Attachment_B__Switchgear_Price_List.xlsx
XLSX spreadsheet 25 KB Posted
- Attached to
- Pad mount Switchgear Contract
- Solicitation number
- PR9454
- Issued by
- Florida
About this file
This is a switchgear price list attachment for Orlando Utilities Commission (OUC), a Florida-based utility provider seeking competitive proposals for pad-mount switchgear equipment. The document provides detailed specifications and pricing for multiple switchgear models across two voltage classes (15KV and 25KV) with varying amperage ratings and configurations. Equipment types include live-front padmount switches (PMH series), dead-front padmount switches (PME series), and source-transfer switches, with models ranging from 200A to 600A ratings. The specifications detail enclosure dimensions, termination heights, base spacer options, fuse holder configurations, and compliance requirements for warning signage meeting ANSI Z535 standards. Lead times vary by equipment type, ranging from 1 to 17 days for different models.
The price list is structured in multiple sections including base equipment pricing by model, equipment options, and pricing tables for add-on features such as stainless steel enclosures, grounding modifications, latching systems, ventilation upgrades, bilingual labeling, base spacers, and fuse storage cabinets. Pricing for fault indicator provisions with and without viewing windows is provided for both mild steel and stainless steel configurations. The document includes a section for custom pricing on PME alternate fuse handling mechanisms and SML-20 fusing configurations for specific base models. All pricing modifications are presented as add or deduct adjustments from stated base unit prices, though specific dollar amounts are not populated in this version of the document.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Addendum_No.1_RFP_PR9454_Padmount_Switchgear.pdf | ||
| procaddendaform.pdf | ||
| RFP_PR9454_Padmount_Switchgear.pdf | ||
| Attachment_C__Equipment_Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Equipment price list
| Stock # | Catalog Number | General Description | Estimated Annual Usage | Lead-Time (Days) | Unit Price |
| 017-07072 | FEDERAL PACIFIC |
PSI-4-42011-B5B2A3OR PSI/II-(SAME)
S&C
PMH-4 55302R3-K18
MALTON
| MES104-B2G2G7S3 | SWITCH, PADMOUNT, 15KV, 200A LIVE-FRONT WITH 3 LOADBREAK FUSES (PMH-4 STYLE) | |
| GEAR IS LIVE FRONT, AIR INSULATED, WITH FUSED SIDE TERMINATION PAD AT 29 1/4" HEIGHT AND SOURCETERMINATION PAD AT 40" HEIGHT (INCLUDES 12" BASE SPACER). UNIT TO HAVE AT LEAST 1 GROUNDING PADPER SIDE. COMPARTMENT-1: INCLUDES THREE SML-4Z FUSE HOLDERS BUT NOT FUSES. COMPARTMENT-2:INCLUDES THREE TERMINATION PADS Enclosure "Warning" & "Danger" signage shall meet latest ANSI Z535requirements and OUC specifi cations approved manufacturer/catalog number (refer to stock#s 012-18091 &012-18092). DIMENSIONS: 34.5" (DOOR SIDES) X 38" (DEEP) S&C model dimensions: 34.875" width X 37.75"length X 44" height (includes 12" height stainless steel base spacer [K-18 option]). SML-4Z fuse holder Length:17.75" | 10 | |
| 017-57073 | S&C |
PMH-4 55303R3-K18
Malton
MES204-B2G2G7SP
FEDERAL PACIFIC
| PSI/II-4; 52011-AS3-B1-G1-G3 | SWITCH, PADMOUNT, 25KV, 200A LIVE-FRONT WITH 3 LOADBREAK FUSES (PMH-4 STYLE) | |
| Include three SML-4Z fuse holders (not refi ll units), barriers on both bus and fuse sides, 12" stainless steel basespacer and one ground pad (without studs) per side. Terminations on fuse side are 35 1/2" and line side are 50"(Includes 12" base spacer). Enclosure "Warning" & "Danger" signage shall meet latest ANSI Z535 requirementsand OUC specifi cations approved manufacturer/catalog number (refer to stock#s 012-18091 & 012-18092). S&Cmodel dimensions: 43" width X 56.75" length X 67" height (includes 12" height stainless steel base spacer). SML-4Z fuse holder Length: 22.25" | 17 | |
| 017-07099 | CHANCE |
LSS-9 C094LQ
Federal Pacific
44221-B1B2G1G2A2 (PSI/II-9)
S&C
55352R4-K17 (PMH-9)
Shallbetter SPL9 w/6" Base Spacer
ABB
| PS109ANNNMSSSSLN00 | SWITCH, PADMOUNT, 15KV, 600A/200A LIVE-FRONT WITH 6 S&C SML-4Z FUSE HOLDERS (PMH-9 STYLE) | |
| Enclosure 11 gauge steel, anti-condensation roof coating, approx. 60 to 70 inch wide and 61 to 76 inch deep,cable termination points at approx. 24 inch height, stainless hinges, viewing windows, GPO-3 fi berglass barriers,grounding studs, lifting brackets, fuse grabler, nameplate with month & year of manufacture and a 3-lineelectrical schematic. Enclosure "Warning" & "Danger" signage shall meet latest ANSI Z535 requirements andOUC specifi cations approved manufacturer/catalog number (refer to stock#s 012-18091 & 012-18092) | 9 | |
| 017-07189 | S&C | |
| 56652R2-C9-K17-N7- Y2-Y4-Y6-Y8 | SWITCH, PADMOUNT, 15KV, SOURCE-TRANSFER S&C WITH MICRO-AT CONTROL & 6 FAULT FITER FUSES (600AAIR-BREAK LIVE FRONT; PMH-9 TYPE) |
Unit comes with auxiliary switches [C9], A 6” stainless steel base spacer [K17], 10KV MOV arresters [N7], overcurrent lockout with 6 current sensors [Y2], remote indication capability [Y4], supervisory control capability [Y6], a communications card [Y8] and Fault Fiter fusing [(6) S&C cat# 99412R1 Fault Fiter fuse holders; (6) Fault Fiter control modules with time delayed compound curve (TCC-421-7; 7010-C40S1T6D8) and (6) S&C cat# 802600R2 Fault Fiter interrupting modules].
