This specification sheet details the construction and material requirements for a modular Blazer PM office building measuring 144 feet by 60 feet, designed for the Portland Air National Guard in Portland, Oregon. The facility is classified as an office/ADA-compliant structure with a transverse roof and will be installed on a provided foundation. The building includes a steel frame with 12 modules (each 11 feet 8 inches by 60 feet), a floor system with R30 insulation and plywood decking, 2x6 exterior wall framing at 128 inches height with R21 insulation, and a roof structure featuring 2x8 rafters with cellulose blow-in insulation (R24) and rigid insulation (R17). The exterior finish specifies LP SmartSide Panel T1-11 siding with finger-jointed cedar trim and fascia, 60 mil TPO roofing, and includes skirting with aluminum vents. The building incorporates four restrooms equipped with ADA-compliant fixtures, a break area with 40 linear feet of cabinets, and comprehensive mechanical, electrical, and plumbing systems.

The specification includes twelve Bard 2.5-ton heat pumps with 10 kilowatt electric resistance and economizers rated at 11 EER, accompanied by supply and return plenums, insulated flexduct, and remote temperature sensors. Plumbing provisions include ADA-compliant toilets, urinals, lavatories, a commercial sink, two electric tankless water heaters, a six-gallon energy-saver water heater, and one barrier-free drinking fountain. Electrical service comprises 120/240-volt single-phase power with twelve 125-amp weather-proof panels, 130 standard duplex receptacles, multiple GFCI-protected outlets, 40 automated wall switches, and 67 LED troffer fixtures with 6000 lumens and occupancy sensors. The specification includes a wet-system sprinkler installation per NFPA 13 for light hazard classification, with crossover unions and on-site testing performed by Western States Sprinkler. The specification excludes backflow devices, fire department connections, under-floor/exterior piping, electrical and fire alarm work, and notes that prevailing wage requirements are not included in the Blazer estimate.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SPECIFICATION SHEET

Bidspec Blazer PM

Date: Size: 144x60 Floor:

Customer: Sabala Management Description: Office/ADARR Wind:

Location: Portland, Oregon Mobile Roof:

Project: Portland Air National Guard Insignias: Oregon

Install insignias on exterior of building as shown on A-3

MBI Seals - One per Module

FOUNDATION

Block and level - Provided and installed on site by others - Tie down straps provided and installed by others

STEEL FRAME

Size: (12) 11'-8" x 60'-0"

Type: Blazer built frame (no outriggers - Full width front and rear crossmembers)

Main Rail: W10 x 12

Axles: 4 or 5-Brake with 8:00x14.5 - 14 ply tires as required per engineering

Hitch: Detachable

FLOOR SYSTEM

Joists: 2x8 @ 16" oc

Rims: Single LVL 7-1/8"

Frame Openings For: (2) Floor Drains

Bottom Board: Class "A" woven polyethylene fabric

Insulation: R30 - Use two layers of R15 unfaced fiberglass batt

Decking (1st): 23/32" (3/4") APA rated Sturd-I-Floor T&G – Glued and Nailed - PointSIX (turquoise edge)

Decking (2nd): 1/4" Plywood Underlayment in Restrooms only

WALL FRAMING

Framing (Exterior): 2x6 @ 16" oc - Height = 128"

Framing (Interior): 2x4 @ 16" oc - Plumbing walls to be 2x6 or 2x8 - Double walls at mod line - Height = 114-1/2"

Plenum Wall: (12) Standard for sound reduction - Insulate stud wall - Shaft to be lined with 5/8" sheetrock

Columns/Posts: Wood end columns with wood and steel posts built into interior walls - Exposed posts in Common Area

ROOF STRUCTURE

Style: Transverse - Roof pitch = 1/4 / 12

Framing: 2x8 Rafters @ 16" oc

Bottom cover: Class "A" woven polyethylene fabric

Modline Beams: Single or Double LVL 1-1/2" x 24" - Double Taper Cut - As required per engineering

Rims: Single LVL 1-1/2" x 14-3/4" - Double Taper Cut

Insulation: Cellulose blow in between rafters (R24) with two layers 1-1/2" rigid (R17) on top of roof framing

Sheathing: 3/4" CDX plywood

Roof Overhang: None

Venting: None

DESIGN LOADS:

120/B

8/11/2026

SPEC-E5808-144x60 Portland Air National Guard (2026 0811) Page 1 of 6 8/11/2026

Blazer PM

EXTERIOR WALL FINISH

Insulation (Exterior): R21 unfaced fiberglass batt

Moisture protection: Wrap lower 12" of building with Moistop - Wrap building with Tyvek building wrap

