Construction Services for MPD Compartmented Access Area – Architectural Drawings and Specifications
This file comprises architectural and engineering drawings and specifications issued by the District of Columbia Department of General Services for construction of a compartmented access area (CAA) for the Metropolitan Police Department (MPD) at the Marion S. Barry, Jr. Building located at 441 4th Street NW, Washington, DC 20001. The project scope includes the buildout of approximately 422 square feet of existing office shell space on the 6th floor into a secure conference room space. Construction work encompasses interior partitioning, flooring (resilient and carpet materials), ceiling systems, wall finishes (gypsum board with acoustic treatments), door and hardware installation, mechanical systems (HVAC with variable air volume terminal units and diffusers), electrical systems (lighting, power distribution, emergency systems), telecommunications cabling (Category 6A copper cabling in conduit), fire alarm systems, and specialized radiofrequency and electromagnetic (RFI/EM) shielding to create a secured enclosure. The construction documents are issued for permit and include detailed floor plans, reflected ceiling plans, enlarged details, HVAC plans with terminal unit schedules, electrical symbols and notes, and comprehensive specifications across all construction trades. The project incorporates security access controls with card readers and electronic locking hardware, asbestos and PCB-free materials compliance, and adherence to the 2017 District of Columbia Building Code based on the 2015 International Building Code.
The specifications establish requirements for material quality, workmanship standards, and installation in accordance with industry standards including ASHRAE, NFPA, IEEE, TIA, BICSI, and SMACNA guidelines. Key material specifications include non-fire-rated wood doors with premium-grade construction, hollow metal frames and doors for fire-rated openings, acoustic ceiling tiles and panels, resilient flooring with rubber base, carpet tiles with adhesive systems, gypsum board assemblies with metal framing, solid surface countertops, architectural woodwork to AWI standards, interior and exterior painting with low-VOC finishes, fire extinguisher cabinets, and specialized shielding materials (radiant barrier sheet with aluminum surfaces). The project mandates contractor-furnished attic stock of finish materials, comprehensive shop drawing submittals with testing and certification for cabling systems, mock-ups for shielding installations, and field testing of electromagnetic shielding per IEEE 299 standards. All work must comply with AIA Document A201-2017 General Conditions, coordinate with owner-furnished and installed items (furniture and equipment), maintain existing building systems operability during construction, and achieve final punch-list completion within two weeks of notification. The specifications require one-year manufacturer warranties on doors, five-year warranties on acoustic ceilings and carpet tiles, and contractor guarantees for one year after final acceptance.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DALY SWING SPACE TO OJS
MPD CONFERENCE ROOM
441 4TH STREET NW
WASHINGTON, DC 20001
ISSUED FOR PERMIT | 06/06/2025
GENERAL NOTES
A. GENERAL NOTES APPLY TO ALL SHEETS.
B. DIMENSIONS ARE ACTUAL AND ARE TO FACE OF WALLS, FACE
OF CONCRETE WALLS, FACE OF CMU WALLS, FACE OF FRAMES,
OR CENTERLINE OF COLUMNS, UNLESS NOTED OTHERWISE.
C. THE OWNER SHALL FURNISH AND INSTALL THE FOLLOWING
ITEMS: 1.FURNITURE, 2. EQUIPMENT, UNO.
D. CONTRACTOR TO INCLUDE ALL OWNER-FURNISHED AND
INSTALLED ITEMS AND OWNER-FURNISHED AND CONTRACTOR-
INSTALLED ITEMS IN THE CONSTRUCTION SCHEDULE, AND
SHALL COORDINATE WITH THE OWNER TO ACCOMMODATE
THESE ITEMS.
E. COORDINATE ALL MECHANICAL CHASE SIZES WITH THE
MECHANICAL CONTRACTOR.
F. SEE SHEET CP1.6 FOR LOCATION OF WALLS OF FIRE-
RESISTANCE-RATED CONSTRUCTION. ALL WALLS OF FIRE-
RESISTANCE-RATED CONSTRUCTION SHALL EXTEND TO
UNDERSIDE OF FLOOR OR ROOF DECK ABOVE.
G. ALL PENETRATIONS THROUGH WALLS SHALL BE SEALED WITH
PENETRATION FIRE STOPPING MATERIAL AS REQUIRED TO
ACHIEVE THE RESPECTIVE FIRE-RESISTANCE RATING AND
SMOKE STOPPAGE. SEE SPECIFICATION SECTION 078413.
H. COORDINATE WITH MECHANICAL AND ELECTRICAL
CONTRACTORS THE SIZE AND LOCATION OF EQUIPMENT PADS
SHOWN ON PLANS.
I. FIRE-RESISTANCE-RATED ENCLOSURES AROUND ALL STEEL
COLUMNS SHALL BE CONTINUOUS FROM FLOOR TO UNDERSIDE
OF FLOOR OR ROOF DECK ABOVE FOR EACH LEVEL.
J. CONSTRUCTION DOCUMENTS ARE COMPLEMENTARY. SEE
DRAWING FOR QUANTITIES AND LOCATION OF WORK. SEE
SPECIFICATIONS FOR QUALITIES AND CONDITIONS OF WORK.
K. WORK: ALL ASPECTS OF THE WORK AND ITEMS NOT
SPECIFICALLY MENTIONED, BUT NECESSARY TO MAKE A
COMPLETE WORKING INSTALLATION, SHALL BE INCLUDED AND
INDICATED IN THE CONTRACTOR'S BID.
L. GENERAL SHEET NOTES ONLY APPLY TO PARTICULAR
DRAWING OR SERIES OF DRAWINGS.
M. NO ASBESTOS OR PCB CONTAINING MATERIALS SHALL BE USED
ON THIS PROJECT.
N. DO NOT SCALE DRAWINGS. DIMENSIONS NOTED PREVAIL.
NOTIFY ARCHITECT IN CASE OF DISCREPANCY.
O. HORIZONTAL AND VERTICAL DIMENSIONS ARE MINIMUM
DIMENSIONS. CLEARANCES ARE GIVEN TO FINISH SURFACES.
GC TO VERIFY ALL CLEARANCES. NOTIFY ARCHITECT IN CASE
OF DISCREPANCY.
GENERAL SYMBOLS
SIM
ROOM NAME
XXX-XX
DETAIL NUMBER
SHEET NUMBER
CROSS REFERENCE
WALL SECTION
SIMILAR OR TYPICAL
REFERENCE
DETAIL REFERENCE
BUILDING SECTION
SHEET NOTE
COLUMN GRID LINE
ROOM NUMBER/NAME
REVISION NUMBER
EARTH
GRAVEL
SAND
CONCRETE
PRECAST CONCRETE
STEEL
STONE
CONCRETE MASONRY UNIT
BRICK VENEER
LEVEL XX
XXX'-XX"
LEVEL ELEVATION
GYM FLOOR
WOOD
(CONTINUOUS BLOCKING)
WOOD
(NON-CONTINUOUS BLOCKING)
WOOD (TRIM/FINISH)
GLASS
SHINGLES
PLYWOOD (LARGE SCALE)
GYPSUM WALL BOARD
BLANKET INSULATION
RIGID INSULATION
SPRAY FOAM INSULATION
MINERAL WOOL INSULATION
PROTECTION BOARD
CARPET (LARGE SCALE)
ACOUSTIC TILE (LARGE SCALE)
TILE (LARGE SCALE)
REFERENCE KEYNOTE
XX A4.XX BUILDING ELEVATION
A12.X
XX
XX XX
XX
INTERIOR ELEVATION
100'-0"
TYP FF EL=
100'-0"
FINISH FLOOR
ELEVATION
SPOT ELEVATION
X
BUILDING CODES:
• 2017 DISTRICT OF COLUMBIA BUILDING CODE (2015 ICC
INTERNATIONAL BUILDING CODE)
• 2017 DISTRICT OF COLUMBIA ELECTRICAL (2014 NFPA NATIONAL
ELECTRIC CODE)
• 2017 DISTRICT OF COLUMBIA FUEL GAS CODE (2015 ICC
INTERNATIONAL FUEL GAS CODE)
• 2017 DISTRICT OF COLUMBIA MECHANICAL CODE (2015 ICC
INTERNATIONAL MECHANICAL CODE)
• 2017 DISTRICT OF COLUMBIA PLUMBING CODE (2015 ICC
INTERNATIONAL PLUMBING CODE)
• 2017 DISTRICT OF COLUMBIA FIRE CODE (2015 ICC
INTERNATIONAL FIRE CODE)
• 2017 DISTRICT OF COLUMBIA ENERGY CONSERVATION CODE
(2013 ENERGY STANDARD FOR BUILDINGS EXCEPT LOW-RISE
RESIDENTIAL BUILDINGS (ANSI/ ASHRAE/ IES 90.1-2013))
• 2017 DISTRICT OF COLUMBIA EXISTING BUILDING CODE (2015 ICC
INTERNATIONAL EXISTING BUILDING CODE)
• 2017 DISTRICT OF COLUMBIA GREEN CONSTRUCTION CODE (2012
ICC INTERNATIONAL GREEN CONSTRUCTION CODE)
• DISTRICT OF COLUMBIA CONSTRUCTION CODES SUPPLEMENT
OF 2017, TITLE 12 DCMR
CODE REFERENCES
ACCESSIBILITY:
• ICC A117.1-2009, ACCESSIBLE AND USABLE BUILDINGS AND
FACILITIES
CODE INFORMATION
SEE SHEET CP1.6
AREA MAP
ARCHITECT:
DLR GROUP
PREPARED BY:
1422 Euclid Avenue, Suite 300 Cleveland, Ohio 44115-1407 216.522.1350
MEP Engineers:
DLR GROUP
1422 Euclid Avenue, Suite 300 Cleveland, Ohio 44115-1407 216.522.1350
IT/ Security:
DLR GROUP
1422 Euclid Avenue, Suite 300 Cleveland, Ohio 44115-1407 216.522.1350
PROJECT DESCRIPTION
BUILDOUT OF APPROXIMATELY 422 SF OF EXISTING OFFICE SHELL
SPACE ON THE 6TH FLOOR OF ONE JUDICIARY SQUARE INTO
CONFERENCE SPACE FOR THE METROPOLITAN POLICE
DEPARTMENT.
