This document is an installation specifications guide for Automated Weather Observation System (AWOS) cable work across Michigan Department of Transportation (MDOT) sites. The specifications detail comprehensive requirements for communication and voice cable installation, power cable installation, counterpoise wire placement, ground rod spacing, trench construction, and conduit installation. Communication and voice cables must be installed at a minimum depth of 24 inches below finished grade with a minimum 6-foot spacing from power cables, while power cables require the same 24-inch depth with conductors spaced at least 3 inches apart. Counterpoise guard wires must maintain a minimum depth of 14 inches below finished grade and be positioned at least 10 inches above any cable. Ground rods are to be spaced no more than 300 feet apart around the entire circuit and positioned at least 3 feet from duct or conduit ends.

The specifications further establish detailed requirements for trench construction, backfilling procedures, and concrete marker placement and identification. Trenches must maintain a minimum depth of 24 inches below finished grade with a minimum 6-inch width and must be backfilled in layers—the first 4 inches loose and uncompacted, the second 4 inches tamped and compacted, and subsequent layers not exceeding 8 inches before compaction. Concrete markers, either 2 feet square by 4 inches thick or 24 inches in diameter by 4 inches thick, must be placed flush with ground at duct or conduit ends and marked with legible identification. Conduit must be installed at a minimum depth of 36 inches below finished grade with a grade of 3 inches per 100 feet toward handholes and must extend 5 feet beyond pavement edges.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Specifications - Page 1

AUTOMATED WEATHER OBSERVATION SYSTEM

SPECIFICATIONS - ALL MICHIGAN SITES

INSTALLATION SPECIFICATIONS:

Communication and Voice Cable Depth minimum of 24 inches below finished grade

Spacing minimum of 6 feet from any power cable, except as necessary to enter a duct bank; minimum of 10 inches below any counterpoise (guard) wire

Power Cable Depth - trenched each conductor a minimum of 24 inches below finished grade

Depth - plowed top conductor a minimum of 24 inches below finished grade, with the second conductor a minimum of 3 inches below the top conductor

Spacing - trenched two conductors spaced laterally a minimum of 3 inches apart; a minimum of 6 feet from any communication or voice cable, except as necessary to enter a duct bank; minimum of 10 inches below any counterpoise (guard) wire

Spacing - plowed two conductors spaced vertically a minimum of 3 inches apart, with the top conductor spaced a minimum of 10 inches below any counterpoise (guard) wire; and a minimum of 6 feet from any communication cable, except as necessary to enter a duct bank

Counterpoise (Guard) Wire Depth a minimum depth of 14 inches below finished grade, while maintaining separation of 10 inches above any cable

Spacing a minimum of 10 inches above any cable, while maintaining a minimum depth of 14 inches below finished grade; will be terminated 3 feet from any duct

Ground Rod Depth top of rod a minimum of 10 inches below finished grade

Spacing spaced no more than 300 feet apart around the entire circuit;

spaced 3 feet from the end on any duct or conduit

Specifications - Page 2

Trench Depth a minimum depth of 24 inches below finished grade

Width a minimum of 6 inches wide

Spacing a minimum of 6 feet apart for communication/voice cables and power cables, except as necessary to enter a duct bank

Backfilling 1st Layer 4 inches deep, loose measurement; not compacted

2nd Layer 4 inches deep, loose measurement; then tamped and compacted

Other Layers not to exceed 8 inches deep, loose measurement; then tamped and compacted

Concrete Marker Size 2 foot square by 4 inches thick, OR 24 inches in diameter by 4 inches thick

Placement flush with ground at th end of each duct or conduit; placed immediately above the end of the duct or conduit

Marking DUCT (with quantity and sizes); letters/numbers 4 inches high and 3 inches wide, with ½ inch width of stroke and 1/4 inch deep

Conduit Depth a minimum depth of 36 inches below finished grade

Grade 3 inches per 100 feet, toward handholes, manholes, and duct ends

Length extend 5 feet beyond edge of pavement or any under drains installed alongside paved area

Trenches SINGLE - - not less than 6 inches nor more than 12 inches wide 2 OR MORE - - proportionately wider