOOR
P3.9 HOT & COLD WATER PLAN - CR WING C - SECOND
FLOOR
P4.0 ENLARGED PLUMBING PLANS
PLUMBING DRAWINGS
P4.1 ENLARGED PLUMBING PLANS
P4.2 ENLARGED WASTE & VENT PLAN - KITCHEN
P4.3 ENLARGED HOT & COLD WATER PLAN - KITCHEN
P5.1 PLUMBING DETAILS
P5.2 PLUMBING DETAILS
ARCHITECTURAL DRAWINGS
A10.5 INTERIOR ELEVATIONS
A10.6 INTERIOR ELEVATIONS
A10.7 INTERIOR ELEVATIONS
A10.8 INTERIOR ELEVATIONS
A13.0 DETAILS - FIRE RATED/LIFE SAFETY
A13.1 DETAILS- FIRE RATED/ LIFE SAFETY
A14.0 ROOFING DETAILS
A14.1 ROOFING DETAILS
A14.2 ROOFING DETAILS
A15.0 DETAILS - KITCHEN
A16.0 TYPICAL PLASTIC PARTITION DETAILS
A16.1 TYPICAL SHOWER STALL DETAILS
A17.0 CMU DETAILS
A17.1 DRY WALL DETAILS
A17.2 MISCELLANEOUS DETAILS
A17.3 CAST STONE PROFILES AND DETAILS
A17.4 CAST STONE PROFILES AND DETAILS
1 ADDENDUM #1: 09/26/2023
2 ADDENDUM #2: 10/04/2023
W D
R E
F
I.
C
R E
F
I.
C
D W
WD
REF
I.C.
REF
I.C.
Ƨ
WING A CONT.
WING C
WING B
WING A
GYMNASIUM
MEDIA CENTER
ADMINISTRATION
CAFETERIA
GYMNASIUM
CAFETERIA
MEDIA CENTER
COMPUTER LAB
PACE
PACE
FAMILY LIVING
PSI
KINDERGARTEN
KINDERGARTEN
1ST GRADE
1ST GRADE
INCLUSION/SPED OFFICES
KINDERGARTEN
KINDERGARTEN
KINDERGARTEN
KINDERGARTEN
1308 STOR
1300.2SPEECH
PRE-K
PRE-K
SPEECH
STAIR
1400.1
KINDERGARTEN
KINDERGARTEN
KINDERGARTEN
KINDERGARTEN
STOR
SEC VEST
COMMONS
TEACHER RESOURCE
1ST GRADE
1ST GRADE
1ST GRADE
1ST GRADE
CUST STOR
1700.2
CORRIDOR
1ST GRADE
1ST GRADE
1ST GRADE
1ST GRADE
CUST. STOR
ELEC
IDF
CUST. OFFICE
CORRIDOR
MUSIC
VEST.
P.E. STORAGE
1206.2
CORR.
ACTIVITY LAB/CONF
BROADCAST STUDIO
SECURED VEST
STUDENT RECEPTION
GENERAL OFFICE
VISITOR RECEPTION
CONF.
PRINCIPAL
CORRIDOR
1901.1
OFFICE
OFFICE
OFFICE
COUNSELOR
1915 COUNSELOR
COUNSELOR
SW
AP
TESTING/CONF
CLINIC
EXAM
1908.2
BOOK KEEPER
INFO SPEC
VAULT
1912.2
ELEC
1916 DATA
STAGE
CHAIR STOR
1801.1
DRY FOOD STORAGE
1810 COOLER
FREEZER
SPKLR / RISER
MECH/ELEC
KITCHEN
SERVING
SECURED VEST
RESOURCE RM
STOR
1600.2
STAIR
1600.1
2ND GRADE
2ND GRADE
2ND GRADE
2ND GRADE
2ND GRADE
GIRLS
BOYS
1601T
ELEV.-1
1501.1-1
CONFERENCE
2ND GRADE
2ND GRADE
2ND GRADE
2ND GRADE
INST. WKRM
ELEC
1108IDF
CORRIDOR
1000.2
SRO
1000.1
WORKROOM
SUPPLY
1912.1
TESTING STOR
JAN
DISH RETURN
CORRIDOR
CORRIDOR
CORRIDOR
VAH-9-1
VAH-9-2
VAH-10-1
VAH-10-2
VAH-10-3
HRC-10
VAH-10-5
EH-9
EF-11
VAH-10-4
EH-7
VAH-9-3
VAH-9-4
VAH-9-5
VAH-7-1
VAH-7-2
VAH-7-3
VAH-7-4
EH-5
VAH-7-7
VAH-7-6
VAH-7-5
VAH-6-8
VAH-6-7
VAH-6-6
VAH-6-3
VAH-4-6
VAH-4-5
VAH-6-2
VAH-5-6
VAH-4-4
VAH-4-3
VAH-5-5
HRC-5
VAH-5-4
EH-4
VAH-5-1
VAH-5-2
VAH-5-3
VAH-6-1
DAH-4
VAH-6-4
HRC-6
VAH-6-5
DAH-5
HRC-10
HRC-9
HRC-7
EH-10
VAH-4-2
VAH-4-1
EF-10
EH-8
VAH-8-1
VAH-8-2
VAH-8-3
VAH-8-4
EH-6
STOR
1400.2
VAH-8-5
VAH-8-6
VAH-8-7
VAH-8-8
HRC-8
HRC-4
VHP-4
DOAS-2 RAC-3
DAH-3
RAC-4
VAH-4-8
VAH-3-11
HRC-3
VAH-3-7
VAH-3-9VAH-3-8
VAH-3-6
RAC-2
VAH-3-5
VAH-3-4
VAH-3-3
DAH-2 VAH-3-1
EF-1
VAH-3-10
RAC-1
DOAS-1
VAH-2-5
VAH-2-7
HRC-1
VAH-1-8 VAH-1-7 VAH-1-6
VAH-1-5
VAH-1-4
VAH-1-2
VAH-1-3
VAH-1-1
VAH-2-8
VAH-2-1
HRC-2
VAH-2-4
VAH-2-3
VAH-2-2
DAH-1
VAH-2-6
VAH-1-9
VAH-1-10
DAH-9
EH-2
EF-5
EF-6
RAC-6
DHP-9
EF-2
RAC-5
FF-1
EH-1
EF-3
EF-4
MAU-1
KEF-1
VAH-4-9
HVAC SHEET NOTES
A CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE A COMPLETE AND
WORKING SYSTEM.
B INSTALL, SUPPORT, & BRACE NEW DUCTWORK AND ACCESSORIES PER
SMACNA GUIDELINES.
C DUCT SIZES SHOWN ARE CLEAR INSIDE DIMENSIONS. CONTRACTOR
SHALL MAKE ALLOWANCE FOR ANY INTERIOR LINING, INSULATION, ETC.
D ALL NEW DUCT ELBOWS SHALL BE RADIUS TYPE. WHERE NECESSARY,
CONTRACTOR MAY SUBSTITUTE MITERED ELBOWS WITH TURNING
VANES.
