About this file

The file is a Price Proposal Template for the County of San Mateo, California, detailing the specifications for generator replacements at five different sites. The project involves replacing existing generators with new Caterpillar generator sets at locations including San Carlos, Brisbane Icehouse Hill, Sweeney Ridge, San Bruno Nike, and Rolph Peak. Each site will receive a new generator with specific technical specifications, including propane-powered standby units ranging from 40kW to 50kW, with UL2200 IBC Seismic Certification, EPA certification for stationary emergency use, and complete with control panels, circuit breakers, transfer switches, and additional equipment like remote annunciator modules and emergency stop features.

The proposal template shows zero dollar amounts for other materials and labor costs, suggesting that pricing details may be completed separately or are part of a broader bid package. The generators are being replaced to support the County's public safety radio communication systems, with each site currently having older generators from manufacturers like Generac and Kohler being replaced by more modern Caterpillar units. The replacement equipment is standardized across sites, featuring similar technical specifications including single-phase 240/120V configurations, 60Hz operation, seismic vibration isolators, and comprehensive safety and operational features designed to ensure reliable backup power for critical infrastructure.

View the file

Other files

File Type Posted
RFP_Installation_and_Replacement_of_Generators_(Addendum_#10_Revision).pdf PDF
Attachment_B_Price_Proposal_Template_ISD-20261908_11_21_25.xlsx XLSX spreadsheet
Attachment_A_ISD-20261908_Installation_and_Replacement_of_Generators_11-21-25.pdf PDF
RFP_Installation_and_Replacement_of_Generators_(Addendum_#4_Revision).pdf PDF
RFP_Installation_and_Replacement_of_Generators_(Addendum_#2_Revision).pdf PDF
RFP_Installation_and_Replacement_of_Generators.pdf PDF
Attachment_A_ISD-20261908_Installation_and_Replacement_of_Generators.pdf PDF
Attachment_A_ISD-20261908_Installation_and_Replacement_of_Generators.pdf PDF
Attachment_A_ISD-20261908_Installation_and_Replacement_of_Generators.pdf PDF
Attachment_A_ISD-20261908_Installation_and_Replacement_of_Generators.pdf PDF
Attachment_E_SMC_Local_Preference_Self-Attestation_Form.pdf PDF
Attachment_E_SMC_Local_Preference_Self-Attestation_Form.pdf PDF
Attachment_E_SMC_Local_Preference_Self-Attestation_Form.pdf PDF
Attachment_E_SMC_Local_Preference_Self-Attestation_Form.pdf PDF
Attachment_C_References_Template.docx DOCX document
Attachment_D_County_Standard_Contract_Template.docx DOCX document
Attachment_D_County_Standard_Contract_Template.docx DOCX document
Attachment_C_References_Template.docx DOCX document
Attachment_D_County_Standard_Contract_Template.docx DOCX document
Attachment_C_References_Template.docx DOCX document
Attachment_D_County_Standard_Contract_Template.docx DOCX document
Attachment_C_References_Template.docx DOCX document
Attachment_B_Price_Proposal_Template_ISD-20261908.xlsx XLSX spreadsheet
Attachment_B_Price_Proposal_Template_ISD-20261908.xlsx XLSX spreadsheet
Attachment_B_Price_Proposal_Template_ISD-20261908.xlsx XLSX spreadsheet
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sites

