This document is a detailed maintenance guidance manual for city gas facilities at a U.S. military base, specifically focused on regulator and volume corrector maintenance procedures. The manual provides comprehensive technical instructions for daily and periodic inspections of gas pressure regulation equipment, including procedures for checking gas leaks, filter maintenance, pressure monitoring, and system diagnostics.
Key technical components include guidance on inspecting direct acting regulators, volume correctors (specifically a JBENERTEK SF-2200H model), and performing routine maintenance tasks such as leak detection, valve checks, and filter replacements. The document specifies technical parameters like pressure ranges (20-70 bar), temperature monitoring (-20 to 50°C), and communication protocols (RS-485, SK Cat M1, LGU+ NBIoT). Maintenance protocols emphasize safety, recommending annual equipment inspections, three-year comprehensive equipment overhauls, and daily visual checks of gas facility components.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
미군부대
도시가스사용시설유지관리기술자료
City-gas Facility Maintenance Guide
목차 (Table of Contents)
1.시설점검주기
Facility Maintenance Cycle
2.메인정압기고장원인,조치방법및관리요령
Main Governor Failure Causes, Measures and Maintenance Guide
3.보정기
Volume Corrector
4.정압기관리요령
Regulator Maintenance Guide
5.가스사용시설일일점검일지
Daily Inspection Log for Gas Usage Facilities
1.시설점검주기 Facility Maintenance Cycle
1.1가스설비점검 Inspection of Gas Facility (KGS FU551 3.3.4)
가스사용시설에설치된압력조정기는매 1년에 1회이상 (필터또는스트레이너의청소는설치
후 3년까지는 1회이상,그이후에는 4년에 1회이상)다음사항에대하여안전점검을실시한다.
The pressure regulator installed in the gas-use facility shall conduct a safety inspection on the following matters at least once a year (cleaning the filter or strainer at least once every three years after installation, and at least once every four years thereafter).
(1)압력조정기의정상작동유무
Whether the pressure regulator is operating normally or not
(2)필터또는스트레이너의청소및손상유무
Whether the filter/strainer is cleaned/damaged or not
(3)압력조정기의몸체및연결부의가스누출유무
Whether there is a gas leak in the body and connection of the pressure regulator
(4)격납상자내부에설치된압력조정기는격납상자의견고한고정여부
Whether the pressure regulator cabinet installed is firmly fixed or not
(5)건축물내부에설치된압력조정기의경우는가스방출구의실외안전장소설치여부
In the case of a pressure regulator installed inside a building, whether the gas outlet is installed in an outdoor safe place
1.2배관설비점검 Inspection of Gas Piping (KGS FU551 3.3.5)
가스사용자는가스사용시설의안전을확보하기위하여그설비의작동상황을 1일 1회이상
점검하고,이상이있을때에는지체없이보수등필요한조치를한다.
In order to ensure the safety of gas-using facilities, users check the operating conditions of the facilities at least once a day, and if there is any malfunction, take necessary measures, such as repair, without delay.
1.3정압기분해점검 Overhaul of Main regulator (KGS FU551 3.3.6)
정압기와필터의경우에는설치후 3년까지는 1회이상,그이후에는 4년에 1회이상분해
점검을실시하고,사고예방설비중도시가스안전확보에필요한시설이나설비는작동상황을
1주일에 1회이상점검하고,이상이있을경우에그시설이나설비가정상적으로작동될수
있도록필요한조치를한다. In the case of main regulator and filters, overhaul shall be performed at least once every three years after installation and at least once every four years thereafter, and during accident prevention work, the operation of facilities or equipment necessary for securing city gas safety shall be checked at least once a week if there is an abnormality, necessary measures are taken so that the facility or equipment can operate normally.
2.메인정압기고장원인,조치방법및관리요령
Main Governor Failure Causes, Measures and Maintenance Guide
2.1정압기고장의대표적증상 Typical Symptoms of Main Governor Failure
: 2차압력의이상상승, 2차압력의이상저하및불규칙(Hunting)및가스누출등
Abnormal rise in secondary pressure, abnormal drop in secondary pressure and irregular (hunting) and gas leakage, etc.