Standard source-transfer configuration:
1) Two 600A transfer switch bays (compartments 2 & 3; back-to-back) adjacent to the control compartment. Mini-Rupter switch rated 22,400A rms-asymmetrical
2) Two 400A (Fault Fiter fusing) load bays (compartments 1 & 4; back-to-back) furthest from control compartment. Fault Fiter rated 22,400A rms-asymmetrical Dimensions: Front (door side) – 67”; Side (depth) – 60.75” Termination heights (including 6” base spacer [K17]):
600A compartments: 22”; 200A compartments: 25”
| Enclosure "Warning" & "Danger" signage shall meet latest ANSI Z535 requirements and OUC specifications (refer to stock#s 012-18091 & 012-18092). | 3 | |
| 017-07090 | CHANCE |
LSS-10 C1000Q
Federal Pacific
PSI/II-10 44400-B1G2A2
S&C
PMH-10 55242R4-K17
Shallbetter SPL10 w/6" Base Spacer
ABB
PS110NNNNMSSSSLN00 SWITCH, PADMOUNT, 15KV, 600A LIVE-FRONT WITH 4-WAY SWITCHES (PMH-10 STYLE) Enclosure 11 gauge steel, anti-condensation roof coating, approx. 60 to 70 inch wide and 61 to 76 inch deep, cable termination points at approx. 24 inch height, stainless hinges, viewing windows, GPO-3 fiberglass barriers, grounding studs, nameplate with month & year of manufacture and a 3-line electrical schematic. Enclosure "Warning" & "Danger" signage shall meet latest ANSI Z535 requirements and OUC specifications approved manufacturer/catalog number (refer to stock#s 012-18091 & 012-18092).
| S&C Dimensions: 67” front X 60.75” depth X 44” height | 4 | |
| 017-07096 | S&C | |
| 65152R1-K17 | SWITCH, PADMOUNT, 15KV, 600A/200A, DEAD-FRONT, (PME-9 STYLE) | |
| UNIT COMES WITH 6 SETS OF FUSE ENDINGS, WITH SILENCER, (CAT# 3093) USED WITH SMU-20 FUSES (FUSESORDERED SEPARATELY). SWITCH AND FUSE COMPONENTS ARE ENCLOSED AND PROTECTED WITHIN AN INNERAIR-INSULATED GROUNDED STEEL COMPARTMENT. VIEWING WINDOW ALLOWS FOR VERIFICATION OF MINI-RUPTER SWITCH-BLADE POSITION (NO NEED TO MOVE 600 AMP ELBOWS TO ESTABLISH CLEARANCES). BUSHINGHEIGHTS: 600A SIDE - 39"; 200A SIDE - 39" (INCLUDING 6" BASE SPACER) Dimensions: 75” front X 66.75” depth X45.5” height ENCLOSURE "WARNING" & "DANGER" SIGNAGE SHALL MEET LATEST ANSI Z535 REQUIREMENTSAND OUC SPECIFICATIONS APPROVED MANUFACTURER/CATALOG NUMBER (REFER TO STOCK#s 012-18091 &012-18092). | 9 | |
| 017-07095 | S&C | |
| 65242R1-K17 | SWITCH, PADMOUNT, 15KV, 600A DEAD-FRONT WITH 4-WAY SWITCHES (PME-10 STYLE) |
EQUIPED WITH 4 SWITCH BAYS EACH HAVING 3-600A BUSHINGS AT 33" HEIGHT. SWITCH COMPONENTS ARE ENCLOSED AND PROTECTED WITHIN AN INNER AIR-INSULATED GROUNDED STEEL COMPARTMENT. VIEWING WINDOW ALLOWS FOR VERIFICATION OF MINI-RUPTER SWITCH-BLADE POSITION (OPEN/CLOSED). ENCLOSURE "WARNING" & "DANGER" SIGNAGE SHALL MEET LATEST ANSI Z535 REQUIREMENTS AND OUC SPECIFICATIONS APPROVED MANUFACTURER/CATALOG NUMBER (REFER TO STOCK#s 012-18091 & 012-18092).