E PROVIDE FLAT BLADE MANUAL VOLUME DAMPERS AT ALL TERMINAL
DUCT BRANCHES AND AS INDICATED.
F INSTALL EQUIPMENT PER MANUFACTURER'S RECOMMENDATIONS.
ROOFTOP EQUIPMENT SHALL BE LOCATED NO CLOSER THAN 10'-0" FROM
THE ROOF EDGE.
G ALL PRIMARY CONDENSATE DRAIN PIPING SHALL BE INSULATED TO A
MINIMUM THICKNESS OF 1/2" AND SHALL INCLUDE A VAPOR RETARDANT
OUTSIDE THE INSULATION. SEAL ALL JOINTS AND PENETRATIONS.
H COORDINATE ALL EXTERIOR PENETRATIONS INCLUDING ROOF
PENETRATIONS WITH OTHER TRADES TO PROVIDE A COMPLETE AND
FULLY WEATHER-PROOF INSTALLATION.
I ALL TRANSFER DUCTWORK SHALL BE INTERNALLY LINED WITH MINIMUM
1/2" ACOUSTIC LINING.
J CONTRACTOR SHALL ENGAGE A TESTING AND BALANCE FIRM CERTIFIED
BY AABC TO PERFORM TESTING AND BALANCING PROCEDURES ON EACH
SYSTEM ACCORDING TO THE PROCEDURES CONTAINED IN AABC'S
"NATIONAL STANDARDS. FOR TESTING AND BALANCING HEATING,
VENTILATING, AND AIR CONDITIONING SYSTEMS" AND PROVIDE TWO
COPIES OF THE CERTIFIED TAB REPORTS.
MethodEG.com 912-963-1611
W A
R N
IN
G
C on tr ac to rs su bc on tr ac to rs ve nd or s an d su pp lie rs a re a dv is ed t ha t t he c on tr ac t do cu m en ts c on si st o f
A rc hi te ct -r ep ro du ce d pr in te d, b ou nd a nd n um be re d sp ec ifi ca tio ns
A rc hi te ct -r ep ro du ce d pr in te d, b ou nd a nd nu m be re d bl ue or b la ck -li ne p rin ts
, a dd en da
, p os t-bi d ad de nd a, a nd c ha ng e or de rs o nl y.
D oc um en ts r ep ro du ce d rt ie s ot he r th an th e A rc hi te ct
, w he th er in h ar d co py o r in e le ct ro ni c fo rm at
, s ha ll no t b e co ns id er ed p ar t o f th e co nt ra ct d oc um en ts a nd d o no t su pe rs ed e th e pr ov is io ns o f t he c on tr ac t d oc um en ts
T he c on tr ac to r, s ub co nt ra ct or s, ve or s an d su pp lie rs a re s ol el y re sp on si bl e fo r ve rif ic at io n th at in fo rm at io n ut ili ze d in b id di ng de ve lo pm en t of s ho p dr aw in gs an d co ns tr uc tio n of t he fa ci lit y ar e id en tic al to t he c on tr ac t do cu m en ts
PROJECT NUMBER
PROJECT DATE
APPROVED BY
CHECKED BY
DRAWN BY
Copyright (c) 2019 All Rights Reserved.
ISSUED FOR:
NOT VALID UNLESS SIGNED
JA
M
E S
W
B U
C K
L E
Y
A S
S O
C
IA
T E
S I
N C
A R
C H
IT
E
C T
S S
W A
IN
S
B O
R O
A
L B
A N
Y R
O M
E A
N D
S A
V A
N N
A H
G E
O R
G
IA
SHEET
NUMBER:
9/
/2
6:
:5
A
M A ut od es k
D oc s:
//2
B lo om in gd al e
E le m en ta ry
S ch oo l/2
1- B lo om in gd al e
E S
-M E
P -R
V
.r vt
H V
A C
C O
M P
O S
IT
E
P L
A N
F
IR
S
T F
L O
O R
B L
O O
M
IN
G D
A L E
E L
E M
E N
T A
R Y
S C
H O
O L
09/13/2023
22-072
AMM
AMM
BMW
FINAL/BID
S A
V A
N N
A H
-C H
A T
H A
M C
O U
N T
Y P
U B
L
IC
S C
H O
O L
S Y
S T
E M
B L
O O
M
IN
G D
A L
E G
E O
R G
IA
S
C H
O O
L C
O D
E
-4
M1.0SCALE: 1/16" = 1'-0"M1.0
1 LEVEL 1 HVAC PLAN
No. PE044663
PROFESSIONAL
G
E O R G
I
A
RE
G ISTERED
ENG INE ER
B R A N
D O N M. W
EB
S T E R
09/13/2023
E
FI.C
WING A CONT.
WING C
WING B
WING A
VAH-11-2
VAH-11-3
VAH-11-4
VAH-11-6
VAH-11-7
VAH-12-1
VAH-12-2
VAH-11-5
VAH-11-12
VAH-11-1
VAH-14-1
VAH-14-2
VAH-14-3
VAH-14-4
VAH-14-9
VAH-14-6
VAH-14-8
VAH-16-6
DAH-7
DAH-8
VAH-16-3
VAH-16-2
VAH-16-1
VAH-15-2
VAH-15-6
VAH-15-1
VAH-15-3
VAH-15-4
VAH-15-5
VAH-16-4
VAH-16-5
VAH-13-1
VAH-13-2
VAH-13-3
VAH-13-4
VAH-13-8
VAH-13-7
VAH-13-6
VAH-13-5
VAH-12-10
DAH-6
VAH-12-9
VAH-12-7
VAH-12-6
VAH-12-5VAH-12-3
DHP-5
DHP-6
VHP-6
VHP-12
DOAS-4
DOAS-3
HRC-11
VHP-5VHP-11
VHP-14
VHP-8
EF-9
HRC-14
EF-7
VAH-14-5
HRC-12 VAH-12-4
VAH-12-8
DHP-8
DHP-7
HRC-15
VHP-10
VHP-16
3RD GRADE
CORRIDOR
2600 3RD GRADE
3RD GRADE
3RD GRADE
CONFERENCE
STORAGE
2602.1
BOYS
COMMONS
VEST
CONF./OFFICE
AP
COUNSELOR
IDF
ELEC
4TH GRADE
4TH GRADE
4TH GRADE
4TH GRADE
4TH GRADE
STAIR
2700.1
CORRIDOR
4TH GRADE
4TH GRADE
4TH GRADE
4TH GRADE
BOOK STORAGE
VHP-7VHP-13
HRC-13
HRC-16
VHP-9
VHP-15
STAIR
2600.1
3RD GRADE
3RD GRADE
3RD GRADE
3RD GRADE
3RD GRADE
CUST STOR
MDF/IDF
2501.1
CONFERENCE
ELEV EQUIP
ELEV.-2
1501.1-2
GIRLS
STAIR
2500.1
WMN
2402.1
MEN
2402.2
VEST
TEACHER RESOURCE
STEM
ART
ENERGY LAB
SPARE CR
SPARE CR
CORRIDOR
STAIR
2400.1
STOR
2401.1
EF-8
ELEC
JAN
VAH-14-7
GIRLS
BOYS
CORRIDOR
5TH GRADE
5TH GRADE
5TH GRADE
5TH GRADE
STAIR
2300.1
5TH GRADE
5TH GRADE
5TH GRADE
5TH GRADE
5TH GRADE
JAN
CORRIDOR
HVAC SHEET NOTES
A CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE A COMPLETE AND
WORKING SYSTEM.
