Attachment A - Statement of Work.pdf
PDF 578 KB Posted
- Attached to
- J012-- Facilities Maintenance | Fire Door/Extinguisher Inspection/Maint (VA-25-00015129)
- Solicitation number
- 36C24425Q0254
About this file
This Statement of Work details requirements for annual fire and smoke door inspection and maintenance services at two VA Pittsburgh Healthcare System (VAPHS) campus locations: University Drive and H.J. Heinz. The contractor must provide all labor, equipment, supplies, materials and travel to inspect and maintain fire/smoke rated doors in accordance with NFPA 101 and NFPA 80 requirements.
Key requirements include inspecting all doors for compliance with 2024 NFPA standards, identifying doors as either compliant or non-compliant, submitting detailed reports of findings, and performing maintenance/repairs as needed with prior approval. Staff qualifications specify project managers must have 5+ years inspection experience, supervisors 3+ years, and technicians 1+ year. The contractor must verify multiple inspection points including door clearances, glazing, hardware functionality, self-closing operation, and gasket integrity. They must affix identification labels to all doors, maintain documentation, and estimate repairs based on historical 60-75% failure rates. Performance hours are Monday-Friday 8:00 AM – 3:30 PM excluding federal holidays. The contractor must also comply with VA safety policies, TB screening requirements, and annual influenza vaccination documentation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24425Q0254 0002.pdf | ||
| 36C24425Q0254 0001.pdf | ||
| 36C24425Q0254.docx | DOCX document | |
| Attachment D - Wage Determination.pdf | ||
| Attachment C - Price Schedule.pdf | ||
| Attachment B - Past Performance Questionnaire.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA Pittsburgh Health System Fire and Smoke Door Survey Annual Inspection
Statement of Work
1.0 Purpose:
The VA Pittsburgh Healthcare System (VAPHS) has a requirement for all labor, equipment, supplies, materials and travel to provide annual inspection and maintenance services for all fire and smoke rated doors in accordance with National Fire Protection Association (NFPA) 101 and NFPA 80 requirements and submit a report of findings that will satisfy all NFPA and Joint Commission requirements for a health care facility.
2.0 Services shall be provided at two VAPHS campus locations:
2.1 University Dr Campus, University Dr. C, Pittsburgh, PA 15240
2.2 H.J. Heinz, 1010 Delafield Rd., Pittsburgh, PA 15215
2.3 Fire door locations are listed in the University Dr. and H.J. Heinz Fire Door Inventory attachments.
3.0 General Requirements:
3.1 The 2024 edition of the Life Safety Code (NFPA 101) requires facilities to complete annual fire and smoke door inspection and testing. Inspections shall comply with 2024 NFPA 101, 2022 NFPA 80 section 5.2 and 2024 NFPA 105 section 5.2.
3.2 The Contractor shall be certified and experienced in performing such inspections. Project
Managers shall have a minimum of five-plus of inspection experience. Supervisors shall have a minimum of three years of experience. Technicians shall have a minimum of one year of experience.
4.0 Fire Door Inspection Requirements:
4.1 A fire door assembly shall consist of either one, two or three doors and the associated frame, hardware and other components.
4.2 The Contractor shall provide inspection services based on VAPHS provided drawings and other related documents and information. The Contractor agrees to provide inspection services in accordance with the following:
4.3 The Contractor shall locate and inspect all doors in both VAPHS locations and identify doors as either Compliant or Non-Compliant, as determined by the Contractor Inspectors. The guidelines for door compliance will be based on The National Fire Protection Association’s (NFPA) Code “2022 NFPA 80, Standard for Fire Doors and Other Opening Protectives” (the “NPFA Code”) Section 5.2.4.2 that states: “i. 5.2.4.2 As a minimum the following items shall be verified.”
4.4 No open holes or breaks exist in surfaces of either the door or the door frame.
4.5 Glazing, vision light frames, and glazing beads are intact and securely fastened in place, if equipped.
4.6 The door, frame, hinges, hardware, and noncombustible thresholds are secured, aligned and in working order with no visible signs of damage.
4.7 No parts are missing or broken.
4.8 Door clearances at the door edge to the frame, on the pull side of the door, do not exceed clearances listed in 4.8.4 and 6.3.1:
4.8.1 Minimum permitted undercut ¾” (4.8.4)
4.8.2 Clearances (6.3.1):
4.8.2.1 For steel doors, clearances between the door and the frame shall be 1/8” +/- 1/16” and clearances at the meeting edges of pairs of doors shall be 1/8” +/-.
4.8.2.2 For wood doors, clearances between the door and the frame shall not exceed 1/8” and clearances at the meeting doors edges of pairs of doors shall not exceed 1/8”.
4.9 The self-closing device is operational, meaning the active door completely closes when operated from the fully open position.
4.10 If a coordinator is installed, the inactive leaf closes before the active leaf.
4.11 Latching hardware operates and secures the door when it is in the closed position.
4.12 Auxiliary hardware items that interfere or prohibit operation are not installed on the door or frame.
4.13 No field modifications to the door assembly have been performed that void the label.
4.14 Gasketing and edge seals, where required, are inspected to verify their presence and integrity.
5.0 The Contractor shall utilize the multi-point inspection checklist comprised of the components of the fire rated assembly to inspect the door that is located at the end of this document. The components that will be inspected include:
5.1 Frame, (2) Door, (3) Hinges/Pivots, (4) Door Bolts, (5) Locks, (6) Door Closers, (7) Fire Exit Hardware, (8) Door Operational Testing, and (9) Miscellaneous Items.
6.0 The Contractor shall survey VAPHS locations to determine if the doors are installed in fire rated walls and partitions. Doors installed in non-rated walls and partitions will be noted on the drawings provided to the Contractor and be included in the Contractor’s findings report.
7.0 The Contractor shall list the location of all doors on VAPHS provided drawings.
8.0 The Contractor shall affix an identification label or sticker to all doors and note the location of each label on VAPHS provided drawings.
9.0 Fire Door Maintenance Requirements:
9.1 The Contractor shall list all deficiencies identified during the inspection service and provide the list to the Point of Contact (POC) with a quote for the cost to complete the repairs.
9.2 Repairs shall be covered by separate CLINs designated for maintenance. The Contractor shall NOT make repairs to any doors without POC approval.
9.3 Maintenance cost estimates are based on a 75% failure rate. A previous contract for these services in 2020 revealed a 60% failure rate.
10.0 Reports:
10.1 The Contractor shall provide a summary of findings report to VAPHS within 10 business days of completing the inspection which includes:
10.1.1 Location of all fire doors by door number, handle type and fire rating.
10.1.2 List of all compliant doors.
10.1.3 List of all non-complaint doors
10.1.4 Number of doors by building number and floor number.
10.1.5 Type of rated door by building number and floor number.
10.1.6 Number of compliant doors by building number and floor number.
10.1.7 Number of non-compliant doors by building number and floor number.
10.1.8 The percentage of non-compliant doors.
10.1.9 A list of findings and deficiencies for all doors that were found to be non-complaint, to include digital photographs.
11.0 Performance Hours - Monday through Friday; 8:00 AM – 3:30 PM; except for Federal holidays.
12.0 Safety
12.1 The Contractor shall adhere to all OSHA, EPA, NFPA Life Safety Codes, and any other regulatory requirements.
12.2 The Contractor shall follow VAPHS safety policies and standards for safe work practices and take such safety precautions as the POC, VAPHS Safety Officer or designee may determine to be reasonably necessary to protect the health of occupants.
12.3 The Contractor shall ensure that their work areas are clean and free from debris. Any work areas the POC deems unclean shall be cleaned again.
12.4 VAPHS is a smoke free, vape free facility. This includes outside areas and parking garages.
12.5 The Contractor shall be responsible for the safety and health of their employees.
12.6 The Contractor shall submit to the VAPHS POC, prior to providing services, any Material
Safety Data Sheets (MSDS) for all potentially hazardous lubricants, cleaners, fluids, etc., that may be used in the performance of the contract, and will not use materials which have not been cleared for use in advance with the POC. MSDS for new chemicals shall be furnished when brought on site. The Contractor shall maintain a copy of all MSDS at the chemical storage site in a location accessible to VAPHS personnel to ensure compliance with all laws and requirements regarding the “Right to Know” law.
12.7 The Contractor shall provide its employees with all required personal protective equipment needed to perform services in accordance with the SOW.
12.8 The Contractor shall adhere to applicable safety requirement standards including lock out/tag out, confined space entry and universal precautions. Training on these standards and proper use of PPE shall be the responsibility of the Contractor.
12.9 The Contractor shall be notified of any non-compliance with safety policies and shall correct the condition and notify the contracting officer in writing that the condition has been corrected. If VAPHS determines the corrective action was insufficient the Contractor shall be ordered to stop to stop work until the condition has been corrected. If the Contractor fails or refuses to comply promptly, the Contracting Officer (CO) shall be notified, and adverse action may be taken against the Contractor.
12.10 The Contractor shall submit in writing to the POC details of any injury or accident occurring during performance of the contract within five business days.
