Attachment A - Colocation Specifications~1.docx
DOCX document 30 KB Posted
- Solicitation number
- 26-448DOIT-ADMIN-B-50925
- Issued by
- Illinois
About this file
This is a Colocation Specifications attachment for a state and local contract opportunity involving the Department of Information Technology (DoIT). The document outlines the technical requirements for colocation services to be provided at Netrality Datacenters in the St. Louis area, specifically at two locations: 210 North Tucker Boulevard and 900 Walnut Street. The provider must supply full racks or individual cabinets based on equipment needs, with 24/7 access for DoIT engineers to the facility and equipment. The colocation services must include multiple power delivery options (48V, 120V, 208V, and A+B feeds) supported by UPS and backup generators, with a guaranteed Service Level Agreement of 99.99% uptime. Additional requirements encompass 24/7 Network Operations Center support, on-site technical support services (Smart Hands), Letters of Authorization for cross-connects and fiber installations, and comprehensive environmental controls including ASHRAE-compliant temperature and humidity regulation, fire suppression, and smoke control systems.
The specifications require the provider to adhere to national and international standards including IEEE, ASHRAE, NEC, NFPA, TIA, ANSI, and ISO for environmental controls and infrastructure management. The provider must support Uptime Institute Tier III and Tier IV practices for dual power path systems and provide details on any Switch/Connectivity Fabric Access and related connectivity offerings. If the provider is a third party, clear delineation must be made regarding which services the provider delivers directly versus those provided by the datacenter owner. No pricing information, set-asides, contract terms, award dates, or renewal options are specified in this attachment.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| vendor-disclosure-formerly-forms-a-v26-2.docx | DOCX document | |
| IFB Offer Form B-50925 St. Louis Data Center Colocation Space for ICN.pdf | ||
| IFB Vendor Instructions B-50925 St. Louis Data Center Colocation Space for ICN.docx | DOCX document | |
| ipg-active-registered-vendor-disclosure-formerly-forms-b-v-26-1.docx | DOCX document | |
| IFB Contract B-50925 St. Louis Data Center.docx | DOCX document | |
| QA 26-448DOIT-ADMIN-B-50925 St. Louis Data Center IFB~1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment A: Colocation Specifications Colocation Specifications:
1. Colocation Facilities:
· The provider must be able to provide services at either Netrality Datacenter in the St. Louis area, specifically the following locations 210 North Tucker St. Louis Data Center 210 North Tucker Boulevard, St. Louis, MO, USA 900 Walnut St. Louis Data Center 900 Walnut St, St. Louis, MO, USA
2. DoIT Engineering Access:
· The provider shall ensure access to the facility and equipment for DOIT engineers as required on a 24/7 basis.
3. Letter of Authorization (LOA) for Cross Connects:
· The provider shall provide Letters of Authorization (LOAs) as required to authorize the installation of cross-connects, home run fibers, and other services as required.
4. Full Rack/Cabinets:
· The provider shall provide full racks or individual cabinets based on our equipment needs.
5. Power:
· The provider shall provide power options including -48V, 120V, 208V, and A+B Feeds including UPS and backup generators.
· The provider shall provide and ensure a Service Level Agreement (SLA) for power, guaranteeing 99.99% uptime and quick response times in the event of power outages.
· Provider shall support Uptime Institute Tier III and Tier IV practices (or similar best practices) for dual power path (A+B) Systems
6. 24x7 NOC/Support:
· The provider shall provide 24x7 Network Operations Center (NOC) support.
7. Environmental Control:
· The provider shall ensure adequate environmental control (ASHRAE or similar), including temperature and humidity regulation, fire suppression and smoke control, to maintain optimal operating conditions for our equipment.
8. On-site Technical Support Services:
· Vendor shall have on-site technical support (aka ‘Smart Hands’) such as hardware support, cabling and connectivity, device management, visual inspections.
9. Fabric Access:
· Detail Switch / Connectivity Fabric Access available, if any.
· Provide detail on connectivity offered via the fabric.
10. General Standards / Overarching Requirements for Data Center/Colocation Facilities.
· Recognize and support one or more National/International power standards IEEE, ASHRAE, NEC, NFPA, TIA, ANSI and ISO as appropriate, for Environmental Controls, UPS and Generator lifecycle management.
11. Third Party Provisions:
· If provider is a third party, provider must clarify what, if any, services are provided by provider directly, and what services are provided directly by the Data Center owner.