B INSTALL, SUPPORT, & BRACE NEW DUCTWORK AND ACCESSORIES PER
SMACNA GUIDELINES.
C DUCT SIZES SHOWN ARE CLEAR INSIDE DIMENSIONS. CONTRACTOR
SHALL MAKE ALLOWANCE FOR ANY INTERIOR LINING, INSULATION, ETC.
D ALL NEW DUCT ELBOWS SHALL BE RADIUS TYPE. WHERE NECESSARY,
CONTRACTOR MAY SUBSTITUTE MITERED ELBOWS WITH TURNING
VANES.
E PROVIDE FLAT BLADE MANUAL VOLUME DAMPERS AT ALL TERMINAL
DUCT BRANCHES AND AS INDICATED.
F INSTALL EQUIPMENT PER MANUFACTURER'S RECOMMENDATIONS.
ROOFTOP EQUIPMENT SHALL BE LOCATED NO CLOSER THAN 10'-0" FROM
THE ROOF EDGE.
G ALL PRIMARY CONDENSATE DRAIN PIPING SHALL BE INSULATED TO A
MINIMUM THICKNESS OF 1/2" AND SHALL INCLUDE A VAPOR RETARDANT
OUTSIDE THE INSULATION. SEAL ALL JOINTS AND PENETRATIONS.
H COORDINATE ALL EXTERIOR PENETRATIONS INCLUDING ROOF
PENETRATIONS WITH OTHER TRADES TO PROVIDE A COMPLETE AND
FULLY WEATHER-PROOF INSTALLATION.
I ALL TRANSFER DUCTWORK SHALL BE INTERNALLY LINED WITH MINIMUM
1/2" ACOUSTIC LINING.
J CONTRACTOR SHALL ENGAGE A TESTING AND BALANCE FIRM CERTIFIED
BY AABC TO PERFORM TESTING AND BALANCING PROCEDURES ON EACH
SYSTEM ACCORDING TO THE PROCEDURES CONTAINED IN AABC'S
"NATIONAL STANDARDS. FOR TESTING AND BALANCING HEATING,
VENTILATING, AND AIR CONDITIONING SYSTEMS" AND PROVIDE TWO
COPIES OF THE CERTIFIED TAB REPORTS.
MethodEG.com 912-963-1611
W A
R N
IN
G
C on tr ac to rs su bc on tr ac to rs ve nd or s an d su pp lie rs a re a dv is ed t ha t t he c on tr ac t do cu m en ts c on si st o f
A rc hi te ct -r ep ro du ce d pr in te d, b ou nd a nd n um be re d sp ec ifi ca tio ns
A rc hi te ct -r ep ro du ce d pr in te d, b ou nd be re d bl ue or b la ck -li ne p rin ts
, a dd en da
, p os t-bi d ad de nd a, a nd c ha ng e or de rs o nl y.
D oc um en ts r ep ro du ce ie s ot he r th an th e A rc hi te ct
, w he th er in h ar d co py o r in e le ct ro ni c fo rm at
, s ha ll no t b e co ns id er ed p ar t o f th e co nt ra ct d oc um en ts a nd d o no t su pe rs ed e th e pr ov is io ns o f t he c on tr ac t d oc um en ts
T he c on tr ac to r, s ub co nt ra ct or s an d su pp lie rs a re s ol el y re sp on si bl e fo r ve rif ic at io n th at in fo rm at io n ut ili ze d in b id di ng de ve lo pm en t of s ho p dr aw in gs an d co ns tr uc tio n of t he fa ci lit y ar e id en tic al to t he c on tr ac t do cu m en ts
PROJECT NUMBER
PROJECT DATE
APPROVED BY
CHECKED BY
DRAWN BY
Copyright (c) 2019 All Rights Reserved.
ISSUED FOR:
NOT VALID UNLESS SIGNED
JA
M
E S
W
B U
C K
L E
Y
A S
S O
C
IA
T E
S I
N C
A R
C H
IT
E
C T
S S
W A
IN
S
B O
R O
A
L B
A N
Y R
O M
E A
N D
S A
V A
N N
A H
G E
O R
G
IA
SHEET
NUMBER:
9/
/2
6:
:1
A
M A ut od es k
D oc s:
//2
B lo om in gd al e
E le m en ta ry
S ch oo l/2
1- B lo om in gd al e
E S
-M E
P -R
V
.r vt
H V
A C
C O
M P
O S
IT
E
P L
A N
S
E C
O N
D F
L O
O R
B L
O O
M
IN
G D
A L E
E L
E M
E N
T A
R Y
S C
H O
O L
09/13/2023
22-072
AMM
AMM
BMW
FINAL/BID
S A
V A
N N
A H
-C H
A T
H A
M C
O U
N T
Y P
U B
L
IC
S C
H O
O L
S Y
S T
E M
B L
O O
M
IN
G D
A L
E G
E O
R G
IA
S
C H
O O
L C
O D
E
-4
M1.1
SCALE: 1/16" = 1'-0"M1.1
1 LEVEL 2 HVAC PLAN
No. PE044663
PROFESSIONAL
G
E O R G
I
A
RE
G ISTERED
ENG INE ER
B R A N
D O N M. W
EB
S T E
09/13/2023
LEGEND
LIGHTING AND POWER
A-2,4,6
CONDUIT RUN CONCEALED ABOVE CEILING OR IN WALL CONTAINING 3 NUMBER 12
CONDUCTORS UNLESS SHOWN OTHERWISE. HASH MARKS, IF SHOWN, INDICATE QUANTITY
OF NUMBER 12 CONDUCTORS. WHERE DRAWING SPACE PROHIBITS HASH MARKS BEING
SHOWN REFER TO CIRCUIT NUMBERS AND PROVIDE REQUIRED NUMBER OF CONDUCTORS
PER CIRCUIT TYPE.
CONDUIT RUN CONCEALED IN OR BELOW FLOOR SLAB, OR UNDERGROUND.
HOMERUN TO PANELBOARD, LETTER OR LETTERS INDICATE PANELBOARDS, NUMBERS
INDICATE CIRCUIT NUMBERS.
EXPOSED CONDUIT RUN.
2-E L.E.D. LIGHTING FIXTURE, "2" INDICATES THE CIRCUIT NUMBER AND "E" THE FIXTURE TYPE.
SEE FIXTURE SCHEDULE FOR DIMENSIONS AND MOUNTING TYPE.
EMERGENCY L.E.D. LIGHTING FIXTURE. SEE FIXTURE SCHEDULE FOR DIMENSIONS,
MOUNTING TYPE AND BATTERY PACK INFORMATION (IF APPLICABLE).
L.E.D. FIXTURE, SURFACE OR STEM MOUNTED.
L.E.D. TROFFER FIXTURE. SEE FIXTURE SCHEDULE FOR DIMENSIONS
AND MOUNTING TYPE.
