Attachment 7- 515-21-701 B157 Inergen Supplimental dwg.pdf
PDF 524 KB Posted
- Solicitation number
- 36C77623R0101
About this file
This document provides as-built drawings for an Inergen clean agent fire suppression system installed at the Battle Creek VA Medical Center in Battle Creek, Michigan. The system protects three separate hazards across multiple rooms in Building 157. It utilizes Ansul Inergen clean agent stored in cylinders, with detection provided by photoelectric smoke detectors. Upon activation, electric actuators release the agent which flows through a network of distribution piping to discharge nozzles in each protected area. The drawings depict the pipe layout, hazard layout, sequence of operations, and details of the detection, control and actuation components. They provide specifications for the piping materials and fittings, support requirements, and mechanical installation notes. Vanguard Fire and Security prepared the drawings for their project S-H096 to install the system.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
V V
V V
V
V
V
V
V
V
V
V
V
V
V
V
INREGEN SUPPRESSION SYSTEM HAZARD LAYOUT
AS-BUILT DRAWINGS
DRAWING STATUS
1-800-444-8719
VANGUARD
O F
SH
EET
DRAWN BY:
SCALE:
DATE:
CONTRACT NO.:DESCRIPTION APPD
FIRMFIRMFIRM
CHKDDRNDATEREV.
5500 ARMSTRONG RD.
VA HOSPITAL BUILDING 157
PH: (616) 245-8719 FAX: (616) 245-7541
CONTRACTOR:
JOB:
GRAND RAPIDS, MICHIGAN 49509
2101 MARTINDALE AVENUE, S.W.
VANGUARD FIRE AND SECURITY, INC.
BATTLE CREEK, MI 49037
10-16-12
AS NOTED
NWL
S/H096
REVIEWED BY:
BWS
ANSUL INERGEN
VANGUARD PROJECT #S/H096
DISTRIBUTION PIPING ISOMETRICS, NOTES & DETAILS
DESCRIPTION
VA HOSPITAL BUILDING 157
CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH INTELLIGENT DETECTION & CONTROL
BATTLE CREEK, MI 49037
SHEET NO.
1 COVER AND DEMO PLANS
AUTOPULSE IQ-318 PANEL WIRING & DEVICE DETAILS
SUBFLOOR HAZARD LAYOUT
5500 ARMSTRONG ROAD
HAZARD LAYOUT
AutoCAD SHX Text 100B
AutoCAD SHX Text
AutoCAD SHX Text 100A
AutoCAD SHX Text 100C
AutoCAD SHX Text 101C
AutoCAD SHX Text 101B
AutoCAD SHX Text 101A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REMOVE EXISTING FIRE PROTECTION SPRINKLER HEADS AND ASSOCIATED PIPING.
AutoCAD SHX Text
REMOVE EXISTING FIRE PROTECTION PIPING.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REMOVE EXISTING FIRE PROTECTION PIPING BACK TO MAIN AND CAP.
AutoCAD SHX Text
EXISTING FIRE PROTECTION MAIN TO REMAIN.
AutoCAD SHX Text
AutoCAD SHX Text
FIRE PROTECTION DEMOLITION NOTES:
AutoCAD SHX Text
EXISTING FIRE PROTECTION SPINKLER HEAD TO REMAIN
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text REMOVE EXISTING DRY PIPE RISER AND ALL ASSOCIATED VALVES AND PIPING AND RECONNECT PIPING.
AutoCAD SHX Text
REMOVE EXISTING DRY PIPE AIR COMPRESSOR AND ALL ASSOCIATED WIRING AND CONTROLS
AutoCAD SHX Text REMOVE ALL EXISTING SMOKE DETECTORS ON CEILING AND UNDER RAISED FLOORS. FIELD VERIFY NUMBER AND LOCATIONS.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text P
AutoCAD SHX Text
AutoCAD SHX Text Armstrong Road
AutoCAD SHX Text
SIGN THINGY
AutoCAD SHX Text
SIGN THINGY
AutoCAD SHX Text 159G
AutoCAD SHX Text O
AutoCAD SHX Text P
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Lambers Trail
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Urban Drive
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text h
AutoCAD SHX Text a
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text e
AutoCAD SHX Text l
AutoCAD SHX Text c
AutoCAD SHX Text f
AutoCAD SHX Text r
AutoCAD SHX Text e
AutoCAD SHX Text t
AutoCAD SHX Text i
AutoCAD SHX Text C
AutoCAD SHX Text r
AutoCAD SHX Text u
AutoCAD SHX Text S
AutoCAD SHX Text o
AutoCAD SHX Text h
AutoCAD SHX Text t
AutoCAD SHX Text
AutoCAD SHX Text
NO PARKING
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Dewey Lane
AutoCAD SHX Text V
AutoCAD SHX Text
AutoCAD SHX Text 160G
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text V
AutoCAD SHX Text V
AutoCAD SHX Text G
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LAB
AutoCAD SHX Text Furlong Lane
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 169G
AutoCAD SHX Text
AutoCAD SHX Text 162G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Shafter Circle North
AutoCAD SHX Text 170G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 163G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Williams Lane
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Johnson Drive
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text
FD
AutoCAD SHX Text
FD
AutoCAD SHX Text
FD
AutoCAD SHX Text
FD
AutoCAD SHX Text T 98
AutoCAD SHX Text
AutoCAD SHX Text 164G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text V
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text "N"
AutoCAD SHX Text Fox Lane
AutoCAD SHX Text 135G
AutoCAD SHX Text
AutoCAD SHX Text V
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CU C
AutoCAD SHX Text
CU C
AutoCAD SHX Text V
AutoCAD SHX Text V
AutoCAD SHX Text V
AutoCAD SHX Text
CU C
AutoCAD SHX Text
CU C
AutoCAD SHX Text
CU
AutoCAD SHX Text
CU
AutoCAD SHX Text 161G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 168G
AutoCAD SHX Text T
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text VAMC boundary
AutoCAD SHX Text Shafter Circle West
AutoCAD SHX Text O
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text V
AutoCAD SHX Text
AutoCAD SHX Text Shafter Circle East
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 165G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text P
AutoCAD SHX Text H
AutoCAD SHX Text e
AutoCAD SHX Text n
AutoCAD SHX Text a
AutoCAD SHX Text l
AutoCAD SHX Text l
AutoCAD SHX Text a
AutoCAD SHX Text r
AutoCAD SHX Text o
AutoCAD SHX Text l
AutoCAD SHX Text F
AutoCAD SHX Text Hammerberg Lane
AutoCAD SHX Text
AutoCAD SHX Text
PANEL DEVICE & WIRING DETAIL
SCALE:N.T.S.