13.0 Security and Privacy Requirements
13.1 The POC is responsible for ensuring that all Contractors comply with physical security policies. The POC will ensure Contractor gets required security badge. A compliant ID badge must be worn by Contractors at all times while on VA premises.
13.2 The Contractor may not have access to the VA network or any VA sensitive information under this contract.
13.3 All Contractors must receive Privacy training annually using one of the following methods:
13.3.1 Complete “VA Privacy Training for Personnel without Access to VA Computer Systems or Direct Access to or Use to VA Sensitive Information” training by using VA’s TMS system (https://www.tms.va.gov/). Contractors may use the TMS Managed Self Enrollment method to complete the training in Talent Management System (TMS).
13.3.2 Complete the hard copy version of “VA Privacy Training for Personnel without Access to
VA Computer Systems or Direct Access to or Use to VA Sensitive Information”. Signed training documents must be submitted to the POC.
14.0 VHA Healthcare Directives:
14.1 Tuberculosis - Review of all contract worker Tuberculosis (TB) screening requirements and options (reference VHA Directive 2011-036 Safety and Health during Construction). Contractor is required to annual certify all Contractors working on VAPHS have documented screening for latent Tuberculosis within the last 12 months and every 12 months thereafter while working at VAPHS. If screening for latent Tuberculosis is positive, clearance from a physician is required prior to working at VAPHS. The Contractor shall also be notified that anyone failing to meet these requirements is not permitted to work onsite and/or may be removed at any time without notice until these requirements are met.
Provide evidence to respective POC.
14.2 For Influenza - Per VHA Directive 1192, all Contractors working at VAPHS are required to show documentation of annual seasonal Influenza vaccination. Provide evidence to the
POC.
VA Pittsburgh Healthcare System - Annual Checklist for Inspection and Testing of Smoke and Fire Door Assemblies
Facility Tester Name
Date Door Type: Fire Smoke Rating
Location (Building Number / Floor Number / Room Number) ______________________________________
The 2024 edition of the Life Safety Code (NFPA 101) requires facilities to complete annual fire and smoke door inspection and testing.
The latest active revision/edition (2024 edition) of the Life Safety Code (NFPA 101) requires facilities to complete annual fire and smoke door inspection and testing. Per NFPA 101, fire rated door assemblies are to be installed, inspected, modified, tested and maintained in accordance with NFPA 80 2022 edition (Standard for Fire Doors and Other Opening Protectives). Per NFPA 101, smoke rated door assemblies are to be installed, inspected and maintained in accordance with NFPA 105 (Standard for Smoke Door Assemblies and Other Opening Protectives). Inspect and test all rated fire door assemblies for items listed below and identify issues or concerns.
Use one form for each door and keep documentation for the life of the assembly.
Operation Swings freely Closes properly* Latches properly* Door Pressure Measurement
(if door is non-latching by allowable exception) Other
* In health care occupancies:
• SNF/NF resident rooms do not require closers.
• Smoke barrier doors do not require latches.
Frame
Label present and legible Is secure No open holes/breaks Frame not rusted through Gaskets intact Other
Door
Label present and legible Correct Clearance (<3/4” bottom, <1/8” other) No open holes/ breaks Glazing/vision light frames intact Door Kickplate Installed – Appropriately Sized Not Damaged / delaminated door Door not rusted-through No non-compliant field modification No visible signs of damage
Door Closer
All hardware installed Strike in good shape Securely installed Other
Hinges Correct Securely installed
Flush Bolts Correct
Lockset / Hardware
Strike in good shape Securely installed Coordinator working properly
Fire Exit Hardware
Strike in good shape
No items that interfere installed No non-compliant field modification Door has appropriate signage Any signage is properly affixed
Comments/Corrections
Tester Signature
Attachment 1 - VA Pittsburgh Healthcare System – October 2020
Site Bldg Flr Door Designation or Room Number Description Type HZ 50 1 50‐COR C1‐10‐FD Cooridor door 2hr Fire door HZ 50 1 50‐SW4‐FD Cafeteria Stairwell door 2hr Fire door HZ 50 1 50‐1A135 Trash Room 1hr Fire door HZ 50 1 50‐1A134 Soiled utility 1hr Fire door HZ 50 1 50‐SW5‐FD Main corridor Stairwell door 2hr Fire door HZ 50 1 50‐1A139 Oxygen storage 1hr Fire door HZ 50 1 50‐1A162 near entrance Soiled utility 1hr Fire door HZ 50 1 50‐COR C1‐12‐SBD (1 North) A Cooridor door Smoke Barrier door HZ 50 1 50‐COR C1‐15‐SBD (1 North) E Cooridor door Smoke Barrier door HZ 50 1 50‐1A154‐SBD Shower Room Smoke Barrier door HZ 50 1 50‐SW6‐FD E corridor Stairwell door 2hr Fire door HZ 50 1 50‐SW7‐FD F corridor Stairwell door 2hr Fire door HZ 50 1 50‐COR C1‐17‐SBD (1 North) G Cooridor door Smoke Barrier door HZ 50 1 50‐SW8‐FD G corridor Stairwell door 2hr Fire door HZ 50 1 50‐1A102 Ceramics Kiln Room 1hr Fire door HZ 50 1 50‐1A102A Ceramic kiln Kiln Room 1hr Fire door HZ 50 1 50‐COR C1‐3‐SBD (1 South) A Cooridor door Smoke Barrier door HZ 50 1 50‐SW2‐FD Corridor C Stairwell door 2hr Fire door HZ 50 1 50‐COR C1‐9‐SBD (1 South) D Cooridor door Smoke Barrier door HZ 50 1 50‐SW3‐FD Corridor D Stairwell door 2hr Fire door HZ 50 1 50‐1A116 Soiled utility 1hr Fire door HZ 50 1 50‐COR C1‐7‐SBD (1 South) B Cooridor door Smoke Barrier door HZ 50 1 50‐SW1‐FD Corridor B Stairwell door 2hr Fire door HZ 50 G 50‐COR CG‐11‐FD Cooridor door 