ATTACHMENT A - DRAWINGS - 605-19-400.pdf
PDF 35 MB Posted
- Solicitation number
- 36C26222B0005
About this file
This document contains details for a federal contract solicitation for emergency generator and switchgear upgrades. Project 605-19-400 involves emergency generator farm and switchgear upgrade work for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22. Offerors are invited to submit proposals in response to solicitation number 36C26222B0005 by the specified due date to provide products and services for the generator and switchgear upgrades. The work location is a VA medical center and the upgrades are needed to ensure emergency power systems function properly.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ROOM
NAME
A101
A101
1t
A101
1 Ref
R e f
1 Ref
R e f
1i
1i
GRID REFERENCE
ROOM NAME/NUMBER
WALL SECTION
DETAIL REFERENCE
KEYNOTE
DOOR REFERENCE
SEE SHEET A-XXX
FOR SCHEDULE
WINDOW REFERENCE
SEE SHEET A-XXX
FOR SCHEDULE
REVISION
INTERIOR ELEVATION
EQUIPMENT REFERENCE
SEE SHEET A-XXX
FOR SCHEDULE
WALL REFERENCE
SEE SHEET A-XXX
FOR WALL TYPES
ELEVATION NUMBER
SHEET NUMBER
DETAIL NUMBER
SHEET NUMBER
SECTION NUMBER
SHEET NUMBER
CONSTRUCTION TYPE: 1-A FIRE SPRINKLERED, WITH INTERSTITIAL SPACE
OCCUPANCY TYPE: 1-2 HOSPITAL
PROJECT SQUARE FOOTAGE: 13,429 SQ. FT.
PROJECT BUILDING INFORMATION:
FULLY SPRINKLERED
BUILDING STORIES: 4 WITH PARTIAL BASEMENT
PROJECT LOCATION: FIRST FLOOR & SITE
PROJECT DESCRIPTION:
REMOVE EXISTING ELECTRICAL SWITCHGEAR AND LOCOMOTIVE GENERATOR IN EXISTING ELECTRICAL ROOMS AND REPLACE WITH NEW SWITCHGEAR. DEMOLISH CURRENT OUTDOOR FUEL YARD AND REPLACE WITH NEW ENCLOSURE TO HOUSE NEW GENERATORS AND EQUIPMENT. NEW UNDERGROUND FUEL TANKS TO BURRIED
ADJACENT TO NEW YARD.
BARTON ROAD
M O
U N
T A
IN
V
IE
W
A V
E N
U E
REDLANDS BOULEVARD
10 FREEWAY
A N
D E
R S
O N
S T
R E
E T
PROJECT
LOCATION
N
N
B E
N T
O N
S T
R E
E T
PROSPECT AVE.
PROJECT AREA
(FIRST FLOOR)
1. EMERGENCY GENERATORS & ANCHORAGE
2. FUEL SYSTEM MOUNTING AND ANCHORAGE:
A. RETURN PUMPS
B. CONTROLLERS
C. LEAK DETECTION/INVENTORY PANEL ARRANGEMENT AND GROUPINGS
D. CABINET SIZE AND WEIGHTS
3. FIRE ALARM
4. FIRE SPRINKLERS
5. STEEL DIAMOND PLATE CATWALK AND STAIRS IN GENERATOR YARD AND SWITCHGEAR ROOM
DEFERRED APPROVALS ARE RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE SUBMITTED TO THE VA AND
THE ARCHITECT FOR REVIEW AND APPROVAL.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
605 -19 - 400
EMERGENY GENERATOR
FARM
11201 BENTON STREET
LOMA LINDA, CA 92357
100% CONSTRUCTION
DOCUMENTS
c|a ARCHITECTS expressly reserves its common law copyright and other property rights in these plans. These plans are not to be reproduced, changed or copied in any form or manner,nor are they to be assigned to any third party without first obtaining the written consent of c|a ARCHITECTS, Inc. COPYRIGHT ©
3633 LONG BEACH BLVD., SUITE 200
T 562.595.5666 | F 562.595.5577
LONG BEACH, CA 90807
www.c-a ARCHITECTS.com
C|A #1474.01
D R
A W
IN
G
N A
M E
P L O
T D
A T
E
P L O
T T
E D
B Y
/1 /2
:2
:0
P M
/1 /2
:2 :0
P
M
B
IM
/1
.0
E m e rg e n c y G e n e ra to r
F a rm
/1 .0
-A
-B M
R
.r v t
GI000
COVER SHEET
DS NH08/30/2021
N H
CONTRACTOR INSTALLED
OF/CI OWNER PROVIDED/
EXIST. EXISTING OWNER INSTALLED
EXT. EXTERIOR OF/OI OWNER PROVIDED/ NOTED
E.W.C. ELECTRICAL WATER CHILLER OPN'G. OPENING U.O.N. UNLESS OTHERWISE
EQUIP. EQUIPMENT O.H. OVERHEAD OTHERWISE
EQ. EQUAL O.D. OITSIDE DIAMETER U.N.O. UNLESS NOTED
ELEV. ELEVATOR O.C. ON CENTER
ELEC. ELECTRIC TYP. TYPICAL
EL. ELEVATION N.T.S. NOT TO SCALE T.W. TOP OF WALL
E.J. EXPANSION JOINT NO. NUMBER T.S.W. TOP OF SIDEWALK
EA. EACH N.I.C. NOT IN CONCRACT T.S. TOPSET BASE
(E) EXISTING (N) NEW T.P. TOP OF PAVING
T.O.W. TOP OF WALL
D.F. DRINKING FOUNTAIN MTD. MOUNTED T.O.S. TOP OF SLAB
DWG. DRAWING M.O. MASONRY OPENING T.O.P. TOP OF PARAPET
DR. DOOR MISC. MISCELLANEOUS THK. THICK(NESS)
D.S. DOWN SPOUT MIN. MINIMUM TELE. TELEPHONE
DN. DOWN M.H. MANHOLE T.C. TOP OF CURB
DIM. DIMENSION MTL. METAL T. TREAD
DIAG. DIAGONAL MECH. MECHANICAL
DIA. DIAMETER M.C. MEDICINE CABINET SYM. SYMMETRICAL
DET. DETAIL M.B. MACHINE BOLT S.Y. SQUARE YARD
DBL. DOUBLE MAX. MAXIMUM SUSP. SUSPENDED
STRUCT. STRUCTURAL
CTS'K. COUNTERSINK LT. LIGHT STL. STEEL
CONTRACTOR INSTALLED L.F. LINEAL FEET STD. STANDARD
CP/CI CONTRACTOR PROVIDED/ LT. WT. LIGHTWEIGHT S.S. STAINLESS STEEL
CONTR. CONTRACTOR LAV. LAVATORY SQ. SQUARE
CONT. CONTINUOUS LAM. LAMINATED S.M.S. SHEET METAL SCREW
CONST. CONSTRUCTION SLDG. SLIDING
CONC. CONCRETE JT. JOINT SIM. SIMILAR
COMP. COMPOSITION JST. JOIST SHF. SHELF
COL. COLUMN JAN. JANITOR SHT. SHEET
C.O. CLEAN OUT S.F. SQUARE FEET
C.M.U. CONCRETE MASONRY UNIT G. WB GYPSUM WALLBOARD S.D. STORM DRAIN
CLR. CLEAR GYP. BD. GYPSUM WALLBOARD SCHED. SCHEDULE
CLG. CEILING GRD. GRADE
CERM. CERAMIC G.L. GLASS R.S. ROUGH SAWN
CEM. CEMENT G.I. GALVANIZED IRON R.O. ROUGH OPENING
C.J. CONTROL JOINT G.D. GARBAGE DISPOSAL RM. ROOM
CENTER LINE GALV. GALVANIZED REQ'D. REQUIRED
C.B. CATCH BASIN GAL. GALLON REINF. REINFORCING
CAB'T. CABINET GA. GAUGE REF. REFRIGERATOR
RF. ROOF
BOTT. BOTTOM FTG. FOOTING R.D. ROOF DRAIN
BD. BOARD F.S. FINISHED SURFACE RAD. RADIUS
BM. BEAM F.O.S. FACE OF STUD R. RISER
BLK. BLOCK F.O.M. FACE OF MASONRY
BLDG. BUILDING F.O.C. FACE OF CONCRETE Q.T. QUARRY TILE
FLR. FLOOR
AMP. AMPERE F.L. FLOW LINE PVC. POLYVINYL CHLORIDE
ARCH. ARCHITECTURAL FIN. FINISH P.S.I. POUNDS PER SQ. INCH
< ANGLE F.H.C. FIRE HOSE CABINET PR. PAIR
ALUM. ALUMINUM F.H. FIRE HYDRANT PLYWD. PLYWOOD
A.F.F. ABOVE FINISH FLOOR F.GL. FIXED GLASS PLAS. PLASTER
ADJ. ADJUSTABLE F.FIN. FACTORY FINISH P.LAM. PLASTIC LAMINATE
A.C. ASPHALT CONCRETE F.E.C. FIRE EXTINGUISHER CABINET PL. PLATE
A.B. ANCHOR BOLT F.D. FLOOR DRAIN P.H. PANIC HARDWARE
@ EACH AT F.O.F. FACE OF FINISH PEN. PENETRATION
ABBREVIATIONS
VA CONSTRUCTION STANDARDS, MASTER SPECIFICATIONS, HANDBOOKS, AND PROGRAM GUIDES.
ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS)
TITLE 19, CALIFORNIA CODE OF REGULATIONS
DIV. 1 - PUBLIC SAFETY - STATE FIRE MARSHAL REGULATIONS.
