The project encompasses roof replacement in five buildings (19, 20, 50, 51, and 62) at the facility. Buildings 19 and 20 require asphalt shingle roof replacement with new wood sheathing, underlayment, flashing, fascia, and soffit materials. Buildings 50, 51, 62, and the connector bridge between them require TPO (thermoplastic polyolefin) membrane roofing systems with R-33 polyiso rigid insulation installed via low-rise foam adhesive over existing concrete decks. The project includes installation of new roof drains, gutters, downspouts, and base flashings at all buildings. Buildings 50 and 62 penthouse roofs will receive asphalt shingles. Alternate Deduct #1 allows deletion of rigid insulation installation in the attics of Buildings 19 and 20. Lightning protection systems per NFPA 780 Class 1 requirements are specified, including air terminals, down conductors, ground rods, and bonding connections. The contractor must coordinate crane operations with the Contracting Officer at least two weeks in advance, provide temporary fencing and staging areas, protect existing structures and landscaping, and address lead-based paint abatement per specification section 02 83 33.13. All roof work must meet 2018 IBC requirements with positive drainage to roof drains and no water ponding. Construction documents include general information, site plans, architectural repair schedules, demolition plans, roof plans, roof detail sections, and electrical lightning protection plans with material specifications and installation requirements.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CENTRAL ALABAMA VETERANS HEALTH CARE
SYSTEM - EAST CAMPUS
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083
PROJECT
LOCATION
AREIAL VIEW
CENTRAL ALABAMA VETERANS HEALTH CARE
SYSTEM - EAST CAMPUS
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
PROJECT SITE MAP PROJECT LOCATION MAP
PROJECT IMAGE
/2
/2
:0
:0
P
M C
U s e rs
\a c a b ra
\D o c u m e n ts \A
-0
V A
T u s k e g e e -R e p la c e
R o o f_
R a c a b ra
M U
S
.r v t
G-001
COVER
1 3RF
REPLACE ROOFS IN BLDGS.
19, 20, 50, 51, AND 62
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083 JUNE 19, 2024
CONSTRUCTION DOCUMENTS
619A4-24-10223-069
19, 20, 50, 51, AND 62
REPLACE ROOFS IN BLDGS. 19, 20, 50, 51, AND 62
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083
VA PROJECT #: 619A4-24-102
WVS
SHEET LIST
SHEET NUMBER SHEET NAME DWG OF DWG
GENERAL
G-001 COVER 1 3
G-002 GENERAL INFORMATION 2 3
GC101 SITE PLAN 3 3
ARCHITECTURAL
A-001 ARCHITECTURAL REPAIR ITEMS AND QUANTITIES 1 14
19.AD101 BUILDING 19 DEMOLITION ROOF PLAN 2 14
19.A-101 BUILDING 19 ROOF PLAN 3 14
20.AD101 BUILDING 20 DEMOLITION ROOF PLAN 4 14
20.A-101 BUILDING 20 ROOF PLAN 5 14
50.AD101 BUILDING 50 DEMOLITION ROOF PLAN 6 14
50.A-101 BUILDING 50 ROOF PLAN 7 14
51.AD101 BUILDING 51 DEMOLITION ROOF PLAN 8 14
51.A-101 BUILDING 51 ROOF PLAN 9 14
62.AD101 BUILDING 62 DEMOLITION ROOF PLAN 10 14
62.A-101 BUILDING 62 ROOF PLAN 11 14
A-501 ROOF DETAILS 12 14
A-502 ROOF DETAILS 13 14
A-503 ROOF DETAILS 14 14
ELECTRICAL
19.E-101 BUILDING 19 ROOF LIGHTNING PROTECTION PLAN 1 6
20.E-101 BUILDING 20 ROOF LIGHTNING PROTECTION PLAN 2 6
50.E-101 BUILDING 50 ROOF LIGHTNING PROTECTION PLAN 3 6
51.E-101 BUILDING 51 ROOF LIGHTNING PROTECTION PLAN 4 6
62.E-101 BUILDING 62 ROOF LIGHTNING PROTECTION PLAN 5 6
E-501 LIGHTNING PROTECTION DETAILS 6 6
W
AL
TE
R DAVID VAN SCOTER
REG. NO. 9953
DocuSign Envelope ID: 0463D4F7-B931-4C62-86FB-9A6716C851A3
6/21/2024
WALL SECTION
SYMBOL
COLUMN GRID
ELEVATION SYMBOL
REVISION NOTE
ENLARGED
DETAIL CALLOUT
BREAK LINE
ROOF SLOPE
DIRECTION SYMBOL
TYPICAL
GRAPHIC
SCALE
DETAIL #
PAGE #
VIEW NORTH ARROW
EXTERIOR ELEVATION
SYMBOL
A8.1
A8.1
A8.1
BUILDING SECTION
SYMBOL
DETAIL #
PAGE #
A8.1
A8.1
DETAIL SECTION
SYMBOL
DETAIL #
PAGE #
A8.1
XX.X
ELEVATION
0'-0"
NORTHNORTH
0 4 8 16
DEMOLITION KEYNOTE
TYPICAL KEYNOTE
#DETAIL #
PAGE #
1. REMOVE EXISTING CONSTRUCTION AS DESIGNATED AND CLEAR AREA OF DEBRIS PRIOR TO PROCEEDING WITH
NEW CONSTRUCTION.
2. EXISTING EQUIPMENT REMOVED SHALL BE PROPERLY DISPOSED OFF PROJECT GROUNDS. COORDINATE WITH
COR.
3. AT AREAS INDICATED TO BE PATCHED AND REPAIRED, FOR ADDITION AND RENOVATION PROJECTS: THE CONSTRUCTION AND ASSEMBLY OF THE PATCH OR REPAIR SHALL MATCH THE ASSEMBLY AND INTEGRITY OF THE ADJACENT EXISTING CONSTRUCTION, FOR FIRE RATING, MATERIALS, FINISH, THICKNESS, AND QUALITY.
4. COORDINATE WORKING HOURS ALLOWED FOR DEMOLITION AND WASTE REMOVAL WITH COR.
5. CONTRACTOR SHALL PROTECT AREA ADJACENT TO THE DEMOTION AND NEW CONSTRUCTION WORK TO PREVENT DAMAGES, (IF DAMAGED REPAIR, RE-PATCH, SAND SMOOTH AND REFINISH TO MATCH EXISTING.)
REPAIR OR REPLACE ITEMS DAMAGED DURING CONSTRUCTION ACTIVITIES AT NO ADDITIONAL COST.
6. THE INFORMATION CONTAINED IN DEMOLITION DOCUMENTS DEFINES GENERAL SCOPE ONLY AND DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY OF PROVIDING ALL DEMOLITION REQUIRED FOR THE
COMPLETION OF THE PROJECT.
7. REFER TO THE ELECTRICAL DRAWINGS FOR FURTHER INFORMATION REGARDING INSTALLATION OF LIGHTING
PROTECTION SYSTEM.
8. PRIOR TO SUBMITTING BID IDENTIFY ANY REQUIRED DEMOLITION BEYOND THE PROJECT SCOPE. NOTIFY AND
THE COR.
9. ALL DEMOLITION WORK SHALL BE PERFORMED WITH DUE CARE AND DILIGENCE IN ORDER TO PREVENT DAMAGE OR INTERRUPTION OF SERVICE OR CONCEALED UTILITIES INTENDED TO REMAIN IN SERVICE.
DISCOVERY OF UTILITIES OR CONDITIONS THAT ARE NOT IDENTIFIED AND AFFECT PROJECT CONSTRUCTION
ARE TO BE REPORTED TO COR.
10. VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK. NOTIFY COR AND ARCHITECT OF ANY CONFLICTS, PRIOR TO PROCEEDING WITH DEMOLITION WORK WITH LISTED QUANTITIES ON A-001.
11. NO DEMOLITION ITEMS ARE TO BE SALVAGED. ALL DEMOLITION DEBRIS TO BE DISPOSED OF OFF SITE.
1. ALL WORK SHALL BE COMPLETED IN ACCORDANCE WITH ALL PUBLISHED APPLICABLE LOCAL / STATE / FEDERAL / NATIONAL CODES, ORDINANCES AND REGULATIONS ALONG WITH ALL RELATED VA DIRECTIVES, DESIGN GUIDES AND
MANUALS, SPECIFICATIONS THAT ARE PROJECT SPECIFIC.
2. EACH CONTRACTOR SHALL HAVE LIABILITY, PROPERTY DAMAGE AND WORKMAN’S COMPENSATION INSURANCE AS REQUIRED BY THE VA IN THE BIDDING DOCUMENTATION. CONTACT THE VA/CO DURING THE BIDDING PHASE WITH ANY QUESTIONS, VERIFICATIONS, AND DOCUMENTATION NECESSARY CONCERNING ALL REQUIREMENTS FOR PROJECT
INSURANCE COVERAGE.
3. BEFORE SUBMITTING A BID, ALL CONTRACTORS WILL CAREFULLY EXAMINE THE DRAWINGS AND SPECIFICATIONS SO AS TO BE THOROUGHLY FAMILIAR WITH ALL THE CONTRACT REQUIREMENTS. EACH BIDDER SHOULD THEN VISIT THE SITE OF THE WORK TO BECOME ACQUAINTED WITH ALL VISIBLE FIELD CONDITIONS AFFECTING THE CONTRACT, SUCH AS OBSTACLES WHICH MAY BE ENCOUNTERED AND ALL OTHER CONDITIONS RELATIVE TO WHAT COULD
AFFECT/IMPACT THE WORK OR BE AFFECTED BY THE PERFORMANCE OF THE WORK.