2hr Fire door HZ 50 G 50‐GA140 Electric Gear Room 1hr Fire door HZ 50 G 50‐GA141 Trash Holding 1hr Fire door HZ 50 G 50‐GA142 1hr Fire door HZ 50 G 50‐GA144 Soiled utility 1hr Fire door HZ 50 G 50‐GA139‐FD Generator Room 2hr Fire door HZ 50 G 50‐SW4‐FD Stairwell door 2hr Fire door HZ 50 G 50‐GA136 Soiled utility 1hr Fire door HZ 50 G 50‐GA137 Trash Room 1hr Fire door HZ 50 G 50‐SW5‐FD Main corridor Stairwell door 2hr Fire door HZ 50 G 50‐GA145 Oxygen storage 1hr Fire door HZ 50 G 50‐GA147 EMS Storage 1hr Fire door HZ 50 G 50‐GA169 Elevator Room 1hr Fire door HZ 50 G 50‐COR CG‐14‐SBD (GN by GA168) Cooridor door Smoke Barrier door HZ 50 G 50‐GA151 SPD Storage 1hr Fire door HZ 50 G 50‐COR CG‐17‐SBD (GN by GA152) Cooridor door Smoke Barrier door HZ 50 G 50‐SW6‐FD E corridor Stairwell door 2hr Fire door HZ 50 G 50‐SW7‐FD F corridor Stairwell door 2hr Fire door HZ 50 G 50‐COR CG‐19‐SBD (GN by GA161) G Corridor Cooridor door Smoke Barrier door HZ 50 G 50‐GA160 (x2) Storage Room 1hr Fire door HZ 50 G 50‐SW8‐FD G corridor Stairwell door 2hr Fire door HZ 50 G 50‐SW8A‐FD Mechanical Rooom 1hr Fire door HZ 50 G 50‐SW4‐FD Cafeteria Stairwell door 2hr Fire door HZ 50 G 50‐COR CG‐4‐SBD (GS by GA109) Main Cooridor door Smoke Barrier door HZ 50 G 50‐COR CG‐9‐SBD (GS by GA126) D Corridor Cooridor door Smoke Barrier door HZ 50 G 50‐SW3‐FD Corridor D Stairwell door 2hr Fire door HZ 50 G 50‐SW2‐FD Corridor C Stairwell door 2hr Fire door HZ 50 G 50‐GA118 Storage Room 1hr Fire door HZ 50 G 50‐GA126 Soiled utility 1hr Fire door HZ 50 G 50‐COR CG‐7‐SBD (GS by GA117) B Corridor Cooridor door Smoke Barrier door HZ 50 G 50‐SW1‐FD Corridor B Stairwell door 2hr Fire door
2019 H.Z. Bldg 50 Fire Door & Smoke Door Inventory
Site Bldg Flr Door Designation or Room Number Description Type HZ 51 Roof 51‐SW1‐FD Stairwell door 2hr Fire door HZ 51 Roof 51‐SW2‐FD To Elevator rm 2hr Fire door HZ 51 PH Roof 51‐SW18 Elevator Room 1hr Fire door HZ 51 Roof 51‐SW3‐FD Stairwell door 2hr Fire door HZ 51 Elevator 51‐ECRI‐FD Elevator Room 2hr Fire door HZ 51 3+ 51‐INT‐SW1‐FD Stairwell door 2hr Fire door HZ 51 3+ 51‐INT‐MR‐FD Mech Half Door 1hr Fire door HZ 51 3+ 51‐INT‐MR‐FD Mech Half Door 1hr Fire door HZ 51 3+ 51‐INT‐SW2‐FD Stairwell door 2hr Fire door HZ 51 3+ 51‐INT‐MR‐FD Mech Half Door 1hr Fire door HZ 51 3+ 51‐INT‐MR‐FD Mech Half Door 1hr Fire door HZ 51 3+ 51‐INT3‐SW3‐FD Stairwell door 2hr Fire door HZ 51 3 51‐COR C3‐9‐SBD (3A147) Cooridor door Smoke Barrier door HZ 51 3 51‐3A131 Mechanical Room 1hr Fire door HZ 51 3 51‐SW1‐FD Stairwell door 2hr Fire door HZ 51 3 51‐3A114 Trash Room 1hr Fire door HZ 51 3 51‐3A112 Soiled utility 1hr Fire door HZ 51 3 51‐COR C3‐3‐SBD (3A108) Cooridor door Smoke Barrier door HZ 51 3 51‐COR C3‐13 (3B153) Cooridor door 1hr Fire door HZ 51 3 asdfsdf Mechanical Room 1hr Fire door HZ 51 3 51‐SW3‐FD Stairwell door 2hr Fire door HZ 51 3 51‐3B190 Soiled utility 1hr Fire door HZ 51 3 51‐COR C3‐19 (3B194) Cooridor door 1hr Fire door HZ 51 3 51‐SW2‐FD Stairwell door 2hr Fire door HZ 51 2+ 51‐INT‐SW1‐FD Stairwell door 2hr Fire door HZ 51 2+ 51‐INT‐MR‐FD Mech Half Door 1hr Fire door HZ 51 2+ 51‐INT‐MR‐FD Mech Half Door 1hr Fire door HZ 51 2+ 51‐INT‐SW2‐FD Stairwell door 2hr Fire door HZ 51 2+ 51‐INT‐MR‐FD Mech Half Door 1hr Fire door HZ 51 2+ 51‐INT‐MR‐FD Mech Half Door 1hr Fire door HZ 51 2+ 51‐INT3‐SW3‐FD Stairwell door 2hr Fire door HZ 51 2 51‐COR C2‐9‐SBD (2A147) Cooridor door Smoke Barrier door HZ 51 2 51‐2A131 Mechanical Room 1hr Fire door HZ 51 2 51‐SW1‐FD Stairwell door 2hr Fire door HZ 51 2 51‐2A114 Trash Room 1hr Fire door HZ 51 2 51‐2A112 Soiled utility 1hr Fire door HZ 51 2 51‐COR C2‐3‐SBD Cooridor door Smoke Barrier door HZ 51 2 51‐COR C2‐13‐SBD Cooridor door Smoke Barrier door HZ 51 2 51‐2B168 Mechanical Room 1hr Fire door HZ 51 2 51‐SW3‐FD Stairwell door 2hr Fire door HZ 51 2 51‐2B184 Trash Room 1hr Fire door HZ 51 2 51‐2B186 Soiled utility 1hr Fire door HZ 51 2 51‐COR C2‐19‐SBD Cooridor door Smoke Barrier door HZ 51 2 51‐SW2‐FD Stairwell door 2hr Fire door HZ 51 1+ 51‐INT‐SW1‐FD Stairwell door 2hr Fire door HZ 51 1+ 51‐INT‐MR‐FD Mech Half Door 1hr Fire door HZ 51 1+ 51‐INT‐MR‐FD Mech Half Door 1hr Fire door HZ 51 1+ 51‐INT‐SW2‐FD Stairwell door 2hr Fire door HZ 51 1+ 51‐INT‐MR‐FD Mech Half Door 1hr Fire door HZ 51 1+ 51‐INT‐MR‐FD Mech Half Door 1hr Fire door HZ 51 1+ 51‐INT3‐SW3‐FD Stairwell door 2hr Fire door HZ 51 1 51‐1A131‐SBD Chaple Smoke Barrier door HZ 51 1 51‐COR C1‐11‐SBD Cooridor door Smoke Barrier door HZ 51 1 51‐1A127 Mechanical Room 1hr Fire door HZ 51 1 51‐1A126 Cooridor door Smoke Barrier door HZ 51 1 51‐COR C1‐9‐SBD Cooridor door Smoke Barrier door HZ 51 1 51‐1A122 Mechanical Room 1hr Fire door HZ 51 1 51‐SW1‐FD Stairwell door 2hr Fire door HZ 51 1 51‐COR C1‐7‐SBD Cooridor door Smoke Barrier door HZ 51 1 51‐1A139 (single door) Retail Store 1hr Fire door HZ 51 1 51‐1A139 (double door) Retail Store 1hr Fire door HZ 51 1 51‐1B142B Retail Sec Storage 1hr Fire door HZ 51 1 51‐COR C1‐15‐SBD Cooridor door Smoke Barrier door HZ 51 1 51‐1B141 Retail Storage 1hr Fire door HZ 51 1 51‐1B144G Kitchen Storage 1hr Fire door HZ 51 1 51‐1B1445 (2 sets) Mechanical Room 1hr Fire door HZ 51 1 51‐SW3‐FD Stairwell door 2hr Fire door HZ 51 1 51‐1B161 Electrical Room 1hr Fire door HZ 51 1 51‐1B154‐SBD Cooridor door Smoke Barrier door
2019 H.Z. Bldg 51 Fire Door & Smoke Door Inventory
