Attachment_C_Peerless_Horizontal-Split-Case_Pump_Installation.pdf
PDF 2 MB Posted
- Attached to
- Fire Pump Maintenance & Repair Services
- Solicitation number
- IFB-299-2549402-1-WO
- Issued by
- Orange County, San Francisco City, California
About this file
This is an Invitation for Bid (IFB-299-2549402-1-WO) issued by OC Waste & Recycling for Fire Pump Maintenance & Repair Services covering Orange County and San Francisco City jurisdictions. The procurement seeks qualified contractors to provide comprehensive maintenance and repair services for a fire pump system at the Frank R. Bowerman Landfill in Irvine, California. Services include maintenance of diesel tanks, fire pumps, diesel engines, engine control panels, piping, and related instruments, with preventative and corrective maintenance required at monthly, 6-month, 12-month, and 24-month intervals. The question submission deadline is December 1, 2023, at 2:00 p.m., with bids due by December 5, 2023, at 2:00 p.m., submitted electronically via OpenGov.com. The contract term runs from December 14, 2023, through December 13, 2026, with potential for two additional one-year renewals. Bidders must submit a Company Profile, References, Bidder Certification form, Signature Page, and OCLSB DVBE documentation if applicable.
The total annual expenditure is capped at $200,000, with pricing to include both standard and emergency labor rates. Evaluation will be based on lowest pricing across categories, with the County reserving the right to make multiple awards or reject submissions. Local Small Businesses (OCLSB) and Disabled Veteran Business Enterprises (DVBE) certified by the State of California Department of General Services are eligible for price matching opportunities within 5% of the lowest bid for IFBs and potential score enhancements for proposals. Contractors must provide comprehensive post-service reporting including equipment information, service descriptions, recommendations, technician details, and photographic documentation. Safety protocols require strict adherence to OCWR safety policies, appropriate personal protective equipment, and industrial safety requirements. Miscellaneous parts and services outside the original contract scope require written quotes and specific authorization.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Horizontal Split Case Model AEF Installation, Operation and Maintenance Manual
Rev 07-2021
2005 Dr Martin Luther King Jr Street Indianapolis, IN 46202
Horizontal Split Case
English (US)
Installation and operating instructions .....................................................................................................................................4 T a b le o f c o n te n ts
Indianapolis, IN 46202
E n g lis h (U
S
English (US) Installation and operating instructions
Original installation and operating instructions
Table of contents
1. General information
1.1 Limited warranty
1.2 Hazard statements
1.3 Notes
1.4 Target group
1.5 General safety warnings
1.6 Material safety data sheet
2. Receiving the product
2.1 Unpacking the product
2.2 Inspecting the product
2.3 Transporting the product
2.4 Scope of delivery
3. Installing the product
3.1 Factory support
3.2 Location
3.3 Mechanical installation
3.4 Installation preparation
3.5 Mechanical installation
3.6 Electrical connection
3.7 Control, monitoring, and alarm equipment
4. Preparing the pump for startup
4.1 Lubricating the pump
4.2 Checking rotation
4.3 Guards
4.4 Flushing the system
4.5 System decontamination
4.6 Priming
4.7 Stuffing box
4.8 Starting up the product
5. Storing and handling the product
5.1 Short-term storage
5.2 Handling the product
6. Product introduction
6.1 Product description
6.2 Intended use
6.3 Identification
7. Taking the product out of operation
8. Servicing the product
8.1 Maintenance
8.2 Maintenance schedule
8.3 Dismantling the pump
8.4 Wear ring
8.5 Replacing the wear ring
8.6 Diametrical clearance
8.7 Inspecting the product
8.8 Repairing the product
8.9 Assembling the pump
9. Parts list and sectional drawings
9.1 AEF
9.2 AEF with double row thrust bearing
9.3 12AEF21
10.
Fault finding the product
11. Technical data
12. Disposing of the product
1. General information
1.1 Limited warranty
New equipment manufactured by seller or service supplied by seller is warranted to be free from defects in material and workmanship under normal use and service for a minimum of twelve (12) months from date of installation, eighteen (18) months from date of shipment, unless otherwise stated in product warranty guide
(available upon request). In the case of spare or replacement parts manufactured by seller, the warranty period shall be for a period of twelve months from shipment. Seller's obligation under this warranty is limited to repairing or replacing, at its option, any part found to its satisfaction to be so defective, provided that such part is, upon request, returned to seller's factory from which it was shipped, transportation prepaid. Parts replaced under warranty shall be warranted for twelve months from the date of the repair, not to exceed the original warranty period. This warranty does not cover parts damaged by decomposition from chemical action or wear caused by abrasive materials, nor does it cover damage resulting from misuse, accident, neglect, or from improper operation, maintenance, installation, modification or adjustment. This warranty does not cover parts repaired outside seller's factory without prior written approval. Seller makes no warranty as to starting equipment, electrical apparatus or other material not of its manufacture. If purchaser or others repair, replace, or adjust equipment or parts without seller's prior written approval, seller is relieved of any further obligation to purchaser under this paragraph with respect to such equipment or parts, unless such repair, replacement, or adjustment was made after seller failed to satisfy within a reasonable time seller's obligations under this paragraph.
