Xtreme Power Conversion UPS M90C-2S-flyer.pdf
PDF 1 MB Posted
- Solicitation number
- 36C77623R0101
About this file
This document contains a product flyer for an uninterruptible power supply system and related federal contract opportunity. The flyer describes the Xtreme Power Conversion M90C-2S modular three-phase UPS system, including its 5kW or 8kW capacity, 98% efficiency, hardwired or plug configurations, LCD display, and 2-year warranty. Product options include a maintenance bypass, output receptacles, and rack or tower mounting.
The related federal contract opportunity is for the Department of Veterans Affairs Technology Acquisition Center Austin to upgrade EHRM infrastructure at the Battle Creek VA medical center. The solicitation number is 36C77623R0101 and opportunity type is a solicitation. The closing date and other contractual details are not provided in this document.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Protect your business.
XTREME POWER CONVERSION M90C-2S
2 Slot Online UPS // 208/120VAC Three-Phase
› Capacity: 5kW or 8kW › Up to 98% ECO mode or 93% online efficiency › Unity output power factor › Hardwired or Plug and Receptacle configurations › 2 year warranty (USA and Canada)
Maintenance bypass— Simplifies UPS repair or re-placement and reduces costly downtime
Optional receptacle panel— configure with L21-20R or L21-30R output receptacles
Reduce energy cost— best-in-class energy efficiency provides lowest energy consumption and heat output
$50,000 load protection policy—offers protection against damaged connected equipment
Rack or tower mount— rail kits or caster base configurations available
LCD display—LCD display of power metering for individual phases and system summary
Line cord— optional input cord set simpli-fies field installation
FEATURES
Modular Three Phase UPS for Continuous Power Availability
Xtreme Power M90C UPS is a modular, flexible solution that combines continuous power availability and the highest efficiency for mission critical applications.
M90C provides unity power factor output providing maximum usable power and avoids any need to over-size the UPS. Maintenance bypass and output distri-bution within the UPS frame eliminates the need for external component connections, reducing installation costs.
The flexible M90C-2S easily mounts into a standard 19” rack or installs as a tower with a caster base. Line cord, and output receptacles can be customized to meet your specific needs.
PRODUCT SNAPSHOT
For a 6 slot enclosure reference at www.xpcc.com/m90c-6s
For more information, visit www.xpcc.com/M90c-2s
XPC USA / Denver, CO / sales@xpcc.com XPC EMEA / Rotterdam, NL / emea@xpcc.com www.xpcc.com
©2023 Xtreme Power Conversion Corporation. All Rights Reserved. M90C.01U (1/19/23)
Protect your business.
MODEL SELECTION GUIDE
MODEL NUMBER M90C-2S5K M90C-2S8K
CAPACITY Power Rating 5kVA/5kW 8kVA/8kW INPUT Voltage/frequency nominal 120/208V, 50/60Hz auto-sensing (3PH+N+G)
Voltage/frequency range 152-269VAC* (L-L) / 40–70Hz OUTPUT Voltage / Frequency 120/208V, 50/60Hz ± 0.1Hz; (3PH+N)
THD (full load) ≤2% (Linear load); ≤3% (Non linear load) Efficiency Up to 98% ECO mode, 93% online mode Overload capacity 100% - 110% for 30 min; 110% - 130% for 5min; 130% - 150% for 10s; > 150% for 200ms
BATTERY SYSTEM Nominal voltage +/-96Vdc or +/-120Vdc (+/-96Vdc default) Max charging (adjustable) 4A
MODULE DIMENSIONS Power module 16.3”W x 24” D x 5.2”H / 38 lbs & WEIGHT Battery module 16.3”W x 24”D x 5.2”H / 107 lbs SYSTEM ENCLOSURE M90C-2S enclosure 17.3”W x 31.5”D x 10.5”H (6U) / 34 lbs
Input connections Terminal blocks or L21-20P line cord Terminal blocks or L21-30P line cord Output connections Terminal blocks or optional output receptacles
ENVIRONMENT Temperature 0–40°C (32–104°F) Altitude 5,200 ft above sea level Audible noise < 58dBA at 1m
APPROVALS UL-1778, cUL, FCC A, RoHS WARRANTY 2 year warranty (USA and Canada) COMMUNICATIONS INTERFACE RS-232, USB, EPO, intelligent slot for optional cards (Web/SNMP, Relay, Modbus) INCLUDED IN BOX User manual, USB cable, R2-232 cable, ViewPower Software
AVAILABLE OPTIONS L21-20P or L21-30P line cord, receptacle panel, extended battery cabinet, caster base, 5 year extended warranty, 4-post rail kit
*Depending on load level
BATTERY RUNTIMES
Runtimes are shown in minutes and will vary based on battery age and site conditions. Maximum 8 battery modules per UPS power module.
M90C-2S front view
Modular Design back plane connector for ease of installation and maintenance of UPS and Battery modules
Receptacle Panels
M90C-RPI (1) L21-20R and breaker
M90C-RPJ (1) L21-30R and breaker
For more information, visit www.xpcc.com/m90c-2s
Maximum of 1 receptacle panel per enclosure
Load (kW) 1kW 2kW 3kW 4kW 5kW 6kW 7kW 8kW
M90C-2S5K 85 38 22 15 12 - - - M90C-2S8K 85 38 22 15 12 9 7 6
Maintenance Bypass
Optional Receptacle Panel
Input breaker Output breaker
M90C-2S rear view
File details come from the government source that posted it. Updated .