Attachment_A_-_Drawings_(MAPS_HVAC_Upgrade).pdf

PDF 8 MB Posted

Attached to
HVAC Upgrades at Moss Avenue Pumping Station (MAPS)
Solicitation number
4517
Issued by
Los Angeles County, San Francisco City, California

About this file

This is a technical drawings document for HVAC system upgrades at the Moss Avenue Pumping Station (MAPS) in Santa Monica, California, prepared by the City of Santa Monica Water Resources Division. The project specifies installation of a Model TUHYE0964AN41AN outdoor condensing unit with 96,000 BTU/H cooling capacity and 108,000 BTU/H heating capacity, paired with a Model TPEFYP072MH140A indoor fan coil unit rated for 72,000 BTU/H cooling and 140,000 BTU/H heating. The drawings detail mechanical plans for both ground and upper floors, including refrigerant piping routes, condensate drain configurations, ductwork layout with supply and return air specifications (3,000 CFM supply grille and 2,250 CFM return louver), outside air intake provisions (750 CFM via 16-inch duct), electrical schematics, and equipment placement requirements. The outdoor unit requires a 6-inch elevated equipment pad with 36-inch clearance on all sides and specified inlet protection, while the indoor fan coil unit must be positioned to maintain minimum 1 percent slope for condensate piping without obstruction. A mandatory job walk is scheduled for March 31, 2026, at 10:00 AM; vendor questions are due April 7, 2026, at 3:00 PM Pacific Time with responses posted by April 14, 2026; and sealed bid submissions are due April 21, 2026, at 3:00 PM Pacific Time.

Qualified contractors must hold California C-10 (electrical) and C-20 (HVAC) licenses along with EPA 608 certification for refrigerant handling. Pricing must be submitted as a lump sum for all materials and labor through the City's Online Vendor Portal. The contract value exceeds $25,000, requiring a payment bond equal to 100 percent of the contract proposal amount. Minimum insurance requirements include $1,000,000 Commercial General Liability on an occurrence basis, $1,000,000 Automobile Liability, and Workers' Compensation with $1,000,000 Employers' Liability per accident. All work must comply with the 2022 California Mechanical Code, Building Code, Plumbing Code, and City of Santa Monica ordinances. Prevailing wage requirements apply under California Labor Code sections 1770 et seq., with all workers subject to established prevailing wage schedules and contractors required to register the determination with the Department of Industrial Relations prior to project execution. Payment terms are net thirty days from delivery and receipt of invoice, with the City responsible for applicable taxes and exempt from Federal Excise Tax. No estimated award value or specific budget range is disclosed in the project documents.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL PLAN

UPPER FLOOR

SCALE: N.T.S.

MECHANICAL

Standard Model� TUHYE0964AN41AN

ACCESSORIES

Big Foot Stand� for details see Big Foot Stands submittals Header Kit� for details see Pipe Accessories Submittal Joint Kit� for details see Pipe Accessories Submittal Low Ambient Kit� for details see Low Ambient Kit Submittal Panel Heater Kit� for details see Panel Heater Kit Submittal Snow/Hail Guards Kit� for details see Snow/Hail Guards Kit Submittal

Specifications System Unit Type TUHYE0964AN41AN

Cooling Capacity (Nominal) BTU/H 96,000 Heating Capacity (Nominal) BTU/H 108,000

Guaranteed Operating Range Cooling ºF [ºC] 23~126 [-5.0~52.0] Heating ºF [ºC] -13~60 [-25.0~15.5]

Extended Operating Range Heating ºF [ºC] -27.4~60 [-33.0~15.5]

External Dimensions (H x W x D) In. [mm] 71-5/8 x 48-7/8 x 29-3/16 [1,818 x 1,240 x 740]

Net Weight Lbs. [kg] 657 [298]

External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type) [MUNSELL 3Y 7.8/1.1 or similar]

Electrical Power Requirements Voltage, Phase, Hertz, Power Tolerance 460V, 3-phase, 60 Hz, ±10% Minimum Circuit Ampacity A 20.0 Maximum Overcurrent Protection A 30 Recommended Fuse Size A 20 Recommended Minimum Wire Size AWG [mm] 12 [3.3] SCCR kA 5

Refrigerant Piping Diameter Liquid (High Pressure) In. [mm] 3/8 [9.52] Brazed (Pipe Size Dependent on Piping Length) Gas (Low Pressure) In. [mm] 7/8 [22.2] Brazed

Max. Total Refrigerant Line Length Ft. 3,280 [1,000] Max. Refrigerant Line Length (Between ODU & IDU) Ft. 541 [165] Max. Control Wiring Length Ft. 1,640 [500]

Indoor Unit Connectable Total Capacity 50.0~130.0% of outdoor unit capacity Model/Quantity P04~P96/1.0~24.0

Sound Pressure Levels dB(A) 56.0/58.5 Sound Power Levels dB(A) 75.0/77.5

FAN4

Type x Quantity Propeller fan x 2 Fan Motor Output kW 0.46+0.46 Airflow Rate CFM 6,700

External Static Pressure In. WG Selectable;

0.00, 0.12, 0.24, 0.32, In. WG;

factory set to 0 In. WG

Compressor Operating Range 15.0% to 100.0% Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Refrigerant Type x Original Charge R410A x 21.0 lbs + 9.0 oz [9.8 kg]

Protection Devices High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) Inverter Circuit (Comp./Fan) Over-current protection

AHRI Ratings (Ducted/Non-ducted)

EER 11.9/12.3

IEER 23.5/26.5

COP 4.04/4.39

CU-2(NEW): TUHYE0964AN41AN

CU-2

PROVIDE EQUIPMENT

PAD 6" ABOVE GRADE

16"Ø OUTSIDE

INLET WITH

GOOSE NECK

AND MESH

SCREEN

GOOSE NECK DETAIL 5

07/21/2025

TO FCU-2 INDOOR

UNIT

GROUND FLOOR

REQUIRED CLEARANCE

FOR CONDENSER

36"

6"6"

12"

EQUIPMENT PAD DETAIL 5

M-1GROUND FLOOR

MECHANICAL PLAN

REFRIGERATION

LINES SHALL BE

RUNNING ALONG SIDE

THE WAL

UPPER FLOOR

SCALE: N.T.S.

MECHANICAL

(EXISTING)

(EXISTING)

Air inletAir outlet

(7/16)(5/8)

5/16)

5/16)

15 10

100(3-15/16)

100x10=1000(3-15/16x10=39-3/8) 50(2)

100(3-15/16)

FCU-2(NEW): TPEFYP072MH140A

36"x14" SUPPLY

AIR DUCT

GENERAL NOTES CONSTRUCTION KEYNOTES

CONTRACTOR TO INSULATE ALL

CONDENSATE PIPING.

ROUTE CONDENSATE PIPING AT MINIMUM

1% SLOPE.

CONTRACTOR TO COORDINATE EQUIPMENT

AND PIPING HEIGHT IN FIELD. ENSURE

CONDENSATE & OVERFLOW PIPING CAN

MAINTAIN MINUMUM SLOPE WITHOUT

OBSTRUCTION OR FALLING BELOW

RESTROOM CEILING HEIGHT. REPORT ANY

DISCREPANCIES TO ARCHTIECT.

ALL DUCT CONSTRUCTION AND SUPPORT

SHALL BE IN CONFORMANCE WITH SMACNA

STANDARDS.

CONTRACTOR SHALL PROVIDE PIPE, DUCT,

EQUIPMENT SUPPORT AND SEISMIC

RESTRAINTS PER SPECIFICATIONS.

CONTRACTOR SHALL VERIFY SIZES AND

FIELD ROUTE REFRIGERANT LINES FROM

CONDENSER TO FAN COIL UNIT.

CONTRACTOR SHALL FIELD VERIFY ALL

EXISTING DIMENTIONS AND CONDITIONS.

1.

2.

3.

4.

5.

6.

7.

CONNECT 3/4"CD WITH TRAP TO

MECHANICAL UNIT. REFER TO MECHANICAL

PLANS FOR EXACT EQUIPMENT LOCATION.

PROVIDE WITH END-OF-LINE CLEANOUT.

CONNECT 3/4"OD TO DRAIN PAN.