2.2직동식정압기 Direct Acting Regulator
Spring Case Cap 이 열림 Spring Case Cap is opened
닫음 Close
배관내의물이나이물질누적
Accumulation of water or foreign objects in piping
제거 Remove
작동중후단압력이
계속적으로떨림
Continuous shake of back pressure during operation
Regulator 용량 과다 Overcapacity of Regulator
Orifice 교체 Replace Orifice
전단 압력 저하 Front end pressure drops
Filter Element 교체 Replace Filter Element
작동중후단압력이
급속한저하
Rapid drop in back pressure during operation
Regulator 용량 부족 Insufficient regulator capacity
Orifice 교체 Replace Orifice
작동중후단압력이상승
Back pressure rises during operation
Diaphragm 파손 Diaphragm damage
교체 Replace
작동정지중
후단압력이서서히상승
Back pressure rises slowly during downtime
Orifice (Port) 및 disk 손상 혹은 이물질 끼임 Orifice (Port) and Disk damage or foreign objects stuck
분해점검 및 교체 Overhaul and replace
현 상 Symptoms
문 제 점 Issues
조치 방법 Measures
2.2.1 1차압력이상상승Abnormal Rise in First pressure
1)점검방법 Inspection Method
*위순서로확인결과 Check result according to the above order
1)전자압력기록계압력상승: Main Valve밀림
Pressure rise in manometer: Main Valve pushed back
2)전자압력기록계압력일정: Pilot이상
Pressure constant in manometer: Pilot failure
Main Valve및 Pilot점검
Inspection of Main Valve and Pilot
(정확한고장부위확인)
(Identification of accurate failure parts)
* Main Valve밀림상태확인
Check the condition of pushed-back main valve
1)정압기작동중지(모든 Valve닫음)
Stop operating the regulator (Lock all valves)
2)주 Line 2차압측정기구에전자압력기록계설치
Install manometer on the main line secondary pressure measuring device
정압기 Valve만서서히열어전자압력기록계압력상승여부
확인으로Main Valve밀림유무확인
Open only the regulator valve slowly and check whether the main valve is pushed by checking whether the pressure of the manometer is rising.
2차압력
Secondary Pressure
*압력계(혹은 P/T)와 Recorder상에표시된압력을서로대조
Compare the pressure displayed on the pressure gauge (or P/T) and the recorder
*서로다르면원인파악후조치
If the pressure values are different, take action after determining the cause.
기록지점검
Recording paper inspection
* Main Valve밀림
Main Valve is pushed back
*온도상승 Temperature rise
점검항목
Inspection List
조치방법
2)원인별조치방법Measures by causes
Recorder Sensing Line연결 Valve의
잠금으로인한부피팽창으로
Recorder만의압력상승
Recorder's pressure increase due to volume expansion due to locking of the Recorder Sensing Line connection valve
Valve Open혹은불량시교체
Orifice및 Disk손상
Damage to O-Ring and Disk
Pilot
이물질삽입
Insert foreign objects 분해점검및교체
Overhaul and Replace
Double Port Type일경우상하 Port조정
불량및풀어짐
