Attachment A - Colocation Specifications~1.docx

DOCX document 30 KB Posted

Attached to
St. Louis Data Center Colocation Space for ICN (IFB)
Solicitation number
26-448DOIT-ADMIN-B-52081
Issued by
Illinois

About this file

This document is an attachment to a colocation services solicitation from the Illinois Department of Innovation and Technology (DoIT) for the establishment of a 10-year contract with the St. Louis Data Center. The specification details comprehensive colocation facility requirements at either 900 Walnut Street or 210 North Tucker Street in St. Louis, Missouri. Services must be provided at Netrality Datacenter locations and include full rack or individual cabinet configurations based on DoIT equipment needs, with power delivery options spanning -48V, 120V, 208V, and A+B feeds supported by UPS and backup generators. The provider must guarantee 99.99% uptime through a Service Level Agreement and maintain Uptime Institute Tier III and Tier IV standards or equivalent practices. Additional requirements include 24/7 access for DoIT engineers, 24/7 Network Operations Center support, on-site technical support services (Smart Hands), environmental controls meeting ASHRAE standards for temperature and humidity regulation, fire suppression and smoke control, and fabric connectivity access with detailed specifications on available connectivity options.

The provider must supply Letters of Authorization for cross-connects, home run fibers, and related services, while recognizing and supporting relevant national and international power standards including IEEE, ASHRAE, NEC, NFPA, TIA, ANSI, and ISO standards. If the provider is a third party, clarification must be provided regarding which services are delivered directly by the provider versus those provided by the data center owner. The colocation services are intended to support DoIT Network Services/ICN in serving K-12 customers, state agencies, and paying customers across Illinois.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment A: Colocation Specifications Colocation Specifications:

1. Colocation Facilities:

· The provider must be able to provide services at either Netrality Datacenter in the St. Louis area, specifically the following locations 210 North Tucker St. Louis Data Center 210 North Tucker Boulevard, St. Louis, MO, USA 900 Walnut St. Louis Data Center 900 Walnut St, St. Louis, MO, USA

2. DoIT Engineering Access:

· The provider shall ensure access to the facility and equipment for DOIT engineers as required on a 24/7 basis.

3. Letter of Authorization (LOA) for Cross Connects:

· The provider shall provide Letters of Authorization (LOAs) as required to authorize the installation of cross-connects, home run fibers, and other services as required.

4. Full Rack/Cabinets:

· The provider shall provide full racks or individual cabinets based on our equipment needs.

5. Power:

· The provider shall provide power options including -48V, 120V, 208V, and A+B Feeds including UPS and backup generators.

· The provider shall provide and ensure a Service Level Agreement (SLA) for power, guaranteeing 99.99% uptime and quick response times in the event of power outages.

· Provider shall support Uptime Institute Tier III and Tier IV practices (or similar best practices) for dual power path (A+B) Systems

6. 24x7 NOC/Support:

· The provider shall provide 24x7 Network Operations Center (NOC) support.

7. Environmental Control:

· The provider shall ensure adequate environmental control (ASHRAE or similar), including temperature and humidity regulation, fire suppression and smoke control, to maintain optimal operating conditions for our equipment.

8. On-site Technical Support Services:

· Vendor shall have on-site technical support (aka ‘Smart Hands’) such as hardware support, cabling and connectivity, device management, visual inspections.

9. Fabric Access:

· Detail Switch / Connectivity Fabric Access available, if any.

· Provide detail on connectivity offered via the fabric.

10. General Standards / Overarching Requirements for Data Center/Colocation Facilities.

· Recognize and support one or more National/International power standards IEEE, ASHRAE, NEC, NFPA, TIA, ANSI and ISO as appropriate, for Environmental Controls, UPS and Generator lifecycle management.

11. Third Party Provisions:

· If provider is a third party, provider must clarify what, if any, services are provided by provider directly, and what services are provided directly by the Data Center owner.