Siding: 76 Series LP SmartSide Panel T1-11 with grooves 8" oc - 4x10

Trims: Corners: 1x4 Finger Jointed Cedar - 2" x 2" galvanized flashing installed over siding and under corners

Mod line: 1x4 Finger Jointed Cedar - Ship loose to be installed on site by others

Fascia: 1x6 Finger Jointed Cedar - Furred out 1-1/2" on all four sides

Door: 1x4 Finger Jointed Cedar

Window: 1x4 Finger Jointed Cedar

Z flashings: 1/2" at bottom of siding and at siding break - 2" back leg and 3/4" front leg

Skirting: Ship loose (34) 4' x 9' pieces of 7/16" LP SmartSide Panel T1-11 with grooves 8" oc with

(4) corners and (58) 16" x 8" Aluminum vents

ROOFING

Cover: 60 mil TPO Carlisle Sure-Weld - Fully Adhered to 1/2" Securock

NOTES: Termination bar installed on perimeter

Ship loose TPO tape for mod line close up

Drainage: Gutters and downspouts - Provided and installed on site

DOORS

QTY

1 3 PAINT

TEXTURED

2 4 VW OAK

3 27 VW OAK

4 2 VW OAK

DOOR TYPE: HM = 18 ga. Insulated Steel door

GALV = Galvanized

SV = Solid core Vinyl wrap (1-3/4" thick)

JAMB: WELDED = 16 ga. Welded Steel Jamb - Weather-stripping, ADA Threshold and Sweep

TM = Timely Jamb - 47S

HARDWARE: ALL DOOR HARDWARE TO HAVE SATIN CHROME / ALUMINUM TYPE FINISH

Key exterior and Common Room doors alike - Provide 2 keys per lock

Door Pull Plate - 4x16 Trimco 1017-3 32D

Push Plate - 4x16 Trimco 1001-3-630

Kick Plate - SS 10x34 - Trimco K0050

Drip Rail 40" Aluminum - Pemko 346C-40 - On all Exterior Doors

NOTE: PROVIDE WALL BUMPERS FOR INTERIOR DOORS

NRP CYPHER LOCK 180 degree

3'x6'8" SV TM BBH NONE

EXT/INT LOCK CLOSERDOOR

FINISH

SIZE DOOR TYPE JAMB HINGES

LITE OPEN DEG

TM STD HAGER 3510

PASSAGE

HM/GALV WELDED SS-BBH SCHLAGE LCN 1461EXT 3'x6'8"

24"x32"

PUSH/PULL

KICK PLATE

INT 3'x6'8" SV

INT 3'x6'8" SV TM STD SCHLAGE

CYPHER LOCK

LCN 1461

180 degree

INT

SPEC-E5808-144x60 Portland Air National Guard (2026 0811) Page 2 of 6 8/11/2026

Blazer PM

WINDOWS

QTY GLAZING FINISH

1 12 DUAL WHITE ARGON

LOW E VINYL GAS

2 8 DUAL WHITE ARGON

LOW E VINYL GAS

NOTE: GALVANIZED FLASHING INSTALLED UNDER SIDING AND OVER TOP FLANGE OF WINDOWS UNDER TRIM

FLOOR COVER

Restrooms: Tarkett Performa sheet vinyl

Base: 4" rubber

All Else: Provided and installed on site by others

Base: Provided and installed on site by others

WALL COVER

Insulation (Interior): Unfaced fiberglass batt insulation at Restroom walls to ceiling height

Unfaced fiberglass batt insulation at plenum walls to ceiling height

NOTES: R15 (2x4 walls) R21 (2x6 walls) Double R15 (2x8 walls)unfaced fiberglass batt insulation

Insulate one side of double modline walls only

Restrooms: Class C - .090 FRP "Textured" wainscot on all walls to 48" AFF with 5/8" vinyl wrap sheetrock above

NOTE: FRP wainscot installed behind and beside drinking fountain to 48" AFF

All Else: 5/8" Vinyl wrap sheetrock

CEILING

Entire Building: 2'x4' T-bar grid and tile - Armstrong "Cortega" #769A

Ceiling Height: 9'-6" AFF

INTERIOR TRIM

Wainscot: Aluminum inside corners and seam battens with vinyl wrap batts at top

Wall: Vinyl wrap corners and batts at each side of windows and doors

Window: Vinyl wrap Oak surrounds and casing

Door (Exterior): Vinyl wrap Oak surrounds and casing

Door (Interior): Vinyl wrap Oak wood doors with metal "Timely" jambs and casing

Door on dbl modlines: Vinyl wrap sheetrock surrounds with vinyl wrap corners and batts

Modline Joints: Vinyl wrap batts - Provided by Blazer - Installed on site by others