2019 CALIFORNIA REFERENCED STANDARDS CODE (CRSC) PART 12, TITLE 24
2019 CALIFORNIA FIRE CODE (CFC) PART 9, TITLE 24, CCR BASED ON THE 2015 INTERNATIONAL FIRE CODE
(IFC)
2019 CALIFORNIA PLUMBING CODE (CPC) PART 5 TITLE 24, CCR BASED ON THE 2015 UNIFORM PLUMBING
CODE (UPC)
2019 CALIFORNIA MECHANICAL CODE (CMC) PART 4, TITLE 24, CCR BASED ON THE 2015 UNIFORM
MECHANICAL CODE (UMC)
2019 CALIFORNIA ELECTRICAL CODE (CEC) PART 3, TITLE 24, CCR BASED ON THE 2014 NATIONAL
ELECTRICAL CODE (NEC)
2019 CALIFORNIA BUILDING CODE (CBC) PART 2, TITLE 24, CCR BASED ON THE 2015 INTERNATIONAL
BUILDING CODE (IBC)
2019 CALIFORNIA ADMINISTRATIVE CODE (CAC)
PART 1, TITLE 24, CALIFORNIA CODE OF REGULATIONS (CCR)
2019 CALIFORNIA BUILDING CODES AS REFERENCED ONLY:
NFPA NO. 13 - INSTALLATION OF SPRINKLER SYSTEMS; 2016 EDITION, AS AMENDED
NFPA NO. 30 - FLAMMABLE AND COMBUSTIBLE LIQUID CODE; 2018 EDITION, AS AMENDED
NFPA NO. 70 - NATIONAL ELECTRICAL CODE; 2016 EDITION, AS AMENDED
NFPA NO. 72 - NATIONAL ALARM CODE; 2016 EDITION, AS AMENDED
NFPA NO. 99 - HEALTH CARE FACILITIES; 2015 EDITION, AS AMENDED...
APPICABLE NFPA STANDARDS
CODES
ARCHITECT
c|a ARCHITECTS
3633 LONG BEACH BOULEVARD, SUITE 200
LONG BEACH, CALIFORNIA 90807
(562) 595-5666
CIVIL/STRUCTURAL/MECHANICAL/PLUMBING/ELECTRICAL
IMEG
222 S. HARBOR BOULEVARD
SUITE 800
ANAHEIM, CALIFORNIA 92805
(626) 463-2800
SHEET INDEX
GENERAL
GI000 COVER SHEET
GI001 GENERAL NOTES, FIRE STOPPING NOTES, AND ICRA FORM
GI101 FIRST FLOOR FIRE LIFE SAFETY AND ACCESS EGRESS PLAN
CIVIL
C-0 TITLE SHEET
C-1 DEMOLITION PLAN
C-2 GRADING PLAN
C-3 UTILITY PLAN
C-4 EROSION CONTROL
C-5 DETAILS
C-6 SECTION & DETAILS
V-1 TOPOGRAPHIC SURVEY (REFERENCE ONLY)
ARCHITECTURAL
AE100 SITE PLAN
AD110 OUTDOOR FUEL CELL YARD DEMOLITION PLAN
AD111 GENERATOR AND SWITCHGEAR ROOM DEMOLITION PLAN
AE110 OUTDOOR GENERATOR YARD FLOOR PLAN
AE111 SWITCHGEAR ROOM, PARTIAL CHILLER ROOM, AND GRAPHIC CONTROL FLOOR PLAN
AE121 GENERATOR & SWITCHGEAR RM DEMOLITION RCP AND NEW RCP
AE190 ROOF PLAN
AE301 FUEL YARD ENLARGED PLANS AND SECTIONS
AI201 EXTERIOR ELEVATIONS
AJ500 DETAILS
AJ501 DETAILS AND SCHEDULES
STRUCTURAL
S000 GENERAL NOTES
S010 TYPICAL DETAILS
S011 TYPICAL DETAILS
S012 TYPICAL DETAILS
S013 TYPICAL DETAILS
S014 TYPICAL DETAILS
S201 OUTDOOR GENERATOR FOUNDATION PLAN
S202 PARTIAL PLANS
MECHANICAL
M001 MECHANICAL COVERSHEET
M002 MECHANICAL SCHEDULES
M100 OVERALL MECHANICAL SITE PLAN
MD111 ENLARGED CENTRAL PLANT - DEMOLITION
MD120 ENLARGED FUEL CELL FARM MECHANICAL PLAN - DEMOLITION
MD200 ENLARGED ROOF PLAN - DEMOLITION
M111 ENLARGED CENTRAL PLAN - REMODEL
M200 ENLARGED ROOF PLAN - REMODEL
M500 CONTROL AND DETAIL PLANS
PLUMBING
P000 PLUMBING SYMBOLS, ABBREV., NOTES AND SHEET INDEX
P001 PLUMBING SCHEDULES
PP120 PLUMBING GENERATOR FARM - REMODEL
PS100 OVERALL PLUMBING SITE PLAN
PS110 ENLARGED PLUMBING SITE PLAN
PD110 ENLARGED CENTRAL PLAN - DEMOLITION
PD120 ENLARGED FUEL CELL FARM - DEMOLITION
PD130 PLUMBING BASEMENT & FIRST FLOOR DEMOLITION PLANS
PP110 ENLARGED CENTRAL PLANT - REMODEL
PP510 PLUMBING DETAILS
PP520 PLUMBING DETAILS
PP610 FUEL OIL PIPING DIAGRAM
ELECTRICAL
E001 ELECTRICAL COVERSHEET
E002 ELECTRICAL COVERSHEET
EDS100 OVERALL ELECTRICAL SITE PLAN - DEMOLITION
EDL100 ENLARGED CENTRAL PLANT LIGHTING DEMOLITION PLAN
EDP100 ENLARGED CENTRAL PLANT POWER DEMOLITION PLAN
EDP110 ENLARGED FUEL CELL FARM POWER DEMOLITION PLAN
ED500 ELECTRICAL DEMOLITION SINGLE LINE DIAGRAM - MAIN DISTRIBUTION
ED510 ELECTRICAL DEMOLITION SINGLE LINE DIAGRAM - FUEL CELL
ES100 OVERALL ELECTRICAL SITE PLAN
ES110 ENLARGED ELECTRICAL SITE PLAN
EL100 ENLARGED CENTRAL PLANT LIGHTING PLAN
EL101 LIGHTING PHOTOMETRICS
EP100 ENLARGED CENTRAL PLANT POWER PLAN
EP110 ENLARGED GEN. FARM POWER PLAN AND GROUNDING SCHEME
EP111 ENLARGED MEZZANINE CENTRAL PLANT - POWER PLAN
EP112 ENLARGED BASEMENT AND FIRST FLOOR - POWER PLAN
EP200 ENLARGED ROOF POWER PLAN
E500 ELECTRICAL REMODEL SINGLE LINE DIAGRAM - MAIN DISTRIBUTION
E501 GEN. & FEEDER TYP. PROTECTION AND CNTL SCHEMANTICS
E502 PARALLEL SWITCHGEAR NOTES
E510 REMODEL RISER DIAGRAM - CENTRAL, GEN., & AREA P PLAN
E600 ELECTRICAL SCHEDULES
E700 ELECTRICAL DETAILS
E701 ELECTRICAL DETAILS
E702 ELECTRICAL DETAILS
E703 ELECTRICAL DETAILS
E704 ELECTRICAL DETAILS
E705 ELECTRICAL DETAILS
E706 ELECTRICAL DETAILS
E707 ELECTRICAL DETAILS
E708 ELECTRICAL DETAILS
E709 ELECTRICAL DETAILS
PROJECT TEAM
VICINITY MAP
SYMBOLS PROJECT DATA
U.S. DEPARTMENT OF VETERAN'S AFFAIRS
3. CONTRACTOR TO PROVIDE COMPLETE ITEMIZED SCHEDULE OF VALUES AS PART OF BID. SCHEDULE OF VALUES TO FOLLOW LATEST VERSION OF MASTER FORMAT. ALL CHANGES IN WORK AND PAYMENT REQUESTS ARE SUBJECT TO
SCHEDULE OF VALUES.
2. CONTRACTOR SHALL HIRE ALL REQUIRED 3RD PARTY INSPECTORS. INSPECTORS SHALL BE APPROVED BY VA AND
ARCHITECT. VA WILL PROVIDE 3RD PARTY INSPECTOR FOR ABATEMENT ONLY.
1. PRODUCTS, MATERIALS, AND FIXTURES LISTED HEREIN ARE A BASIS OF DESIGN, UNLESS OTHERWISE NOTED, AND THEREFORE MAY BE SUBSTITUTED BY A VA AND ARCHITECT APPROVED EQUAL PRODUCT UPON REQUEST BY CONTRACTOR. ANY COST ASSOCIATED WITH REDESIGN AND CONSTRUCTION, INCLUDING OTHER AFFECTED ITEMS SHALL BE CONTRACTOR RESPONSIBILITY. REFER TO SPECIFICATION FOR SUBSTITUTION REQUEST PROCEDURES.
FACILITY NOTES
PROJECT LOCATION
GENERATOR FARM & SWITCHGEAR UPGRADE
11201 BENTON STREET
LOMA LINDA, CA 92357
DEFERRED APPROVAL
Revisions: Date:
65% DESIGN DEVELOPMENT 07.01.2021
35% SCHEMATIC DESIGN 02.26.2021
95% DESIGN DEVELOPMENT 08.30.2021
100% CONSTRUCTION DOCUMENTS 10.12.2021
01 GENERAL
1. ALL WORK SHALL CONFORM TO LISTED BUILDING CODES AND ALL APPLICABLE STATE
AND MUNICIPAL ORDINANCES AND ALL OTHER RULES AND REGULATIONS HAVING
JURISDICTION OVER THIS PROJECT. IN THE EVENT THAT TWO OR MORE REGULATIONS
CONFLICT, THE MORE RESTRICTIVE SHALL GOVERN.
2. FOR CONSTRUCTION PURPOSES, USE NOTED DIMENSIONS ONLY. DO NOT SCALE
DRAWINGS.
3. EXERCISE CARE TO PREVENT DAMAGE TO EXISTING EQUIPMENT, STRUCTURES AND
SERVICES. DAMAGE AS A RESULT OF THIS WORK SHALL BE REPAIRED OR REPLACED AT
NO ADDITIONAL COST TO THE OWNER.
4. VERIFY THE PRECISE LOCATIONS OF ALL EQUIPMENT WITH THE OWNER PRIOR TO THE
INSTALLATION OF THAT EQUIPMENT OR THE SERVICES THAT SUPPORT IT.
5. IT IS HEREBY UNDERSTOOD THAT THE HOSPITAL MUST MAINTAIN IT'S REGULAR
SERVICE DURING THE TIME WORK IS IN PROGRESS. ADVANCE SCHEDULING WITH THE
ENGINEERING DEPARTMENT SHALL BE ARRANGED BY THE CONTRACTOR TO ENSURE
NO DISRUPTION TO FACILITY SERVICES. SOME WORK MAY BE REQUIRED ON NIGHTS
AND WEEKENDS.
6. UPON COMPLETION OF EACH PHASE OF THE WORK AND AT SUCH TIMES AS DIRECTED
BY THE OWNER, REMOVE ALL SURPLUS MATERIAL, TOOLS AND DEBRIS AND LEAVE THE
SITE IN A CLEAN AND NEAT CONDITION.
7. PROVIDE PROTECTION FROM DUST, DIRT AND MOISTURE FOR THE PROTECTION OF THE
WORKMEN, STAFF, PATIENTS, THE PUBLIC AND EXISTING COMPUTER EQUIPMENT AS
REQUIRED BY ALL PERTINENT CODES, REGULATIONS, AND FACILITY STANDARDS.
8. THE INTENT OF THE CONSTRUCTION DOCUMENTS IS TO CONSTRUCT THE PROJECT IN
ACCORDANCE WITH THE 2019 CBC AND NFPA CODES AS APPLICABLE TO THIS PROJECT.
SHOULD ANY CONDITION DEVELOP NOT COVERED BY THE APPROVED CONSTRUCTION
DOCUMENTS, WHEREIN THE FINISHED WORK WILL NOT COMPLY WITH THE 2019 CBSC,
AMENDED CONSTRUCTION DOCUMENTS (ACDs) DETAILING AND SPECIFYING THE
REQUIRED WORK SHALL BE SUBMITTED FOR VA REVIEW AND ACCEPTANCE PRIOR TO
INSTALLATION.
9. DIMENSIONS: ALL DIMENSIONS ARE TO FACE OF STUD (F.O.S.) OR CENTER LINE OF
STUD UNLESS NOTED OTHERWISE.
10. CHANGES IN LEVEL ON ACCESSIBLE ROUTE SHALL CONFORM WITH SECTION 11B-303 OF
THE 2019 CALIFORNIA BUILDING CODE AND ABA STANDARDS WITH VA AMENDMENTS.
11. CONTRACTOR SHALL COORDINATE WITH FACILITY TO MAINTAIN CONTINUOUS
ESSENTIAL SERVICES DURING CONSTRUCTION.
12. DO NOT CUT, NOTCH, DRILL, OR ALTER STRUCTURAL ELEMENTS UNLESS SPECIFICALLY
DETAILED ON APPROVED PLANS OR OTHERWISE ACCEPTED BY COR AND SEOR.
13. ALL ANCHORAGE EXPOSED TO WEATHER MUST BE STAINLESS STEEL OR HOT DIPPED
GALVANIZED.
14. UTILITY SHUTDOWNS REQUIRE A MINIMUM 21 DAY NOTICE TO THE COR. THE
CONTRACTOR SHALL COORDINATE WITH THE VA PROJECT MANAGER ALL UTILITY
SHUTDOWNS A MINIMUM OF 21 DAYS BEFORE THE REQUIRED SHUTDOWN.
15. AN INFECTION CONTROL PERMIT (ICRA) MUST BE OBTAINED PRIOR TO BEGINNING OF
ANY CONSTRUCTION ACTIVITY. ALL REQUIREMENTS MUST BE MET BY GENERAL
CONTRACTOR. SEE SAMPLE ICRA ON THIS PAGE FOR REFERENCE.
16. THE CONTRACTOR SHALL COORDINATE WITH THE COR ALL WORK TO BE
ACCOMPLISHED IN OCCUPIED SPACES. A MINIMUM OF 21 DAYS NOTICE SHALL BE GIVEN
PRIOR TO STARTING THE WORK.
17. NO OVERCUTTING OF THE EXISTING CONCRETE SLAB SHALL BE ALLOWED.
18. TESTING LAB SHALL BE PROVIDED BY THE CONTRACTOR PENDING THE APPROVAL OF
THE V.A. THE TESTING LAB SHALL BE ISSUED AS A SUBMITTAL FOR REVIEW AN
APPROVAL.
19. WHERE POSSIBLE EXISTING UTILITIES SHALL BE RELOCATED TO ALLOW FOR
INSTALLATION OF THE NEW WORK.
20. ALL PIPING, CONDUIT, DUCTWORK AND PENETRATIONS THROUGH FIRE RATED OR
SMOKE WALLS SHALL BE FIRE STOPPED. SEE SHEET 1 FOR FIRESTOPPING
SYSTEMS.
21. ANY CHANGES MUST BE APPROVED BY THE CONTRACTING OFFICER BEFORE DOING
ANY ADDITIONAL WORK. WORK TO BE SCHEDULED DURING REGULAR DAY HOURS.
22. FOR ACCESSIBLE HEIGHTS REQUIRED IN THIS PROJECT, REFER TO
02 EXISTING CONDITIONS
1. VERIFY ALL CONDITIONS AND DIMENSIONS AT THE JOB SITE AND NOTIFY THE
ARCHITECT OF ANY DEVIATION FROM THE CONDITIONS PRESENTED HEREIN. FAILURE
TO DO SO SHALL CONSTITUTE ACCEPTANCE OF THE EXISTING CONDITIONS AND ANY
ADDITIONAL WORK REQUIRED SHALL BE ACCOMPLISHED AT NO ADDITIONAL COST TO
THE OWNER.
2. SALVAGE MATERIALS NOT SCHEDULED FOR REUSE SHALL BE STORED OR DISPOSED
OF AS INSTRUCTED BY THE OWNER.
3. DEMOLITION PLAN AND NOTES ARE INCLUDED FOR GENERAL INFORMATION ONLY AND
ARE NOT INTENDED TO REPRESENT ALL CONDITIONS PRESENT AT THE SITE. THE
CONTRACTOR IS RESPONSIBLE FOR PREPARING THE SITE FOR CONSTRUCTION AS
DESCRIBED AND DETAILED IN THE CONTRACT.
4. WHENEVER CUTTING, PATCHING, ETC. IS REQUIRED, ALL ADJACENT SURFACES SHALL
BE FINISHED TO ACHIEVE A MATCHING SURFACE CONDITION. SAW CUTTING AND CORE
DRILLING SHALL BE USED IN LIEU OF JACK HAMMERING.
5. ASBESTOS OR HAZARDOUS MATERIALS. IT IS UNDERSTOOD AND AGREED THAT THIS
CONTRACT DOES NOT CONTEMPLATE THE HANDLING OF ASBESTOS OR ANY
HAZARDOUS MATERIALS. IF ASBESTOS OR ANY HAZARDOUS MATERIALS IS
ENCOUNTERED, NOTIFY THE OWNER'S REPRESENTATIVE IMMEDIATELY. DO NOT
DISTURB, HANDLE OR ATTEMPT TO REMOVE.
07 THERMAL AND MOISTURE PROTECTION
1. SEAL PENETRATIONS THROUGH RATED WALLS AND FLOORS WITH A MATERIAL
CAPABLE OF PREVENTING THE PASSAGE OF FLAMES AND HOT GASES WHEN SUBJECT
TO THE REQUIREMENTS OF THE TEST STANDARD: SPECIFIC OF FIRE STOPS ASTM E-814.
2. SEE DETAIL FOR FIRE STOPPING SCHEDULE. CONTRACTOR TO PROVIDE
FIRESTOPPING SUBMITTAL TO ARCHITECT OF RECORD FOR REVIEW AND APPROVAL.
SUBMITTAL SHALL INCLUDE FIRESTOPPING DETAILS (WITH APPROVED UL REFERENCE)
COORDINATED WITH A LOCATION FLOOR PLAN. SUBMITTAL TO INCLUDE ENGINEERING
JUDGEMENT IF REQUIRED, SIMILAR FOR FIRE PROOFING PROVISIONS IF NECESSARY.
3. WHERE PROVIDED, THROUGH-PENETRATION FIRESTOP SYSTEM AND MEMBRANE
PENETRATION DETAILS ARE FOR REFERENCE ONLY. THROUGH-PENETRATIONS AND
MEMBRANE PENETRATIONS SHALL BE PROTECTED BY AN APPROVED PENETRATION
FIRESTOP SYSTEM OR MEMBRANE PENETRATION FIRESTOP SYSTEM INSTALLED AS
TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM POSITIVE
PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA) OF WATER OR AS OTHERWISE
PERMITTED BY CBC, SECTION 714. LISTED THROUGH-PENETRATION FIRESTOP SYSTEMS
AND MEMBRANE PENETRATIONS SHALL BE INSTALLED IN ACCORDANCE WITH THE
INSTALLATION DETAILS FOR LISTED SYSTEMS. LISTED THROUGH-PENETRATION
FIRESTOP SYSTEMS, MEMBRANE PENETRATION PROTECTION AND OTHER PERMITTED
MEANS AND METHODS OF PENETRATION PROTECTION SHALL BE SUBMITTED TO COR
FOR REVIEW AND ACCEPTANCE PRIOR TO INSTALLATION.
4. SEE FIRE-STOPPING REQUIREMENTS SECTION ON THIS PAGE FOR ADDITIONAL
INFORMATION.
08 OPENINGS
1. MAXIMUM EFFORT TO OPEN DOORS SHALL BE: 5 LBS. INTERIOR, 5 LBS. EXTERIOR, AND
15 LBS AT FIRE DOORS.
2. HAND-ACTIVATED HARDWARE SHALL BE CENTERED BETWEEN 34 INCHES AND 44
INCHES ABOVE THE FLOOR. LATCHING AND LOCKING DOORS THAT ARE HAND-
ACTIVATED AND WHICH ARE IN A PATH OF TRAVEL, SHALL BE OPERABLE WITH A SINGLE
EFFORT BY HARDWARE DESIGNED TO PROVIDE PASSAGE WITHOUT REQUIRING THE
ABILITY TO GRASP.