HZ 51 1 51‐1B157 Soiled utility 1hr Fire door HZ 51 1 51‐1B156 Trash Room 1hr Fire door HZ 51 1 51‐COR C1‐21‐SBD Cooridor door Smoke Barrier door HZ 51 1 51‐SW2‐FD Stairwell door 2hr Fire door HZ 51 G+ 51‐INT‐SW1‐FD Stairwell door 2hr Fire door HZ 51 G+ 51‐INT‐MR‐FD Mech Half Door 1hr Fire door HZ 51 G+ 51‐INT‐MR‐FD Mech Half Door 1hr Fire door HZ 51 G+ 51‐INT‐SW2‐FD Stairwell door 2hr Fire door HZ 51 G+ 51‐INT‐MR‐FD Mech Half Door 1hr Fire door HZ 51 G+ 51‐INT‐MR‐FD Mech Half Door 1hr Fire door HZ 51 G+ 51‐INT3‐SW3‐FD Stairwell door 2hr Fire door HZ 51 G 51‐COR CG‐8‐SBD Cooridor door Smoke Barrier door HZ 51 G 51‐GA122E Inpatient Pharmacy 1hr Fire door HZ 51 G 51‐GA122K Inpatient Pharmacy 1hr Fire door HZ 51 G 51‐GA115 Mechanical Room 1hr Fire door HZ 51 G 51‐GA110 Oxygen storage 1hr Fire door HZ 51 G 51‐SW1‐FD Stairwell door 2hr Fire door HZ 51 G 51‐GA108T Soiled utility 1hr Fire door HZ 51 G 51‐GA105 Trash Room 1hr Fire door HZ 51 G 51‐GA104 Soiled utility 1hr Fire door HZ 51 G 51‐COR CG‐3‐SBD Cooridor door Smoke Barrier door HZ 51 G 51‐GA102 Office Door Smoke Barrier door HZ 51 G 51‐GA102A Data Closet Smoke Barrier door
HZ 51 G 51‐GB131‐SBD Kitchen Entrance Smoke Barrier door
HZ 51 G 51‐Elev Lobby CG‐12‐SBD Cooridor door Smoke Barrier door HZ 51 G 51‐Elev Lobby to Crawl space Door to Crawl space 1hr Fire door HZ 51 G 51‐GB127‐SBD Kitchen Entrance Smoke Barrier door HZ 51 G 51‐GB127A Electrical Room 1hr Fire door
HZ 51 G 51‐COR CG‐13‐SBD Cooridor door Smoke Barrier door HZ 51 G 51‐SW2‐FD Stairwell door 2hr Fire door HZ 51 G 51‐GB142 Soiled utility 1hr Fire door HZ 51 G 51‐GB141 Trash Room 1hr Fire door HZ 51 G 51‐GB140‐1 Mechanical Room 1hr Fire door
HZ 51 G 51‐GB140‐2 Mechanical Room 1hr Fire door
HZ 51 G 51‐GB139 (rear of room) Linen Room 2hr Fire door HZ 51 G 51‐SW3‐FD Stairwell door 2hr Fire door HZ 51 G 51‐SW3‐FD to Crawl Space Crawl space access 1hr Fire door HZ 51 G 51‐GB134 Elevator Room 1hr Fire door HZ 51 G 51‐GB135 Mechanical Room 1hr Fire door
HZ 51 G 51‐COR CG15‐FD Cooridor door 2hr Fire door
Site Bldg Flr Door Designation or
Room Number Description Type UD 1 Roof 1‐RT‐Elev 14/15‐FD Elevator Equip PH 2hr Fire door UD 1 12 1‐12‐12C100‐FD Elevator Equip PH 2hr Fire door UD 1 12 1‐12‐CrawlSp‐FD Crawl Space door 2hr Fire door UD 1 12 1‐12N‐SW1‐FD Stairwell door 2hr Fire door UD 1 11 1‐11W‐SW2‐FD Stairwell door 2hr Fire door UD 1 11 1‐11N‐Elev 14/15‐SB Elevator Lobby Smoke Barrier door UD 1 11 1‐11N‐SW1‐FD Stairwell door 2hr Fire door UD 1 11 1‐11N‐107‐FD Mechanical Chase 2hr Fire door UD 1 11 1‐11E‐104‐FD Mechanical Chase 2hr Fire door UD 1 11 1‐11E‐11C1‐SHAFT‐FD Mechanical Shaft 2hr Fire door UD 1 11 1‐11E‐SW3‐FD Stairwell door 2hr Fire door UD 1 10 1‐10W‐SW2‐FD Stairwell door 2hr Fire door UD 1 10 1‐10W‐134‐HAZ Storage Room High Hazard door UD 1 10 1‐10W‐111‐FD Soiled Utility 1hr Fire door UD 1 10 1‐10W‐107‐HAZ Storage Room High Hazard door UD 1 10 1‐10W‐106‐HAZ Storage Room High Hazard door UD 1 10 1‐10N‐Elev 14/15‐SB Elevator Lobby Smoke Barrier UD 1 10 1‐10N‐SW1‐FD Stairwell door 2hr Fire door UD 1 10 1‐10N‐108‐FD Mechanical Chase 2hr Fire door UD 1 10 1‐10E‐C10C1‐SHAFT‐FD Mechanical Shaft 2hr Fire door UD 1 10 1‐10E‐104‐HAZ Housekeeping Storage High Hazard door UD 1 10 1‐10E‐SW3‐FD Stairwell door 2hr Fire door UD 1 9 1‐9W‐SW2‐FD Stairwell door 2hr Fire door UD 1 9 1‐9W‐125A‐HAZ Clean Linen Storage High Hazard door UD 1 9 1‐9W‐140‐FD Soiled Utility 1hr Fire door UD 1 9 1‐9W‐COR C9W1‐SB Corridor door Smoke Barrier UD 1 9 1‐9N‐Elev 14/15‐SB Elevator Lobby Smoke Barrier UD 1 9 1‐9N‐SW1‐FD Stairwell door 2hr Fire door UD 1 9 1‐9N‐108‐FD Mechanical Chase 2hr Fire door UD 1 9 1‐9E‐C9C1‐SHAFT‐FD Mechanical Shaft 2hr Fire door UD 1 9 1‐9E‐COR 9CE1‐SB Corridor door Smoke Barrier UD 1 9 1‐9E‐103‐HAZ Mechanical Room High Hazard door UD 1 9 1‐9E‐SW3‐FD Stairwell door 2hr Fire door UD 1 8 1‐8W‐SW2‐FD Stairwell door 2hr Fire door UD 1 8 1‐8W‐109‐HAZ Clean Linen Storage High Hazard door UD 1 8 1‐8W‐108‐FD Soiled Utility 1hr Fire door UD 1 8 1‐8W‐COR C8W1‐SB Corridor door Smoke Barrier UD 1 8 1‐8W‐124‐SB Office Door Smoke Barrier UD 1 8 1‐8W‐103‐SB Restroom Door Smoke Barrier UD 1 8 1‐8N‐Elev 14/15‐SB Elevator Lobby Smoke Barrier
2019 U.D. Bldg 1 Life Safety Door Inventory
UD 1 8 1‐8N‐SW1‐FD Stairwell door 2hr Fire door
UD 1 8 1‐8N‐105‐FD Oxygen storage 1hr Fire door UD 1 8 1‐8N‐108‐FD Mechanical Chase 2hr Fire door UD 1 8 1‐8E‐C8C1‐SHAFT‐FD Mechanical Shaft 2hr Fire door UD 1 8 1‐8E‐COR 8CE1‐SB Corridor door Smoke Barrier UD 1 8 1‐8E‐102‐HAZ Chute Room High Hazard door UD 1 8 1‐8E‐104‐FD Soiled Utility 1hr Fire door UD 1 8 1‐8E‐SW3‐FD Stairwell door 2hr Fire door UD 1 7 1‐7W‐SW2‐FD Stairwell door 2hr Fire door UD 1 7 1‐7W‐139B Elevator Equip 2hr Fire door UD 1 7 1‐7W‐139C‐FD Electric Room 1hr Fire door UD 1 7 1‐7W‐104‐HAZ Storage Room High Hazard door UD 1 7 1‐7W‐COR C7W1‐SB Corridor door Smoke Barrier UD 1 7 1‐7N‐Elev 14/15‐SB Elevator Lobby Smoke Barrier UD 1 7 1‐7N‐SW1‐FD Stairwell door 2hr Fire door UD 1 7 1‐7N‐102‐HAZ Student Lab High Hazard door UD 1 7 1‐7N‐108‐FD Mechanical Chase 2hr Fire door UD 1 7 1‐7E‐C7C1‐SHAFT‐FD Mechanical Shaft 2hr Fire door UD 1 7 1‐7E‐COR C7E1‐SB Corridor door Smoke Barrier UD 1 7 1‐7E‐102‐HAZ Chute Room High Hazard door UD 1 7 1‐7E‐132‐FD Storage Room 1hr Fire door UD 1 7 1‐7E‐129‐SUITE Treatment Room Suite Boundary UD 1 7 1‐7E‐125‐FD Soiled Utility 1hr Fire door UD 1 7 1‐7E‐SW3‐FD Stairwell door 2hr Fire door UD 1 6 1‐6W‐SW2‐FD Stairwell door 2hr Fire door UD 1 6 1‐6W‐COR C6W2(a)‐SB Corridor door Smoke Barrier UD 1 6 1‐6W‐153‐HAZ Storage Room High Hazard door UD 1 6 1‐6W‐150‐FD Soiled Utility 1hr Fire door UD 1 6 1‐6W‐143‐HAZ Clean Utility High Hazard door UD 1 6 1‐6W‐SW2A‐FD Stairwell door 2hr Fire door UD 1 6 1‐6W‐142‐HAZ Linen Room High Hazard door UD 1 6 1‐6W‐COR C6W2(b)‐SB Corridor door Smoke Barrier UD 1 6 1‐6W‐104‐FD Storage Room 1hr Fire door UD 1 6 1‐6W‐COR C6W1‐SB Corridor door Smoke Barrier UD 1 6 1‐6N‐Elev 14/15‐SB Elevator Lobby Smoke Barrier UD 1 6 1‐6N‐SW1‐FD Stairwell door 2hr Fire door UD 1 6 1‐6N‐108‐FD Mechanical Chase 2hr Fire door UD 1 6 1‐6E‐104‐FD Soiled Utility 1hr Fire door UD 1 6 1‐6E‐COR C6E1‐SB Corridor door Smoke Barrier UD 1 6 1‐6E‐109‐HAZ Clean Room High Hazard door UD 1 6 1‐6W‐110‐HAZ Decon Room High Hazard door UD 1 6 1‐6E‐SW3‐FD Stairwell door 2hr Fire door UD 1 5 1‐5A‐SW9A‐FD Stairwell door 1hr Fire door UD 1 5 1‐5A‐111‐FD Storage Room 1hr Fire door UD 1 5 1‐5A‐115(a)‐FD Soiled Utility 1hr Fire door UD 1 5 1‐5A‐115(b)‐FD Soiled Utility 1hr Fire door
