Attachment A Condenser-Evaporator List.pdf
PDF 215 KB Posted
- Attached to
- J045--Replace Walk-in Condenser & Evaporator Federal contract opportunity
- Solicitation number
- 36C25726Q0272
About this file
This is an attachment listing existing equipment specifications for a federal construction project. The document details 13 walk-in freezer and cooler units located in Building 202 at Waco VA (Project #674-26-1-5066-0020) that require condenser and evaporator replacement. Each unit entry includes the room number, unit type (cooler or freezer), component type (condenser or evaporator), model number, serial number, and existing electrical and mechanical requirements including BTU capacity, voltage, phase, and amperage specifications. The units are distributed across rooms 107, 107A3, 107-1, 107-2, 108, 108A-1, 108A-2, 108A-3, 111-1, 111-2, 112-1, 112-2, and 135, with condenser units ranging from 19,000 to 20,600 BTU capacity and operating at either 460V or 208/230V with varying amperage requirements.
The contractor is required to verify all existing unit specifications prior to ordering replacement equipment and must immediately notify the VA of any discrepancies found during field review. All replacement units must meet or exceed the performance of existing units. Key requirements include: new condenser units must be exterior-grade mounted on the roof of Building 202 with contractor-provided cut sheets and details for mounting racks and roof waterproofing integration; all new evaporators must be electronic expansion valve (EEV)-driven; and the contractor shall provide comprehensive documentation for roof-top component integration into the existing roofing system.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SF30 36C25726Q0272 0002.docx | DOCX document | |
| 36C25726Q0272 0002_1.docx | DOCX document | |
| 36C25726Q0272 0001_1.docx | DOCX document | |
| S02 SF30 36C25726Q0272 0001.docx | DOCX document | |
| 36C25726Q0272_1.docx | DOCX document | |
| S02 36C25726Q0272.docx | DOCX document | |
| Service Contract Act WD 2015-5261_rv 28.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment A – Existing Unit Serial & Model Number Replacement of Condenser & Evaporator (13) Walk-in Freezer/Cooler Units
Bldg. 202, Waco VA What follows is the existing Condenser/Evaporator information for the contractor’s review. All replacement units shall meet or exceed the performance of the existing units to be replaced. This list is for reference only.
Unit / Room#
Cooler or Freezer
Unit Type Model# Serial# Existing Elect. /Mech. Requirements (See Special notes at bottom of page.)
107 Cooler Condenser L400 410005403 20,600BTU-460V,3ph,20amp Evaporator ADT2080G D0G 4389 115v, 1ph,15amp
107 A3 Freezer Condenser L400 410005404 19,000BTU-460V,3ph,15amp Evaporator TLP4191LES2B 179499138 115v, 1ph,15amp
107-1 Cooler Condenser L400 410005403 20,600BTU-460V,3ph,15amp Evaporator TLP4191LES2B 139325509 115v, 1ph,15amp
107-2 Cooler Condenser M300 410005229 19,000BTU-460V,3ph,15amp Evaporator TLP4191LES2B 199353643 208/230v, 1ph, 15amp
108 Cooler Condenser L400 410005404 19,000BTU - 460V, 3ph, 15amp Evaporator ADT2080G D0G 4389 115v, 1ph, 15amp
108A-1 Freezer Condenser M300 410005229 20,600BTU – 460v, 3ph, 20amp Evaporator LET2001D DOF 0560 208/230v, 1ph, 15amp
108A-2 Freezer Condenser L400 410005403 20,600BTU – 460v, 3ph, 20amp Evaporator LET2001G D0H 0637 208/230v, 1ph, 15amp
108A-3 Freezer Condenser L400 410005404 20,600BTU – 460v, 3ph, 20amp Evaporator LET2001G DOH 0696 208/230v, 1ph, 15amp
111-1 Cooler Condenser RG1-3 41000529 19,000BTU - 460V, 3ph, 15amp Evaporator ADT2080G D0G 4390 115v, 1ph, 15amp
111-2 Cooler Condenser M300 410005228 20,600BTU – 460v, 3ph, 20amp Evaporator ADT2080G D06 4390 208/230v, 1ph, 15amp
VHACTXBrookS Highlight
Attachment A – Existing Unit Serial & Model Number Replacement of Condenser & Evaporator (13) Walk-in Freezer/Cooler Units
Bldg. 202, Waco VA - PROJECT # 674-26-1-5066-0020
NOTES:
1. The contractor shall verify all existing Condenser/Evaporator unit’s requirements for BTU, Phase (ph), Voltage (v) and amperage (amp) prior to placing orders and beginning any work. The contractor shall immediately notify the VA of any discrepancy between units listed here and what the find in their field review.
2. All new condenser units are to be exterior grade mounted on the roof of Bldg. 202. The contractor shall provide cut-sheet/details for their purpose mounting racks and integration of all roof top components into the existing roofing waterproofing system.
3. All new evaporators shall be EEV-driven (electronic expansion valve).
4. All new units shall meet or exceed existing installed equipment performance requirements.
112-1 Cooler Condenser M300 410005228 20,600BTU – 460v, 3ph, 20amp Evaporator ADT208AK T20C16980 208/230v, 1ph, 15amp 112-2 Cooler Condenser M300 410005228 20,600BTU – 460v, 3ph, 20amp Evaporator ADT2080G D0G 4387 208/230v, 1ph, 15amp
135 Cooler Condenser PC149MOP3 D002183-907757 20,600BTU – 460v, 3ph, 20amp Cooler Evaporator TPLP211MAS1BR6 129214933 115v, 1ph, 15amp