3. ACCESS DOORS - PROVIDE ACCESS DOORS IN ALL HARD CEILINGS CONTAINING
JUNCTION BOXES AND/OR VALVES. LABEL ALL ACCESS DOORS AS TO VALVES LOCATED
ABOVE. NOTIFY HOSPITAL ENGINEERING DEPARTMENT PRIOR TO CLOSING UP CEILING
FOR FINAL REVIEW.
GENERAL NOTES
/1 AJ500
09 FINISHES
1. FINISH MATERIALS IN EXIT WAYS, CORRIDORS, ROOMS AND ENCLOSED SPACES OF
SPRINKLERED BUILDINGS SHALL HAVE A FLAME SPREAD OF 75 OR LESS (CLASS B)
AND A SMOKE DEVELOPMENT OF 450 OR LESS (CLASS B). FINISH MATERIALS IN EXIT
WAYS AND CORRIDORS OF NON-SPRINKLERED BUILDINGS SHALL HAVE A FLAME
SPREAD OF 25 OR LESS (CLASS A) AND A SMOKE DEVELOPMENT OF 450 OR LESS
(CLASS A) AND IN ROOMS AND ENCLOSED SPACES FLAME SPREAD OF 75 OR LESS
(CLASS B) AND A SMOKE DEVELOPMENT OF 450 OR LESS (CLASS B). PER NFPA 10.2.
2. PAINT SHALL BE THE PRODUCT OF ONE MANUFACTURER AND SHALL BE DELIVERED
TO JOB SITE IN SEALED CONTAINERS.
3. PAINT SHALL BE CONSIST OF MINIMUM TWO (2) COAT APPLICATION AND
APPROPRIATE SEALER.
4. RECESSED MOUNTED FIXTURES IN RATED WALLS/CEILINGS SHALL BE BACK BOXED
WITH MATERIALS EQUAL TO RATED WALL ASSEMBLY.
5. CEILINGS SHALL BE SMOOTH, EASILY CLEANED WITH NO ROUGH TEXTURES.
FLOORS SHALL BE SMOOTH, WATERPROOF AND DURABLE.
6. INTERIOR WALL FINISHES SHALL BE SMOOTH, WATERPROOF AND DURABLE.
7. GYPSUM BOARD SHALL BE PRIMED PRIOR TO INSTALLATION OF CASEWORK.
8. SET ALL TOPSET BASE ON SHEET VINYL IN A CONTINUOUS BEAD OF WATER
RESISTANT CAULKING.
26 ELECTRICAL
1. 6'-0" MAX. FLEX CONDUIT WILL BE ALLOWED ABOVE LAY-IN CEILINGS FOR LIGHT
FIXTURES ONLY.
2. VERIFY AND PROVIDE SPRAY PAINTED EMERGENCY CIRCUIT CONDUIT AND BOXES
PER FACILITY STANDARD COLOR.
3. VERIFY AND PROVIDE SPRAY PAINTED FIRE ALARM CIRCUIT CONDUIT AND BOXES
PER FACILITY STANDARD COLOR.
4. ELECTRICAL COVER PLATES SHALL HAVE CIRCUIT NUMBERS AND PANELS
ENGRAVED IN COVER PLATES.
5. LABEL ALL JUNCTION BOXES AS TO CIRCUIT NUMBERS LOCATED WITHIN.
6. FLEXIBLE CONDUIT CAN BE USED FOR LOW VOLTAGE WIRING.
STORM WATER POLLUTION CONTROL REQUIREMENTS FOR CONSTRUCTION
ACTIVITIES MINIMUM WATER QUALITY PROTECTION REQUIREMENTS FOR ALL
DEVELOPMENT CONSTRUCTION PROJECTS/CERTIFICATION STATEMENT
THE FOLLOWING IS INTENDED AS MINIMUM NOTES OR AS AN ATTACHMENT FOR BUILDING
AND GRADING PLANS AND REPRESENT THE MINIMUM STANDARD OF GOOD HOUSEKEEPING
THAT MUST BE IMPLEMENTED ON ALL CONSTRUCTION SITES REGARDLESS OF SIZE.
(APPLIES TO ALL PERMITS)
• ERODED SEDIMENTS AND OTHER POLLUTANTS MUST BE RETAINED ON SITE AND MAY
NOT BE TRANSPORTED FROM THE SITE VIA SHEETFLOW, SWALES, AREA DRAINS,
NATURAL DRAINAGE COURSES OR WIND.
• STOCKPILES OF EARTH AND OTHER CONSTRUCTION RELATED MATERIALS MUST BE
PROTECTED FROM BEING TRANSPORTED FROM THE SITE BY THE FORCES OF WIND OR
WATER.
• FUELS, OILS, SOLVENTS AND OTHER TOXIC MATERIALS MUST BE STORED IN
ACCORDANCE WITH THEIR LISTING AND ARE NOT TO CONTAMINATE THE SOIL AND
SURFACE WATERS. ALL APPROVED STORAGE CONTAINERS ARE TO BE PROTECTED
FROM THE WEATHER. SPILLS MUST BE CLEANED UP IMMEDIATELY AND DISPOSED OF IN
A PROPER MANNER. SPILLS MAY NOT BE WASHED INTO THE DRAINAGE SYSTEM.
• NON-STORMWATER RUNOFF FROM EQUIPMENT AND VEHICLE WASHING AND ANY
OTHER ACTIVITY SHALL BE CONTAINED AT THE PROJECT SITE.
• EXCESS OR WASTE CONCRETE MAY NOT BE WASHED INTO THE PUBLIC WAY OR ANY
OTHER DRAINAGE SYSTEM. PROVISIONS SHALL BE MADE TO RETAIN CONCRETE
WASTES ON SITE UNTIL THEY CAN BE DISPOSED OF AS SOLID WASTE.
• TRASH AND CONSTRUCTION RELATED SOLID WASTES MUST BE DEPOSITED INTO A
COVERED RECEPTACLE TO PREVENT CONTAMINATION OF RAINWATER AND DISPERSAL
BY WIND
• SEDIMENTS AND OTHER MATERIALS MAY NOT BE TRACKED FROM THE SITE BY VEHICLE
TRAFFIC. THE CONSTRUCTION ENTRANCE ROADWAYS MUST BE STABILIZED SO AS TO
INHIBIT SEDIMENTS FROM BEING DEPOSITED INTO THE PUBLIC WAY. ACCIDENTAL
DEPOSITIONS MUST BE SWEPT UP IMMEDIATELY AND MAY NOT BE WASHED DOWN BY
RAIN OR OTHER MEANS.
• ANY SLOPES WITH DISTURBED SOILS OR DENUDE D OF VEGETATION MUST BE
STABILIZED SO AS TO INHIBIT EROSION BY WIND AND WATER
• OTHER:____________________________________________________________________
AS THE PROJECT OWNER OR AUTHORIZED AGENT OF THE OWNER, I HAVE READ
AND UNDERSTAND THE REQUIREMENTS LISTED ABOVE, NECESSARY TO CONTROL STORM
WATER POLLUTION FROM SEDIMENTS, EROSION, AND CONSTRUCTION MATERIALS, AND I
CERTIFY THAT I WILL COMPLY WITH THESE REQUIREMENTS.
PRINT NAME:______________________________________________________________________
OWNER OR AUTHORIZED AGENT OF THE OWNER
SIGNATURE:____________________________________________________ DATE:_____________
(OWNER OR AUTHORIZED AGENT OF THE OWNER)
BEST MANAGEMENT PRACTICES
FOR CONSTRUCTION ACTIVITIES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
605 -19 - 400
EMERGENY GENERATOR
FARM
11201 BENTON STREET
LOMA LINDA, CA 92357
100% CONSTRUCTION
DOCUMENTS
c|a ARCHITECTS expressly reserves its common law copyright and other property rights in these plans. These plans are not to be reproduced, changed or copied in any form or manner,nor are they to be assigned to any third party without first obtaining the written consent of c|a ARCHITECTS, Inc. COPYRIGHT ©
3633 LONG BEACH BLVD., SUITE 200
T 562.595.5666 | F 562.595.5577
LONG BEACH, CA 90807
www.c-a ARCHITECTS.com
C|A #1474.01
D R
A W
IN
G
N A
M E
P L O
T D
A T
E
P L O
T T
E D
B Y
/1 /2
:2
:5
P M
/1 /2
:2 :5
P
M
B
IM
/1
.0
E m e rg e n c y G e n e ra to r
F a rm
/1 .0
-A
-B M
R
.r v t
GI001
GENERAL NOTES, FIRE STOPPING
NOTES, AND ICRA FORM
Approver
Checker Author08/30/2021
A u th o r
ICRA - FOR REFERENCE ONLY
Revisions: Date:
DN
8.5 87.98.6
7 6 5 4 3 2 1
E.5
F
G
H
J
K
K.1
L
G.2
G.5
G.6
H.4
H.5
8.3
F.1
FIRE ZONE
2-9-2
COMPACTOR
1D -10
BOILER
RM
1D -16
BOILERS/CHILLERS
RM
1D -17
GENERATOR
1D -19
EQUIP
RM
1D-01
SERVBAY
SB01-6
SERVBAY
SB01-4
SHELL
SPACE
1D-01A
GENERAL NOTES
1. THE FOLLOWNG CODES ARE USED FOR THE BASIS OF DESIGN FOR THIS PROJECT
BUT ARE NOT LIMITED TO:
A. IBC
B. NFPA 101
C. NEC
D. NFPA 80
E. NFPA 110
F. IMC
G. IPC
H. VA MANUAL H-18-8
I. ASCE-7
2. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING AND USING THE MOST
CURRENT APPLICABLE CODE EDITION.
3. WHERE CONFLICTS EXIST BETWEEN CODES, THE CODE SPECIFIED IN THE VA FIRE
PROTECTION DESIGN GUIDE SHALL BE FOLLOWED. FIRE PROTECTION FEATURES
NOT ADDRESSED IN THE NATIONAL FIRE CODES SHALL BE DESIGNED TO COMPLY
WITH THE 2018 IBC OR AS OTHERWISE ADDRESSED IN THE DESIGN GUIDE.
EGRESS PATH OF TRAVEL
EXIT DISCHARGE
FIRE/LIFE SAFETY LEGEND
2 HOUR SMOKE BARRIER.
GROUP 1-2/ SMOKE COMPARTMENTS.
90-MINUTE DOORS.
2 HOUR FIRE BARRIER.
SHAFT ENCLOSURE WALL/ VERTICAL EXIT
ENCLOSURE WALL.
90-MINUTE DOORS. NO WINDOWS PERMITTED.
1 HOUR FIRE BARRIER.
CARE SUITE WALL/ INCIDENTAL USE
SEPARATION WALL.
45-MINUTE DOORS. 45-MINUTE WINDOWS.
DESCRIPTIONSYMBOL
NFPA 101 19.3.7.6
CODE SECTION
NOT IN SCOPE
NFPA 101 7.2.3.5
NFPA 101 19.3.2.1
NFPA 101 7.5
NFPA 101 A.7.6
NFPA 101 19.3.2.1
2 HOUR OCCUPANCY SEPARATION NFPA 101 6.1.14.4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
605 -19 - 400
EMERGENY GENERATOR
FARM
11201 BENTON STREET
LOMA LINDA, CA 92357
100% CONSTRUCTION
DOCUMENTS
c|a ARCHITECTS expressly reserves its common law copyright and other property rights in these plans. These plans are not to be reproduced, changed or copied in any form or manner,nor are they to be assigned to any third party without first obtaining the written consent of c|a ARCHITECTS, Inc. COPYRIGHT ©
3633 LONG BEACH BLVD., SUITE 200
T 562.595.5666 | F 562.595.5577
LONG BEACH, CA 90807
www.c-a ARCHITECTS.com
C|A #1474.01
D R
A W
IN
G
N A
M E
P L O
T D
A T
E
P L O
T T
E D
B Y
/1 /2
:2
:4
P M
/1 /2
:2 :4
P
M
B
IM
/1
.0
E m e rg e n c y G e n e ra to r
F a rm
/1 .0
-A
-B M
R
.r v t
GI101
FIRST FLOOR FIRE LIFE SAFETY
AND ACCESS EGRESS PLAN
Approver
Checker Author08/30/2021
A u th o r
1/16" = 1'-0" 1FIRST FLOOR FIRE/ LIFE SAFETY AND ACCESS/ EGRESS PLAN
N
Revisions: Date:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
6/
/2
:3 9:
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
11201 BENTON STREET, LOMA LINDA, CA 92357
3633 LONG BEACH BLVD., SUITE 200 LONG BEACH, CA 90807
T 562.595.5666 | F 562.595.5577 www.c-aarchitects.com
DESIGNING HEALTHCARE
65% DESIGN DEVELOPMENT
35% SCHEMATIC DESIGN
605 -19 - 400EMERGENY GENERATOR
FARM C|A #1474.01
1PRELIMINARY
NOT FOR
CONSTRUCTION
07.01.2021 02.26.2021
95% DESIGN DEVELOPMENT 08.30.2021
100% CONSTRUCTION DOCUMENTS 10.12.2021
ENGINEER'S NOTICE TO CONTRACTOR
THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITY PIPES OF STRUCTURES SHOWN ON
THESE PLANS WERE OBTAINED BY A SEARCH OF AVAILABLE RECORDS. THESE LOCATIONS ARE
APPROXIMATE AND SHALL BE CONFIRMED IN FIELD BY THE CONTRACTOR, SO THAT ANY NECESSARY ADJUSTMENT CAN BE MADE IN ALIGNMENT AND/OR GRADE OF THE PROPOSED IMPROVEMENT. THE CONTRACTOR IS REQUIRED TO TAKE DUE PRECAUTIONARY MEASURE TO PROTECT ANY UTILITY LINES
SHOWN AND ANY OTHER LINES NOT OF RECORD OR NOT SHOWN ON THESE PLANS.
THE DESIGN OF THE IMPROVEMENTS SHOWN ON THESE PLANS IS BASED ON THE AS-BUILT PLANS (CITY ID NO. LDR13-0015) DATED 8/25/14 PREPARED BY THIENES ENGINEERING, INC. THE CONTRACTOR SHALL VERIFY THE EXISTING CONDITIONS AND JOIN GRADES IN FIELD AND NOTIFY THE ENGINEER OF ANY
DISCREPANCIES PRIOR TO BID.
STANDARD GENERAL GRADING NOTES
1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THESE PLANS AND STANDARD SPECIFICATIONS
FOR PUBLIC WORKS CONSTRUCTION, LATEST EDITION WITH SPECIFICATIONS FOR PUBLIC WORKS
CONSTRUCTION, LATEST EDITION WITH SUPPLEMENTS, AND THE STANDARD PLANS AND
SPECIFICATIONS OF THE CITY OF LOMA LINDA.
2. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO FAMILIARIZE HIMSELF WITH THE JOB
SITE AND THE LOCATION OF ALL UNDERGROUND FACILITIES SHOWN OR NOT SHOWN ON THESE
PLANS. NEITHER THE CITY OF LOMA LINDA NOR THE ENGINEER WILL BE RESPONSIBLE FOR ANY
DAMAGE TO UNDERGROUND FACILITIES.
3. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO OBTAIN ALL OF THE NECESSARY PERMITS.
4. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO CALL ENGINEER'S OFFICE AT 799-2870 FOR
INSPECTION 24 HOURS PRIOR TO PERFORMING ANY WORK. WORK PERFORMED WITHOUT
CALLING FOR INSPECTION SHALL BE REJECTED AND SHALL BE REMOVED SOLELY AT THE
CONTRACTOR'S EXPENSE.
5. UTILITY CONTRACTORS SHALL BE RESPONSIBLE FOR OBTAINING COMPACTION TESTS OF ALL
TRENCH BACK FILL AND SUBMITTING THEM TO THE CITY ENGINEER FOR APPROVAL. NOTIFY
ENGINEER'S OFFICE AT 799-4400, 24 HOURS PRIOR TO TEST.
6. THE STRUCTURAL SECTIONS SHOWN ON THESE PLANS ARE TENTATIVE. AT THE COMPLETION OF
ROUGH GRADING, A MATERIAL REPORT AND THE PROPOSED STRUCTURAL SECTION SHALL BE
SUBMITTED BY THE TRACT ENGINEER TO THE CITY ENGINEER FOR REVIEW AND EVALUATION,
APPROVAL WILL BE GIVEN WHEN ALL STRUCTURAL SECTION REQUIREMENTS HAVE BEEN MET.
7. CUT SHEETS SHALL BE PREPARED BY THE DEVELOPER'S ENGINEER AND SUBMITTED TO THE CITY
ENGINEER. NO CONSTRUCTION SHALL BE ALLOWED PRIOR TO THE ENGINEER'S APPROVAL OF
THE CUT SHEETS.
8. LOCATIONS OF DRIVEWAY APPROACHES SHALL BE ADDED BY REVISIONS. ANY WATER OR SEWER
LATERALS CONSTRUCTED AT DRIVEWAY APPROACH LOCATIONS SHALL BE RELOCATED AT THE
CONTRACTOR'S EXPENSE.
9. THE CONTRACTOR SHALL SATISFY HIMSELF THAT THE ESTIMATED QUANTITIES SHOWN ARE
CORRECT BEFORE BIDDING ON ANY ITEM.
10. THE CONTRACTOR SHALL MAINTAIN DUST CONTROL AT ALL TIMES.
11. ALL EXISTING PAVEMENT TO BE REMOVED SHALL BE SAW CUT OR WHEEL CUT AND REMOVED TO
CLEAN STRAIGHT LINES.
12. AT ALL LOCATIONS WHERE NEW PAVEMENT JOINS EXISTING, THE EXISTING PAVEMENT SHALL BE
CLEANED AND COATED WITH ASPHALTIC EMISSION.
13. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF ALL UTILITY VALVES, BOXES AND
COVERS, AND ADJUSTING OF ALL CITY WATER VALVE BOXES AND COVERS TO FINISH GRADE.
14. THE CONTRACTOR SHALL RESET MANHOLE RINGS TO SURROUNDING A.C. PAVEMENT GRADE.
15. THE PRIVATE ENGINEER SIGNING THESE PLANS IS RESPONSIBLE FOR THE ACCURACY AND
ACCEPTABILITY OF THE WORK HEREON. IN THE EVENT OF DISCREPANCIES ARISING DURING
CONSTRUCTION, THE PRIVATE ENGINEER SHALL BE RESPONSIBLE FOR DETERMINING AN
ACCEPTABLE SOLUTION AND REVISING THE PLANS FOR APPROVAL OF THE CITY ENGINEER.
16. THE CONTRACTOR SHALL CALL IN A LOCATION REQUEST TO UNDERGROUND SERVICE ALERT
(USA), PHONE NUMBER 1-800-227-2600, TWO WORKING DAYS BEFORE DIGGING. NO INSPECTION WILL BE PROVIDED BY THE CITY ENGINEER'S OFFICE, AND NO CONSTRUCTION PERMIT ISSUED BY
THE PUBLIC WORKS DEPARTMENT INVOLVING EXCAVATION FOR UNDERGROUND FACILITIES WILL
BE VALID UNLESS THE APPLICANT HAS BEEN PROVIDED AN INQUIRY IDENTIFICATION NUMBER BY
USA.
17. ALL ACTIVE IRRIGATION LINES ENCOUNTERED DURING CONSTRUCTION SHALL BE REPLACED
WITH 10 GAGE DOUBLE DIPPED AND WRAPPED-WELDED STEEL PIPE.
18. OBSERVANCE OF THE CONTRACTOR'S WORK BY REPRESENTATIVES OF THE ENGINEER'S OFFICE SHALL NOT RELIEVE THE CONTRACTOR OF THE FINAL AND ULTIMATE RESPONSIBILITY FOR THE
CONSTRUCTION OF THE IMPROVEMENTS IN ACCORDANCE WITH THESE PLANS AND ANY
REFERENCED SPECIFICATIONS, STANDARD DRAWINGS, OR DETAILS.