UD 1 5 1‐5A‐116‐FD Clean Utility 1hr Fire door UD 1 5 1‐5A‐COR C5A02‐FD Corridor door 1hr Fire door
UD 1 5 1‐5W‐SW2‐FD Stairwell door 2hr Fire door UD 1 5 1‐5W‐COR C5W2(a)‐SB Corridor door Smoke Barrier UD 1 5 1‐5W‐153‐HAZ Storage Room High Hazard door UD 1 5 1‐5W‐150‐FD Soiled Utility 1hr Fire door UD 1 5 1‐5W‐143‐HAZ Clean Utility High Hazard door UD 1 5 1‐5W‐SW2A‐FD Stairwell door 2hr Fire door UD 1 5 1‐5W‐142‐HAZ Linen Room High Hazard door UD 1 5 1‐5W‐COR C5W2(b)‐SB Corridor door Smoke Barrier UD 1 5 1‐5W‐104‐FD Storage Room 1hr Fire door UD 1 5 1‐5W‐COR C5W1‐SB Corridor door Smoke Barrier UD 1 5 1‐5N‐101A‐FD Storage Room 1hr Fire door UD 1 5 1‐5N‐SW1‐FD Stairwell door 2hr Fire door UD 1 5 1‐5N‐108‐FD Mechanical Chase 2hr Fire door UD 1 5 1‐5E‐113‐FD Soiled Utility 1hr Fire door UD 1 5 1‐5E‐COR C5E1‐SB Corridor door Smoke Barrier UD 1 5 1‐5E‐148‐HAZ Linen Room High Hazard door UD 1 5 1‐5E‐SW3‐FD Stairwell door 2hr Fire door UD 1 4 1‐4A‐SW9A‐FD Stairwell door 1hr Fire door UD 1 4 1‐4A‐INTER‐FD Mechanical Room 2hr Fire door UD 1 4 1‐4A‐SW9‐FD Stairwell door 2hr Fire door UD 1 4 1‐4W‐SW2‐FD Stairwell door 2hr Fire door UD 1 4 1‐4W‐COR C4W3‐SB Corridor door Smoke Barrier UD 1 4 1‐4W‐153‐HAZ Storage Room High Hazard door UD 1 4 1‐4W‐150‐FD Soiled Utility 1hr Fire door UD 1 4 1‐4W‐143‐HAZ Clean Utility High Hazard door UD 1 4 1‐4W‐SW2A‐FD Stairwell door 2hr Fire door UD 1 4 1‐4W‐142‐HAZ Linen Room High Hazard door UD 1 4 1‐4W‐COR C4W2‐SB Corridor door Smoke Barrier UD 1 4 1‐4W‐COR C4W1‐SB Corridor door Smoke Barrier UD 1 4 1‐4N‐COR C4C4(a)‐SB Corridor door Smoke Barrier UD 1 4 1‐4N‐122‐SB Lounge door Smoke Barrier UD 1 4 1‐4N‐COR C4N1‐SUITE Treatment Room Suite Boundary UD 1 4 1‐4N‐119‐FD Soiled Utility 1hr Fire door UD 1 4 1‐4N‐118‐FD Clean Utility 1hr Fire door UD 1 4 1‐4N‐111‐HAZ Storage Room High Hazard door UD 1 4 1‐4N‐SW6‐FD Stairwell door 2hr Fire door UD 1 4 1‐4N‐Elev 14/15‐SB Elevator Lobby Smoke Barrier UD 1 4 1‐4N‐SW1‐FD Stairwell door 2hr Fire door UD 1 4 1‐4N‐108‐FD Mechanical Chase 2hr Fire door UD 1 4 1‐4N‐COR C4C4(b)‐SB Corridor door Smoke Barrier door UD 1 4 1‐4N‐138‐FD Soiled Utility 1hr Fire door UD 1 4 1‐4N‐140‐HAZ Clean Utility High Hazard door UD 1 4 1‐4N‐SW7‐FD Stairwell door 2hr Fire door UD 1 4 1‐4E‐COR C4E1‐SBD Corridor door Smoke Barrier door
Wayfinding changed room # to 128
UD 1 4 1‐4E‐100‐FD Soiled Utility 1hr Fire door UD 1 4 1‐4E‐101‐HAZ Linen Room High Hazard door UD 1 4 1‐4E‐123‐FD Supply Storage 1hr Fire door UD 1 4 1‐4E‐SW3‐FD Stairwell door 2hr Fire door UD 1 3 1‐3A‐SW9‐FD Stairwell door 2hr Fire door UD 1 3 1‐3A‐COR C3A24‐SB Corridor door Smoke Barrier door UD 1 3 1‐3A‐COR C3A23‐SB Corridor door Smoke Barrier door UD 1 3 1‐3A‐166‐SB Housekeeping Closet Smoke Barrier door UD 1 3 1‐3A‐201(a)‐FD GIP Storage Room 1hr Fire door UD 1 3 1‐3A‐COR C3A14‐SB Corridor door Smoke Barrier door UD 1 3 1‐3A‐COR C3A21‐SUITE Corridor door Suite Boundary UD 1 3 1‐3A‐153‐FD Soiled Utility 1hr Fire door UD 1 3 1‐3A‐COR C3A20‐SUITE Corridor door Suite Boundary UD 1 3 1‐3A‐COR C3A19‐SUITE Corridor door Suite Boundary UD 1 3 1‐3A‐COR C3A6‐SB Corridor door Smoke Barrier door UD 1 3 1‐3A‐COR C3A10‐SUITE Corridor door Suite Boundary UD 1 3 1‐3A‐133‐FD Soiled Utility 1hr Fire door UD 1 3 1‐3A‐COR C3A15‐SUITE Corridor door Suite Boundary UD 1 3 1‐3A‐116‐SUITE Ante‐Room Suite Boundary UD 1 3 1‐3W‐COR C3W2‐SB Corridor door Smoke Barrier door UD 1 3 1‐3W‐SW2‐FD Stairwell door 2hr Fire door UD 1 3 1‐3A‐170‐FD Gas Storage Room 1hr Fire door UD 1 3 1‐3A‐171‐FD Gas Storage Room 1hr Fire door UD 1 3 1‐3A‐176a‐FD Soiled Utility 1hr Fire door UD 1 3 1‐3A‐213‐SB Equip. Room Smoke Barrier door UD 1 3 1‐3A‐214‐SB Closet Smoke Barrier door UD 1 3 1‐3A‐212A‐SB Scrub Room Smoke Barrier door UD 1 3 1‐3A‐201(b)‐FD GIP Storage Room 1hr Fire door UD 1 3 1‐3A‐211A‐SB Scrub Room Smoke Barrier door UD 1 3 1‐3A‐215‐SB Equip. Room Smoke Barrier door UD 1 3 1‐3A‐216‐SB Closet Smoke Barrier door UD 1 3 1‐3A‐211B‐SB Scrub Room Smoke Barrier door UD 1 3 1‐3A‐COR C3A13‐SB Corridor door Smoke Barrier door UD 1 3 1‐3A‐210‐SB Anesthesia Storage Smoke Barrier door UD 1 3 1‐3A‐COR C3A4‐SB Corridor door Smoke Barrier door UD 1 3 1‐3W‐COR B‐SB Corridor door Smoke Barrier door UD 1 3 1‐3A‐COR C3A1‐SB Corridor door Smoke Barrier door UD 1 3 1‐3N‐COR C3N1‐SB Corridor door Smoke Barrier door UD 1 3 1‐3W‐100‐SB Anesthesia Storage Smoke Barrier door UD 1 3 1‐3A‐199‐SB (rear) Scrub Room Smoke Barrier door UD 1 3 1‐3A‐197‐SB (rear) Scrub Room Smoke Barrier door UD 1 3 1‐3A‐194‐SB Lounge Door Smoke Barrier door
UD 1 3 1‐3A‐COR C3N5‐SB Corridor door Smoke Barrier door UD 1 3 1‐3N‐SW6‐FD Stairwell door 2hr Fire door UD 1 3 1‐3N‐COR C3N7‐SB Corridor door Smoke Barrier door
