This solicitation is for the construction of a new mental health outpatient building addition at the Fargo VA Medical Center in North Dakota. Key details include the construction of a two-story 52,000 square foot building addition to provide expanded outpatient mental health care services. The solicitation includes architectural drawings, specifications, and contract documents. The response due date is July 15, 2023 with construction to be completed within 540 calendar days of the notice to proceed. The Department of Veterans Affairs Technology Acquisition Center in Austin is the contracting agency.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL GENERAL NOTES
A. SPECIFICATIONS TAKE PRECEDENT OVER DRAWINGS.
B. CORE DRILL AND SAW CUT, AS REQUIRED, FOR FLOOR AND WALL
PENETRATIONS. SEAL REMAINING ANNULUS WITH FIRE CAULK.
C. FURNISH ACCESS DOORS OR PANELS FOR INSTALLATION BY GENERAL
CONTRACTOR IN WALLS AND CEILINGS WHERE ACCESS IS REQUIRED TO
CONCEALED ELECTRICAL BOXES AND DEVICES.
D. ARMORED CABLE (AC) MAY NOT BE USED.
E. PROVIDE ALL ELECTRICAL WORK IN ACCORDANCE WITH THE CURRENT
NATIONAL ELECTRICAL CODE AND THE REQUIREMENTS OF THE VHA.
F. COORDINATE ALL OUTAGES WITH VA COR PER SPECS PRIOR TO WORK
BEING DONE.
LIGHTING GENERAL NOTES
A. ALL RECESSED LIGHTING FIXTURE IN LAY-IN CEILINGS SHALL BE INSTALLED
WITH 6' LONG FLEXIBLE METAL CONDUIT.
B. ALL MOUNTING HEIGHTS FOR LIGHTING FIXTURES ARE TO THE BOTTOM OF
THE FIXTURES UNLESS INDICATED OTHERWISE.
C. SEE ARCHITECTURAL EXTERIOR ELEVATIONS FOR MOUNTING HEIGHTS OF
EXTERIOR LIGHTING FIXTURES.
D. CIRCUIT WIRING IS NOT SHOWN. SWITCH AND CIRCUITING INTENT SHALL BE
AS DESIGNATED AT EACH LIGHT FIXTURE.
E. PROVIDE PROPER NUMBER OF CONDUCTORS TO ACHIEVE CIRCUITING AND
SWITCHING SHOWN.
F. CIRCUIT NUMBERS AT DEVICES CORRESPOND TO PANELBOARD BREAKERS
(SEE PANELBOARD SCHEDULE). BRANCH CIRCUITS SHALL BE SIZED
ACCORDING TO THE CIRCUIT BREAKER RATING, UNLESS INDICATED
OTHERWISE ON THE ELECTRICAL EQUIPMENT SCHEDULE.
COMMUNICATION GENERAL NOTES
A. FOR WHEELCHAIR PATIENT USE, MOUNT TELEPHONE OUTLETS 35" AFF TO
BOTTOM OF OUTLET BOX.
B. DESK PHONES - MOUNT OUTLET 1'-6" AFF
C. SEE VHA BARRIER FREE DESIGN GUIDE PG-18-13
ELECTRICAL GENERAL NOTES - DEMOLITION
A. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR PHASES OF
DEMOLITION AND CONSTRUCTION. COORDINATE WITH GENERAL
CONSTRUCTION.
B. DISCONNECT AND REMOVE ALL ELECTRICAL DEVICES AND LIGHTING
FIXTURES IN DEMOLITION AREAS UNLESS NOTED OTHERWISE. DISCONNECT
AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO OVERCURRENT
PROTECTIVE DEVICE. DISCONNECT AND REMOVE ALL ABANDONED
CIRCUITS AND CONDUITS. PROVIDE CONDUIT AND WIRE AS REQUIRED FOR
CONTINUITY OF CIRCUITS TO ANY EXISTING DEVICES TO REMAIN.
COORDINATE AND VERIFY REQUIREMENTS WITHIN NEW AREA OF WORK.
KEYNOTES
KEYNOTE00
NEW - EXISTING AND DEMO LINE TYPES
NEW LINE TYPE
EXISTING LINE TYPE
DEMOLITION LINE TYPE
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\k gr ie pe nt ro g\ D oc um en ts
\2 1.
_E
LE
C
_R
_k gr ie pe nt ro gJ G
H
.rv t
5/
/2
7:
:4
A
M
E-001
ELECTRICAL ABBREVIATIONS AND
GENERAL NOTES
CONSTRUCT MENTAL HEALTH
OUTPATIENT BLDG 52 ADDITION
2101 ELM STREET, FARGO, ND 58102
437-316
05/26/2023 RA KEG
100% BID DOCUMENTS
VEG 21.05 DWG 158 of 188
CONTRACT DOCUMENTS SUBMISSION
FULLY SPRINKLERED
MIN MINIMUM
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
N
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NEUT OR N NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
P
P POLE
PA PUBLIC ADDRESS
PB PULL BOX OR PANEL BOARD
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV PERSONAL IDENTIFICATION VERIFICATION
PNL PANEL
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
R
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
REQ REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
S
SCC SHORT CIRCUIT CAPACITY
SD SMOKE DETECTOR
SES SERVICE ENTRANCE SECTION
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
T
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
U
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V
V VOLT
VA VOLT-AMPERE
VAR VOLT-AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W
W WATT
WH WATER HEATER
WP WEATHERPROOF
X
XFER TRANSFER
XFMR TRANSFORMER
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
E
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMERGENCY MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXST EXISTING
F
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLT FLOODLIGHT
FLUOR FLUORESCENT
FLUOR FIXT FLUORESCENT FIXTURE
FOUTT TELEPHONE FLOOR OUTLET
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G
G OR GND ELECTRICAL GROUND
GC GENERAL CONTRACTOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
H
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
I
IESNA ILLUMINATION ENGINEERING SOCIETY OF NORTH
AMERICA
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J
J-BOX JUNCTION BOX
K
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAH KILOVOLT-AMPERE PER HOUR
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWHM KILOWATT HOUR METER
L
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
M
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
1P SINGLE POLE
1PH SINGLE PHASE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE PHASE
4/C FOUR-CONDUCTOR
4W FOUR WIRE
A
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT / ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT OR ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR AVAILABLE FAULT
CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE-HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB OR A AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
B
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BPIP BOILER PLANT INSTRUMENTATION PANEL
BRKR BREAKER
BYP BYPASS
C
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
CD CANDELA OR CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED / CONTRACTOR
INSTALLED
CF/OI CONTRACTOR FURNISHED / OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
CO CONTRACTING OFFICER
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
CUR CURRENT
D
DB DECIBEL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DN DOWN
ELECTRICAL ABBREVIATIONS
0 100% BID DOCUMENTS 05/26/2023
CARD READERBRANCH CIRCUIT HOMERUN. LINES INDICATE NUMBER OF
CIRCUITS,NEUTRAL, AND SWITCH LEG CONDUCTORS. ONE
SEPARATE GREEN GROUNDING CONDUCTOR SHALL BE
PROVIDED FOR EACH HOMERUN; NOT SHOWN
A
XXX-XX
A
A
A
ELECTRICAL SYMBOLS - DIAGRAM COMMUNICATION SYMBOLS: ELECTRICAL SYMBOLS - LIGHTING PLANELECTRICAL SYMBOLS - POWER PLAN
SWITCH, MULTI-POSITION
SWITCH, NORMALLY CLOSED FLOAT
SWITCH, NORMALLY CLOSED FOOT OPERATED
SWITCH, NORMALLY CLOSED LIMIT
SWITCH, NORMALLY CLOSED TIME DELAY
SWITCH, NORMALLY CLOSED TEMPERATURE
ACTIVATED
SWITCH, NORMALLY OPEN FLOAT
SWITCH, NORMALLY OPEN LIMIT
SWITCH, NORMALLY OPEN TEMPERATURE
ACTIVATED
MOTOR, SINGLE-PHASE
MOTOR, THREE-PHASE
DELTA CONNECTION
TRANSFORMER
WYE CONNECTION
PULL BOX
PRESSURE SWITCH-CLOSE ON INCREASE
PRESSURE SWITCH-OPEN ON INCREASE
MANHOLE
TIME CLOCK
VENTILATOR OR FAN COIL UNIT OUTLET
CONDUIT TERMINATED 6" AFF IN STANDARD BOX FOR
EXTENSION TO EQUIPMENT AS DIRECTED.
CONDUIT TERMINATED W/COUPLING (FLUSH W/FINISHED
FLOOR) FOR EXTENSION TO EQUIPMENT AS DIRECTED.
RECEPTACLE,
SWITCHED DUPLEX
DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE,
GROUNDING TYPE, 20A, W/#12 CONDUCTORS IN FLEXIBLE
CORD (CENTER LINE OF OUTLET: 6'-6" AFF. (MINIMUM).
ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" CENTERS OR AS
DESIGNATED ON DRAWINGS), MTD 3'-6" AFF OR AS INDICATED.
3-GANG COMPARTMENT BOX IN FLOOR FOR
TELEPHONE, DATA & RECEPTACLE.
RECEPTACLE, SPECIAL PURPOSE
A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.
B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.
C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.
D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.
E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.
F = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.
G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R.
H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.
ELECTRIC DOOR STRIKE
MAGNETIC DOOR POSITION SWITCH
VANDAL RESISTANT 1080P DOME IP CAMERA
FOUR SQUARE JUNCTION BOX
SECURITRON IMXDA MAGNETIC LOCK
OUTLET, COMBINATION TELEPHONE/DATA
COMMUNICATION
CABLE TELEVISION LINE = CATV
CLOSED CIRCUIT TELEVISION LINE = CCTV.
MINIMUM 1" CONDUIT
FIBER OPTICS LINE = FO
OUTLET TELEPHONE; LETTER INDICATES AS FOLLOWS:
J = JACK TYPE W = WALL TYPE
SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE,
PROVIDE SCHEDULE ON LEGEND
SPEAKER, WALL MOUNTED, "X" INDICATES THE TYPE,
PROVIDE SCHEDULE ON LEGEND. MTD.
7'-6" AFF UNLESS OTHERWISE NOTED.
OUTLET DATA ONLY
TELEPHONE LINE = T
OUTLET; LETTER INDICATES AS FOLLOWS:
A = AUDIO V = VIDEO I = INTERCOM
RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6"
AFF UNLESS OTHERWISE NOTED.
SPEAKER PROGRAM SELECTOR SWITCH & VOLUME
CONTROL MTD. 4'-6" AFF UNLESS OTHERWISE NOTED.
OUTLET, TELEVISION: (1) CAT 6A
MTG HEIGHT TBD (CORRDINATE WITH VA)
INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL OPERATION
OF INSTRUMENT & TYPE REQUIRED)
INTERCOM STAFF STATION
TELECOMMUNICATIONS MANHOLE
DATA BOX
DURESS BUTTON, HARD WIRED TO HEADEND
CCTV SYSTEM WORKSTATION
REQUEST TO EXIT MOTION DETECTOR
USP HUB2SA REMOTE DOOR RELEASE BUTTON
CODE BLUE BUTTON INTEGRATED NURSE CALL SYSTEM
NURSE CALL MASTER CONSOLE
ETHERNET NETWORK SWITCH
WIRELESS ACCESS POINT
SWITCH
F = FUSED SWITCH
K = KEY OPERATED
L = LOCK
LM= LOW VOLTAGE MASTER
M = MANUAL MOTOR STARTING
MC= MOMENTARY CONTACT
MP= MOTOR SNAP WITH PILOT LIGHT
P = WITH PILOT LIGHT (THERMAL TYPE)
X = EXPLOSION PROOF
LIGHTING, ONE HEAD EMERGENCY BATTERY POWER
STREET LIGHT WITH BRACKET
STREET LIGHT POLE, ONE MAST ARM, ONE LUMINAIRE
STREET LIGHT POLE, TWO MAST ARMS, TWO LUMINAIRES
STREET LIGHT POLE, POST TOP MOUNT LUMINAIRE
LIGHTING, TWO HEAD EMERGENCY BATTERY POWER
LIGHTING, THREE HEAD EMERGENCY BATTERY POWER
EXIT SIGN, WALL MOUNTED WITH DIRECTIONAL
ARROWS AND FACES AS SHOWN
EXIT SIGN, CEILING MOUNTED WITH DIRECTIONAL
ARROWS AND FACES AS SHOWN
RECESSED DOWNLIGHT FIXTURE.
NOMENCLATURE EXAMPLE :
('A' DESIGNATES LIGHT FIXTURE TYPE, 'b' DESIGNATES SWITCHLEG, x DESIGNATES CIRCUIT NUMBER) REFER TO
DRAWINGS AND LIGHT FIXTURE SCHEDULE FOR MORE
INFORMATION.
JUNCTION BOX
TRANSFORMER, PLAN
WYE CONNECTION
DUCT, CELL FLOOR HEADER
DUCT, TROLLEY
DUCT, UNDERFLOOR
JUNCTION BOX
EARTH GROUND
LADDER CABLE TRAY
WIREWAY
RIGID CONDUIT LINE = RC
SUBSTATION
BUSWAY
FLOOR OUTLET, VOICE/DATA COMMUNICATION
PUSH BUTTON / EMERGENCY SHUT OFF
DISTRIBUTION PANEL
LIGHTING PANEL
PANELBOARD CABINET, FLUSH MOUNTED
PANELBOARD CABINET, SURFACE MOUNTED
RECEPTACLE, CLOCK HANGER
RECEPTACLE, DUPLEX (MOUNT 18"AFF. UNLESS NOTED OTHERWISE)
RECEPTACLE, DUPLEX ON EMERGENCY POWER
(MOUNT 18" AFF. UNLESS NOTED OTHERWISE)
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT
INTERRUPTER (MOUNT 18" AFF. UNLESS NOTED OTHERWISE)
RECEPTACLE, QUADRAPLEX
RECEPTACLE, SINGLE
RECEPTACLE, SINGLE WITH SWITCH
DIRECT BURIAL CABLE = DB
POWER DUCT = P
HI VOLTAGE SWITCH ON CONCRETE PAD
LOW VOLTAGE SWITCH ON CONCRETE PAD
DUAL POWER AND TELECOMMUNICATIONS MANHOLE
SWITCH, NORMALLY OPEN TIME DELAY
SWITCH, SINGLE BREAK
FUSE WITH RATING
NORMALLY CLOSED RELAY CONTACT
NORMALLY OPEN RELAY CONTACT
MOLDED CASE CIRCUIT BREAKER
LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER
MEDIUM-VOLTAGE OIL CIRCUIT BREAKER
MEDIUM-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER
SWITCH AND FUSE UNIT
FUSED DRAWOUT POTENTIAL TRANSFORMER
FUSIBLE LINK
VARIABLE FREQUENCY DRIVE
GENERATOR, POWER
BATTERY
CAPACITOR
LIGHTNING ARRESTOR
RECTIFIER, CATHODIC PROTECTION
RELAY; LETTER INDICATES RELAY TYPE
50 = INSTANTANEOUS OVERCURRENT OR RATE-OF-RISE
51 = AC-TIME OVERCURRENT
67 = AC-DIRECTIONAL OVERCURRENT
86 = LOCK OUT
DISCONNECT SWITCH, FUSED
DISCONNECT SWITCH, UNFUSED, VAV
STARTER, COMBINATION W/DISCONNECT SWITCH
STARTER OR MOTOR CONTROLLER
POTHEAD
STRESS CONE
AMMETER
VOLTMETER
WATTMETER
WATT-HOUR METER
RECEPTACLE, DUPLEX COUNTER HEIGHT
BLANK OUTLET BOX
RECEPTACLE, QUADRAPLEX ON EMERGENCY POWER
(MOUNT 18" AFF. UNLESS NOTED OTHERWISE
FLOOR OUTLET, RECEPTACLE
GROUNDING BAR
HEADWALL
LIGHT FIXTURE POWER CONNECTION DESIGNATIONS
OPEN - NORMAL POWER CIRCUIT
SHADED - LIFE SAFETY EMERGENCY POWER CIRCUIT
HATCHED - CRITICAL POWER CIRCUIT
RECESSED TROFFER LIGHT FIXTURE.
NOMENCLATURE EXAMPLE :
('A' DESIGNATES LIGHT FIXTURE TYPE, XXX-XX DESIGNATES
CIRCUIT NUMBER) REFER TO DRAWINGS AND LIGHT FIXTURE
SCHEDULES FOR MORE INFORMATION.
CEILING SURFACE MOUNTED LIGHT FIXTURE.
NOMENCLATURE EXAMPLE :
('A' DESIGNATES LIGHT FIXTURE TYPE, XXX-XX DESIGNATES
CIRCUIT NUMBER) REFER TO DRAWINGS AND LIGHT FIXTURE
SCHEDULES FOR MORE INFORMATION.
WALL SURFACE MOUNTED LIGHT FIXTURE.
NOMENCLATURE EXAMPLE :
('A' DESIGNATES LIGHT FIXTURE TYPE, XXX-XX DESIGNATES
CIRCUIT NUMBER) REFER TO DRAWINGS AND LIGHT FIXTURE
SCHEDULES FOR MORE INFORMATION.
PB
P
G
A
V
W
WH
T
T T
J
C C
W W
RC
DB
P
S
P T
B B
DP#__
LP
B
C
S
TC
CATV
CCTV
FO
T
$x w
M
S
OCB
GFCI
VFD
R
B
HVS
LVS
RRB
J
C
S
S
R
R
X
X
WAP
NWS
NCM
CB
DB
WS
RX
ML
FIX
F
ES
CR
P
H
S
A b b b
ELECTRICAL SYMBOLS - LIGHTING CONTROL PLAN
LIGHT SWITCH (# SUBSCRIPT AS INDICATED BELOW):
BLANK =
RECESSED DOWNLIGHT FIXTURE
NOMENCLATURE EXAMPLE :
('b' LOCATED AROUND THE SYMBOL DESIGNATES SWITCHLEG OR
CONTROL CHANNEL) REFER TO DRAWINGS AND LIGHTING CONTROL
SCHEDULES FOR MORE INFORMATION.
RECESSED TROFFER LIGHT FIXTURE
NOMENCLATURE EXAMPLE :
('b' LOCATED AROUND THE SYMBOL DESIGNATES SWITCHLEG OR
LIGHTING CONTROL CHANNEL) REFER TO DRAWINGS AND LIGHTING
CONTROL SCHEDULES FOR MORE INFORMATION.
CEILING SURFACE MOUNTED LIGHT FIXTURE
NOMENCLATURE EXAMPLE :
('b' DESIGNATES SWITCHLEG OR LIGHTING CONTROL CHANNEL)
REFER TO DRAWINGS AND LIGHTING CONTROL SCHEDULES FOR
MORE INFORMATION.
WALL SURFACE MOUNTED LIGHT FIXTURE
NOMENCLATURE EXAMPLE :
('b' DESIGNATES SWITCHLEG OR LIGHTING CONTROL
CHANNEL) REFER TO DRAWINGS AND LIGHTING CONTROL
SCHEDULES FOR MORE INFORMATION.
$X b
LINE VOLTAGE SINGLE POLE SWITCH
X = UPPER CASE LETTERS DESIGNATE LIGHT
SWITCH TYPE. REFER TO LIGHTING
CONTROL DEVICE SCHEDULE ON
DRAWINGS FOR SWITCH TYPE
DESIGNATION
x x = LOWER CASE LETTERS DESIGNATE
SWITCHLEG OR CHANNEL CONTROL
b
XXX-XX
XXX-XX
XXX-XX
CEILING MOUNTED OCCUPANCY SENSOR
(# SUBSCRIPT AS INDICATED BELOW):
X = UPPER CASE LETTERS DESIGNATE
OCCUPANCY SENSOR TYPE. REFER TO
LIGHTING CONTROL DEVICE SCHEDULE ON
DRAWINGS FOR SWITCH TYPE
DESIGNATION
x = LOWER CASE LETTERS DESIGNATE
SWITCHLEG OR CHANNEL CONTROL
LIGHTING CONTROL DEVICES
LIGHTING CONTROL ANNOTATIONLIGHT FIXTURE SYMBOLS AND ANNOTATIONS
LIFE SAFETY LIGHTING
SITE LIGHTING ASSEMBLIES
XXX-XX
INTERIOR PHOTOCELL
CEILING MOUNTED MOTION SENSOR
LIGHTING CONTROL POWER PACK MOUNTED ABOVE ACCESSIBLE
CEILING AND FLUSH MOUNTED IN JUNCTION BOX WITH BLANK
COVER PLATE IN GYP. BOARD CEILING
(# SUBSCRIPT AS INDICATED BELOW):
x
PP = PP INDICATES SWITCH POWER PACK
CONTROLLER
x = LOWER CASE LETTERS DESIGNATE SWITCHLEG OR
CHANNEL CONTROL. NO LETTER INDICATES ALL LIGHT
FIXTURES IN ROOM ARE ON SINGLE CHANNEL AND
CONTROLLED BY LIGHTING CONTROL DEVICE
EXTERIOR PHOTOCELL
PP
TC LIGHTING CONTROL TIME CLOCK
PC
DH
OS
x
X
CT LIGHTING CONTACTOR
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\k gr ie pe nt ro g\ D oc um en ts
\2 1.
_E
LE
C
_R
_k gr ie pe nt ro gJ G
H
.rv t
5/
/2
7:
:4
A
M
E-002
ELECTRICAL SYMBOLS CONSTRUCT MENTAL HEALTH
OUTPATIENT BLDG 52 ADDITION
2101 ELM STREET, FARGO, ND 58102
437-316
05/26/2023 RA KEG
100% BID DOCUMENTS
VEG 21.05 DWG 159 of 188
CONTRACT DOCUMENTS SUBMISSION
FULLY SPRINKLERED
21st AVE. N.
MC
MH
MH
MH
MH
MH
J J JJ
TELE
TELE
T E
LE
TELE
TELE
TELE TELE
TELE
T E
LE
TELE
TELE
TELE
T E
LE
T E
LE
TELE
TELE
TELE
TELE
TELE
TELE
T E
LE
T
E
LE
T E
LE
TELE
TELE CATV
CATV
C A
T V
C A
T V
C A
T V
C A
T V
C A
T V
C A
T V
CATV
CATV
CATV
CATV
CATV
CATV
C A
T V
C A
T V
C A
T V
CATV
CATV
(E) MH
MH-3
(E) MH
(E) MH
MH-27A
(E) MH
CATV
CATV
CATV
CATV
MH-4
MAIN
HOSPITAL
BUILDING
A. CONTRACTOR TO COORDINATE WITH CAMPUS WIDE EHRM UPGRADE
PROJECT. THE EHRM UPGRADE WILL SIGNIFICANTLY CHANGE THE CAMPUS
CABLE ROUTING. CAMPUS LSP CABLING AND BUILDING 52 EXPECTED TO BE
REROUTED OUT OF BUILDING FOOTPRINT. CONTRACTOR TO CONFIRM PRIOR
TO ANY DEMOLITION OF CAMPUS UTILITIES. BUILDING 30 EXPECTED TO HAVE
NEW DUCTBANKS AND BACKBONES. CONTRACTOR TO CONFIRM ROUTING
AND LOCATION. PULL BACK TO FIRST MANHOLE FROM BUILDING 30 AND
PROTECT AND REPURPOSE IF POSSIBLE OR DEMO BACK AND RUN NEW. IF
COORDINATION WITH LSP CABLING IS REQUIRED, CONTACT LUMEN
ENGINEER DAVID MILES, (701) 461-6545.
B. SCHEDULE ALL SHUTDOWNS WITH VAH COR. SHUTDOWN DURATIONS TO BE
AS SHORT AS POSSIBLE.
C. NOT ALL UTILITIES ARE SHOWN FOR CLARITY. REFER TO DRAWING CU101
FOR EXISTING UTILITIES.
D. CONTRACTOR TO PATCH AND REPAIR ANY ASPHALT OR CONCRETE
DISTURBED DURING CONSTRUCTION.
1. RE-STRIPE LOT AS REQUIRED.
2. PROVIDE TRAFFIC CONTROLBARRIER WHERE DIRECTIONAL BORE, DEMO
EQUIPMENT, EXCAVATION, ETC. IS PRESENT.
##KEYNOTES
TELECOM UTILITY NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\k gr ie pe nt ro g\ D oc um en ts
\2 1.
_E
LE
C
_R
_k gr ie pe nt ro gJ G
H
.rv t
5/
/2
7:
:0
A
M
ED101
DEMOLITION TELECOM SITE PLAN CONSTRUCT MENTAL HEALTH
OUTPATIENT BLDG 52 ADDITION
2101 ELM STREET, FARGO, ND 58102
437-316
05/26/2023 RA KEG
100% BID DOCUMENTS
VEG 21.05 DWG 160 of 188
CONTRACT DOCUMENTS SUBMISSION
FULLY SPRINKLERED
64'32'16'8'4'0' N or th
1/16" = 1'-0"
DEMOLITION TELECOM SITE PLAN1
1 ABANDONED CATV CABLE.
2 12 STRAND FIBER OPTIC AND 100 PAIR TELCO IN ONE 3" CONDUIT.
3 REMOVE ALL FIBER OPTIC, CATV, AND COPPER TELECOMMUNICATIONS
BACKBONE FROM BUILDING 30 TO POINT OF ORIGIN IN MAIN HOSPITAL PRIOR
TO DEMOLITION.
UP
21st AVE. N.
MC
P C
J J JJ
EXISTING
MANHOLE 27A
EXISTING TRANSFORMER FEEDING
BUILDING 52 AND 30
7 7
11 12
A. NOT ALL UTILITIES ARE SHOWN FOR CLARITY. REFER TO DRAWING CU101
FOR EXISTING UTILITIES.
B. CONTRACTOR TO PATCH AND REPAIR ANY ASPHALT OR CONRETE
DISTURBED DURING CONSTRUCTION.
1. RE-STRIPE LOT AS REQUIRED.
2. PROVIDE TRAFFIC CONTROL BARRIER WHERE DIRECTIONAL BORE, DEMO
EQUIPMENT, EXCAVATION, ETC. IS PRESENT.
##KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\k gr ie pe nt ro g\ D oc um en ts
\2 1.
_E
LE
C
_R
_k gr ie pe nt ro gJ G
H
.rv t
5/
/2
7:
:0
A
M
ED102
DEMOLITION ELECTRICAL SITE
PLAN
CONSTRUCT MENTAL HEALTH
OUTPATIENT BLDG 52 ADDITION
2101 ELM STREET, FARGO, ND 58102
437-316
05/26/2023 RA MLS
100% BID DOCUMENTS
VEG 21.05 DWG 161 of 188
CONTRACT DOCUMENTS SUBMISSION
FULLY SPRINKLERED
64'32'16'8'4'0'
N or th
1/16" = 1'-0"
DEMOLITION ELECTRICAL SITE PLANE3
1 REMOVE CONDUIT AND WIRING FEEDING BUILDING 30 BACK TO EXISTING
TRANSFORMER.
2 ELECTRICAL FEEDERS TO BE REMOVED. PROVIDE TEMPORARY GENERATOR
TO PROVIDE POWER TO EXISTING BUILDING 52 WHILE SERVICE IS REVISED.
REFER TO SHEET EP101 FOR ADDITIONAL INFORMATION.
3 REMOVE EXISTING 300KVA TRANSFORMER FEEDING BUILDINGS 30 AND 52.
PROTECT EXISTING PRIMARY SIDE CONDUCTORS FOR EXTENSION TO NEW
500KVA TRANSFORMER. REMOVE EXISTING SECONDARY SIDE CONDUCTORS.
PROVIDE18"x18"x12" IN-GRADE SPLICE BOX.
4 LOCATION OF EXISTING PHOTOCELL FOR PARKING LOT LIGHTING CONTROL.
EXISTING PHOTOCELL TO BE RELOCATED WITH CABINET TO NEW LOCATION.
EXTEND EXISTING CONTROL CIRCUITRY TO NEW PHOTOCELL LOCATION.
PROVISIONS SHALL BE MADE TO KEEP THE EXISTING PARKING LOT LIGHTING
FUNCTIONING DURING NIGHTTIME HOURS.
5 EXISTING POLE LIGHTING ASSEMBLY TO BE DISCONNECTED AND REMOVED.
CONTRACTOR TO VERIFY WITH VA COR FOR RIGHT OF FIRST REFUSAL. IF VA
COR DOES NOT RETAIN POSSESION OF LIGHTING ASSEMBLY, CONTRACTOR
TO DISPOSE OF ALONG WITH ASSOCIATED CONCRETE BASE.
6 EXISTING EXTERIOR WALL PACK TO BE DISCONNECTED AND REPLACED WITH
THE FIXTURE WITH EMERGENCY LIGHTING CAPABILITES BEING REMOVED
FROM OTHER LOCATION OF THE BUILDING.
7 EXISTING I-BEAM MOUNTED WEATHERPROOF GFCI RECEPTACLES FOR
BLOCK HEATER CONNECTIONS TO BE REMOVED. PROTECT EXISTING UNITS
FOR REINSTALLATION. PROTECT EXISTING CIRCUITRY FOR EXTENSION TO
NEW LOCATION. NEW CIRCUITRY TO BE RE-ROUTED SO TO INSURE THAT THE
NEW CONDUIT AND WIRE IS NOT IN CONFLICT WITH NEW BUILDING. REFER
TO ELECTRICAL POWER SITE PLAN, SHEET EP101, FOR MORE INFORMATION.
8 EXISTING POLE LIGHTING ASSEMBLY WITH SOLAR PANEL AND BATTERIES TO
BE DISCONNECTED, REMOVED AND STORED FOR REINSTALLATION AS PART
OF THIS PROJECT. ASSOCIATED CONCRETE BASE TO BE REMOVED AND
DISCARDED.