PROJECT SCOPE AREA
DEFERRED SUBMITTALS
• FIRE SPRINKLERS
• ADDRESSIBLE FIRE ALARM SYSTEM
D
L R
G ro u p
REVISIONS
A B C D E F
A P
P R
O V
A L
/2
/2
:3
:5
P
M
A u to d e s k D o c s /5
-2
-0
M
P D
D a ly
/5 -2
-0
M P
D D a ly
-O J S
-C A
A A
R
.r v t
55-21101-00
06/06/2025
D a ly B u ild in g
S w in g t o
O J S
ISSUED FOR
PERMIT
COVER SHEET
G0.1 th S tr e e t N
W
M P
D C o n fe re n c e
R o o m
ARCHITECTURAL
A0.1 GENERAL NOTES, ARCHITECTURAL SYMBOLS & ABBREVIATIONS
A0.4 SPECIFICATIONS
A0.5 SPECIFICATIONS
A0.6 SPECIFICATIONS
A0.7 SPECIFICATIONS
A1.6 FLOOR PLAN, RCP, & DETAILS
GENERAL
G0.1 COVER SHEET
MECHANICAL
M1.6 LEVEL 06 - HVAC PLAN
ELECTRICAL
E0.1 ELECTRICAL SYMBOLS, ABBREVIATIONS & NOTES
E1.6 CONFERENCE AREA FLOOR PLANS
E5.1 ELECTRICAL DIAGRAMS
E6.1 ELECTRICAL DETAILS
# NUMBER
& AND
@ AT
ADA AMERICANS WITH DISABILITY ACT
ADDN ADDITION OR ADDITIONAL
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
ALT ALTERNATE
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APPROX APPROXIMATE
ARCH ARCHITECTURAL
BLDG BUILDING
BSMT BASEMENT
CL CENTER LINE
CLG CEILING
CM CENTIMETER
CONC CONCRETE
CONN(S) CONNECTION(S)
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACT(OR)
CTR CENTER
D DEPTH
DEG DEGREE
DEMO DEMOLISH OR DEMOLITION
DIA DIAMETER
DIM DIMENSION
DIV SPECIFICATION DIVISION
DN DOWN
DTL DETAIL
DWG(S) DRAWING(S)
E EAST
EA EACH
EC ELECTRICAL CONTRACTOR
EL ELEVATION
ELEC ELECTRICAL
ENG ENGINEER
EQ EQUAL
EQUIP EQUIPMENT
EQUIV EQUIVALENT
EXST EXISTING
EXT EXTERIOR
FIN FINISHED
FL FLOOR
FT FEET
FUT FUTURE
GC GENERAL CONTRACTOR
GOVT GOVERNMENT
H HEIGHT
HORIZ HORIZONTAL
HT HEIGHT
i.e. THAT IS
CODE
CP1.6 LEVEL 06 - CODE PLAN
GENERAL ABBREVIATIONS
DRAWING INDEX
IBC INTERNATIONAL BUILDING CODE
IN INCH
INT INTERIOR
LB(S) POUND(S)
M METER
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MECH MECHANICAL
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MM MILLIMETER
N NORTH
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OC ON CENTER
OPP OPPOSITE
OVHD OVERHEAD
PAR PARALLEL
PENT PENTHOUSE
PLYWD PLYWOOD
QTY QUANTITY
REQ(D) REQUIRE(D)
REV REVISION(S)
RM ROOM
RND ROUND
S SOUTH
SCHED SCHEDULE
SECT SECTION
SHT SHEET
SIM SIMILAR
SPEC SPECIFICATION(S)
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SYM SYMETRICAL
TEMP TEMPORARY
TYP TYPICAL
UNEX UNEXCAVATED
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
W WEST
W/ WITH
W/O WITHOUT
N
6TH FLOOR
OCCUPANCY FUNCTION OF SPACE AREA
A ASSEMBLY WITHOUT FIXED SEATS -
UNCONCENTRATED (TABLES & CHAIRS)
422 SF
Grand total: 1 422 SF
DLR Group 6.6.2025
UP
UP
UP
UP
UP UP
UP
UP
O N M L K J H G F E D C B A
4671 SF
BUSINESS
261 SF
MECH
103 SF
TELE
1305 SF
MECH/ ELEC
303 SF
MECH/ ELEC
104 SF
TELE
249 SF
MECH
5694 SF
ASSEMBLY
527 SF
ASSEMBLY
527 SF
ASSEMBLY
633 SF
ASSEMBLY
740 SF
ASSEMBLY
277 SF
ASSEMBLY
398 SF
ASSEMBLY
360 SF
ASSEMBLY
1811 SF
BUSINESS
1549 SF
BUSINESS
4473 SF
BUSINESS
3684 SF
BUSINESS
252 SF
ASSEMBLY
116 SF
BUSINESS
385 SF
A/V
585 SF
ASSEMBLY
516 SF
ASSEMBLY
295 SF
STORAGE
712 SF
MECH/ ELEC
219 SF
STORAGE
9548 SF
CORE & CIRCULATION
447 SF
LOCKER ROOMS
55 SF
STORAGE
4244 SF
BUSINESS
380 SF
ASSEMBLY
108 SF
ASSEMBLY
202 SF
IT
5644 SF
BUSINESS
2438 SF
BUSINESS
2243 SF
BUSINESS
287 SF
ASSEMBLY
484 SF
ASSEMBLY
110 SF
ASSEMBLY
345 SF
ASSEMBLY
109 SF
ASSEMBLY
468 SF
ASSEMBLY
117 SF
ASSEMBLY
145 SF
BUSINESS
72 SF
ASSEMBLY
PROJECT SCOPE AREA
422 SF
ASSEMBLY
SYMBOL LEGEND
WALL SEPARATION LEGEND
- OCCUPANCY LOAD
- ACCESSORY USE AREA
(OCCUPANCY LOAD IS NOT INCLUDED IN LOADS BEYOND THIS ROOM)
- COMBINED OCCUPANT LOAD AT A GIVEN DOOR OR STAIR
- TOTAL EXIT CAPACITY OF DOOR OR STAIR
(THE CAPACITY OF DOORS ARE DETERMINED AS FOLLOWS:
CLEAR OPENING WIDTH IN INCHES DIVIDED BY 0.2
THE CAPACITY OF STAIRS ARE DETERMINED AS FOLLOWS
WIDTH IN INCHES DIVIDED BY 0.3)
- COMBINED OCCUPANT LOAD AT A GIVEN DOOR. (SUM OF THESE EQUALS TOTAL
OCCUPANT LOAD)
- TOTAL EXIT CAPACITY OF DOOR
(THE CAPACITY OF DOORS ARE DETERMINED AS FOLLOWS:
CLEAR OPENING WIDTH IN INCHES DIVIDED BY 0.2)
PD
XX MIN
- PANIC DEVICE
- DOOR FIRE RATING
WALL HOURLY RATING
0 = 0 HOUR
1/2 = 1/2 HOUR
1 = 1 HOUR
2 = 2 HOUR
3 = 3 HOUR
SP = SMOKE PARTITION
SW = SMOKE WALL
WALL FIRE RATING TYPE
C = CORRIDOR
EW = EXTERIOR WALL
FB = FIRE BARRIER
FP = FIRE PARTITION
FSB= FIRE/SMOKE BARRIER
FW = FIRE WALL
HX = HORIZONTAL EXIT
SB = SMOKE BARRIER
VS = VERTICAL SHAFT
VX = VERTICAL EXIT
XP = EXIT PASSAGEWAY
-COMMON PATH OF TRAVEL POINT OF DECISION
-PATH OF TRAVEL (COMMON PATH OF TRAVEL - MINIMUM TRAVEL DISTANCE)
STARTING POINT OF PATH ORIGIN
-OCCUPANT EGRESS PATH OF TRAVEL
OCCUPANT LOAD ALONG PATH (NUMBER INCREASE TOWARDS EXIT)
DIRECTION OF TRAVEL
OCCUPANCY = UNOCCUPIED
OCCUPANCY = "S-1" (STORAGE)
O.L.F. = 1:300 SF
SHADED AREA SHOWN FOR REFERENCE
PURPOSES ONLY. NO NEW SCOPE OF
WORK, CHANGE IN USE OR OCCUPANCY,
AND EGRESS IN THIS AREA
OCCUPANCY = "A" (ACCESSORY)
O.L.F. = 1:15 SF, UNO
OCCUPANCY = "B" (BUSINESS)
O.L.F. = 1:100 SF
FEC-# - FIRE EXTINGUISHER LOCATION/ TYPE
OCCUPANCY
FHC - FIRE HOSE CABINET LOCATION
FEC-EX
FEC-1
FEC-2
EXISTING FEC
NEW SEMI-RECESSED FEC,
10LB 2-A TYPE FE
NEW SURFACE-MOUNTED
FEC, 10LB 80-B TYPE FE
OCCUPANT LOAD SIGNAGE, REF #4/A0.22
TACTILE EXIT SIGN, REF #12/A0.22
NO SMOKING SIGN, REF #9/A0.22
OLS
RIS-E
NSS
OCCUPANCY = LOCKER ROOMS
O.L.F. = 1:50 SF
SIGNAGE
OCCUPANCY = "H-3" (HAZ. STORAGE)
O.L.F. = 1:300 SF
D
L R
G ro u p
REVISIONS
A P
P R
O V
A L
/1
/2
:3
:0
P
M
A u to d e s k D o c s /5
-2
-0
M
P D
D a ly
/5 -2
-0
M P
D D a ly
-O J S
-C A
A A
R
.r v t
55-21101-00
06/06/2025
D a ly B u ild in g
S w in g t o
O J S
ISSUED FOR
PERMIT
LEVEL 06 - CODE
PLAN
CP1.6
th S tr e e t N
W
M P
D C o n fe re n c e
R o o m
SCALE: 1/16" = 1'-0"CP1.6
1 6TH FLOOR LIFE SAFETY PLAN
AREA SCHEDULE - 6TH FLOOR
Number Name Area Function of Space Occupancy
Type Occ Load
Factor Occupant
Load
6.00 CORE & CIRCULATION 9548 SF UNOCCUPIED
6.01 BUSINESS 4244 SF BUSINESS AREAS B 100 65
6.02 LOCKER ROOMS 447 SF LOCKER ROOMS 50 9
6.03 STORAGE 55 SF ACCESSORY STORAGE, MECH EQUIP ROOMS S-1 300 1
6.04 ASSEMBLY 380 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 26
6.05 ASSEMBLY 252 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 34
6.06 BUSINESS 4671 SF BUSINESS AREAS B 100 71
6.07 ASSEMBLY 360 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 12
6.08 STORAGE 295 SF ACCESSORY STORAGE, MECH EQUIP ROOMS S-1 300 1
6.09 ASSEMBLY 527 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 25
6.10 ASSEMBLY 527 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 25
6.11 ASSEMBLY 5694 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 85
6.12 STORAGE 219 SF ACCESSORY STORAGE, MECH EQUIP ROOMS S-1 300 1
6.13 IT 202 SF ACCESSORY STORAGE, MECH EQUIP ROOMS S-1 300 1
6.14 MECH/ ELEC 712 SF ACCESSORY STORAGE, MECH EQUIP ROOMS S-1 300 4
6.15 A/V 385 SF ACCESSORY STORAGE, MECH EQUIP ROOMS S-1 300 2
6.16 ASSEMBLY 585 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 39
6.17 ASSEMBLY 422 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 10
6.18 ASSEMBLY 633 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 25
6.19 ASSEMBLY 108 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 10
6.20 ASSEMBLY 516 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 35
6.21 BUSINESS 116 SF BUSINESS AREAS B 100 2
6.22 BUSINESS 1549 SF BUSINESS AREAS B 100 16