Seller's liability for breach of these warranties (or for breach of any other warranties found by a court of competent jurisdiction to have been given by seller) shall be limited to: (a) accepting return of such equipment exw plant of manufacture, and (b) refunding any amount paid thereon by purchaser (less depreciation at the rate of 15% per year if purchaser has used equipment for more than thirty [30] days), and canceling any balance still owing on the equipment, or
(c) in the case of service, at seller's option, redoing the service, or refunding the purchase order amount of the service or portion thereof upon which such liability is based. These warranties are expressly in lieu of any other warranties, express or implied, and seller specifically disclaims any implied warranty of merchantability or fitness for a particular purpose, and in lieu of any other obligation or liability on the part of the seller whether a claim is based upon negligence, breach of warranty, or any other theory or cause of action. In no event shall seller be liable for any consequential, incidental, indirect, special or punitive damages of any kind. For purposes of this paragraph, the equipment warranted shall not include equipment, parts, and work not manufactured or performed by seller. With respect to such equipment, parts, or work, seller's only obligation shall be to assign to purchaser the warranties provided to seller by the manufacturer or supplier providing such equipment, parts or work. No equipment furnished by seller shall be deemed to be defective by reason of normal wear and tear, failure to resist erosive or corrosive action of any fluid or gas, purchaser's failure to properly store, install, operate, or maintain the equipment in accordance with good industry practices or specific recommendations of seller, including, but not limited to seller's installation and operation manuals, or purchaser's failure to provide complete and accurate information to seller concerning the operational application of the equipment.
1.2 Hazard statements
The symbols and hazard statements below may appear in Peerless installation and operating instructions, safety instructions and service instructions.
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious personal injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious personal injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate personal injury.
The hazard statements are structured in the following way:
SIGNAL WORD
Description of the hazard
Consequence of ignoring the warning
• Action to avoid the hazard.
1.3 Notes
The symbols and notes below may appear in Peerless installation and operating instructions, safety instructions and service instructions.
Observe these instructions for explosion-proof products.
A blue or gray circle with a white graphical symbol indicates that an action must be taken.
A red or gray circle with a diagonal bar, possibly with a black graphical symbol, indicates that an action must not be taken or must be stopped.
If these instructions are not observed, it may result in malfunction or damage to the equipment.
Tips and advice that make the work easier.
1.4 Target group
These installation and operating instructions are intended for professional installers and operators of the product.
We recommend that installation be carried out by skilled persons with technical qualifications required by the specific legislation in force.
1.5 General safety warnings
DANGER
Electric shock Death or serious personal injury
- The electrical installation must be carried out by a qualified electrician in accordance with local regulations and the manuals provided with the electrical accessories.
- Before starting any work on the product, make sure that the power supply has been switched off and that it cannot be accidentally switched on.
- Never do maintenance work on the pump when it is connected to the power supply.
Automatic startup Death or serious personal injury
- Before any inspection, maintenance, service or repair of the product, make sure that the motor controls are in the "OFF" position, locked and tagged.
- Pumping equipment, especially fire pumps, can start up at any time. It is imperative to isolate the engine before doing any maintenance work. Switch off the main power supply, remove fuses, secure fuel lines, apply lock-outs where applicable, and affix suitable isolation warning signs to prevent inadvertent re-connection.
- Isolate the fuel supply to the engine before working on any part of the fuel supply or control system.
- Disconnect the batteries by removal of the negative terminal connector.
- Do not place tools on or near the batteries. This could result in a short circuit.
- Inspect all cables for damage or signs of failure and replace immediately if damaged.
Hazardous and flammable fumes Death or serious personal injury
- Never refuel the engine when it is running or is still hot from recent running.
- Avoid breathing fuel fumes when refueling the product, especially if the product is installed in an enclosed pump room. Maintain maximum ventilation to clear fumes quickly.
- Do not start the engine while fuel fumes remain evident or may be present.
- Battery gasses are hazardous and flammable. The battery area must be well ventilated to clear these gasses quickly.
- Exhaust gases are hazardous and may contain carbon monoxide and other poisonous gasses. The exhaust system must be maintained free from leaks and directed to discharge in a safe area.
Large openings Death or serious personal injury
- If the site is left unattended before the installation is complete, all openings must be covered to prevent entry of children, animals, stones or any other foreign objects.
- Use unbreakable covers that cannot be removed without tools.
Hot surface Death or serious personal injury
- Do not allow skin contact with pump components that have heated above 108 °F (42 °C).
- Wear protective gloves when necessary to touch hot surfaces. Surfaces may remain hot after unit has been shut off.
- Ensure that drain water from stuffing box is cool before contact. The stuffing box and bearing bracket areas on the pump can become hot in the event of a malfunction or maladjustment.
Hot or freezing surfaces Death or serious personal injury
- Protect persons from contact with hot or freezing components or auxiliary heating supplies.
- If complete protection is not possible, limit access to maintenance staff only, with clear visual warnings to those entering the immediate area.
FM
E n g li s h
U
Chemical hazard Death or serious personal injury
- When the pump handles hazardous liquids, avoid exposure to the liquid. Limit personnel access and ensure that operators are properly trained. If the liquid is flammable and/or explosive, strict safety procedures must be required.
- Gland packing must not be used when pumping hazardous liquids.
Overhead load Death or serious personal injury
- Do not lift components by the lifting lugs or eye bolts on the motor. Unload and handle components with a sling.
- Complete pump units must be lifted by fork truck from beneath the pump's steel base.
- When manually lifting pump components, use proper lifting techniques and never bend at the waist. Keep the component close to your body with your back straight, and lift with your legs.
Crushing of hands Death or serious personal injury
- Do not work under a suspended object unless you have taken precautions to stop its fall in the event of sling failure. Do not place hands under a component in such a way that it could fall on your hands if it were dropped.
Sharp and moving machine parts or blades.
Death or serious personal injury
- Ensure an approved coupling guard is in place before operating the product. Failure to observe this warning could result in injury to operating personnel.
- Wear appropriate protective safety equipment including gloves when handling parts and components.
- Read and follow all recommended guarding and safety instructions for accessories, if any.
Rotating equipment and sharp objects Death or serious personal injury
- Do not place fingers, hands, arms, etc. into any opening (such as the air relief valve hole).
- Do not wear loose or frayed clothing or jewelry that could catch on equipment or become trapped in the equipment.