EMERGENCY L.E.D. TROFFER. SEE FIXTURE SCHEDULE FOR DIMENSIONS, MOUNTING TYPE
AND BATTERY PACK INFORMATION (IF APPLICABLE).
L.E.D. LIGHTING FIXTURE, SURFACE WALL BRACKET MOUNTED. MOUNTING HEIGHT AS
NOTED.
L.E.D. LIGHTING FIXTURE, SURFACE WALL BRACKET MOUNTED. MOUNTING HEIGHT AS
NOTED. SEE FIXTURE SCHEDULE FOR BATTERY PACK INFORMATION (IF APPLICABLE).
L.E.D. CHANDELIER OR PENDANT FIXTURE. CEILING PENDANT MOUNTED.
EXIT LIGHT.
JUNCTION BOX, FLUSH WALL MOUNTED.
JUNCTION BOX LOCATED ABOVE CEILING OR BELOW GRADE.
JUNCTION BOX, FLUSH WALL MOUNTED.
TAMPER RESISTANT (TR) DUPLEX CONVENIENCE OUTLET, +18" TO CENTER LINE OF
OUTLET UNLESS OTHERWISE NOTED. 5" INDICATES THE CIRCUIT NUMBER.
TAMPER RESISTANT (TR) DUPLEX CONVENIENCE OUTLET MOUNTED ABOVE COUNTER, AT
+46" TO CENTERLINE OF OUTLET.
TAMPER RESISTANT (TR) DUPLEX CONVENIENCE OUTLET, GFI TYPE. +18" TO CENTER LINE
UNLESS OTHERWISE NOTED. "WP" WHERE SHOWN INDICATES WEATHER-RESISTANT
DEVICE WITH METAL IN-USE WEATHERPROOF COVER.
TAMPER RESISTANT (TR) DUPLEX CONVENIENCE OUTLET, GFI TYPE. MOUNTED ABOVE
COUNTER AT +46" TO CENTERLINE OF RECEPTACLE UNLESS NOTED OTHERWISE.
SPECIAL RECEPTACLE TO SUIT EQUIPMENT FURNISHED.
TAMPER RESISTANT (TR) QUADRUPLEX RECEPTACLE, +18" TO CENTER LINE OF OUTLET
UNLESS OTHERWISE NOTED.
TAMPER RESISTANT (TR) QUADRUPLEX RECEPTACLE, +46" TO CENTER LINE OF OUTLET
UNLESS OTHERWISE NOTED.
FLUSH FLOOR RECEPTACLE, IN FLOOR BOX WITH HINGED COVER.
TAMPER RESISTANT (TR) DUPLEX CONVENIENCE OUTLET CONNECTED TO EMERGENCY
POWER, +18" TO CENTER LINE OF OUTLET UNLESS OTHERWISE NOTED.
TAMPER RESISTANT (TR) DUPLEX CONVENIENCE OUTLET CONNECTED TO EMERGENCY
POWER, +46" TO CENTER LINE OF OUTLET UNLESS OTHERWISE NOTED.
TAMPER RESISTANT (TR) QUADRUPLEX CONVENIENCE OUTLET CONNECTED TO
EMERGENCY POWER, +18" TO CENTER LINE OF OUTLET UNLESS OTHERWISE NOTED.
TAMPER RESISTANT (TR) QUADRUPLEX CONVENIENCE OUTLET CONNECTED TO
EMERGENCY POWER, +46" TO CENTER LINE OF OUTLET UNLESS OTHERWISE NOTED.
TAMPER RESISTANT (TR) GFCI DUPLEX CONVENIENCE OUTLET CONNECTED TO
EMERGENCY POWER, +18" TO CENTERLINE OF RECEPTACLE UNLESS NOTED OTHERWISE.
TAMPER RESISTANT (TR) GFCI DUPLEX CONVENIENCE OUTLET CONNECTED TO
EMERGENCY POWER, +46" TO CENTERLINE OF RECEPTACLE UNLESS NOTED OTHERWISE.
TAMPER RESISTANT (TR) FLUSH FLOOR BOX WITH QUADRUPLEX RECEPTACLE AND
DATA/VOICE OUTLET. SEE SPECIFICATIONS FOR TYPE OF BOX.
SINGLE POLE TOGGLE SWITCH, +46" TO CENTER LINE MOUNTING HEIGHT.
THREE OR FOUR WAY SWITCH AS INDICATED. +46" TO CENTER LINE MOUNTING HEIGHT.
KEY OPERATED SINGLE POLE TOGGLE SWITCH, +46" TO CENTER LINE MOUNTING HEIGHT.
LED DECORA STYLE DIMMER WITH ROCKER ON/OFF SWITCH AND SLIDE DIMMER ON SIDE
OF ROCKER. 0-10VDC CAPABLE DIMMER +3'-6" MOUNTING HEIGHT. LUTRON "DIVA 0-10V" OR
EQUAL BY LEVITON, WATTSTOPPER, HUBBELL, OR COOPER. (NO ADDITIONAL POWER PACK
REQUIRED). DIVISION 26 SHALL PROVIDE ALL ADDITIONAL CONDUCTORS TO ALL FIXTURES
CONNECTED FOR A PROPER 0-10VDC OPERATION. GRAY FINISH.
LED DECORA STYLE DIMMER WITH ROCKER ON/OFF SWITCH AND SLIDE DIMMER ON SIDE
OF ROCKER. 0-10VDC CAPABLE DIMMER WITH PASSIVE INFRARED OCCUPANCY SENSOR. +
3’-6” MOUNTING HEIGHT, GRAY FINISH. LUTRON "DIVA 0-10V" OR EQUAL BY LEVITRON,
WATTSTOPPER, HUBBELL OR COOPER. DIMMER MUST BE COMPATIBLE WITH ALL LIGHTING
COMPONENTS (NO ADDITIONAL POWER PACK REQUIRED). DIVISION 26 SHALL PROVIDE ALL
ADDITIONAL CONDUCTORS TO ALL FIXTURES CONNECTED FOR PROPER 0-10V OPERATION.
LED DECORA STYLE DIMMER WITH ROCKER ON/OFF SWITCH AND SLIDE DIMMER ON SIDE
OF ROCKER. 0-10VDC CAPABLE THREE WAY DIMMER, +3'-6" MOUNTING HEIGHT. LUTRON
"DIVA 0-10V" OR EQUAL BY LEVITON, WATTSTOPPER, HUBBELL, OR COOPER. (NO
ADDITIONAL POWER PACK REQUIRED). DIVISION 26 SHALL PROVIDE ALL ADDITIONAL
CONDUCTORS TO ALL FIXTURES CONNECTED FOR A PROPER 0-10VDC OPERATION. GRAY
FINISH.
LOW VOLTAGE SWITCH WALL MOUNTED. +46" TO CENTER LINE MOUNTING HEIGHT.. SEE
LOW VOLTAGE SWITCHING NOTES FOR SWITCH BUTTON QUANTITY, CONFIGURATION, AND
OPERATION.
PANELBOARD, SEE SCHEDULE.
