ATTACHMENT C Plans and Drawings to Repair HVAC at B243 at Kingsley Field.pdf
PDF 941 KB Posted
- Attached to
- Repair HVAC at B243 at Kingsley Field
- Solicitation number
- S-24800-00007924
- Issued by
- Josephine County, Oregon
About this file
This document is a set of plans and drawings related to a contract opportunity to repair the HVAC system at Building 243 at Kingsley Field, which is operated by the 173rd Civil Engineering Squadron of the Oregon Air National Guard in Klamath Falls, Oregon. The scope of work includes demolition of existing HVAC components, installation of a new evaporator coil, line sets, controls, conduits, a polymer concrete trough, and wall infill. The project involves selective demolition of concrete, EIFS, and other building materials. The drawings provide detailed specifications and dimensions for the new HVAC components and installation. The project is identified by number KJAQ232002 and has a planned completion date of June 2, 2023.
The contract requires the installation of new HVAC equipment, including a 50-ton condenser unit, as well as new electrical components such as a 400-amp fused disconnect switch and junction boxes. The drawings include details for the polymer concrete trough that will house the refrigerant lines, control conduits, and power conduits. The contract calls for the replacement of approximately 1,300 square feet of concrete patio. Funding requirements and sources are not specified in the provided information.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
36C
36A
36B
Room
Mechanical
Con-X- Box
Fuel tank
Comm RM
Mech mezzanine
36'-8"±
35'±
24'-5± 26'-8"
173rd CE Squadron.
Oregon Air National Guard.
221 Wagner St Suite 16.
Kingsley Field
Klamath Falls OR.
(541)885-6303
FAX (541)885-6195
DSN 830-6303
Repair Building 243
HVAC
D-0
Protect all facilities, grounds, plants, and utilities not scheduled to receive work.
Contractor shall confirm location of all utilities within construction area.
1. Demo LB, conduit, to fuel tank and disconnect from interior receptacle.
2. Demo vault, fuel lines and cap off.
3. Drain fuel tank and remove. Demo CMU inclosure,footing and fencing and remove.
4. Selective demo of existing sidewalk, stem wall and interior floor to install (N) trough.
5. Selective demo of (E) 6" thick concrete panels as outlined.
6. demo louver. selective demo of EIFS.
7. Remove disconnect associated equipment as needed. Main breaker is located in electrical RM off main lobby
8. Demo control panel and compressor. (See note 12)
9. Condensing unit and ducting.
10. Demo evaporator coil.
Coil will have to be disassembled to be removed from mezzanine.
Move existing mixing box due to thicker coil.
11. demo condensate line.
12. Gov will provide tanks for recovered refrigerant and will dispose of tanks.
Option 1. Demolish approximately 6" x 1,300sq.
ft PCC and 4" of sub grade.
KJAQ232002
6/2/2023
1/8" = 1'
D. Ray
#2 06/27
1.
E x i s t i n g c o n c r e t e s l a b
Comm cabinets
2.
(E)Sidewalk
Roof line
3.
7.
Cut line
5.
5.
4.
E
P
C
C p a t i o
6.
Mini split head
Mini split conds.
8. 9.
11.
10.
Return disconnect to GOV.
(E)Ducting. (E) Mech .
Cut line
O p t i c n c r e b r p l a c e m e n t
Cut line
(E) clean out.
(E) power
(E) Irrigation box
CB
D. Mauch
#1 06/23
V. Podojil
Engineering
AutoCAD SHX Text Scale
AutoCAD SHX Text Project
AutoCAD SHX Text Date
AutoCAD SHX Text Sheet
AutoCAD SHX Text Revision/Issue
AutoCAD SHX Text Project Name and Address
AutoCAD SHX Text Firm Name and Address
AutoCAD SHX Text No.
AutoCAD SHX Text Date
AutoCAD SHX Text General Notes
Room
Mechanical
Shed
Con-X- Box
L i a f i c r a t e d L i a f i c r a t e d
Mech mezzanine
CB
16'-6"
15'-5"
4'-3"
5'-9"
18'-8"±
9'±
36'-8"± 26'-8"24'-5"±
35'-4"±
M C
M C
173rd CE Squadron.
Oregon Air National Guard.
221 Wagner St Suite 16.
Kingsley Field
Klamath Falls OR.
(541)885-6303
FAX (541)885-6195
DSN 830-6303
G-0
1. New evaporator coil.
2 .Line sets, controls, needed conduits will be mounted to bottom cord of roof truss using unistrut.
3. Polymer concrete trough will run under wall and shall be sized as needed for lines and conduits. Lines and conduits will be mounted as close as possible to the wall. Trough cover sall be cut and drilled to accommodate line sets conduits.
4. Connect existing feeder to new interior J-box thru wall to new exterior rated 400-amp fused disconnect switch. Feeder will return to interior and be ran in 2.5" conduit thru trough to mechanical unit.
5. Infill wall. 18 gauge metal framing. gyp board 8" type X moisture and mildew resistant. Provide backing. Patch any holes or damaged areas on entire south wall to a level 4 finish, 1 coat of primer with minimum of 2 coats of paint. EIFS cut back to nearest control joint or full panel. Match existing ridged insulation board thickness, match existing EIFS texture, style, profile and facility colors.
6. Polymer concrete troughs shall be rated for light traffic, 5' lengths, width sized as needed for lines sets and conduits.
interlocking attachment to one another . covers with non skid surface bolt down covers with lifting pins.
Trough will run under mechanical unit so that condensing lines, controls and power conduits are not exposed outside of the mechanical unit.
7. 1" PVC pipe placed in trough and PCC to drain trough.