- Do not touch the impeller or other rotating elements, if rotated, this can cause severe injury. The area between the stuffing box and bearing bracket is left open to allow for inspection and adjustment of packing.
Never place your hands or fingers into this area while the equipment is in operation. Do not wear loose clothing, long hair, or jewelry around this area.
WARNING
Excessive noise Death or serious personal injury
- If the operating noise level of the product exceeds local code or safe levels (over 85 dBA), the product must be installed in a controlled access area. Provide ear protection to persons authorized to be in this area.
- Fire pumps can start unexpectedly at any time. Ear protection should be carried by, or readily available to, all persons authorized to be in the pump room with these pumps. Observe health and safety regulations limiting exposure of personnel to excessive noise.
Explosive environment Death or serious personal injury
- Do not store lubricants or other volatile substances near the engine. Store these in a designated, suitable storage enclosure.
Partial decomposition of fluoro-elastomers (when fitted) will occur if equipment reaches temperatures above 400
°F (205 °C).
For applications involving potentially explosive atmospheres, contact Peerless for more information.
Avoid rapid temperature change in the pumped liquid.
Thermal shock from sudden temperature changes can damage pump components.
Pumps are not designed to accept external loads from belt-driven arrangements. A separate jackshaft with a bearing structure suitable for belt loading is required.
Do not remove or paint over any safety labels. If labels are lost or damaged, contact your Peerless representative for replacement.
Do not use gland packing when pumping hazardous liquids.
Do not use the pump as a support for pipes. Do not mount expansion joints, so that their force, due to internal pressure, acts on the pump flange, without written authorization from Peerless.
1.6 Material safety data sheet
Material safety data sheets (MSDS) are not supplied with pumps unless required. You may request them from your Peerless representative.
2. Receiving the product
2.1 Unpacking the product
Do not unpack more than required to verify that the equipment is complete and undamaged unless installed immediately. Look through all packaging material that is to be discarded to ensure no parts or instructions are discarded accidentally. In some shipments, small boxes containing additional parts are bound to pump skids.
Leave small parts in their shipping container until installation. While unpacking, make sure that pump unit accessories are clearly marked indicating the exact pump unit they should be used with.
FM
E n g lis h (U
2.2 Inspecting the product
The product must be inspected after transport and before installation.
To complete the inspection, follow the steps below:
1. Check the product for transport damage. Contact the transporter immediately in case of damage.
2. Check that the delivered products correspond to the order.
3. Check the positions and sizes of fittings.
4. Retighten various connections, as they may have become loose during transport.
2.3 Transporting the product
The pump has been prepared for shipment at the factory so as to minimize potential damage due to handling and transport.
WARNING
Crushing hazard Death or serious personal injury
- Make sure all persons stand clear of the load and the lifting equipment while product is lifted, lowered, loaded and unloaded. Do not allow anyone to stand on, under, or near the load.
Do not subject the pump to excessive g-forces during handling or transport.
2.4 Scope of delivery
A typical shipment will include:
• one skid with the fire pump and the driver mounted on the base plate
• one skid with the controller and accessories, if any
• installation and operating instructions.
Refer to the original order in case of questions about shipping, for example, special arrangements with third-party vendors for shipping and storage.
3. Installing the product
3.1 Factory support
For Engineered to Order (ETO) products, Peerless recommends that you invite a Peerless service engineer to supervise the installation and startup. This is to ensure a proper installation.
Peerless recommends that you review the instructions provided with the pump.
3.2 Location
Install the product in a location that meets the following requirements:
3.2.1 Minimum space
Always allow sufficient accessibility space for maintenance and inspection. Provide a clearance of 24 inches (610 mm) with ample head room for use of overhead lifting equipment strong enough to lift the product.
3.2.2 Seismic analysis
When the pump is located in a seismically active area or in certain critical installations, ensure that the pumps, supports, and accessories are earthquake-resistant. The design specifications for earthquake resistance vary depending on the geographical area and the class of the equipment. The class of the equipment depends on defining how critical is the survival of the equipment, the characteristics of the structure's response to accelerations, and the foundation supporting the pump.
E n g li s h
U
If a seismic analysis is required, please refer to the governing bodies recommended for grouting and foundation requirements.
The customer must supply complete specifications for earthquake- resistance requirements including seismic criteria, acceleration, magnitudes, frequency spectrum, location and direction relative to the pump and qualification procedure.
3.3 Mechanical installation
3.3.1 Recommendation for pump foundation
All rotating equipment generates vibrations when turning at high speeds. Proper installation and anchorage of the pumps and installation accessories are critical to limit vibrations and achieve reliable installation. To ensure acceptable vibration levels in the field, all parts of the system must be sufficiently stiff and firmly anchored to minimize vibrations:
This applies for pumps above 13 hp (10 kW).
• The foundation and concrete should be of adequate strength to support the weight of the pump including accessories, the weight of the liquid passing through the pump, and the forces generated by the pump.
• The mass of the concrete foundation should be a minimum of three to five times the mass of the supported equipment and should have sufficient rigidity to withstand the axial, transverse, and torsional loadings generated by these machines.
• The foundation should be 5.9 in (15 cm) wider than the base plate for pumps up to 469 hp (350 kW) and 9.8 in
(25 cm) wider for larger pumps.
• The concrete used in the foundation should have a minimum tensile strength of 362 lbf/in2 (250 N/cm2).
• Always use a non-shrink epoxy grout to fasten the pump base plate to the foundation.
3.3.2 Pump foundation
Large pumps will be mounted on a steel base anchored to two concrete pillars.
Install the pump permanently on a firm, raised concrete foundation of sufficient size to dampen any vibration and prevent any deflection or shaft misalignment. The foundation may float on springs or be a raised part of the floor.
