Attachment C-Drawings~2.pdf
PDF 4 MB Posted
- Attached to
- VRF Cooling System Replacement
- Solicitation number
- S-DASOBO-00017473
- Issued by
- Oregon
About this file
This is a construction document cover sheet and mechanical legend for the VRF Cooling System Replacement project at the Department of Public Safety Standards and Training (DPSST) facility located at 4190 Aumsville Highway SE in Salem, Oregon. The project, dated August 7, 2026, involves the removal of the current building VRF cooling system with two towers in Building E and the installation of a new cooling system, including associated ductwork, testing and balancing, and staff training. The work requires integration with the existing building automation system. The engineering design was prepared by Systems West Engineers (Springfield, OR), with Charlie White serving as Project Manager, and Michael Anderson as the DPSST Facilities Manager serving as the owner's contact. The construction documents are at 100 percent completion stage and include mechanical and electrical drawings with demolition plans, floor plans, details, schedules, and diagrams for both northeast and southeast building sections.
The document provides the sheet index and legend for the mechanical plans, including symbols and abbreviations for various hydronic systems, ductwork types, natural gas, fuel oil, liquefied petroleum gas, chilled water systems, heating water systems, condensate drains, and steam systems at varying pressures. The construction documents are digitally signed by registered Professional Engineer Nate J. Jenkins (License #95772) and expire on June 30, 2027. No pricing, specific quantities, response deadlines, or contract award information is contained within this cover sheet document.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S-DASOBO-00017473-ITB.pdf | ||
| Attachment B-Technical Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NORTH
NORTH
725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com
DATE:
DRAWN:
CHECKED:
PROJECT:
DESIGNED:
OWNER:
MARK DATE DESCRIPTION
SALEM, OREGON
AUGUST 7TH, 2026
S H E E T I N D E X
K E Y P L A NV I C I N I T Y M A P
NOT TO SCALE
NOT TO SCALE
OWNER:
DEPARTMENT of PUBLIC SAFETY STANDARDS and TRAINING 4190 Aumsville Highway SE Salem, OR 97317 Contact: Mr. Michael Anderson Facilities Manager
p. 503.373.7055 michael.anderson@state.or.us
MECHANICAL & ELECTRICAL:
Systems West Engineers
725 A Street Springfield, OR 97477
p. 541.342.7210 www.systemswestengineers.com Contact: Charlie White, PM cwhite@systemswestengineers.com
AREA OF WORK
AREA OF WORK
/1
/2
:3
:4
A
M P
LO
T
T E
D B
Y J
S H
O N
D P
S S
T V
R F
R E
P
LA
C E
M E
N T
STATE OF OREGON
COVER SHEET -
CONTACTS,
VICINITY MAP, SITE
MAP & SHEET LIST
08.07.2026
240024.01
G001
JSH
JSH
NJJ
STATE OF OREGON
DEPARTMENT OF PUBLIC SAFETY
STANDARDS AND TRAINING
100% CONSTRUCTION DOCUMENTS
DPSST VRF REPLACEMENT
D E
P A
R T
M E
N T
O F
P U
B
LI
C S
A F
E T
Y S
T A
N D
A R
D S
A N
D T
R A
IN
IN
G
A um sv ill e H ig hw ay S
E S al em
, O R
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
G001 COVER SHEET - CONTACTS, VICINITY MAP, SITE MAP & SHEET LIST
M001 LEGEND, GENERAL NOTES, & SHEET LIST
M101 DEMOLITION PLANS - NE
M102 DEMOLITION PLANS - SE
M121 FLOOR PLANS - NE
M122 FLOOR PLANS - SE
M501 DETAILS
M601 SCHEDULES
M621 DIAGRAMS
E001 LEGEND, GENERAL NOTES, & SHEET LIST
E101 DEMOLITION PLANS - NE
E102 DEMOLITION PLANS - SE
E121 FLOOR PLANS - NE
E122 FLOOR PLAN - SE
E601 SCHEDULES
© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)
EXPIRES: 06-30-2027
JA NUA RY 14 , 2020
DIGITALLY SIGNED
RE
GI
STERED PROFESSIONALENGINEER# 95772
OREGONN
A
T
E
J . J E NK
I N S
P PP
M E C H A N I C A L L E G E N D
TYPES
DUCTWORK GENERAL
CONTROL SYMBOLS
GENERAL NOTES
SYMBOL ABBREV. DESCRIPTION
HYDRONIC
G(*)
FOS
FOR
LPG
CWS
CWR
HS
HR
CD
CDS
CDR
HRS
HRR
CBR
CBS
GWS
GWR
SMS
SMR
HPS
MPS
LPS
HPR
MPR
LPR
VR
PR
RL
RS
RHG
W
IR
NATURAL GAS (*=SUPPLY PRESSURE)
FUEL OIL SUPPLY
FUEL OIL RETURN
LIQUEFIED PETROLEUM GAS
CHILLED WATER SUPPLY
CHILLED WATER RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
CONDENSATE DRAIN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
HEAT RECOVERY SUPPLY
HEAT RECOVERY RETURN
CHILLED BEAM WATER SUPPLY
CHILLED BEAM WATER RETURN
GEOTHERMAL WATER SUPPLY
GEOTHERMAL WATER RETURN
SNOW MELT WATER SUPPLY
SNOW MELT WATER RETURN
HIGH PRESSURE STEAM >60 psi
MEDIUM PRESSURE STEAM 15 psi-60 psi
LOW PRESSURE STEAM <15 psi
HIGH PRESSURE CONDENSATE RETURN
MEDIUM PRESSURE CONDENSATE RETURN
LOW PRESSURE CONDENSATE RETURN
VACUUM CONDENSATE RETURN
PUMPED CONDENSATE RETURN
REFRIGERANT LIQUID
REFRIGERANT SUCTION
REFRIGERANT HOT GAS
WATER SERVICE
IRRIGATION
DV
BV
BFV
CHV
GV
GBV
PRV
AV
SV
AV
AV
AV
RV
SRV
SSV
TPS
FMS
ABBREV ABBREVIATION
ACH AIR CHANGES PER HOUR
AD ACCESS DOOR
AFF ABOVE FINISHED FLOOR
AFS AUTOMATIC FIRE SPRINKLER
AI ANALOG INPUT
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
AO ANALOG OUTPUT
APD AIR PRESSURE DROP
AWT AVERAGE WATER TEMPERATURE
BAS BUILDING AUTOMATION SYSTEM
BHP BRAKE HORSEPOWER
BOD BOTTOM OF DUCT
BTUH BRITISH THERMAL UNITS PER HOUR
CFH CUBIC FEET per HOUR CFM CUBIC FEET per MINUTE
CMU CONCRETE MASONRY UNIT
CONC CONCRETE
CONT CONTINUATION
CU FT CUBIC FEET
D DEPTH
(D) DEMOLITION
DB DRY BULB
dBa DECIBELS ACOUSTIC
DDC DIRECT DIGITAL CONTROL
DEMO DEMOLITION
DI DIGITAL INPUT
DN DOWN
DO DIGITAL OUTPUT
DP DIFFERENTIAL PRESSURE
DX DIRECT EXPANSION
(E) EXISTING
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
ECM ELECTRONICALLY COMMUTATED MOTOR
EER ENERGY EFFICIENCY RATIO
EFF EFFICIENCY
EG EXHAUST GRILLE
PIPING UP
PIPING DOWN
DIRECTION OF SLOPE
CAPPED PIPE
PIPE REDUCING FITTING:
CONCENTRIC, ECCENTRIC
DIRECTION OF FLOW
DRAIN VALVE WITH HOSE
CONNECTION
UNION
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
GATE VALVE
GLOBE VALVE
BALANCING VALVE /
ECCENTRIC PLUG VALVE
AUTOMATIC CONTROL
VALVE: 2-WAY
AUTOMATIC CONTROL
VALVE: 3-WAY
AUTOMATIC BUTTERFLY VALVE
FLEXIBLE PIPE CONNECTION
WYE STRAINER
BASKET STRAINER
PRESSURE REGULATING VALVE
THREE-WAY BYPASS VALVE
SOLENOID VALVE
RELIEF VALVE
SAFETY RELIEF VALVE
(HYDRONIC)
STEAM SAFETY VALVE
TEMPERATURE/PRESSURE
SAFETY VALVE
SELF CONTAINED CONTROL VALVE
CONSOLIDATED FITTING RETURN
CONSOLIDATED FITTING SUPPLY
THERMOMETER
PRESSURE GAUGE
TEST PLUG
SIGHT FLOW INDICATOR
SENSOR WELL
MANUAL AIR VENT
AUTOMATIC AIR VENT
VENTURI
WATER FLOW METER
FLOW MEASURING STATION
1. THE FACILITY WILL REMAIN IN OPERATION DURING CONSTRUCTION. COORDINATE ALL
SHUTDOWNS AND CONSTRUCTION ACTIVITY WITH FACILITIES STAFF.
2. SIZE AND LOCATION OF ALL PIPING AND OTHER MECHANICAL EQUIPMENT IS APPROXIMATE.
CONTRACTOR SHALL SITE VERIFY THE LOCATION OF EXISTING PIPING AND EQUIPMENT AND
CONSTRUCT WORK FROM FIELD DIMENSIONS. CONTRACTOR SHALL MAKE ADJUSTMENTS NECESSARY
TO ACCOMMODATE MINOR DEVIATIONS AT NO COST TO OWNER.
3. FINE (LIGHT) LINE WORK INDICATES EXISTING PIPING AND OTHER MECHANICAL EQUIPMENT. BOLD
(HEAVY) LINE WORK INDICATES NEW PIPING AND OTHER MECHANICAL EQUIPMENT.
4. IT IS RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE CUTTING AND PATCHING TO
ALLOW THE INSTALLATION OF MATERIALS AND EQUIPMENT AS SPECIFIED AND SHOWN ON DRAWINGS.
SYMBOL ABBREV. DESCRIPTION
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
(E) ø OR dia
SHEET NUMBER
SECTION LETTER
SHEET NUMBER
EXISTING
DIAMETER
NEW TO EXISTING POINT OF CONNECTION
NOTE REFERENCE MARKER
PLAN OR DETAIL REFERENCE MARKER
SECTION REFERENCE MARKER W/VIEW DIRECTION
EQUIPMENT MARKER
ROOM NUMBER
EXISTING SHOWN LIGHT
NEW WORK SHOWN BOLD
EXISTING TO BE REMOVED
M-301
Room Name
PLAN OR DETAIL NUMBER
SYMBOL DESCRIPTION
RECTANGULAR SUPPLY AIR DUCT UP
RECTANGULAR RETURN AIR DUCT UP
RECTANGULAR EXHAUST AIR UP
RECTANGULAR OUTSIDE AIR UP
RECTANGULAR SUPPLY AIR, &
MAKE-UP AIR DUCT DOWN
RECTANGULAR RETURN AIR DOWN
RECTANGULAR EXHAUST AIR or
OUTSIDE AIR DOWN
SA
RA
EA
OSA
ROUND DUCTWORK UP
ROUND DUCTWORK DOWN
TURN VANE ELBOW
STANDARD RADIUS ELBOW
FLEXIBLE DUCT CONNECTION
DUCT SIZE: WIDTH (IN) x DEPTH (IN) 12x6
DIFFUSER TYPE
SIZE - BLOW PATTERN (4-WAY IF NONE SHOWN)
AIR VOLUME IN CUBIC FEET per MINUTE (CFM)
GRILLE TYPE
SIZE
AIR VOLUME IN CUBIC FEET per MINUTE (CFM)
GRILLE TYPE
SIZE
AIR VOLUME IN CUBIC FEET per MINUTE (CFM)
GRILLE TYPE OR SIDE WALL DIFFUSER
SIZE
AIR VOLUME IN CUBIC FEET per MINUTE (CFM)
INTERNALLY LINED OR DOUBLE WALL
DUCTWORK
MANUAL BALANCING DAMPER
CONCENTRIC TRANSITION
ECCENTRIC TRANSITION
TEE FITTING
(RECTANGULAR)
LATERAL BRANCH
(ROUND OR OVAL)
WYE FITTING
(RECTANGULAR)
CONICAL BRANCH
(ROUND OR OVAL)
BEVELED BRANCH
(RECTANGULAR, ROUND, OR OVAL)
F FIRE SPRINKLER SUPPLY
CW POTABLE COLD WATER
HW POTABLE HOT WATER
HWR POTABLE HOT WATER RETURN
TW POTABLE TEMPERED HOT WATER
NP NON-POTABLE COLD WATER
W SANITARY WASTE
AW ACID WASTE
PW
GW
AV
D
SD
OD
PUMPED WASTE
GREASE WASTE
V VENT
ACID VENT
DRAIN
STORM DRAIN
OVERFLOW DRAIN
PSW PUMPED STORM WATER
EG-1
12"x10"
RG-1
12"x10"
EG-1
8"x4"
RECTANGULAR DUCT ANGLED CHANGE IN
ELEVATION
ROUND DUCT ANGLED CHANGE IN ELEVATION
SD-1
10"x10"
DEMOLITION NOTES
1. REVIEW DEMOLITION DRAWINGS FOR ITEMS TO REMAIN, TO BE RETAINED FOR RELOCATION, OR TO BE
SALVAGED TO THE OWNER. REFER TO ARCHITECTURAL DOCUMENTS FOR ADDITIONAL REQUIREMENTS.
2. DEMOLISH EQUIPMENT, FIXTURES, DEVICES, PIPING, CONDUIT, FITTINGS, AND APPURTENANCES INTERIOR TO THE BUILDING THAT ARE MADE OBSOLETE BY THE NEW WORK AND/OR ARE ABANDONED
AND NO LONGER IN USE.
3. PROTECT AND MAINTAIN OPERABLE EXISTING EQUIPMENT, FIXTURES, OR SYSTEMS THAT ARE
INDICATED TO REMAIN, INCLUDING ELECTRICAL POWER, CONTROLS, AND RELATED SYSTEMS
REQUIRED TO MAINTAIN OPERABILITY.
4. EXISTING CONDITIONS SHOWN ARE BASED ON RECORD DOCUMENTS AND LIMITED FIELD
OBSERVATIONS OF ACCESSIBLE AREAS AND MAY NOT SHOW THE ENTIRE SCOPE OF DEMOLITION
WORK. OMISSION OF EXISTING EQUIPMENT, FIXTURES, DEVICES, PIPING, CONDUIT, FITTINGS, AND APPURTENANCES FROM THE DEMOLITION DRAWINGS DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY TO PROVIDE DEMOLITION OF SYSTEMS THAT ARE MADE OBSOLETE BY THE NEW WORK, ARE ABANDONED, OR AS OTHERWISE REQUIRED TO PERFORM THE WORK DESCRIBED HEREIN.
5. PROTECT AND MAINTAIN SERVICES TO REMAIN OPERATIONAL THAT PASS THROUGH THE AREA OF CONSTRUCTION. WHERE IT IS NOT POSSIBLE TO MAINTAIN THESE SERVICES INTACT, REPLACE, REROUTE, MODIFY, OR PROVIDE NEW AS REQUIRED TO MAINTAIN SERVICES.
PACKAGE EQUIPMENT BOUNDRY
M-521
M101
RECTANGULAR MAKE-UP AIR DUCT UPMAS
A P
A P
A
HC
ABBREV.
DP
P
PROCESS PIPING SIGNAL
ELECTRICAL SIGNAL
SPACE TEMPERATURE
SPACE HUMIDITY
SPACE CARBON DIOXIDE
SPACE MULTIFUNCTION
PRESSURE MEASUREMENT
TEMPERATURE MEASUREMENT
HUMIDITY MEASUREMENT
FLOW MEASUREMENT
ELECTRICAL CURRENT/POWER
S = SENSOR
T = TRANSMITTER
FS = FLOW SWITCH
CO2 = CARBON DIOXIDE
CO = CARBON MONOXIDE
NO2 = NITROGEN DIOXIDE
GAS CONCENTRATION
T
FP
HP = HIGH PRESSURE SWITCH
LP = LOW PRESSURE SWITCH
A ACTUATOR
A
ES
AI
ALARM
VFD
CWP-2
AUTOMATIC CONTROL
DAMPER
BAS INPUT/OUTPUT POINT
EMERGENCY STOP SWITCH
AI = ANALOG INPUT
AO = ANALOG OUTPUT
DI = DIGITAL INPUT
DO = DIGITAL OUTPUT
FUNCTION DESIGNATION
S/S = START/STOP
CP = CONTROL PANEL
BCP = BOILER CONTROL PANEL
CCP = CHILLER CONTROL PANEL
FAP = FIRE ALARM PANEL
MC = MOTOR CONTROLLER
VFD = VARIABLE FREQUENCY DRIVE
T
P
H
F
G
CO2
SD SMOKE DETECTOR
E C
RELAY FREEZE PROTECTION
RELAY
DP = DIFFERENTIAL PRESSURE
T
AHU-1
SPACE THERMOSTAT
FITTINGS
PIPING
STEAM
SYMBOL ABBREV. DESCRIPTION
VALVES
FUEL
REFRIGERANT
SITE (REFERENCE)
FIRE PROTECTION
SYMBOL ABBREV. DESCRIPTION
AUTOMATIC VALVES
AAV AUTOMATIC AIR VENT
AC AIR CONDITIONER
ACB ACTIVE CHILLED BEAM
AD AUTOMATIC DAMPER
AF AIR CURTAIN
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
B BOILER
BD BALANCING DAMPER
BDD BACK DRAFT DAMPER
BF BOILER FEED
BF BOOSTER FAN
CB CHILLED BEAM
CC CHILLED WATER COIL
CFP CHEMICAL FEED PUMP
CFT CHEMICAL FEED TANK
CH CHILLER
CP CIRCULATING PUMP
CT COOLING TOWER
CU CONDENSING UNIT
CRU CONDENSATE RETURN UNIT
CV CONTROL VALVE
CWP CHILLED WATER PUMP
EAL EXHAUST AIR LOUVER
EDH ELECTRIC DUCT HEATER
EF EXHAUST FAN
EH EXHAUST HOOD
ET EXPANSION TANK
FC FAN COIL UNIT
FCD FLOW CONTROL DEVICE
FD FIRE DAMPER
FF FINAL FILTER
FSD FIRE SMOKE DAMPER
GF GLYCOL FEEDER
CC
HEATING WATER COIL
CHILLED WATER COIL
FLOW SWITCH
HRC HEAT RECOVERY COIL
SYMBOL ABBREV. DESCRIPTION
MISCELLANEOUS FITTINGS
DIFFUSERS AND GRILLES
SEE SPECIFICATIONS
SYMBOL DESCRIPTIONABBREV.
mA MILLIAMPERE
MA MIXED AIR
MAX MAXIMUM
MBH THOUSAND BTUs per HOUR
MCA MINIMUM CIRCUIT AMPACITY
MERV MINIMUM EFFICIANCY REPORTING VALUE
MFR MANUFACTURER
MIN MINIMUM
MIN EFF MINIMUM EFFICIENCY
MOP MAXIMUM OVERCURRENT PROTECTION
(N) NEW
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NR NOT REQUIRED
OAT OUTSIDE AIR TEMPERATURE
OCC OCCUPIED
OFCI OWNER FURNISHED/
CONTRACTOR INSTALLED
OSA OUTSIDE AIR
PD PRESSURE DROP
PH PHASE
PPH POUNDS per HOUR PSI POUNDS per SQUARE INCH PSIG POUNDS per SQUARE INCH GAUGE
RA RETURN AIR
RAT RETURN AIR TEMPERATURE
REQ'D REQUIRED
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RL REFRIGERANT LIQUID
RLA RUNNING LOAD AMPS
RS REFRIGERANT SUCTION
RPM REVOLUTIONS PER MINUTE
ABBREVIATIONS
EQUIPMENT ABBREVIATIONS
HC HOT WATER COIL
HP HEAT PUMP
HR HEAT RECOVERY EXCHANGER
HRC HEAT RECOVERY COIL
HRU HEAT RECOVERY UNIT
HRV HEAT RECOVERY VENTILATOR
HUM HUMIDIFER
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
L LOUVER
LEF LABORATORY EXHAUST FAN
MUA MAKE UP AIR UNIT
MZ MULTI-ZONE
OAH OUTSIDE AIR HOOD
OBD OPPOSED BLADE DAMPER
OSAL OUTSIDE AIR LOUVER
P PUMP
PF PREFILTER
PHX POOL HEAT EXCHANGER
PTAC PACKAGED TERMINAL AIR
CONDITIONER
RF RETURN FAN
RH RELIEF HOOD
RTU ROOF TOP UNIT
SA SOUND ATTENUATOR
SF SUPPLY FAN
SG SUPPLY GRILLE
SHX STEAM HEAT EXCHANGER
ST STORAGE TANK
TP TOWER PUMP
TU TERMINAL UNIT
UH UNIT HEATER
VD VOLUME DAMPER
VP VACUUM PUMP
CONSOLIDATED SUPPLY FITTINGCFS
CONSOLIDATED RETURN FITTINGCFR
FLEXIBLE DUCT RUNOUT TO
DIFFUSER/GRILLE
PLUMBING
PUMP
PUMP SUCTION DIFFUSER
REDUCED PRESSURE
BACKFLOW PREVENTER
FD
FAN
EQUIPMENT
SYMBOL DESCRIPTIONABBREV.
FLOOR DRAIN
EQUIPMENT CONTROL PANEL
(W/EQUIP. INDICATED UNDERLINED)
EMS ENERGY MANAGEMENT SYSTEM
ENT ENTERING
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
°F DEGREES FAHRENHEIT
FLA FULL LOAD AMPS
FP FIRE PROTECTION
FPM FEET PER MINUTE
FPS FEET PER SECOND
FT FEET
FT2 SQUARE FEET
FT WC FEET WATER COLUMN
FUT FUTURE
GALV GALVANIZED
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GYP BD GYPSUM WALL BOARD
H HEIGHT
HP HORSEPOWER
HR HEAT RECOVERY
HSPF HEATING SEASONAL
PERFORMANCE FACTOR
HVAC HEATING, VENTILATING,
& AIR CONDITIONING
HZ HERTZ (CYCLES PER SECOND)
IAQ INDOOR AIR QUALITY
IN INCHES
IN WC INCHES WATER COLUMN
IPLV INTEGRATED PART LOAD VALUE
IW INDIRECT WASTE
KW KILOWATT
L LENGTH
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LON LOCAL OPERATING NETWORK
LVG LEAVING
LWT LEAVING WATER TEMPERATURE
SA SUPPLY AIR
SAT SUPPLY AIR TEMPERATURE
SCFM STANDARD CUBIC FEET PER MINUTE
SD SUPPLY DIFFUSER
SEER SEASONAL ENERGY EFFICIENCY RATIO
SP STATIC PRESSURE
SS STAINLESS STEEL
STL STEEL
TEMP TEMPERATURE
TDH TOTAL DYNAMIC HEAD
TP TOTAL PRESSURE
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
V VOLT
VFD VARIABLE FREQUENCY DRIVE
VP VELOCITY PRESSURE
VSD VARIABLE SPEED DRIVE
W WATTS
WB WET BULB
WPD WATER PRESSURE DROP
WC WATER COLUMN
WG WATER GAUGE
T
AHU-1
H
G
CO2
C
ROOM MARKER
ROOM NAME
SSV STEAM SAFETY VALVE
SIDESTREAM FILTRATION UNIT
MAV
AAV
S
CFR
CFS
A
RP
SD
W
FS
AC-E-N14A TYPE - NUMBER
MITERED WITH TURNING VANES
(RECTANGULAR, ROUND, OR OVAL)
MITERED WITHOUT TURNING VANES
(RECTANGULAR OR ROUND)
RADIUS
(RECTANGULAR OR ROUND)
ELBOWS
GORED
(OVAL)
MITERED RADIUS
MITERED RADIUS
WYE FITTING
(ROUND OR OVAL)
STRAIGHT BRANCH
(RECTANGULAR, ROUND, OR OVAL)
CO2 = CARBON DIOXIDE
CO = CARBON MONOXIDE
T = TEMPERATURE
H = HUMIDITY
G = GAS (CO2, CO)
FS
FMS
RO
MANUAL BALANCING DAMPER
(FLOW MEASUREING STATION)
MANUAL BALANCING DAMPER
(REMOTE OPERATION)
SMOKE DAMPER
FIRE / SMOKE DAMPER
(VERTICAL BLADE)
FIRE / SMOKE DAMPER
(HORIZONTAL BLADE)
FIRE DAMPER
SMOKE DETECTOR
BACKDRAFT DAMPER
AUTOMATIC CONTROL DAMPER
A
BD
SD
F
C
C1
S
FCV FLOW CONTROL VALVE
GRILLE TYPE
SIZE
AIR VOLUME IN CUBIC FEET per MINUTE (CFM)
SG-1
12"x10"
725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com
DATE:
DRAWN:
CHECKED:
PROJECT:
DESIGNED:
OWNER:
MARK DATE DESCRIPTION
/7
/2
:3
:1
A
M P
LO
T
T E
D B
Y F
R M
O N
D P
S S
T V
R F
R E
P
LA
C E
M E
N T
STATE OF OREGON
LEGEND, GENERAL
NOTES, & SHEET
LIST
08.07.2026
240024.01
M001
CLW
FRM
NJJ
D E
P A
R T
M E
N T
O F
P U
B
LI
C S
A F
E T
Y S
T A
N D
A R
D S
A N
D T
R A
IN
IN
G
A um sv ill e H ig hw ay S
E S al em
, O R
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
SHEET LIST - MECHANICAL
M001 LEGEND, GENERAL NOTES, & SHEET LIST
M101 DEMOLITION PLANS - NE
M102 DEMOLITION PLANS - SE
M121 FLOOR PLANS - NE
M122 FLOOR PLANS - SE
M501 DETAILS
M601 SCHEDULES
M621 DIAGRAMS
H V A C D ES I G N C R I T E R I A
GENERAL
SITE ELEVATION
HEATING COOLING
DESIGN
AMBIENT (F°)
HEATING SPACE
TEMPERATURE (F°)
DESIGN AMBIENT
DRY BULB (F°)
DESIGN AMBIENT
WET BULB (F°)
COOLING SPACE
TEMPERATURE (F°)
NOTES
177' 20 70 93 67 75
© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)
EXPIRES: 06-30-2027
JA NUA RY 14 , 2020
DIGITALLY SIGNED
RE
GI
STERED PROFESSIONALENGINEER# 95772
OREGONN
A
T
E
J . J E NK
EH EJ EK EL EM
E11
E10
E9
1 1/4" CD
1 1/4" CD
1 1/4" CD
GUN STORAGE
E 106C
N HALL
E 101N
COMPUTER LAB
E 105C
DORM E
E 126N
BATH C
E 125N
ELECTRICAL
E 127N
N HALL
E 101N
CUSTODIAN
E 128N
LAUNDRY
E 129N
T
T
T
T 1 1/4" CD
EH EJ EK EL EM
E11
E10
E9
1 1/4" CD
DORM C
E 209C
DORM D
E 211C
BATH B
E 210CBATH A
E 213C
DORM B
E 212C
DORM A
E 214C
STORAGE
E 229N
ELECTRICAL
E 227N
DORM E
E 225N
BATH C
E 224N
MDF/IDF
E 226N
LAUNDRY
E 228N
N HALL
E 201N
T
T 9
EH EJ EK EL EM
E11
E10
E9
EH EJ EK EL EM
E11
E10
E9
1 1/4" CD1 1/4" CD
ELECTRICAL
E 327N
MDF/IDF
E 326N
DORM D
E311C
N HALL
E 301N
LAUNDRY
E 328N
STORAGE
E 329N
DORM B
E 312C
DORM A
E 314C
BATH A
E 313C
DORM C
E 309C
BATH B
E 310C
DORM E
E 325N
BATH C
E 324N T
9T
KEY PLAN
NOT TO SCALE
725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com
DATE:
DRAWN:
CHECKED:
PROJECT:
DESIGNED:
OWNER:
MARK DATE DESCRIPTION
AREA OF WORK
/7
/2
:3
:1
A
M P
LO
T
T E
D B
Y F
R M
O N
D P
S S
T V
R F
R E
P
LA
C E
M E
N T
STATE OF OREGON
DEMOLITION
PLANS - NE
08.07.2026
240024.01
M101
CLW
FRM
NJJ
D E
P A
R T
M E
N T
O F
P U
B
LI
C S
A F
E T
Y S
T A
N D
A R
D S
A N
D T
R A
IN
IN
G
A um sv ill e H ig hw ay S
E S al em
, O R
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
R E F E R E N C E N O T E S :
1 REMOVE EXISTING VRF BRANCH CONTROLLER BOX AND ASSOCIATED REFRIGERANT
PIPING BETWEEN BRANCH CONTROLLER AND OUTDOOR UNIT. RETAIN CONDENSATE
PIPING FOR REUSE.
REMOVE EXISTING VRF FCU AND ASSOCIATED REFRIGERANT PIPING BETWEEN FCU
AND BRANCH CONTROLLER.
EXISITNG CONDENSATE DRAIN ROUTES TO MOP SINK. PRESERVE CONDENSATE DRAIN
FOR CONNECTION TO NEW FCU. VERIFY EXISTING ROUTING DOES NOT GO OVER
ELECTRICAL GEAR AND REROUTE IF NEEDED.
EXISTING TRANSFER AIR OPENING TO REMAIN.
REMOVE EXISTING CIRCULATION FAN AND ASSOCIATED DUCTWORK, CONTROLS, AND
SUPPORTS. PRESERVE OPENING IN WALL FOR NEW SUPPLY DUCTWORK.
DEMOLISH GYP CEILING AS NEEDED TO ACCESS CEILING SPACE FOR PIPING DEMO AND
INSTALLATION.
DEMOLISH PORTION OF CHASE AS NEEDED TO ACCESS PIPING FOR DEMO AND
INSTALLATION.
REMOVE EXISTING VRF OUTDOOR UNIT AND ASSOCIATED CONTROLS, SUPPORTS, AND
REFRIGERANT PIPING BETWEEN OUTDOOR UNIT AND INDOOR UNITS.
REMOVE ANY ABANDONED REFRIGERANT PIPING ASSOCIATED WITH DECOMISSIONED
WALL MOUNT UNIT IN MDF/IDF ROOM.
NORTH
1/8" = 1'-0"1
MECHANICAL FIRST FLOOR DEMOLITION PLAN - NE
NORTH
1/8" = 1'-0"2
MECHANICAL SECOND FLOOR DEMOLITION PLAN - NE
NORTH
1/8" = 1'-0"3
MECHANICAL THIRD FLOOR DEMOLITION PLAN - NE
NORTH
1/8" = 1'-0"4
MECHANICAL DEMOLITION ROOF PLAN - NE
© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)
EXPIRES: 06-30-2027
JA NUA RY 14 , 2020
DIGITALLY SIGNED
RE
GI
STERED PROFESSIONALENGINEER# 95772
OREGONN
A
T
E
J . J E NK
EG EH EJ EK EL EM
E5
E4
1 1/4" CD
DORM E
E 325S
BATH C
E 326S
CUST
E 322SDORM B
E 320S
BATH A
E 319S
DORM B
E 320S
STORAGE
E 321S
ELECTRICAL
E 323S
IDF
E 324S
T
EG EH EJ EK EL EM
E5
E4
EG EH EJ EK EL EM
E5
E4
1 1/4" CD
1 5
1 1/4" CD
ELECTRICAL
E118S
BOILER/CUST
E 119S
MAINTENANCE
E 121S
S HALL
E 101S
STUDENT REC
E 122S
T T
T
DEMOLISH VRF
CONTROLLER
EG EH EJ EK EL EM
E5
E4
DORM B
E 220S
BATH A
E 219S
STORAGE
E 221S
S HALL
E 201S
CUST
E 222S
DORM E
E 225S
IDF
E 224S
ELECTRICAL
E 223S
BATH C
E 226S
1-1/4" CD
T
KEY PLAN
NOT TO SCALE
725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com
DATE:
DRAWN:
CHECKED:
PROJECT:
DESIGNED:
OWNER:
MARK DATE DESCRIPTION
AREA OF WORK
/7
/2
:3
:1
A
M P
LO
T
T E
D B
Y F
R M
O N
D P
S S
T V
R F
R E
P
LA
C E
M E
N T
STATE OF OREGON
DEMOLITION
PLANS - SE
08.07.2026
240024.01
M102
CLW
FRM
NJJ
D E
P A
R T
M E
N T
O F
P U
B
LI
C S
A F
E T
Y S
T A
N D
A R
D S
A N
D T
R A
IN
IN
G
A um sv ill e H ig hw ay S
E S al em
, O R
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
NORTH
1/8" = 1'-0"1
MECHANICAL FIRST FLOOR DEMOLITION PLAN - SE
NORTH
1/8" = 1'-0"2
MECHANICAL SECOND FLOOR DEMOLITION PLAN - SE
NORTH
1/8" = 1'-0"3
MECHANICAL THIRD FLOOR DEMOLITION PLAN - SE
R E F E R E N C E N O T E S :
1 REMOVE EXISTING VRF FCU AND ASSOCIATED REFRIGERANT PIPING BETWEEN FCU
AND BRANCH CONTROLLER.
EXISTING TRANSFER AIR OPENING TO REMAIN.
REMOVE EXISTING CIRCULATION FAN AND ASSOCIATED DUCTWORK, CONTROLS,
AND SUPPORTS. PRESERVE OPENING IN WALL FOR NEW SUPPLY DUCTWORK.
REMOVE EXISTING VRF OUTDOOR UNIT AND ASSOCIATED CONTROLS, SUPPORTS,
AND REFRIGERANT PIPING BETWEEN OUTDOOR UNIT AND INDOOR UNITS.
REMOVE EXISTING VRF BRANCH CONTROLLER BOX AND ASSOCIATED REFRIGERANT
PIPING BETWEEN BRANCH CONTROLLER AND OUTDOOR UNIT. RETAIN CONDENSATE
PIPING FOR REUSE.
DEMOLISH PORTION OF CHASE AS NEEDED TO ACCESS PIPING FOR DEMO AND
INSTALLATION.
NORTH
1/8" = 1'-0"4
MECHANICAL DEMOLITION ROOF PLAN - SE
© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)
EXPIRES: 06-30-2027
JA NUA RY 14 , 2020
DIGITALLY SIGNED
RE
GI
STERED PROFESSIONALENGINEER# 95772
OREGONN
A
T
E
J . J E NK
E10
E9
BC-E-N1
DORM E
E 126N
BATH C
E 125N
ELECTRICAL
E 127N
N HALL
E 101N
LAUNDRY
E 129N
CUSTODIAN
E 128N
GUN STORAGE
E 106C
COMPUTER LAB
E 105C(E
1/
4" C
D
AC-E-N13
AC-E-N11
RL/RS
RL/RS/RHG UP
TO CU-E-N1 ON
ROOF
RL/RS (TYP. OF 4)
1/2" CD
T
T
T
"x
S A
AC-E-N14
SD-1
12x12
344 CFM
SD-1
12x12
344 CFM
RG-1
14x14
688 CFM
38"x16" RA 14"ø RA
10"ø SA
10"ø SA
BC-E-N2
4 RL/RS/RHG
RL/RS
RL/RS
1/2" CD
(E) 1 1/4" CD
(E) 1 1/4" CD
1" CD
EH EJ EK EL EM
E11
E10
E9
(E) 1 1/4" CDLAUNDRY
E 228N
STORAGE
E 229N
N HALL
E 201N
MDF/IDF
E 226N
ELECTRICAL
E 227N
DORM E
E 225N
BATH C
E 224N
DORM D
E 211C
BATH B
E 210C
DORM C
E 209C
BATH A
E 213C
DORM B
E 212C
DORM A
E 214C
AC-E-N21
AC-E-N22
(E) 24"x10" TA
1" CD
RL/RS
RL/RS
1/2" CD
RL/RS (TYP. OF 4) DN TO
BC-E-N1 ON FIRST FLOOR
T T
SG-1
30x10
688 CFM
RL/RS/RHG UP & DN
EH EJ EK EL EM
E11
E10
E9
CU-E-N1
RL/RS/RHG
EH EJ EK EL EM
E11
E10
E9
(E) 1 1/4" CD
DORM E
E 325N
BATH C
E 324N
MDF/IDF
E 326N
N HALL
E 301N
LAUNDRY
E 328N
STORAGE
E 329N
DORM B
E 312C
DORM A
E 314C
BATH A
E 313C
DORM D
E311C
BATH B
E 310C
DORM C
E 309C
ELECTRICAL
E 327N
AC-E-N31
AC-E-N32
(E) 24X10 TA
RL/RS/RHG UP & DN
RL/RS
RL/RS DN TO BC-E-N1
ON FIRST FLOOR
1/2" CD
T
1" CD
T
SG-1
30x10
688 CFM
KEY PLAN
NOT TO SCALE
725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com
DATE:
DRAWN:
CHECKED:
PROJECT:
DESIGNED:
OWNER:
MARK DATE DESCRIPTION
AREA OF WORK
/7
/2
:3
:1
A
M P
LO
T
T E
D B
Y F
R M
O N
D P
S S
T V
R F
R E
P
LA
C E
M E
N T
STATE OF OREGON
FLOOR PLANS - NE
08.07.2026
240024.01
M121
CLW
FRM
NJJ
D E
P A
R T
M E
N T
O F
P U
B
LI
C S
A F
E T
Y S
T A
N D
A R
D S
A N
D T
R A
IN
IN
G
A um sv ill e H ig hw ay S
E S al em
, O R
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
S H E E T N O T E S :
R E F E R E N C E N O T E S :
1 CONNECT CONDENSATE FROM AC-E-N13 INTO EXISTING CONDENSATE LINE.
PATCH CHASE TO MAINTAIN EXISTING FIRE RATING.
PATCH GYP CEILING. FINISH TO MATCH ADJACENT SURFACES.
JUNCTIONS VIA REFNET BRANCH PIPING KIT PER MANUFACTURER.
1. REFRIGERANT PIPING SHOWN IS DIAGRAMATIC. FINAL PIPE ROUTING AND SIZING TO
BE APPROVED BY MANUFACTURER.
2. ALL REFRIGERANT PIPING SHALL BE PROVIDED WITH PIPE IDENTIFICATION
ACCORDING TO OMSC 1109.2.7.
NORTH
1/8" = 1'-0"1
MECHANICAL FIRST FLOOR PLAN - NE
NORTH
1/8" = 1'-0"2
MECHANICAL SECOND FLOOR PLAN - NE
NORTH
1/8" = 1'-0"3
MECHANICAL THIRD FLOOR PLAN - NE
NORTH
1/8" = 1'-0"4
MECHANICAL ROOF PLAN - NE
© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)
EXPIRES: 06-30-2027
JA NUA RY 14 , 2020
DIGITALLY SIGNED
RE
GI
STERED PROFESSIONALENGINEER# 95772
OREGONN
A
T
E
J . J E NK
E4
STORAGE
E 321S
CUST
E 322S
ELECTRICAL
E 323S
IDF
E 324S
DORM E
E 325S
BATH C
E 326S
DORM B
E 320S
BATH A
E 319S
(E) 1 1/4" CD
AC-E-S31
(E) 24x10 TARL/RS
RL/RS/RHG UP & DN
1" CD
RL/RS DN TO
BC-E-S1 ON
FIRST FLOOR
T
SG-1
30x10
688 CFM
EG EH EJ EK EL EM
E5
E4
CU-E-S1
RL/RS/RHG
RL/RS/RHG DN 3
EG EH EJ EK EL EM
E5
E4
BC-E-S1
ELECTRICAL
E118S
BOILER/CUST
E 119S
MAINTENANCE
E 121S
S HALL
E 101S
STUDENT REC
E 122S
1/2" CD
AC-E-S12
AC-E-S13
AC-E-S11 RL/RS
RL/RS/RHG UP
TO CU-E-S1 ON
ROOF
RL/RS
RL/RS
TT
T
1" CD
CENTRALIZED
VRF CONTROLLER
(E) 1 1/4" CD
1/2" CD
EG EH EJ EK EL EM
E5
E4
CUST
E 222S DORM E
E 225S
BATH C
E 226S
IDF
E 224S
ELECTRICAL
E 223S
S HALL
E 201S
STORAGE
E 221S
DORM B
E 220S
BATH A
E 219S
AC-E-S21
RL/RS UP
AND DN
(E) 24x10 TA
1" CD
TRL/RS
SG-1
30x10
688 CFM
RL/RS/RHG UP & DN
KEY PLAN
NOT TO SCALE
725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com
DATE:
DRAWN:
CHECKED:
PROJECT:
DESIGNED:
OWNER:
MARK DATE DESCRIPTION
AREA OF WORK
/7
/2
:3
:1
A
M P
LO
T
T E
D B
Y F
R M
O N
D P
S S
T V
R F
R E
P
LA
C E
M E
N T
STATE OF OREGON
FLOOR PLANS - SE
08.07.2026
240024.01
M122
CLW
FRM
NJJ
D E
P A
R T
M E
N T
O F
P U
B
LI
C S
A F
E T
Y S
T A
N D
A R
D S
A N
D T
R A
IN
IN
G
A um sv ill e H ig hw ay S
E S al em
, O R
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
NORTH
1/8" = 1'-0"1
MECHANICAL FIRST FLOOR PLAN - SE
NORTH
1/8" = 1'-0"2
MECHANICAL SECOND FLOOR PLAN - SE
NORTH
1/8" = 1'-0"3
MECHANICAL THIRD FLOOR PLAN - SE
S H E E T N O T E S :
R E F E R E N C E N O T E S :
1 EXISTING 1-1/4" CONDENSATE DRAIN TERMINATE AT EXISTING MOP SINK.
KEEP CONDENSATE DRAIN HIGH IN IDF ROOM. OFFSET CONDENSATE DRAIN AS
LOW ON THE WALL AS POSSIBLE IN IDF ROOM TO MAKE CONNECTION TO
EXISTING CONDENSATE IN CUSTODIAL ROOM.
PATCH CHASE TO MAINTAIN EXISTING FIRE RATING.
REVISE ROUTING OF PRESSURE RELIEF PIPE ON WEST WALL OF
BOILER/CUSTODIAL ROOM TO MAKE ROOM FOR INSTALLATION OF AC-E-S12 IN
ACCESSIBLE LOCATION. PROVIDE DEDICATED CONDENSATE LINE FOR AC-E-S12
TO TERMINATE AT MOP SINK.
1. REFRIGERANT PIPING SHOWN IS DIAGRAMATIC. FINAL PIPE ROUTING AND SIZING TO
BE APPROVED BY MANUFACTURER.
2. ALL REFRIGERANT PIPING SHALL BE PROVIDED WITH PIPE IDENTIFICATION
ACCORDING TO OMSC 1109.2.7.
NORTH
1/8" = 1'-0"4
MECHANICAL ROOF PLAN - SE
© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)
EXPIRES: 06-30-2027
JA NUA RY 14 , 2020
DIGITALLY SIGNED
RE
GI
STERED PROFESSIONALENGINEER# 95772
OREGONN
A
T
E
J . J E NK
DRAW-THROUGH FAN SYSTEM BLOW-THROUGH FAN SYSTEM
H
H/2 MIN.
H = FAN INLET
PRESSURE (IN. W.C.)
+ 1 INCH
TO DRAIN PAN
CONNECTION
HAND-TIGHT CAP
PLUG (TYP. of 2)
TEE FITTING
SLOPE PIPING TO
DRAINAGE FIXTURE
AS REQUIRED.
1/2"
MIN.
H
SLOPE PIPING TO
DRAINAGE FIXTURE
AS REQUIRED.
H = FAN INLET
PRESSURE (IN. W.C.)
+ 1 INCH
TO DRAIN PAN
CONNECTION
HAND-TIGHT CAP
PLUG (TYP. OF 2)
TEE
FITTING
CONDENSATE DRAIN CONNECTION
UNISTRUT ATTACHED TO
STRUCTURE OR JOISTS
ABOVE - SEE STRUCTURAL.
SA DUCT - SIZE TO MATCH
OPENING WIDTH, HEIGHT AS
REQUIRED FOR LARGEST
CONNECTING DUCT
FLEX CONNECTOR
REFRIGERANT PIPING CONNECTIONS
UNIT SUPPORT AND VIBRATION
ISOLATION AS SPECIFIED
MAINTAIN MINIMUM PIPING &
ELECTRICAL CLEARANCE PER
MANUFACTURER
RECOMMENDATIONS
PLAN VIEW
SECTION VIEW
SA DUCT - SEE PLANS
FOR CONFIGURATION.
CEILING OR
STRUCTURE ABOVE
WALL MOUNTED
FAN COIL UNIT
INSTALL UNIT ON FACTORY-
SUPPLIED MOUNTING BRACKET
PER MANUFACTURER'S
INSTRUCTIONS.
EXISTING STUD WALL
LATERAL STUD
BACKING (TYP)
LAG SCREW - SIZE & NUMBER
PER MANUFACTURER'S
INSTRUCTIONS (TYP)
.4" MIN
6" MAX
2' -0
M
A X
1/4
TYP.
CU BY OTHERS w/750#
MAX. OPERATING WEIGHT
AND 6'-0" MAX. HEIGHT
(4) 3/4" DIA. THRU BOLTS
AT BASE OF UNIT
CONT. HSS 4x2x1/4 FLAT
UNDER SIDE RAILS
1. ALL STEEL IS TO BE GALVANIZED.
(3) #12 ELCO
DRIL-FLEX
SCREWS EA. END
REMOVE AND
REPLACE ROOFING
BY OTHERS AS
REQUIRED AT NEW
STANDS
4" X-STRONG
PIPE TYP.
PL 1/2x12x1'-0" w/ (4)
3/8" DIA. THREADED
RODS OR BOLTS IN
HILTI HDI-P TZ DROP
IN ANCHOR INSERTS
w/3/4" EMBED @ 9" o.c. TYP.
GALV. HILTI HS 158-12
SOLID STRUT EA. SIDE
OF UNIT CENTERED
ON POSTS
3/8" CAP PL TYP.
GC TO VERIFY
REQUIRED
EXTENSION ABOVE
ROOFING
MEMBRANE WITH
ROOFING MANUF.
AND INSTALLER
(E) HOLLOW CORE
PLANKS AND 3"
CONCRETE TOPPING
D E T A I L G E N E R A L N O T E S :
CONDENSATE DRAIN CONNECTION
UNISTRUT ATTACHED TO
STRUCTURE OR JOISTS
ABOVE - SEE STRUCTURAL.
FACTORY FILTER RACK
W/ ACCESS
LINED RA PLENUM SIZED TO
MATCH RA OPENING WIDTH
@ UNIT - 3'-0" LONG MIN,
HEIGHT AS REQUIRED FOR
LARGEST CONNECTING
DUCT
RA BRANCH DUCT - SEE
PLANS FOR SIZE AND
CONFIGURATION.
SA DUCT - SIZE TO MATCH
OPENING WIDTH, HEIGHT AS
REQUIRED FOR LARGEST
CONNECTING DUCT
FLEX CONNECTOR
REFRIGERANT PIPING CONNECTIONS
UNIT SUPPORT AND VIBRATION
ISOLATION AS SPECIFIED
LINED SA DUCT AS SHOWN ON PLANS
MAINTAIN MINIMUM PIPING &
ELECTRICAL CLEARANCE PER
MANUFACTURER
RECOMMENDATIONS
MINIMUM 18"x18" CEILING ACCESS
PER MANUFACTURER
RECOMMENDATIONS
PLAN VIEW
SECTION VIEW
SA DUCT - SEE PLANS
FOR CONFIGURATION.
725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com
DATE:
DRAWN:
CHECKED:
PROJECT:
DESIGNED:
OWNER:
MARK DATE DESCRIPTION
/7
/2
:3
:1
A
M P
LO
T
T E
D B
Y C
LW
O
N
D P
S S
T V
R F
R E
P
LA
C E
M E
N T
STATE OF OREGON
DETAILS
08.07.2026
240024.01
M501
CLW
CLW
NJJ
D E
P A
R T
M E
N T
O F
P U
B
LI
C S
A F
E T
Y S
T A
N D
A R
D S
A N
D T
R A
IN
IN
G
A um sv ill e H ig hw ay S
E S al em
, O R
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
NOT TO SCALE
CONDENSATE DRAIN CONNECTION
NOT TO SCALE
HORIZONTAL FAN COIL - ELECTRICAL ROOM
NOT TO SCALE
WALL MOUNTED FAN COIL
NOT TO SCALE
MECHANICAL UNIT MOUNTING
NOT TO SCALE
HORIZONTAL FAN COIL - COMPUTER LAB
© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)
EXPIRES: 06-30-2027
JA NUA RY 14 , 2020
DIGITALLY SIGNED
RE
GI
STERED PROFESSIONALENGINEER# 95772
OREGONN
A
T
E
J . J E NK
725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com
DATE:
DRAWN:
CHECKED:
PROJECT:
DESIGNED:
OWNER:
MARK DATE DESCRIPTION
/7
/2
:3
:1
A
M P
LO
T
T E
D B
Y C
LW
O
N
D P
S S
T V
R F
R E
P
LA
C E
M E
N T
STATE OF OREGON
SCHEDULES
08.07.2026
240024.01
M601
CLW
CLW
NJJ
D E
P A
R T
M E
N T
O F
P U
B
LI
C S
A F
E T
Y S
T A
N D
A R
D S
A N
D T
R A
IN
IN
G
A um sv ill e H ig hw ay S
E S al em
, O R
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
GENERAL NOTES:
A. PROVIDE UNITS WITH WIND COVERS TO ALLOW FOR LOW AMBIENT COOLING.
V R F A I R C O O L E D C O N D E N S I N G U N I T
TAG MANUFACTURER MODEL
AMBIENT DESIGN CAPACITY EFFICIENCY SOUND
LEVEL
(dB)
UNIT
WEIGHT
(LBS)
ELECTRICAL
NOTESHEAT
(°F)
COOL
(°F)
HEAT
(MBH)
COOL
(MBH)
HEAT
(COP)
COOL (IEER) VOLTS PHASE MCA MOP
CU-E-N1 DAIKIN REYQ120AATJB 20 93 112 129 3.5 19.1 61 725 208 3 36.5 40
CU-E-S1 DAIKIN REYQ72AATJB 20 93 79 78 3.6 19.1 58 525 208 3 27.3 30
V R F B R A N C H C O N T R O L L E R
TAG MANUFACTURER MODEL
ELECTRICAL
NOTES
VOLTS PHASE MCA MOP
BC-E-N1 DAIKIN BSF8Q54TVJ 208 1 0.8 15
BC-E-N2 DAIKIN BSQ36TAVJ 208 1 0.1 15
BC-E-S1 DAIKIN BSF6Q54TVJ 208 1 0.6 15
V R F F A N C O I L U N I T
TAG MANUFACTURER MODEL
REFRIGERANT
TYPE
ASSOCIATED
COND UNIT
HEATING COOLING
AIRFLOW
SOUND
LEVEL
(dBA)
UNIT
WEIGHT
(LBS)
ELECTRICAL
NOTESEAT
(°F)
LAT
(°F) CAPACITY
(BTU/HR)
EAT LAT
TOTAL CAPACITY
(BTU/HR)
VOLTS PHASE MCA MOPDB
(°F)
WB
(°F)
DB
(°F)
WB
(°F)
AC-E-N11 DAIKIN FXAQ12PVJU R410A CU-E-N1 65 108 13499 80 67 55 52 12000 290 CFM 38 30 208 1 0.4 15
AC-E-N13 DAIKIN FXAQ24PVJU R410A CU-E-N1 65 104 26499 80 67 55 54 24000 635 CFM 47 35 208 1 0.6 15
AC-E-N14 DAIKIN FXMQ24TBVJU R410A CU-E-N1 65 101 27000 80 67 58 55 24000 688 CFM 39 85 208 1 1.9 15
AC-E-N21 DAIKIN FXMQ24TBVJU R410A CU-E-N1 65 101 27000 80 67 58 55 24000 688 CFM 39 85 208 1 1.9 15
AC-E-N22 DAIKIN FXAQ12PVJU R410A CU-E-N1 65 108 13499 80 67 55 52 12000 290 CFM 38 30 208 1 0.4 15
AC-E-N31 DAIKIN FXMQ24TBVJU R410A CU-E-N1 65 101 27000 80 67 58 55 24000 688 CFM 39 85 208 1 1.9 15
AC-E-N32 DAIKIN FXAQ12PVJU R410A CU-E-N1 65 108 13499 80 67 55 52 12000 290 CFM 38 30 208 1 0.4 15
AC-E-S11 DAIKIN FXFQ12AAVJU R410A CU-E-S1 65 93 13499 80 67 60 58 12000 440 CFM 30 42 208 1 0.3 15
AC-E-S12 DAIKIN FXAQ12PVJU R410A CU-E-S1 65 108 13499 80 67 55 52 12000 290 CFM 39 27 208 1 0.4 15
AC-E-S13 DAIKIN FXAQ09PVJU R410A CU-E-S1 65 100 10500 80 67 58 56 9500 280 CFM 36 27 208 1 0.3 15
AC-E-S21 DAIKIN FXMQ24TBVJU R410A CU-E-S1 65 101 27000 80 67 58 55 24000 688 CFM 30 82 208 1 1.9 15
AC-E-S31 DAIKIN FXMQ24TBVJU R410A CU-E-S1 65 101 27000 80 67 58 55 24000 688 CFM 30 82 208 1 1.9 15
© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)
EXPIRES: 06-30-2027
JA NUA RY 14 , 2020
DIGITALLY SIGNED
RE
GI
STERED PROFESSIONALENGINEER# 95772
OREGONN
A
T
E
J . J E NK
#1.1
#1.2
#1.9
#1.3
#1.4
#1.5
#1.6
#1.7
#1.8
#1.10
CU-E-N1
REYQ120AATJB
KHRP25M72TUA
BC-E-N1
BSF8Q54TVJ
A
AC-E-N11
FXAQ12PVJU
B
AC-E-N13
FXAQ24PVJU
C
AC-E-N21
FXMQ24TBVJU
D
AC-E-N22
FXAQ12PVJU
E
AC-E-N31
FXMQ24TBVJU
F
AC-E-N32
FXAQ12PVJU
G
H
BS - 3
BSQ36TAVJ
A
AC-E-N14
FXMQ24TBVJU
#2.1
#2.2
#2.3
#2.4
#2.5
#2.6
CU-E-S1
REYQ72AATJB
BC-E-S1
BSF6Q54TVJ
A
AC-E-S13
FXAQ09PVJU
B
AC-E-S12
FXAQ12PVJU
C
AC-E-S11
FXFQ12AAVJU
D
AC-E-S21
FXMQ24TBVJU
E
AC-E-S31
FXMQ24TBVJU
F
L1, L2, L3 27.3A 3ph L1, L2 0.6A 1ph L1, L2 0.3A 1ph
L1, L2 0.4A 1ph
L1, L2 0.3A 1ph
L1, L2 1.9A 1ph
L1, L2 1.9A 1ph
OUT F1,F2
IN F1,F2
to centralized controller
OUT F1,F2
IN F1,F2
P1,P2
F1,F2
P1,P2
F1,F2
P1,P2
F1,F2
P1,P2
F1,F2
P1,P2
F1,F2
REYQ72AATJB
CU-E-S1
REYQ72AATJB
BC-E-S1
BSF6Q54TVJ
A B C D E F
AC-E-S13
FXAQ09PVJU
BRC1NRV71
AC-E-S12
FXAQ12PVJU
BRC1NRV71
AC-E-S11
FXFQ12AAVJU
BRC1NRV71
AC-E-S21
FXMQ24TBVJU
BRC1NRV71
AC-E-S31
FXMQ24TBVJU
BRC1NRV71
L1, L2, L3 36.5A 3ph L1, L2 0.8A 1ph L1, L2 0.4A 1ph
L1, L2 0.6A 1ph
L1, L2 1.9A 1ph
L1, L2 0.4A 1ph
L1, L2 1.9A 1ph
L1, L2 0.4A 1ph
L1, L2 0.1A 1ph L1, L2 1.9A 1ph
OUT F1,F2
IN F1,F2
to centralized controller
OUT F1,F2
IN F1,F2
BS F1,F2
P1,P2
F1,F2
P1,P2
F1,F2
P1,P2
F1,F2
P1,P2
F1,F2
P1,P2
F1,F2
P1,P2
F1,F2
OUT F1,F2 IN F1,F2
P1,P2
F1,F2
REYQ120AATJB
CU-E-N1
REYQ120AATJB
BC-E-N1
BSF8Q54TVJ
A B C D E F G H
AC-E-N11
FXAQ12PVJU
BRC1NRV71
AC-E-N13
FXAQ24PVJU
BRC1NRV71
AC-E-N21
FXMQ24TBVJU
BRC1NRV71
AC-E-N22
FXAQ12PVJU
BRC1NRV71
AC-E-N31
FXMQ24TBVJU
BRC1NRV71
AC-E-N32
FXAQ12PVJU
BRC1NRV71
BS - 3
BSQ36TAVJ
A
AC-E-N14
FXMQ24TBVJU
BRC1NRV71
OUT F1,F2
L,N
Ethernet 100BASE-TX
CU-E-N1 (7)
REYQ120AATJB
CU-E-S1 (5)
REYQ72AATJB
Hero Pro Edge
DGE601A71
1 2
725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com
DATE:
DRAWN:
CHECKED:
PROJECT:
DESIGNED:
OWNER:
MARK DATE DESCRIPTION
/7
/2
:3
:1
A
M P
LO
T
T E
D B
Y J
S H
O N
D P
S S
T V
R F
R E
P
LA
C E
M E
N T
STATE OF OREGON
DIAGRAMS
08.07.2026
240024.01
M621
CLW
JSH
NJJ
D E
P A
R T
M E
N T
O F
P U
B
LI
C S
A F
E T
Y S
T A
N D
A R
D S
A N
D T
R A
IN
IN
G
A um sv ill e H ig hw ay S
E S al em
, O R
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)
NOT TO SCALE
CU-E-N1 PIPING DIAGRAM
NOT TO SCALE
CU-E-S1 PIPING DIAGRAM
NOT TO SCALE
CU-E-S1 WIRING DIAGRAM
NOT TO SCALE
CU-E-N1 WIRING DIAGRAM
NOT TO SCALE
CONTROL GROUP CONTROLLER WIRING DIAGRAM
EXPIRES: 06-30-2027
JA NUA RY 14 , 2020
DIGITALLY SIGNED
RE
GI
STERED PROFESSIONALENGINEER# 95772
OREGONN
A
T
E
J . J E NK
E L E C T R I C A L L E G E N D
COMBINATION DISCONNECT AND MAGNETIC STARTER
NON-FUSED DISCONNECT WITH CHARACTERISTICS AS NOTED.
MAGNETIC STARTER
MOTOR CONNECTION
CONCEALED RACEWAY AND CONDUCTORS. NUMBER OF SLASHES
INDICATES NUMBER OF CONDUCTORS IF MORE THAN TWO. SIZE
OTHER THAN 12 AWG AS NOTED. (APPLIES TO ALL WIRING SYMBOLS)
UNDERGROUND OR UNDERFLOOR RACEWAY
HOMERUN
OVERHEAD POWER LINE
SPLICE
OHD
GROUND CONNECTION
CONDUIT UP
CONDUIT DOWN
JUNCTION BOX
JUNCTION BOX FLUSH WITH FLOOR OR AT GRADE
CONDUIT STUB
CABLE TRAY
CURRENT TRANSFORMER
ELECTRICAL EQUIPMENT AS NOTED ON DRAWINGS
SURFACE-MOUNTED CABINET, TYPE AS NOTED
ELECTRIC METER, TYPE AS NOTED
MAGNETIC DOOR POSITION SENSOR
SECURITY SYSTEM OUTDOOR SIREN WITH TAMPER WIREGUARD
SECURITY SYSTEM OUTDOOR SIREN
CORNER SECURITY SYSTEM MOTION SENSOR
CEILING MOUNTED SECURITY SYSTEM MOTION
SECURITY SYSTEM KEYPAD
REQUEST TO EXIT SENSOR
GLASS BREAKAGE SENSOR
CARD READER
MECHANICAL EQUIPMENT DESIGNATOR, SEE SCHEDULES.
REFERENCE NOTE MARKER
PLAN OR DETAIL NUMBER
SHEET NUMBER
EXISTING WORK SHOWN LIGHT
NEW WORK SHOWN BOLD
EXISTING TO BE REMOVED (APPLIES TO DEMOLITION PLANS ONLY)
E-121
E-501
FUSED DISCONNECT WITH CHARACTERISTICS AS NOTED.
AS = SWITCH RATING, AF = FUSE RATING.
J
J
M
M
GB
CR
REX
PB PULL BOX, SIZE AS NOTED OR AS REQUIRED
FB1
SURFACE-MOUNTED PANELBOARD (120/208V)
SURFACE-MOUNTED PANELBOARD (277/480V)
RECESSED PANELBOARD (120/208V)
RECESSED PANELBOARD (277/480V)
CT
S
WP
SPD
T
CEILING-MOUNTED SECURITY CAMERA
CEILING-MOUNTED 360° VIEW ANGLE SECURITY CAMERA
WALL-MOUNTED SECURITY CAMERA
WALL-MOUNTED 360° VIEW ANGLE SECURITY CAMERA
MULTI-DIRECTIONAL SECURITY CAMERA
DISTRIBUTION TRANSFORMER
GROUNDING BUSBAR
SPECIAL PURPOSE RECEPTACLE WITH NEMA CONFIGURATION AS NOTED.L6-30R
PUSH BUTTON STATION
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE
QUADPLEX RECEPTACLE
FLUSH FLOOR BOX. REFER TO SPECIFICATIONS AND SCHEDULES FOR
DEVICE QUANTITIES AND TYPES.
FLUSH POKE-THROUGH FLOOR BOX. REFER TO SPECIFICATIONS AND
SCHEDULES FOR DEVICE QUANTITIES AND TYPES.
SPLIT-WIRED RECEPTACLE WITH HALF SWITCHED CONTROL VIA MANUAL
CONTROL, OCCUPANCY SENSING CONTROL, OR TIME BASED CONTROL.
REFER TO SPECIFICATIONS AND DRAWINGS.
RECEPTACLE WITH FULL SWITCHED CONTROL VIA MANUAL CONTROL,
OCCUPANCY SENSING CONTROL, OR TIME BASED CONTROL. REFER TO
SPECIFICATIONS AND DRAWINGS.
FB1 FLUSH FLOOR BOX WITH SWITCHED CONTROL VIA MANUAL CONTROL,
OCCUPANCY SENSING CONTROL, OR TIME BASED CONTROL. REFER TO
SPECIFICATIONS AND DRAWINGS.
PT3 FLUSH POKE-THROUGH FLOOR BOX WITH SWITCHED CONTROL VIA MANUAL
CONTROL, OCCUPANCY SENSING CONTROL, OR TIME BASED CONTROL.
REFER TO SPECIFICATIONS AND DRAWINGS.
LETTER DESIGNATOR(S) INDICATE ADDITIONAL RECEPTACLE
CHARACTERISTICS (APPLIES TO ALL RECEPTACLE AND FLOOR BOX TYPES):
A = INTEGRAL AFCI
B = INTEGRAL WITH USB OUTLET(S)
C = SUPPLIED POWER VIA CRITICAL BRANCH (NEC 517)
E = SUPPLIED POWER VIA LIFE SAFETY BRANCH (NEC 517)
G = INTEGRAL GFCI
IG = SUPPLIED POWER VIA AN ISOLATED GRD SYSTEM
P = INTEGRAL SURGE PROTECTIVE DEVICE
S = SUPPLIED POWER VIA OPTIONAL STANDBY BRANCH (NEC 702)
U = SUPPLIED POWER VIA A UPS
WP = WEATHERPROOF AND INTEGRAL GFCI
A
INDICATES RECEPTACLE ROUGH-IN HEIGHT FROM AFF TO CL OF
RECEPTACLE WHEN NOT AT STANDARD MOUNTING HEIGHT.+48"
INDICATES PANELBOARD AND BRANCH CIRCUIT NUMBER SERVING
RECEPTACLE.
2P1:12
INDICATES BRANCH CIRCUIT NUMBER SERVING RECEPTACLE. REFER TO
SHEET NOTES AND REFERENCE NOTES FOR SOURCE.
SURFACE MOUNTED RACEWAY WITH DUPLEX RECEPTACLES
RACEWAYS, BOXES, AND CONDUCTORS
ELECTRICAL EQUIPMENT - PLANS
WIRING DEVICES
ELECTRICAL EQUIPMENT AS NOTED
AUTOMATIC TRANSFER SWITCH
LV -1
3PH 4W
208V 225A
PANELBOARD WITH CHARACTERISTICS AS NOTED. WHERE NO
CHARACTERISTICS NOTED, SEE PANEL SCHEDULES.
PB PULL BOX, DIMENSIONS AS NOTED OR AS REQUIRED
T
T
T
SERVICE TRANSFORMER, PAD-MOUNTED
SERVICE TRANSFORMER, WITH VAULT
DISTRIBUTION TRANSFORMER
G
GENERATOR
PHOTOVOLTAIC INVERTER
ONE-LINE DIAGRAM
CIRCUIT BREAKER WITH CHARACTERISTICS AS NOTED
200A 3P
CIRCUIT BREAKER WITH INTEGRAL GROUND FAULT PROTECTIONG
200A 3P
SWITCH WITH CHARACTERISTICS AS NOTED200A
3P
200AS
200AF
3P
FUSED SWITCH WITH CHARACTERISTICS AS NOTED.
AS = SWITCH RATING, AF = FUSE RATING.
200A
200AS
200AF
SURGE PROTECTIVE DEVICE
EQUIPMENT CONNECTION
3000B FEEDER TAG. SEE FEEDER SCHEDULE.
E
FEEDER CONTINUATION CALLOUT. SEE CALLOUT ON DRAWING IDENTIFIED
WITH THE SAME LETTER TAG.
SECURITY AND ACCESS CONTROL
KP
GENERAL
ABBREVIATIONS
(#) DESIGNATES QUANTITY
A AMPERE (AMP)
AC ALTERNATING CURRENT
AFC AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AL ALUMINUM
ARCH ARCHITECT/ARCHITECTURAL
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BLDG BUILDING
BOCT BOTTOM OF CABLE TRAY
BSC BIOLOGICAL SAFETY CABINET
C. CONDUIT
CENT CENTRIFUGE
CKT CIRCUIT
CL CENTERLINE
CLG CEILING
CRI COLOR RENDERING INDEX
CU COPPER
DC DIRECT CURRENT
DF DRINKING FOUNTAIN
DW DISHWASHER
(E) EXISTING
ECR ENVIRONMENTAL CONTROL ROOM
ELEC ELECTRICAL
EMERG EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EV ELECTRIC VEHICLE
FA FIRE ALARM
FH FUME HOOD
FLA FULL LOAD AMPS
FTL FEED-THROUGH LUGS
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTION
GND GROUND
HP HORSEPOWER
IDF INTERMEDIATE DISTRIBUTION FRAME
INC INCUBATOR
K KELVIN
KW KILOWATT
KWH KILOWATT-HOUR
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
LED LIGHT EMITTING DIODE
LM LUMENS
LV LOW VOLTAGE
LSI LSI ELECTRONIC TRIP UNIT
LSI/G LSI/G ELECTRONIC TRIP UNIT
LTG LIGHTING
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDF MAIN DISTRIBUTION FRAME
MDS MAIN DISTRIBUTION SWITCHBOARD
MDP MAIN DISTRIBUTION PANELBOARD
MECH MECHANICAL
MLO MAIN LUG ONLY
MTS MAIN TRANSFER SWITCH
MVA MEGAVOLT-AMPERE
MW MEGAWATT
(N) NEW
(NL) NEW LOCATION
NA NOT APPLICABLE
NIC NOT IN CONTRACT
PA PUBLIC ADDRESS
PE PHOTOELECTRIC CELL
PF POWER FACTOR
PNL PANELBOARD
PV PHOTOVOLTAIC
PVC POLYVINYL CHLORIDE
PWR POWER
(R) REMOVE
(RL) RELOCATE
REFL REFLECTOR
SCCR SHORT CIRCUIT CURRENT RATING
SDP SUB-DISTRIBUTION PANELBOARD
SWBD SWITCHBOARD
TR TAMPER RESISTANT
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UC UNDER CABINET
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTAGE
VA VOLT-AMPERE
VP VAPOR PROOF
W WATT
WP WEATHERPROOF
XFMR TRANSFORMER
PT1
ELECTRICAL EQUIPMENT DESIGNATIONS
4 E - SWB - D1 A
VOLTAGE
POWER SOURCE
EQUIPMENT TYPE
2 - 208Y/120V (3-PHASE)
4 - 480Y/277V (3-PHASE)
N - NORMAL POWER (ELECTRIC UTILITY)
E - EMERGENCY POWER (GENERATOR, NEC 700)
R - REQUIRED STANDBY POWER (GENERATOR, NEC 701)
S - OPTIONAL STANDBY POWER (GENERATOR, NEC 702)
BLANK - PANELBOARD
SWB - SWITCHBOARD
T - TRANSFORMER
ATS - AUTOMATIC TRANSFER SWITCH
MTS - MANUAL TRANSFER SWITCH
GEN - GENERATOR
DS - DISCONNECT SWITCH
LOCATION BY BUILDING AND LEVEL
SERIES INDICATOR
D1 - DISTRICT UTILITY PLAN, LEVEL 1
CW1 - CORDLEY HALL WEST, LEVEL 1
CW2 - CORDLEY HALL WEST, LEVEL 2
CW3 - CORDLEY HALL WEST, LEVEL 3
CW4 - CORDLEY HALL WEST, LEVEL 4
CW5 - CORDLEY HALL WEST, LEVEL 5
A - FIRST IN A SERIES OF EQUIPMENT
B - SECOND IN A SERIES OF EQUIPMENT
ETC.
E1A-1 LAB EQUIPMENT DESIGNATOR, SEE SCHEDULES.
F
F
F
F
F S S
FACP
F T
MANUAL PULL STATION
FIRE ALARM
F S
F S
STROBE
HORN, SPEAKER
COMBINATION HORN/STROBE, COMBINATION SPEAKER/STROBE
SPRINKLER BELL, CHIME
FLOW SWITCH, TAMPER SWITCH
SMOKE DETECTOR
FIRE/SMOKE DAMPER, SMOKE DAMPER
FIRE ALARM CONTROL PANEL
FAAP FIRE ALARM ANNUNCIATOR PANEL
NAC NOTIFICATION APPLIANCE CIRCUIT EXTENDER
FSCP FIRE SUPPRESSION CONTROL PANEL
DH MAGNETIC DOOR HOLDER AND RELEASING DEVICE
DIGITAL POWER PACK CONCEALED IN CEILING WITH CHARACTERISTICS
AS NOTED. E = EMERGENCY, D = DIMMING (0-10VDC), a = ZONE
CONTROLLED.
CEILING-MOUNTED PHOTOELECTRIC CELL LIGHT LEVEL SENSOR.
A = SPECIAL TYPE (SEE OCCUPANCY SENSOR SCHEDULE).
WALL-MOUNTED OCCUPANCY SENSOR. A = SPECIAL TYPE (SEE
OCCUPANCY SENSOR SCHEDULE).
RELAY
WALL SWITCH WITH CHARACTERISTICS AS NOTED. a = ZONE CONTROLLED, K = KEYED SWITCH, P = WITH INTEGRAL PILOT LIGHT, 3 = THREE-WAY, 4 =
FOUR-WAY, OS = COMBINATION OCCUPANCY SENSOR AND WALL SWITCH,
D = MANUAL DIMMER, T = DIGITAL TIMER SWITCH.
CEILING SURFACE-MOUNTED LUMINAIRE
RECESSED LUMINAIRE
ROUND SUSPENDED LUMINAIRE
SHADING INDICATES LUMINAIRE PROVIDES ILLUMINATION FOR EMERGENCY
EGRESS. SHADING VARIES WITH EACH LUMINAIRE TYPE.
LINEAR CEILING SURFACE-MOUNTED LUMINAIRE
LINEAR SUSPENDED LUMINAIRE
LINEAR WALL-MOUNTED LUMINAIRE
SURFACE WALL-MOUNTED LUMINAIRE
RECESSED WALL-MOUNTED LUMINAIRE
CEILING SURFACE-MOUNTED LUMINAIRE
CEILING SURFACE-MOUNTED ASYMMETRIC LUMINAIRE
CEILING RECESSED LUMINAIRE
RECESSED ASYMMETRIC DOWNLIGHT
POLE-MOUNTED LUMINAIRE
POST TOP LUMINAIRE
ILLUMINATED BOLLARD
TRACK LIGHTING, NUMBER AND TYPE OF HEADS AS SHOWN
WALL MOUNTED EXIT SIGN, SHADING INDICATES FACES
CEILING MOUNTED EXIT SIGN, SHADING INDICATES FACES
CEILING-MOUNTED OCCUPANCY SENSOR. A = SPECIAL TYPE (SEE
OCCUPANCY SENSOR SCHEDULE).
DIGITAL WALL SWITCH. SEE WALL SWITCH SCHEDULE.
a = ZONE(S) CONTROLLED.
R
CEILING MOUNTED EXIT SIGN WITH INTEGRAL EMERGENCY LIGHTS AND
BATTERY PACK
SURFACE-MOUNTED EMERGENCY LIGHT WITH INTEGRAL BATTERY PACK
PP
E,a
LIGHTING
WALL-MOUNTED PHOTOELECTRIC CELL LIGHT LEVEL SENSOR.
A = SPECIAL TYPE (SEE OCCUPANCY SENSOR SCHEDULE).
LINEAR UNDER CABINET-MOUNTED LUMINAIRE
a
WS1 a
A1
LUMINAIRE TYPE IDENTIFIER. SEE LUMINAIRE SCHEDULE.
4N-CW1A:7
7 CONTROL ZONE IDENTIFIER
a
INDICATES PANELBOARD AND BRANCH CIRCUIT NUMBER SERVING LUMINAIRE.
INDICATES BRANCH CIRCUIT NUMBER SERVING LUMINAIRE. REFER TO SHEET
NOTES OR REFERENCE NOTES FOR SOURCE PANELBOARD.
OS
OS
PC
PC
A
A
A
A
TELECOMMUNICATIONS OUTLET, CONDUIT AND BACKBOX ONLY
REFER TO SPECIFICATIONS.
WIRELESS ACCESS POINT, CEILING MOUNTED WIRELESS ACCESS POINT
TELECOMMUNICATIONS OUTLET WITHIN COMBINES SERVICE FLUSH
FLOOR BOX. REFER TO SPECIFICATIONS AND SCHEDULES FOR DEVICE
QUANTITIES AND TYPES.
COAXIAL CABLE OUTLET, COMBINATION COAXIAL AND DATA OUTLET
TELECOMMUNICATIONS
W W
FB1
TV TV
D
SINGLE BED STATION
NURSE ASSIST BUTTON
NURSE CALL STATION. B = BED COMMUNICATION OUTLET, CB = CODE
BLUE, D = DUTY STATION, E = EMERGENCY STATION, NA = NURSE ASSIST
ANNUNCIATOR, N = NURSE LOCATOR STATION, M = PATIENT MONITORING
OUTLET, S = STAFF STATION, U = UTILITY STATION
DOME LIGHT (CEILING AND WALL MOUNTED)
NURSE CALL
ZONE DOME LIGHT (CEILING AND WALL MOUNTED)
NURSE CALL MASTER STATION
B
NCM
ELECTRIC LOCKEL
AC-E-N14A
HEAT DETECTOR
DUCT SMOKE DETECTOR
FUTURE EV CHARGING STATION (ROUGH-IN ONLY)
WALL-MOUNTED EV CHARGING STATION. SINGLE-PORT, DUAL-PORT.
PEDESTAL-MOUNTED EV CHARGING STATION. SINGLE-PORT, DUAL-PORT.
NUMERICAL DESIGNATOR INDICATES EV CHARGING STATION TYPE.
2 = FUTURE LEVEL 2 EV CHARGING STATION, LEVEL 2 EV CHARGING
STATION
3 = FUTURE LEVEL 3 EV CHARGING STATION, LEVEL 3 EV CHARGING
STATION
2 2
F
725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com
DATE:
DRAWN:
CHECKED:
PROJECT:
DESIGNED:
OWNER:
MARK DATE DESCRIPTION
/7
/2
:3
:5
A
M P
LO
T
T E
D B
Y A
JV
O
N
D P
S S
T V
R F
R E
P
LA
C E
M E
N T
STATE OF OREGON
LEGEND, GENERAL
NOTES, & SHEET
LIST
08.07.2026
240024.01
E001
AJV/BRE
AJV
BRE/MBR
D E
P A
R T
M E
N T
O F
P U
B
LI
C S
A F
E T
Y S
T A
N D
A R
D S
A N
D T
R A
IN
IN
G
A um sv ill e H ig hw ay S
E S al em
, O R
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
SHEET LIST - ELECTRICAL
E001 LEGEND, GENERAL NOTES, & SHEET LIST
E101 DEMOLITION PLANS - NE
E102 DEMOLITION PLANS - SE
E121 FLOOR PLANS - NE
E122 FLOOR PLAN - SE
E601 SCHEDULES
© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)
EXP IRES : 12 - 3 1- 26
MA Y 21, 2014
RE
GI
STE
RED PROFESSIONALENGINEER# 80,621
OREGONM
A T
THEW B. R
E I
C
E10
E9
CUSTODIAN
E 128N
LAUNDRY
E 129N
N HALL
E 101N
ELECTRICAL
E 127N
DORM E
E 126N
BATH C
E 125N
COMPUTER LAB
E 105C
GUN STORAGE
E 106C
EH EJ EK EL EM
E11
E10
E9
STORAGE
E 229N
MDF/IDF
E 226N
N HALL
E 201N ELECTRICAL
E 227N
DORM E
E 225N
BATH C
E 224N
DORM D
E 211C
DORM C
E 209C
BATH B
E 210CBATH A
E 213C
DORM A
E 214C
DORM B
E 212C
1 1
EH EJ EK EL EM
E11
E10
E9
EH EJ EK EL EM
E11
E10
E9
E-L3N SECT 1
E-L3N SECT 2
E-L3N SECT 3
DORM E
E 325N
BATH C
E 324N
MDF/IDF
E 326N
N HALL
E 301N
LAUNDRY
E 328N
STORAGE
E 329N
DORM B
E 312C
DORM A
E 314C
BATH A
E 313C
DORM D
E311C
BATH B
E 310C
DORM C
E 309C
ELECTRICAL
E 327N
KEY PLAN
NOT TO SCALE
725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com
DATE:
DRAWN:
CHECKED:
PROJECT:
DESIGNED:
OWNER:
MARK DATE DESCRIPTION
AREA OF WORK
/7
/2
:3
:5
A
M P
LO
T
T E
D B
Y A
JV
O
N
D P
S S
T V
R F
R E
P
LA
C E
M E
N T
STATE OF OREGON
DEMOLITION
PLANS - NE
08.07.2026
240024.01
E101
AJV/BRE
AJV
BRE/MBR
D E
P A
R T
M E
N T
O F
P U
B
LI
C S
A F
E T
Y S
T A
N D
A R
D S
A N
D T
R A
IN
IN
G
A um sv ill e H ig hw ay S
E S al em
, O R
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
S H E E T N O T E S :
R E F E R E N C E N O T E S :
1. FOR DEMOLISHED EQUIMENT SHOWN ON THIS SHEET: RETAIN AND PROTECT
EXISTING CONDUCTORS AND CONDUIT PATHWAYS FOR USE IN NEW WORK.
NORTH
1/8" = 1'-0"1
ELECTRICAL FIRST FLOOR DEMOLITION PLAN - NE
NORTH
1/8" = 1'-0"2
ELECTRICAL SECOND FLOOR DEMOLITION PLAN - NE
NORTH
1/8" = 1'-0"3
ELECTRICAL THIRD FLOOR DEMOLITION PLAN - NE
NORTH
1/8" = 1'-0"4
ELECTRICAL ROOF DEMOLITION PLAN - NE
DISCONNECT EXISTING MECHANICAL EQUIPMENT AND SALVAGE TO OWNER.
COORDINATE WITH MECHANICAL PRIOR TO COMMENCING WORK.
DISCONNECT AND RETAIN LIGHT FIXTURE TO FACILITATE MECHANICAL
CHANGES. RETAIN CIRCUIT AND CONTROLS FOR USE IN NEW WORK.
© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)
EXP IRES : 12 - 3 1- 26
MA Y 21, 2014
RE
GI
STE
RED PROFESSIONALENGINEER# 80,621
OREGONM
A T
THEW B. R
E I
E4
(E) E-L3S SECT 3
(E) E-L3S SECT 2
(E) E-L3S SECT 1
STORAGE
E 321S
CUST
E 322S
ELECTRICAL
E 323S
IDF
E 324S
DORM E
E 325S
BATH C
E 326S
DORM B
E 320S
BATH A
E 319S
EG EH EJ EK EL EM
E5
E4
EG EH EJ EK EL EM
E5
E4
1 1
BOILER/CUST
E 119S
MAINTENANCE
E 121S
S HALL
E 101S
STUDENT REC
E 122S
EG EH EJ EK EL EM
E5
E4
CUST
E 222S
ELECTRICAL
E 223S
DORM E
E 225S
BATH C
E 226S
IDF
E 224S
S HALL
E 201S
STORAGE
E 221S
DORM B
E 220S
BATH A
E 219S
KEY PLAN
NOT TO SCALE
725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com
DATE:
DRAWN:
CHECKED:
PROJECT:
DESIGNED:
OWNER:
MARK DATE DESCRIPTION
AREA OF WORK
/7
/2
:3
:5
A
M P
LO
T
T E
D B
Y A
JV
O
N
D P
S S
T V
R F
R E
P
LA
C E
M E
N T
STATE OF OREGON
DEMOLITION
PLANS - SE
08.07.2026
240024.01
E102
AJV/BRE
AJV
BRE/MBR
D E
P A
R T
M E
N T
O F
P U
B
LI
C S
A F
E T
Y S
T A
N D
A R
D S
A N
D T
R A
IN
IN
G
A um sv ill e H ig hw ay S
E S al em
, O R
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
NORTH
1/8" = 1'-0"1
ELECTRICAL FIRST FLOOR DEMOLITION PLAN - SE
NORTH
1/8" = 1'-0"2
ELECTRICAL SECOND FLOOR DEMOLITION PLAN - SE
NORTH
1/8" = 1'-0"3
ELECTRICAL THIRD FLOOR DEMOLITION PLAN - SE
NORTH
1/8" = 1'-0"4
ELECTRICAL ROOF DEMOLITION PLAN - SE
S H E E T N O T E S :
R E F E R E N C E N O T E S :
1. FOR DEMOLISHED EQUIMENT SHOWN ON THIS SHEET: RETAIN AND PROTECT
EXISTING CONDUCTORS AND CONDUIT PATHWAYS FOR USE IN NEW WORK.
DISCONNECT EXISTING MECHANICAL EQUIPMENT AND SALVAGE TO OWNER.
COORDINATE WITH MECHANICAL PRIOR TO COMMENCING WORK.
DISCONNECT AND RETAIN LIGHT FIXTURE TO FACILITATE MECHANICAL
CHANGES. RETAIN CIRCUIT AND CONTROLS FOR USE IN NEW WORK.
© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)
EXP IRES : 12 - 3 1- 26
MA Y 21, 2014
RE
GI
STE
RED PROFESSIONALENGINEER# 80,621
OREGONM
A T
THEW B. R
E I
E10
E9
DORM E
E 126N
BATH C
E 125N
N HALL
E 101N
ELECTRICAL
E 127N
COMPUTER LAB
E 105C
GUN STORAGE
E 106C
CUSTODIAN
E 128N
LAUNDRY
E 129N
AC-E-N11
BC-E-N1
AC-E-N13
AC-E-N14
BC-E-N2
EH EJ EK EL EM
E11
E10
E9
DORM E
E 225N
BATH C
E 224N
MDF/IDF
E 226N
ELECTRICAL
E 227N
DORM D
E 211C
BATH B
E 210C
DORM C
E 209C
DORM A
E 214C
BATH A
E 213C
DORM B
E 212C
N HALL
E 201N
STORAGE
E 229N
LAUNDRY
E 228N
AC-E-N22
AC-E-N21
EH EJ EK EL EM
E11
E10
E9
CU-E-N1
EH EJ EK EL EM
E11
E10
E9
DORM B
E 312C
DORM A
E 314C
BATH A
E 313C
STORAGE
E 329N
LAUNDRY
E 328N
N HALL
E 301N
MDF/IDF
E 326N
ELECTRICAL
E 327N
DORM E
E 325N
BATH C
E 324N
DORM D
E311C
DORM C
E 309C
BATH B
E 310C
AC-E-N31
(E) E-L3N SECT 1
(E) E-L3N SECT 2
(E) E-L3N SECT 3
AC-E-N32
KEY PLAN
NOT TO SCALE
725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com
DATE:
DRAWN:
CHECKED:
PROJECT:
DESIGNED:
OWNER:
MARK DATE DESCRIPTION
AREA OF WORK
/7
/2
:3
:5
A
M P
LO
T
T E
D B
Y A
JV
O
N
D P
S S
T V
R F
R E
P
LA
C E
M E
N T
STATE OF OREGON
FLOOR PLANS - NE
08.07.2026
240024.01
E121
AJV/BRE
AJV
BRE/MBR
D E
P A
R T
M E
N T
O F
P U
B
LI
C S
A F
E T
Y S
T A
N D
A R
D S
A N
D T
R A
IN
IN
G
A um sv ill e H ig hw ay S
E S al em
, O R
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
S H E E T N O T E S :
R E F E R E N C E N O T E S :
1 REINSTALL SALVAGED FIXTURE. UTILIZE EXISTING CIRCUIT AND CONTROLS
RETAINED FROM DEMOLITION TO SERVE FIXTURE.
NORTH
1/8" = 1'-0"1
ELECTRICAL FIRST FLOOR PLAN - NE
NORTH
1/8" = 1'-0"2
ELECTRICAL SECOND FLOOR PLAN - NE
NORTH
1/8" = 1'-0"3
ELECTRICAL THIRD FLOOR PLAN - NE
NORTH
1/8" = 1'-0"4
ELECTRICAL ROOF PLAN - NE
1. FOR ALL NEW MECHANICAL EQUIPMENT SHOWN ON THIS SHEET: UTILIZE EXISTING
FEEDER AND CONDUIT PATHWAY MADE AVAILABLE DURING DEMOLITION TO SERVE
EQUIPMENT. INTERCEPT AND EXTEND FEEDERS AND PATHWAY AS NECESSARY TO
CONSTRUCT A FUNCTIONAL SYSTEM.
© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)
EXP IRES : 12 - 3 1- 26
MA Y 21, 2014
RE
GI
STE
RED PROFESSIONALENGINEER# 80,621
OREGONM
A T
THEW B. R
E I
E4
DORM B
E 320S
BATH A
E 319S
STORAGE
E 321S
CUST
E 322S
ELECTRICAL
E 323S
IDF
E 324S
DORM E
E 325S
BATH C
E 326S
AC-E-S31
(E) E-L3S SECT 3
(E) E-L3S SECT 2
(E) E-L3S SECT 1
EG EH EJ EK EL EM
E5
E4
CU-E-S1
EG EH EJ EK EL EM
E5
E4
STUDENT REC
E 122S
S HALL
E 101S
MAINTENANCE
E 121S
BOILER/CUST
E 119S
ELECTRICAL
E118S
AC-E-S12
AC-E-S13
BC-E-S1
AC-E-S11
EG EH EJ EK EL EM
E5
E4
DORM E
E 225S
BATH C
E 226S
IDF
E 224S
ELECTRICAL
E 223S
CUST
E 222S
S HALL
E 201S
STORAGE
E 221S
DORM B
E 220S
BATH A
E 219S
AC-E-S21
KEY PLAN
NOT TO SCALE
725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com
DATE:
DRAWN:
CHECKED:
PROJECT:
DESIGNED:
OWNER:
MARK DATE DESCRIPTION
AREA OF WORK
/7
/2
:3
:5
A
M P
LO
T
T E
D B
Y A
JV
O
N
D P
S S
T V
R F
R E
P
LA
C E
M E
N T
STATE OF OREGON
FLOOR PLAN - SE
08.07.2026
240024.01
E122
AJV/BRE
AJV
BRE/MBR
D E
P A
R T
M E
N T
O F
P U
B
LI
C S
A F
E T
Y S
T A
N D
A R
D S
A N
D T
R A
IN
IN
G
A um sv ill e H ig hw ay S
E S al em
, O R
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
NORTH
1/8" = 1'-0"1
ELECTRICAL FIRST FLOOR PLAN - SE
NORTH
1/8" = 1'-0"2
ELECTRICAL SECOND FLOOR PLAN - SE
NORTH
1/8" = 1'-0"3
ELECTRICAL THIRD FLOOR PLAN - SE
S H E E T N O T E S :
1. FOR ALL NEW MECHANICAL EQUIPMENT SHOWN ON THIS SHEET: UTILIZE EXISTING
FEEDER AND CONDUIT PATHWAY MADE AVAILABLE DURING DEMOLITION TO SERVE
EQUIPMENT. INTERCEPT AND EXTEND FEEDERS AND PATHWAY AS NECESSARY TO
CONSTRUCT A FUNCTIONAL SYSTEM.
2. CONTRACTOR TO PERFORM 30-DAY METERING ON EXISTING PANEL E-L3N PER NEC
220.87 TO DETERMINE AVAILABLE AMPACITY FOR THE ADDITION OF NEW
CONDENSING UNIT CU-E-N2.
NORTH
1/8" = 1'-0"4
ELECTRICAL ROOF PLAN - SE
© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)
EXP IRES : 12 - 3 1- 26
MA Y 21, 2014
RE
GI
STE
RED PROFESSIONALENGINEER# 80,621
OREGONM
A T
THEW…