Attachment C-1 Architectural Plans and Drawings.pdf
PDF 11 MB Posted
- Solicitation number
- S-63400-00017666
- Issued by
- Oregon
About this file
Architectural Plans and Drawings Summary
This document comprises architectural construction plans and drawings for the renovation of an existing residence into the North Gateway Visitor Center at Silver Falls State Park in Silverton, Oregon, prepared for the Oregon Parks and Recreation Department. The project involves converting a 9,987 square-foot multi-story residential structure into a visitor center and office space, with approximately 5,431 square feet on the first floor designated for assembly use (dining, lobby, and conference areas) and 1,618 square feet on the second floor for office use, plus 2,938 square feet of basement space for business offices and storage. The renovation includes comprehensive structural modifications, including the installation of a new elevator, interior demolition and reconfiguration of spaces, extensive mechanical and electrical upgrades, fire suppression systems, and construction of a separate fire pump building with an 11,000-gallon underground fire water storage tank. The building is classified as Construction Type V-B with occupancy classifications of A-2 (dining) and B (office), requiring full-coverage NFPA 13 fire sprinkler protection and accommodating a total occupant load of 254 people across multiple floors.
The project design was developed by Anderson Shirley Architects with structural engineering by Lewis & Van Vleet Structural Engineers and MSC Consulting Engineers, mechanical/plumbing/electrical engineering by MFIA Inc., and fire protection engineering also by MFIA Inc. Construction documents include detailed floor plans, elevations, sections, interior elevations, reflected ceiling plans, and extensive construction details addressing wall types, door schedules, finish schedules, window specifications, and roof/exterior wall construction methodologies. The renovation incorporates energy efficiency measures meeting ASHRAE 90.1-2022 standards for Climate Zone 4, with specifications for insulation values, window performance, and building envelope requirements. Interior finishes include exposed timber beams and T&G wood ceilings in public areas, ceramic tile in restrooms, gypsum board with various paint finishes throughout, and stone veneer and fiber cement panel siding on exterior walls. The project scope also encompasses waterproofing of basement walls, installation of various specialty systems including an elevator, fire alarm and suppression systems, HVAC ductwork and distribution, plumbing fixtures and rough-in work, and comprehensive electrical systems with lighting, power distribution, and technology infrastructure.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R
EN
O
VA
TI
O
N O
F
EX
IS
TI
N G
R
ES
ID
EN
C E
N O
R
TH
G
AT
EW
AY
V
IS
IT
O
R C
EN
TE
R
SI
LV
ER
F
AL
LS
S
TA
TE
P
AR
K
H U
LT
R
D S
E
SI
LV
ER
TO
N
, O R
06/01/26 27
SU
IT
E
TITLE PAGE
SITE PLAN
GENERAL NOTES
JMR
A0.1
RENOVATION OF EXISTING RESIDENCE
NORTH GATEWAY VISITOR CENTER
SILVER FALLS STATE PARK
21125 HULT RD SE, SILVERTON OR 97381
AX
X
AX
X
AX
X
WALL / BLDG. SECTION
DETAIL NUMBER
SHEET NUMBER
ELEVATION NUMBER
SHEET NUMBER
DETAIL NUMBER
SHEET NUMBER
INTERIOR ELEVATIONS
DETAIL REFERENCE
NORTH ARROW
WINDOW TYPE
GLASS TYPE
WALL TYPE
1-HR. RATED WALL
X
X
X
DRAWING SYMBOLS (NOT ALL SYMBOLS MAY BE USED IN THIS PROJECT)
SCALEAX
X DRAWING TITLE
STRUCTURAL GRID LINEX
DOOR NUMBER123
TITLE
ROOM
ROOM NAME / NUMBER
NEW DOOR - REUSE
EXIST. WHERE POSSIBLE
EXISTING DOOR
EXISTING DOOR
TO BE REMOVED
SPOT ELEVATION
VICINITY PLAN
N.T.S.
A0.1 SCALE:
OWNER:
OREGON PARKS AND RECREATION DEPARTMENT
725 SUMMER ST NE, SUITE C
SALEM, OR 97301-1266
CONTACT: JAMES ROBINSON
PHONE: 503-428-0851
EMAIL: james.robinson@oprd.oregon.gov
ARCHITECT:
CODE SUMMARY
ANDERSON SHIRLEY ARCHITECTS, INC.
695 COMMERCIAL ST SE SUITE 118
SALEM, OREGON 97301
CONTACT: JOHN SHIRLEY
PHONE: 503-371-1140
EMAIL: john@andersonshirley.com
TITLE PAGE, VICINITY PLAN, & GEN. NOTES
RENOVATE EXISTING UNFINISHED RESIDENCE INTO A
VISITOR CENTER AND OFFICE SPACE
SQUARE FEET
APPROXIMATE
ANCHOR BOLT
BOTTOM OF ...
ABOVE FINISHED FLOOR
ASPHALTIC CONCRETE
CONSTRUCTION
CATCH BASIN
BRG.
C
CAB.
CER.
COL.
CONC.
CONSTR.
CONT.
C.B.
CABINET
CLOCK
BEARING
CONTINUOUS
CONCRETE
COLUMN
CERAMIC
AGGR.
ALUM.
APPROX.
ARCH.
BRD.
BLDG.
BLK.
BLKG.
B.O.
BM.
ARCHITECT
ALUMINUM
AGGREGATE
BEAM
BLOCKING
BLOCK
BUILDING
BOARD
AT
CL.
PL.
A.B.
A.C.
ACOUS.
A.D.
ADJ.
A.F.F.
AND
PLATE
PLUS/MINUS
CENTER LINE
ADJUSTABLE
AREA DRAIN
ACOUSTICAL
SF
DIA.
DIAMETER
CONTRACTOR INSTALLEDC.I.
CPT. CARPET
DRINKING FOUNTAIN
ELECTRICAL PANEL
FIRE HOSE CABINET
FIRE HYDRANT
FIRE EXTINGUISHER
FLOOR DRAIN
FACE OF STUD
FACE OF MASONRY
FACE OF FINISH
FACE OF CONCRETE
ELECTRICAL WATER COOLER
ELEVATION OR ELEVATOR
EXTERIOR INSULATION & FINISH SYSTEM
FIRE EXTINGUISHER CABINETF.E.C.
FTG. FOOTING
F.HY.
F.H.C.
FIN.
F.O.C.
F.O.F.
F.O.M.
F.O.S.
FLASH.
FINISH/FINISHED
FLASHING
ELEV.
E.P.
EQ.
EQUIP.
E.W.C.
EXIST.
EXT.
F.D.
F.EXT.
E.W.
EQUIPMENT
EQUAL
EXTERIOR
EXISTING
EACH WAY
DBL.
D.F.
DIM.
DWR.
D.S.
EA.
E.I.F.S.
ELEC.
DN.
DIMENSION
DOUBLE
DRAWER
ELECTRICAL
EACH
DOWNSPOUT
DOWN
FRT FIRE RETARDANT TREATED
FLUOR. FLUORESCENT
F.R.P. FIBERGLASS REINFORCED PLASTIC
INSIDE DIAMETER/DIMENSION
INTERCOM SYSTEM STAFF PHONE
LANDSCAPING
LONG LEG HORIZONTAL
LONG LEG VERTICAL
H.B. HOSE BIB
HGT.
HORIZ. HORIZONTAL
HEIGHT
HOLLOW METAL
GLAZED MASONRY UNIT
GA.
GALV.
GL.
H.M.
HC
GYP.
GLZ.C.M.U.
G.B.
GALVANIZED
GAUGE
GYPSUM
HANDICAP
GLASS
GRAB BAR
LLH.
LLV.
INT. INTERIOR
JAN.
I
IRRIG.
LAM.
LANDSC.
LAV.
KIT.
IRRIGATION
JANITOR
KITCHEN
LAVATORY
LAMINATED
I.D.
INSUL. INSULATION
GLB. GLUE LAM BEAM NOT IN CONTRACT
MARKER BOARD
MECHANICAL
MISCELLANEOUS
ON CENTER
SANITARY NAPKIN DISPOSAL
OVERFLOW DRAIN
OWNER FURNISHED
OWNER INSTALLED
PLASTIC LAMINATE
PROJECTION SCREEN
PAPER TOWEL DISPENSER
ROOF DRAIN
ROUGH OPENING
NOT TO SCALE
OPP. OPPOSITE
R.O.
P. LAM.
PLAS.
RM.
R.D.
RAD.
P.T.D.
PLYWD.
P.S.
PLASTER
PLYWOOD
RADIUS
ROOM
NOM.
NO.
N.I.C.
O.I.
O.F.
O.D.
N.D.
O.C.
N.T.S.
NUMBER
NOMINAL
MAX.
MAG.
M.R.
MT.
MISC.
MIN.
MTL.
MECH.
M.B.
MAGNETIC
MAXIMUM
METAL
MINIMUM
MOUNT
MAP RAIL
M.O. MASONRY OPENING
OFFICEOFE
PREFINISHEDPREFIN.
PRESSURE TREATEDP.T.
M.S. MOP SINK
O.S. OCCUPANCY SENSOR
INTERCOM SYSTEM SPEAKER
SOAP DISPENSER OR SMOKE
SANITARY NAPKIN DISPENSER
SUSPENDED
TACK BOARD
TOP OF ... (SEE B.O.)
TOILET PAPER HOLDER
UNLESS OTHERWISE NOTED
VISUAL STROBE
SEAT COVER DISPENSER
WASH FOUNTAIN
WELDED WIRE FABRIC
STOR. STORAGE
VEST.
VERT.
V
WDW.
W/O W/ W.W.F.
WD.
W.F.
VERTICAL
VESTIBULE
WOOD
WITH
WITHOUT
WINDOW
SHTHG.
SUSP.
U.O.N.
TYP.
TV.
T.P.H.
T.O.
T.B.
SHEATHING
TELEVISION
TYPICAL
SD.
S
STL.
STD.
SIM.
S.N.
SHT.
SHR.
S.C.D.
SHOWER
SHEET
SIMILAR
STANDARD
STEEL
ST. STL. STAINLESS STEEL
SYSTEMSYS.
VINYL ASBESTOS TILEVAT
VINYL COMPOSITION TILEVCT
DETECTORMANUFACTURERMFR.
ACT. ACOUSTICAL CEILING TILE
CLEANOUTC.O.
INV. INVERT
EL. ELEVATION
(E) EXISTING
OCCUPANT(S)OCC.
REQUIREDREQ'D.
GRG. GLASS REINFORCED GYPSUM
FURR. FURRING
FT. FOOT/FEET
F.S. FLOOR SINK
FLOORFLR.
CLG. CEILING
CORR. CORRIDOR
CONCRETE MASONRY UNITC.M.U.
ALTERNATEALT.
G.F.C.I. GROUND FAULT CIRCUIT INTERRUPT
MECH. / PLUMBING ENGINEER:
MFIA, INC. CONSULTING ENGINEERS
2007 SE ASH ST.
PORTLAND, OREGON 97214
CONTACT: TAKAKO BAKER
PHONE: 503-234-0548
EMAIL: takako.baker@mfia-eng.com
STATE OF OREGON STRUCTURAL SPECIALTY CODE, 2025
EDITION OF THE 2024 INTERNATIONAL BUILDING CODE
OCCUPANCY:
A-2 (DINING), B (OFFICE)
EXISTING USE: RESIDENTIAL
NEW USE: VISITOR'S CENTER, OFFICE
CONSTRUCTION TYPE: V-B
SPRINKLERS: PROVIDE FULL COVERAGE NFPA 13 SYSTEM
MAX. ALLOWABLE HEIGHT: 2 STORIES / 60 FT (WITH
SPRINKLER INCREASE)
ACTUAL HEIGHT: 2 STORIES / 29'-3" + BASEMENT
MAX. ALLOWABLE AREA (A-2): 18,000 S.F. / FLOOR
ACTUAL AREA:
BASEMENT: 2,938 S.F.
FIRST FLOOR: 5,431 S.F. (INCL. 1,278 ADD'L SQFT)
SECOND FLOOR: 1,618 S.F.
TOTAL AREA: 9,987 S.F.
OCCUPANCY (SEE A0.2):
BASEMENT: 20
2,938SF / 150 SF/OCC. (BUSINESS) = 20 OCC
1ST FLOOR: 223
2ND FLOOR: 11
1,620SF / 150 SF/OCC. (BUSINESS) = 11 OCC.