9 EXISTING WALL PACK WITH EMERGENCY LIGHTING CAPABILITES TO BE
DISCONNECTED AND REMOVED FROM EXISTING LOCATION ALONG WITH
EMERGENCY POWER SUPPLY. PROVIDE FINISHED COVER PLATE THAT WILL
BE PAINTED TO MATCH EXISTING BRICK COLOR.
10 NEW LOCATION OF EXISTING WALL PACK WITH EMERGENCY LIGHTING
CAPABILITES. MOVE EMERGENCY POWER SUPPLY TO A LOCATION ABOVE
THE EXISTING CEILING IN THIS AREA AND CONNECT TO EXISTING CIRCUIT.
PROVIDE NEW LAMPS FOR BOTH THE NORMAL AND THE EMERGENCY
LIGHTING COMPONENTS.
11 REMOVE POWER AND DATA TO SYSTEMS FURNITURE IN SUPPORT OF
TEMPORARY ENTRANCE VESTIBULE WORK (REF ARCH). RESTORE AREA TO
EXISTING CONDITIONS UPON NEW BUILDING 30 COMPLETION.
12 REVISE LIGHT FIXTURE LOCATIONS IN CEILINGS TO COORDINATE WITH
TEMPORARY VESTIBULE PARTITIONS. PROVIDE NEW TEMPORARY EXIT SIGN
AND EMERGENCY BATTERY LIGHT IN TEMPORARY VESTIBULE. RESTORE
AREA TO EXISTING CONDITIONS UPON NEW BUILDING 30 COMPLETION .
E
PC
AA1AA1
AA1
AA1
AA1
A. ALL POLE MOUNTED LIGHTING TO BE CONTROLLED BY PARKING LOT
LIGHTING PHOTOCELL.
B. CONTRACTOR TO USE DIRECTIONAL BORE EQUIPMENT AND AVOID
TRENCHING FOR NEW PATHWAYS.
1. CONTRACTOR TO PATCH AND REPAIR ANY ASPHALT DISTURBED DURING
CONSTRUCTION.
2. RE-STRIPE LOT AS REQUIRED.
3. PROVIDE TRAFFIC CONTROL BARRIER WHERE DIRECTIONAL BORE,
EQUIPMENT, EXCAVTAION, ETC. IS PRESENT.
##KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\k gr ie pe nt ro g\ D oc um en ts
\2 1.
_E
LE
C
_R
_k gr ie pe nt ro gJ G
H
.rv t
5/
/2
7:
:0
A
M
EL101
ELECTRICAL LIGHTING SITE PLAN CONSTRUCT MENTAL HEALTH
OUTPATIENT BLDG 52 ADDITION
2101 ELM STREET, FARGO, ND 58102
437-316
05/26/2023 RA JEE
100% BID DOCUMENTS
VEG 21.05 DWG 162 of 188
CONTRACT DOCUMENTS SUBMISSION
FULLY SPRINKLERED
64'32'16'8'4'0' N or th
1/16" = 1'-0"
ELECTRICAL LIGHTING SITE PLANE3
1. INTERCEPT EXISTING UNDERGROUND CIRCUITRY. REMOVE EXISTING
WIRING. EXTEND CONDUIT TO NEW LIGHT POLE ASSEMBLY. PROVIDE NEW
WIRING FROM EXISTING LIGHT POLE ASSEMBLY TO THE NEW LIGHT POLE
ASSEMBLY.
2. EXISTING LIGHT POLE ASSEMBLY.
3. MINIMUM 1 1/2" CONDUIT, 3#8 + GRD. UNDERGROUND ELECTRICAL
CIRCUITING.
4. NEW LOCATION OF EXISTING LIGHTING ASSEMBLY WITH SOLAR PANEL
REMOVED AND STORED DURING DEMOLITION PHASE TO BE REINSTALLED
ON NEW CONCRETE BASE.
5. NEW LOCATION OF EXISTING PHOTOCELL CONTROLLING SITE LIGHTING.
6. EXTEND NEW CIRCUITRY FROM SITE LIGHTING CIRCUIT BREAKER LOCATED
AT THE NEW LOCATION OF EXISTING CABINET TO NEW LIGHT POLE
ASSEMBLY. MINIMUM 1 1/2" CONDUIT, 3#8 + GRD. UNDERGROUND
ELECTRICAL CIRCUITING.
J
CT CT
3 4 6
A
B
G
K
H
5 7
C
D
E
J
F
E.8
G.2
A42
A42
A42
A42
A42
A42
A42
A42
A42
A42
A42
A42
A42
A42
A42
A42
A42
A42
A42
A42
A42
A42
A42
A42
A42
A42
A42A42
A42 A42
A42A42
A42 A42
A42 A42A42E
A42A42
A42 A42
A42E
A42E
F1E
A42
A21A21
A21
A21
A22 A22 A22
A22 A22 A22
A22 A22 A22
A22 A22 A22
A22 A22 A22
A22 A22 A22
A21 A21 A42
A42 A22E
A22
A22
A22E
A22
A22
A22E
A22E
A22
A22
A22E
A22
A22
A22E
A22 A22 A22E A22
A22E
A22
A22
A22E A22 A22 A22E
A22E
A22
A22
F1 F1 F1 F1
V23
C2E
C2
C2
C2
C2E
C2
C2
C2
C2E
C2
C2
C2
C2E
C2
C2
C2
C2E
C2
C2
C2
C2E
C2
C2
C2E
C2
C2E
C2
C2 C2 C2
C2
C2
C2E
C2
C2 C2E C2
C2 C2 C2
B62
B82 B122
V23
F2
F2
F1E
F1
C2
CC1
CC1
CC1
CC1
CC1
CC1
BB4
CC1 CC1 CC1 CC1
CC1 CC1 CC1
110 108
142 140
139141143
147 129
131A
148 130
138 136
131B
A42A42
A42A42
A42A42
L81E
L81E
E1 E1
E1
E1E1
E2 E2
E2
F1E
E2E2
U21U21
B102
C1
D31 D51
D31
D31
V23
C2 C2
C2
11 1
BB4
+10' - 0"
1 1
BB4
BB4
+10' - 0"
BB4
BB4 BB4 BB4
BB4
BB4
BB4
BB4
BB4
BB4BB4BB4
+10' - 0"
+10' - 0"
+10' - 0" +10' - 0" +10' - 0"
+10' - 0"
+10' - 0"
+10' - 0"
+10' - 0"
+10' - 0"
+10' - 0"
+10' - 0" +10' - 0" +10' - 0"
BB4
BB4
+10' - 0"
+10' - 0"
E1
E1
C2
C2
C2
H151 H81
B-11
B-11
B-10
B-10
B-11
B-11
B-11
B-11
B-11
B-11
B-10
B-10
B-10
B-10
B-10
B-10
B-10 B-10 B-10
B-10 B-10 B-10
B-10 B-10 B-10
B-10 B-10 B-10
B-10 B-10 B-10
B-10 B-10 B-10
B -1
1A42
B -1
B -1
B -1
B
-1
B -1
B -1
B -1
B -1
B -1
B -1
B -1
B-11B-11
B-11
B-11
B-10
B-10
B-10
B-10
B-10
B-10
B-10
B-10
B-10
B-10
B-10
B-10
B-10
B -1
B-10 B-10 B-10 B-10
B-10 B-10
B-10
B-10 B-10
B -1
B -1
B -1
B -1
B -1
B
-1
B -1
B -1
B -1
B
-1
B -1
B-14
B-14
B-14
B-14
B-14
B-14
B-14
B-14
B-14
B-14
B-14
B-14
B-14 B-14 B-14 B-14
B-14
B-14
B-14
B-16
B-16
B-16
B-16
B-16
B-16
B-16 B-16 B-16
B-16 B-16 B-16 B-15
B-15 B-15
B-15
B-15 B-15
B-15
B-15
B-15
B-15
B-15
B-15 B-15 B-15
B-15
B-15
B-15
B-15 B-15
B-15
B-15 B-15
B-15
B-15
B-15
B-15 B-15
B-15
B-15 B-15 B-15
B-15 B-15
B-15
B-15 B-15
B-15 B-15
B-15 B-15
B-15 B-15
B-15
B-15
B-15 B-15 B-15B-15
B-16
B-16
B-16 B-16 B-16
B-16
B-16
B-16
B-16
B-16
B-16
B-16B-16B-16
B-16
B-16
B-16
B-16
B -1
B -1
C -7
C -7
C -7
F1
B-15
B-15
B-15
B-15
B-15
B -1
B-15
B-15 B-15
B-15 B-15
B-15
B -1
B-15
B-11
B-11
B -1
B -1
B
-1
B-15
B -1
A B
B-14
B -1
B-15 B-15
B-15
C
F1E
B -1
B-16
B-14
B-15
F1 F1 F1
B-10
B -1
B -1
B -1
D.3
6.13.9
G.6
F1
B -1
B-10 B-10
B-10B-11 B-11
BB4 BB4 BB4
B-16 B-16
CC1 CC1
M41E M41E E-11 E-11
1M41E
M41E
B-14
B-14
+8' - 0"
+8' - 0"
+8' - 0" +8' - 0"
B-15
B-16
##KEYNOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\k gr ie pe nt ro g\ D oc um en ts
\2 1.
_E
LE
C
_R
_k gr ie pe nt ro gJ G
H
.rv t
5/
/2
7:
:0
A
M
EL111
ELECTRICAL LIGHTING RCP -
LEVEL 1
CONSTRUCT MENTAL HEALTH
OUTPATIENT BLDG 52 ADDITION
2101 ELM STREET, FARGO, ND 58102
437-316
05/26/2023 RA JEE
100% BID DOCUMENTS
VEG 21.05 DWG 163 of 188
CONTRACT DOCUMENTS SUBMISSION
FULLY SPRINKLERED
32'16'8'4'2'0' N or th
1/8" = 1'-0"
ELECTRICAL LIGHTING RCP - LEVEL 1F4
1. CONNECT TO UNSWITCHED PORTION OF THE CIRCUIT.
2. STRIP LIGHT FIXTURE TO BE WALL MOUNTED ABOVE THE DOOR.
3. EMERGENCY BACKUP LIGHTING INVERTER EQUAL TO BODINE ELI-S-100,
100VA MAXIMUM OUTPUT POWER. UNIT TO BE MOUNTED ON THE TOP SIDE
OF THE SOFFIT STRUCTURE. LOCATE THE UNIT IN LOCATION WHERE IT IS
NOT VISIBLE WHEN STANDING INSIDE THE VESTIBULE 117.
4. TYPE L81E LUMINAIRE TO HAVE TWO CIRCUIT CONTROL. THE TOP
ILLUMINATION CIRCUIT TO BE CONNECTED TO CIRCUIT VIA INVERTER
DESCRIBED IN NOTE #3.
5. EXISTING EXTERIOR WALL PACK TO BE DISCONNECTED, REMOVED, AND
REPLACED WITH NEW LUMINAIRE. RECONNECT TO EXISTING CIRCUITRY.
6. EMERGENCY BACKUP LIGHTING INVERTER EQUAL TO BODINE ELI-S-100,
100VA MAXIMUM OUTPUT POWER.
7. MOUNTING HEIGHTS SHOWN IN THE AREA ARE MEASURED FROM FIRST
LEVEL FLOOR.
ROOM NUMBER KEY
NUMBER NAME
101 VESTIBULE
102 MECH
103 BARIATRIC RR
104 BARIATRIC OFFICE
105 OFFICE
106 OFFICE
107 CORR
108 OFFICE
109 COMM / EHRM
110 OFFICE
111 ELEV. EQUIP.
112 OFFICE
113 OFFICE
114 OFFICE
115 STAIR A
116 ELEV
117 VESTIBULE
118 RR
119 CORR
120 WAITING
121 WAITING
122 RECEPTION
123 ADMIN
124 STOR
126 FIRE PUMP
127 WORKRM / STOR
128 ELEC
129 GROUP THERAPY
130 STOR
131A ELEC
131B TELEHEALTH
132 STAIR B
133 OFFICE
134 OFFICE
135 CORR
136 OFFICE
137 OFFICE
138 OFFICE
139 OFFICE
140 OFFICE
141 OFFICE
142 OFFICE
143 OFFICE
144 OFFICE
145 OFFICE
146 OFFICE
147 GROUP THERAPY
148 STOR
149 HAC
150 OFFICE
151 LOUNGE
152 RR
153 CLOSET
154 ELEVATOR CAR 1
155 ELEVATOR CAR 2
156 TEMP VESTIBULE
PANEL NAMES
PANEL ID
PANEL
NAME
ROOM
NUMBER
A 52A-N1A-1 128
B 52A-N1A-2 128
C 52A-N1B-1 109
D 52A-N2A-1 226A
E 52A-N2A-2 226A
F 52A-N2B-1 205
G 52A-N1B-2 109
H 52A-N2B-2 205
OD ODOD OD
O D
O D
O S
O S
O S
O S
O S x
LV
D O
D O
D O
D O
D
OS
O D
O
D OD OD OD OD
O D
O D
O S
PP
PP PP
PP
OD OD OD
LV
Da b
LV
D
O D
OSOS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS OS
OS
OS
DH
OS OS
OS
OS
OS
PP
b
LV
OS
LVD
O S
PC
OS
O S
PP PP
OD
DH
TC TC
CT CT
3 4 6
A
B
G
K
H
5 7
C
D
E
J
F
E.8
G.2
112 110 108 106
142 140
137139141143
117 101
147 129
131A
149 148 130
138 136
131B b b b b b b b b b
DT
aa/ab a/b a/b ab ab abab b b
3 3 a/b
DT
D.3 aa
6.13.9
G.6 a a aa a a a aaa a a a ba
B A
C G
LVD
b a 3 aa
LVD
aa ab ab
8 8
A. ALL LIGHTING CONTROL POWER PACKS SHALL BE MOUNTED NEAR DOOR
ABOVE THE CEILING IN ROOMS WITH ACCESSIBLE CEILINGS UNLESS
OTHERWISE NOTED. MOUNT POWER PACKS IN A FLUSH MOUNTED BOX IN
ROOMS WITH INACCESSIBLE CEILING. POWER PACK TAGGING SHALL BE
PROVIDED AS SPECIFIED IN SECTION 26 0923.
B. MAINTAIN 4'-0" RECOMMENDED MANUFACTURER CLEARANCE BETWEEN
OCCUPANCY SENSOR AND MECHANICAL DIFFUSERS FOR PROPER
OCCUPANCY SENSOR FUNCTION. FIELD COORDINATE.
C. COORDINATE LIGHTING CONTROL DEVICE LOCATIONS WITH INTERIOR
FEATURES AND FURNISHINGS TO ASSURE READY ACCESS AND PROPER
SENSOR PERFORMANCE.
D. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL
BE OBTAINED FROM THE ARCHITECTURAL REFLECTED CEILING PLAN.
##KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\k gr ie pe nt ro g\ D oc um en ts
\2 1.
_E
LE
C
_R
_k gr ie pe nt ro gJ G
H
.rv t
5/
/2
7:
:1
A
M
EL112
ELECTRICAL LIGHTING CONTROL
RCP - LEVEL 1
CONSTRUCT MENTAL HEALTH
OUTPATIENT BLDG 52 ADDITION
2101 ELM STREET, FARGO, ND 58102
437-316
05/26/2023 RA JEE
100% BID DOCUMENTS
VEG 21.05 DWG 164 of 188
CONTRACT DOCUMENTS SUBMISSION
FULLY SPRINKLERED
32'16'8'4'2'0' N or th
1/8" = 1'-0"
ELECTRICAL LIGHTING CONTROLS RCP - LEVEL 1F4
ROOM NUMBER KEY
NUMBER NAME
101 VESTIBULE
102 MECH
103 BARIATRIC RR
104 BARIATRIC OFFICE
105 OFFICE
106 OFFICE
107 CORR
108 OFFICE
109 COMM / EHRM
110 OFFICE
111 ELEV. EQUIP.
112 OFFICE
113 OFFICE
114 OFFICE
115 STAIR A
116 ELEV
117 VESTIBULE
118 RR
119 CORR
120 WAITING
121 WAITING
122 RECEPTION
123 ADMIN
124 STOR
126 FIRE PUMP
127 WORKRM / STOR
128 ELEC
129 GROUP THERAPY
130 STOR
131A ELEC
131B TELEHEALTH
132 STAIR B
133 OFFICE
134 OFFICE
135 CORR
136 OFFICE
137 OFFICE
138 OFFICE
139 OFFICE
140 OFFICE
141 OFFICE
142 OFFICE
143 OFFICE
144 OFFICE
145 OFFICE
146 OFFICE
147 GROUP THERAPY
148 STOR
149 HAC
150 OFFICE
151 LOUNGE
152 RR
153 CLOSET
154 ELEVATOR CAR 1
155 ELEVATOR CAR 2
156 TEMP VESTIBULE
1. 3-WAY LIGHT SWITCH FOR ELEVATOR PIT LIGHTS. COORDINATE FINAL
MOUNTING LOCATION WITH ELEVATOR CONTRACTOR.
2. LIGHTING CONTROL PHOTOCELL TO CONTROL LIGHTING CONTROL
CONTACTOR #CX LOCATED IN ELECTRICAL ROOM 128. MOUNT AT 10 A.F.G.
PHOTOCELL TO HAVE 120 VAC OUTPUT.
3. 4 POLE LIGHTING CONTACTOR #C1 TO CONTROL ALL NON-EMERGENCY
LIGHTING LOCATED IN FIRST LEVEL CORRIDORS AND WAITING ROOMS.
4. LIGHTING IN THE STAIRWELL TO BE CONTROLLED WITH INTEGRAL
OCCUPANCY SENSOR MOUNTED IN LIGHT FIXTURES.
5. LIGHT FIXTURES IN STAIRWELLS TO BE CONNECTED TO UNSWITCHED
PORTION OF CIRCUIT.
6. 4 POLE LIGHTING CONTACTOR #CX TO CONTROL ALL EXTERIOR BUILDING
MOUNTED LIGHTING.
7. GENERAL LIGHTING IN ALL CORRIDORS AND WAITING ROOMS ON THIS
LEVEL TO BE CONTROLLED VIA CONTRACTOR #C1. (ROOM #107, 119, 120,
121, 122, AND 135.
8. ALL EXTERIOR BUILDING MOUNTED LIGHTING TO BE CONTROLLED VIA
CONTACTOR #CX.
9. TIME CLOCK FOR CONTACTOR #C1 AND C2 CONTROL.
10. TIME CLOCK FOR CONTACTOR #CX CONTROL.
C T
3 4 6
A
B
G
K
H
5 7
C
D
E
J
F
E.8
G.2
A42
A42
A42
A42
A42
A42
A42
A42
A21A21
A21A21
A22E
A22
A22
A22E
A22
A22
A22E
A22E
A22
A22
A22E
A22
A22
A22E
A22 A22 A22 A22
A42 A42
A42 A42
A42 A42
A42 A42
A42
A42
A42
A42
A42
A42
A42E
A42
A42
A42
A42
A42
A42 A42
A42
A42 A42
C2 C2
A42 A42
A42 A42
A42 A42
A42 A42
A42 A42
A42 A42
A42E
F1 F1
A22E
A22
A22
A22E A22 A22 A22E
A22E
A22
A22
A42
A42
A42
A42
A42
A42
A42
A42
A42 A42
A42E V23
C2 C2
C2
C2
C2E C2
C2
C2E
C2
C2
C2
C2E C2 C2E
C2
C2E
C2E
A42E
F1
F1
V23
239 237 235 233
238 236
209210212213
203218
244A
226A
226B
A42A42
A43 A43
A42 A42
A42A42
A42A42
A42A42
A42EA42
A42 A42
B41
E1
E1
C2 C2
B82
A42 A42
V23
E1
E2 E2
E2
E2
E2
U21 U21
V23
E1
F1
E2
A23 A23
A43E
E-27
E-27
E-27
E-27
E-27
E-27
E-27
E-27
E-19
E-19
E-21
E-21
E-21
E-21
E-21
E-21
E-21
E-21
B-21 B-21
E-19
E-19
E-19
E-19
E-19
E-19
E-19
E-22
B -2
B -2
E -2
E -2
E -2
E -2
E -2
E -2
E -2
E -2
E -2
E -2
E -2
E -2
E -2
E -2
E -1
E -1
E -1
E -1
E -1
E
-1
E -1
E
-1
E -1
E
-1
E -1
E -1
E -1
E -2
2 E -2
E -2
E -2
E -2
E -2
E -2
E -2
E -2
E -2
E -2
E -2
E -2
E -1
E -1
E -2
E -2
E -2
E -1
E-27E-27
E-27E-27
E-27
E-27
E-27
E-27
E-27
E-27
E-27
E-27
E-27
E-27
E-27
E-27
E-27
E-27
E-27 E-27 E-27 E-27
E-27 E-27
B62
C2 C2
E1 E-21
E-21
E-21
E-21
E-21 E-21 E-21 E-21
E-21
E-21
E-21
E -2
E-22
E-22 E-22
E-22
E-22
E-22 E-22
E-22
E-22
E-22
E-22
E-22
E-22 E-22 E-22
E-22
E-22
E-22 E-22
E-22E-22
E -2
E -2
E-22B62
E-22 E-22
E-22
E-27 E-27
E-22
E-21
E-22
E-22 E
-2
B121
B121
H151
E-22
E-22 E-22
B81B81
E -2
E
-2
D
E
F
F -7
F -7
F -7
E-19
E-27
E-22
E-21
T81 E-22
C2EC2E E-22
E-22
H
D.3
C2E
E-22
6.13.9
G.6
H81
E-22
E-27
E-19
E-27 E-27
E -2
F1E-21
E-21
E-21
F1 F1 F1
M41E M41E E-11 E-11
B-14
B-14
M41E
M41E
+22' - 0"
+22' - 0"
+22' - 0" +22' - 0"
M41E
M21 B-14
B-14
+15' - 0"
+15' - 0"
E-22
##KEYNOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\k gr ie pe nt ro g\ D oc um en ts
\2 1.
_E
LE
C
_R
_k gr ie pe nt ro gJ G
H
.rv t
5/
/2
7:
:1
A
M
EL121
ELECTRICAL LIGHTING RCP -
LEVEL 2
CONSTRUCT MENTAL HEALTH
OUTPATIENT BLDG 52 ADDITION
2101 ELM STREET, FARGO, ND 58102
437-316
05/26/2023 RA JEE
100% BID DOCUMENTS
VEG 21.05 DWG 165 of 188
CONTRACT DOCUMENTS SUBMISSION
FULLY SPRINKLERED
32'16'8'4'2'0' N or th
1/8" = 1'-0"
ELECTRICAL LIGHTING RCP - LEVEL 2F4
ROOM NUMBER KEY
NUMBER NAME
201 CORR
202 RR
203 RR
204 OFFICE
205 COMM / EHRM
206 OFFICE
207 OFFICE
208 CORRIDOR
209 OFFICE
210 OFFICE
211 STOR
212 OFFICE
213 OFFICE
214 MED ROOM
215 OFFICE
216 OFFICE
217 STAIR A
218 ELEV
219 RR
220 RECEPTION / WORKSTATION
221 WAITING
222 PHARM D
223 GENERAL TREATMENT
224 WORK ROOM
225 FLEX OFFICE
226A ELEC
226B TELEHEALTH
227 OFFICE
228 STAIR B
229 CLEAN LINEN
230 SOILED LINEN
231 OFFICE
232 OFFICE
233 OFFICE
234 OFFICE
235 OFFICE
236 OFFICE
237 OFFICE
238 OFFICE
239 OFFICE
240 CORRIDOR
241 OFFICE
242 OFFICE
243 OFFICE
244 CONF ROOM
244A STOR
245 OFFICE
246 HAC
247 OFFICE
248 CLOSET
249 STAFF LOUNGE
250 RR
1. CONNECT TO UNSWITCHED PORTION OF THE CIRCUIT.
2. STRIP LIGHT FIXTURE TO BE WALL MOUNTED ABOVE THE DOOR.
3. AFTER HOURS WALK-THRU / EMERGENCY LIGHT OPERATION ONLY. LIGHT
FIXTURE TO OPERATE ONLY AFTER HOURS AND UPON LOSS OF NORMAL
POWER. CONNECT BACK-UP BATTERY TO UNSWITCHED PORTION OF THE
CIRCUIT AND CONTROL CIRCUIT TO BE CONNECTED TO NORMALLY CLOSED
CONTACT IN CONTACTOR #C2..
4. MOUNTING HEIGHTS SHOWN IN THE AREA ARE MEASURED FROM FIRST
LEVEL FLOOR.
5. LIGHT FIXTURE TO BE MOUNTED TO BOTTOM OF OVERHEAD DOOR
ENCLOSURE.
6. 4 POLE LIGHTING CONTACTOR #C2 TO CONTROL ALL LIGHTING LOCATED IN
FIRST LEVEL CORRIDORS AND WAITING ROOMS. 3 NORMALLY OPEN
CONTACT AND 1 NORMALLY CLOSED CONTACT.
PANEL NAMES
PANEL ID
PANEL
NAME
ROOM
NUMBER
A 52A-N1A-1 128
B 52A-N1A-2 128
C 52A-N1B-1 109
D 52A-N2A-1 226A
E 52A-N2A-2 226A
F 52A-N2B-1 205
G 52A-N1B-2 109
H 52A-N2B-2 205
OD OD OD OD
O S
ODODOD
O D
O D
O D
O D
O D
O D a
LVD
O S
O S
OS
a
LV
D O
D O
D O
D O
D O
D OD OD OD OD
OD OS
O S
O D
O D
O D
OS
O D
O D
PP
PP
PP
OS
PP
OS
LVD
OSOS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS OS
OS
OS
PP
x
LVD
OS
OSOS
LV
D
O S
OS
OS
OS
PP
LVD
b
O S b
LV
PP
C T
3 4 6
A
B
G
K
H
5 7
C
D
E
J
F
E.8
G.2
239 237 235 233
238 236
209210212213
244A
226A
226B c cDT c a/ba a b b
DT
a/b
DT
DT
D.3
6.13.9
G.6 b a b a b a a aa
A. ALL LIGHTING CONTROL POWER PACKS SHALL BE MOUNTED NEAR DOOR
ABOVE THE CEILING IN ROOMS WITH ACCESSIBLE CEILINGS UNLESS
OTHERWISE NOTED. MOUNT POWER PACKS IN A FLUSH MOUNTED BOX IN
ROOMS WITH INACCESSIBLE CEILING. POWER PACK TAGGING SHALL BE
PROVIDED AS SPECIFIED IN SECTION 26 0923.
B. MAINTAIN 4'-0" RECOMMENDED MANUFACTURER CLEARANCE BETWEEN
OCCUPANCY SENSOR AND MECHANICAL DIFFUSERS FOR PROPER
OCCUPANCY SENSOR FUNCTION. FIELD COORDINATE.
C. COORDINATE LIGHTING CONTROL DEVICE LOCATIONS WITH INTERIOR
FEATURES AND FURNISHINGS TO ASSURE READY ACCESS AND PROPER
SENSOR PERFORMANCE.
D. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL
BE OBTAINED FROM THE ARCHITECTURAL REFLECTED CEILING PLAN.
##KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\k gr ie pe nt ro g\ D oc um en ts
\2 1.
_E
LE
C
_R
_k gr ie pe nt ro gJ G
H
.rv t
5/
/2
7:
:1
A
M
EL122
ELECTRICAL LIGHTING CONTROLS
RCP - LEVEL 2
CONSTRUCT MENTAL HEALTH
OUTPATIENT BLDG 52 ADDITION
2101 ELM STREET, FARGO, ND 58102
437-316
05/26/2023 RA JEE
100% BID DOCUMENTS
VEG 21.05 DWG 166 of 188
CONTRACT DOCUMENTS SUBMISSION
FULLY SPRINKLERED
32'16'8'4'2'0' N or th
1/8" = 1'-0"
ELECTRICAL LIGHTING CONTROLS RCP - LEVEL 2F4
ROOM NUMBER KEY
NUMBER NAME
201 CORR
202 RR
203 RR
204 OFFICE
205 COMM / EHRM
206 OFFICE
207 OFFICE
208 CORRIDOR
209 OFFICE
210 OFFICE
211 STOR
212 OFFICE
213 OFFICE
214 MED ROOM
215 OFFICE
216 OFFICE
217 STAIR A
218 ELEV
219 RR
220 RECEPTION / WORKSTATION
221 WAITING
222 PHARM D
223 GENERAL TREATMENT
224 WORK ROOM
225 FLEX OFFICE
226A ELEC
226B TELEHEALTH
227 OFFICE
228 STAIR B
229 CLEAN LINEN
230 SOILED LINEN
231 OFFICE
232 OFFICE
233 OFFICE
234 OFFICE
235 OFFICE
236 OFFICE
237 OFFICE
238 OFFICE
239 OFFICE
240 CORRIDOR
241 OFFICE
242 OFFICE
243 OFFICE
244 CONF ROOM
244A STOR
245 OFFICE
246 HAC
247 OFFICE
248 CLOSET
249 STAFF LOUNGE
250 RR
1. GENERAL LIGHTING IN ALL CORRIDORS AND WAITING ROOMS ON THIS
LEVEL TO BE CONTROLLED VIA CONTRACTOR #C2. (ROOM #201, 208, 221,
AND 240.)
2. LIGHTING IN THE STAIRWELL TO BE CONTROLLED WITH INTEGRAL
OCCUPANCY SENSOR MOUNTED IN LIGHT FIXTURES.
3. LIGHT FIXTURES IN STAIRWELLS TO BE CONNECTED TO UNSWITCHED
PORTION OF CIRCUIT.
4. 4 POLE LIGHTING CONTACTOR #C2 TO CONTROL ALL LIGHTING LOCATED IN
SECOND LEVEL CORRIDORS AND WAITING ROOMS. 3 POLES OF THE
CONTACTOR TO BE SET TO NORMALLY OPEN AND ONE CONTACTOR TO BE
SET TO NORMALLY CLOSED.
3 4 6
A
B
G
K
H
5 7
C
D
E
J
F
E.8
G.2
F1 F1 F1
F1
F1
F1
F1
F1
F1
F1F1
EM2
EM2
EM2
EM2
EM2
EM2
EM2
EM2
E -3
E -3
E -3
E-39
E-39
E -3
E -3
E -3
E
-3
E -3
E
-3
E -3
E
-3
E -3
E-39
E1
E2 a
E-39
1E-39
E-39
E-39
E-39
E-39
E-39
E-39
E-39
E-39
F1
F1
F1
F1
BB4
E-39 b b a a a a a a a a a aa a a aa
D.3
6.13.9
G.6
+7' - 0"
+7' - 0"
+7' - 0"
+10' - 0"
+7' - 0"
+7' - 0"
+7' - 0"
+7' - 0"
+7' - 0"
M41E
M21 M41E
B-14
B-14
+7' - 3"
+7' - 3"
M21
B-14
B-14
+28' - 5"
+28' - 5"
##KEYNOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\k gr ie pe nt ro g\ D oc um en ts
\2 1.
_E
LE
C
_R
_k gr ie pe nt ro gJ G
H
.rv t
5/
/2
7:
:2
A
M
EL131
ELECTRICAL LIGHTING PLAN -
PENTHOUSE
CONSTRUCT MENTAL HEALTH
OUTPATIENT BLDG 52 ADDITION
2101 ELM STREET, FARGO, ND 58102
437-316
05/26/2023 RA JEE
100% BID DOCUMENTS
VEG 21.05 DWG 167 of 188
CONTRACT DOCUMENTS SUBMISSION
FULLY SPRINKLERED32'16'8'4'2'0'
N or th
1/8" = 1'-0"
ELECTRICAL LIGHTING - PENTHOUSEF4
1. LIGHT FIXTURE TO BE CONNECTED TO UNSWITCHED PORTION OF CIRCUIT.
2. LIGHTING IN THE STAIRWELL TO BE CONTROLLED WITH INTEGRAL
OCCUPANCY SENSOR MOUNTED IN LIGHT FIXTURES.
3. LIGHT FIXTURES IN STAIRWELLS TO BE CONNECTED TO UNSWITCHED
PORTION OF CIRCUIT.
4. MOUNTING HEIGHTS SHOWN IN THE AREA ARE MEASURED FROM FIRST
LEVEL FLOOR.
PANEL NAMES
PANEL ID
PANEL
NAME
ROOM
NUMBER
A 52A-N1A-1 128
B 52A-N1A-2 128
C 52A-N1B-1 109
D 52A-N2A-1 226A
E 52A-N2A-2 226A
F 52A-N2B-1 205
G 52A-N1B-2 109
H 52A-N2B-2 205
J
J
T
TP
TP
H
E
T
TP
T
78 8
ELECTRICAL SITE WORK PHASING PLAN.
A. INSTALL NEW 750 KVA UTILITY TRANSFORMER.
B. PROVIDE CONDUCTORS AND RACEWAY BACKFEEDING EXISTING BUILDING 52
FROM NEW TRANSFORMER TO BUILDING 52.
C. PROVIDE CONDUCTORS AND RACEWAY FROM NEW TRANFORMER TO
BUILDING 52A AIN DISTRIBUTION EQUIPMENT.
D. PROVIDE CONDUCTORS AND RACEWAAY FROM NEW TRANSFORMER TO FIRE
PUMP EQUIPMENT.
E. ONCE NEW RACEWAY AND CONDUCTORS ARE PLACED, SCHEDULE A
WEEKEND OUTAGE AND TRANSITION FROM EXISTING TO NEW.
F. REMOVE EXISTING DISTIRBUTION AS REQUIRED.
G. NOT ALL UTILITIES ARE SHOWN FOR CLARITY. REFER TO DRAWING CU101
FOR EXISTING UTILITIES.
##KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\k gr ie pe nt ro g\ D oc um en ts
\2 1.
_E
LE
C
_R
_k gr ie pe nt ro gJ G
H
.rv t
5/
/2
7:
:2
A
M
EP101
ELECTRICAL POWER SITE PLAN CONSTRUCT MENTAL HEALTH
OUTPATIENT BLDG 52 ADDITION
2101 ELM STREET, FARGO, ND 58102
437-316
05/26/2023 RA MLS
100% BID DOCUMENTS
VEG 21.05 DWG 168 of 188
CONTRACT DOCUMENTS SUBMISSION
FULLY SPRINKLERED
64'32'16'8'4'0'
N or th 1" = 20'-0"
ELECTRICAL SITE POWER PLANE3
1. PROVIDE NEW SECONDARY FEEDERS FROM NEW TRANSFORMER TO NEW
MDP.
2. LOCATION FOR NEW 750KVA TRANSFORMER. PROVIDE NEW PAD.
REFERENCE ELECTRICAL DETAILS FOR TRANSFORMER PAD SIZING.
PROVIDE MEDIUM VOLTAGE WIRING AND SPLICE BACK AT MANHOLE.
VERFIY EXACT LOCATION AND REQUIREMENTS WITH CIVIL AND
LANSCAPING DRAWINGS.
3. CONNECT NEW TRANSFORMER TO EXISTING SITE UTILITY FEED. PROVIDE
SPLICES AS REQUIRED.
4. NEW 18"x18"x12" SPLICE BOX. INTERCEPT EXISTING 300 KVA TRANSFORMER
PRIMARY FEEDERS AND EXTEND TO NEW TRANSFORMER LOCATION.
5. ELECTRICAL FEED TO NEW FIRE PUMP. REFER TO SHEETS EP111 AND E-602
FOR MORE INFORMATION.
6. EXTEND NEW FEEDER TO BUILDING 52. NEW FEEDER TO MATCH EXISTING.
VERIFY EXACT LOCATION AND ROUTING WITH VA PRIOR TO ROUGH-IN.
REMOVE TEMPORARY GENERATOR AFTER FINAL CONNECTIONS MADE TO
REFEED BUILDING 52.
7. NEW 18"x18"x12" SPLICE BOX.
8. NEW LOCATION FOR EXISTING I-BEAM WITH WEATHERPROOF GFCI
RECEPTACLES REMOVED DURING DEMOLITION. EXTEND EXISTING
CIRCUITRY PROTECTED DURING DEMOLITION TO NEW LOCATION. REFER
TO DEMOLITION ELECTRICAL SITE PLAN, SHEET ED102, FOR MORE
INFORMATION.
9. COORDINATE WITH FOUNDATION WORK AND STEEL ERECTION FOR
CONCRETE ENCASED ELECTRODE AND OTHER GROUNDING
REQUIREMENTS. REFER TO ONE-LINE DIAGRAM, E-500 SHEET SERIES
DETAILS, AND SPECIFICATIONS.
C CC
S B
S B
C
J J
J
J
J
J
J
J
J
JJ
TU
TU TU
TU
TU
TU
TU
TU
TU
TU
TU
TU
TU
TU
TU
TU
TU
TU
TU
TU
TU
J
J
J
J
J J
JJ
J J
J
JJ
J
J
J
J
J
J
J
J J
J
J
J
J
J J
J
J
J
J
GFCI
GFCI
GFCI
GFCI
GFCI
140 138
STAIR B
131A
120 121
149 148
110 108
3 4 6
A
B
G
K
H
5 7
C
D
E
J
F
A B
MDP
E.8
G.2
B-6
B-6
A-1
A-1
A-2
A-2
A-3
A-3 A-3
A-3
A-4A-4
A-4
A-4
A-5
A-5
A-5
A-5
A-6
A-6A-6
A-6A-7
A-7 A-7
A-7
A-8
A-8
A-8
A-8
A-9
A-9A-9
A-9
A-10
A-10
A-10 A-10
A-11
A-11
A-11
A-11
A-12
A-12
A-12
A-12
A-13
A-13 A-13
A-13
A-15
A-15 A-15 B-3 A-15
A-15
A-16
A-16
A-16
A-17 A-17
A-17
A-18
A-16
A-16
A-19
A-19
A-14
A-14
A-14
A-14
A-14
A-14 A-14
A-20
A-20
A-21
A-21 A-21 A-21
A-22
A-22
A-22
A-22 A-22
A-22
A-23
A-23
A-23
A-23 A-23
A-23
A-24
A-24
A-24
A-24
A-25
A-25
A-25A-25
A-26 A-26
A-26 A-26
A-27
A-27
A-27 A-27
A-28
A-28B-28
A-28
A-29
A-29 B-29
A-29
A-30
A-30A-30
A-30
A-31
A-31
A-31
A-32
A-33
A-33 A-33
A-35
A-35
A-35A-34
A-34
A-34 A-36
A-36
A-36
A-37
A-37 A-37
A-39
A-39
A-39
A-39
A-38
A-38 A-38
A-38
A-40
A-40A-40
A-40
A-41A-41
A-41
A-41
B-2
B-1
B-1
A-42
C-1
C-2
C-4
A-12
A-12
B-3
52-TU-09
STAIR A
52-UH-02
52-UH-06
52-UH-05
52-UH-01
52-UH-03
52-IDU-1A
C-8,10
B-8
B-8
B-8
B-8
B-8
52-ACCH-2
52-ACCH-1
A-15
MDP
MDP
GFCI
GFCI GFCI
GFCI
GFCI
B-4
131B
C-5
A-36 A-34 A-35 A-33
C-3
GFCI
GFCI
WP GFCI
WP
B-5
B-5
C-6
GFCI
GFCI
TX-1
TO TRANSFORMER
TX-1
MDP
GFCI
GFCI
GFCI
GFCI
GFCI
WP
GFCI
WP
TR
TR
TR
TR
TRTR
TR
TR
TR
TR
TR
TR
TR
TR
GFCI
TR
TR
TR
WP
WP
WP
GFCI
TRTRTR
GFCI
GFCI
TR
A-37
B-12
52-TU-01
52-TU-02
52-TU-04
52-TU-06
52-TU-05
52-TU-23
52-TU-21
52-TU-20
52-TU-16
52-TU-18
52-TU-19
52-TU-15
52-TU-14
52-TU-17
52-TU-22 52-TU-12
52-TU-11
52-TU-10
GFCI
WP
52-TU-03
52-TU-13
52-TU-08
B-25
B-25
B-26
B-26
B-26
B-26
B-24
B-24
B-24
B-23
B-23
B-13
B-13
B-23
B-13
B-13
B-13 B-23
B-23
B-24
B-24
C G
D.3
GFCI
GFCI
A-11
EP401
F6
B-17
B-17
B-17
B-17
B-17 B-17
B-17 B-17
B-17
B-17
B-18
6.13.9
G.6
B-20
B-20
A-22
A-23
B-27 B-27
B-28
B-28
B-29
B-29
B-30
B-30
B-31
B-31
B-31
B-33
B-35
C-9,11,13
C-12,14,16
G-1,3,5 G-2,4,6
B-32,34,36
B-37,39,41
52-IDU-3 52-IDU-4
E-43,45
E-44,46
GFCI
SP-3
SP-2
B-38
C-15
B-30
##KEYNOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\k gr ie pe nt ro g\ D oc um en ts
\2 1.
_E
LE
C
_R
_k gr ie pe nt ro gJ G
H
.rv t
5/
/2
7:
:3
A
M
EP111
ELECTRICAL POWER PLAN - LEVEL
CONSTRUCT MENTAL HEALTH
OUTPATIENT BLDG 52 ADDITION
2101 ELM STREET, FARGO, ND 58102
437-316
05/26/2023 RA KEG
100% BID DOCUMENTS
VEG 21.05 DWG 169 of 188
CONTRACT DOCUMENTS SUBMISSION
FULLY SPRINKLERED
32'16'8'4'2'0' N or th
1/8" = 1'-0"
ELECTRICAL POWER PLAN - LEVEL 1F4
PANEL NAMES
PANEL ID
PANEL
NAME
ROOM
NUMBER
A 52A-N1A-1 128
B 52A-N1A-2 128
C 52A-N1B-1 109
D 52A-N2A-1 226A
E 52A-N2A-2 226A
F 52A-N2B-1 205
G 52A-N1B-2 109
H 52A-N2B-2 205
ROOM NUMBER KEY
NUMBER NAME
101 VESTIBULE
102 MECH
103 BARIATRIC RR
104 BARIATRIC OFFICE
105 OFFICE
106 OFFICE
107 CORR
108 OFFICE
109 COMM / EHRM
110 OFFICE
111 ELEV. EQUIP.
112 OFFICE
113 OFFICE
114 OFFICE
115 STAIR A
116 ELEV
117 VESTIBULE
118 RR
119 CORR
120 WAITING
121 WAITING
122 RECEPTION
123 ADMIN
124 STOR
126 FIRE PUMP
127 WORKRM / STOR
128 ELEC
129 GROUP THERAPY
130 STOR
131A ELEC
131B TELEHEALTH
132 STAIR B
133 OFFICE
134 OFFICE
135 CORR
136 OFFICE
137 OFFICE
138 OFFICE
139 OFFICE
140 OFFICE
141 OFFICE
142 OFFICE
143 OFFICE
144 OFFICE
145 OFFICE
146 OFFICE
147 GROUP THERAPY
148 STOR
149 HAC
150 OFFICE
151 LOUNGE
152 RR
153 CLOSET
154 ELEVATOR CAR 1
155 ELEVATOR CAR 2
156 TEMP VESTIBULE
1. PROVIDE POWER FEED TO SIDE ROLL ROLL-UP GATE. VERIFY EXACT
LOCATION AND REQUIREMENTS WITH MANUFACTURER PRIOR TO
ROUGH-IN.
2. PROVIDE POWER FEED TO SUMP PUMP CONTROLLER. VERIFY EXACT
LOCATION WITH EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN.
3. POWER FEED TO FIRE PUMP CONTROLLER. REFER TO ONE-LINE DIAGRAM,
SHEET E-602, FOR MORE INFORMATION.
4. POWER FEED TO JOCKEY PUMP CONTROLLER.
5. ROUTE ELECTRICAL FEEDER CONDUIT THROUGH SAME TRENCH AS
MECHANICAL PIPING.
6. PROVIDE POWER CONNECTION TO HEAT TRACE FOR OVERFLOW PIPING AT
WALL PENETRATION. VERIFY EXACT LOCATION AND REQUIREMENTS WITH
PLUMBING CONTRACTOR PRIOR TO ROUGH-IN.
7. PROVIDE POWER CONNECTION TO HEAT TRACE CONTROL PANEL. VERIFY
EXACT LOCATION AND REQUIREMENTS WITH PLUMBING CONTRACTOR
PRIOR TO ROUGH-IN.
8. PROVIDE RECESSED CLOCK TYPE RECEPTACLE AT 60" AFF FOR
TELEVISION. VERIFY EXACT LOCATION AND REQUIREMENTS WITH VA PRIOR
TO ROUGH-IN
9. PROVIDE 100VA, 120/24V CONTROL TRANSFORMER TO SERVE VAVS.
CIRCUIT TRANSFORMER AS INDICATED ON MECHANICAL CONNECTION
SCHEDULE. REFER TO SHEET E-601. COORDINATE WITH MECHANICAL
CONTRACTOR FOR LOCATION OF VAVS TO CREATE MOST EFFECTIVE
PATHWAYS.
10. PROVIDE RECESSED CLOCK TYPE RECEPTACLE AT 96" AFF FOR
TELEVISION. VERIFY EXACT LOCATION AND REQUIREMENTS WITH VA PRIOR
TO ROUGH-IN
11. PROVIDE POWER CONNECTION TO DOOR OPERATOR. VERIFY EXACT
LOCATION AND REQUIREMENTS WITH DOOR SUPPLIER AND VA PRIOR TO
ROUGH-IN.
12. PROVIDE POWER CONNECTION TO FIRE ALARM POWER SUPPLY. VERFIY
EXACT LOCATION AND REQUIREMENTS WITH EQUIPMENT
SUPPLIER/INSTALLER.
13. PROVIDE POWER CONNECTION TO IT RACK. MOUNT JUNCTION BOX AT +96"
AFF. VERFIY EXACT LOCATION WITH EQUIPMENT SUPPLIER PRIOR TO
ROUGH-IN.TYPICAL FOR 4.
14. PROVIDE GROUNDING FOR THE STATIC DISSIPATIVE FLOORING. VERIFY
EXACT REQUIREMENTS WITH MANUFACTURER PRIOR TO ROUGH-IN.
15. PROVIDE POWER FEED TO ACCESS CONTROL PANELS. VERIFY EXACT
LOCATION AND REQUIREMENTS WITH EQUIPMENT SUPPLIER.
16. COORDINATE WITH STRUCTURAL.
GFCI
C
J
CC
J
TU
TUTU
TU
TU
TU
TU
TU
TU
TU
TU
TU
TU
TU
TUTU
TU
TU
TU
TU
TU
TU
J
J
J
J
J
J
J
TU
TU
J
JJ
J
3 4 6
A
B
G
K
H
5 7
C
D
E
J
F
D
E
E.8
G.2
D-1
D-1
D-2
D-2 D-2
F-2
D-2
D-2
D-3
D-3
D-3 D-3
D-5
D-5
D-5
D-7
D-7
D-5
D-4
D-4
D-4
D-4D-6
D-6
D-6
D-6
D-8
D-8
D-8
D-8
D-7
D-9
D-9 D-9
D-9
D-11
D-11
D-11
D-13
D-13
D-13
D-10
D-10
D-10
D-12
D-12
D-12
D-14
D-14 D-14
D-2
D-13 D-11
D-15
D-15 D-15 D-15
D-17 D-17 D-17
D-17
D-17
D-16
D-16
D-16 D-16
D-16
D-18 D-18
D-18 D-18D-19
D-19 D-19
D-20 D-20
D-20 D-20
D-20
D-21
D-21
D-21
D-21
D-23 D-23
D-23 D-23
F-1 F-3 F-5
F-6 F-4
F-2
D-25 D-25
D-25
D-25
D-25
D-25
D-25
D-22 D-22
D-22
D-24 D-24
D-24
D-24
D-24
D-27
D-27
D-29
D-29
D-26
D-31
D-31
D-28
D-28 D-28
D-28
D-33 D-33
D-33 D-33
D-30
D-30
D-30
D-30
D-35
D-35
D-35
D-35
D-37
D-37 D-37
D-37
E-3 E-3
E-3
D-36
D-36
D-36 D-36
D-36
D-38
D-38
D-38 D-38
D-38E-1
E-1
E-1
E-1 E-1
D-41
D-41
D-41
D-41
D-41
E-4 E-4 E-4
E-2E-2
E-2
D-39
D-34
D-34 D-34
237 235
238 236
209210212
203218
244A
226A
D-7
52-IDU-2A
F-8,10
D-42 E-6
GFCI
GFCI
GFCI
GFCI
GFCI
D-40
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
D-2
D-30
E-41
D-41
D-41 D-41
TR TR
TR
TR
TR
TR
TR
TR
TR
TR
GFCI
TR
TR
TR
TR
TR
GFCI
E-3
E-4
E-2
D-14
D-12
D-10
GFCI
GFCI
GFCI
E-30
E-30
52-TU-25
52-TU-27
52-TU-26
52-TU-28
52-TU-29
52-TU-30
52-TU-31
52-TU-35
52-TU-36
52-TU-34
52-TU-24
52-TU-37
52-TU-41
52-TU-39
52-TU-38
52-TU-4052-TU-42
52-TU-43
52-TU-44
52-TU-45
52-TU-47
52-TU-33
52-TU-46
52-TU-32
E-20
E-17
E-22
E-22
E-22 E-29
E-29
E-29
E-20
E-20
E-20
E-20
E-17
E-17
E-17
E-15
E-15
E-15 E
E-17
E-15
E-15
F
D.3
H
6.13.9
G.6
D-21
C
E-41
E-42
D-32
F-9,11,13
H-1,3,5
F-12,14,16
H-2,4,6
F-15
E-15
E-17
D-49
D-50
D-50
D-49
GFCI
GFCI
##KEYNOTES