| Dimensions: 75” front X 72.75” depth X 45.5” height | 8 | |
| 017- 57199 | S&C |
65153R1-K17
ABB
| PS209ANNNMSSSSNN00 | SWITCH, PADMOUNT, 25KV, 600A/200A, DEAD-FRONT, (PME-9 STYLE) | |
| UNIT COMES WITH 6 SETS OF FUSE ENDINGS, WITH SILENCER, (CAT# 3093) USED WITH SMU-20 FUSES (FUSESORDERED SEPARATELY). SWITCH AND FUSE COMPONENTS ARE ENCLOSED AND PROTECTED WITHIN AN INNERAIR-INSULATED GROUNDED STEEL COMPARTMENT. VIEWING WINDOW ALLOWS FOR VERIFICATION OF MINI-RUPTER SWITCH-BLADE POSITION (NO NEED TO MOVE 600 AMP ELBOWS TO ESTABLISH CLEARANCES). UNITHAS 6 INCH STAINLESS STEEL BASE ADAPTER. PAD DIMENSIONS: 96"X 94" EXTERIOR; WITH 78"X 70" OPENING.BUSHING TERMINATION HTS: 600A SIDE - 40"; 200A SIDE - 44.75" FUSE SIDE CABLE GUIDE LOOPS: 7" ABOVEGRADE; 4" WIDE AND 4" PAST BASE EDGE ENCLOSURE "WARNING" & "DANGER" SIGNAGE SHALL MEET LATESTANSI Z535 REQUIREMENTS AND OUC SPECIFICATIONS APPROVED MANUFACTURER/CATALOG NUMBER (REFERTO STOCK#s 012-18091 & 012-18092). S&C Dimensions: 84” front X 81.75” depth X 51.5” height | 3 | |
| 017-57091 | S&C | |
| 65243R1 | SWITCH, PADMOUNT, 600A, 4-WAY DEADFRONT 25kV (PME-10 MODEL) |
SWITCHGEAR HAS FOUR MINI-RUPTER SWITCHES (600A RATED). MODEL TO INCLUDE VISIBLE-BREAK WITH 2-POSITION CONFIGURATION (CLOSE-OPEN). UNIT IS INSULATED AT 125kV BIL WITH A SHORT CIRCUIT RATING OF 12,500A.
Dimensions: 84” front X 88.25” depth X 51.5” height Bushing height: 34"
| Weight: 2400 lbs. | 1 | ||
| 017-07071 | S&C | 55302R3-K8-E101 | |
| Shallbetter SFGL-24-115CL24-L4-SV-22-GA-OUC | SWITCH, PADMOUNT, 15KV, 200A, LIVE-FRONT WITH 2 SWITCHES AND 4 LOADBREAK FUSES (SPECIAL TYPE 4 STYLE) |
Switchgear, Padmounted, 15KV, Live Front, 400A rated bus, Air Insulated, with min. 24" high termination points and 1 Grounding pad per side. Includes holders but not fuses. Has 2 single phase source switch positions (solid disconnect blade in fault fiter mountings [S&C cat# S-90793]) and four 200A fuse positions (SML-4Z fuse holders) – see diagram.