PLUMBING FIXT. (BASED ON 2025 OSSC TABLE 2902.1)
REQUIRED:
A-2 OCCUPANCY 1ST FLOOR: 223 OCCUPANTS
TOILETS:
1 PER 75 MALE + 1 PER 75 FEMALE
= 2 MALE & 2 FEMALE
LAVATORIES:
1 PER 200 MALE + 1 PER 200 FEMALE
= 1 MALE & 1 FEMALE
DRINKING FOUNTAINS:
1 PAIR REQUIRED ON 1ST FLOOR
B OCCUPANCY: 31 OCCUPANTS:
OFFICES (BASEMENT): 20 OCCUPANTS
OFFICES (2ND FLOOR): 11 OCCUPANTS
TOILETS: 1 PER 25 MALE + 1 PER 25 FEMALE
= 1 MALE & 1 FEMALE
LAVATORIES: 1 PER 40 MALE & 1 PER 40 FEMALE
= 1 MALE & 1 FEMALE
DRINKING FOUNTAINS: NONE REQUIRED
TOTALS
TOILETS: 3 MALE & 3 FEMALE
LAVATORIES: 2 MALE & 2 FEMALE
DRINKING FOUNTAINS: 1 PAIR REQUIRED ON 1ST FLOOR
PROVIDED:
TOILETS: 4.67 MALE (1 URINAL = .67 TOILET) + 4 FEMALE
LAVATORIES: 4 MALE + 3 FEMALE
DRINKING FOUNTAINS: 1 PAIR ON 1ST FLOOR
PROJECT SUMMARY
DRAWING INDEX
PROJECT TEAM
A0.1
LIFE SAFETY PLANSA0.2
BASEMENT DEMOLITION PLAN & FLOOR
PLAN, FINISH SCHEDULE, DOOR SCHEDULE
A2.1
FIRST & SECOND FLOOR DEMOLITION PLANSA2.2
ATTIC & ROOF DEMOLITION PLANSA2.3
FIRST FLOOR PLANA2.4
ATTIC PLAN & ROOF PLANA2.6
EXTERIOR ELEVATIONS & WINDOW SCHEDULEA3.1
SECTIONSA3.2
SECTIONSA3.3
PROJECT LOCATION
ENLARGED SITE PLANA0.4
ELECTRICAL ENGINEER:
MFIA , INC. CONSULTING ENGINEERS
2007 SE ASH ST.
PORTLAND, OREGON 97214
CONTACT: ROB CONNELL
PHONE: 503-234-0548
EMAIL: robert.connell@mfia-eng.com
FIRE PROTECTION ENGINEER:
MFIA, INC. CONSULTING ENGINEERS
2007 SE ASH ST..
PORTLAND, OR 97214
CONTACT: TAKAKO BAKER
PHONE: 503-234-0548
EMAIL: takako.baker@mfia-eng.com
SECOND FLOOR PLANA2.5
SECTIONSA3.4
INTERIOR ELEVATIONSA5.1
INTERIOR ELEVATIONSA5.2
INTERIOR ELEVATIONSA5.3
REFLECTED CEILING PLANSA6.1
DETAILSA8.1
DETAILSA8.2
DETAILSA8.3
DETAILSA8.4
DETAILSA8.5
DETAILSA8.6
DETAILSA8.7
STAIRCASE SECTIONSA4.1
DETAILSA8.8
ARCHITECTURAL
ELECTRICAL COVERE1.0
FIRE PROTECTION SITE PLAN, SCHEDULE &
NOTES
F2.1
FIRE PROTECTION PUMP ROOMF2.2
DEFERRED SUBMITTALS
FIRE SPRINKLER DRAWINGS
FIRE ALARM DRAWINGS
TRUSS DRAWINGS
TRUSS CALCULATIONS
ELEVATOR SECTIONSA3.5
STRUCTURAL NOTESS1.0
BASEMENT FOUNDATION PLAN
FOUNDATION DETAILS
STRUCTURAL (VISITOR CENTER)
PLUMBING BASEMENT PLAN
P0.1
PLUMBING 1ST FLOOR PLAN
P2.0
MECHANICAL 1ST FLOOR PLANM1.1
MECHANICAL 2ND FLOOR PLANM1.2
MECHANICAL DETAILSM6.0
MECHANICAL BASEMENT PLANM1.0
PLUMBING 2ND FLOOR PLAN
P2.1
PLUMBING
MECHANICAL
ELECTRICAL
FIRE PROTECTION
FOUNDATION DETAILS
FIRST FLOOR FRAMING PLAN
S1.1 S1.2 S1.3
S2.1 S2.2 S2.3 S2.4 S2.5
SECOND FLOOR FRAMING PLAN
ATTIC FRAMING PLAN
FLOOR FRAMING DETAILS
FLOOR FRAMING DETAILS
BASEMENT FLOOR PLAN - LIGHTINGE2.0
1ST FLOOR PLAN - LIGHTINGE2.1
2ND FLOOR PLAN - LIGHTINGE2.2
3RD FLOOR PLAN - LIGHTINGE2.3
LIGHTING SCHEDULE & DETAILSE2.4
BASEMENT FLOOR PLAN - POWERE3.0
1ST FLOOR PLAN - POWERE3.1
2ND FLOOR PLAN - POWERE3.2
3RD FLOOR PLAN - POWERE3.3
ONE LINE DIAGRAME5.1
PANEL SCHEDULESE5.2
TECHNOLOGY COVERT1.0
BASEMENT FLOOR CEILING PLAN - TECHT2.0
1ST FLOOR CEILING PLAN - TECHNOLOGYT2.1
2ND FLOOR CEILING PLAN - TECHNOLOGYT2.2
3RD FLOOR CEILING PLAN - TECHNOLOGYT2.3
BASEMENT FLOOR PLAN - TECHNOLOGYT3.0
1ST FLOOR PLAN - TECHNOLOGYT3.1
2ND FLOOR PLAN - TECHNOLOGYT3.2
3RD FLOOR PLAN - TECHNOLOGYT3.3
FIRE PROTECTION SPRINKLER PLANS
MAIN BUILDING
F2.3
ENERGY EFFICIENCY - PRESCRIPTIVE ENVELOPE REQUIREMENTS
BUILDING COMPONENT REQUIRED PERFORMANCE EQUIVALENT VALUE
WALL INSULATION - ABOVE
GRADE
U-0.064 R-3.8 c.i. / R-13
WALL INSULATION - BELOW
GRADE
C-0.119 R-7.5 c.i.
FLAT CEILINGS U-0.021 R-49
VAULTED CEILINGS U-0.033 R-30 (RAFTERS)
UNDERFLOORS U-0.033 R-30
SLAB-EDGE PERIMETER F-0.843 R-30 for 24 in.
HEATED SLAB INTERIOR N/A R-10
FIXED WINDOWS U-0.36 MAX., SHGC 0.36 MAX.,
VT/SHGC 1.10 MIN.
OPERABLE WINDOWS U-0.45 MAX., SHGC 0.33 MAX.,
VT/SHGC 1.10 MIN.
ENTRANCE DOOR U-0.63 MAX., SHGC 0.33 MAX.,
VT/SHGC 1.10 MIN.
SKYLIGHTS U-0.50 MAX., SHGC 0.40 MAX.
EXTERIOR DOORS U-0.370 N/A
* NOT APPLICABLE TO THIS PROJECT
ASHRAE 90.1-2022, CLIMATE ZONE 4, NON-RESIDENTIAL
STRUCTURAL ENGINEER (FIRE PUMP BLDG):
MSC CONSULTING ENGINEERS
3470 PIPEBEND PLACE NE, #120
SALEM, OREGON 97301
CONTACT: ZEYAD AL-SAYHOOD
PHONE: 503-399-1399
EMAIL: zeyada@mscengineersinc.com
STRUCTURAL ENGINEER (VISITOR CENTER):
LEWIS & VAN VLEET STRUCTURAL ENGINEERS
14945 SW SEQUIOIA PKWY. #180
PORTLAND, OREGON 97224
CONTACT: ZACHARY MIDDLETON
PHONE: 503-885-8605
EMAIL: zrm@middletonengineer.com
GENERAL NOTESS0.1
PLAN & FOUNDATION DETAILS
ROOF FRAMING DETAILS
STRUCTURAL (FIRE PUMP BLDG.)
S1.1 S2.1
FOUNDATION DETAILSS1.4
MECHANICAL DETAILSM6.1
PLUMBING DETAILS
P2.2
PLUMBING SCHEDULES, LEGEND, NOTES
P6.0
FIRE PROTECTION PUMP ROOM DETAILS AND
SCHEDULES
F2.4
AutoCAD SHX Text
DATE
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
CONSULTANTS
AutoCAD SHX Text
ABBREVIATIONS
AutoCAD SHX Text
PARKS
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text
STATE
AutoCAD SHX Text MEASURED AIR LEAKAGE: WHOLE-BUILDING PRESSURIZATION TESTING SHALL BE CONDUCTED IN ACCORDANCE WITH ASHRAE STANDARD 90.1-2022, ARTICLE 5.4.3.1.4. TESTING SHALL BE CONDUCTED EXCLUDING HVAC RELATED ELEMENTS AND BE PERFORMED BY AN INDEPENDENT THIRD-PARTY VERIFICATION AND TESTING PROVIDER. CONTRACTOR SHALL BE RESPONSIBLE FOR ARRANGING AND PAYING FOR TESTING.
EXIT DOOR
OCCUP: 30 / 3 = 10
REQ'D CAP: 10" X 0.2 = 2"
ACTUAL CAP. = 36"
100'-11 1/2"
35'-6 1/2"UP UP
UP
100 8
BASEMENT
OFFICE 157
500 1
FIRE
PROTECTION
500 1
STORAGE
500 1
STORAGE
500 1
STORAGE
500 1
STORAGE
500 2
STORAGE
COMMON PATH OF
TRAVEL: 28'-1"
COMMON PATH OF
TRAVEL: 39'-11"
TRAVEL DISTANCE: 48'-2"
TRAVEL DISTANCE: 61'-4"
EXIT DOOR
OCCUP: 30 / 3 = 10
REQ'D CAP: 10" X 0.2 = 2"
ACTUAL CAP. = 36"
EXIT DOOR
OCCUP: 30 / 3 = 10
REQ'D CAP: 10" X 0.2 = 2"
ACTUAL CAP. = 36"
FEC
TRAVEL DISTANCE:
98'-6"
EXIT DOOR
OCCUP: 98 / 4 = 25
REQ'D CAP: 24.5 X 0.2" = 4.9"
ACTUAL CAP. = 72"
EXIT DOOR
CONF. OCCUP. LOAD: 123
REQ'D CAP: (123/2) X 0.2" = 12.3"
ACTUAL CAP. = 72"
EXIT DOOR
2ND FLOOR OCCUP.: (17) / 2 = 9
BASEMENT OCCUP.: 10
REQ'D CAP: 19 X 0.2" = 3.8"
ACTUAL CAP. = 36"
EXIT DOOR
1ST FLR. OCCUP: 98 / 4 = 25
2ND FLR.: 17 / 2 = 9
TOTAL OCCUP: 25 + 9 = 34
REQ'D CAP: 34 X 0.2" = 6.8"
ACTUAL CAP. = 72"
PROJECTOR SCREEN
'-3
25'-7 1/2"
7 123
15 40
15 29
15 30
200 1
EXIT DOOR
CONF. OCCUP. LOAD: 123
REQ'D CAP: (123/2) X 0.2" = 12.3"
ACTUAL CAP. = 36"
EXIT DOOR
OCCUP: 98 / 4 = 25
REQ'D CAP: 24.5 X 0.2" = 4.9"
ACTUAL CAP. = 72"
EXIT DOOR
OCCUP: 98 / 4 = 25
REQ'D CAP: 24.5 X 0.2" = 4.9"
ACTUAL CAP. = 36"
COMMON PATH
OF TRAVEL:
48'-3"
TRAVEL
DISTANCE:
50'-7"
TRAVEL
DISTANCE:
73'-9"
CONFERENCE
LOBBY
CAFE
DINING
LOBBY
TRAVEL DISTANCE: 104'-1"
FEC
FEC
COMMON PATH OF TRAVEL: 56'-0"
C O
PI
ER
O F/
O I
STOR.
REMOVE (E) WALL, BRACE
FLOOR ABOVE AS REQ'D.
OPEN TO
BELOW
OPEN TO
BELOW
OPEN TO
BELOW
OPEN TO
BELOW
OPEN TO
BELOW
100 4
OFFICE
100 2
OFFICE
100 2
OFFICE
100 2
OFFICE
OPEN TO
BELOW
FEC
UNOCCUPIED ATTIC
ATTIC ACCESS,
TYP.
FEC
EXIT TRAVEL PATH
EXIT SIGN W/ DIRECTIONAL ARROW
AREA REQUIRING EMERGENCY LIGHTING AT
MIN. 1 FOOT CANDLE AT WALKING SURFACE
ROOM AREA
OCCUPANT LOAD
OCCUPANT LOAD FACTOR
20 5
WORK THAT IS CROSSED OUT IN RED IS FROM
PREVIOUS PROJECTS CONSTRUCTION DOCUMENTS
AND IS FOR REFERENCE ONLY. NOTIFY ARCHITECT
IF WORK SHOWN CROSSED OUT WAS NOT
COMPLETED PER THE OLD PROJECT DOCUMENTS.
TRAVEL
DISTANCE = 24'-9"
CONSTRUCTION: II-B
OCCUPANCY: B
FIRE SUPPRESSION: YES
FIRE DETECTION SYSTEM: YES
ALLOWABLE HEIGHT: 75 FT. (PROPOSED = 10 FT. )
ALLOWABLE AREA: 92,000 SQ. FT. (PROPOSED = 231 SQ. FT.)
OCCUPANTS: 231 / 300 = 1
MAX. EXIT ACCESS TRAVEL DISTANCE (1006.3.4(2)): 100 FT.
1-HR. WALL DUE TO
PROXIMITY TO
PROPANE TANK
R
EN
O
VA
TI
O
N O
F
EX
IS
TI
N G
R
ES
ID
EN
C E
N O
R
TH
G
AT
EW
AY
V
IS
IT
O
R C
EN
TE
R
SI
LV
ER
F
AL
LS
S
TA
TE
P
AR
K
H U
LT
R
D S
E
SI
LV
ER
TO
N
, O R
06/01/26 27
SU
IT
E
LIFE SAFETY PLAN
JMR
A0.2
SECOND FLOOR LIFE SAFETY PLAN
3/32" = 1'
A0.3 SCALE:
BASEMENT LIFE SAFETY PLAN
3/32" = 1'
A0.3 SCALE:
ATTIC SAFETY PLAN
3/32" = 1'
A0.3 SCALE:
FIRST FLOOR LIFE SAFETY PLAN
3/32" = 1'
A0.3 SCALE:
REQUIRED EXITS:
BASEMENT: BUSINESS - 2,938SF (GROSS) / 100 = 30 OCCUPANTS
1ST FLOOR: ASSEMBLY, UNCONCENTRATED
SOUTH LOBBY: 415SF (NET) / 15 = 28 OCCUPANTS
DINING: 427SF (NET) / 15 = 29 OCCUPANTS
MAIN LOBBY: 588SF (NET) / 15 = 40 OCCUPANTS
CONFERENCE: 861SF (NET) / 15 = 58 OCCUPANTS
1ST FLOOR: CAFE
CAFE: 133SF (GROSS) / 200 = 1 OCCUPANT
2ND FLOOR: BUSINESS - 1,620SF (GROSS) / 100 = 17 OCCUPANTS
2 EXITS REQUIRED FROM A SPACE WITH MORE THAN 49 OCCUPANTS (TABLE 1015.1)
PROVIDED: 2 EXITS
TRAVEL DISTANCE
250FT MAX. (A AND R-2 W/ SPRINKLERS). 300FT. MAX. (B W/ SPRINKLERS) MAX LENGTH OF
TRAVEL FROM THE MOST REMOTE LOCATION WITHIN A STORY ALONG THE NATURAL AND
UNOBSTRUCTED PATH OF TRAVEL TO AN EXTERIOR EXIT.
ACTUAL: 104'-1""
COMMON PATH OF TRAVEL
75FT MAX (A OCC.), 100FT MAX (B OCC.), WITH SPRINKLERS (1014.3)
ACTUAL: 56'-0"
EXIT CODE SUMMARY
FIRE PUMP HOUSE
3/32" = 1'
A0.3 SCALE:
AutoCAD SHX Text
FIRE & LIFE SAFETY LEGEND
AutoCAD SHX Text
DATE
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
REVISIONS
CONSULTANTS
UNDERGROUND FIREFIGHTING
TANK (8' DIA., 11,000 GAL.)
12'-0"
2'-0"
2'-0"2'-0"
NE & SW
NW
SE
ROOF CONSTRUCTION
· MANUFACTURED FIRE RETARDANT-TREATED
WOOD TRUSSES (W/ 2x6 TOP CHORDS) @ 24" O.C.
· H-1 CLIPS @ EA. TRUSS
· 1/2" F.R.T. PLYWD. SHEATHING
· 30# BLDG. FELT
· SYNTHETIC SHAKE ROOFING (OF/CI)
CEMENT FIBER PANEL SIDING W/
CEMENT FIBER BATTEN STRIPS
@ 16" O.C., PAINT
WALL CONSTRUCTION
· 6" MTL. STUDS @ 16" O.C.
· 1/2" "SUREBOARD" SHEATHING -
60 MINUTE FIRE RATED
· DRAINAGE PLANE
· 1x4 F.R.T. FURRING, ALIGN W/
STUDS
· CEMENT FIBER PANEL SIDING
W/ BATTENS @ 16" O.C., ALIGN
W/ FURRING & STUDS
12"W x 18"D CONC. FOOTING W/ (2) #4 CONT.
A0.4
F.R.T. WOOD FASCIA. STAIN, TYP.
8' - 6"
MANHOLE TO
FIRE TANK
'-0
12"x16" GALV. ATTIC VENT, PAINT
HOLLOW STL. DOOR &
FRAME, PAINT
PREFIN. MTL. GUTTER, TYP.
4" CONC. SLAB W/ #3 @ 18" O.C. E.W. ON
6" COMPACTED GRAVEL BASE
1/2" DIA. ANCHOR BOLTS @ 48" O.C.
R-21 BATT INSULATION
5/8" TYPE 'X' GYP.
BRD. OVER VAPOR
BARRIER, TYP.
FP1
VERIFY7'-
3"
4'- 7"
2'-0"
F.R.T. WD. FASCIA, STAIN
FP1
14" x 20" PREFIN. ALUM. LOUVERS
@ SW WALL ONLY
40" x 80" PREFIN.
ALUM. LOUVER, TYP.
(VERIFY SIZE)
2'-0"
MANHOLE PER FIRE
PROTECTION DWGS.
2'-0"
1x4 CEMENT FIBER CORNER
BOARDS, TYP.
A8.5
A8.5
A8.5
A8.5
TYP.
TYP.
A8.5
A8.4
MANHOLE PER FIRE
PROTECTION DWGS.
DIESEL FILL BOX PER FIRE
PROTECTION DWGS.
3'- 5"
R.O
3'- 8"
3'- 8"
3'- 5"
R.O
2'- 3"
PREFIN. ALUM.
LOUVER, TYP.
1'-3"R.O.
HIGH AND LOW PREFIN.
ALUM. LOUVERS
PREFIN. ALUM. LOUVERS
EXHAUST FAN, TYP.
SEE F2.2
GENERATOR EXHAUST,
SEE F2.2
TEST HEADER VALVES
SEE F2.2
UNDERGROUND FIRE
PROTECTION TANK W/
PREFABRICATED CONC.
DEADMEN AND HOLD
DOWN STRAPS
UNDERGROUND FIRE PROTECTION TANK
A8.5 TYP.
2'-4"
BOX HEADER, TYP.
5'-0"
24"x24"" ROOF HATCH 22"x22" ACCESS
PANEL
6'-0"
22"x22" CEILING
ACCESS PANEL ABOVE
24"x24" ROOF HATCH
ABOVE
COORDINATE ROOF TRUSS
LAYOUT TO CENTER TRUSS BAY
OVER MANHOLE C/L
ROOF HATCH
D.S.
D.S.
D.S.
PREFIN. MTL.
GUTTER, TYP.
D.S.
A8.8
VISITOR
CENTER
L.O.W.
D.S.
D.S.
D.S.
D.S.
D.S.
D.S.
D.S.
D.S.
D.S.
D.S.
D.S.
D.S.
D.S.
D.S.
PROJECTOR SCREEN
F.D.
F.S.
F.S.
F.D.
CONC.
HOUSEKEEPING PAD
F.D.
F.D.
F.D.
1%
SLOPE
4" CONC. SLAB W
/ 8"
TURNED DOW
N EDGE -
COORD. W
/ M
ECH.
D.S.
(E) 4" DIA. FOOTING
DRAIN (VERIFY)
(E) 4" PVC
(NON-PERFORATED) -
EXTEND PER CIVIL DWGS.
SCOPE OF WORK
THIS PROJECT
SCOPE OF WORK
THIS PROJECT
PUMP HOUSE
UNDERGROUND FIRE
WATER STORAGE
TANK
D.S.
D.S.
R
EN
O
VA
TI
O
N O
F
EX
IS
TI
N G
R
ES
ID
EN
C E
N O
R
TH
G
AT
EW
AY
V
IS
IT
O
R C
EN
TE
R
SI
LV
ER
F
AL
LS
S
TA
TE
P
AR
K
H U
LT
R
D S
E
SI
LV
ER
TO
N
, O R
06/01/26 27
SU
IT
E
ENLARGED SITE PLAN
JMR
A0.3
SITE PLAN
1/16" = 1'
A0.3 SCALE:
PUMP HOUSE FLOOR PLAN
1/4" = 1'
A0.3 SCALE:
PUMP HOUSE ELEVATIONS
1/4" = 1'
A0.3 SCALE:
PUMP HOUSE SECTION
1/4" = 1'
A0.3 SCALE:
AutoCAD SHX Text
VAN
AutoCAD SHX Text
DATE
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
REVISIONS
A3.4
A3.3
SILL 4'-11 1/2
UP
CONC. RETAINING WALL, TYP.
UP
BREAK RM.
A
A DB C
H 1-HR
ELEVATOR
J
1-HR
NEW
NOTE:
RIGID INSULATION @ INTERIOR
PERIMETER WALLS OF BASEMENT.
SEE WALL TYPES FOR AREAS OF
ADD'L INSULATION.
H 1-HR
H
1-HR
J
1-HR
NEW
LINE OF
LOBBY ABV.
UP
A A
A
A
A
A
FIRE SPRINKLER RISER
FIRE
PROTECTION
008 007 006
002 003
004011
STORAGE
STORAGE
I.T. ROOM
STORAGE
UNFINISHED
RESTROOM
S2
STAIR
4" PERF. PVC UNDERSLAB
DRAIN LINE - PATCH BACK
CONC. FLOOR SLAB WHERE
REMOVED, TYP.
AREA DRAIN
AREA DRAIN - REPLACE (E)
COVER W/ HEEL-PROOF
COVER, TYP. OF (2)
VOID
SPACE
INFILL EXIST. OPENING
W/ CONC. WALL
INFILL EXIST. OPENING
W/ CONC. WALL
WINDOW WELL, ALIGN W/ FACE
OF (E) BASEMENT WALL
INFILL EXIST.
RECESS IN FLOOR
'-1
1"
H 1-HR
H
1-HR
K
1-HR
NEW
J 1-HR
NEW
J
H
1-HR
H 1-HR
HALL
H H
H
H
H
HJ
10'-8" 10'-2"10'-0"5'-11"8'-9"
6' -8
8' -9
±4
'-7
24'-9 1/2"
H
EQ
EQ
2'-6"
A A A A
NEW
A
NEW
A AA
NEW COL. & FTG. PER
STRUCTURAL, TYP.
PATCH BACK CONC. FLOOR
SLAB @ AREA OF NEW AND
REMOVED FOOTINGS
4.1
4.1
CONNECT TO
PERIMETER
FND. DRAIN
FEC
CRAWL
SPACE
DUCT
OPENING
DUCT
OPENING
J
008A
STOR.
008A
REF.
MICROWAVE
A5.3
A
NEW
A NEW
A5.3
A
NEW
A
NEW
A5.3
4' -1
ALIGN W/
UPSTAIRS WALL J
NEW
J
H*
NEW
5 5
F.S.
HOUSEKEEPING
PAD, TYP.
F.D.
GENERAL NOTES:
1) REMOVE BATTENS AT ALL
EXTERIOR WALLS
2) REMOVE ALL EXISTING
WINDOWS
KEYNOTES:
SAWCUT OPENINGS FOR DUCTWORK AND CRAWL SPACE ACCESS,
RE-FRAME WALL FURRING AS REQUIRED TO CREATE NEW OPENINGS.
REMOVE (E) CURB AND CONC. SLAB WITHIN
SAWCUT AND REMOVE SLAB. EXCAVATE FOR NEW FOOTING. SHORE OR
REMOVE AND REPLACE (E) WALL FRAMING ABOVE AS REQ'D.
D1
D2
SAWCUT SLAB AS REQ'D. TO ROUTE TRAP PRIMER LINE UP WALL FURRING
SAWCUT AND REMOVE SLAB, EXCAVATE FOR PLUMBING CONNECTION.
SHORE OR REMOVE AND REPLACE (E) WALL FRAMING ABOVE AS REQ'D
REMOVE (E) STUD WALL. BRACE STRUCTURE ABOVE AS REQ'D.
D5
D4
D3 D6
U P
DEMO (E) ELEVATOR PIT
REMOVE EXIST.
STAIR
REMOVE EXIST. WINDOW
(E) COL., RELOCATE
REMOVE (E) COL.
CUT COL. FLUSH
W/ TOP OF SLAB (E) COL.
(E) PENETRATIONS,
6'-3" A.F.F., TYP.
A DB C
SAWCUT OPENING
FOR NEW DOOR
SAWCUT OPENING
FOR NEW DOOR
REMOVE EXIST. WINDOWS,
OPENINGS TO REMAIN
REMOVE (E) WINDOW
CUT PIPE FLUSH W/ TOP OF SLAB
AND GROUT SHUT (DO NOT
IMPEDE ACTION OF UNDERSLAB
SEWER LINES) TYP.