6.23 ASSEMBLY 398 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 10
6.24 BUSINESS 1811 SF BUSINESS AREAS B 100 19
6.25 ASSEMBLY 277 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 10
6.26 BUSINESS 3684 SF BUSINESS AREAS B 100 38
6.27 ASSEMBLY 740 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 25
6.28 BUSINESS 4473 SF BUSINESS AREAS B 100 45
6.29 BUSINESS 5644 SF BUSINESS AREAS B 100 57
6.30 BUSINESS 2438 SF BUSINESS AREAS B 100 25
6.31 BUSINESS 2243 SF BUSINESS AREAS B 100 23
6.32 ASSEMBLY 287 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 20
6.33 ASSEMBLY 484 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 33
6.34 ASSEMBLY 110 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 8
6.35 ASSEMBLY 156 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 11
6.36 ASSEMBLY 345 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 23
6.37 ASSEMBLY 109 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 8
6.38 ASSEMBLY 468 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 32
6.39 ASSEMBLY 117 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 8
6.51 MECH 249 SF EXISTING (ACCESSORY STORAGE, MECH EQUIP ROOMS) S 300 1
6.52 TELE 104 SF EXISTING (ACCESSORY STORAGE, MECH EQUIP ROOMS) S 300 1
6.53 MECH/ ELEC 303 SF EXISTING (ACCESSORY STORAGE, MECH EQUIP ROOMS) S 300 2
6.54 MECH/ ELEC 305 SF EXISTING (ACCESSORY STORAGE, MECH EQUIP ROOMS) S 300 2
6.55 TELE 103 SF EXISTING (ACCESSORY STORAGE, MECH EQUIP ROOMS) S 300 1
6.56 MECH 261 SF EXISTING (ACCESSORY STORAGE, MECH EQUIP ROOMS) S 300 1
P2.03 BUSINESS 145 SF BUSINESS AREAS B 100 2
P2.04 ASSEMBLY 72 SF ASSEMBLY WITHOUT FIXED SEATS - UNCONCENTRATED (TABLES & CHAIRS) A 15 34
Grand total: 48 57775 SF 938
FIRE EXTINGUISHERS (CLASS B) 50' MAXIMUM TRAVEL DISTANCE TO EXTINGUISHER DCBC SECTION 906 EXISTING FIRE EXTINGUISHERS TO REMAIN, SEE LIFE SAFETY PLANS FOR EXISTING & NEW FIRE EXTINGUISHER LOCATIONS
FIRE EXTINGUISHERS (CLASS A) 75' MAXIMUM TRAVEL DISTANCE TO EXTINGUISHER DCBC SECTION 906 EXISTING FIRE EXTINGUISHERS TO REMAIN, SEE LIFE SAFETY PLANS FOR EXISTING & NEW FIRE EXTINGUISHER LOCATIONS
FIRE SUPPRESSION: FULLY SPRINKLERED DCBC (MULTIPLE)
FIRE PROTECTION SYSTEM INFO: VALUE: CODE REFERENCE: COMMENTS:
RAMPED AISLES - A USE:
0.3" PER OCCUPANT FOR RISERS < 7", 0.2" PER OCCUPANT FOR RAMPS < 1:12
SLOPE
DCBC 1029 SMOKE-PROTECTED ASSEMBLY SEATING IS NOT PROVIDED
DOOR EGRESS WIDTH: 0.15" PER OCCUPANT, 32" MIN DCBC 1005.3.2, 1010.1.1
RAMP EGRESS WIDTH: 0.15" PER OCCUPANT, 44" MIN (36" MIN FOR OCC LOAD < 50) DCBC 1005.3.2, 1012.5.1
CORRIDOR EGRESS WIDTH: 0.15" PER OCCUPANT, 44" MIN (36" MIN FOR OCC LOAD < 50) DCBC 1005.3.2, TABLE 1020.2
STAIR EGRESS WIDTH: 0.2" PER OCCUPANT, 44" MIN (36" MIN FOR OCC LOAD < 50) DCBC 1005.3.1, 1011.2
EGRESS WIDTHS: VALUE: CODE REFERENCE: COMMENTS:
NUMBER OF REQUIRED EXITS DCBC 1006.3
MAX DEAD END CORRIDOR - A-3 USE 20' DCBC 1020.4
MAX DEAD END CORRIDOR - B USE: 50' DCBC 1020.4
MIN EXIT STAIRWAY ACCESS SEPARATION:
30' OR NOT LESS THAN 1/4 LENGTH OF MAX OVERALL DIAGONAL DIMENSION
OF BUILDING OR AREA
DCBC 403.5.1
MIN. EXIT ACCESS SEPARATION (OTHER THAN EXIT STAIRWAYS): 1/4 LENGTH OF MAX OVERALL DIAGONAL DIMENSION OF AREA DCBC 1007.1.1 USE EXCEPTION 2.
MAX COMMON PATH OF TRAVEL - A USE: 75' DCBC TABLE 1006.2.1
MAX COMMON PATH OF TRAVEL - B & S USE: 100' DCBC TABLE 1006.2.1
EXIT ACCESS TRAVEL DISTANCE - S-2 USE: 400' DCBC TABLE 1017.2
EXIT ACCESS TRAVEL DISTANCE - A USE: 250' DCBC TABLE 1017.2
EXIT ACCESS TRAVEL DISTANCE - B USE: 300' DCBC TABLE 1017.2
EGRESS DISTANCES: VALUE: CODE REFERENCE: COMMENTS:
FORCE FOR PUSHING/PULLING OPEN INTERIOR SWINGING FIRE
DOOR:
< 15 LBS DCBC 1010.1.3 LATCH TO RELEASE W/ 15 LB FORCE, DOOR TO BE SET IN MOTION W/ 30 LB FORCE
FORCE FOR PUSHING/PULLING OPEN INTERIOR SLIDING & FOLDING
DOORS:
< 15 LBS DCBC 1010.1.3 LATCH TO RELEASE W/ 15 LB FORCE, DOOR TO BE SET IN MOTION W/ 30 LB FORCE
FORCE FOR PUSHING/PULLING OPEN INTERIOR SWINGING DOORS
(OTHER THAN FIRE DOORS)
< 5 LBS DCBC 1010.1.3
AREAS OF REFUGE REQUIRED: NO DCBC 1009.3 USE EXCEPTION 5.
GENERAL EGRESS INFORMATION: VALUE: CODE REFERENCE: COMMENTS:
DECORATIVE MATERIALS & TRIM
NFPA 701, TEST 1 OR 2, OR 100 kW MAX PER NFPA 289 (SUSPENDED
DECORATIVE MATERIALS); CLASS C (TRIM); CLASS II (WALL BASE)
DCBC 806
FLOOR FINISH CPSC 16 CFR PART 1630 OR ASTM D2859 COMPLIANT DCBC 804.4.2 USE EXCEPTION
INTERIOR WALL & CEILING FINISH - A-3
CLASS B (CORRIDORS/ EXIT ACCESS ENCLOSURES), CLASS C (ROOMS/
ENCLOSED SPACES)
DCBC TABLE 803.11
INTERIOR WALL & CEILING FINISH - B
CLASS C (CORRIDORS/ EXIT ACCESS ENCLOSURES & ROOMS/ ENCLOSED
SPACES)
DCBC TABLE 803.11
INTERIOR FINISHES: VALUE: CODE REFERENCE: COMMENTS:
ROOF CONSTRUCTION & SECONDARY MEMBERS: 1-HR DCBC TABLE 601 TAKES 403.2.1.1 RATING REDUCTION
FLOOR CONSTRUCTION & SECONDARY MEMBERS: 2-HR DCBC TABLE 601
NONBEARING WALLS & PARTITIONS (INTERIOR): 0-HR DCBC TABLE 601
BEARING WALLS (EXTERIOR & INTERIOR): 2-HR DCBC TABLE 601 TAKES 403.2.1.1 RATING REDUCTION
PRIMARY STRUCTURAL FRAME (ROOF) 2-HR DCBC TABLE 601 TAKES 403.2.1.1 RATING REDUCTION
PRIMARY STRUCTURAL FRAME (COLUMNS) 3-HR DCBC TABLE 601
PRIMARY STRUCTURAL FRAME (TYPICAL) 2-HR DCBC TABLE 601 TAKES 403.2.1.1 RATING REDUCTION
BUILDING COMPONENT RATINGS: VALUE: CODE REFERENCE: COMMENTS:
WALLS AROUND FUEL TANK STORAGE ROOM 3-HR FIRE BARRIERS
DCBC 415.9.1, DCBC TABLE
508.4
PER NFPA 37, ROOM TO BE CONSTRUCTED OF WALLS, FLOOR, & CEILING HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN 3 HOURS, DOOR TO BE SELF-CLOSING 3-HR RATED, AND ROOM TO BE PROVIDED W/ SPILL CONTAINMENT W/ CAPACITY EQUAL TO THAT
OF LARGEST TANK
WALLS AROUND FIRE PUMP ROOM: 2-HR FIRE BARRIERS DCBC 913.2.1
CORRIDOR WALLS FIRE-RESISTANCE RATING - A & B: 0-HR RATED DCBC TABLE 1020.1
WALLS AROUND ELEVATOR LOBBY (FIRE SERVICE ACCESS): N/A DCBC 403.6.1 OCCUPIED FLOOR LEVEL > 120' ABOVE LOWEST LEVEL OF FIRE DEPT VEHICLE ACCESS
WALLS AROUND ELEVATOR LOBBY (PASSENGER ELEVATORS): N/A DCBC 3006.2 BUILDING PROTECTED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM
WALLS AROUND MISCELLANEOUS SHAFTS: 1-HR FIRE BARRIERS DCBC 403.2.1.2, 713.4 AUTOMATIC SPRINKLERS AT TOP & AT ALTERNATE FLOOR LEVELS. OTHERWISE, 2-HR FIRE BARRIER
WALLS AROUND ELEVATOR SHAFT: 2-HR FIRE BARRIERS DCBC 713.4, 3002
WALLS AROUND EXIT STAIRWAYS: 2-HR FIRE BARRIERS & SMOKEPROOF ENCLOSURE
DCBC 403.5.4, 707.3, 909.20,
1023.11
WALL RATINGS: VALUE: CODE REFERENCE: COMMENTS:
REDUCTION IN MIN. FIRE RESISTANCE RATING OF SHAFTS: NO DCBC 403.2.1.2
REDUCTION IN MIN. FIRE RESISTANCE RATING OF BUILDING
ELEMENTS:
YES DCBC 403.2.1.1
BUILDING IS NOT GREATER THAN 420' AND EXISTING SPRINKLER CONTROL VALVES ARE EQUIPPED W/ SUPERVISORY INITIATING
DEVICES & WATER-FLOW INITIATING DEVICES FOR EACH FLOOR
MOTOR-VEHICLE-RELATED OCCUPANCIES: YES DCBC 406 EXISTING ON LEVELS P1 AND P2
UNDERGROUND BUILDING: NO DCBC 405 EXCEPTION FOR PARKING GARAGES PROVIDED W/ AUTOMATIC SPRINKLER SYSTEMS
ATRIUM: NO DCBC 404
HIGH-RISE BUILDING YES DCBC 403 EXISTING BUILDING HAS OCCUPIED FLOORS > 75' ABOVE LOWEST LEVEL OF FIRE DEPT VEHICLE ACCESS
AREA: UNLIMITED (ACTUAL 592,183 SF) DCBC TABLE 506.2
HEIGHT: UNLIMITED (ACTUAL 125'-10") DCBC TABLE 504.3
STORIES: UNLIMITED (ACTUAL 11) DCBC TABLE 504.4
CONSTRUCTION TYPE: IA DCBC TABLE 601 EXISTING FLOORS, COLUMNS AND BEAMS ARE PROTECTED BY A CONCRETE ASSEMBLY PROVIDING A 3-HOUR FIRE RATING.
H-3: FUEL STORAGE TANK ROOM DCBC CHAPTER 3 FUEL TANK STORAGE ROOM TO BE SEPARATED W/ 3-HR FIRE BARRIERS PER NFPA 37
S-2: PARKING GARAGE, ENCLOSED DCBC CHAPTER 3
S-1: STORAGE DCBC CHAPTER 3 ACCESSORY STORAGE
A-3: JOCC (FLOOR 6) DCBC CHAPTER 3 FLOOR 6 IS MIXED USE AND NONSEPARATED PER DCBC 508.3
USE GROUPS: B: BUSINESS (FLOORS C1, 5, 6, 7, 11) DCBC CHAPTER 3
MIXED USE:
GENERAL BUILDING INFO: VALUE: CODE REFERENCE: COMMENTS:
ARCHITECTURAL SYMBOLS
XX/ A11.X
XX. X. XX
CASEWORK ELEVATION
DOOR NUMBER
EXTERIOR WINDOW /
CURTAIN WALL NUMBER
WALL TYPE
A110
A124
XX/ A11.X XXXX
XX
XX
APC-1
9' - 0"
CEILING TYPE
CEILING HEIGHT
CEILING TYPE
INTERIOR WINDOW
NUMBER
GENERAL ARCHITECTURAL NOTES
1. PARTITION TYPES ARE DESIGNATED ON FLOOR PLANS
THUS: SEE SHEET A1.1 FOR TYPES. ALL INTERIOR
PARTITIONS ARE TYPE SA.3.20 UNLESS NOTED OTHERWISE.
2. ALL MASONRY WALLS AND INTERIOR STUD WALLS SHALL
EXTEND TO UNDERSIDE OF FLOOR OR ROOF DECK ABOVE
UNLESS NOTED OTHERWISE, PER PARTITION TYPE.
3. PROVISIONS ARE MADE AT ALL FULL HEIGHT NON-BEARING
WALLS FOR 1-INCH VERTICAL MOVEMENT OF THE BUILDING
STRUCTURE WITHOUT TRANSFER OF COMPRESSIVE LOADS TO
WALL. FILL IRREGULARITIES BETWEEN TOP OF WALL AND DECK
ABOVE WITH MINERAL WOOL INSULATION OR FIRE STOPPING
MATERIALS AS REQUIRED TO MEET FIRE RATING OF
RESPECTIVE WALLS. SEE DETAILS ON SHEET XX.X.
4. FURNISH AND INSTALL FIRE-TREATED WOOD BLOCKING OR
METAL BACKING PLATE IN METAL STUD PARTITIONS FOR THE
PROPER ANCHORAGE OF ALL WALL ATTACHED ITEMS; I.E.
TOILET ACCESSORIES, CASEWORK, MILLWORK, WALL-
MOUNTED FIXTURES, MARKER BOARDS, TACK BOARDS, DOOR
STOPS, AUDIO VISUAL BRACKETS, AND OTHER WALL ATTACHED
ITEMS.
5. GYPSUM BOARD SURFACES SHALL BE ISOLATED WITH
CONTROL JOINTS WHERE SHOWN ON DRAWINGS AND AS
DESCRIBED IN THE SPECIFICATIONS.
6. "MBD" AND "TBD" INDICATE MARKER BOARDS AND TACK
BOARDS ON PLANS. THE LENGTH PRECEDES THE
DESIGNATION (EXAMPLE 16' MBD). ALL BOARDS ARE 4'-0" TALL.
SEE WALL ELEVATIONS OR SPECIFICATIONS FOR MOUNTING
HEIGHT.
7. EXTEND FURRING CHANNELS AND GYPSUM BOARD UP 4
INCHES ABOVE FINISHED CEILING ON CMU WALLS.
8. SCRIBE GYPSUM WALL BOARD OF WALLS AND PARTITIONS TO
IRREGULARITIES OF DECK ABOVE. SEAL TIGHTLY AROUND ALL
PENETRATIONS.
9. PROVIDE SEISMIC BRACING FOR SUSPENDED CEILINGS OR AS
SHOWN ON THE DRAWINGS.
XX. X. XX
GYPSUM WALL BOARD
METAL FRAMING
SOUND ATTENUATION
BLANKET INSULATION
WHERE OCCURS BY
UNIQUE CONDITION
CHARACTER
T H
K R
O U
G H
GYPSUM WALL BOARD
METAL FRAMING
SOUND ATTENUATION
BLANKET INSULATION
WHERE OCCURS BY
UNIQUE CONDITION
CHARACTER
T H
K R
O U
G H
GYPSUM WALL BOARD
METAL FRAMING
SOUND ATTENUATION
BLANKET INSULATION
WHERE OCCURS BY
UNIQUE CONDITION
CHARACTER
T H
K R
O U
G H
FOIL BARRIER LAYER PER UNIQUE CONDITION ID
GYPSUM WALL BOARD
METAL FRAMING
SOUND ATTENUATION
BLANKET INSULATION
WHERE OCCURS BY
UNIQUE CONDITION
CHARACTER
T H
K R
O U
G H
1/2" PLYWOOD
FOIL BARRIER LAYER PER UNIQUE CONDITION ID
MATERIAL DESCRIPTION
S = STEEL (METAL STUDS)
W = WOOD STUDS
H = SHAFT WALLS
M = MASONRY
C = CONCRETE
RATING / HEIGHT
A = FULL HEIGHT / UNDERSIDE OF STRUCT (NOT RATED)
B = 6" ABOVE CEILING (NOT RATED)
C = UNDERSIDE OF CEILING (NOT RATED)
D = PARTIAL HEIGHT (NOT RATED)
X = VARIABLE HEIGHT (NOT RATED)
S = SMOKE PARTITON (NOT RATED)
0 = 0 HOUR RATED (CORRIDOR)
5 = 0.5 HOUR RATED
1 = 1 HOUR RATED
2 = 2 HOUR RATED
3 = 3 HOUR RATED
4 = 4 HOUR RATED
UNIT WIDTH / CONFIGURATION
F = FURRING STRIPS / CHANNELS
1 = 1 5/8" METAL
2 = 2 1/2" METAL / 1 1/2" WOOD
3 = 3 5/8" METAL
4 = 4" METAL / 3 1/2 WOOD / 3 5/8" CMU
6 = 6" METAL / 5 1/2" WOOD / 5 5/8" CMU / 6" CONC
8 = 8" METAL / 7 1/4" WOOD / 7 5/8" CMU / 8" CONC
10 = 10" CONC
12 = 11 5/8" CMU / 12" CONC
X = NON-STANDARD WIDTH, SEE DETAILS
D = DOUBLE STUD FRAMING
S = STAGGERED STUD FRAMING
GYPSUM WALLBOARD INDICATOR
(NOT INCLUDING SHAFT LINER)
0 = NO GWB
1 = ONE LAYER, TAG SIDE
2 = ONE LAYER, EACH SIDE
3 = TWO LAYERS TAG SIDE, ONE LAYER OTHER
4 = TWO LAYERS, EACH SIDE
5 = TWO LAYERS TAG SIDE, NO GWB OTHER
6 = THREE LAYERS, EACH SIDE
SA.3.10
MATERIAL
RATING / HEIGHT
UNIT WIDTH
GWB INDICATOR
UNIQUE CONDITION
WALL TYPE TAG
PARTITION TYPES
DESCRIPTIONS
UNIQUE CONDITION (SEE SCHEDULE)
(NOT INCLUDING SHAFT LINER)
0 = NO UNIQUE CONDITION
1 = FOIL BARRIER
16 GA. 3-5/8" METAL STUDS 16" O.C.
5/8" GYP. ATTACHED TO EXISTING WALL OR PART OF NEW SA-3-31 PARTITION WHERE OCCURS
SOUND ATTENUATION BATTS IN STUD CAVITY. PROVIDE STRAPPING TO PREVENT INSULATION
FROM SETTLING WITHIN CAVITY. REFER TO WALL TYPE FOR THICKNESS
SCREW STUD FLANGE TO BASE FLANGE. EACH SIDE, EACH STUD.
CONTINUOUS ACOUSTICAL SEALANT
METAL STUD RUNNER ATTACHED TO SUBFLOOR WITH 0.140" DIA POWER DRIVEN PINS @ 24" O.C. AND 6" FROM CORNERS AND DOOR JAMBS, W/ 1 1/4" EMBEDMENT AS PER RAMSET/REDHEAD ICC ESR REPORT #1799 TABLES 1-5 OR EQUAL. METAL STUD RUNNER TO MATCH GAUGE OF METAL STUDS
CONTINUOUS ACOUSTICAL SEALANT BETWEEN METAL STUD RUNNER AND CONCRETE FLOOR
DEEP LEG DEFLECTION TRACK - SECURE TO EXISTING STRUCTURE
CONTINUOUS ACOUSTICAL SEALANT EACH SIDE
(2) LAYERS OF 5/8" TYPE 'X' GYPSUM BOARD INSTALLED VERTICALLY EACH SIDE. ALTERNATE SEAMS.
ATTACH GYPSUM BOARD TO VERTICAL STUDS ONLY; DO NOT ATTACH TO PARTITION HEAD - PAINT AND TEXTURE ENTIRE WALL FROM TRUE FLOOR TO ROOF STRUCTURE. REFER TO WALL TYPE FOR
QUANTITY AND TYPE
FOIL BARRIER BETWEEN PLYWOOD AND GYPSUM BOARD ON CONTROLLED SIDE ONLY. PROVIDE 6" OVERLAP AND FOIL TAPE AT ALL SEAMS AND INTERSECTIONS, TYP. BARRIER MEETS OR EXCEEDS
ASTM E84-09 CLASS 1 / CLASS A
*FOIL SIDE OF WALL TO FACE ROOM INTERIOR UNLESS NOTED OTHERWISE
CONTINUE FOIL ON FLOOR UNDER FLOOR FINISH FOR ENTIRETY OF CONF. SPACE. ADHERE TO CONCRETE
CONTINUOUS ACOUSTICAL SEALANT BETWEEN DEFLECTION TRACK AND EXISTING STRUCTURE
ARDEX FEATHER FINISH OR SIMILAR INSTALLED OVER FOIL, FLOORING TYP.
1/2" FIRE-TREATED PLYWOOD INSTALLED VERTICALLY AFFIXED TO STUDS WITH GLUE AND #10 TAPPING
SCREWS AT 12" O.C.
