This document appears to be a test report for lead air results at the U.S. Government Publishing Office (GPO) Building C, 3rd floor. The air sample collected from the HVAC/duct system on the 3rd floor was tested and found to contain 949.2 micrograms of lead. The GPO is seeking to contract for HVAC duct cleaning services for the 3rd floor of Building C, as records indicate the ducts have not been cleaned in over 50 years. This is due to concerns that the air supply may contain impurities, with lead being the most concerning. The solicitation number is 040ADV-24-R-0064, and the opportunity type is a solicitation for HVAC duct cleaning services.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Client Sample Description ConcentrationLab ID Analyzed Volume Lead

Collected

EMSL Analytical, Inc.

10752 & 10768 Baltimore Avenue, Beltsville, MD 20705 Phone/Fax: (301) 937-5700 / (301) 937-5701 http://www.EMSL.com beltsvillelab@emsl.com

Attn: Joselito Sto Tomas US Govt Publishing Office Safety Branch 732 N. Capitol Street, NW Washington, DC 20401

Received: 3/22/2024 08:30 AM

BLDG. C 2ND FLOOR AHU/DUCT AIR

Fax: (202) 512-1034 Phone: (202) 512-1626

Project:

3/21/2024Collected:

Test Report: Lead in Air by Flame AAS (NIOSH 7082)*

192402957 CustomerID: USGPO80 CustomerPO:

ProjectID:

EMSL Order:

Site: BLDG C 3RD FLOOR COL 3D17 BY LAW TO HOLD BINDER

SECTION

192402957-0001PB1-32124 949.2 <4.2 µg/m³L3/26/20243/21/2024

Site: BLDG C 3RD FLOOR COL 3D21 RIP AND MAKE READY

SECTION

192402957-0002PB2-32124 959.7 <4.2 µg/m³L3/26/20243/21/2024

Site: BLANK 192402957-0003PB-BLANK N/A <4.0 µg/filter 3/26/20243/21/2024

Joe Centifonti, Laboratory Manager or other approved signatory

Test Report ChmSnglePrm/nQC-7.32.3 Printed: 3/26/2024 2:44:16 PM

EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received.

Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. Analysis following Lead in Air by EMSL SOP/Determination of Environmental Lead by FLAA. Reporting limit is 4 µg/filter. ug/filter = µg/m³ x volume sampled (m³).

OSHA PEL - 50 µg/m³. OSHA action level - 30 µg/m³. "<" (less than) result signifies that the analyte was not detected at or above the reporting limit. Measurement of uncertainty is available upon request.

Definitions of modifications are available upon request. The final results are not blank corrected unless specifically indicated.

Samples analyzed by EMSL Analytical, Inc. Beltsville, MD A2LA Accredited - Certificate #2845.02

Initial report from 03/26/2024 14:44:16 http://www.EMSL.com mailto:beltsvillelab@emsl.com