Xtreme Power Conversion UPS M90C-2S-flyer.pdf

PDF 1 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction Battle Creek (VA-23-00019147)
Solicitation number
36C77623R0101
Issued by

About this file

This document contains a product flyer for an uninterruptible power supply system and related federal contract opportunity. The flyer describes the Xtreme Power Conversion M90C-2S modular three-phase UPS system, including its 5kW or 8kW capacity, 98% efficiency, hardwired or plug configurations, LCD display, and 2-year warranty. Product options include a maintenance bypass, output receptacles, and rack or tower mounting.

The related federal contract opportunity is for the Department of Veterans Affairs Technology Acquisition Center Austin to upgrade EHRM infrastructure at the Battle Creek VA medical center. The solicitation number is 36C77623R0101 and opportunity type is a solicitation. The closing date and other contractual details are not provided in this document.

View the file

Other files

File Type Posted
Campus Map - EHRM.pdf PDF
Battle Creek EHRM Infrastructure Upgrades Construction - Technical Questions.docx DOCX document
36C77623R0101 0002.docx DOCX document
36C77623R0101 0001.docx DOCX document
515-21-701 Pre-Bid Site Visit Sign-in Sheet.pdf PDF
Attachment 14- 515-21-701_BATTLE_CREEK-EHRM_FINAL_BID_DOCUMENTS-VOLUME_7.zip ZIP file
Attachment 9- 515-21-701_BATTLE_CREEK-EHRM_FINAL_BID_DOCUMENTS-VOLUME_2.zip ZIP file
Attachment 7- 515-21-701 B157 Inergen Supplimental dwg.pdf PDF
Attachment 1- Contractor Safety - Environmental Form.docx DOCX document
Attachment 8- 515-21-701_BATTLE_CREEK-EHRM_FINAL_BID_DOCUMENTS-VOLUME_1.zip ZIP file
Attachment 4 -Site Visit Instructions 02.docx DOCX document
Attachment 5 - 515-21-701_FINAL_BID_SPECS_VOL_1 - Rev.2_ 7-21-23.pdf PDF
Attachment 3 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 2 - 515-21-701 Brand Name Item Log.xlsx XLSX spreadsheet
Attachment 10- 515-21-701_BATTLE_CREEK-EHRM_FINAL_BID_DOCUMENTS-VOLUME_3.zip ZIP file
Attachment 11 -515-21-701_BATTLE_CREEK-EHRM_FINAL_BID_DOCUMENTS-VOLUME_4.pdf PDF
Attachment 15 - DB Wage Determination Battle Creek.pdf PDF
36C77623R0101_1.docx DOCX document
Attachment 12 - 515-21-701_BATTLE_CREEK-EHRM_FINAL_BID_DOCUMENTS-VOLUME_5.pdf PDF
Attachment 13- 515-21-701_BATTLE_CREEK-EHRM_FINAL_BID_DOCUMENTS-VOLUME_6.zip ZIP file
Attachment 6 - 515-21-701_FINAL_BID_SPECS_VOL_2.pdf PDF
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Protect your business.

XTREME POWER CONVERSION M90C-2S

2 Slot Online UPS // 208/120VAC Three-Phase

› Capacity: 5kW or 8kW › Up to 98% ECO mode or 93% online efficiency › Unity output power factor › Hardwired or Plug and Receptacle configurations › 2 year warranty (USA and Canada)

Maintenance bypass— Simplifies UPS repair or re-placement and reduces costly downtime

Optional receptacle panel— configure with L21-20R or L21-30R output receptacles

Reduce energy cost— best-in-class energy efficiency provides lowest energy consumption and heat output

$50,000 load protection policy—offers protection against damaged connected equipment

Rack or tower mount— rail kits or caster base configurations available

LCD display—LCD display of power metering for individual phases and system summary

Line cord— optional input cord set simpli-fies field installation

FEATURES

Modular Three Phase UPS for Continuous Power Availability

Xtreme Power M90C UPS is a modular, flexible solution that combines continuous power availability and the highest efficiency for mission critical applications.

M90C provides unity power factor output providing maximum usable power and avoids any need to over-size the UPS. Maintenance bypass and output distri-bution within the UPS frame eliminates the need for external component connections, reducing installation costs.

The flexible M90C-2S easily mounts into a standard 19” rack or installs as a tower with a caster base. Line cord, and output receptacles can be customized to meet your specific needs.

PRODUCT SNAPSHOT

For a 6 slot enclosure reference at www.xpcc.com/m90c-6s

For more information, visit www.xpcc.com/M90c-2s

XPC USA / Denver, CO / sales@xpcc.com XPC EMEA / Rotterdam, NL / emea@xpcc.com www.xpcc.com

©2023 Xtreme Power Conversion Corporation. All Rights Reserved. M90C.01U (1/19/23)

Protect your business.

MODEL SELECTION GUIDE

MODEL NUMBER M90C-2S5K M90C-2S8K

CAPACITY Power Rating 5kVA/5kW 8kVA/8kW INPUT Voltage/frequency nominal 120/208V, 50/60Hz auto-sensing (3PH+N+G)

Voltage/frequency range 152-269VAC* (L-L) / 40–70Hz OUTPUT Voltage / Frequency 120/208V, 50/60Hz ± 0.1Hz; (3PH+N)

THD (full load) ≤2% (Linear load); ≤3% (Non linear load) Efficiency Up to 98% ECO mode, 93% online mode Overload capacity 100% - 110% for 30 min; 110% - 130% for 5min; 130% - 150% for 10s; > 150% for 200ms

BATTERY SYSTEM Nominal voltage +/-96Vdc or +/-120Vdc (+/-96Vdc default) Max charging (adjustable) 4A

MODULE DIMENSIONS Power module 16.3”W x 24” D x 5.2”H / 38 lbs & WEIGHT Battery module 16.3”W x 24”D x 5.2”H / 107 lbs SYSTEM ENCLOSURE M90C-2S enclosure 17.3”W x 31.5”D x 10.5”H (6U) / 34 lbs

Input connections Terminal blocks or L21-20P line cord Terminal blocks or L21-30P line cord Output connections Terminal blocks or optional output receptacles

ENVIRONMENT Temperature 0–40°C (32–104°F) Altitude 5,200 ft above sea level Audible noise < 58dBA at 1m

APPROVALS UL-1778, cUL, FCC A, RoHS WARRANTY 2 year warranty (USA and Canada) COMMUNICATIONS INTERFACE RS-232, USB, EPO, intelligent slot for optional cards (Web/SNMP, Relay, Modbus) INCLUDED IN BOX User manual, USB cable, R2-232 cable, ViewPower Software

AVAILABLE OPTIONS L21-20P or L21-30P line cord, receptacle panel, extended battery cabinet, caster base, 5 year extended warranty, 4-post rail kit

*Depending on load level

BATTERY RUNTIMES

Runtimes are shown in minutes and will vary based on battery age and site conditions. Maximum 8 battery modules per UPS power module.

M90C-2S front view

Modular Design back plane connector for ease of installation and maintenance of UPS and Battery modules

Receptacle Panels

M90C-RPI (1) L21-20R and breaker

M90C-RPJ (1) L21-30R and breaker

For more information, visit www.xpcc.com/m90c-2s

Maximum of 1 receptacle panel per enclosure

Load (kW) 1kW 2kW 3kW 4kW 5kW 6kW 7kW 8kW

M90C-2S5K 85 38 22 15 12 - - - M90C-2S8K 85 38 22 15 12 9 7 6

Maintenance Bypass

Optional Receptacle Panel

Input breaker Output breaker

M90C-2S rear view