2" WIDE x 14 GAUGE, COLD FORMED PLATES
@ 16" O.C. ATTTACHED TO DECK FLUTES
TOP OF STEEL DECK
DEFLECTION SLIP TRACK (TYPICAL)
EXISTING OR NEW WALL OR
SUBSTRATE. REFER TO FLOOR PLANS.
2" WIDE x 14 GAUGE, COLD FORMED
PLATES @ 16" O.C. ATTTACHED TO DECK
TOP OF CONC DECK
DEFLECTION SLIP TRACK
(TYPICAL)
DEFLECTION SLIP TRACK (TYPICAL)
U.L. APPROVED 3 1/2" SOUND ATTENUATION
BATT INSULATION
FIRE RATED JOINT SYSTEM MATCHING
HOURLY WALL RATINGS
FINISH FLOOR
REFER TO FINISH
SCHEDULE FOR WALL BASE
EXISTING OR NEW WALL OR
SUBSTRATE. REFER TO FLOOR PLANS.
FINISH FLOOR
REFER TO FINISH SCHEDULE
FOR WALL BASE
4 7/8"
U.L. APPROVED 3 1/2" SOUND
ATTENUATION BATT INSULATION
2 LAYERS OF 5/8" GYP BD EA SIDE
6 1/8"
FINISH FLOOR
REFER TO FINISH SCHEDULE FOR BASE
FIRE RATED JOINT SYSTEM
MATCHING HOURLY WALL RATINGS
D
L R
G ro u p
REVISIONS
A B C D E F
A P
P R
O V
A L
/1
/2
:3
:0
P
M
A u to d e s k D o c s /5
-2
-0
M
P D
D a ly
/5 -2
-0
M P
D D a ly
-O J S
-C A
A A
R
.r v t
55-21101-00
06/06/2025
D a ly B u ild in g
S w in g t o
O J S
ISSUED FOR
PERMIT
GENERAL NOTES,
ARCHITECTURAL
SYMBOLS &
ABBREVIATIONS
A0.1 th S tr e e t N
W
M P
D C o n fe re n c e
R o o m
A/E ARCHITECT/ENGINEER
AB AIR BARRIER
ABS ASBESTOS
ACC ADA ACCESSIBLE
ACR ACRYLIC
ACT ACOUSTIC CEILING TILE
AD ACCESS DOOR
ADJ ADJUSTABLE
ADJT ADJACENT
ADMIN ADMINISTRATION
AEC AUTOMATED EXTERNAL DEFIBRILLATORS
AL ALUMINUM
ALUM ALUMINUM
AP ACCESS PANEL
APC ACOUSTIC PANEL CEILING
ASPH ASPHALT
AUTO AUTOMATIC
AVG AVERAGE
AWP ACOUSTIC WALL PANEL
B.O. BOTTOM OF
BCS BABY CHANGING STATION
BD BOARD
BLK BLOCK
BLKG BLOCKING
BLKHD BULKHEAD
BM(S) BEAM(S)
BOT BOTTOM
BRDG BRIDGING
BRG BEARING
BRKT BRACKET
BT BATHTUB
BTWN BETWEEN
CAB CABINET
CBD CHALKBOARD
CER CERAMIC
CF CUBIC FEET
CFCI CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CFMF COLD-FORMED METAL FRAMING
CG CLEAR FLOAT GLASS
CI CAST IRON
CIG CLEAR INSULATING GLASS
CIP CAST IN PLACE
CJ CONTROL JOINT
CJA CONTROL JOINT ABOVE
CLO CLOSET
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
COM COMMON
COMB COMBINATION
COMM COMMUNICATIONS
COMPR COMPRESSIBLE
CONF CONFERENCE
CONFIG CONFIGURATION
CORR CORRIDOR
CP COVER PLATE
CPT CARPET
CR CHAIR RAIL
CS COUNTERSINK
CSTJ CONSTRUCTION JOINT
CSWK CASEWORK
CT CERAMIC TILE
CTG CLEAR TEMPERED FLOAT GLASS
CTIG CLEAR TEMPERED INSULATING GLASS
CU COPPER
CU COMBINATION UNIT
CV CONDOM VENDOR
CY CUBIC YARD
CYL CYLINDER
DB DECIBEL
DBL DOUBLE
DC DUST COLLECTOR
ARCHITECTURAL ABBREVIATIONS
FINISH SCHEDULE - CFCI
TAG Spec Section DESCRIPTION MANUFACTURER PRODUCT SIZE COLOR/FINISH COMMENTS
081416 FLUSH WOOD DOORS
WD-01 081416 FLUSH WOOD DOORS WOOD DOORS VT INDUSTRIES HERITAGE COLLECTION WHITE OAK CLEAR CL18
095113 ACOUSTICAL PANEL CEILINGS
APC-02 095113 ACOUSTICAL PANEL CEILINGS ACOUSTIC PANEL CEILING ARMSTRONG WORLD
INDUSTRIES
OPTIMA W/ 9/16" SUPRAFINE XL SQUARE TEGULAR 24x24 WHITE (WH)
096500 RESILIENT FLOORING
B-01 096500 RESILIENT FLOORING RESILIENT BASE JOHNSONITE STRAIGHT BASE 6" 23 VAPOR GRAY CG RESILIENT BASE-ROLL GOODS, USE ON ALL WALLS
RF-01 096500 RESILIENT FLOORING RESILIENT FLOORING SHAW CONTRACT SOLITUDE 0648V 5mm 6"x48" NATURAL 48250
096800 CARPETING
CPT-02 096800 CARPETING CARPET TILE SHAW CONTRACT COMPANION TILE 5T352 24x24 INCHES DUO 52597 ASHLAR INSTALLATION
CPT-03 096800 CARPETING CARPET ROLL SHAW CONTRACT DUO 52597 BACK WITH RF FOIL
099000 PAINTING
P-01 099000 PAINTING GENERAL PAINT SHERWIN WILLIAMS LOW VOC, PREMIUM PAINT EXTRA WHITE SW 7006 GENERAL THROUGHOUT
P-06 099000 PAINTING ACCENT PAINT SHERWIN WILLIAMS LOW VOC, PREMIUM PAINT MISTY SW 6232 ACCENT PAINT
P-08 099000 PAINTING EXPOSED CEILING DRYFALL SHERWIN WILLIAMS DRYFALL BLACK MAGIC SW6991, MATTE FINISH EXPOSED CEILING PAINT
FINISH SCHEDULE
PARTITION TYPES
S_-_-1_ NON-RATED STUD PARTITION
MARK ROUGH
THICKNESS
FIRE/SMOKE T.O. WALL
DETAIL
B.O. WALL
DETAIL COMMENTSRATING TESTED ASSEMBLIES
SA 3 10 4 1/4" NR NA 4C/A0.1 5C/A0.1
S_-_-2_ NON-RATED STUD PARTITION
MARK ROUGH
THICKNESS
FIRE/SMOKE T.O. WALL
DETAIL
B.O. WALL
DETAIL COMMENTSRATING TESTED ASSEMBLIES
SA 3 20 4 7/8" NR NA 4D/A0.1 5D/A0.1
S_-_-4_ NON-RATED STUD PARTITION
MARK ROUGH
THICKNESS
FIRE/SMOKE T.O. WALL
DETAIL
B.O. WALL
DETAIL COMMENTSRATING TESTED ASSEMBLIES
SA 3 41 6 1/8" NR NA 4E/A0.1 5E/A0.1
GR GRADE
GRS GALVANIZED RIGID STEEL
GWB GYPSUM WALL BOARD
GYP GYPSUM
HC HOLLOW CORE
HD HAND DRYER
HDF HIGH DENSITY FIBERBOARD
HDR HEADER
HDWD HARDWOOD
HDWR HARDWARE
HM HOLLOW METAL
HR HOUR
HR HANDRAIL
HS HARDWARE SET
HSS HOLLOW STRUCTURAL SHAPE
HVAC HEATING VENTILATING AND AIR CONDITIONING
IAW IN ACCORDANCE WITH
ID INSIDE DIAMETER
IF INSIDE FACE
IIP INSULATED INFILL PANEL GLASS
IJ ISOLATION JOINT
IJS IN JOIST SPACE
INC INCLUDE(ING)
INSUL INSULATION
JAN JANITOR
JBE JOIST BEARING ELEVATION
JCT JUNCTION
JFB JOINT FILLER BOARD
JST JOIST
JT JOINT
KCJ KEYED CONSTRUCTION JOINT
KD KNOCKDOWN
KH KITCHEN HOOD
KIT KITCHEN
L ANGLE
LAB LABORATORY
LAM LAMINATED
LAV LAVATORY
LBR LUMBER
LDG LOADING
LF LINEAR FOOT
LG LENGTH (LONG)
LG LAMINATED GLASS
LIN LINEAR
LINO LINOLEUM
LKR LOCKER
LOC LOCATION
LONG LONGITUDINAL
LSC LIFE SAFETY CODE
LTG LIGHTING
LV LOUVER
LVT LUXURY VINYL TILE
MAG MAGNETIC
MAINT MAINTENANCE
MAN MANUAL
MAS MASONRY
MATL MATERIAL
MB MOP BASIN
MBD MARKER BOARD
MBH MOP/BROOM HOLDER
MC MEDICINE CABINET
MEMB MEMBRANE
MH MANHOLE
MR/S MIRROR WITH SHELF
MTD MOUNTED
MTG MOUNTING
MUL MULLION
NC NOISE CRITERIA
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NOM NOMINAL
O to O OUT TO OUT
OA OVERALL
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OFF OFFICE
OFOI OWNER FURNISHED OWNER INSTALLED
OH OPPOSITE HAND
OPG(S) OPENING(S)
OSHA OPERATIONAL SAFETY AND HEALTH ADMINISTRATION
OTB OPEN TO BELOW
OVFL OVERFLOW
P PAINT
PAN B PANIC BOLT
PB PARTICLE BOARD
PC PRECAST CONCRETE
PCD PAPER CUP DISPENSER
PCT PORCELAIN CERAMIC TILE
PD PANIC DEVICE
PERF PERFORATED
PERP PERPENDICULAR
PG PATTERN GLASS
PIC PORTABLE INSTRUMENT CONNECTION
PIG PATTERN INSULATING GLASS
PL PLATE
PL PROPERTY LINE
PL PLASTIC LAMINATE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PR PAIR
PREFAB PREFABRICATED
PROJ PROJECT(OR) (ION)
PS PROJECTION SCREEN
PT POINT
PT POINT OF TANGENCY
PTD PAPER TOWEL DISPENSER
PTD/R COMBINATION TOWEL DISPENSER/RECEPTACLE
PTN PARTITION
PVC POLYVINYL CHLORIDE
PWL SOUND POWER LEVEL
QT QUARRY TILE
QTR RND QUARTER ROUND
R RISER
RAD RADIUS
RB RUBBER BASE
RC REMOTE CONTROL
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFERENCE
REFL REFLECTED
REM REMOVABLE
RESIL RESILIENT
RF RESILIENT FLOORING
RF RUBBER FLOOR
RFM RECESSED FLOOR MAT
RH ROBE HOOK
RI&C ROUGH IN AND CONNECT
S SINK
SAT SPRAYED ACOUSTIC TREATMENT
SAW SOUND ABSORBING WALL UNITS
SB SPLASH BLOCK
SC SOLID CORE
SC SHOWER CURTAIN
SCD SEAT COVER DISPENSER
SCH SHOWER CURTAIN HOOK
SCR SHOWER CURTAIN ROD
SCT STRUCTURAL CLAY TILE
SD SOAP DISPENSER
SECY SECRETARY
SF SQUARE FEET
SG SPANDREL GLASS
SGL SINGLE
SH SHOWER
SHM SECURITY HOLLOW METAL
DEPR DEPRESS(ION)(ED)
DEPT DEPARTMENT
DET DETENTION
DF DRINKING FOUNTAIN
DG DOOR GRILLE
DIAG DIAGONAL
DPFG DAMPROOFING
DR DOOR
DSN DOWNSPOUT NOZZLE
DW DISHWASHER
DWL(S) DOWEL(S)
DWR DRAWER
EB EXPANSION BOLT
EE EACH END
EEW EMERGENCY EYE WASH
EEWS EMERGENCY EYE WASH SHOWER
EFF EFFICIENCY
EJ EXPANSION JOINT
ELAS ELASTOMERIC
ELEV ELEVATOR
EMER EMERGENCY
ENCL ENCLOSURE
ENTR ENTRANCE
ERF EPOXY RESIN FLOORING
EUI ENERGY USE INTENSITY
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXP EXPANSION
EXP EXPOSED
F FABRIC
F.O. FACE OF
FAB FABRICATE(D)
FB FACE BRICK
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FIG FIGURE
FIX FIXTURE
FLASH FLASHING
FLEX FLEXIBLE
FLG FLOORING
FLM FULL LENGTH MIRROR
FLUOR FLUORESCENT
FO FINISH OPENING
FOC FACE OF CONCRETE
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUD
FOW FACE OF WALL
FP FIREPROOFING
FR FIRE RESISTANT
FRP FIBERGLASS REINFORCED PANEL
FRT FIRE RESISTANCE TREATED
FS FLOOR SINK
FSS FOLDING SHOWER SEAT
FTG FOOTING
FVC FIRE VALVE CABINET
FWC FABRIC WALL COVERING
G GROUT
GA GAUGE
GAL GALLON
GALV GALVANIZED
GB GRAB BAR
GD GARBAGE DISPOSAL
GEN GENERAL
GFA GROSS FLOOR AREA
GL GLUE LAMINATED
GL GLASS
GMP GUARANTEED MAXIMUM PRICE
GR GUARD RAIL
S_-_-3_ NON-RATED STUD PARTITION
MARK ROUGH
THICKNESS
FIRE/SMOKE T.O. WALL
DETAIL
B.O. WALL
DETAIL COMMENTSRATING TESTED ASSEMBLIES
SA 3 31 6 1/4" NR NA 5A/A0.1 5A/A0.1
SCALE: 6" = 1'-0"A0.1
5A PERIMETER LAA WALL DETAIL
SLNT SEALANT
SM SHEET METAL
SND SANITARY NAPKIN DISPOSAL
SNV SANITARY NAPKIN VENDOR
SPL SOUND PRESSURE LEVEL
SQ SQUARE
SS SOLID SURFACE
SSA STORM SHELTER AREA
SSS STAINLESS STEEL SHELF
SST STAINLESS STEEL
ST STONE
ST STAIR
STAG'D STAGGERED
STC SOUND TRANSMISSION CLASS
STGR STRINGER
SUBFL SUBFLOOR
SURF SURFACE
SUSP SUSPENDED
SVF SHEET VINYL FLOORING
T TREAD
T&G TONGUE AND GROOVE
T.O. TOP OF
TAN TANGENT
TB TOWEL BAR
TBD TACK BOARD
TCP TOILET COMPARTMENT PARTITION
TERR TERRAZZO
TFG TINTED FLOAT GLASS
TG TEMPERED GLASS
TH THRESHOLD
THK THICK(NESS)
TI TENANT IMPROVEMENT
TIG TINTED INSULATING GLASS
TMR TILT MIRROR UNIT
TOIL TOILET
TOP TOP OF PAVING
TRANS TRANSVERSE
TT TERRAZZO TILE
TTD TOILET TISSUE DISPENSER
TTG TINTED TEMPERED FLOAT GLASS
TTIG TINTED TEMPERED INSULATING GLASS
TW TACK WALL
UL UNDERWRITERS LABORATORIES
UR URINAL
US UTILITY SHELF
UTIL UTILITY
VB VAPOR BARRIER
VB VINYL BASE
VCB VENTED COVE BASE
VF VINYL FLOOR
VOC VOLITILE ORGANIC COMPOUND
VOL VOLUME
VP VENEER PLASTER
VT VINYL TILE
VWC VINYL WALL COVERING
W WIDE
WB WALL BASE
WC WATER CLOSET
WC WALL COVERING
WCL WATER CLOSET/LAVATORY COMBINATION
WD WOOD
WDF WOOD FLOORING
WDW WINDOW
WG POLISHED WIRE GLASS
WI WROUGHT IRON
WOM WALK OFF MAT
WR WASTE RECEPTACLE
WRB WEATHER RESISTANT BARRIER
WW WARM WHITE
WWF WELDED WIRE FABRIC
YD YARD
SCALE: 1 1/2" = 1'-0"A0.1
4C T.O. WALL DETAIL
SCALE: 1 1/2" = 1'-0"A0.1
4D T.O. WALL DETAIL
SCALE: 1 1/2" = 1'-0"A0.1
4E T.O. WALL DETAIL
SCALE: 1 1/2" = 1'-0"A0.1
5C B.O. WALL DETAIL
SCALE: 1 1/2" = 1'-0"A0.1
5D B.O. WALL DETAIL
SCALE: 1 1/2" = 1'-0"A0.1
5E B.O. WALL DETAIL
THE CONTRACTOR SHALL CAREFULLY STUDY AND COMPARE THE CONSTRUCTION DOCUMENTS INCLUDING
CONSULTANT'S DRAWINGS AND SHALL IMMEDIATELY REPORT ANY NOTED DISCREPANCIES,
INCONSISTENCIES, OR OMISSIONS TO THE ARCHITECT. CONTRACTOR SHALL PERFORM NO PORTION OF THE WORK AT ANY TIME WITHOUT CONSTRUCTION DOCUMENTS, OR WHERE REQUIRED, APPROVED SHOP
DRAWINGS, PRODUCT DATA, OR SAMPLES FOR SUCH PORTIONS OF THE WORK.
AIA DOCUMENT A201- 2017 GENERAL CONDITIONS SHALL BE INCORPORATED INTO THESE DOCUMENTS.
THE CONSTRUCTION DOCUMENTS PREPARED BY THE ARCHITECT FOR THIS PROJECT ARE INSTRUMENTS OF THE ARCHITECT'S DESIGN SERVICE FOR USE SOLELY WITH RESPECT TO THIS PROJECT. THESE DOCUMENTS SHALL NOT BE USED BY OTHERS IN WHOLE OR IN PART FOR ADDITIONS TO THIS PROJECT OR FOR OTHER
PROJECTS.
G1 SUPPLEMENTAL INSTRUCTIONS
G1.1 ADD THE FOLLOWING DEFINITION TO AIA A201, PARAGRAPH 1.1 - BASIC DEFINITIONS, 1.1.9 - THE USE OF THE WORD "PROVIDE" IN CONNECTION WITH ANY ITEM SPECIFIED IS INTENDED TO MEAN THAT SUCH SHALL BE FURNISHED, INSTALLED AND CONNECTED, WHERE SO REQUIRED, UNLESS NOTED
OTHERWISE (U.N.O.)
G1.2 ADD THE FOLLOWING DEFINITION TO AIA A201, PARAGRAPH 1.1 - BASIC DEFINITIONS, 1.1.10 - THE TERM "BUILDING STANDARD" AS NOTED ON DRAWINGS AND AS SPECIFIED HEREIN, REFERS TO ALL MATERIALS, LABOR, INSTALLATION, ETC. PER BUILDING OWNER'S CRITERIA. CONTRACTOR IS
RESPONSIBLE FOR COORDINATING WITH OWNER FOR PROCUREMENT OF BUILDING STANDARDS
DOCUMENTATION.
G1.3 ADD THE FOLLOWING DEFINITION TO AIA A201, PARAGRAPH 1.1 - BASIC DEFINITIONS, 1.1.11 - "WORK"
SHALL INCLUDE ALL LABOR, ASSEMBLIES AND FINISH WORK WITH ALL PARTS AND MATERIALS
NECESSARY TO MAKE A COMPLETE, IN PLACE, PROPERLY WORKING AND FINISHED INSTALLATION, REGARDLESS OF WHETHER SHOWN ON THE DRAWINGS OR NOT.
G2 CONSTRUCTION DOCUMENTS
G2.1 ALL DIMENSIONS AND DESCRIPTIONS ON CONSTRUCTION DRAWINGS ARE COMPLEMENTARY. ANY
WORK SHOWN OR REFERRED TO ON ANY CONSTRUCTION DOCUMENT SHALL BE PROVIDED AS
THOUGH ON ALL RELATED DOCUMENTS.
G2.2 ANY CONFLICTS BETWEEN THE MECHANICAL/ ELECTRICAL/ PLUMBING/ SPECIAL SYSTEMS OR OTHER DRAWINGS IN THIS SET ARE TO BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE ARCHITECT
PRIOR TO CONSTRUCTION.
G2.3 UNLESS NOTED OTHERWISE, ALL DRAWINGS HAVE BEEN PRODUCED TO SCALE, CONTRACTOR SHALL
NOT DIRECTLY MEASURE OR "SCALE" SAID DRAWINGS TO ASCERTAIN ANY DIMENSION.
G3 CONTRACTUAL RELATIONSHIPS
G3.1 NOTHING CONTAINED IN THESE DRAWINGS, OR IN ANY ACCOMPANYING CONTRACT DOCUMENTS, SHALL CREATE ANY CONTRACTUAL RELATIONSHIP BETWEEN THE CONTRACTOR AND THE
ARCHITECT.
G4 BIDDING
G4.1 PRIOR TO THE BID, THE CONTRACTOR SHALL EXAMINE THE SITE AND PORTIONS THEREOF WHICH WILL AFFECT THIS WORK AND SHALL COMPARE IT WITH THE DRAWINGS AND BE SATISFIED AS TO
THE CONDITIONS UNDER WHICH WORK IS TO BE PERFORMED. THE CONTRACTOR SHALL AT SUCH
TIME ASCERTAIN AND CHECK LOCATIONS OF THE EXISTING STRUCTURE AND BUILDING SYSTEMS.