4. IF AWARDED THE CONTRACT, THE CONTRACTORS SHALL NOT BE ALLOWED ANY EXTRA COMPENSATION BY REASON OF ANY UNFORESEEN DIFFICULTIES OR OBSTACLES WHICH THE BIDDER COULD HAVE REASONABLY ANTICIPATED PRIOR TO BIDDING. SHOULD ANY DISCREPANCIES, ERRORS, CONFLICT OR ITEMS NEEDING CLARIFICATION BE DISCOVERED IN THE PLANS AND/OR SPECIFICATIONS, THE CONTRACTOR SHALL NOTIFY THE VA/CO PRIOR TO SUBMITTING A BID AND THE VA/COR BEFORE STARTING ANY OF THE WORK.DRAWINGS ARE PREPARED USING DIMENSIONS AND PRODUCT DRAWINGS FOR SPECIFIC PRODUCTS. DETAILS FOR SPECIFIC PRODUCTS MAY CHANGE BEFORE THEY ARE ACTUALLY INCORPORATED INTO THE WORK, AND PRODUCTS BY OTHER MANUFACTURERS ARE ALSO ACCEPTABLE. THEREFORE, INSTALLATION DETAILS AND DIMENSIONS MAY DIFFER FROM THOSE SHOWN. CONTRACTOR SHALL VERIFY INSTALLATION REQUIREMENTS FOR ALL PRODUCTS TO BE
INCORPORATED IN THE WORK
5. THE DOCUMENTS DO NOT AND ARE NOT INTENDED TO INDICATE OR DESCRIBE IN DETAIL ALL THE NECESSARY WORK REQUIRED FOR FULL PERFORMANCE AND COMPLETION OF THE REQUIREMENTS OF THE CONTRACT. ON THE BASIS OF THE GENERAL SCOPE INDICATED IN THESE DOCUMENTS, THE TRADE CONTRACTORS SHALL FURNISH ALL ITEMS REQUIRED FOR THE PROPER EXECUTION AND COMPLETION OF THEIR WORK.
6. THE DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY; ITEMS SHOWN IN ANY ONE LOCATION IN THE DRAWINGS SHALL BE CONSIDERED TO BE REQUIREMENTS OF THE CONTRACT FOR CONSTRUCTION. IN THE EVENT OF AN INCONSISTENCY BETWEEN THE DRAWINGS AND SPECIFICATIONS, OR WITHIN EITHER DOCUMENT, THE CONTRACTOR SHALL SEEK CLARIFICATION OR INTERPRETATION FROM THE COR PRIOR TO BIDDING. WHERE INCONSISTENCIES ARE NOT CLARIFIED PRIOR TO BIDDING, AND WHERE THE ACTUAL SOLUTION OR INTENT CANNOT BE REASONABLY INFERRED, THE CONTRACTOR SHALL PROVIDE THE BETTER
QUALITY OR GREATER QUANTITY OF WORK.
7. THE CONTRACTOR SHALL NOTIFY THE COR IMMEDIATELY SHOULD DISCREPANCIES BE FOUND IN THE
DRAWINGS AND SPECIFICATIONS.
8. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING ALL FIELD CONDITIONS AND DIMENSIONS AS THEY RELATE TO THIS PROJECT. SHOULD DISCREPANCIES EXIST BETWEEN THE WORK INDICATED AND ACTUAL FIELD
CONDITIONS NOTIFY THE COR PRIOR TO BIDDING.
9. DO NOT SCALE THE DRAWINGS. DRAWING SCALES AS INDICATED ARE FOR REFERENCE ONLY AND ARE NOT INTENDED TO ACCURATELY DEPICT ACTUAL OR DESIGNATED CONDITIONS. WRITTEN DIMENSIONS SHALL
GOVERN.
10. CONTRACTORS SHALL REFERENCE ALL DRAWINGS IN ALL SECTIONS OF WORK FOR FULLY DEFINING THEIR SCOPE OF WORK RESPONSIBILITIES AND COORDINATE SAME WITH THE GENERAL/PRIME CONTRACTOR. SUBCONTRACTORS AND SUPPLIERS FOR EACH TRADE ARE ADVISED THAT INFORMATION PERTINENT TO THEIR SCOPE OF WORK ALSO OCCURS
IN OTHER SECTIONS OF THE DRAWINGS AND THE COMPLETE SET OF CONTRACT DOCUMENTS.
11. EACH CONTRACTOR SHALL MAINTAIN A COMPETENT OSHA-30 FOREMAN OR DIRECT REPRESENTATIVE ON THE JOB AT ALL TIMES. THE CONTRACTOR SHALL COOPERATE WITH AND COORDINATE WITH THE SUPERINTENDENT AND FOREMAN OF OTHER TRADES IN ORDER THAT THERE BE NO DELAYS IN THE EXECUTION AND COMPLETION OF THE
WORK.
12. IT SHALL BE THE RESPONSIBILITY OF EACH CONTRACTOR TO ADEQUATELY PROTECT EXISTING CONSTRUCTION AND FINISHES TO REMAIN IN PLACE DURING BOTH DEMOLITION AND CONSTRUCTION SEQUENCES OF THE WORK. ANY
DAMAGE TO SUCH AREAS SHALL BE RESTORED.
13. THE CONTRACTOR IS RESPONSIBLE FOR THE PATCH, REPAIR, REFINISHING AND/OR REPLACEMENT OF ALL CONSTRUCTION, MATERIALS, ASSEMBLIES, EQUIPMENT, SIGNAGE AND FINISHES DAMAGED BY THE PROJECT DEMOLITION, TEMPORARY CONSTRUCTION, NEW CONSTRUCTION OR THE MOVEMENT OF PERSONNEL, TOOLS, EQUIPMENT, MATERIALS, ETC. BOTH INSIDE AND OUTSIDE OF THE DESIGNATED AREAS OF WORK.
14. THE CONTRACTOR IS RESPONSIBLE TO PROVIDE THE REMOVAL OF ALL CONSTRUCTION DEMOLITION DEBRIS, SOIL AND
MATERIALS FROM THE PROJECT SITE.
15. PROVIDE SEALANT AT ALL INTERSECTIONS BETWEEN DIFFERENT MATERIALS.
16. ALL WOOD IN CONTACT WITH CONCRETE SHALL BE PRESSURE TREATED.
AFF ABOVE FINISHED FLOOR
ACP/APC ACOUSTIC CEILING PANEL/
ACOUSTIC PANEL CEILING
ACT ACOUSTIC(AL) TILE
ADJ ADJUSTABLE
ADT'L ADDITIONAL
AGG AGGREGATE
ALT ALTERNATE
AL ALUMINUM
APPROX APPROXIMATE(LY)
ASPH ASPHALT
AUTO AUTOMATIC
B/O BOTTOM OF
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BOT BOTTOM
BRG BEARING
CENTERLINE
C/C CENTER TO CENTER
CJ CONTROL JOINT
CLL CONTRACT LIMIT LINE
CEM CEMENT(ITIOUS)
CMU CONCRETE MASONRY UNIT
CLG CEILING
CLR CLEAR
COL COLUMN
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
CPT CARPET
CT CERAMIC TILE
CTR CENTER(ED)
DF DRINKING FOUNTAIN
DS DOWNSPOUT
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION
DET/DTL DETAIL
DIA DIAMETER
DIM DIMENSION
DN DOWN
DWG(S) DRAWING(S)
E EAST
EC ELECTRICAL CONTRACTOR
EHO ELECTRICAL HOLD OPEN
EJ EXPANSION JOINT
EW EACH WAY
EA EACH
EIFS EXTERIOR INSULATION
FINISH SYSTEM
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EMER EMERGENCY
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
EXT EXTERIOR
EWC ELECTRIC WATER COOLER
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FFE FINISH FLOOR ELEVATION
FV FIELD VERIFY
FEC FIRE EXTINGUISHER CABINET
FDN FOUNDATION
FIN FINISH
FLSHG FLASHING
FLR FLOOR
FRMG FRAMING
FRT FIRE RETARDANT TREATED
FT FOOT/FEET
FTG FOOTING
GC GENERAL CONTRACTOR
GA GAUGE
GALV GALVANIZED
GEN GENERAL
GYP GYPSUM
HM HOLLOW METAL
HDWR HARDWARE
HOL HOLLOW
HOR HORIZONTAL
HT HEIGHT
HVAC HEATING/VENTILATION/AIR
CONDITIONING
ID INSIDE DIAMETER
IN INCH
INCL INCLUDING
INSUL INSULATION
INT INTERIOR
JAN JANITOR
JT JOINT
LAV LAVATORY
LB(S) POUND(S)
L/S LANDSCAPE
LT LIGHT
MO MASONRY OPENING
MAS MASONRY
MAT'L MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
MTL METAL
N NORTH
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NOM NOMINAL
OC ON CENTER
OD OUTSIDE DIAMETER
O TO O OUT TO OUT
OPNG OPENING
OPP OPPOSITE
OVHD OVERHEAD
PEB PRE-ENGINEERED BUILDING
PJF PREFORMED JOINT FILLER
PERIM PERIMETER
PL PLATE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PLYWD PLYWOOD
PNT PAINT
PR PAIR
PT PRESSURE TREATED
PTD PAINTED
PWR POWER
RB RUBBER BASE
RD ROOF DRAIN
RF FIRE RETARDANT TREATED
RO ROUGH OPENING
RAD RADIUS
REC RECESSED
REINF REINFORCED
REQ'D REQUIRED
REV REVISED (REVISION)
RM ROOM
S SOUTH
SB SPLASH BLOCK
SF SQUARE FEET
SS STAINLESS STEEL
SIM SIMILAR
SPEC SPECIFICATIONS
SQ SQUARE
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
T&G TONGUE AND GROOVE
T/O TOP OF
TELE TELEPHONE
TRTD TREATED
TS TUBE STEEL
TYP TYPICAL
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
VERT VERTICAL
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WWF WELDED WIRE FABRIC
WD WOOD
WH WATER HEATER
WT WEIGHT
CL
BASE BID:
ALL WORK AS DESCRIBED BY CONTRACT DOCUMENTS.
ALTERNATE DEDUCT #1:
DELETE ALL WORK AND MATERIAL ASSOCIATED WITH INSTALLATION OF RIGID INSULATION IN ATTIC OF BUILDINGS 19 & 20. INCLUDING BUT NOT LIMITED TO ALL DEMOLITION
WORK FOR PREPARATION OF INSTALLATION.