FIRE ALARM SYSTEM
VOICE EVACUATION SIGNAL, SPEAKER, AND STROBE LIGHT, +6'-10" MOUNTING HEIGHT TO
CENTER OF DEVICE, UNLESS NOTED BY "C" MOUNT TO CEILING.
HEAT DETECTOR, CEILING MOUNTED.
SMOKE DETECTOR, CEILING MOUNTED.
CARBON MONOXIDE DETECTOR, CEILING MOUNTED.
TAMPER SWITCH, FURNISHED AND INSTALLED WITH SPRINKLER SYSTEM. INTERLOCK WITH
FIRE ALARM SYSTEM BY ELECTRICAL.
FLOW SWITCH, FURNISHED AND INSTALLED WITH SPRINKLER SYSTEM. INTERLOCK WITH
FIRE ALARM SYSTEM BY ELECTRICAL.
SIGNAL, CHIME, AND STROBE LIGHT, 6'-10" MOUNTING HEIGHT.
STROBE LIGHT, 6'-10" MOUNTING HEIGHT TO CENTER OF DEVICE.
STROBE LIGHT, CEILING MOUNTED.
PULL STATION. WALL MOUNTED +46" TO CENTER LINE MOUNTING HEIGHT.
FIRE ALARM DOCUMENTATION BOX.
FIRE ALARM CONTROL PANEL. SURFACE WALL MOUNTED.
FIRE ALARM LCD REMOTE ALPHANUMERIC ANNUNCIATOR. FLUSH WALL MOUNTED.
DUCT SMOKE DETECTOR, LOCATED AT HVAC UNIT OR UP STREAM OF SMOKE DAMPER.
COORDINATE EXACT LOCATION WITH MECHANICAL DRAWINGS PRIOR TO ROUGHING IN.
J
J
VE
SL
SL
FACP
DOC
FAA
DD
VS
WF
C H
FIRE ALARM CONNECTION TO HOOD EXTINGUISHING SYSTEM. SEE MECHANICAL
DRAWINGS FOR LOCATION.
FIRE ALARM CONNECTION TO DOOR HOLDER, FLOOR OR WALL MOUNTED. CONSULT
ARCHITECTURAL DRAWINGS TO DETERMINE TYPE REQUIRED.
FIRE ALARM REMOTE ELEVATOR INTERFACE MODULE.
VOICE EVACUATION REMOTE MICROPHONE.
CONTROL/MONITOR MODULE.
TELEPHONE / DATA SYSTEMS
PLYWOOD BACKBOARD "T.B." INDICATES TELECOMMUNICATIONS BOARD.
DATA RACK, 2 POST, WITH VERTICAL CABLE WIRE MANAGEMENT. SEE SPECIFICATIONS.
DATA RACK, 4 POST, WITH VERTICAL CABLE WIRE MANAGEMENT. SEE SPECIFICATIONS.
VOICE OUTLET., +46" TO CENTER LINE OF OUTLET UNLESS NOTED OTHERWISE. STUB UP
1"C. TO CEILING SPACE ABOVE.
DATA OUTLET., +18" TO CENTER LINE OF OUTLET UNLESS NOTED OTHERWISE. STUB UP
1"C. TO CEILING SPACE ABOVE.
DATA OUTLET., +46" TO CENTER LINE OF OUTLET UNLESS NOTED OTHERWISE. STUB UP
1"C. TO CEILING SPACE ABOVE.
DATA OUTLET. (WIRELESS ACCESS POINT), +6" ABOVE ACCESSIBLE CEILING UNLESS NOTED
OTHERWISE. WHERE THERE IS NO CEILING OR HIGH CEILING, WALL MOUNT AT +11' A.F.F.
FCSU
DH
MIC
C M
ESR
TB
W
F
ULTRASONIC OCCUPANCY SENSOR. CEILING MOUNTED (WATTSTOPPER "UT" SERIES OR
EQUAL). PROVIDE ALL NECESSARY COMPONENTS TO INSURE PROPER OPERATION
(POWER PACKS, SLAVE PACKS, ETC.)
ULTRASONIC HALLWAY OCCUPANCY SENSOR. CEILING MOUNTED. (WATTSTOPPER
"WT-2255" OR EQUAL). PROVIDE ALL NECESSARY COMPONENTS TO INSURE PROPER
OPERATION (POWER PACKS, SLAVE PACKS, ETC.)
UO
HO
DISCONNECT SWITCH, SIZE AS NOTED ON DRAWINGS. FUSED PER MANUFACTURER'S
NAME PLATE DATA OF EQUIPMENT SERVED.
MANUAL MOTOR STARTER / DISCONNECT. SIZE AS NOTED ON DRAWINGS.
SINGLE OR DOUBLE POLE, MINIMUM 20 AMP MOTOR RATED ENCLOSED SWITCH WITH
"LOCK-OUT" OPTION. MOUNTED NEAR EQUIPMENT BEING SERVED.
MOTOR.M
PROVIDE 4 11/16" SQUARE BY 3-1/2" DEEP JUNCTION BOX WITH 1 1/2" CONDUIT
STUBBED UP TO ABOVE CEILING. AUDIO/VISUAL OUTLET. SEE DETAIL 3/8.4.
AV
2" EMT TROUGH WALL WITH PLASTIC BUSHINGS ON EACH END. UNLESS OTHERWISE
NOTED.
EMERGENCY OVERRIDE LIGHTING RELAY "BYPASS". SEE DETAIL 8/E8.2.
EMERGENCY OVERRIDE LIGHTING RELAY "NORMAL". SEE DETAIL 1/E8.3.
WALL MOUNTED 120V HAND DRYER. COORDINATE EXACT HEIGHT WITH ARCHITECTURAL
ELEVATIONS PRIOR TO ROUGH-IN.
ELECTRICAL WATER COOLER. PROVIDE A DUPLEX RECEPTACLE AT WATER COOLER.
CIRCUIT SHALL BE GFCI PROTECTED. REFER TO DETAIL 3/E8.1 FOR ROUGH-IN.
POWER SUPPLY. PROVIDE JUNCTION BOX AND 120V CONNECTION.
E O
E N
HD
WC
PS
CABLE TRAY SIZE: 18"W x 4"H TYP.
GENERATOR REMOTE ANNUNCIATOR. FLUSH RECESSED MOUNTED.G
A
OCCUPANCY SENSORS
SWITCH, WALL MOUNTED OCCUPANCY SENSOR (WATTSTOPPER PW-100 OR EQUAL). +46"
TO CENTER LINE MOUNTING HEIGHT.
DUAL TECHNOLOGY 360° OCCUPANCY SENSOR. CEILING MOUNTED. INFRARED/ULTRASONIC
(WATTSTOPPER "DT" SERIES OR EQUAL). PROVIDE ALL NECESSARY COMPONENTS TO
INSURE PROPER OPERATION (POWER PACKS, SLAVE PACKS, ETC.)
os
ACCESS CONTROLS SYSTEM (BACKBOXES AND CONDUIT ONLY, SYSTEMS BY OTHERS)
DOOR CONTACT POSITION SENSOR LOCATION. PROVIDE SINGLE GANG BOX BY DIVISION
16 AT DOOR FRAME ON SECURE SIDE OF DOOR. COORDINATE EXACT LOCATION WITH
ACCESS CONTROL SYSTEM VENDOR. PROVIDE 3/4"C., WITH PULLSTRING FROM BOX TO
STUB-OUT 6" ACCESSIBLE CEILING AT DOOR. SEE DETAIL 3/E8.2.
ACCESS CONTROL HEAD END.
C.C.T.V. SYSTEM
CCTV SYSTEM CAMERA, WALL OR CEILING MOUNTED. NUMBER DESIGNATES CAMERA
NUMBER, "WP" INDICATES WEATHERPROOF.
CCTV SYSTEM HEAD END EQUIPMENT.
CCTV SYSTEM MONITOR. VERIFY LOCATIONS WITH ARCHITECT/OWNER.
TELEVISION OUTLET, +98" TO CENTER LINE, UNLESS OTHERWISE NOTED. LOCATE DUPLEX
OUTLET SHOWN DIRECTLY ADJACENT TO T.V. OUTLET AT SAME HEIGHT.
INTRUSION ALARM SYSTEM
INTRUSION ALARM DETECTOR, INFRARED. CEILING MOUNTED UNIT. 50'-0" COVERAGE
UNLESS OTHERWISE NOTED.
INTRUSION ALARM, KEY PAD. +46" TO CENTER LINE MOUNTING HEIGHT.
INTRUSION ALARM CONTROL PANEL.
SOUND SYSTEM
SPEAKER, CEILING RECESSED.
SPEAKER FLUSH WALL MOUNTED. SEE DRAWING FOR MOUNTING HEIGHT. "WP" WHERE
SHOWN INDICATES EXTERIOR WEATHERPROOF SPEAKER.
EMERGENCY CALL STAFF STATION. +46" TO CENTER LINE MOUNTING HEIGHT. HANDSET
TYPE. SEE SPECIFICATIONS.
CALL-IN STATION WITH MONITOR SPEAKER ATLAS-SOUNDOLIER #VPVT +48" MOUNTING
HEIGHT TO COMPLY WITH ADA. FLUSH WALL MOUNTED. "WP" WHERE SHOWN INDICATES
EXTERIOR WEATHERPROOF OUTLET BOX AND COVER.
VOLUME CONTROL, +46" TO CENTER LINE MOUNTING HEIGHT.
SOUND CABINET. SEE SPECIFICATIONS.
ADMINISTRATION INTERCOM TELEPHONE OUTLET AND PHONE (BOGEN MODEL MCDS4).
MOUNT +18" ABOVE FINISHED FLOOR TO CENTER OF OUTLET.
STAFF INTERCOM TELEPHONE OUTLET AND PHONE (BOGEN MODEL MCDS4). MOUNT +18"
ABOVE FINISHED FLOOR TO CENTER OF OUTLET.
I
I K
C P
S
S WP
E
ES
V
SC
A
S
TV
C
CC
M
AC
DC
A C
PRIORITY EMERGENCY CALL PUSHBUTTON. INTERFACE TO PHONE LINE FOR DIRECT 911
CALL. ADEMCO #268.
"AREA OF REFUGE" INDICATOR SIGN, DIE CAST ALUMINUM HOUSING, GREEN LETTERING
WITH "AREA OF REFUGE" LETTERING AND PICTOGRAM. FIXTURE SHALL BE OF SAME
MANUFACTURER AS TYPE "X" EXIT SIGN. TIE INTO EXIT SIGN CIRCUIT.
AREA OF REFUGE MASTER STATION. +48" AFF RECEIVES ALL CALLS FROM "AREA OF
REFUGE PHONES" SHOWN.
"AREA OF REFUGE PHONE" FLUSH MOUNTED AT 42" AFF. DEDICATED TWO-WAY
COMMUNICATION DEVICE TO BE CONNECTED TO CENTRAL PHONE LOCATION IN GENERAL
OFFICE 1901 AS WELL AS PROGRAMMED TO DIAL OFF SITE LOCATION. DEVICE SHALL HAVE
STAINLESS STEEL COVER WITH SINGLE PUSHBUTTON OPERATION AND LABELED AS
"EMERGENCY PHONE" (BRAILLE LABELING INCLUDED), PROVIDE SIGNAGE (TALK-A-PHONE #
ETP-SIGN-PFH) AND EMERGENCY PHONE (TALK-A-PHONE #ETP-400V)
AREA OF REFUGE COMMUNICATION SYSTEM SEE SHEETS E5.3 AND E5.4
AR
AR M
L
AR
E
ACCESS CONTROL CARD ACCESS VIDEO DOOR STATION WITH SURFACE MOUNTED
BACKBOX. SURFACE MOUNT AT +54" A.F.F. SEE DETAIL 3/E8.2.
ACCESS CONTROL CREDENTIAL READER. PROVIDE UNIT WITH CARD SWIPE/ PROXIMITY
READER AND CONNECT TO ACCESS CONTROL SYSTEM. MOUNT AT +48" A.F.F. SEE DETAIL
3/E8.2.
CR
TRACK LIGHT FIXTURE(S). CEILING OR PENDANT MOUNTED.
AMPLIFIER, FLUSH WALL MOUNTED ENCLOSURE.
MICROPHONE OUTLET, FLUSH WALL MOUNTED +3'-6" ABOVE FINISHED FLOOR UNLESS
OTHERWISE NOTED.
A
TAMPER RESISTANT (TR) FLUSH POKE THRU WITH QUADRUPLEX RECEPTACLE AND
DATA/VOICE OUTLET. SEE SPECIFICATIONS FOR TYPE OF POKE THRU.
(BACKBOXES AND CONDUIT ONLY. SYSTEMS BY OTHERS.)
(BACKBOXES AND CONDUIT ONLY, SYSTEMS BY OTHERS.)
(BACKBOXES AND CONDUIT ONLY, SYSTEMS BY OTHERS.)
DUAL TECHNOLOGY 360° OCCUPANCY SENSOR. CEILING MOUNTED. HIGHBAY TYPE.os
HB
PANEL
DESIGNATION:
FIXTURE TYPE:
TYPE "A" IF NO
CAPITAL LETTER
SHOWN
B/ HA1 -1, b
SWITCH LEG
DESIGNATION
WHEN MULTIPLE
SWITCHES ARE IN
SAME SPARE/AREA
CIRCUIT
NUMBER:
EXAMPLE: B/HA1-1,b
LIGHT FIXTURE
DESIGNATION DESCRIPTION
EQUIPMENT ID:
MECHANICAL/
PLUMBING
EQUIPMENT
PANEL - CIRCUIT
NUMBER:
EXAMPLE:
MECHANICAL EQUIPMENT
TAG DESCRIPTION
NOTE: REFER TO MECHANICAL CONNECTION SCHEDULES FOR
CIRCUITING INFORMATION
RAC-1
HR-7,9,11
RAC-1
HR-7,9,11
A M
E S
E.