DescriptionOther Materials $Other Costs $Labor $Total
Site 1 - San Carlos Site 60$0.00
Current Equipment: Generac 20kW, 120/240 VAC, Model # 20A00252-S, mounted on reinforced wood pads
County Provided Replacement Equipment:
Caterpillar DG40 40kW Standby Propane Indoor Generator Set, 240/120V, Single Phase, 60Hz, 1800 rpm
UL2200
IBC Seismic Certification
EPA Certified for Stationary Emergency Use, GCCP 1.2 Control Panel
NFPA 110 Local Alarm Panel Circuit Breakers
1 x 250 amps 100% Rated Main Breaker, LSI with shunt trip and aux contacts
Jacket Water Heater
Anti-condensation alternator winding space heater
DC Charging Alternator
Starting Motor
AC Battery Charger Starting Batteries with Rack Seismic Vibration Isolators
(1) Remote Annunciator Module, 16 light, shipped loose
(1) Remote E Stop shipped loose
Automatic Transfer Switch: CG 260A, 480V, 1PH, NEMA 1, Delayed Transition, Non-Bypass, 50kAIC
Site 2 - Brisbane Icehouse Hill$0.00
Current Equipment: Generac 20kW, 120/240 VAC, Model # 20A00252-S, mounted on reinforced wood pads
County Provided Replacement Equipment:
Caterpillar DG40 40kW Standby Propane Indoor Generator Set, 240/120V, Single Phase, 60Hz, 1800 rpm
UL2200
IBC Seismic Certification
EPA Certified for Stationary Emergency Use, GCCP 1.2 Control Panel
NFPA 110 Local Alarm Panel Circuit Breakers
1 x 250 amps 100% Rated Main Breaker, LSI with shunt trip and aux contacts
Jacket Water Heater
Anti-condensation alternator winding space heater
DC Charging Alternator
Starting Motor
AC Battery Charger Starting Batteries with Rack Seismic Vibration Isolators
(1) Remote Annunciator Module, 16 light, shipped loose
(1) Remote E Stop shipped loose
Automatic Transfer Switch: CG 260A, 480V, 1PH, NEMA 1, Delayed Transition, Non-Bypass, 50kAIC
Site 3 - Sweeney Ridge$0.00
Current Equipment: Generac 20kW, 120/240 VAC, Model # 20A00252-S, mounted on reinforced wood pads
County Provided Replacement Equipment:
Caterpillar DG40 40kW Standby Propane Indoor Generator Set, 240/120V, Single Phase, 60Hz, 1800 rpm
UL2200
IBC Seismic Certification
EPA Certified for Stationary Emergency Use, GCCP 1.2 Control Panel
NFPA 110 Local Alarm Panel Circuit Breakers
1 x 250 amps 100% Rated Main Breaker, LSI with shunt trip and aux contacts
Jacket Water Heater
Anti-condensation alternator winding space heater
DC Charging Alternator
Starting Motor
AC Battery Charger Starting Batteries with Rack Seismic Vibration Isolators
(1) Remote Annunciator Module, 16 light, shipped loose
(1) Remote E Stop shipped loose
Automatic Transfer Switch: CG 260A, 480V, 1PH, NEMA 1, Delayed Transition, Non-Bypass, 50kAIC
Site 4 - San Bruno Nike$0.00
Current Equipment: Kohler 35kW, 120/240 VAC, Model # 35RZ61, mounted on concrete floors.
County Provided Replacement Equipment:
Caterpillar DG50 50kW Standby Propane Indoor Generator Set, 240/120V, Single Phase, 60Hz, 1800 rpm
UL2200
IBC Seismic Certification
EPA Certified for Stationary Emergency Use, GCCP 1.2 Control Panel
NFPA 110 Local Alarm Panel Circuit Breakers
1 x 250 amps 100% Rated Main Breaker, LSI with shunt trip and aux contacts
Jacket Water Heater
Anti-condensation alternator winding space heater
DC Charging Alternator
Starting Motor
AC Battery Charger Starting Batteries with Rack Seismic Vibration Isolators
(1) Remote Annunciator Module, 16 light, shipped loose
(1) Remote E Stop shipped loose
Automatic Transfer Switch: CG 260A, 480V, 1PH, NEMA 1, Delayed Transition, Non-Bypass, 50kAIC
Site 5 - Rolph Peak$0.00
Current Equipment: Kohler 49kW, 120/240 VAC, Model # 50RZ262, mounted on concrete floors.
County Provided Replacement Equipment:
Caterpillar DG50 50kW Standby Propane Indoor Generator Set, 240/120V, Single Phase, 60Hz, 1800 rpm
UL2200
IBC Seismic Certification
EPA Certified for Stationary Emergency Use, GCCP 1.2 Control Panel
NFPA 110 Local Alarm Panel Circuit Breakers
1 x 250 amps 100% Rated Main Breaker, LSI with shunt trip and aux contacts
Jacket Water Heater
Anti-condensation alternator winding space heater
DC Charging Alternator
Starting Motor
AC Battery Charger Starting Batteries with Rack Seismic Vibration Isolators
(1) Remote Annunciator Module, 16 light, shipped loose
(1) Remote E Stop shipped loose
Automatic Transfer Switch: CG 260A, 480V, 1PH, NEMA 1, Delayed Transition, Non-Bypass, 50kAIC