ROUTE 3/4"CD DOWN IN WALL TO LAVATORY

TAILPIECE.

3/4"OD TERMINATE DOWN TO 1" BELOW

CEILING WITH ESCUTCHEON. COORDINATE

FINAL LOCATION WITH ARCHITECT.

EXISTING CONDENSATE AND OVERFLOW

DRAIN FROM EXISTING MECHANICAL UNIT

TO REMAIN.

PROVIDE SIDE SHOT SUPPLY GRILLE, 3000

CFM, 900 FPM WITH AIR FLOW VANES TO

DIRECT THE AIR TOWARDS THE HEATED

ELECTRICAL EUIPMENT

PROVIDE RETURN LOUVER, 2250 CFM, 500

FPM.

16"Ø OUTSIDE AIR RISER UP TO THE

GROUND FLOOR, 750 CFM.

FCU-2 16"Ø OUTSIDE

AIR DUCT

GENERAL FEATURES

•Single phase
•Dual set point functionality
•DC Motor
•Static Pressure Features

-- Adjustable up to 1” -- No change in static pressure with voltage change -- Side access control panel

•Flexibility in duct configuration
•Choice of fan speed

GENERAL FEATURES

Joint Adapter (Port Connector)� CMY-R160C-J Drain pump� PAC-KE05DM-F External Heater Adapter� CN24RELAY-KIT-CM3 Filter Box (With 4” MERV 13 filter)� FBH4-4

Capacity* Cooling� 96,000 Btu/h Heating� 108,000 Btu/h

Power Power Source� 208 / 230V, 1-phase, 60 Hz

Power Consumption Cooling� 0.82 kW Heating� 0.82 kW

Current Cooling� 4.89/4.43 A Heating� 4.89/4.43 A Minimum Circuit Ampacity (MCA)� 8.2 A Maximum Overcurrent Protection (MOCP) Fuse� 15 A External Finish� Galvanized-steel Sheet

External Dimensions Inches� 18-9/16 H x 49-1/4 W x 44-1/8 D mm� 470 H x 1,250 W x 1,120D

Net Weight Unit� 221 lbs / 100 kg

Coil Type� Cross Fin � (Aluminum Plate Fin and Copper Tube)

Fan Type x Quantity� Sirocco Fan x 2 Airflow Rate (Low-Mid-High)� 2,048 - 2,507 - 2,966 CFM External Static Pressure� 0.20-0.40-0.60-0.80-1.00 “WG � (External static pressure is factory set to 0.60”WG)

Motor Type� DC Brushless Motor

Refrigerant Piping Dimensions Liquid (High Pressure)� 3/8” / 9.52 mm (Brazed) Gas (Low Pressure)� 7/8” / 22.22 mm (Brazed)

Drainpipe Dimension� O.D. 1-1/4” / 32 mm

Sound Pressure Levels (Low-Mid-High) Low-Mid-High� 39 - 42 - 46 dB(A)

REFRIGERATION LINE SIZE

PER MANUFACTURER

RECOMENDATION

FLEXIBLE

CONNECTION

FLEXIBLE

CONNECTION

RETURN PLENUM

AND FILTER BOX

MV

DUCT HANGER DETAIL

DUCT THROUGH DETAIL PIPING SUPPORT DETAIL

2 3

TO OUTDOOR

UNIT CU-2

CD

OD

3/4"CD

3/4"OD

1%

1%1

CO

01/28/2025

M-2

UPPER FLOOR

MECHANICAL PLAN

OS

OS

a,b

OS

DL

6-30-26

08/08/2025

SINGLE LINE DIAGRAM KEY NOTES:

SINGLE LINE DIAGRAM

SCALE: N.T.S.

SITE PLAN

SCALE: N.T.S.

UPPER FLOOR

SCALE: N.T.S.

PLAN KEY NOTE/S:

TOP FLOOR

SCALE: N.T.S.

PLAN KEY NOTE/S:

Sheets and Views
240020 - City of Santa Monica Sewer_ELEC-E-2
240020 - City of Santa Monica Sewer_ELEC-E-3
240020 - City of Santa Monica Sewer_ELEC-E-4
240020 - City of Santa Monica Sewer_ELEC-E-5