J
FLE M I
NO. PE326
PROFESSIONAL
I I I
G
EORGIA
REG
ISTERED
ENGINEER
N
G
ELECTRICAL ENGINEERS
1201 BROAD ST., SUITE 1-A
AUGUSTA, GA 30901
PH: (706) 724-3551
FAX: (706) 724-8507
EDC PROJECT #:
W A
R N
IN
G
C on tr ac to rs su bc on tr ac to rs ve nd or s an d su pp lie rs a re a dv is ed t ha t t he c on tr ac t do cu m en ts c on si st o f
A rc hi te ct -r ep ro du ce d pr in te d, b ou nd a nd n um be re d sp ec ifi ca tio ns
A rc hi te ct -r ep ro du ce d pr in te d, b ou nd be re d bl ue or b la ck -li ne p rin ts
, a dd en da
, p os t-bi d ad de nd a, a nd c ha ng e or de rs o nl y.
D oc um en ts r ep ro du ce ie s ot he r th an th e A rc hi te ct
, w he th er in h ar d co py o r in e le ct ro ni c fo rm at
, s ha ll no t b e co ns id er ed p ar t o f th e co nt ra ct d oc um en ts a nd d o no t su pe rs ed e th e pr ov is io ns o f t he c on tr ac t d oc um en ts
T he c on tr ac to r, s ub co nt ra ct or s an d su pp lie rs a re s ol el y re sp on si bl e fo r ve rif ic at io n th at in fo rm at io n ut ili ze d in b id di ng de ve lo pm en t of s ho p dr aw in gs an d co ns tr uc tio n of t he fa ci lit y ar e id en tic al to t he c on tr ac t do cu m en ts
PROJECT NUMBER
PROJECT DATE
APPROVED BY
CHECKED BY
DRAWN BY
Copyright (c) 2023 All Rights Reserved.
ISSUED FOR:
JA
M
E S
W
B U
C K
L E
Y
A S
S O
C
IA
T E
S I
N C
A R
C H
IT
E
C T
S S
W A
IN
S
B O
R O
A
L B
A N
Y R
O M
E A
N D
S A
V A
N N
A H
G E
O R
G
IA
SHEET
NUMBER:
23060
9 13 23
9/
/2
:1 4:
P
M A ut od es k
D oc s:
//2
B lo om in gd al e E
S /2
E D
C E le ct ric al
R
B lo om in gd al e E
S .r vt
L E
G E
N D
N
O T
E S
D
E T
A
IL
S A
N D
F
IX
T U
R E
S C
H E
D U
L E
B L
O O
M
IN
G D
A L E
E L
E M
E N
T A
R Y
S C
H O
O L
09/13/2023
22-072
JEF
JEF
AN/CT
FINAL/BID
S A
V A
N N
A H
-C H
A T
H A
M C
O U
N T
Y P
U B
L
IC
S C
H O
O L
S Y
S T
E M
B L
O O
M
IN
G D
A L
E G
E O
R G
IA
S
C H
O O
L C
O D
E
-4
E1.0
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION WATTS LUMENS
COLOR
TEMP MANUFACTURERS NOTES
A1 LED FIXTURE, 2' x 4' RECESSED CEILING GRID TYPE EDGE-LIT FLAT
PANEL FIXTURE WITH SINGLE PIECE INJECTION FRAME AND SMOOTH
WHITE LENS.
37 W 4000 3500 K METALUX "24FP" SERIES
LITHONIA, COLUMBIA,
ORACLE, JADEMAR
B1 LED FIXTURE, 2' x 4' RECESSED CEILING GRID TYPE BACK-LIT FLAT
PANEL FIXTURE WITH SINGLE PIECE INJECTION FRAME AND SMOOTH
WHITE LENS.
32 W 4000 3500 K LITHONIA "CPX" SERIES
METALUX, COLUMBIA,
ORACLE, JADEMAR
B2 LED FIXTURE, 2' x 4' RECESSED CEILING GRID TYPE BACK-LIT FLAT
PANEL FIXTURE WITH SINGLE PIECE INJECTION FRAME AND SMOOTH
WHITE LENS.
45 W 5000 3500 K LITHONIA "CPX" SERIES
METALUX, COLUMBIA,
ORACLE, JADEMAR
C LED FIXTURE, 2' x 2' RECESSED CEILING GRID TYPE BACK-LIT FLAT
PANEL FIXTURE WITH SINGLE PIECE INJECTION FRAME AND SMOOTH
WHITE LENS.
30 W 3400 3500 K LITHONIA "CPX" SERIES
METALUX, COLUMBIA,
ORACLE, JADEMAR
E1 4' STRIP LIGHT FIXTURE SURFACE MOUNTED WITH WHITE ACRYLIC
LENS AND WHITE FINISH. (SURFACE, STEM, OR CHAIN SUSPEND
WHERE REQUIRED)
43 W 5437 3500 K LITHONIA "CSS" SERIES
METALUX, COLUMBIA, H.E.
WILLIAMS, ILP
F1 RECESSED COMMERCIAL GRADE DOWNLIGHT WITH 6" APERTURE
WITH WHITE TRIM . FIXTURE SHALL BE CONSTRUCTED OUT OF 16
GAUGE GALVANIZED STEEL WITH OPEN DOWNLIGHT REFLECTOR AND
PASSIVE COOLING. WET LISTED.
31 W 2500 3500 K LITHONIA "LBR6" SERIES
PEACHTREE, PRESCOLITE,
HALO COMMERCIAL, ELITE
LIGHTING, LSI, SPECTRUM,
GREEN CREATIVE
F2 RECESSED COMMERCIAL GRADE DOWNLIGHT WITH 6" APERTURE
WITH WHITE TRIM . FIXTURE SHALL BE CONSTRUCTED OUT OF 16
GAUGE GALVANIZED STEEL WITH OPEN DOWNLIGHT REFLECTOR AND
PASSIVE COOLING. WET LISTED.
20 W 1500 3500 K LITHONIA "LBR6" SERIES
PEACHTREE, PRESCOLITE,
HALO COMMERCIAL, ELITE
LIGHTING, LSI, SPECTRUM,
GREEN CREATIVE
HB FULL BODY LED HIGH BAY FIXTURE WITH DIE FORMED ALUMINUM OR
STEEL HOUSING, ANODIZED ALUMINUM REFLECTOR, CLEAR ACRYLIC
LENS WITH WIREGUARD IN DOOR FRAME.WHITE POWDER COAT
FINISH. MOUNT TO BOTTOM OF TRUSS. PROVIDE SAFETY CHAINS ON
WIRE GUARD, TO FIXTURE, TO STRUCTURE ABOVE.
150 W 24000 3500 K LITHONIA IBG SERIES IBG 24L
MVOLT 5K
COOPER
COLUMBIA
LITHONIA
LSI
ILP
LS LED FLOODLIGHT, BLACK FINISH TENON MOUNTED ON TOP OF 12'
ABOVE GRADE RACK POST.
6800 4000 K LITHONIA, STONCO, LUMARK
OE L.E.D. GROUND MOUNTED FLOOD LIGHT WITH ONE PIECE.