GENERATOR FARM & SWITCHGEAR UPGRADE
LOMA LINDA, CA 92357
ASPH ASPHALT
AVE AVENUE
BLDG BUILDING
BLVD BOULEVARD
BC BACK OF CURB
BW BOTTOM OF WALL
C&G CURB AND GUTTER
CL CENTERLINE
CONC CONCRETE
CY CUBIC YARD
DEMO DEMOLISH
DIA DIAMETER
DRV DRIVEWAY
E-E EDGE TO EDGE
EL ELEVATION
EP EDGE OF PAVEMENT
EX EXISTING
FF FINISH FLOOR
FL FLOWLINE
FS FINISH SURFACE
GB GRADE BREAK
GUT GUTTER
LF LINEAL/LINEAR FEET
PCC PORTLAND CEMENT CONCRETE
PR PROPOSED
PVMT PAVEMENT
R RADIUS
RD ROAD
SF SQUARE FEET
ST STREET
STD STANDARD
SW SIDEWALK
TC TOP OF CURB
TEMP TEMPORARY
TW TOP OF WALL
UG UNDERGROUND
UTILITY NOTE
THE LOCATIONS OF THOSE BURIED AND ABOVE GROUND UTILITIES SHOWN ARE APPROXIMATE, ARE
SHOWN CONTRACTOR INFORMATIONAL USE ONLY, AND ARE NOT TO BE REFERENCED FOR
CONSTRUCTION PURPOSES. THE IMPLIED PRESENCE OR ABSENCE OF UTILITIES IS NOT TO BE
CONSTRUED BY THE OWNER, ENGINEER, CONTRACTOR, OR SUBCONTRACTORS TO BE AN ACCURATE AND COMPLETE REPRESENTATION OF UTILITIES THAT MAY OR MAY NOT EXIST ON THE CONSTRUCTION SITE. BURIED AND ABOVE GROUND UTILITY LOCATION, IDENTIFICATION, AND MARKING ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR, REROUTING, DISCONNECTION, PROTECTION, ETC. OF ANY UTILITY MUST BE COORDINATED BETWEEN THE CONTRACTOR, UTILITY COMPANY, AND OWNER. SITE SAFETY, INCLUDING THE AVOIDANCE OF HAZARDS ASSOCIATED WITH BURIED AND ABOVE GROUND
UTILITES, REMAINS THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
BASIS OF BEARING
THE BASIS OF BEARINGS FOR THIS SURVEY IS BASED ON LOCAL
CONTROL POINTS PROVIDED TO THE SURVEYOR BY THE CLIENT.
SURVEYOR MAKES NO REFERENCE AS TO ITS SOURCE AND MAKES NO
CLAIMS TO ITS ACCURACY AND COMPLETENESS.
IN ADDITION TO THE LOCAL CONTROL POINTS PROVIDED, THE
FOLLOWING STATEMENT WAS ALSO SUPPLIED TO THE SURVEYOR. THIS
INFORMATION IS FOR REFERENCE ONLY AND HAS NOT BEEN SURVEYED
OR VERIFIED BY THE SURVEYOR.
"BASIS OF BEARING -
THE CALCULATED BEARING BETWEEN MLFP AND GISA PER NGS DATA
SHEET LOCATIONS
I.E. N28°24'17E
NOTE: RTK DATA WAS SCALED TO GROUND USING LOCAL CONTROL
POINTS."
BENCHMARK
THE BENCHMARK FOR THIS SURVEY IS BASED ON LOCAL CONTROL
POINTS PROVIDED TO THE SURVEYOR BY THE CLIENT. SURVEYOR
MAKES NO REFERENCE AS TO ITS SOURCE AND MAKES NO CLAIMS TO
ITS ACCURACY AND COMPLETENESS.
IN ADDITION TO THE LOCAL CONTROL POINTS PROVIDED, THE
FOLLOWING STATEMENT WAS ALSO SUPPLIED TO THE SURVEYOR. THIS
INFORMATION IS FOR REFERENCE ONLY AND HAS NOT BEEN SURVEYED
OR VERIFIED BY THE SURVEYOR.
"BENCHMARK-
CITY OF LOMA LINDA VERTICAL BENCHMARK LLBM-81-14 FOUND BRASS
CAP IN CONCRETE 2' N.E OF STREET SIGN IN CONCRETE SIDEWALK AT
THE SOUTH END OF THE INTERSECTION OF TULIP AVENUE AND
HILLCREST STREET ELEVATION - 1177.938' "
VICINITY MAP
SHEET INDEX
C-0 TITLE SHEET
C-1 DEMOLITION PLAN
C-2 GRADING PLAN
C-3 UTILITY PLAN
C-4 EROSION CONTROL
C-5 DETAILS
C-6 SECTION & DETAILS
V-1 TOPOGRAPHIC SURVEY
(REF ONLY)
C-0
TITLE SHEET
CMC RKL08/30/2021
PH: 909.477.6915
FAX: 909.477.6916
www.imegcorp.com
901 VIA PIEMONTE
SUITE 400
ONTARIO, CA 91764
PROJECT LOCATION
CONTACTS
DEPARTMENT OF VETERANS AFFAIRS MEDICAL CENTER
11201 BENTON ST
LOMA LINDA, CA 92357
OWNER
ARCHITECT
CIVIL ENGINEER
IMEG CORP
222 S HARBOR BLVD. #800
ANAHEIM, CA 92805
T.714.490.5555 | F.626.463.2801
WWW.IMEGCORP.COM
C|A ARCHITECTS
3633 LONG BEACH BLVD., SUITE 200
LONG BEACH, CA 90807
T.562.595.5666 | F.562.595.5577
WWW.C-AARCHITECTS.COM
ABBREVIATIONS
UNLESS OTHERWISE MODIFIED BELOW, ABBREVIATIONS SHALL BE PER THE STANDARD
SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION (SSPWC), THE STAND PLANS FOR
PUBLIC WORKS CONTSTRUCTION (SPPWC), THE STATE STANDARD PLANS, AND/OR THE
STATE STANDARD SPECIFICATIONS.
EXISTING STORM DRAIN MANHOLE
PROPOSED STORM DRAIN PIPE
EXISTING STORM DRAIN PIPE
PROPOSED STREET LIGHT
LANDSCAPED AREA
PROPOSED STORM DRAIN CATCH BASIN
EXISTING STORM DRAIN CATCH BASIN
CONCRETE AREA
RETAINING WALL
LEGEND
G :\2
9\
.0 1\
D es ig n\
C iv il\ C
3D \P lo t\1
1.
-C
V R
-N O
TE
-D
E
TA
IL
.d w g
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
6/
/2
:3 9:
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
11201 BENTON STREET, LOMA LINDA, CA 92357
3633 LONG BEACH BLVD., SUITE 200 LONG BEACH, CA 90807
T 562.595.5666 | F 562.595.5577 www.c-aarchitects.com
DESIGNING HEALTHCARE
65% DESIGN DEVELOPMENT
35% SCHEMATIC DESIGN
605 -19 - 400EMERGENY GENERATOR
FARM C|A #1474.01
1PRELIMINARY
NOT FOR
CONSTRUCTION
07.01.2021 02.26.2021
95% DESIGN DEVELOPMENT 08.30.2021
100% CONSTRUCTION DOCUMENTS 10.12.2021
DEMOLITION NOTES
C-1
DISPOSITION NOTES
DEMO PLAN
CMC RKL08/30/2021
PH: 909.477.6915
FAX: 909.477.6916
www.imegcorp.com
901 VIA PIEMONTE
SUITE 400
ONTARIO, CA 91764
G :\2
9\
.0 1\
D es ig n\
C iv il\ C
3D \P lo t\1
1.
-D
E M
O -P
LA
N
.d
C-6U
N D
E R
G R
O U
N D
F U
E L
O
IL
T A
N K
U N
D E
R G
R O
U N
D F
U E
L O
IL
T
A N
K
FUTURE EQUIPMENT
PAD BY OTHERS
PAD = 1166.80
EQUIPMENT PAD
BY OTHERS
C-6
C-6
C-6
EXISTING BUILDING
EX
IS
TI
N
G B
U
IL
D
IN
G
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
6/
/2
:3 9:
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
11201 BENTON STREET, LOMA LINDA, CA 92357
3633 LONG BEACH BLVD., SUITE 200 LONG BEACH, CA 90807
T 562.595.5666 | F 562.595.5577 www.c-aarchitects.com
DESIGNING HEALTHCARE
65% DESIGN DEVELOPMENT
35% SCHEMATIC DESIGN
605 -19 - 400EMERGENY GENERATOR
FARM C|A #1474.01
1PRELIMINARY
NOT FOR
CONSTRUCTION
07.01.2021 02.26.2021
95% DESIGN DEVELOPMENT 08.30.2021
100% CONSTRUCTION DOCUMENTS 10.12.2021
CONSTRUCTION NOTES
C-2
M
AT
C H
LI
N
E
- S
EE
B
EL
O
W R
IG
H
T
M
AT
C H
LI
N
E
- S
EE
A
BO
VE
L
EF
T
GRADING PLAN
CMC RKL08/30/2021
PH: 909.477.6915
FAX: 909.477.6916
www.imegcorp.com
901 VIA PIEMONTE
SUITE 400
ONTARIO, CA 91764
G :\2
9\
.0 1\
D es ig n\
C iv il\ C
3D \P lo t\1
1.
-G
R A
D
IN
G -P
LA
N
P ha se
.d w g
DEDUCTIVE ALTERNATE #4
ALTERNATE UTILITY
PATHWAY
DEDUCTIVE ALTERNATE #2
DO NOT INSTALL (1) FUEL TANK
REDUCTION OF SURFACE
DISTURBANCE.