REMOVE
(E) F.D.
SAWCUT & REMOVE SLAB
FOR U/S DRAIN SYSTEMREMOVE (E) CONC. CURBS
REMOVE (E)
CONC. CURB
REMOVE (E) CONC.
WINDOW WELL
SAWCUT SLAB FOR
NEW FOOTING
(E) COL.
SAWCUT SLAB &
EXIST. FTG FOR
NEW FOOTING
REMOVE (E)
TREE TRUNK &
FOUNDATION
(E) FLOOR
RECESS
D1
D1
D3
D3
D2
D4 D3
D5
D6
D1
D1
D6
D5
(E) EDGE OF
SLAB
2X6 STUDS
@ 16" O.C.
5/8" GYP. BRD.
2X4 STUDS
@ 16" O.C.
5/8" GYP. BRD.
EA. SIDE *
2X4 STUDS @ 16" O.C.
5/8" GYP. BRD.
EA. SIDE
ACOUSTICAL
INSULATION
2X6 STUDS @ 16" O.C.
5/8" GYP. BRD.
EA. SIDE *
2X6 STUDS
@ 16" O.C.
5/8" GYP. BRD.
EA. SIDE *
ACOUSTICAL
INSULATION
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLS
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLS
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLS
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLS H JF G KA
GA FILE NO WP 3614: GYPSUM WALLBOARD, WOOD STUDS:
ONE LAYER 5/8" TYPE X GYP. BRD. OR GYP VENEER BASE APPLIED PARALLEL OR
AT RIGHT ANGLES TO EACH SIDE OF 2X WOOD STUDS 16" O.C. WITH 1 1/4" TYPE W
DRYWALL SCREWS 12" O.C. JOINTS STAGGERED 16" ON OPPOSITE SIDES.
GA FILE NO WP 3644: GYPSUM WALLBOARD, WOOD STUDS, MINERAL FIBER INSULATION:
ONE LAYER 5/8" TYPE X GYB. BRD APPLIED AT RIGHT ANGLE TO EACH SIDE OF 2X WOOD
STUDS 16" O.C. WITH 2 1/4" TYP S OR W DRYWALL SCREWS 12" O.C. MINERAL FIBER
INSULATION, NOMINAL 2.5 PCF, FRICTION FIT IN STUD SPACE. VERTICAL JOINTS STAGGERED
16" O.C., HORIZONTAL JOINTS STAGGERED 24" O.C., ON OPPOSITE SIDES.
SIDING PER
ELEVATIONS
(E) DRAINAGE
PLANE
(E) PLYWD.
SHEATHING
5/8" GYP. BRD.
B C
STONE VENEER IN LIEU
OF SIDING WHERE
INDICATED
(E) R-1 1/2" RIGID
INSUL.
(E) CONC. WALL
1 1/2" RIGID INSUL.
*H GYP. ONE SIDE
(E) 2X6 STUDS
5/8" GYP. BRD.
EA. SIDE *
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLSL
*L GYP. ONE SIDE
R-13 FIBERGLASS
BATT INSUL.
2X4 STUDS @ 16"
O.C. (E) 2X6 STUDS
@ 16" O.C.
R-21 FIBERGLASS
BATT INSUL.
PLYWD. SHEATHING
5/8" GYP. BRD.
1 1/2" RIGID INSUL.
2X6 STUDS @ 16" O.C.
R-21 FIBERGLASS
BATT INSUL.
R-13 FIBERGLASS BATT
INSUL., 2 LAYERS
1/2" MIN. AIR SPACE
WALL TYPES
*CONST. WHERE INDICATED FOR 1-HR WALL
(E) PLYWD. SIDING
SIDING PER
ELEVATIONS
(E) PLYWD.
SHEATHING
5/8" TYPE 'X' GYP. BRD.
M
1 1/2" RIGID INSUL.
(E) 2X6 STUDS
@ 16" O.C.
R-21 FIBERGLASS
BATT INSUL.
5/8" TYPE 'X' GYP.
SHEATHING
5/8" GYP. BRD.
SIDING PER
ELEVATIONS
"NEW" TAG INDICATES ENTIRELY NEW WALL, INCLUDING FRAMING
2X4 STUDS
@ 16" O.C.
DOOR SCHEDULE
D
O O
R M
AR
K
D O
O R
S
IZ
E
TY
PE
(N O
TE
C O
N
ST
R U
C
TI
O N
(2
M
AT
ER
IA
L
FI
N
IS
H (3
G
LA
SS
(4
R
AT
IN
G
H
AR
D W
AR
E
(5
D
ET
AI
LS
A 8.
N O
TE
S
A SC WT - - 1 11 -
003 3'-0"x7'-0"
3'-0"x7'-0"004
-112--A
3'-0"x7'-0"005
-112-A
(2) 3'-0"x7'-0"006
13,74-E
3'-0"x7'-0"008
-11560-
3'-0"x7'-0"009
-113--
3'-0"x7'-0"010
116-
3'-0"x7'-0"011
112-
3'-0"x7'-11"101
11560FLWTSCD
(2) 3'-0"x7'-11"101A
3,74-TIE
88-TIE
3'-0"x7'-0"103
1,2
11A9-TPE
3'-0"x7'-0"104
810-E
(2) 3'-0"x7'-11"105
1,2
1116-TPD
(2) 3'-0"x7'-11"106
1112-TP
3'-0"x7'-0"107
810-TIWCE
3'-0"x7'-0"108
1,2
11A11-TPWCE
3'-0"x7'-0"109
1112-TPWTSCD
3'-0"x7'-0"110
1113--
-WTWC
A
E
3'-0"x7'-0"111
1113--A
(2) 3'-0"x7'-11"112
112--WTSCA
3'-0"x7'-11"113
3'-0"x7'-0"117
810-TIWCE
(2) 3'-0"x7'-11"115
1,2
88-TIWCE
3'-0"x7'-0"204
2,3
112--WTSCA
3'-0"x7'-0"206
814-TIWCE
3'-0"x7'-0"207
115-TPWTWCE
3'-0"x7'-0"208
116-TPWTWCE
3'-0"x7'-0"209
115-TPWTWCE -
116TP
3'-0"x7'-0"S-2a
116-TPWTWCE
3'-0"x7'-0"S-2b
111--WTSCA
3'-0"x7'-0"
8860 -
115 -
11760FLWTSCD -S-2c
3'-0"x7'-0"001
3'-0"x7'-0"002
007 113-- -
3'-0"x7'-0"201
A
B
D
MEHM
WT/WEWC
WTWC
WC
WTSC
B WTSC
WTSC
WTSC
FLWTSCD
60FLMEHSD
--WTSCA
203 116-TPWTWCE -3'-0"x7'-0"
(2) 3'-0"x7'-0" A
MEHM
(2) 3'-0"x7'-11" TI
WTSC TP
TI
SC WT
SC WT
A SC WT
SC WT
SC WT
SC WT TP
(2) 3'-0"x6'-8"FP1 -3- --MEHSA
3'-0"x7'-0"107A 11A15-TPWTWCE -
FI
EL
D V
ER
IF
Y
EX
IS
TI
N G
R O
U G
H O
PE
N
IN
G
S
IZ
ES
3'-0"x7'-0"008A 113- -A SC WT -
WT/WE
WT/WE
WT
WT/WE
WT/WE
WT/WE
R O
O M
N O
N
AM
E
8 5
KEY
4 2
ALL AROUND
ROOM FINISH SCHEDULE
208 OFFICE
OFFICE
HALL
BRIDGE
OFFICE
OFFICE
COPY ROOM
HALL
STORAGE
CAFE
HALL
MAIN LOBBY
HALL
MEN'S RESTROOM
WOMEN'S RESTROOM
CUSTODIAL STORAGE
FAMILY RESTROOM
CONFERENCE
VESTIBULE
VESTIBULE115
RESTROOM
I.T. ROOM
STORAGE
UNFINISHED
FIRE PROTECTION
STORAGE
STORAGE
BREAK RM.
HALL
LOBBY
DINING
HALL103
SE
AL
ED
C
O N
C R
ET
E
C
AR
PE
T
#1
EP
O
XY
F
LO
O
R
IN
G
C O
N C
R
ET
E
LA
TE
X
PA
IN
T
1X T
&G , S
TA
IN
EX
PO
SE
D
T &G
D
EC
K, S
TA
IN
W O
O D
P
AN
EL
IN
G
FR
P
W
AI
N
SC
O T
PL
AS
TI
C
L
AM
IN
AT
E W
AI
N
SC
O
T
C
ER
AM
IC
T
IL
E W
AI
N
SC
O
T
G
YP
. B O
AR
D
, S M
O O
TH
F
IN
IS
H , L
EV
EL
R O
O M
N O
N
AM
E
8 5
KEY
4 2
ALL AROUND
X X X
FLOOR NOTE
W
AL
K- O
FF
M
AT
SH
EE
T
VI
N
YL
LA
M
IN
AT
E
C
AR
PE
T
#2
NEW / EXIST.
SU
SP
EN
D
ED
A
C O
U
ST
IC
T
IL
E
SU
SP
EN
D
ED
A
C O
U
ST
IC
T
IL
E
209 RESTROOM
BASE
NEW / EXIST.
WALLS
NEW / EXIST. NEW / EXIST.
CEILING
XN
O
B
AS
E
C
ER
AM
IC
T
IL
E
SE
LF
-C O
VE
S
H
EE
T
VI
N
YL
W O
O D
, 1 x6
U .N
.O
4" R
U
BB
ER
6" E
PO
XY
C O
VE
B
AS
E
X
SE
AL
ED
C
O N
C R
ET
E
C
AR
PE
T
#1
XC
O
N C
R
ET
E
W
AL
K- O
FF
M
AT
SH
EE
T
VI
N
YL
LA
M
IN
AT
E
C
AR
PE
T
#2
NOTES:
1) WALK-OFF MAT @ ENTRY, CARPET ON LANDINGS AND STAIRS.
2) SEE INTERIOR ELEVATIONS FOR LOCATION OF WOOD PANELING
FLOOR NOTE
NEW / EXIST.
BASE
NEW / EXIST.
WALLS
NEW / EXIST. NEW / EXIST.
CEILING
1X T
&G , S
TA
IN
EX
PO
SE
D
T &G
D
EC
K, S
TA
IN
N O
B
AS
E
C
ER
AM
IC
T
IL
E
SE
LF
-C O
VE
S
H
EE
T
VI
N
YL
W O
O D
4" R
U
BB
ER
G
YP
. B O
AR
D
, T
EX
TU
R
ED
, L
EV
EL
EP
O
XY
P
AI
N
T
X
LA
TE
X
PA
IN
T
W O
O D
P
AN
EL
IN
G
FR
P
W
AI
N
SC
O T
PL
AS
TI
C
L
AM
IN
AT
E W
AI
N
SC
O
T
C
ER
AM
IC
T
IL
E W
AI
N
SC
O
T
G
YP
. B O
AR
D
, S M
O O
TH
F
IN
IS
H , L
EV
EL
G
YP
. B O
AR
D
, T
EX
TU
R
ED
, L
EV
EL
EP
O
XY
P
AI
N
T
X
G
YP
. B O
AR
D
, S M
O O
TH
F
IN
IS
H , L
EV
EL
G
YP
. B O
AR
D
, T
EX
TU
R
ED
, L
EV
EL
G
YP
. B O
AR
D
, S M
O O
TH
F
IN
IS
H , L
EV
EL
G
YP
. B O
AR
D
, T
EX
TU
R
ED
, L
EV
EL
LA
TE
X
PA
IN
T
EP
O
XY
P
AI
N
T
LA
TE
X
PA
IN
T
EP
O
XY
P
AI
N
T
S1
S2
STAIR 1
STAIR 2 NOTE 1
STOR.008A
EX
PO
SE
D
S
TR
U C
TU
R
E, N
O F
IN
IS
H
NOTE 2
NOTE 2
NOTE 2
NOTE 2
ELEV ELEVATOR
X
PV
C S
AF
ET
Y
FL
O O
R
IN
G
A
4"
2' -6
3' -0
1' -0
2'
-0
6"
B
GLASS
C
EN
TE
R
O F
PA
N
IC
H
D W
R
C
GLASS
6"
6"
6" 6"
GLASS
6" 8"
D
GLASS
1. DOOR TYPES
6"
6" 1'
-0
E
2. Construction
SC - Solid Core HM - Hollow Metal AL - Aluminum & Glass
3. Material/Finish
WE - Wood Enamel ME - Metal Enamel
TI - Tempered Insulated
5. Number refers to hardware group of hardware schedule.
FL - Firelite
4. Glass
TP - Tempered Plate
WT - Wood Transparent Stain
WC - Stile-and-Rail Wood
GLASS
Notes:
1. OF/CI door and frame
2. Prep OF/CI door for specified hardware
3. OF/CI door - provide new frame
KEYNOTES:
NOT USED
NEW POST PER STRUCTURAL - REMOVE AND
REPLACE (E) FURRING / INSULATION AS REQ'D.
24" WIDE x18" TALL PLYWOOD CRAWL SPACE
ACCESS DOOR.
(E) SUMP TO REMAIN - REFER TO
PLUMBING DRAWINGS FOR MODIFICATIONS.
RE-FRAME DOOR ROUGH OPENING FOR
SCHEDULED DOOR AND FRAME SIZE. WHERE
DOOR IS OF/CI, RE-FRAME OPENING TO SUIT
OWNER-FURNISHED DOOR AND FRAME.
(N) CONC. SLAB OR FOOTING, FLUSH W/ ADJ.
FLOOR. PROVIDE 10" EPOXY DOWELS INTO (E)
SLAB @ 24" O.C.
NOT USED
GRIND (E) FLOOR SLAB / PATCHES FLUSH AND
SMOOTH.
WORK THAT IS CROSSED OUT IN RED IS FROM
PREVIOUS PROJECTS CONSTRUCTION DOCUMENTS
AND IS FOR REFERENCE ONLY. NOTIFY ARCHITECT
IF WORK SHOWN CROSSED OUT WAS NOT
COMPLETED PER THE OLD PROJECT DOCUMENTS.
SCALE:
A2.1
BASEMENT PLAN
1/8" = 1'-0"
R
EN
O
VA
TI
O
N O
F
EX
IS
TI
N G
R
ES
ID
EN
C E
N O
R
TH
G
AT
EW
AY
V
IS
IT
O
R C
EN
TE
R
SI
LV
ER
F
AL
LS
S
TA
TE
P
AR
K
H U
LT
R
D S
E
SI
LV
ER
TO
N
, O R
06/01/26 27
SU
IT
E
BASEMENT PLANS
FINISH SCHEDULE
DOOR SCHEDULE
JMR
A2.1
SCALE:
A2.1
BASEMENT DEMOLITION PLAN
1/8" = 1'-0"
AutoCAD SHX Text
DATE
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
REVISIONS
REMOVE EXIST STAIR
REMOVE RAISED
FLOOR FRAMING
REMOVE LOG
POST, TYP.
REMOVE CONC. SLAB
EXIST.
OPENING IN
FLOOR
(E) ELEC. PANEL,
RELOCATE
REMOVE (E) POOL ROOM
FOUNDATION AND FOOTING
REMOVE HORIZ.
LOG ABV.
(E) COL.
(E) COL.
(E) COL.
(E) COL.
DA B C
REMOVE SECTION
OF FLOOR FOR NEW
ELEVATOR SHAFT
REMOVE EXIST. COLUMNS
(E) CONC. PLINTH
REMOVE EXIST
WINDOWS, TYP.
REMOVE (E)
TREE TRUNK (E) TREE
TRUNK
REMOVE (E) FLOOR SHEATHING
REMOVE (E) WING WALLS
REMOVE (E) CONC. CURB
REMOVE (E) WALL
CONST., TYP.
REMOVE (E)
LOW WALL
REMOVE (E) WALL, BRACE
FLOOR ABOVE AS REQ'D.
GENERAL NOTES:
1) REMOVE BATTENS AT ALL
EXTERIOR WALLS
2) REMOVE ALL EXISTING
WINDOWS
EXIST.
OPENING
IN FLOOR
REMOVE FLOOR
CONST. FOR NEW
2-STORY SPACE
REMOVE 2-STORY SPACE
OPEN TO
BELOW
MOVE (E) COL.
(E) COL.
B DA C
REMOVE SECTION
OF FLOOR FOR NEW
ELEVATOR SHAFT
REMOVE FLOOR
CONST. FOR
NEW STAIR
REMOVE (E) PLANT BALCONY
REMOVE EXIST. FRAMING
FOR NEW FLOOR CONST.
REMOVE (E) WALL, BRACE
FLOOR ABOVE AS REQ'D.
WORK THAT IS CROSSED OUT IN RED IS FROM
PREVIOUS PROJECTS CONSTRUCTION DOCUMENTS
AND IS FOR REFERENCE ONLY. NOTIFY ARCHITECT
IF WORK SHOWN CROSSED OUT WAS NOT
COMPLETED PER THE OLD PROJECT DOCUMENTS.
SCALE:
A2.2
FIRST FLOOR DEMOLITION PLAN
1/8" = 1'-0"
R
EN
O
VA
TI
O
N O
F
EX
IS
TI
N G
R
ES
ID
EN
C E
N O
R
TH
G
AT
EW
AY
V
IS
IT
O
R C
EN
TE
R
SI
LV
ER
F
AL
LS
S
TA
TE
P
AR
K
H U
LT
R
D S
E
SI
LV
ER
TO
N
, O R
06/01/26 27
SU
IT
E
FIRST & SECOND
FLOOR DEMO PLANS
JMR
A2.2
SCALE:
A2.2
SECOND FLOOR DEMOLITION PLAN
1/8" = 1'-0"
AutoCAD SHX Text
DATE
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
REVISIONS
(E) COL.
REMOVE SECTION
OF FLOOR FOR NEW
ELEVATOR SHAFT
REMOVE FLOOR CONST.
FOR NEW OPENING(E) ATTIC SPACE
(E) ATTIC SPACE
REMOVE FRAMING
FOR ATTIC ACCESS
HATCH
REMOVE FRAMING
FOR ATTIC ACCESS
HATCH
CONC.
HOUSEKEEPING
PAD, TYP.
REMOVE EXIST. ROOF CONST., TYP.
REMOVE ROOF DECKING
IN THIS AREA, EXISTING
FRAMING TO REMAIN
REMOVE ROOF DECKING
& FRAMING THIS AREA
FOR NEW CHIMNEY
WORK THAT IS CROSSED OUT IN RED IS FROM
PREVIOUS PROJECTS CONSTRUCTION DOCUMENTS
AND IS FOR REFERENCE ONLY. NOTIFY ARCHITECT
IF WORK SHOWN CROSSED OUT WAS NOT
COMPLETED PER THE OLD PROJECT DOCUMENTS.
R
EN
O
VA
TI
O
N O
F
EX
IS
TI
N G
R
ES
ID
EN
C E
N O
R
TH
G
AT
EW
AY
V
IS
IT
O
R C
EN
TE
R
SI
LV
ER
F
AL
LS
S
TA
TE
P
AR
K
H U
LT
R
D S
E
SI
LV
ER
TO
N
, O R
06/01/26 27
SU
IT
E
ATTIC & ROOF
DEMOLITION PLANS
JMR
A2.3
SCALE:
A2.3
ROOF DEMOLITION PLAN
1/8" = 1'-0"
SCALE:
A2.3
ATTIC DEMOLITION PLAN
1/8" = 1'-0"
AutoCAD SHX Text
DATE
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
REVISIONS
D
(E) 3 1/2" X 3 1/2"
STL. COL.
A B C
ELEV. +100.00'
CONC. SLAB
+99.65'
COVERED ENTRY ROOF
MAIN
LOBBY
DINING
LOBBY
CAFE
HALL
WOMEN'S
RESTROOM
STORAGE
ELEVATOR
C
C
J
H 1-HR
C
M 1-HR
J
B
B
C
C
C B
B
C
J
1-HR
K
1-HR
C
J
B
C
B
H 1-HR
J
1-HR
NEW
J
B
C B
B C
A5.1
A5.2
7' -6
/4
7'
-6
/4
4' -1
3/
4"
IN
SI
D
E C
LE
AR
1'-6 5/8"3'-1" R.O.3'-1" R.O.
2'-8 1/2"
EQ. 2'-4" 3'-9" R.O.
5'-6"
7'-8" CLR. 5'-2 1/2" 4'-8"
MEN'S
RESTROOM
A5.2
ELEV. OF
LANDING
BELOW
+89.85'
7'-3 1/2"
9' -5
±6
'-2
/2
G,L
J
A3.2
A3.2
A3.4
A8.6
A8.7
A8.6
A8.310
A8.3
9'-5"
6' -3
A3.4
CONFERENCE
FAMILY
RESTROOM
HALL
CUSTODIAL
STORAGE
VESTIBULE
B
HALL
A3.3
EQ
EQ
3' -4
S2
STAIR 2
S1
STAIR 1
6'-5"
7' -1
4'-0"
4' -0
5'-6"
3' -0
4'-2"
GAS FIREPLACE
A3.3
9'-11"9'-11" EQ.NEW FLOOR OVER
EXIST. STAIRS
FIRE SPRINKLER
RISER
S-2b
S-2a 106
102 101
3'-1" R.O. 3'-1" R.O.3" 5" 3" 5" 3"3'-1" R.O. 3'-1" R.O.
1'-2 1/2", TYP.
3'-9" R.O. 3" 3'-9" R.O. 4'-4" 3" 3'-9" R.O. 1'-8 3/8" 2'-4"
1'-2 1/2"
2'-9 5/8" 6'-10 1/2" 2'-9 5/8"
1'-2 1/2"
1' -2
/2
6'
-8
1' -2
/2
'-8
/2
1' -3
1/ 2"
4' -1
1" 6"
'-5
5'
-7
6"
'-0
1'
-2
/2
1' -4
/4
5' -0
1'-2 1/2" 10'-3 5/8" 1'-2 1/2" 10'-3 5/8" 1'-2 1/2"1'-2 1/2"
1'-4 3/4"
EXIST. OPENING, TYP. OF (4)
1'-6" 3'-0" R.O. ±13'-0" 3'-0" R.O. 1'-6" ±6'-1 3/8" 5'-0" R.O. 7'-5 5/8" 5'-0" R.O. 2'-3" 1'-2" 4'-0" R.O. 3'-11" 3'-11" 4'-0" R.O. 1'-2 5/8" 3'-10 5/8"
+100.00'
10" 10"
2' -6
8' -7
±3
'-1
/2
4' -2
11'-0" ±14'-3" 5'-0"
1'-2 1/2" 6'-2 7/8" 1'-2 1/2"
6' -5
1'
-2
/2
6'-2 7/8"
3' -4
/2
EQ
EQ
3'
-4
/2
1' -6
5' -9
" C
LR
'-1
J 1-HR
NEW
4'-7"
101A
VESTIBULE
1'-0"
WINDOW WELL BELOW
3' -4
2'-2 3/4"
23'-10 3/8"
A8.5
F
F
F
F
F
L
F H 12 A8.4
A8.2
A8.4
C
A5.1
A5.1
A5.2
K(NO
INSUL.)
39'-5" (VERIFY)
1'-4 3/4"
A4.1
A4.1
A5.2
A5.2
A5.2
A5.2
A5.2
A5.2
3' -0
" R .O
3"
3' -0
" R .O
3'
-0 " R
.O
3" 3'
-0 " R
.O
3' -0
" R .O
3"
3' -0
" R .O
3'-0" R.O.
3"
3'-0" R.O.
3'-0" R.O.
3"
3'-0" R.O.
A8.1
A8.1
6'-3"+/- 5'-0"+/- 5'-5 1/2"+/- 6'-4 7/8"+/- 10'-0"+/- 6'-1 5/8"+/-
A5.3
A5.3
F
U P
DN
DN
HEARTH
C
WOOD-BURNING
FIREPLACE
HEARTH
C C
H
H
6X6 POST, TYP.
2' -1
W.O.M.CPT.
UP
DN
C D.S.
D.S.
D.S.
D.S. D.S.
D.S.
D.S.D.S.D.S.D.S.D.S.
D.S. D.S.
D.S.
H*
FEC
FEC
L 1-HR
A8.4
A8.4 6
A8.4
1'-0"6'-0"
5' -0
10'-6"
107A
PROJECTOR SCREEN
OVERHEAD COILING DOOR
OVERHEAD COILING
DOOR
J
NEW
CONT. LAYER 3/4" PLYWD.
UNDER GYP. BRD.
EQ
A'
EQ
A'
1' -8
C.J.
C .J
C .J
C .J
C .J
C .J
C .J
C.J.
C.J.
PATCH CONC. SLAB @
REMOVED CURB
J
NEW
J 1-HR
NEW (2x10
STUDS)
NEW FLOOR SHEATHING
FLUSH WITH EXISTING
A8.5
ICE CREAM FREEZER, OF/OI
ICE MAKER, OF/OI
TURBOCHEF, OF/OI
M
AT
C H
E Q
A'
M
AT
C H
E Q
A'
A8.4
WINDOW WELL COVER
EXIST. STEPPED CONC. RETAINING WALL -
EXTEND HEIGHT PER DETAIL
A8.3 EXIST. STEPPED CONC. RETAINING WALL -
EXTEND HEIGHT PER DETAIL
4' -0
" C
LR
(E) JAMB -
REMOVE LOWER
WALL
J
J
F
F
L + 2x6
FURRING
J
(V
ER
IF
Y)
(VERIFY)
EXIST. CONC. STAIRS
NEW STAIRS
& LANDINGNEW STAIRS &
LANDING EXIST. CONC. STAIRS
'-6
'-5
A8.8
A8.8 SIM.
REV.
5 RAISE
HEADER
5 RAISE
HEADER
RAISE
HEADER
RAISE
HEADER
RAISE
HEADER
EL. 99.68'
EL. 99.72'
SL
O
PE
1/
8"
FT
ALIGN W/ FACE OF
BEAM ABOVE, TYP.
L + 2x6
FURRING
5"
2x4 FURRINGDUCT PER MECH.
5"2x4 FURRING
HVAC DUCT PER
MECH.
F.D.F.S. F.S.
F.D.
CONC.
HOUSEKEEPING PAD
F.D.
F.D. F.D.
1% SLOPE
4" CONC. SLAB W/ 8"
TURNED DOWN EDGE -
COORD. W/ MECH.
D.S.
GA FILE NO WP 3614: GYPSUM WALLBOARD, WOOD STUDS:
ONE LAYER 5/8" TYPE X GYP. BRD. OR GYP VENEER BASE APPLIED PARALLEL OR
AT RIGHT ANGLES TO EACH SIDE OF 2X WOOD STUDS 16" O.C. WITH 1 1/4" TYPE W
DRYWALL SCREWS 12" O.C. JOINTS STAGGERED 16" ON OPPOSITE SIDES.
*CONST. WHERE INDICATED FOR 1-HR WALL
SIDING PERGA FILE NO WP 3644: GYPSUM WALLBOARD, WOOD STUDS, MINERAL FIBER INSULATION:
ONE LAYER 5/8" TYPE X GYB. BRD APPLIED AT RIGHT ANGLE TO EACH SIDE OF 2X WOOD
STUDS 16" O.C. WITH 2 1/4" TYP S OR W DRYWALL SCREWS 12" O.C. MINERAL FIBER
INSULATION, NOMINAL 2.5 PCF, FRICTION FIT IN STUD SPACE. VERTICAL JOINTS STAGGERED
16" O.C., HORIZONTAL JOINTS STAGGERED 24" O.C., ON OPPOSITE SIDES.
KEYNOTES:
WORK THAT IS CROSSED OUT IN RED IS FROM
PREVIOUS PROJECTS CONSTRUCTION DOCUMENTS
AND IS FOR REFERENCE ONLY. NOTIFY ARCHITECT
IF WORK SHOWN CROSSED OUT WAS NOT
COMPLETED PER THE OLD PROJECT DOCUMENTS.
PROVIDE ADDITIONAL FASTENERS IN (E) FLOOR
SHEATHING TO ACHIEVE 6" MAX. O.C. SPACING AT EACH
(E) FLOOR JOIST. IN LIEU OF 1/2" PLYWD.
UNDERLAYMENT, PROVIDE 3/4" MARINE GRADE PLYWD.,
GLUED TO UNDERLYING SHEATHING WITH HIGH
QUALITY CONSTRUCTION ADHESIVE. STAGGER JOINTS
BETWEEN UNDERLAYMENT PANELS AND SHEATHING
JOINTS. ATTACH UNDERLAYMENT WITH SCREWS AT 6"
O.C. EA. WAY. APPLIES TO ENTIRE ROOM.
RE-FRAME DOOR ROUGH OPENING FOR SCHEDULED
DOOR AND FRAME SIZE. WHERE DOOR IS OF/CI,
RE-FRAME OPENING TO SUIT OWNER-FURNISHED DOOR
AND FRAME.
2X6 STUDS
@ 16" O.C.
5/8" GYP. BRD.
2X4 STUDS
@ 16" O.C.
5/8" GYP. BRD.
EA. SIDE *
2X4 STUDS @ 16" O.C.
5/8" GYP. BRD.
EA. SIDE
ACOUSTICAL
INSULATION
2X6 STUDS @ 16" O.C.
5/8" GYP. BRD.
EA. SIDE *
2X6 STUDS
@ 16" O.C.
5/8" GYP. BRD.
EA. SIDE *
ACOUSTICAL
INSULATION
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLS
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLS
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLS
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLS H JF G KA
SIDING PER
ELEVATIONS
(E) DRAINAGE
PLANE
(E) PLYWD.
SHEATHING
5/8" GYP. BRD.
B C
STONE VENEER IN LIEU
OF SIDING WHERE
INDICATED
(E) R-1 1/2" RIGID
INSUL.
(E) CONC. WALL
1 1/2" RIGID INSUL.
*H GYP. ONE SIDE
(E) 2X6 STUDS
5/8" GYP. BRD.
EA. SIDE *
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLSL
*L GYP. ONE SIDE
R-13 FIBERGLASS
BATT INSUL.
2X4 STUDS @ 16"
O.C. (E) 2X6 STUDS
@ 16" O.C.
R-21 FIBERGLASS
BATT INSUL.
PLYWD. SHEATHING
5/8" GYP. BRD.
1 1/2" RIGID INSUL.
2X6 STUDS @ 16" O.C.
R-21 FIBERGLASS
BATT INSUL.
R-13 FIBERGLASS BATT
INSUL., 2 LAYERS
1/2" MIN. AIR SPACE
WALL TYPES
(E) PLYWD. SIDING
SIDING PER
ELEVATIONS
(E) PLYWD.
SHEATHING
5/8" TYPE 'X' GYP. BRD.
M
1 1/2" RIGID INSUL.
(E) 2X6 STUDS
@ 16" O.C.
R-21 FIBERGLASS
BATT INSUL.
5/8" TYPE 'X' GYP.
SHEATHING
5/8" GYP. BRD.
SIDING PER
ELEVATIONS
"NEW" TAG INDICATES ENTIRELY NEW WALL, INCLUDING FRAMING
2X4 STUDS
@ 16" O.C.
GENERAL NOTES:
1. FILL/PATCH ALL HOLES IN FLOOR SHEATHING
2. SCREW DOWN ALL FLOOR SHEATHING TO ELIMINATE
SQUEAKING
SCALE:
A2.4
FIRST FLOOR PLAN
1/4" = 1'-0"
R
EN
O
VA
TI
O
N O
F
EX
IS
TI
N G
R
ES
ID
EN
C E
N O
R
TH
G
AT
EW
AY
V
IS
IT
O
R C
EN
TE
R
SI
LV
ER
F
AL
LS
S
TA
TE
P
AR
K
H U
LT
R
D S
E
SI
LV
ER
TO
N
, O R
06/01/26 27
SU
IT
E
FIRST FLOOR PLAN
JMR
A2.4
AutoCAD SHX Text
DATE
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
REVISIONS
OPEN TO BELOW
OPEN TO BELOW
OPEN TO BELOW
B DA C
OFFICE
OFFICE
HALL
COPY
ROOM
HALL
K
G 1-HR
M
1-HR
J
H 1-HR
C
J
H
1-HR
B
C
C
C
B
K
1-HR
K
B
'-5
J 1-HR
NEW
A8.2
ELEVATOR
H 1-HR
J 1-HR
NEW
OFFICE
OFFICE
BRIDGE
C
C O
PI
ER
O F/
O I
OPEN TO BELOW
A3.2
A3.2
A3.4
S-2c
A3.4
A3.3
A3.3
RESTROOM
9'-6" TALL WALL
OPEN TO BELOW
BUILT-IN
CASEWORK
ATTIC
ACCESS
ABV.
ATTIC
ACCESS
ABV.
FIRE SPRINKLER
RISER
STOR.
OPEN TO BELOW
J 1-HR
2'-6"
9'-5"
4' -0
6'
-9
/2
±1 '-9
/2
3'
-0 " R
.O
4' -0
3'
-0 " R
.O
4' -0
2'-9" 3'-0" R.O. 7'-2" 1'-2" 4'-0" R.O. 1'-5" 3'-4" 3'-4" 1'-5" 4'-0" R.O. 1'-2"
4'-10"
3'-0" R.O. 2'-11 1/2"
±4'-0 3/4" 6'-0" R.O. 2'-1" 6'-0" R.O. 1'-4 3/4"
5' -1
/2
9'
-8
/2
11 1/2"6'-0" R.O.2'-1"6'-0" R.O.
3'-0" R.O.
6'-0" CTR. ON
DOOR BELOW
1'-10 1/2" 6'-0" R.O. 2'-3" 6'-0" R.O. 3'-10 1/2" 2'-10 1/2" 6'-0" R.O.2'-6"
±1 5'
-4
3' -0
" R .O
±1
7' -4
(E ) R
.O . 3
'-0
3' -0
" R .O
1'
-5
4' -0
3'
-0 " R
.O
2' -6
3'
-0 " R
.O
4' -0
3'
-0 " R
.O
4' -0
6' -0
2'
-8
4'-10"
7' -6
C
C
J
H
J
J
J
J J
J
J
J
A8.4
3'-0" R.O.3"3'-0" R.O. 3'-0" R.O.
3"
1'-0 1/2"
3" 3'
-0 " R
.O
H (SIM.)
3'-0" R.O.
3"
A5.3
A5.3
A5.3
A4.1
A4.1
7'-0"
3" 3'-0" R.O. 3'-0" R.O.
3" 3'-0" R.O.
3' -0
CTR. DOOR ON BRIDGE
7"7" 3'
-7
2' -0
3' -7
CENTER ON
WINDOWS
BELOW
2' -1
10 3/4"
A4.1DN
S1
STAIR 1
DN
S2
STAIR 2
C C
C C
C
D.S.
F NEW
D.S.
D.S.
C
D.S. TO ROOF
D.S.
D.S. TO ROOF
C C
D.S.
D.S.
D.S.
H* NEW
C C
FEC
G
J 1-HR
NEW
BEAMS BELOW
GYP. ONE
SIDE
CONTRACTOR TO CAREFULLY
RELOCATE OWNER FURNISHED
DESK (+/- 6'-6" x +/- 10'-6") FROM
MAIN LOBBY INTO OFFICE 204
HVAC DUCT PER MECH., TYP.
2x4 FURRING, TYP.
F.D.
2X6 STUDS
@ 16" O.C.
5/8" GYP. BRD.
2X4 STUDS
@ 16" O.C.
5/8" GYP. BRD.
EA. SIDE *
2X4 STUDS @ 16" O.C.
5/8" GYP. BRD.
EA. SIDE
ACOUSTICAL
INSULATION
2X6 STUDS @ 16" O.C.
5/8" GYP. BRD.
EA. SIDE *
2X6 STUDS
@ 16" O.C.
5/8" GYP. BRD.
EA. SIDE *
ACOUSTICAL
INSULATION
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLS
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLS
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLS
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLS H JF G KA
GA FILE NO WP 3614: GYPSUM WALLBOARD, WOOD STUDS:
ONE LAYER 5/8" TYPE X GYP. BRD. OR GYP VENEER BASE APPLIED PARALLEL OR
AT RIGHT ANGLES TO EACH SIDE OF 2X WOOD STUDS 16" O.C. WITH 1 1/4" TYPE W
DRYWALL SCREWS 12" O.C. JOINTS STAGGERED 16" ON OPPOSITE SIDES.
GA FILE NO WP 3644: GYPSUM WALLBOARD, WOOD STUDS, MINERAL FIBER INSULATION:
ONE LAYER 5/8" TYPE X GYB. BRD APPLIED AT RIGHT ANGLE TO EACH SIDE OF 2X WOOD
STUDS 16" O.C. WITH 2 1/4" TYP S OR W DRYWALL SCREWS 12" O.C. MINERAL FIBER
INSULATION, NOMINAL 2.5 PCF, FRICTION FIT IN STUD SPACE. VERTICAL JOINTS STAGGERED
16" O.C., HORIZONTAL JOINTS STAGGERED 24" O.C., ON OPPOSITE SIDES.
SIDING PER
ELEVATIONS
(E) DRAINAGE
PLANE
(E) PLYWD.
SHEATHING
5/8" GYP. BRD.
B C
STONE VENEER IN LIEU
OF SIDING WHERE
INDICATED
(E) R-1 1/2" RIGID
INSUL.
(E) CONC. WALL
1 1/2" RIGID INSUL.
*H GYP. ONE SIDE
(E) 2X6 STUDS
5/8" GYP. BRD.
EA. SIDE *
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLSL
*L GYP. ONE SIDE
R-13 FIBERGLASS
BATT INSUL.
2X4 STUDS @ 16"
O.C. (E) 2X6 STUDS
@ 16" O.C.
R-21 FIBERGLASS
BATT INSUL.
PLYWD. SHEATHING
5/8" GYP. BRD.
1 1/2" RIGID INSUL.
2X6 STUDS @ 16" O.C.
R-21 FIBERGLASS
BATT INSUL.
R-13 FIBERGLASS BATT
INSUL., 2 LAYERS
1/2" MIN. AIR SPACE
WALL TYPES
*CONST. WHERE INDICATED FOR 1-HR WALL
(E) PLYWD. SIDING
SIDING PER
ELEVATIONS
(E) PLYWD.
SHEATHING
5/8" TYPE 'X' GYP. BRD.
M
1 1/2" RIGID INSUL.
(E) 2X6 STUDS
@ 16" O.C.
R-21 FIBERGLASS
BATT INSUL.
5/8" TYPE 'X' GYP.
SHEATHING
5/8" GYP. BRD.
SIDING PER
ELEVATIONS
"NEW" TAG INDICATES ENTIRELY NEW WALL, INCLUDING FRAMING
2X4 STUDS
@ 16" O.C.
KEYNOTES:
WORK THAT IS CROSSED OUT IN RED IS FROM
PREVIOUS PROJECTS CONSTRUCTION DOCUMENTS
AND IS FOR REFERENCE ONLY. NOTIFY ARCHITECT
IF WORK SHOWN CROSSED OUT WAS NOT
COMPLETED PER THE OLD PROJECT DOCUMENTS.
PROVIDE ADDITIONAL FASTENERS IN (E) FLOOR
SHEATHING TO ACHIEVE 6" MAX. O.C. SPACING AT EACH
(E) FLOOR JOIST. IN LIEU OF 1/2" PLYWD.
UNDERLAYMENT, PROVIDE 3/4" MARINE GRADE PLYWD.,
GLUED TO UNDERLYING SHEATHING WITH HIGH
QUALITY CONSTRUCTION ADHESIVE. STAGGER JOINTS
BETWEEN UNDERLAYMENT PANELS AND SHEATHING
JOINTS. ATTACH UNDERLAYMENT WITH SCREWS AT 6"
O.C. EA. WAY. APPLIES TO ENTIRE ROOM.
RE-FRAME DOOR ROUGH OPENING FOR SCHEDULED
DOOR AND FRAME SIZE. WHERE DOOR IS OF/CI,
RE-FRAME OPENING TO SUIT OWNER-FURNISHED DOOR
AND FRAME.
GENERAL NOTES:
1. FILL/PATCH ALL HOLES IN FLOOR SHEATHING
2. SCREW DOWN ALL FLOOR SHEATHING TO ELIMINATE
SQUEAKING
SCALE:
A2.5
SECOND FLOOR PLAN
1/4" = 1'-0"
R
EN
O
VA
TI
O
N O
F
EX
IS
TI
N G
R
ES
ID
EN
C E
N O
R
TH
G
AT
EW
AY
V
IS
IT
O
R C
EN
TE
R
SI
LV
ER
F
AL
LS
S
TA
TE
P
AR
K
H U
LT
R
D S
E
SI
LV
ER
TO
N
, O R
06/01/26 27
SU
IT
E
SECOND FLOOR PLAN
JMR
A2.5
AutoCAD SHX Text
DATE
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
REVISIONS
A3.3
ELEVATOR SHAFT,
OPEN TO BELOW
FIRE SPRINKLER
RISER
RAISED CEILING BELOW
ATTIC
ACCESS
HATCH
ATTIC
ACCESS
HATCH
ALIGN W/ LOBBY
WALLS BELOW
EQ. EQ.
EQ
EQ
12'-0"
'-0
(E) R.O.(E) R.O. (E) R.O.
(E) R.O.4'-0" R.O. (E) R.O. 4'-0" R.O.5'-5 1/2"5'-5 1/2"5'-5 1/2"
6'-0" 6'-0" 6'-0" 6'-0"4'-0" R.O. 4'-0" R.O.
J 1-HR
J 1-HR
J 1-HR
B
B
B
B
FF
'-8
'-8
FFEC
2:
12:12 12:12
NEW ROOF CONST., TYP.
2:
6:
6:
TY
P.
TY
P.
6:
6:
NEW SYNTHETIC
SHAKES ON ALL NEW
OR EXISTING ROOFS
CONTINUOUS INSULATION & PLYWOOD
OVER EXIST. ROOF CONST., TYP.
NEW EAVE BELOW AT AREA OF
REMOVED PLANT BALCONY
2' -0
3' -0
3' -0
2'
-0
2' -0
2' -0
4:
5'-2 1/2"
1'-6"
3'-6 1/2"
3'-2"
10"5'-2 1/2"
3'-6 1/2"
1'-6"
6"
5'-2 1/2"
3'-6 1/2"
8 REMOVE (E) COPPER
CRICKET, REPLACE
W/ NEW
LOWER
ROOF
PORCH
ROOF
BELOW
8UPPER AND
LOWER ROOFS 8 UPPER AND
LOWER ROOFS
2X6 STUDS
@ 16" O.C.
5/8" GYP. BRD.
2X4 STUDS
@ 16" O.C.
5/8" GYP. BRD.
EA. SIDE *
2X4 STUDS @ 16" O.C.
5/8" GYP. BRD.
EA. SIDE
ACOUSTICAL
INSULATION
2X6 STUDS @ 16" O.C.
5/8" GYP. BRD.
EA. SIDE *
2X6 STUDS
@ 16" O.C.
5/8" GYP. BRD.
EA. SIDE *
ACOUSTICAL
INSULATION
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLS
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLS
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLS
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLS H JF G KA
GA FILE NO WP 3614: GYPSUM WALLBOARD, WOOD STUDS:
ONE LAYER 5/8" TYPE X GYP. BRD. OR GYP VENEER BASE APPLIED PARALLEL OR
AT RIGHT ANGLES TO EACH SIDE OF 2X WOOD STUDS 16" O.C. WITH 1 1/4" TYPE W
DRYWALL SCREWS 12" O.C. JOINTS STAGGERED 16" ON OPPOSITE SIDES.
GA FILE NO WP 3644: GYPSUM WALLBOARD, WOOD STUDS, MINERAL FIBER INSULATION:
ONE LAYER 5/8" TYPE X GYB. BRD APPLIED AT RIGHT ANGLE TO EACH SIDE OF 2X WOOD
STUDS 16" O.C. WITH 2 1/4" TYP S OR W DRYWALL SCREWS 12" O.C. MINERAL FIBER
INSULATION, NOMINAL 2.5 PCF, FRICTION FIT IN STUD SPACE. VERTICAL JOINTS STAGGERED
16" O.C., HORIZONTAL JOINTS STAGGERED 24" O.C., ON OPPOSITE SIDES.
SIDING PER
ELEVATIONS
(E) DRAINAGE
PLANE
(E) PLYWD.
SHEATHING
5/8" GYP. BRD.
B C
STONE VENEER IN LIEU
OF SIDING WHERE
INDICATED
(E) R-1 1/2" RIGID
INSUL.
(E) CONC. WALL
1 1/2" RIGID INSUL.
*H GYP. ONE SIDE
(E) 2X6 STUDS
5/8" GYP. BRD.
EA. SIDE *
NOTE: SEE STRUC.
DWGS FOR ADDED
PLYWD. @ SHEAR
WALLSL
*L GYP. ONE SIDE
R-13 FIBERGLASS
BATT INSUL.
2X4 STUDS @ 16"
O.C. (E) 2X6 STUDS
@ 16" O.C.
R-21 FIBERGLASS
BATT INSUL.
PLYWD. SHEATHING
5/8" GYP. BRD.
1 1/2" RIGID INSUL.
2X6 STUDS @ 16" O.C.
R-21 FIBERGLASS
BATT INSUL.
R-13 FIBERGLASS BATT
INSUL., 2 LAYERS
1/2" MIN. AIR SPACE
WALL TYPES
*CONST. WHERE INDICATED FOR 1-HR WALL
(E) PLYWD. SIDING
SIDING PER
ELEVATIONS
(E) PLYWD.
SHEATHING
5/8" TYPE 'X' GYP. BRD.
M
1 1/2" RIGID INSUL.
(E) 2X6 STUDS
@ 16" O.C.
R-21 FIBERGLASS
BATT INSUL.
5/8" TYPE 'X' GYP.
SHEATHING
5/8" GYP. BRD.
SIDING PER
ELEVATIONS
"NEW" TAG INDICATES ENTIRELY NEW WALL, INCLUDING FRAMING
2X4 STUDS
@ 16" O.C.
KEYNOTES:
REMOVE (E) SIDING AND BATTENS. PROVIDE (N)
SIDING AND (N) BATTENS. ALIGN BATTENS WITH
(E) FURRING AND STUDS.
RP
REMOVE (E) ROOF SHAKES, FELT, PLYWOOD
UNDERLAYMENT, AND RIGID INSULATION AS
REQ'D TO ACCESS STRUCTURAL DECK FOR
NAILING. PATCH BACK TO MATCH ORIGINAL
CONSTRUCTION AFTER STRUCTURAL WORK.
RP
WORK THAT IS CROSSED OUT IN RED IS FROM
PREVIOUS PROJECTS CONSTRUCTION DOCUMENTS
AND IS FOR REFERENCE ONLY. NOTIFY ARCHITECT
IF WORK SHOWN CROSSED OUT WAS NOT
COMPLETED PER THE OLD PROJECT DOCUMENTS.
GENERAL NOTES:
1. FILL/PATCH ALL HOLES IN FLOOR SHEATHING
2. SCREW DOWN ALL FLOOR SHEATHING TO ELIMINATE
SQUEAKING
R
EN
O
VA
TI
O
N O
F
EX
IS
TI
N G
R
ES
ID
EN
C E
N O
R
TH
G
AT
EW
AY
V
IS
IT
O
R C
EN
TE
R
SI
LV
ER
F
AL
LS
S
TA
TE
P
AR
K
H U
LT
R
D S
E
SI
LV
ER
TO
N
, O R
06/01/26 27
SU
IT
E
ATTIC & ROOF
FLOOR PLANS
JMR
A2.6
SCALE:
A2.6
ROOF PLAN
1/8" = 1'-0"
SCALE:
A2.6
ATTIC FLOOR PLAN
1/8" = 1'-0"
AutoCAD SHX Text
DATE
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
REVISIONS
2ND FLR. TOP OF SHTHG.
EL. 109'-1 3/4"
ATTIC TOP OF SHTHG
EL. 118'-5 5/8"
1ST FLR. TOP OF SHTHG.
EL. 100'-0" (REF.)
BASEMENT TOP OF SLAB
EL. 89'-10 1/4"
SYNTHETIC SHAKE ROOFING
REMOVE AND REPLACE (E) CEMENT FIBER PANEL SIDING W/ (N)
CEMENT FIBER SIDING W/ BATTEN STRIPS @ 16" O.C., PAINT,
TYP. ENTIRE BUILDING
COPPER GUTTERS, TYP.
VINYL WINDOWS, TYP.
CLAD WOOD DOORS, TYP.
THIN STONE VENEER, TYP.
EXIST. CONC. BASEMENT
WALL & FOOTING, TYP.
HEAVY TIMBER TRUSS, BEAMS
AND COLUMNS, STAIN, TYP.
C C C C D G
M M M M N N N N
SEE 5/A3.1 FOR ENTRY
VESTIBULE ELEVATION
G G
A8.7
A8.7
A8.2
A8.6
A8.6
AAAAA
DDD
A8.6
A8.1
D.S.D.S.
D.S.D.S.
D.S.
D.S.D.S.
3" DIA. COPPER DOWNSPOUT, TYP.
1 1
4 TYP.
'-0
RP
REPAIR LEAK @ D.S.
REPLACE DAMAGED FIN. FASCIA RP
PROVIDE MISSING
FASCIA TRIM RP
5 TYP. ENTIRE
ELEVATION
RP
7 7 7 7 7
14"x20" ALUM. LOUVER
A8.5SIM.
S Q
2ND FLR. TOP OF SHTHG.
EL. 109'-1 3/4"
ATTIC TOP OF SHTHG
EL. 118'-5 5/8"
1ST FLR. TOP OF SHTHG.
EL. 100'-0" (REF.)
BASEMENT TOP OF SLAB
EL. 89'-10 1/4"
STAINLESS STL. CHIMNEY CAP
T
C C
D D DKKEXIST. PLANT BALCONY
TO BE REMOVED
N N Q R R
A
A
A8.7
S S
AA
D D D
T T TT T
V
D.S. D.S.
D.S.D.S.
D.S.
D.S.
'-0
COPPER TOP AND END CAP W/
OPEN BOT., TYP. EA. END OF BEAM
A8.3
A8.3
5 TYP. ENTIRE
ELEVATION
(E) D.S.
COPPER FLASHING
FACE OF PLYWD.
SHEATHING
'-4
5'-3"
6'-3"
6'-10"
7'-10"
TOP OF EXIST. CONC. RET. WALL, TYP.
NEW CONC. RET. WALL EXTENSION, TYP.
EXIST. CONC. STEPS, TYP.
NEW CONC. STEPS, TYP.
REFER TO NOTES AT LEFT
5 EQ. SPACES4 EQ. SPACES
GALV. STL. HANDRAIL, EA. SIDE
OF STAIR, TYP.
1'-0"
1'-0"
A8.7
24"x12" ALUM.
LOUVER
24"x12" ALUM.
LOUVER
12 6
S
2ND FLR. TOP OF SHTHG.
EL. 109'-1 3/4"
ATTIC TOP OF SHTHG
EL. 118'-5 5/8"
1ST FLR. TOP OF SHTHG.
EL. 100'-0" (REF.)