UD 1 3 1‐3N‐116‐SB On‐Call Room Smoke Barrier door UD 1 3 1‐3W‐COR C3W1‐SB Corridor door Smoke Barrier door UD 1 3 1‐3W‐COR D‐SUITE Corridor door Suite Boundary UD 1 3 1‐3W‐101‐SB Reception Desk Smoke Barrier door UD 1 3 1‐3W‐108‐FD Soiled Utility 1hr Fire door UD 1 3 1‐3W‐110‐HAZ Clean Utility High Hazard door UD 1 3 1‐3W‐COR A‐SUITE Corridor door Suite Boundary UD 1 3 1‐3W‐COR C3W200B‐FD Corridor door 1hr Fire door UD 1 3 1‐3W‐200‐FD Recovery Area 1hr Fire door UD 1 3 1‐3W‐213‐FD Supply Storage 1hr Fire door UD 1 3 1‐3W‐214(a)‐FD Supply Storage 1hr Fire door UD 1 3 1‐3W‐214(b)‐FD Supply Storage 1hr Fire door UD 1 3 1‐3W‐216‐HAZ Scope Storage High Hazard door UD 1 3 1‐3W‐217‐HAZ Clean Utility High Hazard door UD 1 3 1‐3W‐228‐FD Soiled Utility 1hr Fire door UD 1 3 1‐3W‐SW2A‐FD Stairwell door 2hr Fire door UD 1 3 1‐3W‐218‐SUITE Decon Room Suite Boundary UD 1 3 1‐3W‐COR C3W200C‐SUITE Corridor door Suite Boundary UD 1 3 1‐3W‐226‐SUITE Housekeeping Suite Boundary UD 1 3 1‐3W‐COR C3W200C‐FD Corridor door 1hr Fire door UD 1 3 1‐3N‐Elev 14/15‐SB Elevator Lobby Smoke Barrier door UD 1 3 1‐3N‐SW1‐FD Stairwell door 2hr Fire door UD 1 3 1‐3N‐COR C3N5‐SB Corridor door Smoke Barrier door UD 1 3 1‐3N‐131‐HAZ Clean Utility High Hazard door UD 1 3 1‐3N‐240‐SB Office Door Smoke Barrier door UD 1 3 1‐3N‐239‐SB Treatment Room Smoke Barrier door UD 1 3 1‐3N‐204‐FD Soiled Utility 1hr Fire door UD 1 3 1‐3N‐206‐HAZ Storage Room High Hazard door UD 1 3 1‐3N‐SW7‐FD Stairwell door 2hr Fire door UD 1 3 1‐3E‐COR C3E1‐SB Corridor door Smoke Barrier door UD 1 3 1‐3E‐102‐FD Soiled Utility 1hr Fire door UD 1 3 1‐3E‐131‐HAZ Linen Room High Hazard door UD 1 3 1‐3E‐120‐FD Soiled Utility 1hr Fire door UD 1 3 1‐3E‐SW3‐FD Stairwell door 2hr Fire door UD 1 2 1‐2A‐SW9‐FD Stairwell door 2hr Fire door UD 1 2 1‐2A‐131(a)‐FD Mechanical Room 1hr Fire door UD 1 2 1‐2A‐131(b)‐FB Mechanical Room 1hr Fire door UD 1 2 1‐2A‐SW10‐FD Stairwell door 2hr Fire door UD 1 2 1‐2A‐130(a)‐FD Mechanical Room 1hr Fire door UD 1 2 1‐2A‐130(b)‐FD Mechanical Room 1hr Fire door UD 1 2 1‐2A‐130(c)‐FD Mechanical Room 1hr Fire door UD 1 2 1‐2A‐214‐HAZ Scope Sterilizer Room High Hazard door UD 1 2 1‐2A‐206‐HAZ Linen Room High Hazard door UD 1 2 1‐2A‐COR 2A200‐FD Corridor door 1hr Fire door UD 1 2 1‐2W‐109‐FD Check‐In Area 1hr Fire door UD 1 2 1‐2W‐SW2‐FD Stairwell door 2hr Fire door
UD 1 2 1‐2W‐200‐HAZ Mechanical Room High Hazard door UD 1 2 1‐2W‐COR C2W143A‐FD Corridor door 1hr Fire door UD 1 2 1‐2W‐SW5‐FD Stairwell door 2hr Fire door UD 1 2 1‐2W‐COR C2W5‐FD Corridor door 1hr Fire door UD 1 2 1‐2W‐COR C2W7‐FD Corridor door 1hr Fire door UD 1 2 1‐2W‐132‐FD Clean Utility 1hr Fire door UD 1 2 1‐2W‐131‐FD Soiled Utility 1hr Fire door UD 1 2 1‐2W‐130‐FD Electric Closet 1hr Fire door UD 1 2 1‐2W‐SW2A‐FD Stairwell door 2hr Fire door UD 1 2 1‐2W‐151‐HAZ Storage Room High Hazard door UD 1 2 1‐2W‐176‐FD Laboratory 1hr Fire door UD 1 2 1‐2W‐173(a)‐FD Laboratory 1hr Fire door UD 1 2 2W‐COR C2C3A‐1‐FD Corridor door 1hr Fire door UD 1 2 1‐2W‐173(b)‐FD Laboratory 1hr Fire door UD 1 2 1‐2W‐104‐HAZ Storage Room High Hazard door UD 1 2 1‐2NW‐102A‐SB Storage Room Smoke Barrier door UD 1 2 1‐2NW‐101‐SB Core Lab Smoke Barrier door UD 1 2 1‐2N‐SW1‐FD Stairwell door 2hr Fire door UD 1 2 1‐2N‐COR C2N1‐SB Corridor door Smoke Barrier door UD 1 2 1‐2N‐Elev 14/15‐SB Elevator Lobby Smoke Barrier door UD 1 2 1‐2NW‐118‐HAZ Bio‐Waste Storage High Hazard door UD 1 2 1‐2N‐COR C2NW1‐SB Corridor door Smoke Barrier door UD 1 2 1‐2N‐SW6‐FD Stairwell door 2hr Fire door UD 1 2 1‐2NW‐106‐HAZ Sterilization Room High Hazard door UD 1 2 1‐2N‐SW8(a)‐FD Stairwell door 2hr Fire door UD 1 2 1‐2N‐SW8(b)‐FD Stairwell door 2hr Fire door UD 1 2 1‐2N‐COR C2N1A‐SB Corridor door Smoke Barrier door UD 1 2 1‐2NE‐108‐HAZ Storage Room High Hazard door UD 1 2 1‐2N‐SW7‐FD Stairwell door 2hr Fire door UD 1 2 1‐2NE‐119‐FD Office 1hr Fire door UD 1 2 1‐2NE‐118‐FD Histology Lab 1hr Fire door UD 1 2 1‐2NE‐117‐FD Histology Lab 1hr Fire door UD 1 2 1‐2NE‐115‐HAZ Storage Room High Hazard door UD 1 2 1‐2NE‐100‐SB Laboratory Smoke Barrier door UD 1 2 1‐2C‐106‐SB Data Closet Smoke Barrier door UD 1 2 1‐2E‐COR C2E1‐SB Corridor door Smoke Barrier door UD 1 2 1‐2E‐140‐FD Tissue Lab 1hr Fire door UD 1 2 1‐2E‐SW3‐FD Stairwell door 2hr Fire door UD 1 2 1‐2NW‐120‐SB Immunology Smoke Barrier door UD 1 2 1‐2W‐171‐FD Tissue Lab 1hr Fire door UD 1 2 1‐2NW102A(B)‐HAZ Immunology High Hazard door UD 1 2 1‐2NW102A(A)‐HAZ Immunology High Hazard door UD 1 2 1‐2NE‐102‐SB W/C Spec Smoke Barrier door UD 1 2 1‐2NE‐101A‐SB Lactations Smoke Barrier door UD 1 2 1‐2A‐218(A)‐HAZ Soiled Scope Room High Hazard door UD 1 2 1‐2A‐218(B)‐HAZ Soiled Scope Room High Hazard door
UD 1 2 1‐2A‐218(C)‐HAZ Soiled Scope Room High Hazard door UD 1 1 1‐1A‐SW9‐FD Stairwell door 2hr Fire door UD 1 1 1‐1A‐COR C1‐17‐SB Corridor door Smoke Barrier door UD 1 1 1‐1A‐194‐FD Soiled Utility 1hr Fire door UD 1 1 1‐1A‐193‐HAZ Clean Utility High Hazard door UD 1 1 1‐1A‐COR C1‐14‐SB Corridor door Smoke Barrier door UD 1 1 1‐1A‐SW10‐FD Stairwell door 2hr Fire door UD 1 1 1‐1A‐175X (a)‐FD Electrical Room 2hr Fire door UD 1 1 1‐1A‐175X (b)‐FD Electrical Room 2hr Fire door UD 1 1 1‐1A‐174‐SUITE Procedure Room Suite Boundary UD 1 1 1‐1A‐170‐SUITE Procedure Room Suite Boundary UD 1 1 1‐1A‐COR C1‐12‐SB Corridor door Smoke Barrier door UD 1 1 1‐1A‐167‐SUITE Procedure Room Suite Boundary UD 1 1 1‐1A‐162‐SUITE Procedure Room Suite Boundary UD 1 1 1‐1A‐158‐SUITE Procedure Room Suite Boundary UD 1 1 1‐1A‐156‐SUITE Procedure Room Suite Boundary UD 1 1 1‐1A‐145‐SUITE Work Corridor door Suite Boundary UD 1 1 1‐1A‐148‐HAZ Clean Utility High Hazard door UD 1 1 1‐1A‐147‐FD Soiled Utility 1hr Fire door UD 1 1 1‐1A‐COR 1A143‐SB Work Corridor door Smoke Barrier door UD 1 1 1‐1A‐143‐SUITE Work Corridor door Suite Boundary UD 1 1 1‐1A‐142‐SUITE Procedure Room Suite Boundary UD 1 1 1‐1A‐127‐SUITE Patient Holding Suite Boundary UD 1 1 1‐1A‐124‐SB Dressing Room Smoke Barrier door UD 1 1 1‐1A‐123‐SB Patient Holding Smoke Barrier door UD 1 1 1‐1A‐122B‐SB Office door Smoke Barrier door UD 1 1 1‐1A‐122‐SUITE Procedure Room Suite Boundary UD 1 1 1‐1A‐COR C1‐4‐SB Corridor door Smoke Barrier door UD 1 1 1‐1W‐160 Waiting Room Smoke Barrier door UD 1 1 1‐1A‐121‐SUITE Procedure Room Suite Boundary UD 1 1 1‐1A‐119‐SUITE Procedure Room Suite Boundary UD 1 1 1‐1A‐118‐SUITE Procedure Room Suite Boundary UD 1 1 1‐1A‐117‐SUITE Procedure Room Suite Boundary UD 1 1 1‐1A‐116‐HAZ Clean Utility High Hazard door UD 1 1 1‐1A‐114‐HAZ Clean Utility High Hazard door UD 1 1 1‐1A‐112‐HAZ Soiled Utility High Hazard door UD 1 1 1‐1A‐111‐HAZ Soiled Utility High Hazard door UD 1 1 1‐1W‐COR 1W171‐SB Corridor door Smoke Barrier door UD 1 1 1‐1A‐105‐SUITE Procedure Room Suite Boundary UD 1 1 1‐1A‐104‐SUITE Restroom Door Suite Boundary UD 1 1 1‐1A‐102‐SUITE Procedure Room Suite Boundary UD 1 1 1‐1W‐SW5‐FD Stairwell door 2hr Fire door UD 1 1 1‐1W‐138A‐FD Tank Storage 1hr Fire door UD 1 1 1‐1W‐129C‐SUITE Procedure Room Suite Boundary UD 1 1 1‐1A‐123‐SUITE Procedure Room Suite Boundary UD 1 1 1‐1W‐118‐HAZ Clean Utility High Hazard door