U N
D E
R G
R O
U N
D F
U E
L O
IL
T
A N
K
U N
D E
R G
R O
U N
D F
U E
L O
IL
T
A N
K
FUTURE EQUIPMENT
PAD BY OTHERS
PAD = 1166.80
EQUIPMENT PAD
BY OTHERS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
6/
/2
:3 9:
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
11201 BENTON STREET, LOMA LINDA, CA 92357
3633 LONG BEACH BLVD., SUITE 200 LONG BEACH, CA 90807
T 562.595.5666 | F 562.595.5577 www.c-aarchitects.com
DESIGNING HEALTHCARE
65% DESIGN DEVELOPMENT
35% SCHEMATIC DESIGN
605 -19 - 400EMERGENY GENERATOR
FARM C|A #1474.01
1PRELIMINARY
NOT FOR
CONSTRUCTION
07.01.2021 02.26.2021
95% DESIGN DEVELOPMENT 08.30.2021
100% CONSTRUCTION DOCUMENTS 10.12.2021
1. THE LOCATIONS OF THOSE BURIED AND ABOVE GROUND UTILITIES SHOWN
ARE APPROXIMATE, ARE SHOWN FOR CONTRACTOR INFORMATIONAL USE
ONLY, AND SHALL BE CONFIRMED IN THE FIELD PRIOR TO REFERENCING
FOR CONSTRUCTION PURPOSES.
2. THE IMPLIED PRESENCE OR ABSENCE OF UTILITIES IS NOT TO BE
CONSTRUED BY THE OWNER, ENGINEER, CONTRACTOR, OR
SUBCONTRACTORS TO BE AN ACCURATE AND COMPLETE REPRESENTATION
OF UTILITIES THAT MAY OR MAY NOT EXIST ON THE CONSTRUCTION SITE.
3. BURIED AND ABOVE GROUND UTILITY LOCATION, IDENTIFICATION, AND
MARKING ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
4. REROUTING, DISCONNECTION, PROTECTION, ETC. OF ANY UTILITY MUST BE
COORDINATED BETWEEN THE CONTRACTOR, UTILITY COMPANY, AND
OWNER.
5. SITE SAFETY, INCLUDING THE AVOIDANCE OF HAZARDS ASSOCIATED WITH
BURIED AND ABOVE GROUND UTILITIES, REMAINS THE SOLE RESPONSIBILITY
OF THE CONTRACTOR.
THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITY PIPES OF
STRUCTURES SHOWN ON THESE PLANS WERE OBTAINED BY A SEARCH OF
AVAILABLE RECORDS. THESE LOCATIONS ARE APPROXIMATE AND SHALL BE
CONFIRMED IN FIELD BY THE CONTRACTOR. SO THAT ANY OF THE
NECESSARY ADJUSTMENT CAN BE MADE IN ALIGNMENT AND/OR GRADE OF
THE PROPOSED IMPROVEMENT. THE CONTRACTOR IS REQUIRED TO TAKE
DUE PRECAUTIONARY MEASURE TO PROTECT ANY UTILITY LINES SHOWN
AND ANY OTHER LINES NOT OF RECORD OR NOT SHOWN ON THESE PLANS.
THE EXISTING UTILITIES SHOWN ON THESE PLANS IS BASED ON THE
AS-BUILT PLANS (PA07-0080, PA13-0022) DATED 8/25/14, PREPARED BY
THIENES ENGINEERING, INC AND AS-BUILT PLANS (PA07-0079/00800) DATED
10/21/13, PREPARED BY ENCO UTILITY SERVICES. THE CONTRACTOR SHALL
VERIFY THE EXISTING CONDITIONS IN FIELD AND NOTIFY THE ENGINEER OF
ANY DISCREPANCIES PRIOR TO BID.
ENGINEER'S NOTICE TO CONTRACTOR
UTILITY NOTES
STORM DRAIN CONSTRUCTION NOTES
C-3
Know what's below.
before you dig.Call
R
M
AT
C H
LI
N
E
- S
EE
B
EL
O
W R
IG
H
T
M
AT
C H
LI
N
E
- S
EE
A
BO
VE
L
EF
T
UTILITY PLAN
CMC RKL08/30/2021
PH: 909.477.6915
FAX: 909.477.6916
www.imegcorp.com
901 VIA PIEMONTE
SUITE 400
ONTARIO, CA 91764
G :\2
9\
.0 1\
D es ig n\
C iv il\ C
3D \P lo t\1
1.
-U
TI
LI
TY
-P
LA
N
.d w g
DEDUCTIVE ALTERNATE #4
ALTERNATE UTILITY
PATHWAY
U
D E
R G
R O
U N
D F
U E
L O
IL
T
A N
K
U N
D E
R G
R O
U N
D F
U E
L O
IL
T
A N
K
FUTURE EQUIPMENT
PAD BY OTHERS
PAD = 1166.80
EQUIPMENT PAD
BY OTHERS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
6/
/2
:3 9:
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
11201 BENTON STREET, LOMA LINDA, CA 92357
3633 LONG BEACH BLVD., SUITE 200 LONG BEACH, CA 90807
T 562.595.5666 | F 562.595.5577 www.c-aarchitects.com
DESIGNING HEALTHCARE
65% DESIGN DEVELOPMENT
35% SCHEMATIC DESIGN
605 -19 - 400EMERGENY GENERATOR
FARM C|A #1474.01
1PRELIMINARY
NOT FOR
CONSTRUCTION
07.01.2021 02.26.2021
95% DESIGN DEVELOPMENT 08.30.2021
100% CONSTRUCTION DOCUMENTS 10.12.2021
EROSION CONTROL NOTES
C-4
A
SECTION A-AA
GRAVEL BAG DETAILS 2
A
SECTION A-A
A
NOTES:
1SILT FENCE
SILT FENCE
M
AT
C H
LI
N
E
- S
EE
B
EL
O
W R
IG
H
T
M
AT
C H
LI
N
E
- S
EE
A
BO
VE
L
EF
T
EROSION CONTROL
CMC RKL08/30/2021
PH: 909.477.6915
FAX: 909.477.6916
www.imegcorp.com
901 VIA PIEMONTE
SUITE 400
ONTARIO, CA 91764
G :\2
9\
.0 1\
D es ig n\
C iv il\ C
3D \P lo t\1
1.
-E
R O
S
IO
N .d
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
6/
/2
:3 9:
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
11201 BENTON STREET, LOMA LINDA, CA 92357
3633 LONG BEACH BLVD., SUITE 200 LONG BEACH, CA 90807
T 562.595.5666 | F 562.595.5577 www.c-aarchitects.com
DESIGNING HEALTHCARE
65% DESIGN DEVELOPMENT
35% SCHEMATIC DESIGN
605 -19 - 400EMERGENY GENERATOR
FARM C|A #1474.01
1PRELIMINARY
NOT FOR
CONSTRUCTION
07.01.2021 02.26.2021
95% DESIGN DEVELOPMENT 08.30.2021
100% CONSTRUCTION DOCUMENTS 10.12.2021
C-5
2CATCH BASIN
4CONCRETE V-GUTTER
5CURB AND GUTTER TRANSITION
DETAILS
CMC RKL08/30/2021
PH: 909.477.6915
FAX: 909.477.6916
www.imegcorp.com
901 VIA PIEMONTE
SUITE 400
ONTARIO, CA 91764
G :\2
9\
.0 1\
D es ig n\
C iv il\ C
3D \P lo t\1
1.
-D
E
TA
IL
S
.d
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
6/
/2
:3 9:
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
11201 BENTON STREET, LOMA LINDA, CA 92357
3633 LONG BEACH BLVD., SUITE 200 LONG BEACH, CA 90807
T 562.595.5666 | F 562.595.5577 www.c-aarchitects.com
DESIGNING HEALTHCARE
65% DESIGN DEVELOPMENT
35% SCHEMATIC DESIGN
605 -19 - 400EMERGENY GENERATOR
FARM C|A #1474.01
1PRELIMINARY
NOT FOR
CONSTRUCTION
07.01.2021 02.26.2021
95% DESIGN DEVELOPMENT 08.30.2021
100% CONSTRUCTION DOCUMENTS 10.12.2021
C-6
SECTION &
DETAILS
CMC RKL08/30/2021
PH: 909.477.6915
FAX: 909.477.6916
www.imegcorp.com
901 VIA PIEMONTE
SUITE 400
ONTARIO, CA 91764
G :\2
9\
.0 1\
D es ig n\
C iv il\ C
3D \P lo t\1
1.
-S
E C
TI
O
N D
E
TA
IL
S
.d w g
SECTION DETAIL
SECTION DETAIL
SECTION DETAIL
SECTION DETAIL
EMERGENCY GENERATOR
EMERGENCY GENERATOR
FUTURE
EMERGENCY
GENERATOR
o.
R E
V
IS
IO
N
S
File Name:
IMEG Project No:
Date:
Drawn By:
Checked By:
Sheet of
D E
S C
R
IP
TI
O
N D
A
TE
COPYRIGHT
ALL RIGHTS RESERVED
C
4211.01 Topographic Survey.dwg
Field Book No:
P H
: 9
.4
.6 w w w
.im eg co rp
.c om
V
IA
P
IE
M O
N
TE
S U
IT
E
O N
TA
R
IO
, C
A
VA
H
O
SP
IT
AL
S
UR
VE
Y
LO
M
A L
IN
D
A , C
A
LI
FO
R
N
IA
TO
PO
G R
AP
H
IC
S
U R
VE
Y
19004211.01
SAM
NDO
12/02/2020
V-1 1 1
SURVEYOR'S STATEMENT
VICINITY MAP
TOPOGRAPHIC SURVEY
VA LOMA LINDA HOSPITAL SURVEY
11210 BENTON ST, LOMA LINDA, CALIFORNIA
TOPOGRAPHIC SURVEY
ABBREVIATIONS
BASIS OF BEARING
UTILITY LEGEND & NOTES
BENCHMARK
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONCCONC
CONC
CONC
CONC
CONC
CONC
CONCCONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
CONC
BR
ID
GE
V
V
V
V
V
V
V
V
V
V
V
1163.33
7 1183.07
1183.16
1172.35
HV-1
W.L.