BASEMENT TOP OF SLAB
EL. 89'-10 1/4"
O
GAS FIREPLACE EXHAUST W/
CLR. RADIUS PER MANUF.
B
D.S.
D.S.
D.S.
D.S.
D.S.
4 TYP.
'-0
5 TYP. ENTIRE
ELEVATION
CEDAR TRIM OVER (E) BEAM -
SEE 11/A8.5
6 TYP.
2ND FLR. TOP OF SHTHG.
EL. 109'-1 3/4"
ATTIC TOP OF SHTHG
EL. 118'-5 5/8"
1ST FLR. TOP OF SHTHG.
EL. 100'-0" (REF.)
BASEMENT TOP OF SLAB
EL. 89'-10 1/4"
H J
H
N N N N N N
U
WINDOW WELL
D.S.
D.S.
D.S.
D.S.
D.S.
'-0
'-0
1 1
2 2
2 1
4 TYP.
5 TYP. ENTIRE
ELEVATION
TYP.
6 TYP. (4)
WINDOWS
THIS ELEV.
P
E E
REV.
A8.4
A8.4
P
REV.
D.S. D.S.
3" W. WD. MULLIONS
CAULK JOINTS BETWEEN
BEAMS AND STL. PLATES,
TYP. CAULK TO MATCH
WOOD
SET LOOSE TRUSS
BOLT @ CONNECTOR
PLATE RP
A
2' -0
B
3'-0"
E
5' -3
/2
4'-0"
D
3' -6
3'-0"
5' -7
/4
4' -3
/8
M N
WINDOW SCHEDULE
NOTES:
1. VINYL WINDOWS, MILGARD MONTECITO SERIES OR JELD-WEN PREMIUM VINYL
SERIES W/ 1-1/16" SCULPTED ALUM. GRIDS MATCHING FRAME COLOR (INT. AND EXT.)
2. EXTERIOR COLOR: ESPRESSO (MILGARD COLOR), INTERIOR COLOR: WHITE
3. DIMENSIONS ARE TO EDGE OF FRAMES (NOT ROUGH OPENING) U.N.O.
4. ALL NON-OPERABLE WINDOWS TO BE FIXED CASEMENT/AWNING STYLE TO
PROVIDE CONSISTENT APPEARANCE
5. U-VALUE = 0.35 MAX., SHGC = 0.33 MAX., AIR INFILTRATION 0.30 CFM/S.F. MAX
(AAMA 101 OR NFRC 400)
6. FOR FLEXIBLE WINDOW FLASHING INSTALLATION SEQUENCE SEE 9/A8.6.
7. FIRE-RATED WINDOWS PER SPECIFICATION SECTION 08510
P Q
4'-5"
4' -1
1" 1'
-1
1/ 2"
R
EXIST.
OPENING -
VERIFY
SIZE
S
1t
= CLEAR INSULATED GLASS
= CLEAR INSULATED FULL-TEMPERED GLASS
2 = TINTED INSULATED HALF-TEMPERED GLASS
1ST FLR.
T.O. SHTHG.
ATTIC
T.O. SHTHG.
2ND FLR.
T.O. SHTHG.
2' -6
C
6'-0"
3' -8
/8
2' -0
/2
2'-0 1/2" +/-
3' -0
3' -9
/8
"± VERIFY EXIST.
SILL HT.
3' -4
"± VERIFY EXIST.
HDR. HT.
HG
1 1
4'-0"
3' -6
3'
-8
/8
J
3'-9"
3' -0
5'
-0
3'-0"
1' -8
6'
-0
1t
3'-11 3/4"
2' -1
1/
2"
4'
-1
1/ 2"
R .O
1'
-1
1/ 2"
/4
3'-0"
2' -1
1/
2"
4'
-1
1/ 2"
R .O
3'
-8
/4
/4
7 1/4" 2'-2" +/-
O
5'-0"
2' -0
4'
-7
/2
1 1
6 6
4'-0"
6' -3
1'
-8
3'-1"
5' -0
3'
-0
3'-0"
5' -0
2'
-0
1t 2t
K
3'-0"
5' -0
'-9
/4
(INTERIOR)
VERIFY W/ EXIST.
FRAMED OPENING
'-9
A8.6
A8.6
A8.6
TYP., U.O.N.
TYP., U.O.N.
TYP., U.O.N.
5' -0
3'-0"
3' -0
/-VERIFY W/ EXIST.
FRAMED OPENING
2' -1
/2
6'-0"
'-8
L
T
BASEMENT
T.O. SLAB
U V
5'-0"
4' -1
1/
2" 2'
-0
6'-0"
4' -1
1/
2" 2'
-0
111 1
2t = TINTED INSULATED FULL-TEMPERED GLASS
= TEMPERED GLASS
= MIRROR GLASS
5 = CLEAR INSULATED 45-MINUTE FIRE RATED GLASS
(SINGLE PANE AT INTERIOR WINDOW)
6 = OBSCURE INSULATED GLASS
TINT ON WEST ELEV.
(TYPE 2 GLAZING)
TINT ON WEST ELEV.
(TYPE 2t GLAZING)
TINT ON WEST ELEV.
(TYPE 2 GLAZING)
TINT ON WEST ELEV.
(TYPE 2 GLAZING)
A8.6
A8.4
A8.4
A8.4
R.O.
R .O
A8.4
A8.6
A8.4
A8.6
M
AT
C H
(E
W
IN
D O
W
TY
PE
"O
" 11 A8.4
A8.4
A8.4
R.O. R.O.
R .O
M
AT
C
H (E
W
IN
D
O W
TY
PE
"O
PROVIDE VINYL WDW. ON S. ELEVATION AND
FIRE-RATED WINDOW ON N. ELEVATION
VINYL WDW. EXISTS ON S. ELEVATION - PROVIDE
FIRE - RATED WINDOW ON N. ELEVATION
FIELD VERIFY WINDOW
R.O. DIMENSIONS
A8.4
R.O. R.O.
R .O
R
.O
R .O
. R.O.
R .O
HOLLOW STL. FRAME -
45-MIN. RATED AT STAIR 2
TYP. ALL
LITES
ALL LITES @
STAIR 2
3'-0"+/-
4' -3
8' -4
W
COORDINATE DIMENSIONS W/
EXISTING TIMBER FRAMING
COORDINATE DIMENSIONS W/
EXISTING TIMBER FRAMING
KEYNOTES:
IN ADDITION TO SIDING REMOVAL/REPLACEMENT
NOTED ON PLANS, REMOVE (E) INSULATION AND
FURRING AS REQUIRED TO ACCESS WALL
SHEATHING FOR STRUCTURAL WORK. PATCH
BACK TO MATCH EXISTING CONSTRUCTION.
REMOVE AND REINSTALL (E) WINDOW TRIM AS
REQUIRED TO ACCESS SHEATHING FOR
STRUCTURAL WORK.
HORIZONTAL SIDING JOINT WITH Z-FURRING,
INSTALL PER MANUF. RECOMMENDATIONS
PROVIDE COPPER CAPS ON BEAM ENDS PER
SECTIONS AND DETAILS
SET AND FILL NAIL HEADS AT ALL TRIM BOARDS.
REMOVE (E) VERT. MULLION TRIM AND REPLACE
WITH NEW, BEVEL CUT TIGHT TO SILL
CUT EXISTING D.S., ADD ELBOWS, AND JOG OVER
STONE VENEER AND PRECAST CONC. TRIM
RP
RP
RP
RP
RP
WORK THAT IS CROSSED OUT IN RED IS FROM
PREVIOUS PROJECTS CONSTRUCTION DOCUMENTS
AND IS FOR REFERENCE ONLY. NOTIFY ARCHITECT
IF WORK SHOWN CROSSED OUT WAS NOT
COMPLETED PER THE OLD PROJECT DOCUMENTS.
R
EN
O
VA
TI
O
N O
F
EX
IS
TI
N G
R
ES
ID
EN
C E
N O
R
TH
G
AT
EW
AY
V
IS
IT
O
R C
EN
TE
R
SI
LV
ER
F
AL
LS
S
TA
TE
P
AR
K
H U
LT
R
D S
E
SI
LV
ER
TO
N
, O R
06/01/26 27
SU
IT
E
EXTERIOR
ELEVATIONS &
WINDOW SCHEDULE
JMR
A3.1
SCALE:
A3.1
EAST ELEVATION
1/8" = 1'-0"
SCALE:
A3.1
WEST ELEVATION
1/8" = 1'-0"
SCALE:
A3.1
SOUTH ELEVATION
1/8" = 1'-0"
SCALE:
A3.1
NORTH ELEVATION
1/8" = 1'-0"
SCALE:
A3.1
EAST ELEVATION - VESTIBULE
1/8" = 1'-0"
AutoCAD SHX Text
DATE
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
REVISIONS
BEAM PER STRUCT. STAIN
REMOVE EXISTING LOG BEAM AND STUD WALL
2x6 FURRING @ 24" O.C. W/ RIGID INSULATION INFILL, AND T&G WD. CEILING BETWEEN EXIST. BEAMS
TYP. FLOOR CONST. PER A8.1
EXIST. 4x12 BEAMS,WRAP W/ TRIM, TYP.
NEW WALL AND WINDOWS
REMOVE EXIST. DECKING & ROOFING @ NEW CLERESTORY
TYP. ROOF CONST. PER A8.1
A8.4
A8.1
A8.2
A8.2
5/4X6 WD. TRIM, STAIN
2ND FLR. TOP OF SHTHG.
EL. 109'-1 3/4"
ATTIC TOP OF SHTHG
EL. 118'-5 5/8"
1ST FLR. TOP OF SHTHG.
EL. 100'-0" (REF.)
A8.1
SIM.
REV.
2x6 FRAMING, INSUL. AND T&G
CEILING BEYOND
EXIST. FLOOR CONST.
EXIST. BASEMENT WALL
REMOVE EXIST. RAISED FLOOR
TYP. FLOOR CONST.
PER A8.1
REMOVE EXIST. TREE
TRUNK
(E) RETAINING WALL &
STAIRS - EXTEND PER
PLAN & ELEV.
LINE OF STAIRS BEHIND
PARTIAL HEIGHT WALL
9' -6
OPEN TO
BEYOND
OPEN TO
BEYOND
A8.1
A8.7
A8.7
FILL JOIST CAVITY W/ FIBERGLASS
BATT R-30 INSULATION
2ND FLR. TOP OF SHTHG.
EL. 109'-1 3/4"
ATTIC TOP OF SHTHG
EL. 118'-5 5/8"
1ST FLR. TOP OF SHTHG.
EL. 100'-0" (REF.)
BASEMENT TOP OF SLAB
EL. 89'-10 1/4"
A8.3
NEW BEAM PER STRUCTURAL, STAIN
A8.7
TYP. EXT. WALL CONST. PER A8.1
TYP. ROOF CONST. PER A8.1
A8.3
A8.1
6" RAIN DRAIN, TYP.
WATER-PROOFING ON EXIST. BASEMENT WALL, TYP.
4" CONC. SLAB PATCH, TYP.
4"Ø PERF. UNDERSLAB DRAIN, TYP.
DRAIN ROCK, TYP.
A8.3
KEYNOTES:
REMOVE NARROW STRIP OF PLYOOD AT BOTTOM
OF ROUGH FASCIA. REPLACE WITH 2x2 TRIM.
PROVIDE 1x TRIM OVER ROUGH FASCIA AND 2x2
PER DETAIL 4/A8.2
1RP
WORK THAT IS CROSSED OUT IN RED IS FROM
PREVIOUS PROJECTS CONSTRUCTION DOCUMENTS
AND IS FOR REFERENCE ONLY. NOTIFY ARCHITECT
IF WORK SHOWN CROSSED OUT WAS NOT
COMPLETED PER THE OLD PROJECT DOCUMENTS.
R
EN
O
VA
TI
O
N O
F
EX
IS
TI
N G
R
ES
ID
EN
C E
N O
R
TH
G
AT
EW
AY
V
IS
IT
O
R C
EN
TE
R
SI
LV
ER
F
AL
LS
S
TA
TE
P
AR
K
H U
LT
R
D S
E
SI
LV
ER
TO
N
, O R
06/01/26 27
SU
IT
E
SECTIONS
JMR
A3.2
SCALE:
A3.2
BUILDING SECTION - LOBBY
1/4" = 1'-0"
SCALE:
A3.2
BUILDING SECTION - DISPLAY & DINING
1/4" = 1'-0"
AutoCAD SHX Text
DATE
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
REVISIONS
TYP. FLOOR CONST. PER A8.1
EXIST. BEAM
EXIST. BASEMENT WALL PER PLAN
FURRED WALL PER PLAN
2'-0" 2'-0"
OPEN TO
BEYOND
1' -4
2ND FLR. TOP OF SHTHG.
EL. 109'-1 3/4"
ATTIC TOP OF SHTHG
EL. 118'-5 5/8"
1ST FLR. TOP OF SHTHG.
EL. 100'-0" (REF.)
BASEMENT…