Enclosure "Warning" & "Danger" signage shall meet latest ANSI Z535 requirements and OUC specifications approved manufacturer/catalog number (refer to stock#s 012-18091 & 012-18092). 1 http://www.aursi.com/ Base Price EQUIPMENT TYPE Equipment Base Price Catalog Number Lead Time (days) Equipment Freight Charges (per unit)
| 15KV PMH - 4 |
| 15KV PMH - 6 |
| 15KV PMH - 9 |
| 15KV PMH - 10 |
| 15KV PMH - 11 |
| 15KV PMH - 12 |
| 15KV PMH - 13 |
| 15KV PME - 6 |
| 15KV PME - 9 |
| 15KV PME - 10 |
| 15KV PME - 11 |
| 25KV PMH - 4 |
| 25KV PMH - 5 |
| 25KV PMH - 9 |
| 25KV PMH - 10 |
| 25KV PMH - 11 |
| 25KV PMH - 12 |
| 25KV PME - 6 |
| 25KV PME - 9 |
| 25KV PME - 10 |
| 25KV PME - 11 |
| 25KV PME - 12 |
Equipment Options
| EQUIPMENT TYPE | Option (a) | Option (b) | Option (c) | Option (d) | Option (e) | Option (f) | Option (g) | Option (h) |
| 15KV PMH - 4 | $ | $ | $ | $ | $ | $ | $ | $ |
| 15KV PMH - 6 | $ | $ | $ | $ | $ | $ | $ | $ |
| 15KV PMH - 9 | $ | $ | $ | $ | $ | $ | $ | $ |
| 15KV PMH - 10 | $ | $ | $ | $ | $ | $ | $ | $ |
| 15KV PMH - 11 | $ | $ | $ | $ | $ | $ | $ | $ |
| 15KV PMH - 12 | $ | $ | $ | $ | $ | $ | $ | $ |
| 15KV PMH - 13 | $ | $ | $ | $ | $ | $ | $ | $ |
| 15KV PME - 6 | $ | $ | $ | $ | $ | $ | $ | $ |
| 15KV PME - 9 | $ | $ | $ | $ | $ | $ | $ | $ |
| 15KV PME - 10 | $ | $ | $ | $ | $ | $ | $ | $ |
| 15KV PME - 11 | $ | $ | $ | $ | $ | $ | $ | $ |
| 25KV PMH - 4 | $ | $ | $ | $ | $ | $ | $ | $ |
| 25KV PMH - 5 | $ | $ | $ | $ | $ | $ | $ | $ |
| 25KV PMH - 9 | $ | $ | $ | $ | $ | $ | $ | $ |
| 25KV PMH - 10 | $ | $ | $ | $ | $ | $ | $ | $ |
| 25KV PMH - 11 | $ | $ | $ | $ | $ | $ | $ | $ |
| 25KV PMH - 12 | $ | $ | $ | $ | $ | $ | $ | $ |
| 25KV PME - 6 | $ | $ | $ | $ | $ | $ | $ | $ |
| 25KV PME - 9 | $ | $ | $ | $ | $ | $ | $ | $ |
| 25KV PME - 10 | $ | $ | $ | $ | $ | $ | $ | $ |
| 25KV PME - 11 | $ | $ | $ | $ | $ | $ | $ | $ |
| a. Stainless Steel - Add / Deduct to base unit for making the enclosure and doors out of Stainless Steel. | ||||||||
| b. Grounding- Add/Deduct to base unit for changing the grounding studs as per the option specifications | ||||||||
| c. 3 Point Latching- Add/Deduct to base unit for changing the 3 Point Latching as per the option specifications - PMH Switchgear from Manual to Automatic & PME Switchgear from Automatic to Manual | ||||||||
| d. Ventilation System- Add/Deduct to base unit for changing the Ventilation | ||||||||
| e. Warning & Danger Labels- Add/Deduct to base unit for changing the Labels to Bilingual per the option specifications | ||||||||
| f. PME- Alternate Fuse Handling Mechanism- Add/Deduct to base unit for changing the Fuse Handling Mechanism from the S&C Specified to another type per the option specifications. | ||||||||
| g. Provide a price for adding a 6 inch stainless steel base spacers to a PMH and/or PME switchgear | ||||||||
| h. Provide a price for adding a 12 inch stainless steel base spacers to a PMH and/or PME switchgear |
Other Pricing Tables
| Description | Price | Lead Time | |
| (Days) | Catalog Code | Add or Deduct from Base Price | |
| Fuse Storage Mild Steel Cabinet – | |||
| Add/Deduct to base unit for one extra fuse-storage feature. | $ | ||
| Fuse Storage Stainless Steel Cabinet – | |||
| Add/Deduct to base unit for one extra fuse-storage feature. | $ | ||
| Fault Indicator Provisions without a viewing window Mild Steel Cabinet – Add/Deduct to base unit for manufacturing the enclosure with provisions to accommodate a three-phase fault indicator. (Price is per location) | $ | ||
| Fault Indicator Provisions without a viewing window Stainless Steel Cabinet – Add/Deduct to base unit for manufacturing the enclosure with provisions to accommodate a three-phase fault indicator. (Price is per location) | $ | ||
| Fault Indicator Provisions with a viewing window Mild Steel Cabinet – Add/Deduct to base unit for manufacturing the enclosure with provisions to accommodate a three-phase fault indicator. (Price is per location) | $ | ||
| Fault Indicator Provisions with a viewing window Stainless Steel Cabinet – Add/Deduct to base unit for manufacturing the enclosure with provisions to accommodate a three-phase fault indicator. (Price is per location) | $ | ||
| PMH– SML-20 Fusing – Provide a price for the base model 15kV PMH – 9 using a SML – 20 Fusing configuration instead of the SME-4Z called out in the specifications. | $ |
File details come from the government source that posted it. Updated .