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:0
:0
P
M C
U s e rs
\a c a b ra
\D o c u m e n ts \A
-0
V A
T u s k e g e e -R e p la c e
R o o f_
R a c a b ra
M U
S
.r v t
G-002
GENERAL INFORMATION
2 3RF
REPLACE ROOFS IN BLDGS.
19, 20, 50, 51, AND 62
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083 JUNE 19, 2024
CONSTRUCTION DOCUMENTS
619A4-24-10223-069
WVS
ARCHITECTURAL SYMBOL LEGEND
DEMOLITION NOTES
GENERAL NOTES
G_ABBREVIATIONS
19, 20, 50, 51, AND 62
DEDUCTIVE ALTERNATIVES
W
AL
2 3
1 2 3
2 3
HOSPITAL R
D
H O S
PITA
L R D
W E
S T
G A
T E
R D
HOSPITAL R
D
H O
S P
IT
A L R
D
HOSPITAL RD
ROBERT CIR.
4A
3A
49 8
0 40 80 160
BUILDINGS IN SCOPE OF
WORK
SCOPE OF WORK
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:0
:0
P
M C
U s e rs
\a c a b ra
\D o c u m e n ts \A
-0
V A
T u s k e g e e -R e p la c e
R o o f_
R a c a b ra
M U
S
.r v t
GC101
SITE PLAN
3 3RF
REPLACE ROOFS IN BLDGS.
19, 20, 50, 51, AND 62
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083 JUNE 19, 2024
CONSTRUCTION DOCUMENTS
619A4-24-10223-069
WVS
A. CONTRACTOR TO COORDINATE LOCATION AND
SCHEDULING OF CRANE TO LIFT SUPPLIES ONTO
ROOF WITH COR PRIOR TO CRANE OPERATIONS
STARTING. MINIMUM TWO WEEKS PRIOR TO
CRANE ARRIVAL. CRANE LIFT PLAN SUBMITAL
REQUIRED.
B. CONTRACTOR RESPONSIBLE TO PROTECT ALL
PAVING, CONCRETE, & LANDSCAPE IN AREAS OF
CRANE LOCATION INCLUDING CRANE TRANSIT
ON SITE TO AND FROM LIFT LOCATIONS.
C. CONTRACTOR SHALL REPAIR ALL DAMAGE
FROM CONSTRUCTION ACTIVITIES. INCLUDING,
BUT NOT LIMITED TO GRASS AREAS, PAVED
AREAS, AND LANDSCAPING. REPAIRED AREAS
TO BE BACK TO ORIGINAL CONDITION OR
BETTER.
D. CONTRACTOR SHALL VERIFY DIMENSIONS IN
FIELD PRIOR TO BEGINNING CONSTRUCTION.
E. PROVIDE POSITIVE DRAINAGE TO ALL ROOF
DRAINS.
F. ROOFING COMPONENTS MAY VARY DEPENDING
ON ROOFING MANUFACTURER. CONTRACTOR
SHALL INSTALL A COMPLETE CODE COMPLIANT
AND WARRANTIED ROOFING SYSTEM BASED ON
THE ROOFING MANUFACTURERS WRITTEN
INSTRUCTIONS AND INSTALLATION GUIDELINES.
G. ROOFING INSULATION R-VALUE MAY VARY
DEPENDING ON INSULATION MANUFACTURER.
ROOFING CONTRACTOR TO CONSULT
INSULATION MANUFACTURERS WRITTEN
DOCUMENTATION AND PROVIDE A ROOF
INSULATION THICKNESS TO MEET OR EXCEED
2018 IBC REQUIREMENTS.
H. NEW ROOF AREAS MUST HAVE POSITIVE
DRAINAGE. NEW ROOFS TO HAVE NO PONDING
OF WATER.
I. THE CONTRACTOR SHALL ENSURE THAT UPON
COMPLETION OF ROOF WORK, ALL ROOF
DRAINS ARE CLEAN AND CLEAR OF DEBRIS TO
PROVIDE AND UNOBSTRUCTED, FREE FLOW OF
WATER.
J. DUMPSTER AND TRASH CHUTE LOCATIONS ARE
TO BE COORDINATED WITH THE COR PRIOR TO
LOCATION ON SITE. SEE THIS SHEET FOR
SUGGESTED LOCATIONS OF DUMPSTER, CHUTE,
AND STAGING AREAS.
K. BUILDING ACCESS FOR WORKERS:
CONTRACTOR'S DISCRETION, POTENTIAL
ACCESS METHODS: THRU BUILDING INTERIOR,
EXISTING FIRE ESCAPES, SCAFFOLDING BUILT
STAIRS, OR LIFTS.
1 POTENTIAL LOCATION OF CRANE FOR LIFTING
SUPPLIES TO THE ROOF OR REMOVING DEBRIS
FORM FROM ROOF. COORDINATE WITH COR.
2 POTENTIAL LOCATION OF DUMPSTER,
COORDINATE WITH COR PRIOR TO START OF
CONSTRUCTION. ALL DUMPSTERS TO HAVE
FABRIC GUARD TO LIMIT DUST.
3 STAGING AREA. CONTRACTOR TO PROVIDE
SECURE AREA WITH 6' HIGH CONSTRUCTION
CHAIN LINK FENCE (PANEL TYPE WITH SAND
BAGS). WITH PRIVACY FABRIC. PROVIDE ONE
DOUBLE SWINGING 10'-0" GATE ACCESS.
COORDINATE EXACT EXTENT AND LAYOUT WITH
COR.
4 EXISTING BUILDING TO BE RE-ROOFED.
5 ENCLOSED CONNECTOR BRIDGE BETWEEN
BUILDINGS 50, 51 + 62 .
6 PROVIDE (1) DOUBLE SWINGING 10'-0" GATE. 6'
HIGH CHAIN LINK WITH PRIVACY FABRIC. POSTS
TO BE INSTALLED IN AUGER DUG HOLES AS PER
GATE SUPPLIER INSTALLATION INSTRUCTIONS.
WIDTH OF EXISTING ROAD 30'. FROM NORTH SIDE
OF ROAD TO EXISTING FENCE 20'.
7 EXISTING CAMPUS PERIMETER SECURITY FENCE.
8 EXISTING GUARDHOUSE.
9 POTENTIAL DEBRIS CHUTE LOCATION
CONTRACTOR TO VERIFY LOCATIONS WITH THE
C.O.R. PRIOR TO START OF CONSTRUCTION.
10 PROVIDE TEMPORARY FENCING 6' HIGH
CONSTRUCTION CHAIN LINK FENCE WITH PRIVACY
FABRIC - APPROX 70 LF. (PANEL TYPE WITH SAND
BAGS).
Scale: 1" = 80'-0"
SITE PLAN
19, 20, 50, 51, AND 62
NORTH
W
AL
ROOF REPAIR ITEMS AND QUANTITIES
BUILDING 19
REPAIR / REPLACEMENT APROX. QTY UNIT NOTES
BUILDING 20
REPAIR / REPLACEMENT APROX. QTY UNIT NOTES
REMOVE ASPHALT SHINGLES ROOF
REMOVE BUR SYSTEM FROM ENTRANCE ROOF
SQUARE
FOOT
REMOVE AND REPLACE ROOF HATCH
REPLACE VALLEY FLASHING
REPLACE FLASHING AT CHIMNEYS, FANS, VTR,
ETC.
REPLACE ALL DRIP EDGE
REPLACE ALL WOOD FASCIA, TRIM, SOFFIT, ETC.
