This document is a fire inspection checklist and code summary guide for hotel occupancies used by fire inspection personnel to identify general fire and life safety hazards and code compliance requirements.

The checklist is organized into twelve major categories: Exterior (fire lanes, address visibility, hydrants, combustible storage, key boxes, connections, gas piping, and dumpster placement); Exit Features/Means of Egress (adequate exits, second means of egress from sleeping rooms, obstruction-free paths, door operation, exit signs, emergency lighting, interior finish, and corridor ratings); Construction Features (fire-rated construction, separated/sprinklered incidental use areas, operational fire doors, and protected vertical openings); Storage (orderly storage, prohibited combustible storage in electrical rooms, attic storage, clearance maintenance, and rubbish disposal); Flammable/Combustible Liquids (safety containers, distance from exits, ignition sources, quantities, basement storage, and ventilation); Fire Extinguishers (accessibility, travel distance, and annual testing); Hazardous Materials (secured cylinders, labeling, acceptable quantities, and material separation); Utility/Mechanical/HVAC (shut-off valves, approved piping, combustion air supply, clearances, and hood duct cleanliness); Sprinkler Systems (coverage, controls, locked valves, supervision, head condition, tools, testing, and labeling); Fire Alarm & Detection Systems (panel condition, detector installation, annual testing, single-station smoke detectors, and required system installation); Other Fire Protection Systems (standpipes, hood systems); and Electrical (hazards, appliance condition, overcurrent protection, cord usage, and panel access).

The code summary section provides occupant load factors, egress feature requirements differentiated between unsprinklered and sprinklered conditions, and specific thresholds for when second, third, and fourth exits are required. Sprinkler system requirements apply to Group R fire areas exceeding three stories or combined floor areas exceeding 9,250 square feet. Fire alarm system and detection requirements vary based on whether the building is new or existing, with specific thresholds involving guest room count and building height, and automatic detection mandated in mechanical and storage areas plus common areas and corridors serving as required means of egress.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

This checklist is intended as a guide to assist fire inspection personnel in identifying general fire and life safety hazards, other possible code requirements may apply. Please refer to other checklists for information on certain occupancies/topics.

INSPECTION CHECKLIST

Hotel Occupancies

Y = Meets Requirements; N= Does Not Meet Requirements Y N Y N

EXTERIOR:

Fire Lanes marked/unobstructed (IFC 503.3, 503.4) Address visible (IFC 505.1) Fire hydrants/water supply accessible (IFC 508) Combustible accumulations/storage acceptable

(IFC 304.2, IFC 315.3)

F.D. key box present/maintained (IFC 506) F.D. connections visible/maintained (IFC 912) Gas meter/piping protected against impact

(IFC 312, 603.9)

Dumpsters are outside and 5 ft. or more from combustible walls, openings or combustible roof eave lines. (IFC 304.3.3)

EXIT FEATURES/MEANS OF EGRESS:

Adequate number of exits

(IFC 1004.4, 1015, 1019, 1027.23)

Second means of egress from sleeping rooms

(IFC 1026)

Exits, aisles, & corridors free of obstructions

(IFC 1028.3)

Exit doors open from inside (IFC 1008.1.8) Exit signs present (IFC 1011, 1027.3) Emergency lighting present & operational

(IFC 1006, 1027.5)

Interior finish acceptable (IFC 803, 804) Exit corridors rated (IFC 1017.1, 1027.17.1)

CONSTRUCTION FEATURES:

Fire rated construction present/maintained

(IFC 703.1)

Incidental use areas separated/sprinklered

(IFC 705.3)

Rated fire doors operational (IFC 703.2) Vertical openings protected (IFC 704.2)

STORAGE:

Storage neat and orderly (IFC 315.2) Combustible storage prohibited in electrical equipment rooms, restrictions apply in boiler/mechanical rooms

(IFC 315.2.3)

Attic storage (IFC 315.2.4) Storage maintained [2’ below ceiling un-sprinklered, 18” sprinklered] (IFC 315.2.1) Rubbish/waste subject to spontaneous ignition shall be disposed of daily and in listed container

(IFC 304.3.1)

FLAMMABLE/COMBUSTIBLE LIQUIDS:

Safety containers if used (IFC 3405.2.4) Not stored/kept near exits (IFC 3404.3.3.3) No sources of ignition (IFC 3404.2.4) Quantities >10 gals in cabinet (IFC 3404.3.4.4) No basement storage unless sprinklered

(IFC 3404.3.5.1)

Adequate ventilation (IFC 3405.3.7.5.1)

FIRE EXTINGUISHERS:

Readily accessible (IFC 906.5) Travel distance not exceeded (IFC 906.1, 906.3) Tested/inspected at least annually (IFC 901.6.1)

HAZARDOUS MATERIALS:

Compressed gas cylinders secured (IFC 3003.5) Rooms/areas properly labeled (IFC 2703.5) Acceptable quantities (IFC 2703.1.1) Separation of incompatible materials (IFC 2703.9.8)

UTILITY/MECHANICAL/HVAC:

Shut off valves present on gas appliances (IFC 603.1) Approved piping, connections & appliances used

(IFC 603.1.2)

Combustion air supply/venting present (IFC 603.1) Adequate clearance between combustibles and appliances (IFC 305.1, 603.5.3) Commercial hood ducts/filters are clean