Proceed like this:
1. Pour the foundation without interruption to 0.75- 1.5 in
(20-40 mm) below the final pump level. Leave the top of the foundation rough. Then clean and wet it down.
2. Scour and groove the top surface of the foundation before the concrete sets to provide a suitable bonding surface for the grout.
3. Place anchor bolts in pipe sleeves for positioning allowance.
4. Allow enough bolt length for grout, base flange, nuts, and washers.
5. Allow the foundation to cure several days before proceeding to install the pump.
Indianapolis, IN 46202
E n g lis h (U
3.3.2.1 Foundation, grout and anchor bolt installation
6 9
5. After pump alignment has been established, put nuts on the anchor bolts and tighten them just enough to keep the base plate from moving.
6. Construct a formwork around the concrete foundation and pour grout inside the base plate. The grout will compensate for the uneven foundation, distribute the weight of the pump, and prevent shifting.
Use an approved, non-shrinking grout.
7. Allow for the grout to cure fully before proceeding with torquing the anchor bolts and the pipe connections.
8. After the grout has thoroughly hardened, check the anchor bolts and tighten them if necessary. Recheck the pump alignment after tightening the anchor bolts.
Fig. Foundation, grout, and anchor bolt installation
Position Description
1 Finished grouting
2 0.75-1.25 in (19-32 mm) allowance for grout
3 Formwork
4 Pipe sleeve
5 Washer
6 Base plate
7 0.2-0.4 in (5-10 mm)
8 Lug
9 Grout
10 Wedges or shims left in place
11 Top of foundation
3.3.3 Positioning the pump
When the raised concrete foundation has been poured and allowed to set, proceed as follows:
WARNING
Overhead load Death or serious personal injury
- Never attempt to lift the entire pump by means of eyebolts screwed into the driver mounting holes. This attachment point may not be strong enough to carry the weight of the entire unit.
Adequate space above the installation site must be provided to accommodate rigging and the longest section of the pump to be handled.
1. Lower the base plate over the anchor bolts and rest it on loose adjustment wedges or shims placed near each anchor bolt and at intervals not exceeding 24 in (610 mm) along each side.
2. Place the shims or wedges so that they raise the bottom of the base plate 0.75-1.25 in (19-32 mm) above the foundation, allowing clearance for grout.
3. Level the pump shaft, flanges, and base plate using a level, adjusting the wedges or shims, as required.
If the pump is equipped with jacking screws, use them to lift the pump and adjust the wedges or shims.
4. Make sure that the pipes can be aligned to the pump flanges without placing any strain on either flange.
T M
Fig. Raising the base plate with wedges or shims
3.3.4 Dowel pins
To comply with the Hydraulic Institute recommendations, all pumps should be dowelled.
The pump feet can be drilled for dowels at the factory or in the field. Doweling the pump feet accomplishes the following:
• Prevents lateral movement.
• Eases realignment if the pump is removed from the base.
• Temporarily holds the pump if the hold-down bolts loosen.
3.3.5 Installing dowel pins
If dowel holes were not drilled in the pump feet at the factory then determine the dowel and hole size by measuring the diameter of the mounting hole in the pump foot and subtract
3/8".
Peerless recommends the use of straight dowel pins as described in the following steps:
1. Check the coupling alignment and correct if necessary.
2. Drill holes in opposite pump feet. The holes should be 1/64" smaller than the dowel diameter.
3. Clear the debris.
4. Ream the holes in the pump feet and base to the correct diameter. Allowing for a push fit.
5. Clear the debris.
6. Insert the dowels to a depth that leaves sufficient thread to attach a nut.
7. Thread the nuts onto the dowel and tighten.
T M
3.4 Installation preparation
3.4.1 Engine preparation
The following installation requirements help to ensure safe and efficient operation of a pumping unit driven by a diesel engine:
1. Ensure that the operator is familiar with the installation and service manual supplied with the engine.
2. Ventilate the area around the engine to keep the ambient temperature as low as possible. With 60 °F (15.6 °C) as a data point, every Δ 10 °F (Δ 6 °C) rise in temperature reduces the horsepower of the engine by approximately 1%.
3. Provide adequate air for efficient combustion.
4. Provide the engine with an efficient exhaust system so that the combustion gasses discharge with a minimum of back pressure.
5. Ensure that the fuel system is of adequate capacity and meets codes and regulations.
6. Provide ample space to access the engine for maintenance.
7. Provide correct rotation of the pump. Engine rotation is determined at the factory, and no change to engine rotation can be made in the field.
3.5 Mechanical installation
3.5.1 Pipes and connections
3.5.1.1 Inlet pipe
The inlet pipe must be installed in a manner that minimizes pressure loss and permits sufficient liquid flow into the pump during starting and operation.
At no point must the diameter of the inlet pipe be smaller than that of the pump inlet port.
Observe the following precautions when installing the inlet pipe:
• Run the inlet pipe as direct as possible, and ideally, make sure the length is at least ten times the pipe diameter. A short inlet pipe can be the same diameter as the inlet port. A long inlet pipe must be one or two sizes larger than the inlet port, depending on the length, and with a reducer between the pipe and the inlet port.
• Use an eccentric reducer, with the tapered side down.
• If possible, run a horizontal inlet line along an even gradient.
We recommend a gradual upward slope to the pump operating in suction lift conditions, and a gradual downward slope operating in positive inlet pressure conditions.
• Avoid any high points, such as pipe loops, as this may create air pockets and throttle the system or cause erratic pumping.
• Install a gate valve in the inlet line to be able to isolate the pump during shutdown and maintenance, and to facilitate pump removal. Where two or more pumps are connected to the same inlet pipe, install two gate valves to be able to isolate each pump from the pipe.
Always install isolation valves in positions that prevent air pockets.
Do not use globe valves, particularly when NPSH is a critical operating factor.
• During pumping operation, the valves on the inlet line must always be fully open.
• Install properly sized pressure gauges in the tapped holes on the pump inlet and outlet flanges or pipes
Pressure gauges will enable the operator to monitor the pump performance and determine whether the pump conforms to the parameters of the performance curve
If cavitation, vapor binding, or other unstable operating situations occur, the pressure gauges will indicate with wide fluctuation in the inlet and outlet pressures.
3.5.1.2 Vibration dampers
To prevent the transmission of vibrations to foundations and surrounding structures, isolate the pump and foundation from connected structures by means of vibration dampers. The selection of the correct vibration damper requires the following data:
• forces transmitted through the damper
• motor speed(s)
• required dampening in %.
The selection of a vibration damper differs from installation to installation. In certain cases, a wrong damper may increase the vibration level. Peerless recommends that the vibration dampers be sized by the supplier. If you install the pump on a foundation with vibration dampers, always fit expansion joints on the pump flanges.
Install expansion joints on the pump flanges to prevent the pump from "hanging" in the flanges.
3.5.1.3 Inlet pipe
The inlet pipe must be installed in a manner that minimizes pressure loss and permits sufficient liquid flow into the pump during starting and operation.
At no point must the diameter of the inlet pipe be smaller than that of the pump inlet port.
Observe the following precautions when installing the inlet pipe:
• Run the inlet pipe as direct as possible, and ideally, make sure the length is at least ten times the pipe diameter. A short inlet pipe can be the same diameter as the inlet port. A long inlet pipe must be one or two sizes larger than the inlet port, depending on the length, and with a reducer between the pipe and the inlet port.
• Use an eccentric reducer, with the tapered side down.
• If possible, run a horizontal inlet line along an even gradient.
We recommend a gradual upward slope to the pump operating in suction lift conditions, and a gradual downward slope operating in positive inlet pressure conditions.
• Avoid any high points, such as pipe loops, as this may create air pockets and throttle the system or cause erratic pumping.
• Install a gate valve in the inlet line to be able to isolate the pump during shutdown and maintenance, and to facilitate pump removal. Where two or more pumps are connected to the same inlet pipe, install two gate valves to be able to isolate each pump from the pipe.
Always install isolation valves in positions that prevent air pockets.
Do not use globe valves, particularly when NPSH is a critical operating factor.
• During pumping operation, the valves on the inlet line must always be fully open.
• Install properly sized pressure gauges in the tapped holes on the pump inlet and outlet flanges or pipes
E n g li s h
U
Indianapolis, IN 46202
X
E n g lis h (U
Pressure gauges will enable the operator to monitor the pump performance and determine whether the pump conforms to the parameters of the performance curve
If cavitation, vapor binding, or other unstable operating situations occur, the pressure gauges will indicate with wide fluctuation in the inlet and outlet pressures.
3.5.1.4 Outlet pipe
• A short outlet pipe can be the same diameter as the pump outlet port. A long outlet pipe must be one or two sizes larger than the outlet port, depending on the length.
• It is best to use long horizontal outlet pipes.
• Install a non-return valve to protect the pump from backflow and excessive backpressure. The check valve should be installed between the isolation valve and pump.
Pump backspin and hydraulic shock can cause severe damage to the pump and driver.
• Install a gate valve near the outlet port to be able to isolate the pump during shutdown and maintenance, and to facilitate pump removal.
• Any high points in the outlet pipe may entrap air or gas and thus reduce pump operation.
Operating pumps against a closed valve will cause an increase in pressure and power.
If an increaser is used on the outlet pipe to increase the pipe size then it should be placed between the non-return valve and the pump. If expansion joints are used then they should be placed between the pipe support or anchor and the non-return valve.
3.5.1.5 Nozzle load
The pipes should be aligned with the pump nozzles to minimize pump nozzle loads. Refer to ANSI/HI 9.6.2 for assessment of applied nozzle loads.
3.5.2 Impeller clearance
To achieve optimal performance and service life, the impeller clearance must be centered in the volute. Pumps are shipped from the factory with the impeller clearance set.
3.5.3 Alignment
Misalignment of the pump and driver can cause product failure.
Reliable, trouble-free, and efficient operation requires accurate alignment of pumps and drivers mounted on a common base plate.
Shipping and installation can alter the factory alignment. Therefore, check the alignment after:
• mounting.
• the grout has hardened.
• the foundation bolts are tightened or adjusted.
• the pipes to the product are connected.
• pump, driver or base plate is moved.
To check alignment, mount a dial indicator to measure shaft movement before and after tightening the flange bolts.
• excessive force on the pipes distorting or shifting the machine.
• settling of the building.
• shifting of pump or driver on the base plate or foundation.
Misalignment may be the cause of:
• noisy pump operation
• vibration
• premature bearing failure
• excessive coupling wear.
3.5.3.1 Checking the alignment
The procedure for verifying the alignment of a pump and driver connected by a flexible coupling, mounted on a common base plate are:
1. Disconnect the coupling halves.
2. Set the coupling gap to the recommended alignment dimension.
3. Test for parallel and angular alignment with a straight edge and feeler gauge.
4. An alternate test for parallel and angular alignment may be made as follows with a dial indicator mounted:
• Scribe the index lines on the coupling halves or set the indicator dial to zero.
• Slowly turn both coupling halves so that the index lines match.
• Observe the dial reading to determine whether pump or driver
• Acceptable parallel and angular alignment occur when total indicator reading (complete turn) does not exceed limits shown on either a tag or decal on the unit or on the unit outline drawing.
5. When a significant operating temperature differential exists between the pump and driver (i.e. a steam turbine driver with a pump handling cold liquid), thermal growth causes the hotter component to rise. You can compensate for this by initially setting the hotter unit 0.003 to 0.005 in. (0.076 to 0.127
mm) lower. When both units are at normal operating temperature, make a final check and correct the alignment if necessary.
Check for correct electric motor rotation while coupling halves are disconnected.
6. Correct for excessive parallel and angular misalignment by slightly shifting the leveling wedges under the base plate. Tap lightly (in or out) with a hammer. Retest alignment each time after you shift a wedge.
7. It may be necessary to change the shims under the pump or driver or even relocate the pump or driver on the base plate.
Make such changes only after you are sure that shifting the wedges do not achieve alignment.
8. If wedges are shifted or shims are shifted, recheck the pipe alignment and the level of the shafts.
Y
To facilitate accurate field alignment, we do not dowel the pumps or drivers on the base plates before shipment.
If the product does not stay in alignment after installation, possible causes of misalignment are:
• setting, seasoning or springing of the foundation.
Fig. Angular misalignment
T M
3.5.3.3 Coupling gap and maximum misalignment, KTR
ROTEX
size E distance
Max.
parallel
Max.
angularity Max. axial
[in (mm)] [in (mm)] [in (mm)] [in (mm)]
Fig. Parallel misalignment 14 0.51 (13)
0.006
(0.15)
19 0.63 (16) 0.007
(0.18)
1.1 (28) -0.02 (-0.5) + 0.04 (1)
1 (25) -0.02 (-0.5) + 0.05 (1.3)
24 0.71 (18) 0.008 (0.2) 0.08 (2) -0.02 (-0.5)
+ 0.06 (1.5)
28 0.79 (20.1) 0.009
(0.23)
0.09 (2) -0.03 (-0.8)
+ 0.06 (1.5)
38 0.94 (23.9) 0.01 (0.25) 0.09 (2) -0.03 (-0.8)
+ 0.07 (1.8)
Fig.
Using a dial indicator to check alignment
42 1.02 (25.9) 0.011
(0.28)
48 1.1 (27.9) 0.013
(0.33)
1 (25) -0.04 (-1) +
0.08 (2)
1.1 (28) -0.04 (-1) +
0.08 (2)
3.5.3.2 Coupling gap settings, Falk/Clarke/Dodge
55 1.18 (30)
0.014
1.1 (28)
(0.36)
-0.04 (-1) +
0.09 (2.3)
Coupling Max.
Parallel Angularity Weight Torque 65 1.38 (35.1)
0.015
1.1 (28)
(0.38)
-0.04 (-1) +
0.1 (2.5) [in
(mm)] [in (mm)] [lb (kg)]
[lb-in
(Nm)]
75 1.57 (39.9) 0.017
1.1 (28) (0.43)
-0.06 (-1.5)
+ 0.12 (3) 0.006
(0.15)
0.003
(0.08)
4.2
(1.9) 460 (52) -0.06 (-1.5)
1.2 (30) + 0.15 (3.8)
0.008
(0.2)
0.004
(0.1)
12 (5.4)
(435)
110 2.17 (55.1) 0.02 (0.51) 1.2 (30) -0.08 (-2) +
0.17 (4.3)
0.008 0.005
16 (7.3)
125 2.36 (59.9) 0.021
(0.53)
1.2 (30)
0.18 (4.6)
140 2.56 (65) 0.022
1.2 (30)
(0.56) 0.2 (5.1)
160 2.95 (74.9) 0.022
-0.1 (-2.5) +
(0.56) 0.22 (5.6)
180 3.35 (85.1)
0.024
-0.12 (-3) +
(0.61) 0.25 (6.4)
Fig. E (Distance)
E
P
P
T M g li s h
U
S
RPM
0.006
0.003
5.7
90 1.77 (45) 0.018
1.2 (30) + 0.13 (0.46)
(3.3)
(0.15) (0.08) (2.6) (149) -0.06 (-1.5)
0.006 0.003 7.4 2200 100 1.97 (50)
0.019
(0.48)
(0.15) (0.08) (3.4) (249)
(0.2) (0.13) (684)
0.008 0.005 23 8800
(0.2) (0.13) (10.4) (994)
0.008 0.006 39 18150
(0.2) (0.15) (17.7) (2051)
0.008 0.007 56 33000
(0.2) (0.18) (25.4) (3729)
0.01 0.008 93 55550
(0.25) (0.2) (42.2) (6276)
0.01 0.009 120 82500
(0.25) (0.23) (54.4) (9321)
0.011 0.01 179 121000
(0.28) (0.25) (81.2) (13671)
0.011 0.012 266 176000
(0.28) (0.3) (120.7) (19885)
0.011 0.013 392 253000
(0.28) (0.33) (177.8) (28585) g lis h (U
3.5.3.4 Aligning the engine drivers
Engine-driven units are typically supplied with the pump and drive on a common base plate. For units that are supplied separately, contact Peerless.
If a universal drive is installed, contact the manufacturer for instructions.
1. Check the angular alignment between the pump and engine shafts.
2. Check the parallel alignment between the pump and engine shafts.
3. When coupled, verify that the angle between the pump and drive shaft is less than three degrees. For assistance, contact Peerless.
4. Verify that at least 3/4 of the key is engaged with the coupler and shaft.
3.5.4 Lubrication, priming and cooling systems
If supplied, please refer to additional documents attached to the pump, or contact Peerless.
3.6 Electrical connection
All electrical connections must be carried out by a qualified electrician in accordance with local regulations.
DANGER
Electric shock Death or serious personal injury
- Switch off the power supply before you start any work on the product.
- Make sure that the power supply cannot be switched on accidentally.
Locate the electrical conduit and boxes so as to avoid obstruction of the pump.
Check speed versus torque requirements during the starting phase of a pump against the speed versus torque curve of the driving motor.
In order to accelerate the pump up to rated speed, the driver should be capable of supplying more torque at each speed than required by the pump. In general, this condition is easily attainable with standard induction or synchronous motors, except under certain conditions when a motor with high pull-in torque may be required, such as high specific speed pumps over 5000 US units (100 metric units) or reduced voltage startup.
To achieve a smooth start for the pumping equipment, consider connecting autotransformers to the starting panel or using solid-state starters. These provide a gradual increase in voltage up to rated voltage ensuring even acceleration.
Control, monitoring and alarm equipment
All control and alarm systems should be checked for correct installation and functioning in accordance with the manufacturer's instructions. All alarm point settings should be checked.
Stopping the unit/reverse runaway speed
A sudden power and/or discharge valve failure during pump operation against a static head will result in a flow reversal, and the pump will operate as a hydraulic turbine in a direction opposite to that of a normal pump operation. If the driver offers little resistance while running backward, the rotational speed may approach the pump specific speed. This condition is called runaway speed and causes mechanical problems. Contact Peerless for aid in preventing this condition.
3.7 Control, monitoring, and alarm equipment
Check control and alarm systems for correct installation and function according to the manufacturer's instructions.
Check all alarm point settings.
3.7.1 Stopping the unit/reverse runaway speed
A sudden power and/or discharge valve failure during pump operation against a static head will result in a flow reversal, and the pump will operate as a hydraulic turbine in a direction opposite to that of a normal pump operation.
If the driver offers little resistance while running backward, the rotational speed may approach the pump specific speed.
4. Preparing the pump for startup
4.1 Lubricating the pump
Before attempting to start the pump, check the following items:
• lubrication fitting at packing, if applicable
• lubrication for pump bearing
• lubrication of the driver
• oil-cooling connections for the driver, if applicable
• coupling, refer to the manufacturer's instructions. Good practice includes the following:
• Keep lubricant clean, and use a dust-tight cover on the storage container.
• Use the oldest lubricant first.
• Clean the pump lubricant fittings before re-lubricating with grease.
• Use clean dispensing equipment.
• Remove 0.25 in (6.4 mm) of drain pipe plug on the bottom outside of the bearing housing cover. Inject clean, new grease forcing out the old grease through the drain opening.
• Start and run the pump for a short time to eject any excess grease. Reinstall 0.25 in (6.4 mm) of pipe plug.
Wipe off any ejected grease.
• Use the proper amount of lubricant. Too much lubricant results in churning, unnecessary power consumption, rapid heating to a high temperature and inadequate lubrication.
Normal bearing temperatures vary with the seasons and environment and may range from 0 to 250 °F (-18 to 121
°C). A continuous rise from the established, normal operating temperature indicates trouble and probable failure of the bearing. Shut down the pump immediately.
4.2 Checking rotation
Electric shock Death or serious personal injury
- Switch off the power supply before you start any work on the product.
Three-phase motor shaft rotation can be reversed by switching any two of the three power leads.
Do not attempt to switch any leads in a single-phase motor to change the direction of rotation. The rotation of most single-phase motors is determined by internal wiring and cannot be changed easily.
1. Disconnect the power supply.
2. Lockout-Tagout the power supply.
3. Disconnect the coupling from the motor and pump shaft. Motor shaft spins without driving or contacting the pump shaft.
4. Rotate the motor shaft by hand in both directions.
Verify that the motor spins without binding.
5. Momentarily energize the motor.
Verify that the motor spins in the direction indicated on the pump volute.
6. Install the coupling and guards.
4.3 Guards
Moving machine parts or blades Death or serious personal injury
- Guards must not be removed while the pump is operational. Ensure an approved coupling guard is in place before operating the pump.
Refer to the accessory manufacturer's safety instructions.
4.4 Flushing the system
Before the pump is installed, we recommend that you clean the
Tightly pressed packing will result in burnt packing and scoring of the shaft or shaft sleeve.
The stuffing box should slowly leak fluid, 40-60 drops per minute, during operation. When the leak can no longer be controlled by adjusting the stuffing box gland, add one additional ring of packing and ensure the gland is loose.
When the leak can no longer be controlled, all packing rings must be replaced.
• The stuffing box is packed at the factory.
• Each ring is cut to the proper length.
The end of the rings must come together and not overlap.
• The rings are placed in the stuffing box so that the joints of the packing rings are staggered.
• The stuffing box is furnished with a lantern or seal ring.
• The box has a tapped connection for grease lubrication, if applicable.
- 3 oz. (89 mL) of grease must be injected into the stuffing box every 24 hours of operation.
Automatic grease seal lubrication systems can be installed as an accessory.
After the stuffing box housing and stuffing box gland reach approximately the same temperature as the pump parts, the running-in of the stuffing box gland has been completed. If the stuffing box leaks too much, tighten it slightly and evenly while the pump is running. To ensure continuous lubrication, a few drops should always drip from the stuffing box to protect the packing or shaft sleeve against damage. See 4.7.1 Recommended packing for recommendations for leakage rate. If the pump is to be left idle for a long period of time, we recommend that you replace the packing before starting the pump.
4.7.1 Recommended packing
Recommended stuffing box packing arrangements for use with water:
system to remove debris, for example, stubs of welding rod, welding slag, and loose scale. Protect the pump and other sensitive parts with startup strainers.
4.5 System decontamination
After the system has been flushed to remove debris, determine if the system needs to be decontaminated. If the system needs to be decontaminated, it must be done before priming and filling the pump.
4.6 Priming
The pump should not be run unless it is completely filled with liquid, as there is danger of damaging some of the pump components.
If the system has suction pressure, follow these steps:
1. Bleed all air from the pump casing and suction pipe by the opening of the automatic relief valve at the top of the pump.
2. Rotate the shaft a few times, if possible, to evacuate any air trapped inside the impeller passages.
4.7 Stuffing box
The stuffing box gland must be loose when the pump is first put into operation
Inlet pressure range
6.0 - 100 psi (0.41 -
6.9 bar)
100 - 175 psi (6.9 -
12 bar)
175 - 250 psi (12 -
17 bar)
Packing shaft/ sleeve
PTFE braided graphite synthetic- lattice
Continuous carbon filament yarn, braided lattice packing containing colloidal graphite
Continuous carbon filament yarn, braided lattice packing containing colloidal graphite
E n g li s h
U
Leakage rate
60 drops/minute
1/3 pint/minute (0.16 liters/minute)
1 pint/minute (0.47 liters/minute)
4.8 Starting up the product
4.8.1 Starting the pump
1. Open the inlet valve completely, and close the outlet valve completely.
2. Switch the power supply on.
3. Start the pump.
4. Immediately make a visual check of the pump and inlet pipe.
5. Allow the pump to ramp up to full speed.
6. Slowly open the outlet valve until the operational flow is achieved.
7. Check the outlet pipe for leaks.
8. Open the isolating valves for the pressure gauges.
9. Record the pressure readings.
10. Verify that the pump performance is within the tolerance of the pump performance curve.
4.8.1.1 Air in the system
Entrained air reduces pump total head and flow rate.
Use an eccentric reducer on the inlet pipe.
Return lines into tanks should terminate a minimum of two pipe diameters below the low liquid level.
4.8.1.2 Checking the driver lubrication
Before running the drivers either separately or connected to the pump:
1. Follow the driver manufacturer instructions for lubrication requirements.
2. Ensure that the grease-lubricated bearings in the driver have been properly greased with the grade of grease recommended by the driver manufacturer.
4.8.1.3 Driver settings
Refer to the manufacturer's instructions.
4.8.1.4 Pump performance
Initial field test data becomes a valuable baseline for future troubleshooting and maintenance. It may not be possible to match the factory performance due to differences in system resistance.
Once the pump is operating, verify the following:
1. The pipe connections are tight, and no leaks are present.
2. The following attributes match the pump nameplate:
a. operating speed
b. flow rate
c. inlet and outlet pressure
d. power input, P1.
5. Storing and handling the product
5.1 Short-term storage
Standard factory packaging is suitable for protection during shipment and during covered storage at a job site for a short period between installation and startup. The preservatives applied at the factory have an effective life of two to three months from the date of shipment from the factory, depending on the severity of the environment in which the equipment is exposed. For international destinations, this will vary depending on the seaworthiness of export boxing.
E n g lis h (U
5.1.1 Controlled storage
Storage facilities should be maintained at an even temperature with a relative humidity lower than 50%, and little or no dust. Inspect and recoat the equipment periodically with water displacement rust inhibitor, vapor phase inhibitor, or rust preventive coating.The equipment must be inspected weekly to ensure that all preservatives are intact, and internals are protected.
5.1.2 Uncontrolled storage
For uncontrolled storage periods of three months or less, inspect the equipment weekly to ensure preservatives are intact and internal parts are protected.
Preparing the product for uncontrolled storage
• Periodically inspect and recoat the equipment with rust and vapor phase corrosion inhibitors.
• Seal all pipe threads and flanged pipe covers with tape.
Place an adequate amount of desiccant near the center of the pump.
• If the pump is assembled, place and securely fasten additional desiccant in the outlet of the pump.
• Cover the equipment with black polyethylene or equivalent, with a minimum thickness of 0.006 in
(0.15 mm).
• Provide a ventilation hole approximately the size of a small coin.
• Provide protection from direct exposure to the environment.
• If applicable, connect space heaters on equipment such as motors, engines or controls.
5.1.3 Short-term storage
• The pump and equipment, as shipped, have adequate protection for short-term storage for up to three months.
• If the product is not to be installed and operated immediately after receiving it, store it in a clean, dry area at a moderate ambient temperature.
• For packed-type pumps, the packing glands may be left on the pump shaft and securely fastened in position. All exposed machined surfaces should be thoroughly coated with a film of rust preventative material.
• For packed-type pumps, the stuffing box packing must be removed and stored in a sealed plastic bag. Seal the end of the stuffing box with rolled vapor phase inhibitor paper and seal with weatherproof tape.
• Rotate the shaft by hand periodically, at least monthly, to coat the bearing with a lubricant to retard oxidation and corrosion.
• Make sure the pump cannot roll or fall over.
• Follow the motor manufacturer's storage recommendations where applicable.
5.1.4 Long-term storage
• Long-term storage protection provided by the factory does not extend the warranty in any manner.
• The warranty is valid only if the equipment is properly handled and stored.
• In case of storage up to six months or longer, the pump must be protected against heat and moisture as described in the previous sections.
• Periodically, at least monthly, manually rotate the shaft to coat the bearing with a lubricant to retard oxidation and corrosion.
• Ensure that the pump cannot roll or fall over.
• Follow the motor manufacturer's storage recommendations where applicable.
• Inspect the pump before putting it into operation. Make sure that the impeller can rotate freely. Pay special attention to the condition of the shaft seals or the packing and O-rings.
5.1.5 Accessories storage
Store accessories according to the manufacturer's instructions.
5.2 Handling the product
When storing and handling the product:
• Use properly sized and rated lifting equipment.
• Handle and lift the product according to the local regulations.
• Ensure that point loads do not occur.
DANGER
Crushing hazard Death or serious personal injury
- Place the product on a level surface to prevent overturning.
If the product is equipped with lifting points, use the points during handling.
6. Product introduction
6.1 Product description
Peerless AEF pumps are horizontal split case fire pumps with appropriate fittings for providing water supply to fire protection systems in buildings, plants, and yards.
6.1.1 Pump components
6.3 Identification
6.3.1 Nameplate
Each pump has a nameplate with the pump's serial number. You will find an example of the pump nameplate in the figure below.
Reference the serial number when contacting Peerless with questions or a service request.
A nameplate can also be…