This is a technical specifications document for the Michigan Department of Transportation (MDOT) Office of Aeronautics detailing foundation standards and installation requirements for Automated Weather Observation System (AWOS) installations at Michigan airport sites, including Gladwin Zettel Memorial Airport (GDW) and Paul C. Miller–Sparta Airport (8D4). The document provides comprehensive engineering plans and specifications for excavation, landscaping, grounding systems, and sensor layout configurations. It includes detailed CAD drawings showing excavation depths ranging from 2 to 5 feet, specifications for limestone geotextile materials, earth electrode systems with copper components, and precise placement of weather sensors including lightning sensors, wind towers, barometers, rain gauges, and visibility equipment. The installation specifications outline requirements for communication cables, power cables, counterpoise wires, and ground rods with specific depth, spacing, and separation requirements to ensure proper functionality and safety of the AWOS installations.

The foundation standards establish minimum installation depths of 24 inches below finished grade for communication and power cables, with lateral spacing requirements of at least 6 feet between different cable types except where necessary for duct bank entry. Ground rods must be spaced no more than 300 feet apart around the entire circuit, with 3-foot separation from duct or conduit ends, and the top of each rod must be at least 10 inches below finished grade. Backfilling procedures require specific layer depths and compaction standards, with concrete markers required at duct and conduit ends. Trenches must be a minimum of 24 inches deep and 6 inches wide, with conduit installations at a minimum of 36 inches below finished grade graded at 3 inches per 100 feet toward handholes and duct ends. The document establishes standards applicable to all Michigan AWOS sites, providing contractors with uniform technical requirements for concrete and electrical work at multiple airport locations.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A1

A2

A3

A4

A5

A6

A7

A8

A9

N

A A

21.0

2' excavation around the perimeter of the excavation.

Access ramp from ground level to the bottom of the excavation.

3' excavation.

4' excavation.

5' excavation.

34.0'

Scale 1" = 4'

2.0 ' 3.0

' 4.0

2.0

5.0'

A-A

A10 Rev # Date DESCRIPTION Initials

Michigan Department of Transportation

OFFICE OF AERONAUTICS

Electronic Facilities Unit

Drawn By: P. Murphy

Date: 01/02/2025

Site: GDW

Gladwin Zettel Memorial Airport

EXCAVATION PLAN

File Name: GDW AWOS 2024.dwg

AutoCAD SHX Text All excavated soil will be placed at the

AutoCAD SHX Text corners of the site to allow maximun

AutoCAD SHX Text access to the excavation site for further

AutoCAD SHX Text work.

AutoCAD SHX Text The excess excavated soil will be

AutoCAD SHX Text disbursed at a site that will be determined

AutoCAD SHX Text and approved by the authorized MDOT

AutoCAD SHX Text person.

N 6AA Limestone

Geotextile material

6AA Limestone

Geotextile material

6AA Limestone

Geotextile material

A11 Rev # Date DESCRIPTION Initials

Michigan Department of Transportation

OFFICE OF AERONAUTICS

Electronic Facilities Unit

Drawn By: P. Murphy

Date: 01/02/2025

Site: GDW

Gladwin Zettel Memorial Airport

LANDSCAPING PLAN

File Name: GDW AWOS 2024.dwg

Lightning Sensor

|--------------------17'-----------------|

AutoCAD SHX Text 4"

AutoCAD SHX Text 2"

AutoCAD SHX Text 6"

AutoCAD SHX Text Perimeter Edging

AutoCAD SHX Text 4"

AutoCAD SHX Text Foundation Edging

AutoCAD SHX Text Earth Electrode Access Edging

AutoCAD SHX Text 18'

AutoCAD SHX Text Scale 1" = 3'

AutoCAD SHX Text 21'

AutoCAD SHX Text

EARTH ELECTRODE ACCESS

AutoCAD SHX Text 6'

AutoCAD SHX Text 4'

Top of Limestone

#2 AWG Bare Copper, 7 Strand

4/0 AWG Bare Copper, 19 Strand

Cadweld Mold

P/N: GTC 182Q

#115 Weld Metal

Cadweld Mold

P/N: PCC 2Q1V

#115 Weld Metal

3/4" x 10' Copper Clad Ground Rod (4)

#2 AWG Bare Copper, 7 Strand

Plastic Bushings (2)

POWER CABLE CONDUIT

1" Galvanized Rigid

Counterpoise above underground cable to enter access well 10 - 14" below top of well cover.

COMMUNICATIONS CABLE CONDUIT

1" Galvanized Rigid

4/0 AWG Bare Copper, 19 Strand

3/4" x10' Ground Rod

NEUTRAL CONDUIT

3/4" Galvanized Rigid

MDOT WILL MAKE CONNECTIONS

IN ACCESS WELL

Cadweld Mold

P/N: SSC 20

#90 Weld Metal

Cover

Quazite P/N PG1324BA08 Enclosure w/No Base

Wind Tower Signal Conduit 3/4" Galvanized Rigid

Quazite P/N PG1324EA08 Enclosure Extension

Quazite P/N PG1324DA12 Enclosure w/Base

A12 Rev # Date DESCRIPTION Initials

Michigan Department of Transportation

OFFICE OF AERONAUTICS

Electronic Facilities Unit

Drawn By: Zach Tecson

Date: 11/05/2021

Site: 8D4

Paul C. Miller - Sparta Airport

EARTH ELECTRODE SYSTEM

File Name: 8D4 AWOS 2021.dwg

Lightning Sensor

30'

|-------------17"---------------|

RWY 07/25

TRUE

1 Temperature & Dewpoint Variation = 5° 43' W

Visibility

Removed Scale 1" = 3' VHF Transmitter

ACU Processor

VHF Antenna

Rain Gage

Barometer Vent

Removed

UPS + UPS Batteries

Ultrasonic Wind Sensor

Dual Obstruction Light

Wind Tower

4" 6AA limestone over geotextile weedblock.

50'

Drawn By: Zach Tecson Paul C. Miller - Sparta Airport A13

Rev # Date DESCRIPTION Initials Michigan Department of Transportation

OFFICE OF AERONAUTICS

Electronic Facilities Unit

Date: 11/05/2021

Site: 8D4

SENSOR LAYOUT

File Name: 8D4 AWOS 2021.dwg

Lightning Sensor

|----------------17'-------------------|

AUTOMATED WEATHER OBSERVATION SYSTEM

SPECIFICATIONS - ALL MICHIGAN SITES

INSTALLATION SPECIFICATIONS:

Communication and Voice Cable Depth minimum of 24 inches below finished grade

Spacing minimum of 6 feet from any power cable, except as necessary to enter a duct bank; minimum of 10 inches below any counterpoise (guard) wire

Power Cable Depth - trenched each conductor a minimum of 24 inches below finished grade

Depth - plowed top conductor a minimum of 24 inches below finished grade, with the second conductor a minimum of 3 inches below the top conductor

Spacing - trenched two conductors spaced laterally a minimum of 3 inches apart; a minimum of 6 feet from any communication or voice cable, except as necessary to enter a duct bank; minimum of 10 inches below any counterpoise (guard) wire

Spacing - plowed two conductors spaced vertically a minimum of 3 inches apart, with the top conductor spaced a minimum of 10 inches below any counterpoise (guard) wire; and a minimum of 6 feet from any communication cable, except as necessary to enter a duct bank

Counterpoise (Guard) Wire Depth a minimum depth of 14 inches below finished grade, while maintaining separation of 10 inches above any cable

Spacing a minimum of 10 inches above any cable, while maintaining a minimum depth of 14 inches below finished grade; will be terminated 3 feet from any duct

Ground Rod Depth top of rod a minimum of 10 inches below finished grade

Spacing spaced no more than 300 feet apart around the entire circuit;

spaced 3 feet from the end on any duct or conduit

Specifications - Page 1

A14

Trench Depth a minimum depth of 24 inches below finished grade

Width a minimum of 6 inches wide

Spacing a minimum of 6 feet apart for communication/voice cables and power cables, except as necessary to enter a duct bank

Backfilling 1st Layer 4 inches deep, loose measurement; not compacted

2nd Layer 4 inches deep, loose measurement; then tamped and compacted

Other Layers not to exceed 8 inches deep, loose measurement; then tamped and compacted

Concrete Marker Size 2 foot square by 4 inches thick, OR 24 inches in diameter by 4 inches thick

Placement flush with ground at th end of each duct or conduit; placed immediately above the end of the duct or conduit

Marking DUCT (with quantity and sizes); letters/numbers 4 inches high and 3 inches wide, with ½ inch width of stroke and 1/4 inch deep

Conduit Depth a minimum depth of 36 inches below finished grade

Grade 3 inches per 100 feet, toward handholes, manholes, and duct ends

Length extend 5 feet beyond edge of pavement or any under drains installed alongside paved area

Trenches SINGLE - - not less than 6 inches nor more than 12 inches wide 2 OR MORE - - proportionately wider

Specifications - Page 2

A15

Foundation Standards Vaisala.pdf
GDW AWOS 2024_09Excavation.pdf
Sheets and Views
GDW AWOS 2024-Excavation
GDW AWOS 2024_08Landscaping.pdf
Sheets and Views
GDW AWOS 2024-Landscaping
8D4.8 Earth Electrode System.pdf
8D4.5 Sensor Layout.pdf

File details come from the government source that posted it. Updated .