(IFC 904.11.6.3)

SPRINKLER SYSTEM:

Coverage is adequate (IFC 903.3.1) Controls are readily accessible (IFC 903.3.1) Valves locked open (IFC 903.4.4) System and valves supervised [>20 sprinklers new, ≥ 100 in existing] (IFC 903.4) Heads in good condition (IFC 903.3.1) Wrench/spare sprinklers present (IFC 903.3.1) Tested/inspected at least annually (IFC 901.6.1) Riser/pump rooms labeled (IFC 510.1)

FIRE ALARM & DETECTION SYSTEMS:

Control panel/annunciator panel in normal condition

[no trouble or alarm conditions] (IFC 901.6, 901.7) Detectors properly installed (IFC 907) Tested/inspected at least annually (IFC 907.20) Single station smoke detectors present in each apartment (IFC 907.2.10, 907.3.6) Fire alarm system installed where required

(IFC 907.2.9, 907.3.5)

OTHER FIRE PROTECTION SYSTEMS:

Standpipes needed (IFC 905) Standpipes/hose in good condition (IFC 905.2) Adequate coverage (IFC 905.2) Hood system fuel shutoff present (IFC 904.11.2) Hood system properly maintained/serviced

(IFC 904.11.6)

ELECTRICAL:

No electrical hazards (IFC 605.1, 605.6) Appliances/fixtures in good condition (IFC 605.7) Overcurrent protection present (IFC 605.1) Power taps not used (IFC 605.4) Extension cords not substituted for fixed wiring

(IFC 605.5)

Power strips properly used (IFC 605.4) Access/clearance to electrical panels (IFC 605.3) Electrical Rooms labeled (IFC 605.3.1)

This checklist is intended as a guide to assist fire inspection personnel in identifying general fire and life safety hazards, other possible code requirements may apply. Please refer to other checklists for information on certain occupancies/topics.

CODE SUMMARY

Hotel Occupancies

COMMON OCCUPANT LOAD FACTORS (MSFC 1004.1.1):

Residential Areas 200 sq. ft/person (gross) Assembly (chairs only) 7 sq. ft/person (net) Assembly (tables/chairs) 15 sq. ft/person (net) Exercise Areas 50 sq. ft/person (gross)

Mechanical Areas 300 sq. ft/person (gross) Parking Garages/Areas 200 sq. ft. /person (gross) Storage Areas 300 sq. ft/person (gross)

EGRESS FEATURES: UNSPRINKLERED: SPRINKLERED: REFERENCE SECTION:

Egress Width – Stairs (in./occupant) 0.3 0.2 IFC 1005.1

Egress Width – Other (in./occupant) 0.2 0.15 IFC 1005.1

Common Path of Travel – new (ft.) 75 75 IFC 1014.3

Common Path of Travel – existing (ft.) 75 75 IFC 1027.19

Dead-End Limit – new (ft.) 20 20 IFC 1017.3

Unlimited allowable if length < (2.5 x width)

Dead-End Limit – existing (ft.) 50 50 IFC 1027.17.4

Unlimited allowable if length < (2.5 x width)

Exit Access Travel Distance (ft.) 200 250 IFC 1016.1 – N; 1027.18 – E

Corridor Fire-Rating Req. – new (hr.) Not Allowed 0.5 For > 10 occupants. IFC 1017.1

Corridor Fire-Rating Req. – exist. (hr.) 1 0 For > 10 occupants. IFC 1027.17.1

COMMON OCCUPANT LOAD FACTORS:

2nd Exit Required - more than 10 occupants (IFC 1015.1) OR common path of travel exceeds 75 ft.

(IFC 1015.1) OR all stories above 2nd story (IFC 1019.2) 3rd Exit Required - 501 to 1,000 occupants (IFC 1019.1) 4th Exit required - 1,001 or more occupants (IFC 1019.1)

SPRINKLER SYSTEM REQUIRED (IFC 903.2.7):

Sprinkler protection required for buildings where:

Group R fire area that is more than 3 stories above grade plane OR Combined area on all floors including mezzanines exceeds 9,250 sq. ft.

Sprinklers can be an alternate to fire department access roads and inadequate water supplies.

FIRE ALARM SYSTEM AND DETECTION GENERAL REQUIREMENTS AND WHERE REQUIRED:

Automatic detection is required in boiler rooms, furnace rooms, shops, laundry rooms, mechanical rooms, electrical rooms, trash collection rooms, storage rooms, gift shops, locker rooms and similar areas. Automatic smoke detectors required in all common areas and interior corridors serving as a required means of egress (not required if sprinklered and manual activation provided at constantly attended location).

Activation of fire alarm or fire sprinkler system shall activate a general evacuation system throughout building.

Single station smoke detectors/alarms are required in each guest room but are not to be connected to fire alarm system.

Existing (IFC 907.3.4):

Building contains 20 or more guest rooms (with some exceptions) OR Building is 3 or more stories in height

New (IFC 907.2.8):

All buildings unless:

Building contains 5 or less guest rooms OR Building is 2 stories or less and all guest rooms, attic and crawl spaces are separated from each other and public/common areas by a minimum 1 hour fire partition and all guest rooms have exit to public way, exit court or yard.