재조정및조임
Adjust and Tighten
Valve Plug모서리부분손상
Damage to the edge of the Valve Plug
O-Ring및 Seal부분손상
Damage to O-Ring and Seal Main Valve
이물질삽입
Insert foreign objects
분해점검및교체
Overhaul and Replace
고장부위
Failure Parts
원인
Causes
조치방법
2.2.1 2차압력이상저하
1)점검방법
Pilot 점검
* Pilot Filter 막힘
* Orifice 막힘
* Diaphragm 파손 및 늘어짐
* Main Valve 와 Pilot 연결관 막힘
* Pilot Spring 상태
Main Valve 점검
* Main Diaphragm 파손 및 늘어짐
* Main Spring 상태
* Relief Valve 상태
1 차 압력 점검
* Filter전단압력측정
* Filter차압점검
2 차 압력 점검 *압력계(혹은 P/T)와 Recorder상에표시된압력을서로대조
*서로다르면원인파악후조치
기록지점검
*압력저하
점검항목 조치방법
2)원인별조치방법
고장 부위 원인 조치방법
정압기 용량 설계용량을초과하여 Gas를
사용할경우 기종변경
Pilot Spring조정불량및 Tension
불량 재조정및교체
Main Valve와 Pilot연결관막힘 분해점검
Diaphragm파손및늘어짐 교체
Orifice막힘 분해점검
Pilot
Pilot Filter막힘 분해점검및 Element교체
Stroke조정불량(Travel Stop) 재조정
Relief Valve불량 분해점검및교체
Main Spring불량 재조정및필요시교체 Main Valve
Main Diaphragm파손및늘어짐 교체
Filter Element막힘 분해점검및 Element교체
1 차 압력
1차측공급압력이설계압력
이하로저하
일시적으로 By-Pass로공급할수있으나
근본적조치필요
2.2.1 3차압력불규칙(Hunting)
1)점검항목
Hunting원인파악
* By-Pass를통하여 Gas를공급하여
1) Hunting멎으면:정압기원인
2) Hunting멎지않으면:정압기외의원인
2차압력점검
*압력계(혹은 P/T)와 Recorder상에표시된압력을서로대조
*서로틀리면원인파악후조치
* Recorder Sensing위치확인
정압기외의원인일경우 *배관내부의물
*정압기부근의환경(철길,도로변,기타진동)
정압기자체의원인일경우
* Stem부분의윤활상태
* Main Diaphragm늘어짐
* Sensing위치및 Sensing Line내의물과이물질
기록지 점검
*압력저하
점검항목 조치방법
2)원인별조치방법
설계용량에비해실제사용량이과도하게
적을경우
기종변경정압기용량
정압기부근의환경(철길,도로변,기타진동) 근본적인검토
정압기외원인 배관내의물체류 제거
Sensing위치부적절(난류발생지점) 위치변경 Main Valve
Sensing Line 내의 물 및 이물질 체류 분해 점검
1차압력이설계시보다승압됨
(Regulator의최대허용차압관계)
Main Spring교체
Main Diaphragm늘어짐 교체 1 차 압력
Stem부분윤활불량 윤활유주입
고장 부위 원인 조치방법
2.3메인정압기구성도
1.입구차단밸브:입구측압력을차단한다 4. 압력기록장치:사용압력을기록한다
2.필터(Filter):이물질을걸러준다 5.출구차단밸브:출구측압력을차단한다
3.정압기:사용압력을일정하게유지시킨다. 6.안전밸브:이상압력발생시가스를방출한다.
2.3.1정압기교체운전및필터청소요령
필터에붙어있는차압계의차압발생시아래와같은
요령으로필터를청소(교체)합니다.
-차압계의게이지가 0.2 Mpa이상을올라가있을시
필터를청소(교체)하여주십시요.
-아래그램과같이정해진순서를반드시지켜주시기
바랍니다.
1)예비라인중압밸브(valve)열기
그림과같이예비라인의전단밸브(중압측밸브)를서서히열어줍니다.
-밸브의급조작시에는높은압력이유입되어정압기를손상시킬수있으므로주의하여주시기
바랍니다.
2)예비라인저압밸브(valve)열기
그림과같이 예비라인의후단밸브(저압측밸브)를서서히열어줍니다.
-밸브의급조작시에는높은압력이유입되어정압기를손상시킬수있으므로주의하여주시기
바랍니다.현재주라인과예비라인으로두방향으로도시가스가흐르고있는상태입니다.
3)필터(Filter)분해점검및 Element교체
필터분해점검 (교체)을하고자하는주라인의전단밸브(중압측밸브)를서서히닫아줍니다.
-밸브의급조작시에는정압기의후단압력의일정치않을수있으므로주의하여주시기바랍니다.
이제예비라인으로도시가스가흐르고있는상태입니다.
필터분해점검(교체)을하고자하는주라인의후단밸브(저압측밸브)를서서히닫아줍니다.이제
주라인으로도시가스가완전히차단된상태입니다.
필터하단의드레인밸브의볼트를풀고밸브를서서히열어필터내의가스를방출시킵니다.
-필터내부에는중압이있으므로드레인밸브를서서히열어줍니다
필터상단의볼트를대각선방향으로풀어줍니다.