PAINT

Exterior Siding/Trims: Miller "Evolution" Exterior (satin)

Exterior Doors: Miller "Acrimax" (satin)

WASHROOM ACCESSORIES

Toilet Tissue: (4) Double roll Bobrick B-2740

Mirror: (4) 18" wide x 30" high - Framed Glass Bobrick B-165-1830

Grab Bars: (2) 18", (2) 36" and (2) 42" Bobrick B-6806 Series

Toilet Partitions: (4) Metal - Powder Coated - Floor Mounted

Signs - Restroom: (1) Plastic - (1) Men's with Braille Donjo HS-9070-01

(1) Plastic - (1) Women's with Braille Donjo HS-9070-05

SLIDER

3'x4' PRIME SINGLE HUNG

BRAND TYPE

EXT 4'x4' PRIME

9000 SLIDER

EXT

EXT/INT SIZE

W x H

HORIZONTAL

VERTICAL

SPEC-E5808-144x60 Portland Air National Guard (2026 0811) Page 3 of 6 8/11/2026

SPECIALITIES

Signs - Exit: (3) 6" wide x 6" high - Plastic Exit Sign with Braille Donjo HS-9070-35

To Exit: (4) 6" wide x 6" high - Plastic "To Exit" with Braille Donjo

CABINETS

Type: Plastic laminate - Wilsonart

Brand/Style: Cascade Casework

Break Area: 21 LF of base and 19 LF of uppers

Countertop: Wilsonart plastic laminate countertop, backsplash and front edge

NOTE: 24" water heater cabinet has No floor

APPLIANCES

Refrigerator: (1) Rough-in only by Blazer

NOTE: Refrigerator provided and installed on site

HVAC

Comb Heat/AC: (12) Bard wall hung Heat Pumps - 2.5 ton 10 kw with Economizers - 11 EER W30HB-A10xP4xxR

Filter: MERV 8

Plenums: (12) Supply Plenums Model #PWS132

(12) Return Plenums Model #PWR113

Supply Ducting: Round galvanized overhead and insulated flexduct with flexduct isolation sleeves and flow controls at wyes - R4 insulated flexduct

Return Ducting: Overhead - R4 insulated flexduct

Diffuser: 24"x24" T-bar with no dampers

Thermostat: (5) Programmable - Bard #8403-060

Indoor Temp. Sensor: (6) Remote Indoor Temperature Sensor - Bard #8403-062

Outdoor Temp. Sensor: Installed in each HVAC unit from factory

HVAC Relay Box: (2) HVAC Relay Box for (3) Units

(1) HVAC Relay Box for (4) Units

Return Air: Thru return air grills in ceiling ducted back to plenum walls

Outside Air: As required to meet Indoor Ventilation Code

NOTE: Balancing on site

Provide: (10) HVAC Duct Smoke Detector Air Products and Control Inc SL-2000-P

(10) Firex Sampling Tube 2.5'-5' APC STN 5.0

NOTE: Duct smoke detectors installed at return or supply plenums

Exhaust Fan: (3) S110-130-150 CFM - Switched with light in Restroom Fantech 484315

NOTE: Exhaust fans ducted through roof with galvanized 6" hard duct

SPEC-E5808-144x60 Portland Air National Guard (2026 0811) Page 4 of 6 8/11/2026

PLUMBING

Toilet - ADA: (2) ADA Height, Elongated Bowl, Pressure Assist Gerber UF-21-377

Toilet - Standard: (2) Standard Height, Elongated Bowl, Pressure Assist Gerber UL21-372

Urinal - ADA: (1) ADA Height, Siphon Jet, Top Spud Gerber HE27-710

Flush Valve: (1) 1.0/ 1.5/ 0.5/ 0.125/ 0.25 Gallon Flush Cycle, ADA Handle Sloan 186-0.5-XL

Lavatory: (4) 19" x 17" Wall Hung, One Piece Wall Hanger 4" center 3 hole Proflo PF5414WH

Faucet: (4) Ceramic Disc, Hot Limit Stop, ADA Lever Handle A/S 7385.050.002

Sink: (1) 33" x 19" Stainless Steel, Double Compartment Dayton D233193

Faucet: (1) Ceramic Disc, ADA Single Handle, Swing Spout A/S 7074.000.002

Water Heaters: (2) Electric Tankless Water Heater 240V - 7.2kw Stiebel DHC-E 8/10

(1) 6 Gallon, 120 Volts, 1650 Watts, Energy Saver AO Smith EJC-6

NOTES: Tankless Water Heaters mounted on wall in Restrooms below Lavatories

6 gallon Water Heater mounted on floor in Base Cabinet

Floor Drain: (2) PVC Body, Polished Nickel Ring and Grate S8222PNR

Trap Primer: (2) Automatically Activated at Pressure Drops Proflo PFTP2500

Arrestors: (1) Maintenance-Free, Brass Body, Piston Type Sioux Chief 654-CS

Drinking Fountain: (1) Barrier-Free, Split-Level, ADA Pads, Cooled with bottle filler Elkay ELZSTL8WSLP

Ice Maker Outlet Box: (1) 1/4 Turn Valves, 6" x 6" Plastic Body and Faceplate Oatey 39152

Water Lines: Copper and Aquapex - Single Point Water Stub

Sewer Lines: PVC DWV Schedule 40 Plastic

ELECTRICAL

Service: 120/240V Single phase

NOTE: Bond each frame together and to each panel with #6 copper

Panel: (12) 125 amp - Weather Proof - 36" AFF to top of box Square D HOM2448M125PRB

Material: Metallic Raceway System

NOTE: All devices and face plates to be White

Receptacles: (130) Duplex 20 amp Leviton BR20

(2) Dedicated Duplex 20 amp Leviton BR20

(6) Duplex 20 amp GFCI Leviton GFNT2

(2) 20 amp Faceless GFCI - Refrigerator/Drinking Fountain Leviton GFRBF

(6) 20 amp WP GFCI Leviton GFWR2 w/ Intermatic WP 5000C cover

(1) Dedicated 20 amp WP Leviton WBR20 w/ CHE WP TP7199 cover

Mounted under floor, for site installed Heat Tape

Fed from 20 amp Ground Fault Equipment Protection device (GFEPD) HOM120EPD

Switches: (40) nLight Air Wall Switch Lithonia RPODLA

Automatic Controls: (2) Occupancy sensor - Ceiling mount Lithonia NCMPDT9ADCX

Data Box: (65) 4" square boxes with single gang mud ring - Stub up and down with 3/4" flex conduit -

Electrical Continued on next page

SPEC-E5808-144x60 Portland Air National Guard (2026 0811) Page 5 of 6 8/11/2026

Blazer PM

Provide: (2) 20 amp dedicated J-boxes above ceiling for future power drops

Wire For: (12) 2.5 ton 10 kw Heat Pumps with Economizers - 11 EER

(5) Programmable Thermostats

(6) Remote Temperature Sensor

(10) HVAC Duct Smoke Detectors

(2) HVAC Relay Box for (3) Units

(1) HVAC Relay Box for (4) Units

(1) 6 Gallon, 120 Volt, 1650 Watt Water Heater

(2) Electric Tankless Water Heater 240V - 7.2kw

(3) Exhaust fans - Switched with lights in Restrooms

Sign circuit: (1) 20 amp dedicated circuit

Lights: (67) Troffer 2'x4' NLight AIR Enabled - LED - 6000 Lumen - 48 Watts - 4000k

Lithonia 2BLT4 60L ADPT EZ1 LP840 NLTAIR2 RES7 PWS1836

(3) 18.5 Watt LED Wall Pack with integral Photo Cell Lithonia OLWPLEDSWW212OPEDDBM4

(3) dual head with battery back up KEYBL KTEMTP3WHWLSD

(7) Illuminated with dual head emergency lights and battery back up - Red Letters Lithonia LHQM

(7) dual head with battery back up Lithonia ELM2

Exterior Light:

Ext. Emergency Light:

Exit-Emergency Combo:

Int. Emergency Light:

SPRINKLER SYSTEM

PIPE SYSTEM PER NFPA 13 LIGHT HAZARD - WET SYSTEM

CROSSOVER UNIONS SUPPLIED AND INSTALLED ON SITE BY WESTERN STATES

SPRINKLER HEADS ARE WHITE SEMI-RECESSED

RISER PROVIDED - LOCATION TO BE DECIDED

TESTING OF SYSTEM ON SITE BY WESTERN STATES

WORK DOES NOT INCLUDE:

* BACKFLOW, OR FIRE DEPARTMENT CONNECTION

* UNDER FLOOR OR EXTERIOR PIPING

* ELECTRICAL/FIRE ALARM WORK

SYSTEM ASSUMES ADEQUATE WATER SUPPLY AND PIPING/LAYOUT BETWEEN

EXISTING SITE WATER SUPPLY AND BUILDING TO MEET BUILDING SPRINKLER

SYSTEM REQUIREMENTS

OTHER

Building Height: 13'-2" - Add 2'-8" for mobile frame height to get total shipping height

Close-up: Standard close-up plastic

Prevailing wages: Blazer's estimate does not include any allowance for prevailing wage requirements.

SPEC-E5808-144x60 Portland Air National Guard (2026 0811) Page 6 of 6 8/11/2026