7,200 1, 2, 3
SQUARE
FOOT
EACH
LINEAL
FOOT
LINEAL
FOOT
LINEAL
FOOT
LINEAL
FOOT
5, 6
REMOVE AND REPLACE ASPHALT SHINGLE ROOF SQUARE
FOOT
6,400 1, 2
INSTALL NEW ROOF HATCH AT EXISTING HATCH
OPENING
EACH1 5, 6
REPLACE VALLEY FLASHING LINEAL
FOOT
REPLACE FLASHING AT FANS, VTR, ETC. 20
REPLACE ALL DRIP EDGE 460
REPLACE ALL WOOD FASCIA, TRIM, SOFFIT, ETC. 460
REPAIR OR REPLACE INTEGRAL GUTTER 40
LINEAL
FOOT
LINEAL
FOOT
LINEAL
FOOT
LINEAL
FOOT
9, UPPER AND LOWER ROOFS
ROOF REPAIR ITEMS AND QUANTITIES
REPLACE WOOD ROOF SHEATHING 800 SQUARE
FOOT
REPLACE WOOD ROOF SHEATHING 800
SQUARE
FOOT
NEW BUILT IN GUTTER 460
LINEAL
FOOT
NEW BUILT IN GUTTER 460
LINEAL
FOOT
UPPER AND LOWER ROOFS
UPPER AND LOWER ROOFS
UPPER AND LOWER ROOFS
ROOF REPAIR ITEM AND QUANTITIES
BUILDING 50
REPAIR / REPLACEMENT APROX. QTY UNIT NOTES
REMOVE EXISTING BUR SYSTEM
REMOVE ASPHALT SHIGLES FROM PITCHED ROOF
REMOVE EXHAUST FANS
INSTALL NEW RIGID INSULATION, SLOPE TO ROOF
DRAINS
INSTALL NEW TPO ROOF SYSTEM
INSTALL NEW ASPHALT SHINGLE ROOF ON
MECHANICAL PENTHOUSE ROOF
SQUARE
FOOT
SQUARE
FOOT
SQUARE
FOOT
SQUARE
FOOT
SQUARE
FOOT
EACH
REMOVE AND REPLACE ALL FLASHING
PATCH CONCRETE ROOF SLAB WHERE
EQUIPMENT IS REMOVED
SQUARE
FOOT
LINEAL
FOOT
17,300
2,500
17,300
17,300
2,500
1, 2
2,500
REPLACE WOOD SHEATHING MECHANICAL
PENTHOUSE ROOF
SQUARE
FOOT
ROOF REPAIR ITEMS AND QUANTITIES
BUILDING 51
REPAIR / REPLACEMENT APROX. QTY UNIT NOTES
REMOVE EXISTING BUR SYSTEM
REMOVE EXHAUST FANS
INSTALL NEW RIGID INSULATION, SLOPE TO ROOF
DRAINS
INSTALL NEW TPO ROOF SYSTEM
SQUARE
FOOT
SQUARE
FOOT
SQUARE
FOOT
EACH
REMOVE AND REPLACE ALL FLASHING
PATCH CONCRETE ROOF SLAB WHERE
EQUIPMENT IS REMOVED
SQUARE
FOOT
LINEAL
FOOT
17,000
12,710
17,000
LINEAL
FOOT
SQUARE
FOOT
STONE COPING RESET
BRICK WALL REBUILDING
ROOF REPAIR ITEMS AND QUANTITIES
BUILDING 62
REPAIR / REPLACEMENT APROX. QTY UNIT NOTES
BUILDINGS 50, 51, AND 62 CONNECTOR
REPAIR / REPLACEMENT APROX. QTY UNIT NOTES
ROOF REPAIR ITEMS AND QUANTITIES
REMOVE EXISTING BUR SYSTEM
INSTALL NEW RIGID INSULATION, SLOP TO ROOF
DRAINS
INSTALL NEW TPO ROOF SYSTEM
SQUARE
FOOT
SQUARE
FOOT
SQUARE
FOOT
PATCH CONCRETE ROOF SLAB WHERE
EQUIPMENT IS REMOVED
SQUARE
FOOT
4,000
REMOVE EXISTING BUR SYSTEM
REMOVE ASPHALT SHIGLES FROM PITCHED ROOF
REMOVE EXHAUST FANS
INSTALL NEW RIGID INSULATION, SLOPE TO ROOF
DRAINS
INSTALL NEW TPO ROOF SYSTEM
INSTALL NEW ASPHALT SHINGLE ROOF ON
MECHANICAL PENTHOUSE ROOF
SQUARE
FOOT
SQUARE
FOOT
SQUARE
FOOT
SQUARE
FOOT
SQUARE
FOOT
EACH
REMOVE AND REPLACE ALL FLASHING
LINEAL
FOOT
17,300
2,500
17,300
17,300
2,500
1, 2
PATCH CONCRETE ROOF SLAB WHERE
EQUIPMENT IS REMOVED
REPLACE WOOD SHEATHING MECHANICAL
PENTHOUSE ROOF
2,500
SQUARE
FOOT 11
4,000
4,000
SQUARE
FOOT
INSTALL NEW ROOF DRAINS EACH6
A. ASSUME ALL EXTERIOR PAINTED SURFACES CONTAIN
LEAD BASED PAINT. REMOVE PER SPECIFICATION
SECTION 02 83 33.13 LEAD BASED PAINT REMOVAL.
B. ALL NEW MATERIALS TO BE INSTALLED PER
CONTRACT DOCUMENTS, DRAWINGS AND
SPECIFICATIONS.
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:0
:0
P
M C
U s e rs
\a c a b ra
\D o c u m e n ts \A
-0
V A
T u s k e g e e -R e p la c e
R o o f_
R a c a b ra
M U
S
.r v t
A-001
ARCHITECTURAL REPAIR ITEMS AND
QUANTITIES
1 14RF
REPLACE ROOFS IN BLDGS.
19, 20, 50, 51, AND 62
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083 JUNE 19, 2024
CONSTRUCTION DOCUMENTS
619A4-24-10223-069
WVS
19, 20, 50, 51, AND 62
NOTES:
1. REMOVE ASPHALT SHINGLES AND ROOF
UNDERLAYMENT TO EXISTING SUBSTRATE.
2. REPLACE DAMAGED OR DETERIORATED WOOD
SUBSTRATE MATERIALS.
3. REPLACE INTEGRAL GUTTER SYSTEM AT ROOF EDGE.
INCLUDE ALL WOOD FRAMING REQUIRED TO
RESTORE OPERABLE GUTTER SYSTEM.
4. REMOVE ENTIRE ROOF SYSTEM, INCLUDING
EXISTING SUBSTRATE.
5. REPLACE WOOD FRAMING AT EXISTING ROOF HATCH.
6. INSTALL NEW ROOF HATCH.
7. REMOVE EXISTING BUILT UP ROOF SYSTEM,
INSULATION, UNDERLAYMENT, ETC. TO SUBSTRATE.
8. REMOVE EXISTING EXHAUST FANS AND EQUIPMENT.
9. REPLACE ALL FASCIA, TRIM, SOFFIT, ETC. AROUND
ENTIRE EDGE OF PITCHED ROOF.
10. REMOVE SBS SINGLE PLY ROOF SYSTEM, INSULATION
AND UNDERLAYMENT TO EXISTING SUBSTRATE.
11. PATCH THE EXISTING OPENINGS IN ROOF SLAB
WHERE EXHAUST FANS/EQUIPMENT REMOVED.
W
AL
7 6
1 1
6 7
6 7
3 3
SLOPE: 5 1/2:12
62'-3" 28'-0"
SLOPE: 5 1/2:12
A-501
A-501
19.A 19.B 19.C 19.D 19.E 19.F 19.G 19.H 19.I 19.J
11'-3" 11'-3" 11'-3" 11'-3" 11'-0" 12'-8" 12'-8" 12'-8" 11'-0"
19.K 19.L 19.M 19.N
11'-3" 11'-3" 11'-3" 11'-3"
19.1
19.2
19.3
19.4
19.5
56'-3" 40'-0" 56'-3"
62'-3"
S L O
P E
/2 :1
S L O
P E
/2 :1
80 S.F.
75 S.F.
150 S.F.
20'-0" 20'-0"
Engineers Architects
# DEMOLITION KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:0
:1
P
M C
U s e rs
\a c a b ra
\D o c u m e n ts \A
-0
V A
T u s k e g e e -R e p la c e
R o o f_
R a c a b ra
M U
S
.r v t
19.AD101
BUILDING 19 DEMOLITION ROOF PLAN
2 14RF
REPLACE ROOFS IN BLDGS.
19, 20, 50, 51, AND 62
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083 JUNE 19, 2024
CONSTRUCTION DOCUMENTS
619A4-24-10223-069
WVS
Scale: 1/8" = 1'-0"
BUILDING 19 DEMOLITION ROOF PLAN
1 REMOVE EXISTING ASPHALT SHINGLE ROOF
AND UNDERLAYMENT TO EXISTING
SUBSTRATE.
2 REMOVE EXISTING EXHAUST FAN IN ITS
ENTIRETY. FILL IN HOLE WITH 3/4" FT
PLYWOOD.
3 EXISTING VENT TO BE REMOVED.
4 REMOVE EXISTING ROTTED / DAMAGED WOOD
SUBSTRATE PREP FOR NEW MATERIAL
INSTALLATION. SEE A-001 FOR QUANTITIES.
5 EXISTING METAL CANOPY TO REMAIN. NO
WORK ON THIS ROOF.
6 REPLACE DAMAGED AND DETERIORATED
WOOD AROUND INTERIOR GUTTER. REPAIR
GUTTER SECTIONS TO MAKE A CONTINUOUS,
FULLY FUNCTIONING, INTERIOR GUTTER
SYSTEM.
7 REMOVE AND REPLACE WOOD FASCIA, WOOD
TRIM AND DECORATIVE WOOD ITEMS.
8 REMOVE EXISTING ROOF HATCH.
9 REMOVE EXISTING VALLEY FLASHING.
10 EXISTING BRICK MASONRY CHIMNEY TO
REMAIN. RE-POINT ALL EXPOSED BRICK.
11 REMOVE CAPPED EQUIPMENT CURB AND INFILL
ROOF OPENING WITH 3/4" FT PLYWOOD.
12 REMOVE FLAT BUILT-UP ROOF INCLUDING
SUBSTRATE (ASSUMED WOOD PLANKING
DECK).
13 REMOVE EXIST. SUBSTRATE IN THIS AREA.
PRIOR TO FILLING IN WITH NEW SHEATHING,
USE OPEN AREA FOR MATERIAL MOVEMENT
FOR ATTIC RIGID INSULATION.
14 EXISTING STEEL FIRE ESCAPE TO REMAIN.
15 REMOVE ALL VEGETATION FROM WALL IN THIS
AREA. AFTER REMOVAL, SPRAY WALL WITH
ENVIRONMENTALLY SAFE WEED KILL TO
PREVENT GROW BACK.
16 REMOVE EXISTING SUBSTRATE THIS AREA.
17 REMOVE EXISTING BUILT IN COPPER GUTTER
AND DOWNSPOUTS.
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
NORTH
0 4 8 16
A. CONTRACTOR TO ENSURE PROPER SAFETY
BARRIERS AND ENCLOSURES ARE PROVIDED AT
ALL ENTRY/EXIT POINTS FROM BUILDING WHERE
WORK IS BEING PERFORMED ABOVE.
B. ALL PERSONNEL TO WEAR PROPER SAFETY
DEVICES/FALL PROTECTION.
C. CONTRACTOR SHALL PROVIDE PROTECTION AS
PER OSHA REQUIREMENTS.
D. CONTRACTOR TO ASSUME ALL DEMOLITION OF
PAINT OR PAINTED WOOD OR METAL CONTAINS
LBP AND NEEDS TO BE ABATED PER SPEC
SECTION 02 83 33.13
E. ALL DIMENSIONS ON THE DRAWINGS HAVE BEEN
DETERMINED BASED ON MINIMAL AS-BUILT
INFORMATION AVAILABLE. CONTRACTOR TO
VERIFY ALL DIMENSIONS AND QUANTITIES PRIOR
TO SUBMITTING BID.
F. CONTRACTOR SHALL PROVIDE TEMPORARY
SHORING OF EXISTING ROOF STRUCTURE AS
NECESSARY FOR CONSTRUCTION LIVE LOADS.
G. APPROXIMATE HEIGHT TO EAVE FROM GRADE
AVERAGES APPROX. 30'-0". APPROXIMATE
HEIGHT TO LOW FRONT ROOF FROM GRADE
12'-0".
H. ATTIC ACCESS FOR WORKERS ACCEPTABLE
THROUGH BUILDING INTERIOR. POWER IS NOT
AVAILABLE AT THIS BUILDING SITE. ANY
ELECTRICAL POWER NEEDED SHALL BE
PROVIDED BY THE CONTRACTOR.
W
AL
7 8 7 8
7 87 8
7 8
3 4
7 8
S L O
P E
/2 :1
SLOPE: 5 1/2:12
SLOPE: 5 1/2:12
8'-11"
56'-3" 40'-0" 56'-3"
152'-7"
62'-3" 28'-0" 62'-3"
A-501
A-501
A-502
19.A 19.B 19.C 19.D 19.E 19.F 19.G 19.H 19.I 19.J 19.K 19.L 19.M 19.N
19.1
19.2
19.3
19.4
19.5
11'-3" 11'-3" 11'-3" 11'-3" 11'-0" 12'-8" 12'-8" 12'-8" 11'-0" 11'-3" 11'-3" 11'-3" 11'-3"
13 13 13 13
26'-9" 26'-9" 26'-9" 26'-9"
152'-7"
19.A-101
19.A-101
TYP.
TYP.
S L O
P E
/2 :1
S L O
P E
/2 :1
80 S.F.
75 S.F.
150 S.F.
B19 ROOF LEVEL
36' - 0"
ATTIC
TYP.
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:0
:1
P
M C
U s e rs
\a c a b ra
\D o c u m e n ts \A
-0
V A
T u s k e g e e -R e p la c e
R o o f_
R a c a b ra
M U
S
.r v t
19.A-101
BUILDING 19 ROOF PLAN
3 14RF
REPLACE ROOFS IN BLDGS.
19, 20, 50, 51, AND 62
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083 JUNE 19, 2024
CONSTRUCTION DOCUMENTS
619A4-24-10223-069
WVS
1 INSTALL NEW ASPHALT SHINGLE ROOF SYSTEM
OVER SELF ADHERED SHEET MEMBRANE ROOF
UNDERLAYMENT. MEMBRANE THICKNESS 40 MIL.
2 REPLACE EXISTING ROOF HATCH, MATCH EXISTING
HATCH SIZES. BASIS OF DESIGN: BILCO TYPE S
ROOF HATCH W/ LADDER OR EQUAL. INSTALL
FLASHING UP TO INTEGRAL CAP FLASHING ON
HATCH FRAME. REPLACE DETERIORATED WOOD
FRAMING FOR HATCH, ALL WOOD FRAMING AND
SHEATHING AROUND HATCH TO BE REPLACED.
3 INSTALL NEW 3/4" WOOD SHEATHING ENTIRE LOW
ROOF (APPROX. 200 S.F.). SLOPE SHEATHING TO
BUILT IN GUTTER VIA SHIMS.
4 INSTALL NEW 60 MIL FLEECE BACK TPO ROOFING ON
NEW SHEATHING.
5 INSTALL NEW VALLEY FLASHING.
6 INSTALL NEW BASE FLASHING AT WALL PER ROOF
SYSTEM MANUFACTURER'S STANDARD DETAILS.
7 EXISTING INTEGRAL GUTTER WITH NEW COPPER
LINING, ENSURE PROPER CONNECTIONS TO ALL
DOWNSPOUTS AND ALL GUTTER SECTIONS.
8 REPLACE FASCIA, EAVES, SOFFITS AND OTHER
ROTTED OR DETERIORATED WOOD MATERIAL
BEFORE INSTALLING NEW FLASHING OR ROOF
MATERIAL. SEE SHEET A-001 FOR QUANTITIES.
9 INSTALL NEW 3/4" WOOD SHEATHING FLUSH WITH
EXISTING (APPROX. 80 S.F.).
10 INSTALL NEW 3/4" WOOD SHEATHING FLUSH WITH
EXISTING (APPROX. 150 S.F.).
11 INSTALL NEW 3/4" WOOD SHEATHING FLUSH WITH
EXISTING (APPROX. 75 S.F.).
12 INSTALL NEW 16 OZ COPPER BUILT IN GUTTER
MATCH EXISTING PROFILE. ALL WELDED SEAMS.
NEW 18 OZ 3" ROUND DOWNSPOUTS.
13 INSTALL NEW FALL PROTECTION STANCHION. BOD:
FRONTLINE COMMERCIAL ROOF ANCHOR - R012 OR
EQUAL, TYPICAL.
14 NEW 16 OZ COPPER CRICKET W/ SELF ADHERED
UNDERLAYMENT. AS PER SMACNA.
15 SHINGLE OVER RIDGE VENT. SUBMITTAL REQUIRED.
16 12 X 12 ROOF VENT. BASIS OF DESIGN: GAF, MASTER
FLOW ROOF LOUVER SSB960 METAL, SLANT BACK.
COLOR TO MATCH SHINGLES, OR EQUAL.
17 INSTALL (3) LAYERS OF 2" XPS INSULATION ON TOP
OF EXISTING ATTIC SLAB. DEMOLISH ALL CONDUIT
AND PIPING TO ALLOW INSULATION TO LAY ON ATTIC
SLAB. (35 PENETRATIONS) SEAL ALL OPENINGS WITH
FIRE CAULKING. METHOD OF ATTACHMENT -
ADHESIVE. BASIS OF DESIGN: OWENS CORNING,
FOAMULAR 250, 2" THICK, 4'X8' SHEETS, OR EQUAL
ENTIRE ATTIC AREA.
Scale: 1/8" = 1'-0"
BUILDING 19 ROOF PLAN
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
NORTH
0 4 8 16
A. CONTRACTOR TO ENSURE PROPER SAFETY
BARRIERS AND ENCLOSURES ARE PROVIDED AT
ALL ENTRY/EXIT POINTS FROM BUILDING WHERE
WORK IS BEING PERFORMED ABOVE.
B. ALL PERSONNEL TO WEAR PROPER SAFETY
DEVICES/FALL PROTECTION.
C. CONTRACTOR SHALL PROVIDE FALL PROTECTION
PER OSHA REQUIREMENTS.
D. ALL DIMENSIONS ON THE DRAWINGS HAVE BEEN
DETERMINED BASED ON MINIMAL AS-BUILT
INFORMATION AVAILABLE. CONTRACTOR TO
VERIFY ALL DIMENSIONS AND QUANTITIES PRIOR
TO SUBMITTING BID.
E. CONTRACTOR SHALL PROVIDE TEMPORARY
SHORING OF EXISTING ROOF STRUCTURE AS
NECCESSARY FOR CONTRUCTION LIVE LOADS.
F. APPROXIMATE HEIGHT TO EAVE FROM GRADE
AVERAGES APPROX. 30'-0".
G. ATTIC ACCESS FOR WORKERS PERMITTED
THROUGH BUILDING INTERIOR.
H. ANY WOOD RAFTER DISCOVERED TO BE NON
STRUCTURALLY SOUND SHALL BE REPAIRED AS
PER DETAIL 9/A-502.
I. POWER IS NOT AVAILABLE AT THIS BUILDING SITE.
ANY ELECTRICAL POWER NEEDED SHALL BE
PROVIDED BY THE CONTRACTOR.
Scale: 1/4" = 1'-0"
BUILDING 19 SCHEMATIC SECTION
W
AL
20.A
20.1
1 1
2 2 2
6 7
10 67
42'-8" 38'-0" 45'-4"
28'-0"
S L O
P E
/2 :1
SLOPE: 5 1/2:12
SLOPE: 5 1/2:12
20.B 20.C 20.D 20.E 20.F 20.G 20.H 20.I 20.J
126'-0"
20.2
20.3
20.4
20.5
14'-0" 14'-0" 14'-0" 14'-0" 14'-0" 14'-0" 14'-0" 14'-0" 14'-0"
6 6
A-501
A-501
S L O
P E
/2 :1
100 S.F.
260 S.F.
100 S.F.
140 S.F.
18 19
Engineers Architects
# DEMOLITION KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:0
:1
P
M C
U s e rs
\a c a b ra
\D o c u m e n ts \A
-0
V A
T u s k e g e e -R e p la c e
R o o f_
R a c a b ra
M U
S
.r v t
20.AD101
BUILDING 20 DEMOLITION ROOF PLAN
4 14RF
REPLACE ROOFS IN BLDGS.
19, 20, 50, 51, AND 62
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083 JUNE 19, 2024
CONSTRUCTION DOCUMENTS
619A4-24-10223-069
WVS
Scale: 1/8" = 1'-0"
BUILDING 20 DEMOLITION ROOF PLAN
1 REMOVE EXISTING ASPHALT SHINGLE ROOF AND
UNDERLAYMENT TO EXISTING SUBSTRATE.
2 REMOVE EXISTING EXHAUST FAN IN ITS ENTIRETY.
FILL IN HOLE WITH 3/4" FT PLYWOOD.
3 EXISTING VENT TO BE REMOVED.
4 REMOVE EXISTING ROTTED / DAMAGED WOOD
SUBSTRATE PREP FOR NEW MATERIAL
INSTALLATION. SEE A-001 FOR QUANTITIES.
5 REMOVE EXISTING SUBSTRATE IN THIS AREA ALL
THE WAY DOWN TO FRAMING. PRIOR TO FILLING IN
WITH NEW SHEATHING, USE OPEN AREA FOR
MATERIAL MOVEMENT.
6 REPLACE DAMAGED AND DETERIORATED WOOD
AROUND INTERIOR GUTTER. REPAIR GUTTER
SECTIONS TO MAKE A CONTINUOUS, FULLY
FUNCTIONING, INTERIOR GUTTER SYSTEM.
7 REMOVE AND REPLACE WOOD FASCIA, WOOD TRIM
AND DECORATIVE WOOD ITEMS.
8 REMOVE EXISTING ROOF HATCH.
9 REMOVE EXITING VALLEY FLASHING.
10 REMOVE DETERIORATED RAFTER TAILS.
11 REMOVE SLOTTED PARAPET WALL, TRIM, AND CAP.
12 EXISTING MAGNOLIA TREE, TRIM 10 LARGE
BRANCHES (BACK TO MAIN TRUNK) THAT ARE
POINTING TOWARD THE BUILDING OR OVER LOWER
ROOF.
13 EXISTING LARGE TREE, TRIM 10 LARGE BRANCHES
(BACK TO MAIN TRUNK) THAT ARE POINTING
TOWARD THE BUILDING.
14 EXISTING STEEL FIRE ESCAPE TO REMAIN.
15 REMOVE ALL VEGETATION FROM WHOLE
ELEVATION THIS WALL. AFTER REMOVAL, SPRAY
WALL WITH ENVIRONMENTALLY SAFE WEED KILL
TO PREVENT GROW BACK.
16 EXISTING LARGE TREE TO BE CUT DOWN AND
REMOVED OFFSITE. CUT 1'-0" +/- ABOVE GRADE.
17 REMOVE EXISTING SUBSTRATE IN THIS AREA
DOWN TO FRAMING.
18 REMOVE COPING.
19 REMOVE EXISTING BUILT IN COPPER GUTTER.
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
NORTH
0 4 8 16
A. CONTRACTOR TO ENSURE PROPER SAFETY
BARRIERS AND ENCLOSURES ARE PROVIDED AT
ALL ENTRY/EXIT POINTS FROM BUILDING WHERE
WORK IS BEING PERFORMED ABOVE.
B. ALL PERSONNEL TO WEAR PROPER SAFETY
DEVICES/FALL PROTECTION.
C. CONTRACTOR SHALL PROVIDE PROTECTION AS
PER OSHA REQUIREMENTS.
D. CONTRACTOR TO ASSUME ALL DEMOLITION OF
PAINT OR PAINTED WOOD OR METAL CONTAINS
LBP AND NEEDS TO BE ABATED PER SPEC
SECTION 02 83 33.13
E. ALL DIMENSIONS ON THE DRAWINGS HAVE BEEN
DETERMINED BASED ON MINIMAL AS-BUILT
INFORMATION AVAILABLE. CONTRACTOR TO
VERIFY ALL DIMENSIONS AND QUANTITIES PRIOR
TO SUBMITTING BID.
F. CONTRACTOR SHALL PROVIDE TEMPORARY
SHORING OF EXISTING ROOF STRUCTURE AS
NECESSARY FOR CONSTRUCTION LIVE LOADS.
G. APPROXIMATE HEIGHT TO EAVE FROM GRADE
AVERAGES APPROX. 30'-0". APPROXIMATE
HEIGHT TO LOW FRONT ROOF FROM GRADE
APPROX. 12'-0".
H. ATTIC ACCESS FOR WORKERS ACCEPTABLE
THROUGH BUILDING INTERIOR. POWER IS NOT
AVAILABLE AT THIS BUILDING SITE. ANY
ELECTRICAL POWER NEEDED SHALL BE
PROVIDED BY THE CONTRACTOR.
REFERENCE PHOTO LOW
ROOF AT ENTRANCE
W
AL
7 8
7 87 8 13
7 8 13
7 8
126'-11"
42'-8" 38'-0" 45'-4"
S L O
P E
/2 :1
SLOPE: 5 1/2:12
28'-0"
SLOPE: 4:12 SLOPE: 4:12
A-502
20.B 20.C 20.D 20.E 20.F 20.G 20.H 20.I 20.J
20.2
20.3
20.4
20.5
SLOPE: 5 1/2:12
7 8
A-501
A-501
1'-0" 26'-4" 26'-4" 26'-4" 1'-0"
171717
14'-0" 14'-0" 14'-0" 14'-0" 14'-0" 14'-0" 14'-0" 14'-0" 14'-0"
100 S.F.
260 S.F.
100 S.F.
140 S.F.
20.A-101
20.A-101
S L O
P E
/2 :1
TYP.
TYP.
TYP.
ATTIC
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:0
:1
P
M C
U s e rs
\a c a b ra
\D o c u m e n ts \A
-0
V A
T u s k e g e e -R e p la c e
R o o f_
R a c a b ra
M U
S
.r v t
20.A-101
BUILDING 20 ROOF PLAN
5 14RF
REPLACE ROOFS IN BLDGS.
19, 20, 50, 51, AND 62
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083 JUNE 19, 2024
CONSTRUCTION DOCUMENTS
619A4-24-10223-069
WVS
Scale: 1/8" = 1'-0"
BUILDING 20 ROOF PLAN
1 INSTALL NEW ASPHALT SHINGLE ROOF SYSTEM.
2 REPLACE EXISTING ROOF HATCH, MATCH EXISTING
HATCH SIZES. BASIS OF DESIGN: BILCO TYPE S
ROOF HATCH W/ LADDER OR EQUAL. INSTALL
FLASHING UP TO INTEGRAL CAP FLASHING ON
HATCH FRAME. REPLACE DETERIORATED WOOD
FRAMING FOR HATCH, ASSUME ALL WOOD TO BE
REPLACED.
3 NEW 16 OZ COPPER CRICKET W/SELF ADHERED
UNDERLAYMENT. AS PER SMACNA.
4 INSTALL NEW 60 MIL FLEECE BACK TPO ROOFING
ON NEW SHEATHING.
5 INSTALL NEW VALLEY FLASHING.
6 INSTALL NEW BASE FLASHING AT WALL PER ROOF
SYSTEM MANUFACTURER'S STANDARD DETAILS.
7 EXISTING INTEGRAL GUTTER WITH NEW COPPER
LINING, ENSURE PROPER CONNECTIONS TO ALL
DOWNSPOUTS AND ALL GUTTER SECTIONS.
8 REPLACE FASCIA, EAVES, SOFFITS AND OTHER
ROTTED OR DETERIORATED WOOD MATERIAL
BEFORE INSTALLING NEW FLASHING OR ROOF
MATERIAL. SEE SHEET A-001 FOR QUANTITIES.
9 INSTALL NEW 3/4" WOOD SHEATHING FLUSH WITH
EXISTING (APPROX. 140 S.F.).
10 INSTALL NEW 3/4" WOOD SHEATHING FLUSH WITH
EXISTING (APPROX. 260 S.F.).
11 INSTALL NEW 3/4" WOOD SHEATHING FLUSH WITH
EXISTING (APPROX. 100 S.F.).
12 NEW 16 OZ COPPER COPING, MATCH EXISTING
PROFILE.
13 INSTALL NEW RAFTER TAIL LENGTH MIN 4'-0"
(QUANTITY 12).
14 INSTALL NEW 3/4" WOOD SHEATHING. SLOPE
SHEATHING TO BUILT IN GUTTER VIA SHIMS.
15 SHINGLE OVER RIDGE VENT.
16 12 X 12 ROOF VENT. BASIS OF DESIGN: GAF,
MASTER FLOW ROOF LOUVER SSB960 METAL,
SLANT BACK. COLOR TO MATCH SHINGLES, OR
EQUAL.
17 INSTALL NEW FALL PROTECTION STANCHION. BOD:
FRONTLINE COMMERCIAL ROOF ANCHOR - R012 OR
EQUAL, TYPICAL.
18 INSTALL (3) LAYERS OF 2" XPS INSULATION ON TOP
OF EXISTING ATTIC SLAB. DEMOLISH ALL CONDUIT
AND PIPING TO ALLOW INSULATION TO LAY ON
ATTIC SLAB. SEAL ALL OPENINGS WITH FIRE
CAULKING. METHOD OF ATTACHMENT - ADHESIVE.
BASIS OF DESIGN: OWENS CORNING, FOAMULAR
250, 2" THICK, 4'X8' SHEETS, OR EQUAL ENTIRE
ATTIC AREA.
19 INSTALL NEW BUILT IN 16 OZ COPPER GUTTER,
PROFILE TO MATCH EXISTING, ALL WELDED SEAMS,
NEW 3" ROUND 18 OZ COPPER DOWNSPOUTS.
20 REBUILD SLOTTED PARAPET WALL, INCLUDING
FRAMING, WOOD TRIM TO MATCH EXISTING, AND
CAP. NEW PARAPET WALL TO MATCH EXISTING IN
HEIGHT AND APPEARANCE.
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
NORTH
0 4 8 16
A. CONTRACTOR TO ENSURE PROPER SAFETY
BARRIERS AND ENCLOSURES ARE PROVIDED AT
ALL ENTRY/EXIT POINTS FROM BUILDING WHERE
WORK IS BEING PERFORMED ABOVE.
B. ALL PERSONNEL TO WEAR PROPER SAFETY
DEVICES/FALL PROTECTION.
C. CONTRACTOR SHALL PROVIDE FALL PROTECTION
PER OSHA REQUIREMENTS.
D. ALL DIMENSIONS ON THE DRAWINGS HAVE BEEN
DETERMINED BASED ON MINIMAL AS-BUILT
INFORMATION AVAILABLE. CONTRACTOR TO
VERIFY ALL DIMENSIONS AND QUANTITIES PRIOR
TO SUBMITTING BID.
E. CONTRACTOR SHALL PROVIDE TEMPORARY
SHORING OF EXISTING ROOF STRUCTURE AS
NECCESSARY FOR CONTRUCTION LIVE LOADS.
F. APPROXIMATE HEIGHT TO EAVE FROM GRADE
AVERAGES APPROX. 30'-0".
G. ATTIC ACCESS FOR WORKERS ACCEPTABLE
THROUGH BUILDING INTERIOR.
H. ANY WOOD RAFTER DISCOVERED TO BE NON
STRUCTURALLY SOUND SHALL BE REPAIRED AS
PER DETAIL 9/A-502.
I. POWER IS NOT AVAILABLE AT THIS BUILDING SITE.
ANY ELECTRICAL POWER NEEDED SHALL BE
PROVIDED BY THE CONTRACTOR.
Scale: 1/4" = 1'-0"
BUILDING 20 SCHEMATIC SECTION
W
AL
H I J K L M N O P Q R S T U
V
W
X
Y
Z
AA
5 5 5
5 5
5 5
5 5
3 3 3
3 4
ENCLOSED CONNECTOR BRIDGE
BETWEEN BUILDINGS 50,51+62
39'-8"
38'-0"
S L O
P E
:1
S L O
P E
:1
SLOPE: 5:12"
SLOPE: 5:12"SLOPE: 5:12"
3 4
1 1
85'-9
73'-8"
TO EDGE OF BUILDING 51
A-501
A-501
A-501
7 7
10 10
124'-6" 10'-5" 124'-6"
18'-1" 23'-0" 23'-0" 22'-4" 23'-8" 11'-4" 15'-0" 11'-6" 23'-8" 22'-4" 23'-0" 23'-0" 18'-1"
111'-2" 37'-0" 111'-2"
259'-4"
86'-6" 86'-5" 86'-6"
TYP.
Engineers Architects
# DEMOLITION KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:0
:1
P
M C
U s e rs
\a c a b ra
\D o c u m e n ts \A
-0
V A
T u s k e g e e -R e p la c e
R o o f_
R a c a b ra
M U
S
.r v t
50.AD101
BUILDING 50 DEMOLITION ROOF PLAN
6 14RF
REPLACE ROOFS IN BLDGS.
19, 20, 50, 51, AND 62
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083 JUNE 19, 2024
CONSTRUCTION DOCUMENTS
619A4-24-10223-069
WVS
N O
R T
H0 4 8 16
Scale: 1/8" = 1'-0"
BUILDING 50 DEMOLITION ROOF PLAN
1 REMOVE EXISTING ASPHALT SHINGLE ROOF
SYSTEM AND ALL PARTS OF ROOF SYSTEM
INCLUDING EXISTING SUBSTRATE.
2 REMOVE ALL ABANDONED EQUIPMENT,
SUPPORTS, PIPES, ANTENNAS, ETC. NOT IN USE.
3 REMOVE FLASHING FOR INSTALLATION OF NEW
ROOF SYSTEM.
4 REMOVE EXISTING BUILT UP ROOF SYSTEM
INCLUDING INSULATION, ETC. TO CONCRETE
SUBSTRATE.
5 EXISTING EXHAUST FANS TO BE REMOVED AND
INFILL OPENING IN CONCRETE SUBSTRATE.
6 REMOVE EXISTING ROTTED / DAMAGED
FASCIA/DRIP EDGE AROUND PERIMETER OF
ROOF.
7 EXISTING CAST STONE/CONCRETE COPING CAP
TO REMAIN.
8 REMOVE ALL SUBSTRATE PLANKS, TYPICAL.
9 EXISTING ROOF DRAINS TO BE REMOVED.
VERTICAL PIPE TO FIRST 90 DEGREE ELBOW AND
THE FIRST 90 DEGREE ELBOW TO BE REPLACED,
SEE DETAIL 4/A-502.
10 EXISTING CAST STONE NOTCH IN PARAPET WALL
TO REMAIN, TYPICAL.
11 EXISTING LARGE TREE TO BE CUT DOWN AND
REMOVED OFFSITE. CUT 1'-0" +/- ABOVE GRADE.
12 EXISTING LARGE TREE, TRIM 10 LARGE
BRANCHES (BACK TO MAIN TRUNK) THAT ARE
POINTING TOWARD THE BUILDING.
13 REMOVE EXISTING THRESHOLD.
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
A. CONTRACTOR TO ENSURE PROPER SAFETY
BARRIERS AND ENCLOSURES ARE PROVIDED AT
ALL ENTRY/EXIT POINTS FROM BUILDING WHERE
WORK IS BEING PERFORMED ABOVE.
B. ALL PERSONNEL TO WEAR PROPER SAFETY
DEVICES/FALL PROTECTION.
C. CONTRACTOR TO REMOVE ALL ROOF DRAIN
COVERS AND PROVIDE BLOW DOWN OF DRAIN
PIPES TO ENSURE NO BLOCKAGE.
D. CONTRACTOR SHALL PROTECT THE EXISTING
CONCRETE SLAB FROM DAMAGE DURING
CONSTRUCTION.
E. CONTRACTOR TO ASSUME ALL DEMOLITION OF
PAINT OR PAINTED WOOD OR METAL CONTAINS
LBP AND NEEDS TO BE ABATED PER SPEC
SECTION 02 83 33.13
F. ALL DIMENSIONS ON THE DRAWINGS HAVE BEEN
DETERMINED BASED ON MINIMAL AS-BUILT
INFORMATION AVAILABLE. CONTRACTOR TO
VERIFY ALL DIMENSIONS AND QUANTITIES PRIOR
TO SUBMITTING BID.
G. CONTRACTOR SHALL PROVIDE TEMPORARY
SHORING OF EXISTING ROOF STRUCTURE AS
NECESSARY FOR CONSTRUCTION LIVE LOADS.
H. THIS ROOFING PROJECT IS A COMPLETE TEAR
OFF AND RE-ROOF. EXIST ROOF HAS A 2 PLY
BUILT UP. INSULATION TYPE AND THICKNESS,
UNKNOWN. PRICE DEMOLITION OF 6" POLY ISO.
W
AL
H I J K L M N O P Q R S T U
V
W
X
Y
Z
AA
6 7
6 7
5 5
2 3
11 11
2 3
ENCLOSED CONNECTOR BRIDGE
BETWEEN BUILDINGS 50,51+62
124'-6" 10'-5" 124'-6"
18'-1" 23'-0" 23'-0" 22'-4" 23'-8" 11'-4" 15'-0" 11'-6" 23'-8" 22'-4" 23'-0" 23'-0" 18'-1"
111'-2" 37'-0" 111'-2"
259'-4"
12 12
12 12
12121212
S L O
P E
:1
S L O
P E
:1
SLOPE: 5:12"SLOPE: 5:12"
SLOPE: 5:12"
SLOPE: 5:12"
2 3
2 3 5
85'-9
73'-8"
TO EDGE OF BUILDING 51
A-501
A-501
A-502
A-502
A-501
8 8
CONTINUES
ON 51.A-101
86'-6" 86'-5" 86'-6"
DS
13DS13 DS
DS
2 3
2 3
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:0
:1
P
M C
U s e rs
\a c a b ra
\D o c u m e n ts \A
-0
V A
T u s k e g e e -R e p la c e
R o o f_
R a c a b ra
M U
S
.r v t
50.A-101
BUILDING 50 ROOF PLAN
7 14RF
REPLACE ROOFS IN BLDGS.
19, 20, 50, 51, AND 62
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083 JUNE 19, 2024
CONSTRUCTION DOCUMENTS
619A4-24-10223-069
WVS
Scale: 1/8" = 1'-0"
BUILDING 50 ROOF PLAN
1 INSTALL NEW ASPHALT SHINGLE ROOF SYSTEM.
2 INSTALL NEW TPO ROOFING SYSTEM.
3 INSTALL ROOF INSULATION AND INSTALL MIN
R-33 POLY ISO INSULATION. APPLICATION
METHOD - LOW RISE FOAM.
4 EXISTING CAST STONE CONCRETE PARAPET
CAP, PRESSURE WASH CAP CLEAN.
5 INSTALL NEW BASE FLASHING AT WALL PER
ROOF SYSTEM VENDOR STANDARD DETAILS AND
RECOMMENDATIONS.
6 INSTALL NEW GUTTER AND DOWNSPOUTS TO
MATCH EXISTING SEE DETAIL 4/A-501.
7 REPLACE ALL FASCIAS, EAVES, SOFFITS, &
RAKES BEFORE INSTALLING FLASHING OR
REROOFING.
8 FILL ABANDONED CORE HOLES FROM
EQUIPMENT DEMOLITION WITH NON SHRINKING
CEMENTITIOUS GROUT. ACCEPTABLE METHODS
OF INSTALLATION. PLYWOOD FORMS BELOW OR
HOLE MOLE CORE HOLE FILLING SYSTEM OR
EQUAL.
9 INSTALL NEW ROOF DRAIN ASSEMBLY, REPLACE
EXISTING VERTICAL PIPE TO FIRST ELBOW AND
REPLACE FIRST 90 DEGREE ELBOW AND
RECONNECT TO EXISTING STORM.
10 REPLACE ALL SUBSTRATE PLANKS, WITH NEW
3/4" PT PLYWOOD, TYPICAL.
11 PATCH OPENINGS IN CONCRETE ROOF DECK
WHERE EQUIPMENT WAS REMOVED, SEE DETAIL
3/A-501.
12 INSTALL CRICKETS WITH TAPERED RIGID
INSULATION. ALL ANGLES TO BE 2:1 OR 3:1.
13 PROVIDE AND INSTALL 12"X24"X4" H MIN. PRE
CAST CONCRETE SPLASH BLOCK.
14 INTERNAL DRAINS NOT ABLE TO BE LOCATED AT
BUILDING 50, 51, 62, CONNECTOR DURING A/E
SURVEY. CONTRACTOR TO INCLUDE PRICING
FOR INSTALLATION OF 6 NEW ROOF DRAINS AT
CONNECTOR. INSTALLATION OF DRAIN VERTICAL
PIPE DOWN AND 90 ELBOW TO BE INCLUDED.
15 NEW BRAKE METAL THRESHOLD. 16 GA.
GALVANIZED METAL 3" VERTICAL LEG TO
EXTERIOR, HORIZONTAL = WIDTH OF WALL
VERTICAL LEG TO BE OVER NEW MEMBRANE.
TYPICAL (2) LOCATIONS.
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
N O R
TH0 4 8 16
A. CONTRACTOR TO ENSURE PROPER SAFETY
BARRIERS AND ENCLOSURES ARE PROVIDED AT
ALL ENTRY/EXIT POINTS FROM BUILDING WHERE
WORK IS BEING PERFORMED ABOVE.
B. ALL PERSONNEL TO WEAR PROPER SAFETY
DEVICES/FALL PROTECTION.
C. CONTRACTOR TO REMOVE ALL ROOF DRAIN
COVERS AND PROVIDE BLOW DOWN OF DRAIN
PIPES TO ENSURE NO BLOCKAGE.
D. CONTRACTOR TO VERIFY ALL EXISTING ROOF
CURBS, PENETRATIONS, OR ANYTHING
ATTACHED TO THE ROOF MEET ROOFING
MINIMUM HEIGHT REQUIREMENTS. NOTIFY COR
IMMEDIATELY PRIOR TO STARTING WORK.
E. CONTRACTOR SHALL PROVIDE PROTECTION
STRUCTURES AS NECESSARY AT ALL
WALKWAYS.
F. CONTRACTOR SHALL PROTECT THE EXISTING
CONCRETE SLAB FROM DAMAGE DURING
CONSTRUCTION.
G. CONTRACTOR TO ASSUME ALL DEMOLITION OF
PAINT OR PAINTED WOOD OR METAL CONTAINS
LBP AND NEEDS TO BE ABATED PER SPEC
SECTION 02 83 33.13.
H. ALL DIMENSIONS ON THE DRAWINGS HAVE BEEN
DETERMINED BASED ON MINIMAL AS-BUILT
INFORMATION AVAILABLE. CONTRACTOR TO
VERIFY ALL DIMENSIONS AND QUANTITIES PRIOR
TO SUBMITTING BID.
I. CONTRACTOR TO ENSURE ROOFS SLOPE TO
DRAINS, MINIMUM ROOF SLOPE 1/4" = 1'-0".
J. CONTRACTOR SHALL PROVIDE TEMPORARY
SHORING OF EXISTING ROOF STRUCTURE AS
NECESSARY FOR CONTRUCTION LIVE LOADS.
K. PENTHOUSE ROOF SLOPE IS 5:12 FOR PITCHED
ROOF.
L. NEW ROOFING SYSTEM: INSTALL VAPOR BARRIER
ON EXISTING CONCRETE DECK (BASIS OF
DESIGN, GAF SA VAPOR RETARDER XL, OR
EQUAL). R-33 PLYISO INSULATION, ADHERED,
LOW RISE FOAM. 5/8" GYPSUM COVER BOARD,
ADHERED, LOW RISE FOAM, AND 60 MIL FLEECE
BACK, ADHERED, LOW RISE FOAM. (BASIS OF
DESIGN, EVERGAURD TPO FLEECE BACK
MEMBRANE OR EQUAL).
M. INTERNAL DRAINS NOT ABLE TO BE LOCATED AT
BUILDING 50, 51, 62, CONNECTOR DURING A/E
SURVEY. CONTRACTOR TO INCLUDE PRICING
FOR INSTALLATION OF 6 NEW ROOF DRAINS AT
CONNECTOR. INSTALLATION OF DRAIN VERTICAL
PIPE DOWN AND 90 ELBOW TO BE INCLUDED.
W
AL
51.K
51.5
51.L 51.M 51.N 51.O 51.P 51.Q 51.R 51.S 51.T 51.U
51.6
51.7
51.9
51.10
51.11
51.12
2 2
1 1 1
3 3
6 6
3 3
6 3 11
ENCLOSED CONNECTOR
BRIDGE BETWEEN
BUILDINGS 50,51+62.
HEIGHT FROM GRADE
APPROX. 16'-0".
12'-0"
T O
T U
R N
I N
C O
N N
E C
T O
R
T O
T U
R N
I N
C O
N N
E C
T O
R
14 14 14
11 11
9'-6" 53'-0" 66'-0" 20'-0"
54'-0" 54'-0" 32'-0"
T O
T U
R N
I N
C O
N N
E C
T O
R
13'-3" 13'-3" 13'-3" 13'-3" 13'-9" 13'-9" 13'-9" 13'-9" 13'-3" 18'-10"
8 8
Engineers Architects
# DEMOLITION KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:0
:1
P
M C
U s e rs
\a c a b ra
\D o c u m e n ts \A
-0
V A
T u s k e g e e -R e p la c e
R o o f_
R a c a b ra
M U
S
.r v t
51.AD101
BUILDING 51 DEMOLITION ROOF PLAN
8 14RF
REPLACE ROOFS IN BLDGS.
19, 20, 50, 51, AND 62
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083 JUNE 19, 2024
CONSTRUCTION DOCUMENTS
619A4-24-10223-069
WVS
Scale: 1/8" = 1'-0"
BUILDING 51 DEMOLITION ROOF PLAN
1 REMOVE EXISTING BUILT UP ROOF SYSTEM
INCLUDING INSULATION, ETC. TO CONCRETE
SUBSTRATE.
2 REMOVE ALL ABANDONED EQUIPMENT, SUPPORTS,
PIPES, ANTENNAS, ETC. NOT IN USE. CONFIRM
ABANDONED ITEMS WITH COR PRIOR TO REMOVAL.
3 REMOVE FLASHING.
4 REMOVE EXISTING LOW PROFILE EDGE MATERIAL
FOR BUILT UP ROOF SYSTEM.
5 EXISTING VTR TO BE REMOVED.
6 EXISTING CAST STONE/CONCRETE COPING CAP TO
REMAIN.
7 EXISTING METAL COPING TO REMAIN, REMOVE AS
NECESSARY TO REROOF AREA.
8 EXISTING ROOF DRAINS TO BE REMOVED.
9 REMOVE THROUGH WALL SCUPPER.
10 BRICK DAMAGE AND STONE COPING DISPLACEMENT.
REBUILD ALL LAYERS OF BRICK (APPROX. 100 S.F.)
AND RE-SET 20 L.F. OF STONE COPING.
11 EXISTING ROOF DRAINS TO BE REMOVED. VERTICAL
PIPE TO EXISTING STORM SEWER BELOW TO BE
REPLACED. BLOW OUT DRAIN TO ENSURE THERE IS
NO BLOCKAGE. SEE DETAIL 4/A-502
12 EXISTING LARGE TREE TO BE CUT DOWN AND
REMOVED OFFSITE. CUT 1'-0" +/- ABOVE GRADE.
13 REMOVE EXISTING COPPER COPING.
14 REMOVE EXISTING SLOPED COPPER.
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
NORTH
0 4 8 16
A. CONTRACTOR TO ENSURE PROPER SAFETY
BARRIERS AND ENCLOSURES ARE PROVIDED AT
ALL ENTRY/EXIT POINTS FROM BUILDING WHERE
WORK IS BEING PERFORMED ABOVE.
B. ALL PERSONNEL TO WEAR PROPER SAFETY
DEVICES/FALL PROTECTION.
C. CONTRACTOR TO REMOVE ALL ROOF DRAIN
COVERS AND PROVIDE BLOW DOWN OF DRAIN
PIPES TO ENSURE NO BLOCKAGE. DRAIN PIPING
TO BE REPLACED TO FIRST 90 DEGREE ELBOW.
D. CONTRACTOR SHALL PROTECT THE EXISTING
CONCRETE SLAB FROM DAMAGE DURING
CONSTRUCTION.
E. CONTRACTOR SHALL PROVIDE PROTECTION
STRUCTURES AS NECESSARY AT ALL
WALKWAYS.
F. CONTRACTOR SHALL PROTECT THE EXISTING
CONCRETE SLAB FROM DAMAGE DURING
RESTORATION.
G. CONTRACTOR TO ASSUME ALL DEMOLITION OF
PAINT OR PAINTED WOOD OR METAL CONTAINS
LBP AND NEEDS TO BE ABATED PER SPEC
SECTION 02 83 33.13
H. ALL DIMENSIONS ON THE DRAWINGS HAVE
BEEN DETERMINED BASED ON MINIMAL AS-BUILT
INFORMATION AVAILABLE. CONTRACTOR TO
VERIFY ALL DIMENSIONS AND QUANTITIES
PRIOR TO SUBMITTING BID.
J. CONTRACTOR SHALL PROVIDE TEMPORARY
SHORING OF EXISTING ROOF STRUCTURE AS
NECESSARY FOR CONSTRUCTION LIVE LOADS.
W
AL
51.K
51.5
51.L 51.M 51.N 51.O 51.P 51.Q 51.R 51.S 51.T 51.U
51.6
51.7
51.9
51.10
51.11
51.12
1 3
10 10 10
2 3
2 3
2 3
ENCLOSED CONNECTOR
BRIDGE BETWEEN
BUILDINGS 50,51+62
9'-6" 53'-0" 66'-0" 20'-0"
12'-0"
66 6
88 5
54'-0" 54'-0" 32'-0"
2 3
2 3
T O
T U
R N
I N
C O
N N
E C
T O
R
T O
T U
R N
I N
C O
N N
E C
T O
R
6 6
6 6
CONTINUES
ON 62.A-101
CONTINUES
ON 50.A-101
13'-3" 13'-3" 13'-3" 13'-3" 13'-9" 13'-9" 13'-9" 13'-9" 13'-3" 18'-10"
6 6
MAIN ROOF
EAST ROOF
CANOPY ROOF
6 6 6 6
WEST ROOF
151515
A-503
2 3
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:0
:1
P
M C
U s e rs
\a c a b ra
\D o c u m e n ts \A
-0
V A
T u s k e g e e -R e p la c e
R o o f_
R a c a b ra
M U
S
.r v t
51.A-101
BUILDING 51 ROOF PLAN
9 14RF
REPLACE ROOFS IN BLDGS.
19, 20, 50, 51, AND 62
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083 JUNE 19, 2024
CONSTRUCTION DOCUMENTS
619A4-24-10223-069
WVS
Scale: 1/8" = 1'-0"
BUILDING 51 ROOF PLAN
1 INSTALL NEW 60 MIL FLEECE BACK TPO MEMBRANE
(LOW RISE FOAM) OVER 2" POLY STYRENE (LOW
RISE FOAM).
2…