8. PCC 3500psi, air 5% ±1, slump 5 max, reinforcement #4-16" o.c.
Base slab will 4" with 1' monolithic thickened edges. House keeping pad 4" wider thin unit and 4" high.
D. Mauch
#1
(3)Line sets controls coming up inside bldg through trough.
See detail 1,2,3.
(N)Landscape rock match existing
O p t i b p l a c e m e n t
7.1" PVC to drain trough.
See detail 3.
House keeping pad 3" higher.
See detail 1.
Edge of (E) PCC. to remain
(E)PCC control line
(E)Sidewalk
(2)Line sets, conduits.
See detail 1,2.
(1)Evaporator coil
(E) adjust mixing box
(6)Trough
See detail 1,2,3.
8. Concrete same elevation as sidewalk.
(4)Interior J-box w/ exterior disconnect.
See detail 1,2.
(5)Infill wall.
(E)CO
Irrigation box
E
S l a b
Slope
(E)PCC control line
Grade control point
Repair Building 243
HVAC
KJAQ232002
6/2/2023
1/8" = 1'
06/23
(N)PCC
S l o p e
S l o p e
(Option 2. repair EIFS marked gray
(E) Condenser (typ)
D-1,2
D. Ray
#2 06/27
V. Podojil
Engineering
AutoCAD SHX Text Scale
AutoCAD SHX Text Project
AutoCAD SHX Text Date
AutoCAD SHX Text Sheet
AutoCAD SHX Text Revision/Issue
AutoCAD SHX Text Project Name and Address
AutoCAD SHX Text Firm Name and Address
AutoCAD SHX Text No.
AutoCAD SHX Text Date
3"EMT.
J-box sized as needed.
6"x6"Wall mounted trough.
Refrigerant lines
Unistrut.
LV control conduits.
Roof structure.
(E) power feed coming thru slab. Main breaker is located in E RM off main lobby.
50 ton condenser unit.
(N)Exterior rated
400-amp fused disconnect.
(N)J-box sized as needed.
2-1/2" conduits thru wall to disconnect.
(E) Interior PCC
(E)Patio PCC connection point / ramp down.
(N)6"x6" Metal Cable trough mounted on the wall, extending down into trough. 2-1/2" conduit from mech unit will attach to the back of the trough.
(N)2-1/2"EMT.
(N)Refrigerant lines and LV conduits mounted to roof framing w/ unistrut.
(N)Refrigerant and control line shall run from trough up into condenser unit.
2-1/2"EMT Shall run thru end of the trough and continue thru the PCC then turn up into the bottom of mech unit.
Flexible conduit shall be used to make connection.
(E) Sidewalk
(N)Level house keeping pad. 3" high. 4" beyond base of unit.
(N)6"±Raised PCC pad sloping away from sidewalk.
16'-6"± 5'-9"±
6"
1'
18'-8"±
5'
Verify 6"
Bolt down
Lift pin
Polymer concrete cover with Non skid surface
(E)Sidewalk
Verify 2'
(N)4" PCC
/w
"radius.(TYP)
Trough
Mech base.
(N)Wall built over trough.
House keeping pad is open to trough.
" radius.
Trough cover cut to fit utilities
2'-6" 2'-6"
1" sch 40 PVC to drain trough
173rd CE Squadron.
Oregon Air National Guard.
221 Wagner St Suite 16.
Kingsley Field
Klamath Falls OR.
(541)885-6303
FAX (541)885-6195
DSN 830-6303
D-1
Contractor shall verify size of polymer concrete trough to meet their needs.
House keeping pad will need to be poured and placed to accommodate the trough terminating underneath condensing unit as needed to make connections.
Trough will be installed prior to wall being built.
The 3 troughs shall be 5' long. 2 will be installed intact, 1 will be cut in half and adjusted as needed to create the ends with formed in-place concrete to create the end caps.
The trough end underneath the condensing unit shall have a 2-1
2" conduit poured and placed in the end of the trough and the conduit shall continued thru the slab and turned up in an open area in the bottom of the unit framing to make power supply connection.
PCC placed next to trough and cut concrete shall have edges finished with 18" radius, All other edges shall be finished with 34" radius.
Place 6" of 3/4- base rock compacted to 95% over compacted native soil.
New raised concrete pad shall match elevation of existing sidewalk then have a minimal slope to shed water away from the sidewalk. The house keeping pad will be extend 3" above the raised concrete pad and level in all directions.
And extending 4" beyond the base of the unit.
The cable trough example is made by Armorcast Products.
NTS
3 Cable Trough assembly.
D. Mauch
#1
Repair Building 243
HVAC
KJAQ232002
6/2/2023
06/23
1 N-S Cut section.
2 Detail. interior view. NTS.
3a Plan cover.
3b Cross section
Note: Contractor can propose on an alternate configuration. Objective was to not have the power crossing over the line sets and LV conduits.
3c Longitudinal cross section
Scale: 1/4"=1'
Scale: 1/2"=1'
D. Ray
#2 06/27
V. Podojil
Engineering
AutoCAD SHX Text Scale
AutoCAD SHX Text Project
AutoCAD SHX Text Date
AutoCAD SHX Text Sheet
AutoCAD SHX Text Revision/Issue
AutoCAD SHX Text Project Name and Address
AutoCAD SHX Text Firm Name and Address
AutoCAD SHX Text No.
AutoCAD SHX Text Date
| 1. D-0 Demo |
| Sheets and Views |
| KJAQ232002 Repair B243 HVAC - Shortcut-D-0 Demo |
| 2. G-0 Construct |
| Sheets and Views |
| KJAQ232002 Repair B243 HVAC - Shortcut-G-0 |
| 3. D-1 Detail |
| Sheets and Views |
| KJAQ232002 Repair B243 HVAC - Shortcut-Details |
File details come from the government source that posted it. Updated .