1150.6
W.L.
1150.6
W.L.
1150.6
W.L.
1146.3
W.L.
1144.8
W.L.
1142.0
W.L.
1142.3
RAMP
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
C O N C R E T E
C O N C R E T E
BARTON ROAD
B E
N T
O N
S T
R E
E T
AREA OF WORK
AD111
AE111
AD110
ROOMS: ID-09A & ID-19
GENERATOR YARD
AE110
AE190
AE111
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
605 -19 - 400
EMERGENY GENERATOR
FARM
11201 BENTON STREET
LOMA LINDA, CA 92357
100% CONSTRUCTION
DOCUMENTS
c|a ARCHITECTS expressly reserves its common law copyright and other property rights in these plans. These plans are not to be reproduced, changed or copied in any form or manner,nor are they to be assigned to any third party without first obtaining the written consent of c|a ARCHITECTS, Inc. COPYRIGHT ©
3633 LONG BEACH BLVD., SUITE 200
T 562.595.5666 | F 562.595.5577
LONG BEACH, CA 90807
www.c-a ARCHITECTS.com
C|A #1474.01
D R
A W
IN
G
N A
M E
P L O
T D
A T
E
P L O
T T
E D
B Y
/1 /2
:2
:2
P M
/1 /2
:2 :2
P
M
B
IM
/1
.0
E m e rg e n c y G e n e ra to r
F a rm
/1 .0
-A
-B M
R
.r v t
AE100
SITE PLAN
DS NH08/30/2021
N H
1" = 60'-0" 1SITE PLAN
N
Revisions: Date:
65% DESIGN DEVELOPMENT 07.01.2021
35% SCHEMATIC DESIGN 02.26.2021
A. EXISTING ITEMS SCHEDULED TO REMAIN SHALL
BE PROTECTED IN PLACE AND MAINTAINED BY
THE CONTRACTOR. DAMAGE TO EXISTING
EQUIPMENT, STRUCTURES, SYSTEMS AND
SERVICES ARE THE RESPONSIBILITY OF THE
CONTRACTOR AND SHALL BE RESTORED OR
REPLACED TO THE SATISFACTION OF THE
OWNER'S REPRESENTATIVE AT THE
CONTRACTOR'S EXPENSE.
B. ITEMS SCHEDULED TO BE DEMOLISHED SHALL
BE DISPOSED OF BY THE CONTRACTOR OFF SITE.
C. ITEMS SCHEDULED TO BE REMOVED SHALL BE
STORED FOR REUSE OR RETURNED TO THE
OWNER'S REPRESENTATIVE AS DIRECTED.
D. ITEMS SCHEDULED FOR
REINSTALLATION/RELOCATION SHALL BE
CLEANED, REATTACHED, RECONNECTED AND
RETURNED TO THEIR FULLY FUNCTIONING
CONDITION.
E. UTILITIES PREVIOUSLY SERVING DEMOLISHED
ITEMS SHALL BE CAPPED BEHIND ADJACENT
FINISHED SURFACES UNLESS OTHERWISE
DIRECTED IN THE CONTRACT DOCUMENTS. SEE
MECHANICAL AND ELECTRICAL.
F. DAMAGED OR PREVIOUSLY UNFINISHED
SURFACES SHALL BE RESTORED, PATCHED OR
FINISHED TO MATCH ADJACENT FINISHED
SURFACES.
G. SAW CUTTING AND/OR CORE DRILLING SHALL BE
USED IN LIEU OF JACK HAMMERING IN ORDER TO
MINIMIZE DISRUPTION TO FACILITY SERVICES
AND PERSONNEL.
H. THE DEMOLITION PLAN AND NOTES ARE
PRESENTED AS GENERAL INFORMATION ONLY
AND ARE NOT INTENDED TO REPRESENT A
COMPREHENSIVE ACCOUNTING OF ALL
CONDITIONS PRESENT AT THE PROJECT SITE.
THE CONTRACTOR IS RESPONSIBLE FOR
PREPARING THE SITE AS REQUIRED TO
COMPLETE THE CONSTRUCTION OF THE
FINISHED PROJECT AS DESIGNED AND DETAILED
IN THE CONTRACT DOCUMENTS.
GENERAL
DEMOLITION NOTES
2.1
2.32.3
2.32.3
2.10
V.I.F.
70' - 6 5/8" V
.I .F
/2
' - 4
22' - 8"
2.302.30
2.8
2.3
2.3
2.19
2.16
2.18
2.16
2.31
2.32
2.32
2.302.30
2.31
2.31
2.3
2.31
0"
2' - 11"
2.34
2.38 2.31
2.43
2.332.33
2.332.33
NON RATED WALL
2 HOUR RATED WALL
OCCUPATION SEPARATION WALL
CONCRETE WALL
CMU WALL
1i WALL TAG. SEE AE500
WALL TO REMAIN
WALL TO BE DEMOLISHED
NOT IN SCOPE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
605 -19 - 400
EMERGENY GENERATOR
FARM
11201 BENTON STREET
LOMA LINDA, CA 92357
100% CONSTRUCTION
DOCUMENTS
c|a ARCHITECTS expressly reserves its common law copyright and other property rights in these plans. These plans are not to be reproduced, changed or copied in any form or manner,nor are they to be assigned to any third party without first obtaining the written consent of c|a ARCHITECTS, Inc. COPYRIGHT ©
3633 LONG BEACH BLVD., SUITE 200
T 562.595.5666 | F 562.595.5577
LONG BEACH, CA 90807
www.c-a ARCHITECTS.com
C|A #1474.01
D R
A W
IN
G
N A
M E
P L O
T D
A T
E
P L O
T T
E D
B Y
/1 /2
:2
:2
P M
/1 /2
:2 :2
P
M
B
IM
/1
.0
E m e rg e n c y G e n e ra to r
F a rm
/1 .0
-A
-B M
R
.r v t
AD110
OUTDOOR FUEL CELL YARD
DEMOLITION PLAN
DS NH08/30/2021
N H
KEYNOTES
2.1 DEMOLISHEXISTING TRANSFORMER AND PAD.
2.3 DEMOLISH EXISTING EQUIPMENT AND LINES. SEE
PLUMBING AND ELECTRICAL DRAWINGS.
2.8 DEMOLISH EXISTING GUARDRAIL.
2.10 DEMOLISH EXISTING BOLLARDS.
2.16 EXISTING SIGNAGE TO BE RELOCATED.
2.18 EXISTING TELE. VAULT TO BE RELOCATED.
2.19 EXISTING ELEC. VAULT TO BE RELOCATED. SEE
ELECTRICAL DRAWINGS.
2.30 DEMOLISH EXISTING 4" CONCETE SLAB ON GRADE
IN PREPARATION FOR NEW GENERATORS AND
ASSOCIATED EQUIPMENT AND CONDUITS.
2.31 EXISTING CMU BLOCK WALL TO REMAIN. PROTECT
IN PLACE.
2.32 DEMOLISH EXISTING METAL GATES/DOORS.
2.33 SEE CIVIL DRAWINGS FOR SCOPE IN THIS AREA.
2.34 AFTER DEMOLITION OF EXISTING EQUIPMENT AND
DOORS FILL ALL HOLES IN EXISTING CMU WALL
WITH NON-SHRINK GROUT.
2.38 SAWCUT/GRIND EXISTING SPLITFACE EDGE FOR
ATTACHMENT OF NEW WALL. SEE FLOOR PLAN.
CONTRACTOR TO MATCH EXISTING MODULE SIZE.
2.43 DEMOLISH EXISTING WALL MOUNTED LADDER.
1/8" = 1'-0" 1GENERATOR YARD DEMOLITION PLAN
WALL LEGEND
N
Revisions: Date:
65% DESIGN DEVELOPMENT 07.01.2021
35% SCHEMATIC DESIGN 02.26.2021
NON RATED WALL
2 HOUR RATED WALL
OCCUPATION SEPARATION WALL
CONCRETE WALL
CMU WALL
1i WALL TAG. SEE AE500
WALL TO REMAIN
WALL TO BE DEMOLISHED
NOT IN SCOPE
A. EXISTING ITEMS SCHEDULED TO REMAIN SHALL
BE PROTECTED IN PLACE AND MAINTAINED BY
THE CONTRACTOR. DAMAGE TO EXISTING
EQUIPMENT, STRUCTURES, SYSTEMS AND
SERVICES ARE THE RESPONSIBILITY OF THE
CONTRACTOR AND SHALL BE RESTORED OR
REPLACED TO THE SATISFACTION OF THE
OWNER'S REPRESENTATIVE AT THE
CONTRACTOR'S EXPENSE.
B. ITEMS SCHEDULED TO BE DEMOLISHED SHALL
BE DISPOSED OF BY THE CONTRACTOR OFF SITE.
C. ITEMS SCHEDULED TO BE REMOVED SHALL BE
STORED FOR REUSE OR RETURNED TO THE
OWNER'S REPRESENTATIVE AS DIRECTED.
D. ITEMS SCHEDULED FOR
REINSTALLATION/RELOCATION SHALL BE
CLEANED, REATTACHED, RECONNECTED AND
RETURNED TO THEIR FULLY FUNCTIONING
CONDITION.
E. UTILITIES PREVIOUSLY SERVING DEMOLISHED
ITEMS SHALL BE CAPPED BEHIND ADJACENT
FINISHED SURFACES UNLESS OTHERWISE
DIRECTED IN THE CONTRACT DOCUMENTS. SEE
MECHANICAL AND ELECTRICAL.
F. DAMAGED OR PREVIOUSLY UNFINISHED
SURFACES SHALL BE RESTORED, PATCHED OR
FINISHED TO MATCH ADJACENT FINISHED
SURFACES.
G. SAW CUTTING AND/OR CORE DRILLING SHALL BE
USED IN LIEU OF JACK HAMMERING IN ORDER TO
MINIMIZE DISRUPTION TO FACILITY SERVICES
AND PERSONNEL.
H. THE DEMOLITION PLAN AND NOTES ARE
PRESENTED AS GENERAL…
This is the start of the file's text. The full file is on GovTribe.