UD 1 1 1‐1W‐COR 1W176‐FD Corridor door 1hr Fire door UD 1 1 1‐1W‐163‐FD Decay Storage Room 1hr Fire door UD 1 1 1‐1W‐161‐FD Office door 1hr Fire door UD 1 1 1‐1W‐SW2‐FD Stairwell door 2hr Fire door UD 1 1 1‐1W‐160‐SUITE Procedure Room Suite Boundary UD 1 1 1‐1W‐COR 1W178(a)‐SUITE Corridor door Suite Boundary UD 1 1 1‐1W‐112 Mechanical Room 1hr Fire door UD 1 1 1‐1W‐108‐SUITE Uptake Room Suite Boundary UD 1 1 1‐1W‐106‐SUITE Restroom Door Suite Boundary UD 1 1 1‐1W‐105‐SUITE Restroom Door Suite Boundary UD 1 1 1‐1W‐COR 1W178(b)‐SUITE Corridor door Suite Boundary
UD 1 1 1‐1W‐153‐FD Soiled Utility 1hr Fire door UD 1 1 1‐1W‐COR 1W170‐FD Corridor door 2hr Fire door UD 1 1 1‐1N‐COR C1C3(a)‐SB Corridor door Smoke Barrier door UD 1 1 1‐1N‐COR C1‐2‐SB Corridor door Smoke Barrier door UD 1 1 1‐1N‐COR 1N1A‐FD Corridor door 2hr Fire door UD 1 1 1‐1N‐COR 1N1B‐FD Corridor door 2hr Fire door UD 1 1 1‐1N‐COR 1N1C‐FD Corridor door 2hr Fire door UD 1 1 1‐1N‐COR 1NW114‐FD Corridor door 2hr Fire door UD 1 1 1‐1NW‐SW6(a)‐FD Stairwell door 2hr Fire door UD 1 1 1‐1NW‐SW6(b)‐FD Stairwell door 2hr Fire door UD 1 1 1‐1NW‐117‐FD Soiled Utility 1hr Fire door UD 1 1 1‐1NW‐109‐HAZ Equip. Room High Hazard door UD 1 1 1‐1NW‐COR 1NW129‐SUITE Corridor door Suite Boundary UD 1 1 1‐1NE‐108‐FD Storage Room 1hr Fire door UD 1 1 1‐1NE‐SW7‐FD Stairwell door 2hr Fire door UD 1 1 1‐1N‐COR 1NE110‐FD Corridor door 2hr Fire door UD 1 1 1‐1N‐COR C1N127A‐SB Corridor door Smoke Barrier door UD 1 1 1‐1N‐SW8(a)‐FD Stairwell door 2hr Fire door UD 1 1 1‐1N‐SW8(b)‐FD Stairwell door 2hr Fire door UD 1 1 1‐1N‐219F‐SB Pharmacy door Smoke Barrier door UD 1 1 1‐1N‐210‐SB Pharmacy door Smoke Barrier door UD 1 1 1‐1N‐209‐SB Pharmacy door Smoke Barrier door UD 1 1 1‐1N‐COR C1C3(b)‐SB Corridor door Smoke Barrier door UD 1 1 1‐1N‐147‐HAZ Storage Room High Hazard door UD 1 1 1‐1N‐148‐HAZ Mechanical Room High Hazard door UD 1 1 1‐1N‐SW1‐FD Stairwell door 2hr Fire door UD 1 1 1‐1N‐Elev 14/15‐SB Elevator Lobby Smoke Barrier door UD 1 1 1‐1E‐SW3‐FD Stairwell door 2hr Fire door UD 1 1 1‐1E‐COR 1E134‐SB Corridor door Smoke Barrier door UD 1 1 1‐1E‐120‐FD Soiled Utility 1hr Fire door UD 1 1 1‐1E‐SW4‐FD Stairwell door 2hr Fire door UD 1 1 1‐1W‐103‐SUITE Exam Suite Boundary UD 1 1 1‐1W‐102‐SUITE Exam Suite Boundary UD 1 1 1‐1W‐123‐SUITE MRI Entry Suite Boundary UD 1 G AA‐SW9‐FD Stairwell door 2hr Fire door
UD 1 G AA‐143(a)‐FD Clean Linen Storage 1hr Fire door UD 1 G AA‐143(b)‐FD Clean Linen Storage 1hr Fire door UD 1 G AA‐141(a)‐FD Soiled Linen Storage 1hr Fire door UD 1 G AA‐141(b)‐FD Soiled Linen Storage 1hr Fire door UD 1 G AA‐133‐FD West Loading Dock 2hr Fire door UD 1 G AA‐114A‐FD Transformer Room 2hr Fire door UD 1 G AA‐COR CAA1(a)‐FD Corridor door 2hr Fire door UD 1 G AA‐117‐FD Decomtam Room 2hr Fire door UD 1 G AA‐COR CAA8‐FD Corridor door 2hr Fire door UD 1 G AA‐116(a)‐FD Mechanical Room 2hr Fire door
UD 1 G AA‐116(b)‐FD Mechanical Room 2hr Fire door UD 1 G AA‐116(c)‐FD Mechanical Room 2hr Fire door UD 1 G AA‐116(d)‐FD Mechanical Room 2hr Fire door UD 1 G AW‐SW2‐FD Stairwell door 2hr Fire door UD 1 G AA‐COR CA3‐FD Corridor door 2hr Fire door UD 1 G AA‐SW10‐FD Stairwell door 2hr Fire door UD 1 G AA‐113‐FD Generator Room 2hr Fire door
UD 1 G AA‐114‐FD Mechanical Room 2hr Fire door UD 1 G AW‐COR CAW24B‐FD Corridor door 2hr Fire door UD 1 G AW‐134‐HAZ Storage Room High Hazard door UD 1 G AW‐COR CAW24D‐SB Corridor door Smoke Barrier door UD 1 G AW‐125‐HAZ Clean Equipmt Room High Hazard door UD 1 G AW‐121‐HAZ Storage Room High Hazard door UD 1 G AW‐SW5‐FD Stairwell door 2hr Fire door UD 1 G AW‐116‐HAZ Storage Room High Hazard door UD 1 G AW‐COR CAW24‐SB Corridor door Smoke Barrier door UD 1 G AW‐114‐HAZ Storage Room High Hazard door UD 1 G AN‐207‐FD Gas Storage Room 2hr Fire door UD 1 G AN‐206‐FD Oxygen storage 2hr Fire door
UD 1 G AN‐205A‐FD Gas Storage Room 2hr Fire door UD 1 G AN‐COR AA100‐FD Corridor door 2hr Fire door UD 1 G AA‐COR CA4‐SB Corridor door Smoke Barrier door UD 1 G AA‐108‐SB Break Room Smoke Barrier door UD 1 G AA‐109‐SB Wipe Down Room Smoke Barrier door UD 1 G AA‐122(a)‐SB Sterilization Room Smoke Barrier door UD 1 G AA‐122(b)‐SB Sterilization Room Smoke Barrier door UD 1 G AA‐122(c)‐SB Sterilization Room Smoke Barrier door UD 1 G AA‐131‐FB Elev Machine Room 1hr Fire door UD 1 G AA‐142‐FB Chute Room 1hr Fire door UD 1 G AA‐152‐SB SPD Breakout Smoke Barrier door UD 1 G AA‐153‐SB Logistics Receiving Smoke Barrier door UD 1 G AA‐160‐SB Bio‐Med Workroom Smoke Barrier door
UD 1 G AA‐COR CAA1(b)‐FD Corridor door 2hr Fire door UD 1 G AA‐COR CAA3‐SB Corridor door Smoke Barrier door UD 1 G AA‐157(a)‐FD Reg Waste Storage 1hr Fire door UD 1 G AA‐157(b)‐FD Reg Waste Storage 1hr Fire door UD 1 G AA‐149‐SB North Loading Dock Smoke Barrier door UD 1 G AN‐SW7A‐FD Stairwell door 2hr Fire door UD 1 G AN‐316‐HAZ Bio‐Med Workroom High Hazard door UD 1 G AN‐SW8‐FD Stairwell door 2hr Fire door UD 1 G AN‐120(a)‐HAZ Pharmacy Storage High Hazard door UD 1 G AN‐120(b)‐HAZ Pharmacy Storage High Hazard door UD 1 G AN‐201‐HAZ Storage Room High Hazard door UD 1 G AN‐SW1‐FD Stairwell door 2hr Fire door UD 1 G AE‐COR CAC6‐SBD Corridor door Smoke Barrier door UD 1 G AE‐COR CAE1‐SBD Corridor door Smoke Barrier door UD 1 G AE‐121‐HAZ Retail Store High Hazard door UD 1 G AE‐114‐HAZ Storage Room High Hazard door UD 1 G AE‐115‐HAZ Mail/Copy Room High Hazard door UD 1 G AE‐SW3‐FD Stairwell door 2hr Fire door UD 1 G GG‐109 Vestibule door 2hr Fire door UD 1 G AE‐SW4‐FD Stairwell door 2hr Fire door UD 1 G 1‐AE‐157(a)‐FD Trash 1hr Fire door UD 1 G 1‐AE‐157(b)‐FD Trash 1hr Fire door UD 1 B BW‐SW5‐FD Stairwell door 1hr Fire door UD 1 B BW‐233‐FD Soiled Utility 1hr Fire door UD 1 B BW‐234‐FD Clean Utility 1hr Fire door UD 1 B BW‐COR CBW7‐FD Corridor door 1hr Fire door UD 1 B BW‐202‐FD Electrical Closet 1hr Fire door UD 1 B BW‐106B‐FD Paint Storage Room 1hr Fire door UD 1 B BW‐106‐HAZ Carpenter Shop High Hazard door UD 1 B BW‐106A‐FD Fire Pump Room 1hr Fire door UD 1 B BW‐COR CBW6‐SB Corridor door Smoke Barrier door UD 1 B BW‐103‐HAZ Electric Shop High Hazard door UD 1 B BN‐210‐FD Elev Machine Room 2hr Fire door UD 1 B BN‐211‐FD Mechanical Room 1hr Fire door UD 1 B BN‐110A‐FD Storage Room 1hr Fire door UD 1 B BN‐106‐FD Elect Switchgear Room 2hr Fire door UD 1 B BN‐104(a)‐FD Transformer Room 2hr Fire door UD 1 B BN‐104(b)‐FD Transformer Room 2hr Fire door UD 1 B BN‐102(a)‐FD Elect Switchgear Room 2hr Fire door UD 1 B BN‐102(b)‐FD Elect Switchgear Room 2hr Fire door UD 1 B BN‐101‐FD Elect Switchgear Room 2hr Fire door UD 1 B BN‐SW1‐FD Stairwell door 2hr Fire door UD 1 B BC‐103(a)‐FD Linen Chute Room 2hr Fire door UD 1 B BC‐103(b)‐FD Crawl Space door 2hr Fire door
UD 1 B 1‐COR CBC1A‐FD Corridor door 1hr Fire door
Site Bldg Flr Door Designation or
Room Number Description Type UD 29 7 29‐7‐RM101‐FD Elevator Controls 2hr Fire door UD 29 6 29‐PM‐SWM2‐FD Stairwell door 2hr Fire door UD 29 6 29‐PM‐105A‐HAZ Mechanical Room High Hazard door UD 29 6 29‐PM‐SWM3‐FD Stairwell door 2hr Fire door UD 29 6 29‐PM‐105‐FD Mechanical Room 1hr Fire door UD 29 6 29‐PM‐106A‐FD Mechanical Room 2hr Fire door UD 29 6 29‐PM‐106‐HAZ Mechanical Room High Hazard door UD 29 6 29‐PM‐SWM4‐FD Stairwell door 2hr Fire door UD 29 5 29‐5M‐SWM2‐FD Stairwell door 2hr Fire door UD 29 5 29‐5M‐SWM3‐FD Stairwell door 2hr Fire door UD 29 5 29‐5M‐151‐FD Soiled Utility 1hr Fire door UD 29 5 29‐5M‐COR 4MC105‐SB Cooridor door Smoke Barrier door UD 29 5 29‐5M‐106‐FD Laundry 1hr Fire door UD 29 5 29‐5M‐104‐FD Soiled Utility 1hr Fire door UD 29 5 29‐5M‐167‐FD Storage Room 1hr Fire door UD 29 5 29‐5M‐SWM4‐FD Stairwell door 2hr Fire door UD 29 4 29‐4M‐SWM2‐FD Stairwell door 2hr Fire door UD 29 4 29‐4M‐SWM3‐FD Stairwell door 2hr Fire door UD 29 4 29‐4M‐151‐FD Soiled Utility 1hr Fire door UD 29 4 29‐4M‐COR 4MC105‐SB Cooridor door Smoke Barrier door UD 29 4 29‐4M‐106‐FD Laundry 1hr Fire door UD 29 4 29‐4M‐104‐FD Soiled Utility 1hr Fire door UD 29 4 29‐4M‐167‐FD Storage Room 1hr Fire door UD 29 4 29‐4M‐SWM4‐FD Stairwell door 2hr Fire door UD 29 3 29‐3M‐SWM2‐FD Stairwell door 2hr Fire door UD 29 3 29‐3M‐128A‐FD Storage Room 1hr Fire door UD 29 3 29‐3M‐SWM3‐FD Stairwell door 2hr Fire door UD 29 3 29‐3M‐151‐FD Soiled Utility 1hr Fire door UD 29 3 29‐3M‐COR 3MC105‐SB Cooridor door Smoke Barrier door UD 29 3 29‐3M‐101A‐HAZ Storage Room High Hazard door UD 29 3 29‐3M‐106‐FD Laundry 1hr Fire door UD 29 3 29‐3M‐104‐FD Soiled Utility 1hr Fire door UD 29 3 1‐3M‐159‐HAZ Shell Space High Hazard door UD 29 3 29‐3M‐SWM4‐FD Stairwell door 2hr Fire door UD 29 2 29‐2M‐SWM2‐FD Stairwell door 2hr Fire door UD 29 2 29‐2M‐SWM3‐FD Stairwell door 2hr Fire door UD 29 2 29‐2M‐282‐HAZ Storage Room High Hazard door UD 29 2 29‐2M‐SWM4‐FD Stairwell door 2hr Fire door UD 29 2 29‐2M‐COR 2MC112‐FD Cooridor door 2hr Fire door UD 29 2 29‐2M‐202(a)‐FD Auditorium 2hr Fire door
2019 U.D. Bldg 29 Fire Door & Smoke Door Inspections
UD 29 2 29‐2M‐202(b)‐FD Auditorium 2hr Fire door UD 29 2 29‐2M‐202(c)‐FD Auditorium 2hr Fire door UD 29 2 29‐2M‐COR 2MC107‐FD Cooridor door 2hr Fire door UD 29 1 29‐1M‐SWM2‐FD Stairwell door 2hr Fire door UD 29 1 29‐1M‐137‐FD Soiled Utility 1hr Fire door UD 29 1 29‐1M‐169‐FD Clean Supply 1hr Fire door UD 29 1 29‐1M‐196‐FD Clean Supply 1hr Fire door UD 29 1 29‐1M‐SWM3‐FD Stairwell door 2hr Fire door UD 29 1 29‐1M‐SWM4‐FD Stairwell door 2hr Fire door UD 29 1 29‐1M‐COR 1MC119‐SB Vestibule door Smoke Barrier door UD 29 1 29‐1M‐100‐SB Lobby Entrance Smoke Barrier door UD 29 1 29‐1M‐220‐SB Fire Control Room Smoke Barrier door UD 29 G 29‐GM‐SWM4‐FD Stairwell door 2hr Fire door UD 29 G 29‐GM‐104(a)‐FD Mechanical Room 2hr Fire door UD 29 G 29‐GM‐104(b)‐FD Mechanical Room 2hr Fire door UD 29 G 29‐GM‐105(a)‐FD Mechanical Room 2hr Fire door UD 29 G 29‐GM‐105(b)‐FD Mechanical Room 2hr Fire door UD 29 G 29‐GM‐104A‐FD Mechanical Room 2hr Fire door UD 29 G 29‐GM‐107‐FD Storage Room 2hr Fire door UD 29 G 29‐GM‐103‐FD Storage Room 1hr Fire door UD 29 G 29‐GM‐COR GMC110‐SB Cooridor door Smoke Barrier door UD 29 G 29‐GM‐111‐FD Storage Room 1hr Fire door UD 29 G 29‐COR GMC101‐FD Cooridor door 1hr Fire door UD 29 G 29‐GM‐109‐FD Office Doors 1hr Fire door UD 29 G 29‐GMS‐107‐FD Exit Passage 2hr Fire door UD 29 G 29‐GM‐101‐FD Storage Room 1hr Fire door UD 29 G 29‐COR GMC104‐FD Cooridor door 1hr Fire door UD 29 B 29‐BM‐SWM4‐FD Stairwell door 2hr Fire door
| Att 1 - Door Inspection and Testing Form - DRAFT Rev3.pdf |
| Operation |
| Frame |
| Door |
| Door Closer |
| Hinges |
| Flush Bolts |
| Lockset / Hardware |
| Fire Exit Hardware |
| Other |
File details come from the government source that posted it. Updated .