G4.2 CONTRACTOR SHALL NOTIFY THE ARCHITECT IN WRITING OF ANY VARIATIONS OR DISCREPANCIES FROM THE EXISTING CONDITIONS PRIOR TO SUBMITTING BID. THE SUBMISSION OF A BID WILL BE CONSTRUED AS EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT AND/ OR MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD SUCH AN EXAMINATION BEEN MADE, WILL NOT BE RECOGNIZED.
G4.3 WITHIN FIVE (5) DAYS FROM AWARD OF THE CONTRACT, CONTRACTOR SHALL PROVIDE A
SUBCONTRACTOR'S LIST INCLUDING CONTACT AND LICENSING INFORMATION.
G4.4 THE CONTRACTOR SHALL EXPRESSLY ACKNOWLEDGE, IN WRITING, IN HIS BID, THAT HE HAS READ
AND REVIEWED THESE CONSTRUCTION DOCUMENTS IN THEIR ENTIRETY, INCLUDING ALL
INFORMATION CONTAINED IN THESE SPECIFICATION SHEETS.
G5 CONSTRUCTION PROGRESS SCHEDULE
G5.1 THE CONTRACTOR, PRIOR TO BEING GIVEN NOTICE TO PROCEED, SHALL PREPARE AND SUBMIT TO
THE ARCHITECT A PRELIMINARY CONSTRUCTION SCHEDULE OF THE WORK IN BAR CHART FORM.
G5.2 THE CONTRACTOR SHALL BE RESPONSIBLE FOR SECURING PERMITS FOR ALL PHASES OF THE WORK
AS REQUIRED BY FEDERAL, STATE, COUNTY AND MUNICIPAL LAW.
G6 USE OF PREMISES
G6.1 CONTRACTOR SHALL CONFINE HIS APPARATUS, DELIVERY AND STORAGE OF MATERIALS, AND THE
OPERATION OF HIS WORKERS TO LIMITS DEFINED BY THE OWNER. CONTRACTOR SHALL NOT
UNREASONABLY ENCUMBER THE PREMISES TO THE INCONVENIENCE OF THE TENANTS AND OWNER'S
PERSONNEL AND OPERATION.
G6.2 CONTRACTOR SHALL MINIMIZE NOISE DISTURBANCE TO ADJACENT OCCUPANTS.
G6.3 CORING AND OTHER WORK WHICH MIGHT AFFECT OTHER TENANTS SHALL BE SCHEDULED WITH
OWNER'S AND BUILDING LANDLORD'S APPROVAL.
G6.4 CONTRACTOR IS RESPONSIBLE FOR STACKING OF ALL MATERIALS DURING CONSTRUCTION IN A MANNER THAT PREVENTS LIVE LOADS FROM EXCEEDING THOSE ALLOWED FOR IN THE BUILDING'S
STRUCTURAL DESIGN. CONTRACTOR TO COORDINATE THIS WITH BUILDING LANDLORD.
G7 CONSTRUCTION OFFICE
G7.1 CONTRACTOR SHALL PROVIDE AND MAINTAIN A FIELD CONSTRUCTION OFFICE, LOCATED AS
DIRECTED BY THE OWNER AND/OR LANDLORD.
G7.2 CONTRACTOR SHALL ALLOW FOR ACCESS BY OTHER VENDORS AND OWNER'S OWN FORCES.
CONTRACTOR SHALL COOPERATE WITH THE TENANT ON SCHEDULING AND PERFORMING THE
CONTRACTOR'S WORK TO AVOID CONFLICT, DELAY, OR INTERFERENCE WITH THE WORK OF OTHER
VENDORS OR THE CONSTRUCTION OR OPERATIONS OF THE OWNER'S OWN FORCES.
G7.3 CONTRACTOR SHALL MAINTAIN, ON THE SITE, ONE RECORD COPY OF THE RECORD DRAWINGS, RECORD SHOP DRAWINGS, PRODUCT DATA, SAMPLES AND SIMILAR REQUIRED SUBMITTALS FOR
REFERENCE.
G7.4 CONTRACTOR SHALL PROVIDE UNLIMITED LOCAL TELEPHONE SERVICE FOR THE USE OF ALL SUBCONTRACTORS, SUPPLIERS, DESIGNERS, AND INSPECTORS. LONG DISTANCE CHARGES SHALL
BE PAID BY THE CONTRACTOR AND MAY BE CHARGED TO THOSE INCURRING SUCH COSTS.
G8 TOILET FACILITIES AND DRINKING WATER
G8.1 UPON THE APPROVAL OF THE OWNER, THE USE OF DESIGNATED TOILET FACILITIES AND DRINKING FOUNTAINS WITHIN THE BUILDING SHALL BE AVAILABLE FOR THE USE OF ALL WORKERS FOR THE DURATION OF THE PROJECT. IF, AT ANY TIME, THE OWNER FEELS THAT ANY OF THE WORKMEN ARE RESPONSIBLE FOR LEAVING A TOILET ROOM OR DRINKING FOUNTAIN UNNECESSARILY DIRTY, OR
ARE RESPONSIBLE FOR CAUSING ANY DAMAGE TO EXISTING TOILET FACILITIES OR DRINKING
FOUNTAINS, THE OWNER MAY HOLD THE CONTRACTOR RESPONSIBLE FOR THE COST OF CLEANUP
OR REPAIR.
G9 PROTECTION OF PERSONS AND PROPERTY
G9.1 CONTRACTOR SHALL PROTECT AREAS AND NEW OR EXISTING MATERIALS AND FINISHES FROM DAMAGE WHICH MAY OCCUR FROM CONSTRUCTION, DEMOLITION, DUST, WATER, ETC., AND SHALL
PROVIDE AND MAINTAIN TEMPORARY BARRICADES, CLOSURE WALLS, ETC., AS REQUIRED TO
PROTECT THE PUBLIC DURING THE PERIOD OF CONSTRUCTION. DAMAGE TO NEW AND EXISTING
MATERIAL, FINISHES, STRUCTURES, AND EQUIPMENT SHALL BE REPAIRED OR REPLACED TO THE
SATISFACTION OF THE OWNER AT THE EXPENSE OF THE CONTRACTOR.
G9.2 CONTRACTOR SHALL ERECT DUST-PROOF BARRIERS, AT THE DIRECTION OF THE OWNER.
G10 INTERRUPTION OF SERVICES
G10.1 CONTRACTOR SHALL COOPERATE WITH OWNER IN REGARD TO ANY INTERRUPTIONS OR SHUTDOWN OF ELECTRICAL, MECHANICAL, PLUMBING, OR TELEPHONE SERVICE. OWNER SHALL BE NOTIFIED AS
REQUIRED BUT NOT LESS THAN 48 HOURS IN ADVANCE BEFORE SHUTDOWN OCCURS.
G11 SECURITY
G11.1 CONTRACTOR SHALL OBTAIN THROUGH OWNER, THE REQUIRED SECURITY CLEARANCES, ACCESS
ARRANGEMENTS, PASSES, OR BADGES NECESSARY FOR ALL WORKERS, SUBCONTRACTORS, AND
SUPPLIERS WHO MAY REQUIRE ACCESS TO THE FACILITY DURING CONSTRUCTION, AND SHALL
COOPERATE WITH THE OWNER IN REGARD TO ANY AREAS OF LIMITED ACCESS.
G12 DEBRIS CONTROL AND CLEANING
G12.1 THE CONTRACTOR SHALL REMOVE ALL RUBBISH AND WASTE MATERIAL ON A REGULAR BASIS, AND SHALL EXERCISE STRICT CONTROL OVER JOB CLEANING TO PREVENT ANY DIRT, DEBRIS, OR DUST FROM AFFECTING, IN ANY WAY, FINISHED AREAS INSIDE OR OUTSIDE JOB SITE. THE BUILDING REFUSE
FACILITIES SHALL NOT BE USED FOR THIS PURPOSE.
G12.2 AT COMPLETION, THE CONTRACTOR SHALL LEAVE PREMISES AND ALL SURFACES AND FIXTURES
FINISHED, CLEANED, ORDERLY, AND READY FOR MOVE-IN.
G14 PROJECT MEETINGS
G13.1 AT THE OWNERS REQUEST, THE CONTRACTOR SHALL SCHEDULE REGULAR AND PERIODIC MEETINGS
TO REVIEW THE PROJECT.
G13.2 THE CONTRACTOR SHALL PREPARE AGENDAS OF THE MEETING AND DISTRIBUTE COPIES TO PARTIES IN ATTENDANCE. IN GENERAL, THESE MEETINGS SHOULD BE ATTENDED BY: THE CONTRACTOR, THE OWNER OR OWNER'S REPRESENTATIVE, THE ARCHITECT, THE SUBCONTRACTORS OR SUPPLIERS AS
MAY BE APPROPRIATE TO THE AGENDA, AND OTHERS.
G13.3 THE CONTRACTOR SHALL RECORD MINUTES OF THE PROJECT MEETINGS INCLUDING SIGNIFICANT PROCEDURES AND DECISIONS. COPIES OF THESE MINUTES SHALL BE DISTRIBUTED WITHIN FOUR
DAYS AFTER EACH MEETING TO ALL PARTICIPANTS.
G14 WORKMANSHIP AND MATERIALS
G14.1 ALL WORK SHALL BE DONE IN THE FINEST QUALITY/WORKMANSHIP - LIKE MANNER, IN ACCORDANCE WITH THE INDUSTRY STANDARD FOR CONSTRUCTION, FABRICATION AND INSTALLATION FOR EACH TRADE. UNLESS OTHERWISE NOTED, USE ONLY NEW, HIGHEST QUALITY MATERIALS CONSISTENT
WITH SPECIFICATIONS AS INDICATED.
G15 SUBMITTALS
G15.1 WITHIN FIVE (5) DAYS FROM AWARD OF THE CONTRACT, CONTRACTOR SHALL SUBMIT TO THE
ARCHITECT, A DETAILED SHOP DRAWING SUBMITTAL AND SAMPLE SCHEDULE.
G15.2 THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR ALL FABRICATED ITEMS INCLUDING MECHANICAL AND ELECTRICAL EQUIPMENT, CUT SHEETS FOR ALL FIXTURES AND EQUIPMENT AND SAMPLES OF ALL FINISHES TO THE ARCHITECT PRIOR TO TIMELY ORDERING. A SUMMARY OF (BUT
NOT LIMITED TO) SUBMITTALS REQUIRED UNDER THE ARCHITECTURAL SCOPE OF WORK ARE AS
FOLLOWS.
G15.3 THE CONTRACTOR SHALL PERFORM NO PORTION OF THE WORK REQUIRING SUBMITTAL AND
REVIEW OF SHOP DRAWINGS, PRODUCT DATA, SAMPLES OR SIMILAR SUBMITTALS UNTIL THE
RESPECTIVE SUBMITTAL HAS BEEN REVIEWED AND APPROVED BY THE ARCHITECT. SUCH WORK
SHALL BE IN ACCORDANCE WITH ACCEPTED SUBMITTALS.
G15.4 THE CONTRACTOR SHALL NOT BE RELIEVED OF RESPONSIBILITIES FOR DEVIATIONS FROM
REQUIREMENTS OF THE CONTRACT DOCUMENTS BY ARCHITECT'S REVIEW OF SHOP DRAWINGS,
PRODUCT DATA, SAMPLES OR SIMILAR SUBMITTALS UNLESS THE CONTRACTOR HAS SPECIFICALLY INFORMED THE ARCHITECT, IN WRITING, OF SUCH DEVIATION AT THE TIME OF SUBMITTAL AND THE
ARCHITECT HAS GIVEN WRITTEN ACCEPTANCE TO THE SPECIFIC DEVIATION. THE CONTRACTOR
SHALL NOT BE RELIEVED OF RESPONSIBILITY FOR ERRORS OR OMISSIONS OF SHOP DRAWINGS, PRODUCT DATA, SAMPLES OR SIMILAR SUBMITTALS BY ARCHITECT'S ACCEPTANCE THEREOF.
G15.5 THE ARCHITECT WILL REVIEW OR TAKE OTHER APPROPRIATE ACTION UPON THE CONTRACTOR'S SUBMITTALS SUCH AS SHOP DRAWINGS, PRODUCT DATA AND SAMPLES, BUT ONLY FOR THE LIMITED PURPOSE OF CHECKING FOR CONFORMANCE WITH INFORMATION GIVEN AND THE DESIGN CONCEPT
EXPRESSED IN THE CONTRACT DOCUMENTS. ARCHITECT'S ACTION WILL BE TAKEN WITH SUCH
REASONABLE PROMPTNESS AS TO CAUSE NO DELAY IN THE WORK OR IN THE ACTIVITIES OF THE
OWNER, CONTRACTOR OR SEPARATE CONTRACTORS, WHILE ALLOWING SUFFICIENT TIME IN
ARCHITECT'S PROFESSIONAL JUDGMENT TO PERMIT ADEQUATE REVIEW. REVIEW OF SUCH
SUBMITTALS IS NOT CONDUCTED FOR THE PURPOSE OF DETERMINING THE ACCURACY AND
COMPLETENESS OF OTHER DETAILS SUCH AS DIMENSIONS AND QUANTITIES, OR FOR
SUBSTANTIATING INSTRUCTIONS FOR INSTALLATION OR PERFORMANCE OF EQUIPMENT OR SYSTEMS ALL OF WHICH REMAIN THE RESPONSIBILITY OF THE CONTRACTOR AS REQUIRED BY THE CONTRACT DOCUMENTS. ARCHITECT'S REVIEW SHALL NOT CONSTITUTE APPROVAL OF SAFETY PRECAUTIONS, OR UNLESS OTHERWISE SPECIFICALLY STATED BY THE ARCHITECT, OF ANY CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES. ARCHITECT'S REVIEW OF A SPECIFIC ITEM
SHALL NOT INDICATE APPROVAL OF AN ASSEMBLY OF WHICH THE ITEM IS A COMPONENT.
G15.6 BY APPROVING AND SUBMITTING SHOP DRAWINGS AND SAMPLES TO THE ARCHITECT, THE CONTRACTOR REPRESENTS THAT HE HAS DETERMINED AND VERIFIED FIELD MEASUREMENTS, FIELD
CONSTRUCTION CRITERIA, MATERIALS, CATALOG NUMBERS AND SIMILAR DATA, THAT EACH
SUBMITTAL HAS BEEN CHECKED AND COORDINATED WITH THE REQUIREMENTS OF THE CONTRACT.
G15.7 THE CONTRACTOR SHALL REVIEW AND STAMP, WITH HIS APPROVAL , ALL SUBMITTALS. ANY
SUBMITTALS WHICH DO NOT BEAR CONTRACTOR'S APPROVAL STAMP SHALL BE RETURNED
WITHOUT REVIEW. WHERE PRINTED MATERIALS DESCRIBE MORE THAN ONE PRODUCT OR MODEL,
CLEARLY IDENTIFY WHICH IS TO BE FURNISHED. SHOP DRAWINGS SHALL NOT BE REPRODUCTIONS
OF CONSTRUCTION DOCUMENTS. EACH SHOP DRAWING, SAMPLE AND PRODUCT DATA SUBMITTAL
SHALL BE PROPERLY IDENTIFIED BEARING THE NAME AND QUALITY OF THE MATERIAL, THE
MANUFACTURER'S NAME, THE CONTRACTOR'S NAME, THE SUBCONTRACTOR'S NAME, THE NAME OF
THE PROJECT AND THE DATE OF SUBMISSION.
G15.8 REJECTED SHOP DRAWINGS AND SAMPLES SHALL BE RESUBMITTED AS SOON AS POSSIBLE AND
SHALL BE IDENTIFIED AS "RESUBMITTALS".
G15.9 THE CONTRACTOR SHALL IDENTIFY SPECIFIC ATTENTION, IN WRITING, ON RESUBMITTED SHOP DRAWINGS, PRODUCT DATA OR SAMPLES TO REVISIONS, OTHER THAN THOSE REQUESTED BY THE
ARCHITECT.
G15.10 THE CONTRACTOR SHALL MAKE SUBMITTALS IN THE FOLLOWING QUANTITIES:
PROVIDE 1 COPY OF THE FOLLOWING SECTIONS:
092116 104416 087100 115213 113000 100000
PROVIDE 1 COPY AND 3 SAMPLES OF THE FOLLOWING SECTIONS:
072700 081100 044300 081400 083000 081116 093000 095100 088000 096513 096800 096500 098000 099000 097200 106900 122000 101100
PROVIDE 2 COPIES AND 3 SAMPLES OF THE FOLLOWING SECTIONS:
055800 064000 055200 099700 079000
PROVIDE 4 COPIES OF THE FOLLOWING SECTION:
230000 260000
G16 CLARIFICATIONS
G16.1 ALL REQUESTS FOR CLARIFICATION OF THE CONSTRUCTION DRAWINGS SHALL BE DIRECTED TO THE ARCHITECT USING THE REQUEST FOR INFORMATION (R.F.I) FORM. ALL RESPONSES SHALL BE ISSUED THROUGH THE ARCHITECT IN THE R.F.I. FORM OR ARCHITECTS SUPPLEMENTAL INSTRUCTION (A.S.I.).
G17 CLAIMS FOR ADDITIONAL COSTS
G17.1 IF THE CONTRACTOR WISHES TO MAKE A CLAIM FOR AN INCREASE IN THE CONTRACT SUM, HE SHALL GIVE THE ARCHITECT WRITTEN NOTICE THEREOF WITHIN SEVEN (7) DAYS AFTER THE OCCURRENCE OF THE EVENT GIVING RISE TO SUCH CLAIM. THIS NOTICE SHALL BE GIVEN BY THE CONTRACTOR BEFORE PROCEEDING TO EXECUTE THE WORK, EXCEPT IN AN EMERGENCY ENDANGERING LIFE OR
PROPERTY. ANY CHANGE IN THE CONTRACT SUM RESULTING FROM SUCH CLAIM SHALL BE
AUTHORIZED BY A WRITTEN CHANGE ORDER APPROVED BY OWNER.
G18 DOCUMENTATION AT SITE
G18.1 CONTRACTOR SHALL MAINTAIN, ON THE SITE, ONE RECORD COPY OF THE DRAWINGS/
SPECIFICATIONS, ADDENDA, CHANGE ORDERS AND OTHER MODIFICATIONS, AND MARKED
CURRENTLY TO RECORD FIELD CHANGES AND SELECTIONS MADE DURING CONSTRUCTION. THREE
COPIES OF THESE RECORD DRAWINGS ARE TO BE DELIVERED TO THE ARCHITECT FOR SUBMITTAL TO
THE OWNER UPON COMPLETION OF THE WORK.
G19 WARRANTIES AND OPERATING INSTRUCTIONS
G19.1 PRIOR TO FINAL APPLICATION FOR PAYMENT OF THE PROJECT, THE CONTRACTOR SHALL SUBMIT TO THE ARCHITECT, IN TRIPLICATE, ON BEHALF OF HIMSELF AND HIS SUBCONTRACTORS: A ONE (1) YEAR WRITTEN GUARANTEE AGAINST DEFECTIVE RESPECTIVE WORKMANSHIP AND/OR MATERIALS.
THIS GUARANTEE SHALL BE IN ADDITION TO (NOT IN LIEU OF) ANY WARRANTIES AND/OR GUARANTEES
PROVIDED BY PRODUCT MANUFACTURERS, SUPPLIERS, ETC.
G19.2 PRIOR TO FINAL APPLICATION FOR PAYMENT, CONTRACTOR SHALL SUBMIT TO THE ARCHITECT, IN
TRIPLICATE, CLOSEOUT DOCUMENTATION CONSISTING OF THE FOLLOWING:
EVIDENCE OF COMPLIANCE WITH REQUIREMENTS OF GOVERNING AUTHORITIES.
PROJECT RECORD DOCUMENTS
OPERATIONS AND MAINTENANCE DATA
WARRANTIES AND BONDS
SPARE PARTS AND MAINTENANCE MATERIALS
KEY AND KEYING SCHEDULE
EVIDENCE OF PAYMENT AND RELEASE OF LIENS
CONSENT OF SURETY AND FINAL PAYMENT
CERTIFICATES OF INSURANCE FOR PRODUCTS AND COMPLETED OPERATIONS.
G20 COMPLETION
G20.1 WHEN CONTRACTOR IS NEARING COMPLETION, HE SHALL NOTIFY THE ARCHITECT ACCORDINGLY IN WRITING. UPON INSPECTION, THE ARCHITECT SHALL PREPARE A FINAL PUNCH LIST OUTLINING
INCOMPLETE OR UNACCEPTABLE WORK. CONTRACTOR SHALL COMPLETE ALL PUNCH LIST ITEMS
WITHIN TWO (2) WEEKS OF RECEIPT OF PUNCH LIST. THE PROJECT WILL NOT BE CONSIDERED COMPLETE UNTIL ALL ITEMS ON THE PUNCH LIST HAVE BEEN RESOLVED AND ALL RECORD DRAWINGS, WARRANTIES AND OPERATING INSTRUCTIONS HAVE BEEN RECEIVED AND REVIEWED BY THE
ARCHITECT.
DRAWINGS SAMPLE DATA
044300 STONE MASONRY X X
055200 METAL RAILINGS X
055800 FORMED METAL FABRICATIONS X X X
064000 ARCHITECTURAL WOODWORK X X X
072700 AIR BARRIERS X X
079000 JOINT PROTECTION X X
081100 METAL DOORS & FRAMES X X
081116 ALUMINUM DOORS & FRAMES X X X
081400 WOOD DOORS X X X
083000 SPECIALTY DOORS & FRAMES X X
087100 DOOR HARDWARE X X
088000 GLAZING X X X
092116 GYPSUM BOARD ASSEMBLIES X X X
093000 TILING X X
095100 ACOUSTICAL CEILINGS X X
096500 RESILIENT FLOORING X X
096513 RESILIENT BASE X X
096800 CARPETING X X X
097200 WALL COVERING X X
099000 PAINTING AND COATING X X
096900 ACCESS FLOORING X X X
099700 SPECIAL COATINGS X X
100000…