LOWCOPPER ALUMINUM ALLOY CONSTRUCTION AND
IMPACTRESISTANT TEMPERED GLASS. FINISH AS SELECTED
BYARCHITECT. COORDINATE BEAM ANGLE TO PROPERLY ILLUMINATE
FLAG POLE.
10000 4000 K KIM LIGHTING "KFL3" SERIES
HYDREL,
COOPER
Q LED FLOOD FIXTURE, DIE-CAST ALUMINUM HOUSING WITH TEMPERED
GLASS LENS WITH ADJUSTABLE BASE MOUNT, 10° DISTRIBUTION, RGB
COLOR CHANGING LED (MAXIMUM LIGHT OUTPUT WHEN WHITE).
FIXTURE SHALL HAVE GLARE VISOR AND HAVE BLACK TEXTURED
FINISH. MOUNTED TO STRUCTURE WITH ALL REQUIRED MOUNTING
EQUIPMENT NECESSARY FOR PROPER INSTALLATION.
DRIVER: 120V WITH DMX CONTROLS. PROVIDE WITH WINONA "EASYL"
DMX CONTROLLER AND BELDEN 9829 CABLE FOR DMX SIGNAL DAISY
CHAINED BETWEEN FIXTURES TO THE CONTROLLER.
1894 4000 K WINONA "PFL707" SERIES
ACCLAIM LIGHTING
INSIGHT LIGHTING
BEACON LIGHTING
GVA LIGHTING
S 4' FIXTURE SURFACE MOUNT, LOW PROFILE, VANDAL RESISTANT.
FIXTURE SHALL BE EQUIPPED WITH MOTION SENSOR.
52 W 5900 3500 K LUMINAIRE "TSL" SERIES,
LITHONIA, METALUX,
COLUMBIA, LAMAR
T1 LED TRACK MOUNTED FIXTURE WITH ALUMINUM HOUSING,
ADJUSTABLE BASE MOUNT, 60 DEGREE DISTRIBUTION, TGB COLOR
CHANGING LED AND WHITE LIGHT OPTION. FIXTURE SHALL HAVE
FINISH. FIXTURE SHALL BE SURFACE MOUNTED IN LENGTH AS
SHOWN, BLAKC FINISH, AND HAVE DMX INOUT CAPABILITIES. PROVIDE
ACCESSORIES AS NEEDED FOR A PROPER MOUNTING AND
INSTALLATION.
2000 4000 K TIMES SQUARE "MOSAIC"
SERIES
ALTMAN, AMERLUX, LITELAB
HELIOS "6R"
T2 LED TRACK MOUNTED FIXTURE WITH FLOOD OPTICS. TGB COLOR
CHANGING LED AND WHITE LIGHT OPTION. FIXTURE SHALL BE
SURFACE MOUNTED IN LENGTH AS SHOWN, WHITE FINISH, AND HAVE
DMX INPUT CAPABILITIES. PROVIDE ACCESSORIES AS NEEDED FOR A
PROPER MOUNTING AND INSTALLATION.
1168 3500 K JUNO "R620L" SERIES OR
EQUAL
W L.E.D WALL MOUNTED FIXTURE, TRAPEZOID HOUSING. TYPE II
DISTRIBUTION WITH FINISH TO BE SELECTED BY ARCHITECT.
COORDINATE MOUNTING HEIGHT WITH ARCHITECT.
18 W 2000 4000 K LITHONIA "WDGE2 LED"
SERIES
GARDCO, HUBBELL, LUMARK,
ILP
A. CONTRACTOR SHALL REFER TO SPECIFICATIONS REGARDING PROVIDING ADDITIONAL SPARE LAMPS, LENSES, AND GLOBES.
B. WHERE "APPROVED EQUAL" IS LISTED IN THE MANUFACTURER COLUMN, FIXTURES MUST BE SUBMITTED AS A SUBSTITUTION FOR APPROVAL PRIOR TO BID SUBMISSION.
C. ALL FIXTURE VOLTAGES SHALL BE MULTI VOLT TYPE UNLESS OTHERWISE NOTED.
D. PROVIDE DIMMING DRIVER, 0-10VDC,1-100% ON ALL FIXTURES EXCEPT TYPES E1, OE, W, AND X.
GENERAL NOTES:
L.E.D. EXIT LIGHT, PROVIDE WITH DIE-CAST BRUSHED ALUMINUM
HOUSING AND GREEN FACED BACKGROUND. UNIVERSAL
MOUNTING.
LAMPS: L.E.D.
DRIVER: MULTI VOLT INPUT
LITHONIA "LQC" SERIES
SURE-LITE "CX" SERIES
CHLORIDE "46 LINE" SERIES
DUAL-LITE "SEMPRA" SERIES
1. DO NOT SCALE DRAWINGS TO LOCATE EQUIPMENT OR OUTLETS.
2. MOUNTING HEIGHTS AS INDICATED ON THE DRAWINGS SHALL BE FROM THE FINISHED FLOOR TO THE
CENTER LINE OF THE OUTLET BOX.
3. THE ELECTRICAL DRAWINGS ARE ONLY A PART OF THE CONTRACT DOCUMENTS. ALL OF THE DRAWINGS AND SPECIFICATIONS MUST BE REVIEWED FOR THEIR INTERRELATIONSHIP AND REQUIRED COORDINATION
BETWEEN DISCIPLINES.
4. SYMBOL INDICATING ROOM OR SPACE NUMBER.
5. IN AREAS WHERE COMPUTER OUTLETS AND TELEPHONE OUTLETS ARE LOCATED BENEATH A WINDOW, AND WINDOW PREVENTS THE ROUTING OF CONDUIT UP TO CEILING SPACE, CONDUIT SHALL BE ROUTED TO A
WALL WHICH ALLOWS CONDUIT TO RISE UP TO CEILING SPACE.
6. ALL CONDUIT ROUTED FROM DISCONNECT TO EXTERIOR HVAC UNITS SHALL BE ROUTED UNDERGROUND.
TURN UP ADJACENT TO UNIT AND MAKE TRANSITION TO SEALTITE TO SERVE UNIT. CONDUIT SHALL BE.
ROUTED CONCEALED IN WALL.
7. ALL FLUSH RECESSED OUTLET BOXES SHALL BE INSTALLED SUCH THAT FRONT EDGE OF BOX WILL NOT BE SET BACK OF THE FINISHED SURFACE MORE THAN 1/4" IN ORDER TO COMPLY WITH N.E.C. 314-20. SUPPORT
OF OUTLET BOX BY RECEPTACLE AND COVERPLATE IS NOT ACCEPTABLE.
8. ALL CONDUIT, OUTLET BOXES, AND LOW VOLTAGE CABLING SHALL BE APPROPRIATELY SUPPORTED THROUGHOUT THE PROJECT. SUPPORT OF THESE ITEMS BY CEILING GRID OR GRID SUPPORT WIRES IS NOT
ACCEPTABLE.
9. ALL EXTERIOR DISCONNECTS SHALL BE RATED NEMA 3R.
10. COORDINATE EXACT LOCATION OF ALL MECHANICAL AND PLUMBING EQUIPMENT WITH DIVISION 23…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .