Attachment C-Drawings~2.pdf

PDF 4 MB Posted

Attached to
VRF Cooling System Replacement
Solicitation number
S-DASOBO-00017473
Issued by
Oregon

About this file

This is a construction document cover sheet and mechanical legend for the VRF Cooling System Replacement project at the Department of Public Safety Standards and Training (DPSST) facility located at 4190 Aumsville Highway SE in Salem, Oregon. The project, dated August 7, 2026, involves the removal of the current building VRF cooling system with two towers in Building E and the installation of a new cooling system, including associated ductwork, testing and balancing, and staff training. The work requires integration with the existing building automation system. The engineering design was prepared by Systems West Engineers (Springfield, OR), with Charlie White serving as Project Manager, and Michael Anderson as the DPSST Facilities Manager serving as the owner's contact. The construction documents are at 100 percent completion stage and include mechanical and electrical drawings with demolition plans, floor plans, details, schedules, and diagrams for both northeast and southeast building sections.

The document provides the sheet index and legend for the mechanical plans, including symbols and abbreviations for various hydronic systems, ductwork types, natural gas, fuel oil, liquefied petroleum gas, chilled water systems, heating water systems, condensate drains, and steam systems at varying pressures. The construction documents are digitally signed by registered Professional Engineer Nate J. Jenkins (License #95772) and expire on June 30, 2027. No pricing, specific quantities, response deadlines, or contract award information is contained within this cover sheet document.

View the file

Other files

File Type Posted
S-DASOBO-00017473-ITB.pdf PDF
Attachment B-Technical Specifications.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NORTH

NORTH

725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com

DATE:

DRAWN:

CHECKED:

PROJECT:

DESIGNED:

OWNER:

MARK DATE DESCRIPTION

SALEM, OREGON

AUGUST 7TH, 2026

S H E E T I N D E X

K E Y P L A NV I C I N I T Y M A P

NOT TO SCALE

NOT TO SCALE

OWNER:

DEPARTMENT of PUBLIC SAFETY STANDARDS and TRAINING 4190 Aumsville Highway SE Salem, OR 97317 Contact: Mr. Michael Anderson Facilities Manager

p. 503.373.7055 michael.anderson@state.or.us

MECHANICAL & ELECTRICAL:

Systems West Engineers

725 A Street Springfield, OR 97477

p. 541.342.7210 www.systemswestengineers.com Contact: Charlie White, PM cwhite@systemswestengineers.com

AREA OF WORK

AREA OF WORK

/1

/2

:3

:4

A

M P

LO

T

T E

D B

Y J

S H

O N

D P

S S

T V

R F

R E

P

LA

C E

M E

N T

STATE OF OREGON

COVER SHEET -

CONTACTS,

VICINITY MAP, SITE

MAP & SHEET LIST

08.07.2026

240024.01

G001

JSH

JSH

NJJ

STATE OF OREGON

DEPARTMENT OF PUBLIC SAFETY

STANDARDS AND TRAINING

100% CONSTRUCTION DOCUMENTS

DPSST VRF REPLACEMENT

D E

P A

R T

M E

N T

O F

P U

B

LI

C S

A F

E T

Y S

T A

N D

A R

D S

A N

D T

R A

IN

IN

G

A um sv ill e H ig hw ay S

E S al em

, O R

0%

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

G001 COVER SHEET - CONTACTS, VICINITY MAP, SITE MAP & SHEET LIST

M001 LEGEND, GENERAL NOTES, & SHEET LIST

M101 DEMOLITION PLANS - NE

M102 DEMOLITION PLANS - SE

M121 FLOOR PLANS - NE

M122 FLOOR PLANS - SE

M501 DETAILS

M601 SCHEDULES

M621 DIAGRAMS

E001 LEGEND, GENERAL NOTES, & SHEET LIST

E101 DEMOLITION PLANS - NE

E102 DEMOLITION PLANS - SE

E121 FLOOR PLANS - NE

E122 FLOOR PLAN - SE

E601 SCHEDULES

© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)

EXPIRES: 06-30-2027

JA NUA RY 14 , 2020

DIGITALLY SIGNED

RE

GI

STERED PROFESSIONALENGINEER# 95772

OREGONN

A

T

E

J . J E NK

I N S

P PP

M E C H A N I C A L L E G E N D

TYPES

DUCTWORK GENERAL

CONTROL SYMBOLS

GENERAL NOTES

SYMBOL ABBREV. DESCRIPTION

HYDRONIC

G(*)

FOS

FOR

LPG

CWS

CWR

HS

HR

CD

CDS

CDR

HRS

HRR

CBR

CBS

GWS

GWR

SMS

SMR

HPS

MPS

LPS

HPR

MPR

LPR

VR

PR

RL

RS

RHG

W

IR

NATURAL GAS (*=SUPPLY PRESSURE)

FUEL OIL SUPPLY

FUEL OIL RETURN

LIQUEFIED PETROLEUM GAS

CHILLED WATER SUPPLY

CHILLED WATER RETURN

HEATING WATER SUPPLY

HEATING WATER RETURN

CONDENSATE DRAIN

CONDENSER WATER SUPPLY

CONDENSER WATER RETURN

HEAT RECOVERY SUPPLY

HEAT RECOVERY RETURN

CHILLED BEAM WATER SUPPLY

CHILLED BEAM WATER RETURN

GEOTHERMAL WATER SUPPLY

GEOTHERMAL WATER RETURN

SNOW MELT WATER SUPPLY

SNOW MELT WATER RETURN

HIGH PRESSURE STEAM >60 psi

MEDIUM PRESSURE STEAM 15 psi-60 psi

LOW PRESSURE STEAM <15 psi

HIGH PRESSURE CONDENSATE RETURN

MEDIUM PRESSURE CONDENSATE RETURN

LOW PRESSURE CONDENSATE RETURN

VACUUM CONDENSATE RETURN

PUMPED CONDENSATE RETURN

REFRIGERANT LIQUID

REFRIGERANT SUCTION

REFRIGERANT HOT GAS

WATER SERVICE

IRRIGATION

DV

BV

BFV

CHV

GV

GBV

PRV

AV

SV

AV

AV

AV

RV

SRV

SSV

TPS

FMS

ABBREV ABBREVIATION

ACH AIR CHANGES PER HOUR

AD ACCESS DOOR

AFF ABOVE FINISHED FLOOR

AFS AUTOMATIC FIRE SPRINKLER

AI ANALOG INPUT

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

AO ANALOG OUTPUT

APD AIR PRESSURE DROP

AWT AVERAGE WATER TEMPERATURE

BAS BUILDING AUTOMATION SYSTEM

BHP BRAKE HORSEPOWER

BOD BOTTOM OF DUCT

BTUH BRITISH THERMAL UNITS PER HOUR

CFH CUBIC FEET per HOUR CFM CUBIC FEET per MINUTE

CMU CONCRETE MASONRY UNIT

CONC CONCRETE

CONT CONTINUATION

CU FT CUBIC FEET

D DEPTH

(D) DEMOLITION

DB DRY BULB

dBa DECIBELS ACOUSTIC

DDC DIRECT DIGITAL CONTROL

DEMO DEMOLITION

DI DIGITAL INPUT

DN DOWN

DO DIGITAL OUTPUT

DP DIFFERENTIAL PRESSURE

DX DIRECT EXPANSION

(E) EXISTING

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

ECM ELECTRONICALLY COMMUTATED MOTOR

EER ENERGY EFFICIENCY RATIO

EFF EFFICIENCY

EG EXHAUST GRILLE

PIPING UP

PIPING DOWN

DIRECTION OF SLOPE

CAPPED PIPE

PIPE REDUCING FITTING:

CONCENTRIC, ECCENTRIC

DIRECTION OF FLOW

DRAIN VALVE WITH HOSE

CONNECTION

UNION

BALL VALVE

BUTTERFLY VALVE

CHECK VALVE

GATE VALVE

GLOBE VALVE

BALANCING VALVE /

ECCENTRIC PLUG VALVE

AUTOMATIC CONTROL

VALVE: 2-WAY

AUTOMATIC CONTROL

VALVE: 3-WAY

AUTOMATIC BUTTERFLY VALVE

FLEXIBLE PIPE CONNECTION

WYE STRAINER

BASKET STRAINER

PRESSURE REGULATING VALVE

THREE-WAY BYPASS VALVE

SOLENOID VALVE

RELIEF VALVE

SAFETY RELIEF VALVE

(HYDRONIC)

STEAM SAFETY VALVE

TEMPERATURE/PRESSURE

SAFETY VALVE

SELF CONTAINED CONTROL VALVE

CONSOLIDATED FITTING RETURN

CONSOLIDATED FITTING SUPPLY

THERMOMETER

PRESSURE GAUGE

TEST PLUG

SIGHT FLOW INDICATOR

SENSOR WELL

MANUAL AIR VENT

AUTOMATIC AIR VENT

VENTURI

WATER FLOW METER

FLOW MEASURING STATION

1. THE FACILITY WILL REMAIN IN OPERATION DURING CONSTRUCTION. COORDINATE ALL

SHUTDOWNS AND CONSTRUCTION ACTIVITY WITH FACILITIES STAFF.

2. SIZE AND LOCATION OF ALL PIPING AND OTHER MECHANICAL EQUIPMENT IS APPROXIMATE.

CONTRACTOR SHALL SITE VERIFY THE LOCATION OF EXISTING PIPING AND EQUIPMENT AND

CONSTRUCT WORK FROM FIELD DIMENSIONS. CONTRACTOR SHALL MAKE ADJUSTMENTS NECESSARY

TO ACCOMMODATE MINOR DEVIATIONS AT NO COST TO OWNER.

3. FINE (LIGHT) LINE WORK INDICATES EXISTING PIPING AND OTHER MECHANICAL EQUIPMENT. BOLD

(HEAVY) LINE WORK INDICATES NEW PIPING AND OTHER MECHANICAL EQUIPMENT.

4. IT IS RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE CUTTING AND PATCHING TO

ALLOW THE INSTALLATION OF MATERIALS AND EQUIPMENT AS SPECIFIED AND SHOWN ON DRAWINGS.

SYMBOL ABBREV. DESCRIPTION

SYMBOL DESCRIPTION SYMBOL DESCRIPTION

SYMBOL DESCRIPTION

(E) ø OR dia

SHEET NUMBER

SECTION LETTER

SHEET NUMBER

EXISTING

DIAMETER

NEW TO EXISTING POINT OF CONNECTION

NOTE REFERENCE MARKER

PLAN OR DETAIL REFERENCE MARKER

SECTION REFERENCE MARKER W/VIEW DIRECTION

EQUIPMENT MARKER

ROOM NUMBER

EXISTING SHOWN LIGHT

NEW WORK SHOWN BOLD

EXISTING TO BE REMOVED

M-301

Room Name

PLAN OR DETAIL NUMBER

SYMBOL DESCRIPTION

RECTANGULAR SUPPLY AIR DUCT UP

RECTANGULAR RETURN AIR DUCT UP

RECTANGULAR EXHAUST AIR UP

RECTANGULAR OUTSIDE AIR UP

RECTANGULAR SUPPLY AIR, &

MAKE-UP AIR DUCT DOWN

RECTANGULAR RETURN AIR DOWN

RECTANGULAR EXHAUST AIR or

OUTSIDE AIR DOWN

SA

RA

EA

OSA

ROUND DUCTWORK UP

ROUND DUCTWORK DOWN

TURN VANE ELBOW

STANDARD RADIUS ELBOW

FLEXIBLE DUCT CONNECTION

DUCT SIZE: WIDTH (IN) x DEPTH (IN) 12x6

DIFFUSER TYPE

SIZE - BLOW PATTERN (4-WAY IF NONE SHOWN)

AIR VOLUME IN CUBIC FEET per MINUTE (CFM)

GRILLE TYPE

SIZE

AIR VOLUME IN CUBIC FEET per MINUTE (CFM)

GRILLE TYPE

SIZE

AIR VOLUME IN CUBIC FEET per MINUTE (CFM)

GRILLE TYPE OR SIDE WALL DIFFUSER

SIZE

AIR VOLUME IN CUBIC FEET per MINUTE (CFM)

INTERNALLY LINED OR DOUBLE WALL

DUCTWORK

MANUAL BALANCING DAMPER

CONCENTRIC TRANSITION

ECCENTRIC TRANSITION

TEE FITTING

(RECTANGULAR)

LATERAL BRANCH

(ROUND OR OVAL)

WYE FITTING

(RECTANGULAR)

CONICAL BRANCH

(ROUND OR OVAL)

BEVELED BRANCH

(RECTANGULAR, ROUND, OR OVAL)

F FIRE SPRINKLER SUPPLY

CW POTABLE COLD WATER

HW POTABLE HOT WATER

HWR POTABLE HOT WATER RETURN

TW POTABLE TEMPERED HOT WATER

NP NON-POTABLE COLD WATER

W SANITARY WASTE

AW ACID WASTE

PW

GW

AV

D

SD

OD

PUMPED WASTE

GREASE WASTE

V VENT

ACID VENT

DRAIN

STORM DRAIN

OVERFLOW DRAIN

PSW PUMPED STORM WATER

EG-1

12"x10"

RG-1

12"x10"

EG-1

8"x4"

RECTANGULAR DUCT ANGLED CHANGE IN

ELEVATION

ROUND DUCT ANGLED CHANGE IN ELEVATION

SD-1

10"x10"

DEMOLITION NOTES

1. REVIEW DEMOLITION DRAWINGS FOR ITEMS TO REMAIN, TO BE RETAINED FOR RELOCATION, OR TO BE

SALVAGED TO THE OWNER. REFER TO ARCHITECTURAL DOCUMENTS FOR ADDITIONAL REQUIREMENTS.

2. DEMOLISH EQUIPMENT, FIXTURES, DEVICES, PIPING, CONDUIT, FITTINGS, AND APPURTENANCES INTERIOR TO THE BUILDING THAT ARE MADE OBSOLETE BY THE NEW WORK AND/OR ARE ABANDONED

AND NO LONGER IN USE.

3. PROTECT AND MAINTAIN OPERABLE EXISTING EQUIPMENT, FIXTURES, OR SYSTEMS THAT ARE

INDICATED TO REMAIN, INCLUDING ELECTRICAL POWER, CONTROLS, AND RELATED SYSTEMS

REQUIRED TO MAINTAIN OPERABILITY.

4. EXISTING CONDITIONS SHOWN ARE BASED ON RECORD DOCUMENTS AND LIMITED FIELD

OBSERVATIONS OF ACCESSIBLE AREAS AND MAY NOT SHOW THE ENTIRE SCOPE OF DEMOLITION

WORK. OMISSION OF EXISTING EQUIPMENT, FIXTURES, DEVICES, PIPING, CONDUIT, FITTINGS, AND APPURTENANCES FROM THE DEMOLITION DRAWINGS DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY TO PROVIDE DEMOLITION OF SYSTEMS THAT ARE MADE OBSOLETE BY THE NEW WORK, ARE ABANDONED, OR AS OTHERWISE REQUIRED TO PERFORM THE WORK DESCRIBED HEREIN.

5. PROTECT AND MAINTAIN SERVICES TO REMAIN OPERATIONAL THAT PASS THROUGH THE AREA OF CONSTRUCTION. WHERE IT IS NOT POSSIBLE TO MAINTAIN THESE SERVICES INTACT, REPLACE, REROUTE, MODIFY, OR PROVIDE NEW AS REQUIRED TO MAINTAIN SERVICES.

PACKAGE EQUIPMENT BOUNDRY

M-521

M101

RECTANGULAR MAKE-UP AIR DUCT UPMAS

A P

A P

A

HC

ABBREV.

DP

P

PROCESS PIPING SIGNAL

ELECTRICAL SIGNAL

SPACE TEMPERATURE

SPACE HUMIDITY

SPACE CARBON DIOXIDE

SPACE MULTIFUNCTION

PRESSURE MEASUREMENT

TEMPERATURE MEASUREMENT

HUMIDITY MEASUREMENT

FLOW MEASUREMENT

ELECTRICAL CURRENT/POWER

S = SENSOR

T = TRANSMITTER

FS = FLOW SWITCH

CO2 = CARBON DIOXIDE

CO = CARBON MONOXIDE

NO2 = NITROGEN DIOXIDE

GAS CONCENTRATION

T

FP

HP = HIGH PRESSURE SWITCH

LP = LOW PRESSURE SWITCH

A ACTUATOR

A

ES

AI

ALARM

VFD

CWP-2

AUTOMATIC CONTROL

DAMPER

BAS INPUT/OUTPUT POINT

EMERGENCY STOP SWITCH

AI = ANALOG INPUT

AO = ANALOG OUTPUT

DI = DIGITAL INPUT

DO = DIGITAL OUTPUT

FUNCTION DESIGNATION

S/S = START/STOP

CP = CONTROL PANEL

BCP = BOILER CONTROL PANEL

CCP = CHILLER CONTROL PANEL

FAP = FIRE ALARM PANEL

MC = MOTOR CONTROLLER

VFD = VARIABLE FREQUENCY DRIVE

T

P

H

F

G

CO2

SD SMOKE DETECTOR

E C

RELAY FREEZE PROTECTION

RELAY

DP = DIFFERENTIAL PRESSURE

T

AHU-1

SPACE THERMOSTAT

FITTINGS

PIPING

STEAM

SYMBOL ABBREV. DESCRIPTION

VALVES

FUEL

REFRIGERANT

SITE (REFERENCE)

FIRE PROTECTION

SYMBOL ABBREV. DESCRIPTION

AUTOMATIC VALVES

AAV AUTOMATIC AIR VENT

AC AIR CONDITIONER

ACB ACTIVE CHILLED BEAM

AD AUTOMATIC DAMPER

AF AIR CURTAIN

AHU AIR HANDLING UNIT

AS AIR SEPARATOR

B BOILER

BD BALANCING DAMPER

BDD BACK DRAFT DAMPER

BF BOILER FEED

BF BOOSTER FAN

CB CHILLED BEAM

CC CHILLED WATER COIL

CFP CHEMICAL FEED PUMP

CFT CHEMICAL FEED TANK

CH CHILLER

CP CIRCULATING PUMP

CT COOLING TOWER

CU CONDENSING UNIT

CRU CONDENSATE RETURN UNIT

CV CONTROL VALVE

CWP CHILLED WATER PUMP

EAL EXHAUST AIR LOUVER

EDH ELECTRIC DUCT HEATER

EF EXHAUST FAN

EH EXHAUST HOOD

ET EXPANSION TANK

FC FAN COIL UNIT

FCD FLOW CONTROL DEVICE

FD FIRE DAMPER

FF FINAL FILTER

FSD FIRE SMOKE DAMPER

GF GLYCOL FEEDER

CC

HEATING WATER COIL

CHILLED WATER COIL

FLOW SWITCH

HRC HEAT RECOVERY COIL

SYMBOL ABBREV. DESCRIPTION

MISCELLANEOUS FITTINGS

DIFFUSERS AND GRILLES

SEE SPECIFICATIONS

SYMBOL DESCRIPTIONABBREV.

mA MILLIAMPERE

MA MIXED AIR

MAX MAXIMUM

MBH THOUSAND BTUs per HOUR

MCA MINIMUM CIRCUIT AMPACITY

MERV MINIMUM EFFICIANCY REPORTING VALUE

MFR MANUFACTURER

MIN MINIMUM

MIN EFF MINIMUM EFFICIENCY

MOP MAXIMUM OVERCURRENT PROTECTION

(N) NEW

NC NOISE CRITERIA

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NPLV NON-STANDARD PART LOAD VALUE

NPSH NET POSITIVE SUCTION HEAD

NR NOT REQUIRED

OAT OUTSIDE AIR TEMPERATURE

OCC OCCUPIED

OFCI OWNER FURNISHED/

CONTRACTOR INSTALLED

OSA OUTSIDE AIR

PD PRESSURE DROP

PH PHASE

PPH POUNDS per HOUR PSI POUNDS per SQUARE INCH PSIG POUNDS per SQUARE INCH GAUGE

RA RETURN AIR

RAT RETURN AIR TEMPERATURE

REQ'D REQUIRED

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RL REFRIGERANT LIQUID

RLA RUNNING LOAD AMPS

RS REFRIGERANT SUCTION

RPM REVOLUTIONS PER MINUTE

ABBREVIATIONS

EQUIPMENT ABBREVIATIONS

HC HOT WATER COIL

HP HEAT PUMP

HR HEAT RECOVERY EXCHANGER

HRC HEAT RECOVERY COIL

HRU HEAT RECOVERY UNIT

HRV HEAT RECOVERY VENTILATOR

HUM HUMIDIFER

HWP HEATING WATER PUMP

HX HEAT EXCHANGER

L LOUVER

LEF LABORATORY EXHAUST FAN

MUA MAKE UP AIR UNIT

MZ MULTI-ZONE

OAH OUTSIDE AIR HOOD

OBD OPPOSED BLADE DAMPER

OSAL OUTSIDE AIR LOUVER

P PUMP

PF PREFILTER

PHX POOL HEAT EXCHANGER

PTAC PACKAGED TERMINAL AIR

CONDITIONER

RF RETURN FAN

RH RELIEF HOOD

RTU ROOF TOP UNIT

SA SOUND ATTENUATOR

SF SUPPLY FAN

SG SUPPLY GRILLE

SHX STEAM HEAT EXCHANGER

ST STORAGE TANK

TP TOWER PUMP

TU TERMINAL UNIT

UH UNIT HEATER

VD VOLUME DAMPER

VP VACUUM PUMP

CONSOLIDATED SUPPLY FITTINGCFS

CONSOLIDATED RETURN FITTINGCFR

FLEXIBLE DUCT RUNOUT TO

DIFFUSER/GRILLE

PLUMBING

PUMP

PUMP SUCTION DIFFUSER

REDUCED PRESSURE

BACKFLOW PREVENTER

FD

FAN

EQUIPMENT

SYMBOL DESCRIPTIONABBREV.

FLOOR DRAIN

EQUIPMENT CONTROL PANEL

(W/EQUIP. INDICATED UNDERLINED)

EMS ENERGY MANAGEMENT SYSTEM

ENT ENTERING

ESP EXTERNAL STATIC PRESSURE

EWT ENTERING WATER TEMPERATURE

°F DEGREES FAHRENHEIT

FLA FULL LOAD AMPS

FP FIRE PROTECTION

FPM FEET PER MINUTE

FPS FEET PER SECOND

FT FEET

FT2 SQUARE FEET

FT WC FEET WATER COLUMN

FUT FUTURE

GALV GALVANIZED

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GYP BD GYPSUM WALL BOARD

H HEIGHT

HP HORSEPOWER

HR HEAT RECOVERY

HSPF HEATING SEASONAL

PERFORMANCE FACTOR

HVAC HEATING, VENTILATING,

& AIR CONDITIONING

HZ HERTZ (CYCLES PER SECOND)

IAQ INDOOR AIR QUALITY

IN INCHES

IN WC INCHES WATER COLUMN

IPLV INTEGRATED PART LOAD VALUE

IW INDIRECT WASTE

KW KILOWATT

L LENGTH

LAT LEAVING AIR TEMPERATURE

LBS POUNDS

LON LOCAL OPERATING NETWORK

LVG LEAVING

LWT LEAVING WATER TEMPERATURE

SA SUPPLY AIR

SAT SUPPLY AIR TEMPERATURE

SCFM STANDARD CUBIC FEET PER MINUTE

SD SUPPLY DIFFUSER

SEER SEASONAL ENERGY EFFICIENCY RATIO

SP STATIC PRESSURE

SS STAINLESS STEEL

STL STEEL

TEMP TEMPERATURE

TDH TOTAL DYNAMIC HEAD

TP TOTAL PRESSURE

TSP TOTAL STATIC PRESSURE

TYP TYPICAL

V VOLT

VFD VARIABLE FREQUENCY DRIVE

VP VELOCITY PRESSURE

VSD VARIABLE SPEED DRIVE

W WATTS

WB WET BULB

WPD WATER PRESSURE DROP

WC WATER COLUMN

WG WATER GAUGE

T

AHU-1

H

G

CO2

C

ROOM MARKER

ROOM NAME

SSV STEAM SAFETY VALVE

SIDESTREAM FILTRATION UNIT

MAV

AAV

S

CFR

CFS

A

RP

SD

W

FS

AC-E-N14A TYPE - NUMBER

MITERED WITH TURNING VANES

(RECTANGULAR, ROUND, OR OVAL)

MITERED WITHOUT TURNING VANES

(RECTANGULAR OR ROUND)

RADIUS

(RECTANGULAR OR ROUND)

ELBOWS

GORED

(OVAL)

MITERED RADIUS

MITERED RADIUS

WYE FITTING

(ROUND OR OVAL)

STRAIGHT BRANCH

(RECTANGULAR, ROUND, OR OVAL)

CO2 = CARBON DIOXIDE

CO = CARBON MONOXIDE

T = TEMPERATURE

H = HUMIDITY

G = GAS (CO2, CO)

FS

FMS

RO

MANUAL BALANCING DAMPER

(FLOW MEASUREING STATION)

MANUAL BALANCING DAMPER

(REMOTE OPERATION)

SMOKE DAMPER

FIRE / SMOKE DAMPER

(VERTICAL BLADE)

FIRE / SMOKE DAMPER

(HORIZONTAL BLADE)

FIRE DAMPER

SMOKE DETECTOR

BACKDRAFT DAMPER

AUTOMATIC CONTROL DAMPER

A

BD

SD

F

C

C1

S

FCV FLOW CONTROL VALVE

GRILLE TYPE

SIZE

AIR VOLUME IN CUBIC FEET per MINUTE (CFM)

SG-1

12"x10"

725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com

DATE:

DRAWN:

CHECKED:

PROJECT:

DESIGNED:

OWNER:

MARK DATE DESCRIPTION

/7

/2

:3

:1

A

M P

LO

T

T E

D B

Y F

R M

O N

D P

S S

T V

R F

R E

P

LA

C E

M E

N T

STATE OF OREGON

LEGEND, GENERAL

NOTES, & SHEET

LIST

08.07.2026

240024.01

M001

CLW

FRM

NJJ

D E

P A

R T

M E

N T

O F

P U

B

LI

C S

A F

E T

Y S

T A

N D

A R

D S

A N

D T

R A

IN

IN

G

A um sv ill e H ig hw ay S

E S al em

, O R

0%

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

SHEET LIST - MECHANICAL

M001 LEGEND, GENERAL NOTES, & SHEET LIST

M101 DEMOLITION PLANS - NE

M102 DEMOLITION PLANS - SE

M121 FLOOR PLANS - NE

M122 FLOOR PLANS - SE

M501 DETAILS

M601 SCHEDULES

M621 DIAGRAMS

H V A C D ES I G N C R I T E R I A

GENERAL

SITE ELEVATION

HEATING COOLING

DESIGN

AMBIENT (F°)

HEATING SPACE

TEMPERATURE (F°)

DESIGN AMBIENT

DRY BULB (F°)

DESIGN AMBIENT

WET BULB (F°)

COOLING SPACE

TEMPERATURE (F°)

NOTES

177' 20 70 93 67 75

© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)

EXPIRES: 06-30-2027

JA NUA RY 14 , 2020

DIGITALLY SIGNED

RE

GI

STERED PROFESSIONALENGINEER# 95772

OREGONN

A

T

E

J . J E NK

EH EJ EK EL EM

E11

E10

E9

1 1/4" CD

1 1/4" CD

1 1/4" CD

GUN STORAGE

E 106C

N HALL

E 101N

COMPUTER LAB

E 105C

DORM E

E 126N

BATH C

E 125N

ELECTRICAL

E 127N

N HALL

E 101N

CUSTODIAN

E 128N

LAUNDRY

E 129N

T

T

T

T 1 1/4" CD

EH EJ EK EL EM

E11

E10

E9

1 1/4" CD

DORM C

E 209C

DORM D

E 211C

BATH B

E 210CBATH A

E 213C

DORM B

E 212C

DORM A

E 214C

STORAGE

E 229N

ELECTRICAL

E 227N

DORM E

E 225N

BATH C

E 224N

MDF/IDF

E 226N

LAUNDRY

E 228N

N HALL

E 201N

T

T 9

EH EJ EK EL EM

E11

E10

E9

EH EJ EK EL EM

E11

E10

E9

1 1/4" CD1 1/4" CD

ELECTRICAL

E 327N

MDF/IDF

E 326N

DORM D

E311C

N HALL

E 301N

LAUNDRY

E 328N

STORAGE

E 329N

DORM B

E 312C

DORM A

E 314C

BATH A

E 313C

DORM C

E 309C

BATH B

E 310C

DORM E

E 325N

BATH C

E 324N T

9T

KEY PLAN

NOT TO SCALE

725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com

DATE:

DRAWN:

CHECKED:

PROJECT:

DESIGNED:

OWNER:

MARK DATE DESCRIPTION

AREA OF WORK

/7

/2

:3

:1

A

M P

LO

T

T E

D B

Y F

R M

O N

D P

S S

T V

R F

R E

P

LA

C E

M E

N T

STATE OF OREGON

DEMOLITION

PLANS - NE

08.07.2026

240024.01

M101

CLW

FRM

NJJ

D E

P A

R T

M E

N T

O F

P U

B

LI

C S

A F

E T

Y S

T A

N D

A R

D S

A N

D T

R A

IN

IN

G

A um sv ill e H ig hw ay S

E S al em

, O R

0%

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

R E F E R E N C E N O T E S :

1 REMOVE EXISTING VRF BRANCH CONTROLLER BOX AND ASSOCIATED REFRIGERANT

PIPING BETWEEN BRANCH CONTROLLER AND OUTDOOR UNIT. RETAIN CONDENSATE

PIPING FOR REUSE.

REMOVE EXISTING VRF FCU AND ASSOCIATED REFRIGERANT PIPING BETWEEN FCU

AND BRANCH CONTROLLER.

EXISITNG CONDENSATE DRAIN ROUTES TO MOP SINK. PRESERVE CONDENSATE DRAIN

FOR CONNECTION TO NEW FCU. VERIFY EXISTING ROUTING DOES NOT GO OVER

ELECTRICAL GEAR AND REROUTE IF NEEDED.

EXISTING TRANSFER AIR OPENING TO REMAIN.

REMOVE EXISTING CIRCULATION FAN AND ASSOCIATED DUCTWORK, CONTROLS, AND

SUPPORTS. PRESERVE OPENING IN WALL FOR NEW SUPPLY DUCTWORK.

DEMOLISH GYP CEILING AS NEEDED TO ACCESS CEILING SPACE FOR PIPING DEMO AND

INSTALLATION.

DEMOLISH PORTION OF CHASE AS NEEDED TO ACCESS PIPING FOR DEMO AND

INSTALLATION.

REMOVE EXISTING VRF OUTDOOR UNIT AND ASSOCIATED CONTROLS, SUPPORTS, AND

REFRIGERANT PIPING BETWEEN OUTDOOR UNIT AND INDOOR UNITS.

REMOVE ANY ABANDONED REFRIGERANT PIPING ASSOCIATED WITH DECOMISSIONED

WALL MOUNT UNIT IN MDF/IDF ROOM.

NORTH

1/8" = 1'-0"1

MECHANICAL FIRST FLOOR DEMOLITION PLAN - NE

NORTH

1/8" = 1'-0"2

MECHANICAL SECOND FLOOR DEMOLITION PLAN - NE

NORTH

1/8" = 1'-0"3

MECHANICAL THIRD FLOOR DEMOLITION PLAN - NE

NORTH

1/8" = 1'-0"4

MECHANICAL DEMOLITION ROOF PLAN - NE

© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)

EXPIRES: 06-30-2027

JA NUA RY 14 , 2020

DIGITALLY SIGNED

RE

GI

STERED PROFESSIONALENGINEER# 95772

OREGONN

A

T

E

J . J E NK

EG EH EJ EK EL EM

E5

E4

1 1/4" CD

DORM E

E 325S

BATH C

E 326S

CUST

E 322SDORM B

E 320S

BATH A

E 319S

DORM B

E 320S

STORAGE

E 321S

ELECTRICAL

E 323S

IDF

E 324S

T

EG EH EJ EK EL EM

E5

E4

EG EH EJ EK EL EM

E5

E4

1 1/4" CD

1 5

1 1/4" CD

ELECTRICAL

E118S

BOILER/CUST

E 119S

MAINTENANCE

E 121S

S HALL

E 101S

STUDENT REC

E 122S

T T

T

DEMOLISH VRF

CONTROLLER

EG EH EJ EK EL EM

E5

E4

DORM B

E 220S

BATH A

E 219S

STORAGE

E 221S

S HALL

E 201S

CUST

E 222S

DORM E

E 225S

IDF

E 224S

ELECTRICAL

E 223S

BATH C

E 226S

1-1/4" CD

T

KEY PLAN

NOT TO SCALE

725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com

DATE:

DRAWN:

CHECKED:

PROJECT:

DESIGNED:

OWNER:

MARK DATE DESCRIPTION

AREA OF WORK

/7

/2

:3

:1

A

M P

LO

T

T E

D B

Y F

R M

O N

D P

S S

T V

R F

R E

P

LA

C E

M E

N T

STATE OF OREGON

DEMOLITION

PLANS - SE

08.07.2026

240024.01

M102

CLW

FRM

NJJ

D E

P A

R T

M E

N T

O F

P U

B

LI

C S

A F

E T

Y S

T A

N D

A R

D S

A N

D T

R A

IN

IN

G

A um sv ill e H ig hw ay S

E S al em

, O R

0%

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

NORTH

1/8" = 1'-0"1

MECHANICAL FIRST FLOOR DEMOLITION PLAN - SE

NORTH

1/8" = 1'-0"2

MECHANICAL SECOND FLOOR DEMOLITION PLAN - SE

NORTH

1/8" = 1'-0"3

MECHANICAL THIRD FLOOR DEMOLITION PLAN - SE

R E F E R E N C E N O T E S :

1 REMOVE EXISTING VRF FCU AND ASSOCIATED REFRIGERANT PIPING BETWEEN FCU

AND BRANCH CONTROLLER.

EXISTING TRANSFER AIR OPENING TO REMAIN.

REMOVE EXISTING CIRCULATION FAN AND ASSOCIATED DUCTWORK, CONTROLS,

AND SUPPORTS. PRESERVE OPENING IN WALL FOR NEW SUPPLY DUCTWORK.

REMOVE EXISTING VRF OUTDOOR UNIT AND ASSOCIATED CONTROLS, SUPPORTS,

AND REFRIGERANT PIPING BETWEEN OUTDOOR UNIT AND INDOOR UNITS.

REMOVE EXISTING VRF BRANCH CONTROLLER BOX AND ASSOCIATED REFRIGERANT

PIPING BETWEEN BRANCH CONTROLLER AND OUTDOOR UNIT. RETAIN CONDENSATE

PIPING FOR REUSE.

DEMOLISH PORTION OF CHASE AS NEEDED TO ACCESS PIPING FOR DEMO AND

INSTALLATION.

NORTH

1/8" = 1'-0"4

MECHANICAL DEMOLITION ROOF PLAN - SE

© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)

EXPIRES: 06-30-2027

JA NUA RY 14 , 2020

DIGITALLY SIGNED

RE

GI

STERED PROFESSIONALENGINEER# 95772

OREGONN

A

T

E

J . J E NK

E10

E9

BC-E-N1

DORM E

E 126N

BATH C

E 125N

ELECTRICAL

E 127N

N HALL

E 101N

LAUNDRY

E 129N

CUSTODIAN

E 128N

GUN STORAGE

E 106C

COMPUTER LAB

E 105C(E

1/

4" C

D

AC-E-N13

AC-E-N11

RL/RS

RL/RS/RHG UP

TO CU-E-N1 ON

ROOF

RL/RS (TYP. OF 4)

1/2" CD

T

T

T

"x

S A

AC-E-N14

SD-1

12x12

344 CFM

SD-1

12x12

344 CFM

RG-1

14x14

688 CFM

38"x16" RA 14"ø RA

10"ø SA

10"ø SA

BC-E-N2

4 RL/RS/RHG

RL/RS

RL/RS

1/2" CD

(E) 1 1/4" CD

(E) 1 1/4" CD

1" CD

EH EJ EK EL EM

E11

E10

E9

(E) 1 1/4" CDLAUNDRY

E 228N

STORAGE

E 229N

N HALL

E 201N

MDF/IDF

E 226N

ELECTRICAL

E 227N

DORM E

E 225N

BATH C

E 224N

DORM D

E 211C

BATH B

E 210C

DORM C

E 209C

BATH A

E 213C

DORM B

E 212C

DORM A

E 214C

AC-E-N21

AC-E-N22

(E) 24"x10" TA

1" CD

RL/RS

RL/RS

1/2" CD

RL/RS (TYP. OF 4) DN TO

BC-E-N1 ON FIRST FLOOR

T T

SG-1

30x10

688 CFM

RL/RS/RHG UP & DN

EH EJ EK EL EM

E11

E10

E9

CU-E-N1

RL/RS/RHG

EH EJ EK EL EM

E11

E10

E9

(E) 1 1/4" CD

DORM E

E 325N

BATH C

E 324N

MDF/IDF

E 326N

N HALL

E 301N

LAUNDRY

E 328N

STORAGE

E 329N

DORM B

E 312C

DORM A

E 314C

BATH A

E 313C

DORM D

E311C

BATH B

E 310C

DORM C

E 309C

ELECTRICAL

E 327N

AC-E-N31

AC-E-N32

(E) 24X10 TA

RL/RS/RHG UP & DN

RL/RS

RL/RS DN TO BC-E-N1

ON FIRST FLOOR

1/2" CD

T

1" CD

T

SG-1

30x10

688 CFM

KEY PLAN

NOT TO SCALE

725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com

DATE:

DRAWN:

CHECKED:

PROJECT:

DESIGNED:

OWNER:

MARK DATE DESCRIPTION

AREA OF WORK

/7

/2

:3

:1

A

M P

LO

T

T E

D B

Y F

R M

O N

D P

S S

T V

R F

R E

P

LA

C E

M E

N T

STATE OF OREGON

FLOOR PLANS - NE

08.07.2026

240024.01

M121

CLW

FRM

NJJ

D E

P A

R T

M E

N T

O F

P U

B

LI

C S

A F

E T

Y S

T A

N D

A R

D S

A N

D T

R A

IN

IN

G

A um sv ill e H ig hw ay S

E S al em

, O R

0%

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

S H E E T N O T E S :

R E F E R E N C E N O T E S :

1 CONNECT CONDENSATE FROM AC-E-N13 INTO EXISTING CONDENSATE LINE.

PATCH CHASE TO MAINTAIN EXISTING FIRE RATING.

PATCH GYP CEILING. FINISH TO MATCH ADJACENT SURFACES.

JUNCTIONS VIA REFNET BRANCH PIPING KIT PER MANUFACTURER.

1. REFRIGERANT PIPING SHOWN IS DIAGRAMATIC. FINAL PIPE ROUTING AND SIZING TO

BE APPROVED BY MANUFACTURER.

2. ALL REFRIGERANT PIPING SHALL BE PROVIDED WITH PIPE IDENTIFICATION

ACCORDING TO OMSC 1109.2.7.

NORTH

1/8" = 1'-0"1

MECHANICAL FIRST FLOOR PLAN - NE

NORTH

1/8" = 1'-0"2

MECHANICAL SECOND FLOOR PLAN - NE

NORTH

1/8" = 1'-0"3

MECHANICAL THIRD FLOOR PLAN - NE

NORTH

1/8" = 1'-0"4

MECHANICAL ROOF PLAN - NE

© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)

EXPIRES: 06-30-2027

JA NUA RY 14 , 2020

DIGITALLY SIGNED

RE

GI

STERED PROFESSIONALENGINEER# 95772

OREGONN

A

T

E

J . J E NK

E4

STORAGE

E 321S

CUST

E 322S

ELECTRICAL

E 323S

IDF

E 324S

DORM E

E 325S

BATH C

E 326S

DORM B

E 320S

BATH A

E 319S

(E) 1 1/4" CD

AC-E-S31

(E) 24x10 TARL/RS

RL/RS/RHG UP & DN

1" CD

RL/RS DN TO

BC-E-S1 ON

FIRST FLOOR

T

SG-1

30x10

688 CFM

EG EH EJ EK EL EM

E5

E4

CU-E-S1

RL/RS/RHG

RL/RS/RHG DN 3

EG EH EJ EK EL EM

E5

E4

BC-E-S1

ELECTRICAL

E118S

BOILER/CUST

E 119S

MAINTENANCE

E 121S

S HALL

E 101S

STUDENT REC

E 122S

1/2" CD

AC-E-S12

AC-E-S13

AC-E-S11 RL/RS

RL/RS/RHG UP

TO CU-E-S1 ON

ROOF

RL/RS

RL/RS

TT

T

1" CD

CENTRALIZED

VRF CONTROLLER

(E) 1 1/4" CD

1/2" CD

EG EH EJ EK EL EM

E5

E4

CUST

E 222S DORM E

E 225S

BATH C

E 226S

IDF

E 224S

ELECTRICAL

E 223S

S HALL

E 201S

STORAGE

E 221S

DORM B

E 220S

BATH A

E 219S

AC-E-S21

RL/RS UP

AND DN

(E) 24x10 TA

1" CD

TRL/RS

SG-1

30x10

688 CFM

RL/RS/RHG UP & DN

KEY PLAN

NOT TO SCALE

725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com

DATE:

DRAWN:

CHECKED:

PROJECT:

DESIGNED:

OWNER:

MARK DATE DESCRIPTION

AREA OF WORK

/7

/2

:3

:1

A

M P

LO

T

T E

D B

Y F

R M

O N

D P

S S

T V

R F

R E

P

LA

C E

M E

N T

STATE OF OREGON

FLOOR PLANS - SE

08.07.2026

240024.01

M122

CLW

FRM

NJJ

D E

P A

R T

M E

N T

O F

P U

B

LI

C S

A F

E T

Y S

T A

N D

A R

D S

A N

D T

R A

IN

IN

G

A um sv ill e H ig hw ay S

E S al em

, O R

0%

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

NORTH

1/8" = 1'-0"1

MECHANICAL FIRST FLOOR PLAN - SE

NORTH

1/8" = 1'-0"2

MECHANICAL SECOND FLOOR PLAN - SE

NORTH

1/8" = 1'-0"3

MECHANICAL THIRD FLOOR PLAN - SE

S H E E T N O T E S :

R E F E R E N C E N O T E S :

1 EXISTING 1-1/4" CONDENSATE DRAIN TERMINATE AT EXISTING MOP SINK.

KEEP CONDENSATE DRAIN HIGH IN IDF ROOM. OFFSET CONDENSATE DRAIN AS

LOW ON THE WALL AS POSSIBLE IN IDF ROOM TO MAKE CONNECTION TO

EXISTING CONDENSATE IN CUSTODIAL ROOM.

PATCH CHASE TO MAINTAIN EXISTING FIRE RATING.

REVISE ROUTING OF PRESSURE RELIEF PIPE ON WEST WALL OF

BOILER/CUSTODIAL ROOM TO MAKE ROOM FOR INSTALLATION OF AC-E-S12 IN

ACCESSIBLE LOCATION. PROVIDE DEDICATED CONDENSATE LINE FOR AC-E-S12

TO TERMINATE AT MOP SINK.

1. REFRIGERANT PIPING SHOWN IS DIAGRAMATIC. FINAL PIPE ROUTING AND SIZING TO

BE APPROVED BY MANUFACTURER.

2. ALL REFRIGERANT PIPING SHALL BE PROVIDED WITH PIPE IDENTIFICATION

ACCORDING TO OMSC 1109.2.7.

NORTH

1/8" = 1'-0"4

MECHANICAL ROOF PLAN - SE

© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)

EXPIRES: 06-30-2027

JA NUA RY 14 , 2020

DIGITALLY SIGNED

RE

GI

STERED PROFESSIONALENGINEER# 95772

OREGONN

A

T

E

J . J E NK

DRAW-THROUGH FAN SYSTEM BLOW-THROUGH FAN SYSTEM

H

H/2 MIN.

H = FAN INLET

PRESSURE (IN. W.C.)

+ 1 INCH

TO DRAIN PAN

CONNECTION

HAND-TIGHT CAP

PLUG (TYP. of 2)

TEE FITTING

SLOPE PIPING TO

DRAINAGE FIXTURE

AS REQUIRED.

1/2"

MIN.

H

SLOPE PIPING TO

DRAINAGE FIXTURE

AS REQUIRED.

H = FAN INLET

PRESSURE (IN. W.C.)

+ 1 INCH

TO DRAIN PAN

CONNECTION

HAND-TIGHT CAP

PLUG (TYP. OF 2)

TEE

FITTING

CONDENSATE DRAIN CONNECTION

UNISTRUT ATTACHED TO

STRUCTURE OR JOISTS

ABOVE - SEE STRUCTURAL.

SA DUCT - SIZE TO MATCH

OPENING WIDTH, HEIGHT AS

REQUIRED FOR LARGEST

CONNECTING DUCT

FLEX CONNECTOR

REFRIGERANT PIPING CONNECTIONS

UNIT SUPPORT AND VIBRATION

ISOLATION AS SPECIFIED

MAINTAIN MINIMUM PIPING &

ELECTRICAL CLEARANCE PER

MANUFACTURER

RECOMMENDATIONS

PLAN VIEW

SECTION VIEW

SA DUCT - SEE PLANS

FOR CONFIGURATION.

CEILING OR

STRUCTURE ABOVE

WALL MOUNTED

FAN COIL UNIT

INSTALL UNIT ON FACTORY-

SUPPLIED MOUNTING BRACKET

PER MANUFACTURER'S

INSTRUCTIONS.

EXISTING STUD WALL

LATERAL STUD

BACKING (TYP)

LAG SCREW - SIZE & NUMBER

PER MANUFACTURER'S

INSTRUCTIONS (TYP)

.4" MIN

6" MAX

2' -0

M

A X

1/4

TYP.

CU BY OTHERS w/750#

MAX. OPERATING WEIGHT

AND 6'-0" MAX. HEIGHT

(4) 3/4" DIA. THRU BOLTS

AT BASE OF UNIT

CONT. HSS 4x2x1/4 FLAT

UNDER SIDE RAILS

1. ALL STEEL IS TO BE GALVANIZED.

(3) #12 ELCO

DRIL-FLEX

SCREWS EA. END

REMOVE AND

REPLACE ROOFING

BY OTHERS AS

REQUIRED AT NEW

STANDS

4" X-STRONG

PIPE TYP.

PL 1/2x12x1'-0" w/ (4)

3/8" DIA. THREADED

RODS OR BOLTS IN

HILTI HDI-P TZ DROP

IN ANCHOR INSERTS

w/3/4" EMBED @ 9" o.c. TYP.

GALV. HILTI HS 158-12

SOLID STRUT EA. SIDE

OF UNIT CENTERED

ON POSTS

3/8" CAP PL TYP.

GC TO VERIFY

REQUIRED

EXTENSION ABOVE

ROOFING

MEMBRANE WITH

ROOFING MANUF.

AND INSTALLER

(E) HOLLOW CORE

PLANKS AND 3"

CONCRETE TOPPING

D E T A I L G E N E R A L N O T E S :

CONDENSATE DRAIN CONNECTION

UNISTRUT ATTACHED TO

STRUCTURE OR JOISTS

ABOVE - SEE STRUCTURAL.

FACTORY FILTER RACK

W/ ACCESS

LINED RA PLENUM SIZED TO

MATCH RA OPENING WIDTH

@ UNIT - 3'-0" LONG MIN,

HEIGHT AS REQUIRED FOR

LARGEST CONNECTING

DUCT

RA BRANCH DUCT - SEE

PLANS FOR SIZE AND

CONFIGURATION.

SA DUCT - SIZE TO MATCH

OPENING WIDTH, HEIGHT AS

REQUIRED FOR LARGEST

CONNECTING DUCT

FLEX CONNECTOR

REFRIGERANT PIPING CONNECTIONS

UNIT SUPPORT AND VIBRATION

ISOLATION AS SPECIFIED

LINED SA DUCT AS SHOWN ON PLANS

MAINTAIN MINIMUM PIPING &

ELECTRICAL CLEARANCE PER

MANUFACTURER

RECOMMENDATIONS

MINIMUM 18"x18" CEILING ACCESS

PER MANUFACTURER

RECOMMENDATIONS

PLAN VIEW

SECTION VIEW

SA DUCT - SEE PLANS

FOR CONFIGURATION.

725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com

DATE:

DRAWN:

CHECKED:

PROJECT:

DESIGNED:

OWNER:

MARK DATE DESCRIPTION

/7

/2

:3

:1

A

M P

LO

T

T E

D B

Y C

LW

O

N

D P

S S

T V

R F

R E

P

LA

C E

M E

N T

STATE OF OREGON

DETAILS

08.07.2026

240024.01

M501

CLW

CLW

NJJ

D E

P A

R T

M E

N T

O F

P U

B

LI

C S

A F

E T

Y S

T A

N D

A R

D S

A N

D T

R A

IN

IN

G

A um sv ill e H ig hw ay S

E S al em

, O R

0%

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

NOT TO SCALE

CONDENSATE DRAIN CONNECTION

NOT TO SCALE

HORIZONTAL FAN COIL - ELECTRICAL ROOM

NOT TO SCALE

WALL MOUNTED FAN COIL

NOT TO SCALE

MECHANICAL UNIT MOUNTING

NOT TO SCALE

HORIZONTAL FAN COIL - COMPUTER LAB

© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)

EXPIRES: 06-30-2027

JA NUA RY 14 , 2020

DIGITALLY SIGNED

RE

GI

STERED PROFESSIONALENGINEER# 95772

OREGONN

A

T

E

J . J E NK

725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com

DATE:

DRAWN:

CHECKED:

PROJECT:

DESIGNED:

OWNER:

MARK DATE DESCRIPTION

/7

/2

:3

:1

A

M P

LO

T

T E

D B

Y C

LW

O

N

D P

S S

T V

R F

R E

P

LA

C E

M E

N T

STATE OF OREGON

SCHEDULES

08.07.2026

240024.01

M601

CLW

CLW

NJJ

D E

P A

R T

M E

N T

O F

P U

B

LI

C S

A F

E T

Y S

T A

N D

A R

D S

A N

D T

R A

IN

IN

G

A um sv ill e H ig hw ay S

E S al em

, O R

0%

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

GENERAL NOTES:

A. PROVIDE UNITS WITH WIND COVERS TO ALLOW FOR LOW AMBIENT COOLING.

V R F A I R C O O L E D C O N D E N S I N G U N I T

TAG MANUFACTURER MODEL

AMBIENT DESIGN CAPACITY EFFICIENCY SOUND

LEVEL

(dB)

UNIT

WEIGHT

(LBS)

ELECTRICAL

NOTESHEAT

(°F)

COOL

(°F)

HEAT

(MBH)

COOL

(MBH)

HEAT

(COP)

COOL (IEER) VOLTS PHASE MCA MOP

CU-E-N1 DAIKIN REYQ120AATJB 20 93 112 129 3.5 19.1 61 725 208 3 36.5 40

CU-E-S1 DAIKIN REYQ72AATJB 20 93 79 78 3.6 19.1 58 525 208 3 27.3 30

V R F B R A N C H C O N T R O L L E R

TAG MANUFACTURER MODEL

ELECTRICAL

NOTES

VOLTS PHASE MCA MOP

BC-E-N1 DAIKIN BSF8Q54TVJ 208 1 0.8 15

BC-E-N2 DAIKIN BSQ36TAVJ 208 1 0.1 15

BC-E-S1 DAIKIN BSF6Q54TVJ 208 1 0.6 15

V R F F A N C O I L U N I T

TAG MANUFACTURER MODEL

REFRIGERANT

TYPE

ASSOCIATED

COND UNIT

HEATING COOLING

AIRFLOW

SOUND

LEVEL

(dBA)

UNIT

WEIGHT

(LBS)

ELECTRICAL

NOTESEAT

(°F)

LAT

(°F) CAPACITY

(BTU/HR)

EAT LAT

TOTAL CAPACITY

(BTU/HR)

VOLTS PHASE MCA MOPDB

(°F)

WB

(°F)

DB

(°F)

WB

(°F)

AC-E-N11 DAIKIN FXAQ12PVJU R410A CU-E-N1 65 108 13499 80 67 55 52 12000 290 CFM 38 30 208 1 0.4 15

AC-E-N13 DAIKIN FXAQ24PVJU R410A CU-E-N1 65 104 26499 80 67 55 54 24000 635 CFM 47 35 208 1 0.6 15

AC-E-N14 DAIKIN FXMQ24TBVJU R410A CU-E-N1 65 101 27000 80 67 58 55 24000 688 CFM 39 85 208 1 1.9 15

AC-E-N21 DAIKIN FXMQ24TBVJU R410A CU-E-N1 65 101 27000 80 67 58 55 24000 688 CFM 39 85 208 1 1.9 15

AC-E-N22 DAIKIN FXAQ12PVJU R410A CU-E-N1 65 108 13499 80 67 55 52 12000 290 CFM 38 30 208 1 0.4 15

AC-E-N31 DAIKIN FXMQ24TBVJU R410A CU-E-N1 65 101 27000 80 67 58 55 24000 688 CFM 39 85 208 1 1.9 15

AC-E-N32 DAIKIN FXAQ12PVJU R410A CU-E-N1 65 108 13499 80 67 55 52 12000 290 CFM 38 30 208 1 0.4 15

AC-E-S11 DAIKIN FXFQ12AAVJU R410A CU-E-S1 65 93 13499 80 67 60 58 12000 440 CFM 30 42 208 1 0.3 15

AC-E-S12 DAIKIN FXAQ12PVJU R410A CU-E-S1 65 108 13499 80 67 55 52 12000 290 CFM 39 27 208 1 0.4 15

AC-E-S13 DAIKIN FXAQ09PVJU R410A CU-E-S1 65 100 10500 80 67 58 56 9500 280 CFM 36 27 208 1 0.3 15

AC-E-S21 DAIKIN FXMQ24TBVJU R410A CU-E-S1 65 101 27000 80 67 58 55 24000 688 CFM 30 82 208 1 1.9 15

AC-E-S31 DAIKIN FXMQ24TBVJU R410A CU-E-S1 65 101 27000 80 67 58 55 24000 688 CFM 30 82 208 1 1.9 15

© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)

EXPIRES: 06-30-2027

JA NUA RY 14 , 2020

DIGITALLY SIGNED

RE

GI

STERED PROFESSIONALENGINEER# 95772

OREGONN

A

T

E

J . J E NK

#1.1

#1.2

#1.9

#1.3

#1.4

#1.5

#1.6

#1.7

#1.8

#1.10

CU-E-N1

REYQ120AATJB

KHRP25M72TUA

BC-E-N1

BSF8Q54TVJ

A

AC-E-N11

FXAQ12PVJU

B

AC-E-N13

FXAQ24PVJU

C

AC-E-N21

FXMQ24TBVJU

D

AC-E-N22

FXAQ12PVJU

E

AC-E-N31

FXMQ24TBVJU

F

AC-E-N32

FXAQ12PVJU

G

H

BS - 3

BSQ36TAVJ

A

AC-E-N14

FXMQ24TBVJU

#2.1

#2.2

#2.3

#2.4

#2.5

#2.6

CU-E-S1

REYQ72AATJB

BC-E-S1

BSF6Q54TVJ

A

AC-E-S13

FXAQ09PVJU

B

AC-E-S12

FXAQ12PVJU

C

AC-E-S11

FXFQ12AAVJU

D

AC-E-S21

FXMQ24TBVJU

E

AC-E-S31

FXMQ24TBVJU

F

L1, L2, L3 27.3A 3ph L1, L2 0.6A 1ph L1, L2 0.3A 1ph

L1, L2 0.4A 1ph

L1, L2 0.3A 1ph

L1, L2 1.9A 1ph

L1, L2 1.9A 1ph

OUT F1,F2

IN F1,F2

to centralized controller

OUT F1,F2

IN F1,F2

P1,P2

F1,F2

P1,P2

F1,F2

P1,P2

F1,F2

P1,P2

F1,F2

P1,P2

F1,F2

REYQ72AATJB

CU-E-S1

REYQ72AATJB

BC-E-S1

BSF6Q54TVJ

A B C D E F

AC-E-S13

FXAQ09PVJU

BRC1NRV71

AC-E-S12

FXAQ12PVJU

BRC1NRV71

AC-E-S11

FXFQ12AAVJU

BRC1NRV71

AC-E-S21

FXMQ24TBVJU

BRC1NRV71

AC-E-S31

FXMQ24TBVJU

BRC1NRV71

L1, L2, L3 36.5A 3ph L1, L2 0.8A 1ph L1, L2 0.4A 1ph

L1, L2 0.6A 1ph

L1, L2 1.9A 1ph

L1, L2 0.4A 1ph

L1, L2 1.9A 1ph

L1, L2 0.4A 1ph

L1, L2 0.1A 1ph L1, L2 1.9A 1ph

OUT F1,F2

IN F1,F2

to centralized controller

OUT F1,F2

IN F1,F2

BS F1,F2

P1,P2

F1,F2

P1,P2

F1,F2

P1,P2

F1,F2

P1,P2

F1,F2

P1,P2

F1,F2

P1,P2

F1,F2

OUT F1,F2 IN F1,F2

P1,P2

F1,F2

REYQ120AATJB

CU-E-N1

REYQ120AATJB

BC-E-N1

BSF8Q54TVJ

A B C D E F G H

AC-E-N11

FXAQ12PVJU

BRC1NRV71

AC-E-N13

FXAQ24PVJU

BRC1NRV71

AC-E-N21

FXMQ24TBVJU

BRC1NRV71

AC-E-N22

FXAQ12PVJU

BRC1NRV71

AC-E-N31

FXMQ24TBVJU

BRC1NRV71

AC-E-N32

FXAQ12PVJU

BRC1NRV71

BS - 3

BSQ36TAVJ

A

AC-E-N14

FXMQ24TBVJU

BRC1NRV71

OUT F1,F2

L,N

Ethernet 100BASE-TX

CU-E-N1 (7)

REYQ120AATJB

CU-E-S1 (5)

REYQ72AATJB

Hero Pro Edge

DGE601A71

1 2

725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com

DATE:

DRAWN:

CHECKED:

PROJECT:

DESIGNED:

OWNER:

MARK DATE DESCRIPTION

/7

/2

:3

:1

A

M P

LO

T

T E

D B

Y J

S H

O N

D P

S S

T V

R F

R E

P

LA

C E

M E

N T

STATE OF OREGON

DIAGRAMS

08.07.2026

240024.01

M621

CLW

JSH

NJJ

D E

P A

R T

M E

N T

O F

P U

B

LI

C S

A F

E T

Y S

T A

N D

A R

D S

A N

D T

R A

IN

IN

G

A um sv ill e H ig hw ay S

E S al em

, O R

0%

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)

NOT TO SCALE

CU-E-N1 PIPING DIAGRAM

NOT TO SCALE

CU-E-S1 PIPING DIAGRAM

NOT TO SCALE

CU-E-S1 WIRING DIAGRAM

NOT TO SCALE

CU-E-N1 WIRING DIAGRAM

NOT TO SCALE

CONTROL GROUP CONTROLLER WIRING DIAGRAM

EXPIRES: 06-30-2027

JA NUA RY 14 , 2020

DIGITALLY SIGNED

RE

GI

STERED PROFESSIONALENGINEER# 95772

OREGONN

A

T

E

J . J E NK

E L E C T R I C A L L E G E N D

COMBINATION DISCONNECT AND MAGNETIC STARTER

NON-FUSED DISCONNECT WITH CHARACTERISTICS AS NOTED.

MAGNETIC STARTER

MOTOR CONNECTION

CONCEALED RACEWAY AND CONDUCTORS. NUMBER OF SLASHES

INDICATES NUMBER OF CONDUCTORS IF MORE THAN TWO. SIZE

OTHER THAN 12 AWG AS NOTED. (APPLIES TO ALL WIRING SYMBOLS)

UNDERGROUND OR UNDERFLOOR RACEWAY

HOMERUN

OVERHEAD POWER LINE

SPLICE

OHD

GROUND CONNECTION

CONDUIT UP

CONDUIT DOWN

JUNCTION BOX

JUNCTION BOX FLUSH WITH FLOOR OR AT GRADE

CONDUIT STUB

CABLE TRAY

CURRENT TRANSFORMER

ELECTRICAL EQUIPMENT AS NOTED ON DRAWINGS

SURFACE-MOUNTED CABINET, TYPE AS NOTED

ELECTRIC METER, TYPE AS NOTED

MAGNETIC DOOR POSITION SENSOR

SECURITY SYSTEM OUTDOOR SIREN WITH TAMPER WIREGUARD

SECURITY SYSTEM OUTDOOR SIREN

CORNER SECURITY SYSTEM MOTION SENSOR

CEILING MOUNTED SECURITY SYSTEM MOTION

SECURITY SYSTEM KEYPAD

REQUEST TO EXIT SENSOR

GLASS BREAKAGE SENSOR

CARD READER

MECHANICAL EQUIPMENT DESIGNATOR, SEE SCHEDULES.

REFERENCE NOTE MARKER

PLAN OR DETAIL NUMBER

SHEET NUMBER

EXISTING WORK SHOWN LIGHT

NEW WORK SHOWN BOLD

EXISTING TO BE REMOVED (APPLIES TO DEMOLITION PLANS ONLY)

E-121

E-501

FUSED DISCONNECT WITH CHARACTERISTICS AS NOTED.

AS = SWITCH RATING, AF = FUSE RATING.

J

J

M

M

GB

CR

REX

PB PULL BOX, SIZE AS NOTED OR AS REQUIRED

FB1

SURFACE-MOUNTED PANELBOARD (120/208V)

SURFACE-MOUNTED PANELBOARD (277/480V)

RECESSED PANELBOARD (120/208V)

RECESSED PANELBOARD (277/480V)

CT

S

WP

SPD

T

CEILING-MOUNTED SECURITY CAMERA

CEILING-MOUNTED 360° VIEW ANGLE SECURITY CAMERA

WALL-MOUNTED SECURITY CAMERA

WALL-MOUNTED 360° VIEW ANGLE SECURITY CAMERA

MULTI-DIRECTIONAL SECURITY CAMERA

DISTRIBUTION TRANSFORMER

GROUNDING BUSBAR

SPECIAL PURPOSE RECEPTACLE WITH NEMA CONFIGURATION AS NOTED.L6-30R

PUSH BUTTON STATION

SIMPLEX RECEPTACLE

DUPLEX RECEPTACLE

QUADPLEX RECEPTACLE

FLUSH FLOOR BOX. REFER TO SPECIFICATIONS AND SCHEDULES FOR

DEVICE QUANTITIES AND TYPES.

FLUSH POKE-THROUGH FLOOR BOX. REFER TO SPECIFICATIONS AND

SCHEDULES FOR DEVICE QUANTITIES AND TYPES.

SPLIT-WIRED RECEPTACLE WITH HALF SWITCHED CONTROL VIA MANUAL

CONTROL, OCCUPANCY SENSING CONTROL, OR TIME BASED CONTROL.

REFER TO SPECIFICATIONS AND DRAWINGS.

RECEPTACLE WITH FULL SWITCHED CONTROL VIA MANUAL CONTROL,

OCCUPANCY SENSING CONTROL, OR TIME BASED CONTROL. REFER TO

SPECIFICATIONS AND DRAWINGS.

FB1 FLUSH FLOOR BOX WITH SWITCHED CONTROL VIA MANUAL CONTROL,

OCCUPANCY SENSING CONTROL, OR TIME BASED CONTROL. REFER TO

SPECIFICATIONS AND DRAWINGS.

PT3 FLUSH POKE-THROUGH FLOOR BOX WITH SWITCHED CONTROL VIA MANUAL

CONTROL, OCCUPANCY SENSING CONTROL, OR TIME BASED CONTROL.

REFER TO SPECIFICATIONS AND DRAWINGS.

LETTER DESIGNATOR(S) INDICATE ADDITIONAL RECEPTACLE

CHARACTERISTICS (APPLIES TO ALL RECEPTACLE AND FLOOR BOX TYPES):

A = INTEGRAL AFCI

B = INTEGRAL WITH USB OUTLET(S)

C = SUPPLIED POWER VIA CRITICAL BRANCH (NEC 517)

E = SUPPLIED POWER VIA LIFE SAFETY BRANCH (NEC 517)

G = INTEGRAL GFCI

IG = SUPPLIED POWER VIA AN ISOLATED GRD SYSTEM

P = INTEGRAL SURGE PROTECTIVE DEVICE

S = SUPPLIED POWER VIA OPTIONAL STANDBY BRANCH (NEC 702)

U = SUPPLIED POWER VIA A UPS

WP = WEATHERPROOF AND INTEGRAL GFCI

A

INDICATES RECEPTACLE ROUGH-IN HEIGHT FROM AFF TO CL OF

RECEPTACLE WHEN NOT AT STANDARD MOUNTING HEIGHT.+48"

INDICATES PANELBOARD AND BRANCH CIRCUIT NUMBER SERVING

RECEPTACLE.

2P1:12

INDICATES BRANCH CIRCUIT NUMBER SERVING RECEPTACLE. REFER TO

SHEET NOTES AND REFERENCE NOTES FOR SOURCE.

SURFACE MOUNTED RACEWAY WITH DUPLEX RECEPTACLES

RACEWAYS, BOXES, AND CONDUCTORS

ELECTRICAL EQUIPMENT - PLANS

WIRING DEVICES

ELECTRICAL EQUIPMENT AS NOTED

AUTOMATIC TRANSFER SWITCH

LV -1

3PH 4W

208V 225A

PANELBOARD WITH CHARACTERISTICS AS NOTED. WHERE NO

CHARACTERISTICS NOTED, SEE PANEL SCHEDULES.

PB PULL BOX, DIMENSIONS AS NOTED OR AS REQUIRED

T

T

T

SERVICE TRANSFORMER, PAD-MOUNTED

SERVICE TRANSFORMER, WITH VAULT

DISTRIBUTION TRANSFORMER

G

GENERATOR

PHOTOVOLTAIC INVERTER

ONE-LINE DIAGRAM

CIRCUIT BREAKER WITH CHARACTERISTICS AS NOTED

200A 3P

CIRCUIT BREAKER WITH INTEGRAL GROUND FAULT PROTECTIONG

200A 3P

SWITCH WITH CHARACTERISTICS AS NOTED200A

3P

200AS

200AF

3P

FUSED SWITCH WITH CHARACTERISTICS AS NOTED.

AS = SWITCH RATING, AF = FUSE RATING.

200A

200AS

200AF

SURGE PROTECTIVE DEVICE

EQUIPMENT CONNECTION

3000B FEEDER TAG. SEE FEEDER SCHEDULE.

E

FEEDER CONTINUATION CALLOUT. SEE CALLOUT ON DRAWING IDENTIFIED

WITH THE SAME LETTER TAG.

SECURITY AND ACCESS CONTROL

KP

GENERAL

ABBREVIATIONS

(#) DESIGNATES QUANTITY

A AMPERE (AMP)

AC ALTERNATING CURRENT

AFC AVAILABLE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AL ALUMINUM

ARCH ARCHITECT/ARCHITECTURAL

ATS AUTOMATIC TRANSFER SWITCH

AWG AMERICAN WIRE GAUGE

BLDG BUILDING

BOCT BOTTOM OF CABLE TRAY

BSC BIOLOGICAL SAFETY CABINET

C. CONDUIT

CENT CENTRIFUGE

CKT CIRCUIT

CL CENTERLINE

CLG CEILING

CRI COLOR RENDERING INDEX

CU COPPER

DC DIRECT CURRENT

DF DRINKING FOUNTAIN

DW DISHWASHER

(E) EXISTING

ECR ENVIRONMENTAL CONTROL ROOM

ELEC ELECTRICAL

EMERG EMERGENCY

EMT ELECTRICAL METALLIC TUBING

EV ELECTRIC VEHICLE

FA FIRE ALARM

FH FUME HOOD

FLA FULL LOAD AMPS

FTL FEED-THROUGH LUGS

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTION

GND GROUND

HP HORSEPOWER

IDF INTERMEDIATE DISTRIBUTION FRAME

INC INCUBATOR

K KELVIN

KW KILOWATT

KWH KILOWATT-HOUR

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

LED LIGHT EMITTING DIODE

LM LUMENS

LV LOW VOLTAGE

LSI LSI ELECTRONIC TRIP UNIT

LSI/G LSI/G ELECTRONIC TRIP UNIT

LTG LIGHTING

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDF MAIN DISTRIBUTION FRAME

MDS MAIN DISTRIBUTION SWITCHBOARD

MDP MAIN DISTRIBUTION PANELBOARD

MECH MECHANICAL

MLO MAIN LUG ONLY

MTS MAIN TRANSFER SWITCH

MVA MEGAVOLT-AMPERE

MW MEGAWATT

(N) NEW

(NL) NEW LOCATION

NA NOT APPLICABLE

NIC NOT IN CONTRACT

PA PUBLIC ADDRESS

PE PHOTOELECTRIC CELL

PF POWER FACTOR

PNL PANELBOARD

PV PHOTOVOLTAIC

PVC POLYVINYL CHLORIDE

PWR POWER

(R) REMOVE

(RL) RELOCATE

REFL REFLECTOR

SCCR SHORT CIRCUIT CURRENT RATING

SDP SUB-DISTRIBUTION PANELBOARD

SWBD SWITCHBOARD

TR TAMPER RESISTANT

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UC UNDER CABINET

UG UNDERGROUND

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLTAGE

VA VOLT-AMPERE

VP VAPOR PROOF

W WATT

WP WEATHERPROOF

XFMR TRANSFORMER

PT1

ELECTRICAL EQUIPMENT DESIGNATIONS

4 E - SWB - D1 A

VOLTAGE

POWER SOURCE

EQUIPMENT TYPE

2 - 208Y/120V (3-PHASE)

4 - 480Y/277V (3-PHASE)

N - NORMAL POWER (ELECTRIC UTILITY)

E - EMERGENCY POWER (GENERATOR, NEC 700)

R - REQUIRED STANDBY POWER (GENERATOR, NEC 701)

S - OPTIONAL STANDBY POWER (GENERATOR, NEC 702)

BLANK - PANELBOARD

SWB - SWITCHBOARD

T - TRANSFORMER

ATS - AUTOMATIC TRANSFER SWITCH

MTS - MANUAL TRANSFER SWITCH

GEN - GENERATOR

DS - DISCONNECT SWITCH

LOCATION BY BUILDING AND LEVEL

SERIES INDICATOR

D1 - DISTRICT UTILITY PLAN, LEVEL 1

CW1 - CORDLEY HALL WEST, LEVEL 1

CW2 - CORDLEY HALL WEST, LEVEL 2

CW3 - CORDLEY HALL WEST, LEVEL 3

CW4 - CORDLEY HALL WEST, LEVEL 4

CW5 - CORDLEY HALL WEST, LEVEL 5

A - FIRST IN A SERIES OF EQUIPMENT

B - SECOND IN A SERIES OF EQUIPMENT

ETC.

E1A-1 LAB EQUIPMENT DESIGNATOR, SEE SCHEDULES.

F

F

F

F

F S S

FACP

F T

MANUAL PULL STATION

FIRE ALARM

F S

F S

STROBE

HORN, SPEAKER

COMBINATION HORN/STROBE, COMBINATION SPEAKER/STROBE

SPRINKLER BELL, CHIME

FLOW SWITCH, TAMPER SWITCH

SMOKE DETECTOR

FIRE/SMOKE DAMPER, SMOKE DAMPER

FIRE ALARM CONTROL PANEL

FAAP FIRE ALARM ANNUNCIATOR PANEL

NAC NOTIFICATION APPLIANCE CIRCUIT EXTENDER

FSCP FIRE SUPPRESSION CONTROL PANEL

DH MAGNETIC DOOR HOLDER AND RELEASING DEVICE

DIGITAL POWER PACK CONCEALED IN CEILING WITH CHARACTERISTICS

AS NOTED. E = EMERGENCY, D = DIMMING (0-10VDC), a = ZONE

CONTROLLED.

CEILING-MOUNTED PHOTOELECTRIC CELL LIGHT LEVEL SENSOR.

A = SPECIAL TYPE (SEE OCCUPANCY SENSOR SCHEDULE).

WALL-MOUNTED OCCUPANCY SENSOR. A = SPECIAL TYPE (SEE

OCCUPANCY SENSOR SCHEDULE).

RELAY

WALL SWITCH WITH CHARACTERISTICS AS NOTED. a = ZONE CONTROLLED, K = KEYED SWITCH, P = WITH INTEGRAL PILOT LIGHT, 3 = THREE-WAY, 4 =

FOUR-WAY, OS = COMBINATION OCCUPANCY SENSOR AND WALL SWITCH,

D = MANUAL DIMMER, T = DIGITAL TIMER SWITCH.

CEILING SURFACE-MOUNTED LUMINAIRE

RECESSED LUMINAIRE

ROUND SUSPENDED LUMINAIRE

SHADING INDICATES LUMINAIRE PROVIDES ILLUMINATION FOR EMERGENCY

EGRESS. SHADING VARIES WITH EACH LUMINAIRE TYPE.

LINEAR CEILING SURFACE-MOUNTED LUMINAIRE

LINEAR SUSPENDED LUMINAIRE

LINEAR WALL-MOUNTED LUMINAIRE

SURFACE WALL-MOUNTED LUMINAIRE

RECESSED WALL-MOUNTED LUMINAIRE

CEILING SURFACE-MOUNTED LUMINAIRE

CEILING SURFACE-MOUNTED ASYMMETRIC LUMINAIRE

CEILING RECESSED LUMINAIRE

RECESSED ASYMMETRIC DOWNLIGHT

POLE-MOUNTED LUMINAIRE

POST TOP LUMINAIRE

ILLUMINATED BOLLARD

TRACK LIGHTING, NUMBER AND TYPE OF HEADS AS SHOWN

WALL MOUNTED EXIT SIGN, SHADING INDICATES FACES

CEILING MOUNTED EXIT SIGN, SHADING INDICATES FACES

CEILING-MOUNTED OCCUPANCY SENSOR. A = SPECIAL TYPE (SEE

OCCUPANCY SENSOR SCHEDULE).

DIGITAL WALL SWITCH. SEE WALL SWITCH SCHEDULE.

a = ZONE(S) CONTROLLED.

R

CEILING MOUNTED EXIT SIGN WITH INTEGRAL EMERGENCY LIGHTS AND

BATTERY PACK

SURFACE-MOUNTED EMERGENCY LIGHT WITH INTEGRAL BATTERY PACK

PP

E,a

LIGHTING

WALL-MOUNTED PHOTOELECTRIC CELL LIGHT LEVEL SENSOR.

A = SPECIAL TYPE (SEE OCCUPANCY SENSOR SCHEDULE).

LINEAR UNDER CABINET-MOUNTED LUMINAIRE

a

WS1 a

A1

LUMINAIRE TYPE IDENTIFIER. SEE LUMINAIRE SCHEDULE.

4N-CW1A:7

7 CONTROL ZONE IDENTIFIER

a

INDICATES PANELBOARD AND BRANCH CIRCUIT NUMBER SERVING LUMINAIRE.

INDICATES BRANCH CIRCUIT NUMBER SERVING LUMINAIRE. REFER TO SHEET

NOTES OR REFERENCE NOTES FOR SOURCE PANELBOARD.

OS

OS

PC

PC

A

A

A

A

TELECOMMUNICATIONS OUTLET, CONDUIT AND BACKBOX ONLY

REFER TO SPECIFICATIONS.

WIRELESS ACCESS POINT, CEILING MOUNTED WIRELESS ACCESS POINT

TELECOMMUNICATIONS OUTLET WITHIN COMBINES SERVICE FLUSH

FLOOR BOX. REFER TO SPECIFICATIONS AND SCHEDULES FOR DEVICE

QUANTITIES AND TYPES.

COAXIAL CABLE OUTLET, COMBINATION COAXIAL AND DATA OUTLET

TELECOMMUNICATIONS

W W

FB1

TV TV

D

SINGLE BED STATION

NURSE ASSIST BUTTON

NURSE CALL STATION. B = BED COMMUNICATION OUTLET, CB = CODE

BLUE, D = DUTY STATION, E = EMERGENCY STATION, NA = NURSE ASSIST

ANNUNCIATOR, N = NURSE LOCATOR STATION, M = PATIENT MONITORING

OUTLET, S = STAFF STATION, U = UTILITY STATION

DOME LIGHT (CEILING AND WALL MOUNTED)

NURSE CALL

ZONE DOME LIGHT (CEILING AND WALL MOUNTED)

NURSE CALL MASTER STATION

B

NCM

ELECTRIC LOCKEL

AC-E-N14A

HEAT DETECTOR

DUCT SMOKE DETECTOR

FUTURE EV CHARGING STATION (ROUGH-IN ONLY)

WALL-MOUNTED EV CHARGING STATION. SINGLE-PORT, DUAL-PORT.

PEDESTAL-MOUNTED EV CHARGING STATION. SINGLE-PORT, DUAL-PORT.

NUMERICAL DESIGNATOR INDICATES EV CHARGING STATION TYPE.

2 = FUTURE LEVEL 2 EV CHARGING STATION, LEVEL 2 EV CHARGING

STATION

3 = FUTURE LEVEL 3 EV CHARGING STATION, LEVEL 3 EV CHARGING

STATION

2 2

F

725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com

DATE:

DRAWN:

CHECKED:

PROJECT:

DESIGNED:

OWNER:

MARK DATE DESCRIPTION

/7

/2

:3

:5

A

M P

LO

T

T E

D B

Y A

JV

O

N

D P

S S

T V

R F

R E

P

LA

C E

M E

N T

STATE OF OREGON

LEGEND, GENERAL

NOTES, & SHEET

LIST

08.07.2026

240024.01

E001

AJV/BRE

AJV

BRE/MBR

D E

P A

R T

M E

N T

O F

P U

B

LI

C S

A F

E T

Y S

T A

N D

A R

D S

A N

D T

R A

IN

IN

G

A um sv ill e H ig hw ay S

E S al em

, O R

0%

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

SHEET LIST - ELECTRICAL

E001 LEGEND, GENERAL NOTES, & SHEET LIST

E101 DEMOLITION PLANS - NE

E102 DEMOLITION PLANS - SE

E121 FLOOR PLANS - NE

E122 FLOOR PLAN - SE

E601 SCHEDULES

© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)

EXP IRES : 12 - 3 1- 26

MA Y 21, 2014

RE

GI

STE

RED PROFESSIONALENGINEER# 80,621

OREGONM

A T

THEW B. R

E I

C

E10

E9

CUSTODIAN

E 128N

LAUNDRY

E 129N

N HALL

E 101N

ELECTRICAL

E 127N

DORM E

E 126N

BATH C

E 125N

COMPUTER LAB

E 105C

GUN STORAGE

E 106C

EH EJ EK EL EM

E11

E10

E9

STORAGE

E 229N

MDF/IDF

E 226N

N HALL

E 201N ELECTRICAL

E 227N

DORM E

E 225N

BATH C

E 224N

DORM D

E 211C

DORM C

E 209C

BATH B

E 210CBATH A

E 213C

DORM A

E 214C

DORM B

E 212C

1 1

EH EJ EK EL EM

E11

E10

E9

EH EJ EK EL EM

E11

E10

E9

E-L3N SECT 1

E-L3N SECT 2

E-L3N SECT 3

DORM E

E 325N

BATH C

E 324N

MDF/IDF

E 326N

N HALL

E 301N

LAUNDRY

E 328N

STORAGE

E 329N

DORM B

E 312C

DORM A

E 314C

BATH A

E 313C

DORM D

E311C

BATH B

E 310C

DORM C

E 309C

ELECTRICAL

E 327N

KEY PLAN

NOT TO SCALE

725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com

DATE:

DRAWN:

CHECKED:

PROJECT:

DESIGNED:

OWNER:

MARK DATE DESCRIPTION

AREA OF WORK

/7

/2

:3

:5

A

M P

LO

T

T E

D B

Y A

JV

O

N

D P

S S

T V

R F

R E

P

LA

C E

M E

N T

STATE OF OREGON

DEMOLITION

PLANS - NE

08.07.2026

240024.01

E101

AJV/BRE

AJV

BRE/MBR

D E

P A

R T

M E

N T

O F

P U

B

LI

C S

A F

E T

Y S

T A

N D

A R

D S

A N

D T

R A

IN

IN

G

A um sv ill e H ig hw ay S

E S al em

, O R

0%

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

S H E E T N O T E S :

R E F E R E N C E N O T E S :

1. FOR DEMOLISHED EQUIMENT SHOWN ON THIS SHEET: RETAIN AND PROTECT

EXISTING CONDUCTORS AND CONDUIT PATHWAYS FOR USE IN NEW WORK.

NORTH

1/8" = 1'-0"1

ELECTRICAL FIRST FLOOR DEMOLITION PLAN - NE

NORTH

1/8" = 1'-0"2

ELECTRICAL SECOND FLOOR DEMOLITION PLAN - NE

NORTH

1/8" = 1'-0"3

ELECTRICAL THIRD FLOOR DEMOLITION PLAN - NE

NORTH

1/8" = 1'-0"4

ELECTRICAL ROOF DEMOLITION PLAN - NE

DISCONNECT EXISTING MECHANICAL EQUIPMENT AND SALVAGE TO OWNER.

COORDINATE WITH MECHANICAL PRIOR TO COMMENCING WORK.

DISCONNECT AND RETAIN LIGHT FIXTURE TO FACILITATE MECHANICAL

CHANGES. RETAIN CIRCUIT AND CONTROLS FOR USE IN NEW WORK.

© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)

EXP IRES : 12 - 3 1- 26

MA Y 21, 2014

RE

GI

STE

RED PROFESSIONALENGINEER# 80,621

OREGONM

A T

THEW B. R

E I

E4

(E) E-L3S SECT 3

(E) E-L3S SECT 2

(E) E-L3S SECT 1

STORAGE

E 321S

CUST

E 322S

ELECTRICAL

E 323S

IDF

E 324S

DORM E

E 325S

BATH C

E 326S

DORM B

E 320S

BATH A

E 319S

EG EH EJ EK EL EM

E5

E4

EG EH EJ EK EL EM

E5

E4

1 1

BOILER/CUST

E 119S

MAINTENANCE

E 121S

S HALL

E 101S

STUDENT REC

E 122S

EG EH EJ EK EL EM

E5

E4

CUST

E 222S

ELECTRICAL

E 223S

DORM E

E 225S

BATH C

E 226S

IDF

E 224S

S HALL

E 201S

STORAGE

E 221S

DORM B

E 220S

BATH A

E 219S

KEY PLAN

NOT TO SCALE

725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com

DATE:

DRAWN:

CHECKED:

PROJECT:

DESIGNED:

OWNER:

MARK DATE DESCRIPTION

AREA OF WORK

/7

/2

:3

:5

A

M P

LO

T

T E

D B

Y A

JV

O

N

D P

S S

T V

R F

R E

P

LA

C E

M E

N T

STATE OF OREGON

DEMOLITION

PLANS - SE

08.07.2026

240024.01

E102

AJV/BRE

AJV

BRE/MBR

D E

P A

R T

M E

N T

O F

P U

B

LI

C S

A F

E T

Y S

T A

N D

A R

D S

A N

D T

R A

IN

IN

G

A um sv ill e H ig hw ay S

E S al em

, O R

0%

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

NORTH

1/8" = 1'-0"1

ELECTRICAL FIRST FLOOR DEMOLITION PLAN - SE

NORTH

1/8" = 1'-0"2

ELECTRICAL SECOND FLOOR DEMOLITION PLAN - SE

NORTH

1/8" = 1'-0"3

ELECTRICAL THIRD FLOOR DEMOLITION PLAN - SE

NORTH

1/8" = 1'-0"4

ELECTRICAL ROOF DEMOLITION PLAN - SE

S H E E T N O T E S :

R E F E R E N C E N O T E S :

1. FOR DEMOLISHED EQUIMENT SHOWN ON THIS SHEET: RETAIN AND PROTECT

EXISTING CONDUCTORS AND CONDUIT PATHWAYS FOR USE IN NEW WORK.

DISCONNECT EXISTING MECHANICAL EQUIPMENT AND SALVAGE TO OWNER.

COORDINATE WITH MECHANICAL PRIOR TO COMMENCING WORK.

DISCONNECT AND RETAIN LIGHT FIXTURE TO FACILITATE MECHANICAL

CHANGES. RETAIN CIRCUIT AND CONTROLS FOR USE IN NEW WORK.

© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)

EXP IRES : 12 - 3 1- 26

MA Y 21, 2014

RE

GI

STE

RED PROFESSIONALENGINEER# 80,621

OREGONM

A T

THEW B. R

E I

E10

E9

DORM E

E 126N

BATH C

E 125N

N HALL

E 101N

ELECTRICAL

E 127N

COMPUTER LAB

E 105C

GUN STORAGE

E 106C

CUSTODIAN

E 128N

LAUNDRY

E 129N

AC-E-N11

BC-E-N1

AC-E-N13

AC-E-N14

BC-E-N2

EH EJ EK EL EM

E11

E10

E9

DORM E

E 225N

BATH C

E 224N

MDF/IDF

E 226N

ELECTRICAL

E 227N

DORM D

E 211C

BATH B

E 210C

DORM C

E 209C

DORM A

E 214C

BATH A

E 213C

DORM B

E 212C

N HALL

E 201N

STORAGE

E 229N

LAUNDRY

E 228N

AC-E-N22

AC-E-N21

EH EJ EK EL EM

E11

E10

E9

CU-E-N1

EH EJ EK EL EM

E11

E10

E9

DORM B

E 312C

DORM A

E 314C

BATH A

E 313C

STORAGE

E 329N

LAUNDRY

E 328N

N HALL

E 301N

MDF/IDF

E 326N

ELECTRICAL

E 327N

DORM E

E 325N

BATH C

E 324N

DORM D

E311C

DORM C

E 309C

BATH B

E 310C

AC-E-N31

(E) E-L3N SECT 1

(E) E-L3N SECT 2

(E) E-L3N SECT 3

AC-E-N32

KEY PLAN

NOT TO SCALE

725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com

DATE:

DRAWN:

CHECKED:

PROJECT:

DESIGNED:

OWNER:

MARK DATE DESCRIPTION

AREA OF WORK

/7

/2

:3

:5

A

M P

LO

T

T E

D B

Y A

JV

O

N

D P

S S

T V

R F

R E

P

LA

C E

M E

N T

STATE OF OREGON

FLOOR PLANS - NE

08.07.2026

240024.01

E121

AJV/BRE

AJV

BRE/MBR

D E

P A

R T

M E

N T

O F

P U

B

LI

C S

A F

E T

Y S

T A

N D

A R

D S

A N

D T

R A

IN

IN

G

A um sv ill e H ig hw ay S

E S al em

, O R

0%

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

S H E E T N O T E S :

R E F E R E N C E N O T E S :

1 REINSTALL SALVAGED FIXTURE. UTILIZE EXISTING CIRCUIT AND CONTROLS

RETAINED FROM DEMOLITION TO SERVE FIXTURE.

NORTH

1/8" = 1'-0"1

ELECTRICAL FIRST FLOOR PLAN - NE

NORTH

1/8" = 1'-0"2

ELECTRICAL SECOND FLOOR PLAN - NE

NORTH

1/8" = 1'-0"3

ELECTRICAL THIRD FLOOR PLAN - NE

NORTH

1/8" = 1'-0"4

ELECTRICAL ROOF PLAN - NE

1. FOR ALL NEW MECHANICAL EQUIPMENT SHOWN ON THIS SHEET: UTILIZE EXISTING

FEEDER AND CONDUIT PATHWAY MADE AVAILABLE DURING DEMOLITION TO SERVE

EQUIPMENT. INTERCEPT AND EXTEND FEEDERS AND PATHWAY AS NECESSARY TO

CONSTRUCT A FUNCTIONAL SYSTEM.

© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)

EXP IRES : 12 - 3 1- 26

MA Y 21, 2014

RE

GI

STE

RED PROFESSIONALENGINEER# 80,621

OREGONM

A T

THEW B. R

E I

E4

DORM B

E 320S

BATH A

E 319S

STORAGE

E 321S

CUST

E 322S

ELECTRICAL

E 323S

IDF

E 324S

DORM E

E 325S

BATH C

E 326S

AC-E-S31

(E) E-L3S SECT 3

(E) E-L3S SECT 2

(E) E-L3S SECT 1

EG EH EJ EK EL EM

E5

E4

CU-E-S1

EG EH EJ EK EL EM

E5

E4

STUDENT REC

E 122S

S HALL

E 101S

MAINTENANCE

E 121S

BOILER/CUST

E 119S

ELECTRICAL

E118S

AC-E-S12

AC-E-S13

BC-E-S1

AC-E-S11

EG EH EJ EK EL EM

E5

E4

DORM E

E 225S

BATH C

E 226S

IDF

E 224S

ELECTRICAL

E 223S

CUST

E 222S

S HALL

E 201S

STORAGE

E 221S

DORM B

E 220S

BATH A

E 219S

AC-E-S21

KEY PLAN

NOT TO SCALE

725 A Street Springfield, OR 97477 541.342.7210 systemswestengineers.com

DATE:

DRAWN:

CHECKED:

PROJECT:

DESIGNED:

OWNER:

MARK DATE DESCRIPTION

AREA OF WORK

/7

/2

:3

:5

A

M P

LO

T

T E

D B

Y A

JV

O

N

D P

S S

T V

R F

R E

P

LA

C E

M E

N T

STATE OF OREGON

FLOOR PLAN - SE

08.07.2026

240024.01

E122

AJV/BRE

AJV

BRE/MBR

D E

P A

R T

M E

N T

O F

P U

B

LI

C S

A F

E T

Y S

T A

N D

A R

D S

A N

D T

R A

IN

IN

G

A um sv ill e H ig hw ay S

E S al em

, O R

0%

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

NORTH

1/8" = 1'-0"1

ELECTRICAL FIRST FLOOR PLAN - SE

NORTH

1/8" = 1'-0"2

ELECTRICAL SECOND FLOOR PLAN - SE

NORTH

1/8" = 1'-0"3

ELECTRICAL THIRD FLOOR PLAN - SE

S H E E T N O T E S :

1. FOR ALL NEW MECHANICAL EQUIPMENT SHOWN ON THIS SHEET: UTILIZE EXISTING

FEEDER AND CONDUIT PATHWAY MADE AVAILABLE DURING DEMOLITION TO SERVE

EQUIPMENT. INTERCEPT AND EXTEND FEEDERS AND PATHWAY AS NECESSARY TO

CONSTRUCT A FUNCTIONAL SYSTEM.

2. CONTRACTOR TO PERFORM 30-DAY METERING ON EXISTING PANEL E-L3N PER NEC

220.87 TO DETERMINE AVAILABLE AMPACITY FOR THE ADDITION OF NEW

CONDENSING UNIT CU-E-N2.

NORTH

1/8" = 1'-0"4

ELECTRICAL ROOF PLAN - SE

© Systems West Engineers, Inc. 2026. The signature in this document is encrypted. Editing this document is prohibited. (OAR 820)

EXP IRES : 12 - 3 1- 26

MA Y 21, 2014

RE

GI

STE

RED PROFESSIONALENGINEER# 80,621

OREGONM

A T

THEW…