This Pre-Construction Risk Assessment details a VA mechanical systems upgrade project for Building 1, Floor 2 Imaging, Floor 3 Mech Penthouse, and Floor 5 ICU. The project is scheduled to start on 12/31/2025 with an estimated duration of 1 year (Project Number 668-22-105). Key risks and mitigation strategies include: short-duration HVAC outages coordinated after hours/on weekends, crane placement near the ambulance entrance causing a temporary loop closure, and a HAZMAT survey revealing asbestos-containing material (ACM) in the A524 Mechanical Room that will require specialized abatement. Additionally, the project will require an Infection Control Risk Assessment (ICRA), potential patient flow disruption due to construction fencing, and may necessitate an Interim Bed (IB) reduction. Safety considerations include hot work permits, potential confined space work, and maintaining fire and life safety system integrity throughout construction.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R e v 6 P a g e 1 | 3
Pre-Construction Risk Assessment Project Number and Name: Planned Project Start Date:
Location of Construction: Estimated Duration:
Safety/Life Safety Risk Assessment-Safety officer should be involved in the design/planning of all projects
Y N 1. FIRE AND LIFE SAFETY IMPACTS
a. Will egress routes and exit signage from occupied areas remain unchanged? If no, ILSM is needed.
b. Will exit stairs remain unobstructed with appropriate fire protection? If no, ILSM is needed.
c. Will fire & smoke compartments remain intact & unchanged? If no, ILSM is needed.
d. Will fire alarm and detection systems remain functional & unimpaired; outages
<4 hours? If no, ILSM is needed.
e. Will fire suppression systems remain functional & unimpaired; outages <10 hours? If no, ILSM is needed.
f. Will construction area be separated by solid non-combustible smoke tight partitions? If no, ILSM is needed.
g. Will emergency access by Fire Department remain unobstructed? If no, ILSM is needed.
h. Will hot work be performed? If yes, submit hot work permit to Safety
2. SAFETY
a. Will a confined space work permit be required? If yes, submit permit
b. Will the project introduce other significant hazards? If yes, describe below
Additional Requirements and Description of Mitigation:
Construction Safety Specialist / Safety Specialist Signature: Date:
Y N 3. PHYSICAL SECURITY IMPACTS
a. Will the construction compromise security? If yes, describe necessary mitigation below
b. Will construction affect traffic control or cause road closures?
c. Do badging requirements exceed non-PIV level?
Additional Requirements and Description of Mitigation:
VA Police Signature: Date:
R e v 6 P a g e 2 | 3
Y N 4. CONTRACT COMPLIANCE
a. Will contract clauses be included for enforcement of identified risks? If no, describe necessary mitigation below
Y N 5. CONSTRUCTION ACTIVITY
a. Will there be any anticipated utility shutdowns? (Communications, electrical, heating/cooling, HVAC, medical gases, vacuum, water, sewer) If yes, describe necessary mitigation below and consider impact memo
b. Will there be nuisance noise levels for adjacent areas? If yes, describe necessary mitigation below
c. Will vibration levels affect operations of sensitive medical equipment? If yes, describe necessary mitigation below
d. Will construction require trenching?
e. Will radiographic examination be required of piping or structural steel? If yes, contact RPO
f. Will construction affect traffic control or cause road closures?
g. Will this contract complete work with a biological area such as a lab? If yes, Facility Specific Training required.
Additional Requirements and Description of Mitigation:
Project Manager Signature: Date:
Y N 6. ENVIRONMENTAL
a. Will the project require a NEPA assessment above a CATEX? Contact GEMS for a determination. CATEX #: If yes, submit draft NEPA to GEMS
b. Will the project require a permit from the Air Quality District? Contact GEMS for a determination. If yes, submit draft to GEMS
c. Will this project require a storm water permit? Contact GEMS for a determination. If yes, submit draft to GEMS
Y N 7. HAZARDOUS MATERIALS
a. Will this contract disturb known asbestos containing material (ACM)? Contact
Safety for a determination. If yes, describe necessary intervention:
b. Will contract require the use of hazardous chemicals? If yes, review by facility IH is required
GEMS Signature: Date:
R e v 6 P a g e 3 | 3
Y N 8. INFECTION CONTROL
a. Will this contract require an Infection Control Risk Assessment? If yes, ICRA shall be completed prior to construction start.
Additional Requirements and Description of Mitigation:
Infection Control Representative Signature: Date:
Y N 9. PATIENT SAFETY
a. Will project require additional monitoring for patient safety?
b. Will construction affect patient access?
c. Will patients need relocation during construction?
Patient Safety Signature: Date:
| Project Number and Name: 668-22-105 Upgrade Mechanical Systems AHU 9&15 | |
| Planned Project Start Date: 12/31/2025 | |
| Estimated Duration: 1 year | |
| Date: 11/27/2024 | |
| Date_2: 11/27/2024 | |
| Date_3: 11/27/2024 | |
| Date_4: 11/29/2024 | |
| Date_5: | |
| Date_6: | |
| Location of Construction: Building 1, Floor 2 Imaging, Floor 3 Mech Penthouse, Floor 5 ICU | |
| 2024-11-27T07:51:31-0800 | |
| KEVIN SCOTT |
| 2024-11-27T10:04:14-0800 | |
| KENNETH KESTI |
| 2024-11-29T07:20:14-0800 | |
| JEREMI MILLER |
| 2024-12-04T14:02:47-0800 | |
| JESUS ORDAZ |
| 2024-12-10T09:32:28-0800 | |
| STACY DANCKER |
| 2024-11-27T09:52:04-0800 | |
| TIMOTHY BELLUS |
| 2b: N |
| 2a: N |
| 1h: Y |
| 1g: N |
| 1e: Y |
| 1d: Y |
| 1c: Y |
| 1b: Y |
| 1f: Y |
| 1a: Y |
| 3a: N |
| 3b: Y |
| 3c: N |
| 4a: Y |
| 5a: Y |
| 5b: N |
| 5c: N |
| 5d: N |
| 5e: N |
| 5f: Y |
| 5g: N |
| 6a: N |
| 6b: N |
| 6c: N |
| 7a: Y |
| 7b: N |
| 8a: Y |
| 9a: N |
| 9b: Y |
| 9c: N |
| Additional Requirements and Description of Mitigation_Fire Life Safety: 1g. Crane placement may impact SFD access. Re-evaluate at time of use. |
1h. Submit hot work permit to Safety prior to performing hot work.
| Additional Requirements and Description of Mitigation_Physical Security Impacts: 3b. A crane will be used to lift the new air handlers will be located near the ambulance entrance, causing a temporary closure of the loop. |
| Additional Requirements and Description of Mitigation_Contract Compliance & Construction Activity: 5a. Short duration HVAC outages required in order to hook up temporary HVAC units. Outages will be coordinated to take place after hours/on weekends. |
5f. A crane will lift both the temporary AHU and the new AHUs to their locations. The crane will be placed near the ambulance entrance causing a temporary closure of the loop.
| Additional Requirements and Description of Mitigation_Environmental & Hazardous Materials: 7a. HAZMAT survey was performed by the A/E and ACM flooring was found in A524 Mechanical Room. Construction contractor will hire a qualified ACM abatement team to remediate the room before construction. |
| Additional Requirements and Description of Mitigation_Infection Control: ICRA completed |
| Additional Requirements and Description of Mitigation_Patient Safety: 9b. A crane will be located near the front entry and a construction fence will be put up around the work zone. Depending on where the contractor chooses to place the crane, this may affect patient flow to the main entry to some degree. Contractor will be required to submit a Crane Lift Plan prior to lifting air handlers. |
9c. Potential IB needed for reduction of available beds.
CATEX #: