This attachment details the Montrose Campus Wastewater Treatment Plant (WWTP) permit requirements under New York State Department of Environmental Conservation (NYS DEC) SPDES Permit NY0021326. The document specifies comprehensive effluent monitoring and discharge limitations for the facility's outfall into the Hudson River, including monthly and daily parameters for flow, biochemical oxygen demand (BOD), suspended solids, pH, coliform bacteria, and other environmental metrics. Key operational requirements include seasonal disinfection from May 1st to October 1st, with ongoing commissioning of a new Trojan UV System expected to modify the plant's chlorination process. Monitoring frequencies range from daily to monthly, with specific sampling types including continuous recording, composite, and grab samples at both influent and effluent locations. The vendor is expected to incorporate the new UV system and its operational changes into their proposal, ensuring compliance with stringent environmental discharge standards.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENT A – MONTROSE CAMPUS WWTP PERMIT REQUIREMENTS
Meet Current Montrose WWTP NYS DEQ SPDES Permit NY0021326 requirements including but not limited to:
OUTFALL No. LIMITATIONS APPLY: RECEIVING WATER EFFECTIVE EXPIRING 001 All year unless otherwise noted Hudson River EDPM ExDP
PARAMETER EFFLUENT LIMIT MONITORING REQUIREMENTS FN
TYPE LIMIT UNITS LIMIT UNITS SAMPLE
FREQUENCY
SAMPLE
TYPE
LOCATION
INF. EFF.
Flow Monthly Average
0.40 MGD Continuous Recorder X
BOD 30-Day Arithmetic
Mean
30 mg/l 100 lbs./day 1/month 6 hr.
Composite
X X 1
BOD 7-Day Arithmetic
Mean
45 mg/l 150 lbs./day 1/month 6 hr.
Composite
Solids, Suspended
30-Day Arithmetic
Mean
30 mg/l 100 lbs./day 1/month 6 hr.
Composite
X X 1
Solids, Suspended
7-Day Arithmetic
Mean
45 mg/l 150 lbs../day 1/month 6 hr.
Composite
X
Solids, Settleable
Daily Maximum
0.3 ml/l Daily Grab X pH Range 6.0-9.0 SU Daily Grab X Nitrogen, Ammonia (as N)
Daily Maximum
Monitor mg/l 1/month Grab X
Temperature Daily Maximum
Monitor Deg C Daily Grab X X
Effluent Disinfection Required:[ ] All Year [X] Seasonal from May 1st to October 1st Coliform, Fecal 30-Day
Geometric Mean
200 No./ 100 ml
1/month Grab X
Coliform 7-Day Geometric
Mean
400 No./ 100 ml
1/month Grab X
Coliform 6 Hr.
Geometric
Mean
800 No./ 100 ml
See Footnote See Footnote
X 2
Coliform Individual Sample
2400 No./ 100 ml
See Footnote See Footnote
X 2
Coliform Daily Maximum
.375 Mg/l Daily Grab X 3,4
Coliform P/A 44 annually. They are scheduled periodically throughout the year.
Heterotrophic plate count 44 annually. Sites same as above coliform test
In accordance with page 3 of SPDES permit NY002136 attached. Use the list from the attachment for this section. There are more tests required then he outlines below.
BOD5 Influent and Effluent monthly
TSS Influent and Effluent monthly
Nitrogen/Ammonia N monthly
Total Coliform monthly May 1st -Oct 31st (during chlorination period)
Fecal Coliform monthly May-Oct (during chlorination period)
Vendor shall incorporate into their proposal newly installed Trojan UV System; commissioning of system is on-going and expected to be completed by the end of 2019. Once finalized and operational, the system will affect requirements for the plant chlorination process. Vendor shall incorporate these expected changes to the plant operation into their proposal.
SPDES PERMIT NUMBER NY0021326 (PAGE 3)
FOOTNOTES:
(1) AND EFFLUENT SHALL NOT EXCEED 15% AND 15% OF INFLUENT CONCENTRATION
VALUES FOR BOD & TSS RESPECTIVELY.
(2) THIS IS AN INTERSTATE ENVIRONMENT COMMISSION (IEC) REQUIREMENT. THE
PERMITTEE IS NOT REQUIRED TO PERFORM THIS SAMPLING BUT SHALL BE
REQUIRED TO MEET THE PERMIT LIMIT AT ALL TIMES. EPA, DEC OR IEC MAY
PERFORM SAMPLING.
(3) AN INTERIM TOTAL RESIDUAL CHLORINE LIMIT OF 0.5-2.0 MG/L IS IN EFFECT UNTIL
THE DISINFECTION SYSTEM IS UPGRADED TO MEET THE FINAL EFFLUENT LIMIT OF
0.375 MG/L IN ACCORDANCE WITH THE SCHEDULE OF COMPLIANCE ON PAGE 4 OF
THIS PERMIT
(4) FINAL EFFLUENT LIMIT