12VDC 18AH BATTERY
12VDC 18AH BATTERY
120 VAC
C
NO
NC
TROUBLE RELAY
ALARM RELAY
TO MAIN BUILDING FIRE ALARM PANEL
TO MAIN BUILDING FIRE ALARM PANEL
IQ-318 CONTROL PANEL
WIRING DIAGRAM
HOT
NEUT
GND
TB6
TB7
TB8
TB9
NAC #4
NAC #2
NAC #1
NAC #3
24VDC
NON RESETTABLE
ALARM
B+ A+ B- A-
BATT+BATT-
TB4
C
NO
NC
TROUBLE
C NONC
SECURITY
C NONC
SUPERVISORY
TB5
A-
A+
B-
B+
A-
A+
B-
B+
A-
A+
B-
B+
A-
A+
B-
B+
24VDC
RESETTABLE
TB13
TB12TB11TB10
TB3
PRINTER TERMINAL BLOCK - SEE MANUALEIA-485 TERMINAL BLOCK - SEE MANUAL
LOCKOUT
SWITCH
ELEC. SOUNDER WITH
STROBE
NAC ZONE #3
AUDIBLESTROBE
SLC
24V
FCM-1REL
6 7
LOOP (-)
(BLACK)(RED)
LOOP (+)
6 7 8
LOOP
(VIOLET)
IDC (+)
1 14
FMM-101
ADDRESS
4 11
IDC (-)
(YELLOW)
47K
RESISTOR
ELEC. SOUNDER WITH
STROBE
NAC ZONE #3
AUDIBLESTROBE
TYPICAL MANUAL
PULL STATION
LOCKOUT SWITCH TO ELECTRONICALLY
DISABLE TANK ACTUATION BY
DISABLING 24VDC TO THE ACTUATION
MODULES (FCM-1REL)
24VDC
24VDC 24VDC
24VDC
EOL
47K 1/2W
NO
NC
IDC (+)
(VIOLET)(YELLOW)
IDC (-)
6 7 8
0 15
ADDRESS
FMM-101
LOOP
LOOP (+)
(RED)
(BLACK)
LOOP (-)
ELECTRIC ACTUATOR FOR 8 TANK
SYSTEM CYLINDERS
WITH THE BASIC LAYOUT AS SHOWN ON DRAWINGS TO PREVENT
POWER UP
SEQUENCE.
4. POWER UP & POWER DOWN ON PANEL MUST BE DONE IN PROPER
B - TURN OFF AC POWER PRIMARY & SECONDARY.
A - TURN ON AC POWER PRIMARY & SECONDARY.
5. THE FIRE ALARM CONTROL PANEL SHALL NOT BE USED TO POWER ANY
CIRCUIT OVERLOAD.
A - DISCONNECT BATTERY.
B - RECONNECT BATTERIES.
POWER DOWN
UNAUTHORIZED EXTERNAL DEVICE.
EQUIPMENT TO BE DETERMINED IN THE FIELD, BUT SHALL CONFORM
3. WIRE RUNS ARE SHOWN DIAGRAMMATICALLY. EXACT LOCATION OF ALL
ALL EQUIPMENT SHALL BE UL LISTED. ALL DEVICES SHALL BE
1. ALL WIRING MUST CONFORM WITH NEC ARTICLE 760 AND LOCAL CODES.
DETECTION AND CONTROL NOTES
PER NEC 760 AND UL 864 REQUIREMENTS.
COMPATIBLE WITH THE CONTROL PANELS. SYSTEM IS POWER LIMITED
2. CIRCUIT POLARITY MUST BE OBSERVED.
POWER. THE AIR CONDITIONER UNIT IN ROOM IS TO BE SHUT DOWN UPON DISCHARGE.
6. PER NFPA 75, UPON DISCHARGE, COMPUTER EQUIPMENT IS TO RETAIN CONTINUOUS
7. 20 amp DEDICATED CIRCUIT W/ LOCKOUT TO BE PROVIDED BY ELECTRICAL
CONTRACTOR. BREAKER TO BE LABELED FOR SUPPRESSION SYSTEM.
THE PARTICULAR EXTERNAL COMPONENT BEING MOUNTED.
WIRE FOR THE AC POWER SUPPLY CONNECTIONS.
CARRY WIRING TO, FROM AND BETWEEN THE CONTROL SYSTEM AND
THE SIZE JUNCTION BOX RECOMMENDED BY THE MANUFACTURER OF
EXTERNAL COMPONENTS IN ONE-HALF INCH MINIMUM CONDUIT. USE
COLOR CODED WIRE FOR SUPERVISED CIRCUITS. USE NO. 14 AWG
HAVING JURISDICTION, USE WIRE SIZE AS NOTED IN THE CHART,
ELECTRICAL CODE. UNLESS OTHERWISE SPECIFIED BY AUTHORITIES
ARTICLE 760, FIRE PROTECTIVE SIGNALING SYSTEMS, NATIONAL
INSTALL WIRING AND EQUIPMENT IN ACCORDANCE WITH NFPA 70,
TOTAL WIRE RESISTANCE PER CIRCUIT MUST NOT EXCEED 20 ohms.
MAN. PULL
DETECTION
ABORT
18 AWG
18 AWG
18 AWG
16 AWG
16 AWG
16 AWG 14 AWG
14 AWG
14 AWG
CIRCUIT 1500 FT. 2200 FT. 4000 FT.
INPUT 0 TO 1500 FT. TO 2200 FT. TO
CIRCUIT 1000 FT. 1000 FT.
OUTPUT 0 TO GREATER THAN
WIRE LENGTH/MINIMUM WIRE GAUGE
ALARM
RELEASE
14 AWG
14 AWG
12 AWG
12 AWG
ELEC. SOUNDER WITH
STROBE
NAC ZONE #3
AUDIBLESTROBE
AS-BUILT DRAWINGS
DRAWING STATUS
1-800-444-8719
VANGUARD
N O F
SH
EETDRAWN BY:
SCALE:
DATE:
CONTRACT NO.:DESCRIPTION APPD
FIRMFIRMFIRM
CHKDDRNDATEREV.
PH: (616) 245-8719 FAX: (616) 245-7541
CONTRACTOR:
JOB:
GRAND RAPIDS, MICHIGAN 49509
2101 MARTINDALE AVENUE, S.W.
VANGUARD FIRE AND SECURITY, INC.
10-16-12
AS NOTED
NWL
S/H096
REVIEWED BY:
BWS 5
PLAN NORTH
5500 ARMSTRONG RD.
VA HOSPITAL BUILDING 157
BATTLE CREEK, MI 49037
INREGEN SUPPRESSION SYSTEM HAZARD LAYOUT
ELEC. SOUNDER WITH
STROBE
NAC ZONE #2
AUDIBLESTROBE
ELEC. SOUNDER WITH
STROBE
NAC ZONE #1
AUDIBLESTROBE
ELEC. SOUNDER WITH
STROBE
NAC ZONE #1
AUDIBLESTROBE
2.2K 1/2 WATT
ELEC. STROBE
NAC ZONE #1
STROBE
ELEC. SOUNDER WITH
STROBE
NAC ZONE #4
AUDIBLESTROBE
ELEC. SOUNDER WITH
STROBE
NAC ZONE #4
AUDIBLESTROBE
ELEC. SOUNDER WITH
STROBE
NAC ZONE #3
AUDIBLESTROBE
2.2K 1/2 WATT
ELEC. SOUNDER WITH
STROBE
NAC ZONE #3
AUDIBLESTROBE
2.2K 1/2 WATT
2.2K 1/2 WATT
LOOP (-)
(BLACK)(RED)
LOOP (+)
6 7 8
LOOP
(VIOLET)
IDC (+)
1 14
FMM-101
ADDRESS
4 11
IDC (-)
(YELLOW)
47K
RESISTOR
TYPICAL ABORT
STATION
LOOP (-)
(BLACK)(RED)
LOOP (+)
6 7 8
LOOP
(VIOLET)
IDC (+)
1 14
FMM-101
ADDRESS
4 11
IDC (-)
(YELLOW)
47K
RESISTOR
TYPICAL MANUAL
PULL STATION
LOOP (-)
(BLACK)(RED)
LOOP (+)
6 7 8
LOOP
(VIOLET)
IDC (+)
1 14
FMM-101
ADDRESS
4 11
IDC (-)
(YELLOW)
47K
RESISTOR
TYPICAL ABORT
STATION
LOOP (-)
(BLACK)(RED)
LOOP (+)
6 7 8
LOOP
(VIOLET)
IDC (+)
1 14
FMM-101
ADDRESS
4 11
IDC (-)
(YELLOW)
47K
RESISTOR
TYPICAL MANUAL
PULL STATION
LOOP (-)
(BLACK)(RED)
LOOP (+)
6 7 8
LOOP
(VIOLET)
IDC (+)
1 14
FMM-101
ADDRESS
4 11
IDC (-)
(YELLOW)
47K
RESISTOR
TYPICAL ABORT
STATION
LOOP (-)
(BLACK)(RED)
LOOP (+)
6 7 8
LOOP
(VIOLET)
IDC (+)
1 14
FMM-101
ADDRESS
4 11
IDC (-)
(YELLOW)
47K
RESISTOR
TYPICAL MANUAL
PULL STATION
LOOP (-)
(BLACK)(RED)
LOOP (+)
6 7 8
LOOP
(VIOLET)
IDC (+)
1 14
FMM-101
ADDRESS
4 11
IDC (-)
(YELLOW)
47K
RESISTOR
TYPICAL ABORT
STATION
LOOP (-)
(BLACK)(RED)
LOOP (+)
6 7 8
LOOP
(VIOLET)
IDC (+)
1 14
FMM-101
ADDRESS
4 11
IDC (-)
(YELLOW)
47K
RESISTOR
TYPICAL MANUAL
PULL STATION
LOOP (-)
(BLACK)(RED)
LOOP (+)
6 7 8
LOOP
(VIOLET)
IDC (+)
1 14
FMM-101
ADDRESS
4 11
IDC (-)
(YELLOW)
47K
RESISTOR
TYPICAL ABORT
STATION
LOOP (-)
(BLACK)(RED)
LOOP (+)
6 7 8
LOOP
(VIOLET)
IDC (+)
1 14
FMM-101
ADDRESS
4 11
IDC (-)
(YELLOW)
47K
RESISTOR
TYPICAL MANUAL
PULL STATION
LOOP (-)
(BLACK)(RED)
LOOP (+)
6 7 8
LOOP
(VIOLET)
IDC (+)
1 14
FMM-101
ADDRESS
4 11
IDC (-)
(YELLOW)
47K
RESISTOR
TYPICAL ABORT
STATION
SLC
24V
FCM-1REL
6 7
24VDC
ELECTRIC ACTUATOR FOR 14
TANK SYSTEM CYLINDERS
SLC
24V
FCM-1REL
6 7
ELECTRIC ACTUATOR FOR
SELECTOR VALVE 1
SLC
24V
FCM-1REL
6 7
ELECTRIC ACTUATOR FOR
SELECTOR VALVE 2
SLC
24V
FCM-1REL
6 7
ELECTRIC ACTUATOR FOR
SELECTOR VALVE 3
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
2 (+)
ADDRESSLOOP
ION
THER
1 (-)
PHOTO
TYPE
TYPICAL SMOKE
DETECTOR
24VDC 24VDC 24VDC
SUBFLOOR
62'-1"
36'-6"
HF
SV
HF HF
SVSV 1 2 3
HF
HF
PS
PROTECTED AREA : VISTA #100B - Z1
: 1'-5"
: 2098 FT²
: 2973 FT³
: 1269.5 FT³
: 1416.2 FT³
PROTECTED AREA : MAIN IT ROOM
SUBFLOOR - Z3
NORMALLY UNOCCUPIED
SUBFLOOR HEIGHT
TOTAL AREA
TOTAL VOLUME
AGENT REQUIRED (34.2%)
DESIGN QUANTITY
: 0'-10.5"
: 770 FT²
: 684 FT³
: 292 FT³
: 333.4FT³
PROTECTED AREA : ROOMS 100, 100A & 100B
COMMON SUBFLOOR - Z1
NORMALLY UNOCCUPIED
SUBFLOOR HEIGHT
TOTAL AREA
TOTAL VOLUME
AGENT REQUIRED (34.2%)
DESIGN QUANTITY
PROTECTED AREA : VISTA #100 - Z1
D017 D015
D016
D041
D042
D043
D044
D045
D046 D040
D018
D019
NO SUBFLOOR IN THIS AREA
1/2" NOZZLE
1/2" NOZZLE
1/2" NOZZLE
1/2" NOZZLE
1/2" NOZZLE
31'-3"
22'
7'-4"
11'-4"
SUBFLOOR
SUBFLOOR
SUBFLOOR
SUBFLOOR
SUBFLOOR
SUBFLOOR
SUBFLOOR
SUBFLOOR
SUBFLOORSUBFLOOR
SUBFLOOR
DOWN TO
SUBFLOOR
DOWN TO
SUBFLOOR
AS-BUILT DRAWINGS
DRAWING STATUS
1-800-444-8719
VANGUARD
N O F
SH
EETDRAWN BY:
SCALE:
DATE:
CONTRACT NO.:
SIGNATURE:
DESCRIPTION APPD
FIRMFIRMFIRM
CHKDDRNDATEREV.
PH: (616) 245-8719 FAX: (616) 245-7541
CONTRACTOR:
JOB:
GRAND RAPIDS, MICHIGAN 49509
2101 MARTINDALE AVENUE, S.W.
VANGUARD FIRE AND SECURITY, INC.
8-4-11
AS NOTED
NWL
S/H096
REVIEWED BY: 5
SEQUENCE OF OPERATIONS
ANSUL INERGEN CLEAN AGENT SUPPRESSION SYSTEM WITH SELECTOR VAVLES
AUTOPULSE DETECTION & CONTROL RELEASING SYSTEM
SYSTEM OVERVIEW
O THESE HAZARDS ARE PROTECTED BY ANSUL INERGEN.
O THE HAZARDS ARE MONITORED BY PHOTOELECTRIC SMOKE DETECTORS.
STANDBY CONDITION
O GREEN LED ON PANEL ILLUMINATED (AC POWER)
O ALL OTHER LEDS OFF
SYSTEM MAINTENANCE
O THE BUILDING FIRE ALARM MONITORING COMPANY MUST BE NOTIFIED BEFORE ANY
MAINTENANCE BEGINS.
O IN ORDER TO PLACE SYSTEM IN MAINTENANCE MODE, THE MAINTENANCE SWITCH
MUST BE ENGAGED. THIS SWITCH DISABLES THE TANK ACTUATION CIRCUIT.
AUTOMATIC SMOKE DETECTION SEQUENCE
O THE CONTROL PANEL BEING UTILIZED USES A “COUNTING ZONING” FEATURE.
O WHEN ONE DETECTOR IN A ZONE SENSES AN ALARM CONDITION:
-BELLS WILL SOUND IN THAT ZONE.
-PANEL DISPLAY WILL SHOW WHICH DETECTOR IS IN ALARM.
-ALARM CONTACTS WILL CHANGE STATE.
O WHEN A SECOND DETECTOR IN THE SAME ZONE SENSES AN ALARM CONDITION:
-BELLS STOP SOUNDING
-STROBES WILL FLASH AND HORNS WILL SOUND ½ SECOND ON, ½ SECOND OFF.
-PANEL DISPLAY WILL SHOW BOTH DETECTORS IN ALARM.
-30-SECOND DISCHARGE TIME DELAY WILL BEGIN.
-AFTER TIME DELAY HAS EXPIRED, DISCHARGE WILL OCCUR AS OUTLINED IN THE
AGENT DISCHARGE SEQUENCE” SECTION
MANUAL PULL STATION
O A PULL STATION MAY BE ACTIVATED AT ANY TIME. PULL STATIONS ARE LOCATED INSIDE
THEIR RESPECTIVE ZONES.
O ACTIVATION OF PULL STATION WILL OVERRIDE ANY ABORT OR TIME DELAY
FUNCTIONS.
O SYSTEM WILL DISCHARGE IMMEDIATELY AS OUTLINED IN THE “AGENT DISCHARGE
SEQUENCE” SECTION.
AGENT DISCHAGRE SEQUENCE
O STROBES WILL CONTINUE TO FLASH AND HORNS WILL SOUND IN STEADY MODE.
O THE AGENT-RELEASING ZONE ON THE MODULE WILL ENERGIZE, ACTIVATING THE
ELECTRIC ACTUATOR(S), IMMEDIATELY RELEASING THE FM-200 AGENT FROM THE TANK.
O THE APPROPRIATE SELECTOR VALVE FOR THE AFFECTED HAZARD WILL OPEN ALLOWING
THE FLOW OF AGENT TO REACH THE SPACE.
ABORT STATION
O THE ABORT STATION MAY BE PRESSED AND HELD TO PAUSE SYSTEM DISCHARGE
COUNTDOWN SEQUENCE WHEN ACTIVATED BY SMOKE DETECTION.
O THE ABORT STATION MAY BE PRESSED AND HELD AT ANY TIME DURING FIRST STAGE
PRE-ALARM OR DURING SECOND STAGE ALARM (30 SECOND DISCHARGE TIME DELAY)
O RELEASE OF THE ABORT STATION WILL RESULT IN SYSTEM DISCHARGE AFTER 10
SECONDS OR AFTER THE 30 SECOND TIMER HAS EXPIRED.
BATTERY BACKUP
O SYSTEM IS DESIGNED TO RUN ON BACK-UP BATTERY POWER FOR A PERIOD OF AT
LEAST 24 HOURS IN SUPERVISION MODE AND 15 MIN. IN ALARM MODE.
H 80" MINP
MANUAL
DEVICE MOUNTING HEIGHT DETAIL
RELEASE STATION
N.T.S.
42" - 48"
D L O
H
PULL DOWN
ANSUL
S U
THEN
PUSH HERE
ABORT
6'-0"
AUTOPULSE
STATION
ABORT
FIRE INERGEN
96" MAX
HORN/STROBE
FIRE
5500 ARMSTRONG RD.
VA HOSPITAL BUILDING 157
BATTLE CREEK, MI 49037
SUBFLOOR HAZARD LAYOUT
1/4"=1'-0
INREGEN SUPPRESSION SYSTEM HAZARD LAYOUT
N
JOB SPECIFIC DETECTION AND ACTUATION NOTES:
- THIS SYSTEM IS DESIGNED TO PROTECT THREE SEPARATE HAZARDS.
- EXISTING SPRINKLERS AND PIPING TO BE REMOVED IN PROTECTED AREAS OTHER THEN NOTED ON PLAN
- THE SYSTEM DETECTS SMOKE VIA PHOTOELECTRIC DETECTORS.
- MANUAL RELEASE STATIONS AND DEADMAN ABORT STATIONS ARE LOCATED AT THE EGRESS POINTS OF EACH SPACE.
- THE AGENT DISTRIBUTION TANKS AND PIPING ARE SIZED TO DISCHARGE INTO ANY ONE DISCHARGE ZONE. AFTER ANY DISCHARGE, THE EMPTY TANKS MUST
BE REFILLED IN ORDER FOR THE SYSTEM TO BE BACK IN AN OPERATIONAL MODE
- DISCHARGE ZONE #1 (Z1):
THIS ZONE IS DEFINED AS THE BELOW CEILING AND BELOW SUBFLOOR SPACES IN THE "VISTA" (ROOMS 100, 100A & 100B) THE DISCHARGE SEQUENCE FOR THIS ZONE CONSISTS OF DISCHARGING EIGHT INERGEN TANKS THRU ONE SELECTOR VALVE AND
DISTRIBUTING THE AGENT BETWEEN SIX NOZZLES INTO THE SIX SPACES.
- DISCHARGE ZONE #2 (Z2):
THIS ZONE IS DEFINED AS THE DECK TO DECK SPACE IN THE "MIDDLE TELEPHONE ROOM" (ROOM 100C) ALONG WITH THE BATTERY CLOSET
THAT IS INSIDE THIS SPACE.
THE DISCHARGE SEQUENCE FOR THIS ZONE CONSISTS OF DISCHARGING EIGHT INERGEN TANKS THRU ONE SELECTOR VALVE AND
DISTRIBUTING THE AGENT BETWEEN THREE NOZZLES INTO THE TWO SPACES.
- DISCHARGE ZONE #3 (Z3):
THIS ZONE IS DEFINED AS THE BELOW CEILING AND BELOW SUBFLOOR SPACES IN THE "SERVER ROOM" (ROOM 101) THE THREE OFFICES THAT ARE ADJACENT TO THIS SPACE ARE NOT PROTECTED AS PART OF THE INERGEN SYSTEM AND ARE TO BE EQUIPPED
WITH A MECHANISM THAT ALLOWS THE DOORS TO CLOSE PRIOR TO THE AGENT DISCHARGE.
THE DISCHARGE SEQUENCE FOR THIS ZONE CONSISTS OF DISCHARGING A TOTAL OF TWENTY-TWO INERGEN TANKS.
EIGHT TANKS ARE DISCHARGED THRU ONE SELECTOR VALVE AND ARE DISTRIBUTED BETWEEN FOUR NOZZLES IN THE MAIN
SPACE AND IN THE SUBFLOOR SPACE
THE REMAINING FOURTEEN TANKS ARE DISCHARGED THRU AN INDEPENDENT PIPE NETWORK AND DISTRIBUTE AGENT
BETWEEN FOUR NOZZLES IN THE MAIN SERVER ROOM SPACE.
PROTECTED AREA : MIDDLE TELEPHONE ROOM 100C & BATTERY CLOSET - Z2
NORMALLY OCCUPIABLE SPACE
CEILING HEIGHT
TOTAL AREA
TOTAL VOLUME
AGENT REQUIRED (34.2%)
DESIGN QUANTITY
: 10'-4"
: 733 FT²
: 7574 FT³
: 3234.1 FT³
: 3512 FT³
62'-1"
36'-6"
A
FCM-1R M004 - 8 TANK ACTUATION - ALL ZONES
FCM-1R M005 - 14 TANK ACTUATION - Z1
FCM-1R M003 - SELECTOR VALVE 3 - Z3
FCM-1R M002 - SELECTOR VALVE 2 - Z2
FCM-1R M001 - SELECTOR VALVE 1 - Z1
RSFACU CA
HF
SV
HF HF
SVSV 1 2 3
M006 - LOCKOUT SWITCH
A
A
A
HF
HF
X2FMM-101
X2FMM-101 X2FMM-101
X3FMM-101
M
PROTECTED AREA : VISTA #100B - Z1
PROTECTED AREA : MAIN IT ROOM 101- Z3
NORMALLY OCCUPIABLE SPACE
CEILING HEIGHT
TOTAL AREA
TOTAL VOLUME
AGENT REQUIRED (34.2%)
DESIGN QUANTITY
: 9'-1"
: 2098 FT²
: 19056 FT³
: 8136.9 FT³
: 6146 FT³ + 2095.8 FT³
PROTECTED AREA : ROOMS 100, 100A & 100B
MAIN ROOM SPACES - DISCHARGE ZONE Z1
NORMALLY OCCUPIABLE SPACE
CEILING HEIGHT
TOTAL AREA
TOTAL VOLUME
AGENT REQUIRED (34.2%)
DESIGN QUANTITY
: 8'-6"
: 770 FT²
: 6545 FT³
: 2794.8 FT³
: 3178.6 FT³
PROTECTED AREA : VISTA #100 - Z1
PROTECTED AREA : VISTA #100A - Z1
D011 D012
D010
D013
D014
M011 M012
M021M022
M031
M032
M033 M034
D021 D022D020
D031
D032
D033
D034
D035
D036 D030
NAC1
NAC2
NAC4
EOLR
EOLR
EOLR
NAC4
NAC1 NAC1
NAC3
NAC3
NAC3
NAC3
1" NOZZLE
1" NOZZLE
1/2" NOZZLE
1/2" NOZZLE
1" NOZZLE1" NOZZLE
1" NOZZLE
1.25" NOZZLE 1.25" NOZZLE
1.25" NOZZLE 1.25" NOZZLE
21'-3"
22'
7'-4"
11'-4"
9'-3"
TO REMAIN IN THIS ROOM
EXISTING SPRINKLERS
TO REMAIN IN THIS ROOM
EXISTING SPRINKLERS
TO REMAIN IN THIS ROOM
EXISTING SPRINKLERS
TO REMAIN IN THIS ROOM
EXISTING SPRINKLERS
TO REMAIN IN THIS ROOM
EXISTING SPRINKLERS
DOWN TO
SUBFLOOR
DOWN TO
SUBFLOOR
321 322
342 341
343 344
22'-10"
30'-10"
THIS SPACE IS AN OLD BATTERY ROOM THAT IS
NO LONGER USED FOR BATTERY STORAGE.
THE INERGEN SYSTEM WILL PROTECT THIS
ROOM AS PART OF THE "Z2" DISCHARGE,
HOWEVER, THERE WILL NO DETECTION ADDED
TO THIS SPACE AS IT CURRENTLY HOUSES
EXPLOSION PROOF ELECTRICAL EQUIPMENT
AND THE E.P. INTEGRITY OF THE ROOM IS TO BE
KEPT IN TACT.
FRM-1 M007 - DISCHARGE RELAY FOR MONITORING
FRM-1 M008 - Z3 RELAY FOR DOOR HOLD OPEN IN OFFICES
(1.2)41/4
A hanger shall be installed within 1ft.
(.3 m) of each nozzle.
1 1/2 and larger 1 1/4
2.
3/4 1/2
(3.7) (4.6)
(2.4) (3.7)
(1.8)
Maximum Spacing
Install the pipe hangers in accordance with good piping
The maximum spacing between hangers must not
Hanger Applications practice as well as the following.
exceed those listed below.
in. NPT Pipe Size
1.
Between Hangers
ft. (m)
AS-BUILT DRAWINGS
DRAWING STATUS
1-800-444-8719
VANGUARD
N O F
SH
EETDRAWN BY:
SCALE:
DATE:
CONTRACT NO.:
SIGNATURE:
DESCRIPTION APPD
FIRMFIRMFIRM
CHKDDRNDATEREV.
PH: (616) 245-8719 FAX: (616) 245-7541
CONTRACTOR:
JOB:
GRAND RAPIDS, MICHIGAN 49509
2101 MARTINDALE AVENUE, S.W.
VANGUARD FIRE AND SECURITY, INC.
8-4-11
AS NOTED
NWL
S/H096
REVIEWED BY:
5500 ARMSTRONG RD.
VA HOSPITAL BUILDING 157
BATTLE CREEK, MI 49037
INREGEN SUPPRESSION SYSTEM HAZARD LAYOUT
HAZARD LAYOUT
1/4"=1'-0
N
6'-0" 1.25"
6'-0" 1.25"
6'-0" 1.25"
6'-0" 1.25" 10'-0"
1.25"
10'-0" 1.25"8'-7
1.25"
9'-0" 1.25"
14'-7 1.25"
2'-8 1"
7'-5 1"
3'-0 1"
4'-6 1"
15'-0 1"
10'-6 1"
2'-0 1"
16'-1 1"
15'-0 1/2"
5'-9 1.25"
5'-9 1.25"
3'-0 1.25"
2'-0 1.25"
2'-0 1.25"1'-6
1.25"
1'-6 1.25"
0-10 1.25" 3'-0
1.25"
10'-2 1.25"
10'-2 1.25"
16'-3 1.25"
14'-1 1.25"
1'-0 1.25"
1'-0 1.25"
0-4 1.25"
2'-6 1.25"
DIRT LEG SEE DETAIL
DIRT LEG SEE DETAIL
DIRT LEG SEE DETAIL
DIRT LEG SEE DETAIL
DIRT LEG SEE DETAIL
DIRT LEG SEE DETAILDIRT LEG SEE DETAIL
DIRT LEG SEE DETAILDIRT LEG SEE DETAIL
DIRT LEG SEE DETAIL
11'-8 1/2"
4'-3 1/2"
9'-0 1/2"
3'-0 1"
3'-0 1"
3'-3 1/2"
6'-0 1"
6'-0 1"
14'-4 1/2"
2'-6 1/2"
1'-0 1/2"
11'-8 1"
2'-3 1"
1'-11 1"
0'-6 1"
2'-0 1/2"
10'-1 1"
0'-6 1"
0'-6 1"
1'-2 1"
0-10 1"
0-10 1.25"
0-10 1.25"
0-10 1.25"
0-10 1.25"
#301
#311 #312
#31313
DIRT LEG SEE DETAIL
DIRT LEG SEE DETAIL
34341
REDUCING COUPLING TO DISTRIBUTION PIPE
1" UNION WITH 1" X 1.25"
1.25" TEE WITH 1.25" X 1" BUSHINGS
HOSE (TYP.)
½"
1" 3000# TEE WITH 1" X 12" BUSHING FOR
HOSE CONNECTION (TYPICAL)
1'-0" 1"
0'-6" 1"
HOSE (TYP.)
½"
PIPE BETWEEN SELECTOR VALVES AND ORIFICE UNIONS SHALL BE SCHEDULE 80 THREADED
PIPE DOWNSTREAM OF SELECTOR VALVES & ORIFICE UNIONS SHALL BE SCHEDULE 40 THREADED
PIPE UPSTREAM OF SELECTOR VALVES & ORIFICE UNIONS SHALL BE SCHEDULE 80 THREADED
3000# CLASS FITTINGS SHALL BE USED WHERE SCHEDULE 80 PIPE IS REQUIRED
MINIMUM 300# CLASS FITTINGS SHALL SHALL BE USED WITH SCHEDULE 40 PIPE
JOB SPECIFIC PIPING NOTES:
ALL PIPE RUNS ARE SHOWN DIAGRAMICALLY.
PIPE RUN LENGTHS HAVE BEEN ESTIMATED FOR THE CALCULATION PROGRAM.
PIPE RUN ESTIMATIONS HAVE BEEN ENTERED INTO THE CALCULATION PROGRAM TO DETERMINE PIPE SIZES AND FLOW RATES.
CALCULATED PIPE SIZES MAY NOT BE CHANGED.
PIPE SIZE LABELS DENOTE PIPE SIZES FROM NODE TO NODE.
FIELD ADJUSTMENTS TO PIPE RUNS MAY BE MADE AS NEEDED.
FITTINGS ON CALCULATIONS ARE APPROXIMATE.
FITTINGS MAY BE ADDED AS NEEDED.
TEE SPLITS SHOWN SHALL RETAIN THEIR ORIENTATION. I.E. SIDE TEE, THRU TEE, BULL TEE PIPE SIZE REDUCTIONS MAY BE ACHIEVED BY THE USE OF REDUCING BUSHINGS OR REDUCING COUPLINGS.
THE "H" PATTERN PIPING IN THE CEILING OF THE MAIN SERVER ROOM IS TO BE BALANCED.
1'-0" 1"
1'-0" 1"
0'-6" 1"
0'-6" 1"
1'-0" 1"
1'-0" 1"
1'-0" 1"
1'-0" 1"
1'-0" 1"
1'-0" 1"
1'-0" 1" 1'-6"
1"
0'-6" 1"
1.25" 3000# TEE WITH 1.25" X 1" BUSHING
FOR HOSE CONNECTION (TYPICAL)
0'-6" 1"
0'-6" 1"
0'-6" 1"
1'-0" 1"
1'-0" 1"
1'-0" 1"
Z3
Z2
Z1
1" 90° WITH 1" X 1/2" BUSHING
Z3
1" 3000# EL WITH 1" X 12" BUSHING FOR
HOSE CONNECTION (TYPICAL)
1.25" S80 NIPPLE TO ORIFICE UNION
SECURE TANKS WITH ALL THREAD ROD
CYLINDER BRACKETING DETAIL
BOLT TO UPRIGHT AT 38½" A.F.F.
CYLINDER BACKFRAME -CYLINDER W/CV-98 VALVE
22 TOTAL
N.T.S.
WELD TO UPRIGHT
BRACKET FOOT -
UPRIGHT
UPRIGHT
WEIGH RAIL SUPPORT -
WELD TO UPRIGHT
BOLT TO BACK FRAME
WITH ALL THREAD ROD
CYLINDER CLAMP -
MANIFOLDS
6'-10 1/2"
6'-7"
2'-10"
SECOND ROW OF TANKS
CYLINDER BRACKET FOR 3RD ROW OF TANKS
3/8"x1" BOLT BETWEEN TANKS
SPRING NUT
UNISTRUT TO HOLD TANKS
ALL THREAD ROD BETWEEN TANKS
NUT AND WASHER
MANIFOLD DETAIL
N.T.S.
2" 3 1/2"
1'
1'-1"
1'-3"1' 1' 1' 1' 1'
UP TO SYSTEM PIPE
UP TO SYSTEM PIPE
UP TO SYSTEM PIPE
UP TO SYSTEM PIPE
9 1/2"
AS-BUILT DRAWINGS
DRAWING STATUS
1-800-444-8719
VANGUARD
N O F
SH
EETDRAWN BY:
SCALE:
DATE:
CONTRACT NO.:
SIGNATURE:
DESCRIPTION APPD
FIRMFIRMFIRM
CHKDDRNDATEREV.
PH: (616) 245-8719 FAX: (616) 245-7541
CONTRACTOR:
JOB:
GRAND RAPIDS, MICHIGAN 49509
2101 MARTINDALE AVENUE, S.W.
VANGUARD FIRE AND SECURITY, INC.
8-4-11
AS NOTED
NWL
S/H096
REVIEWED BY:
ILLUSTRATIONS BELOW SHOW METHODS OF CONNECTING PIPE.
ILLUSTRATIONS BELOW SHOW ACCEPTABLE METHODS OF SPLITTING TEES
LENGTH REQUIRED
NO MINIMUM
BULL TEE
INCOMING
THRU TEE
INCOMING
LENGTH REQUIRED
NO MINIMUM
THRU SIDE
NO MINIMUM
LENGTH REQUIRED
tribution piping network(s) depicted herein shall be carefully cut, reamed and blown clear. Furthermore, each shall be internally cleaned and swabbed before final assembly.
All agent distribution piping sections shall be free of particulate matter and cutting oil residue before the installation of INERGEN shall be field-measured from center of fitting to center of of at least two (2) inches in total length.
each INERGEN Agent discharge nozzle. All dead-end piping
Inergen Agent storage cylinders and agent distribution piping related component parts shall be located and/or installed as shall be approved in advance by the system designer.
system hydraulic performance. Deviations and/or alterations deviations from the intended design installation could effect close to depicted location as is possible. Alterations and/or distribution piping network components as depicted herein.
assembly. Each shall consist of a pipe tee and a capped nipple
All INERGEN Agent fire suppression system items, materials and system installer(s) to correctly measure and assemble all agent all accuracy. It shall be the responsibility of the INERGEN Agent fitting. Dimensions shown shall be field-verified to ensure over-
All pipe fitting dimensions depicted within this installation drawing sections shall include the installation of an acceptable dirt-trap network components shall be securely bracketed, particularly at
Agent discharge nozzles and/or pneumatically operated devices.
11.
9.
10.
8.
type materials.
fittings shall be employed for larger sizes. Flanged joint type
All pipe fittings employed to construct the agent cylinder forged steel conforming to ANSI B16.11 standards.
connections shall be made using a minimum of class 600 Lb.
iron threaded fittings through 3.0" diameter. Forged steel pipe a minimum, 300 Lb. ANSI B16.3 black or galvanized malleable All pipe fittings beyond the Orifice Union Assembly shall be, as
Union Assembly, shall be black or galvanized 2000 or 3000 Lb.
manifold assembly, including those fittings ahead of the Orifice
Protection. All pipe sections associated with the agent dis- The use of Teflon joint tape is recommended by ANSUL Fire
6.
7.
5.
SCHEDULE AND SIZE
the following types, sizes and specified grades.
Orifice Union Assembly, shall be black or galvanized steel of assembly, including all agent distribution piping ahead of the All threaded pipe used to construct each cylinder manifold
A106 SEAMLESS, GRADE A
A106 SEAMLESS, GRADE B
A106 SEAMLESS, GRADE C
A53 ERW, GRADE B
A53 ERW, GRADE A
A106 SEAMLESS, GRADE A
A106 SEAMLESS, GRADE B
A106 SEAMLESS, GRADE C
4.
SCHED 80 Thru .75" SCHED 80 Thru 1.0" SCHED 80 Thru .50"
SCHEDULE AND SIZE
SCHED 80 Thru 2.5" SCHED 80 Thru 1.25"
SCHED 40 Thru 2.5" SCHED 40 Thru 5.0" SCHED 40 Thru 8.0"
SCHED 40 Thru 3.0" SCHED 40 Thru 1.25"
MECHANICAL INSTALLATION NOTES
Fire Protection, and NFPA 2001, 1994, "Clean Agent Fire accordance with the National Electric Code, 1993 edition.
materials and related components shall be installed in strict
The completed installation shall meet or exceed the specified performed in accordance with the ANSUL Inergen Systems System(s) depicted within these installation drawings shall be to facilitate this installation. All threaded pipe beyond the the following types, sizes and specified grades.
Orifice Union Assembly shall be black or galvanized steel of type pipe and related components shall NOT be used
Agent distribution piping components shall conform to ASTM
The installation of the ANSUL Inergen Agent Fire Suppression requirements of the Local Authority Having Jurisdiction, ANSUL
Extinguishing Systems." Electronic detection and control items, specifications for A106 pipe and related materials. A120 / A53
Design, Installation, Recharge and Maintenance Manual. ANSUL
3.
2.
1.
5500 ARMSTRONG RD.
VA HOSPITAL BUILDING 157
BATTLE CREEK, MI 49037
INREGEN SUPPRESSION SYSTEM HAZARD LAYOUT
PIPING LAYOUT ISOMETRIC
1/4"=1'-0
MANIFOLD LAYOUT ISOMETRIC
1"=1'-0
| Sheets and Views |
| BATTLE CREEK VA HOSPITAL S-H096 inergen as-built-DEMO COVER |
| BATTLE CREEK VA HOSPITAL S-H096 inergen as-built-2 |
| BATTLE CREEK VA HOSPITAL S-H096 inergen as-built-3 |
| BATTLE CREEK VA HOSPITAL S-H096 inergen as-built-4 |
| BATTLE CREEK VA HOSPITAL S-H096 inergen as-built-5 |
File details come from the government source that posted it. Updated .