필터뚜껑을열고 Element를교체합니다.
(필터청소후역순으로다시조립한후누설검사를시행합니다.)
2.3.2누설점검및밸브점검
2.3.2.1누설점검
-후렌지등접합부위를가스누설검지기또는비눗물을이용하여누설여부를점검합니다.
-도시가스누설시검지기는소리,비눗물검사시는기포가발생합니다.
<검지기를이용한누설점검> <비눗물을이용한누설점검>
2.3.2.2방출관점검
-방출관밸브가열려있는지점검합니다.
-방출관은이상압력발생시도시가스를외부로방출시키는장치이므로
항상열려있어야합니다.
<방출관밸브확인>
2.3.2.3이상압력통보장치점검
하한치의지침과상한치의지침의설정압력을점검하고통보기신호음을점검합니다
사용압력이 70 kpa일경우
상한압력: 85 kpa
하한압력 55 kpa로설정합니다.
2.3.2.4방폭등점검
방폭등스위치를작동시켜방폭등의점등여부를확인합니다.
2.4기타사항
-압력(Pressure)
1차압력: 0.4Mpa (400 Kpa) –군산도시가스에서미군부대로공급되는압력
3.보정기 (Volume Corrector)
3.1보정기개념
공급되는실제가스의상태는표준상태보다높은압력과높은온도로공급됩니다.즉, 기준압력보다높은압력이므로가스는표준상태보다압축되어적은부피를가지게되고, 기준온도보다높은온도이므로가스는표준상태보다팽창되어많은부피를차지하게됩니다.
따라서이러한실제가스의부피를표준상태(0℃, 1Bar)의부피로보정하여주기위하여
실제가스의온도와압력을판매기준(0℃, 2KPa)상태로보정하게되며이러한역할을하는설비가
보정기(Volume Corretor)입니다.
3.2보정기모델
전자식 JBENERTEK CO., LTD SF-2200H
형식 제조사 모델명 비고
3.3보정기설치사진
*제원표
1) General
- Dimension: 180 X 190 X 83(H XW X D)
- Weight: 2.5 kg
- Power: 3.6 VDC 38000mA/h (Lithium battery)
- Display: Graphic LCD
- Communication : RS-485, (무선통신 - Cat M1(SK), NBIoT(LGU+) )
-보호등급 : IP65
-제 1형식가스부피환산장치 (완성형)
2) Pressure
- 1/4 PT 6mm Tube connector
- Range : 20 ~ 70bar(a)*
- Accuracy : 0.25%
3) Temperature
- Range : -20 ~ 50 ‘C
- Type : PT100 Sensor 4wire (Class A)
- Accuracy : 0.5%
4) Communication Type
- Communication : SK Cat M1, LGU+ NBIoT
- Power : 3.6 VDC 38000mA/h ( Lithium battery )
5) RS485 Serial Communication
- Communication : RS-485 serial
- Protocol : Standard Modbus,9600bps, 8bit, None, 1bit(onl
6) Digital Out
- Communication : Open collector NPN
- Pulse width : 10 ~ 100m sec
7) Compressibility : AGA8 GCM2, S-GERG
8) Input pulse :
- LF : Max 2 Hz
- HF : Max 1,000 Hz
9) Memory :
-시간당 Data : 3년이상
- Event : 125개이상
10) Display
한글/영문메뉴
- Vb :표준상태의체적
- Vm :측정상태의체적
- T :가스의온도
- P :가스의압력
- C :보정계수 K :압축비(Z/Zb)등
3.4보정기작동법
4.정압기일일점검및관리요령
(Regulator Daily Inspection and Maintenance Guide)
4.1정압기점검요령
-작동점검
1일 1회일상적인정압기유지관리업무로육안으로작동상태를점검합니다.
-누설점검
가스누설검지기및비눗물을이용하여정압기및부속류연결부위의누설여부를점검하고
상태를기록합니다.
-필터점검및교체
차압계를확인하여이물질이많이발생하였을경우필터를교체합니다.
-정압기분해점검
정압기의안전성을확보하기위하여 3년에 1회이상정압기분해점검을실시하고그결과를
기록보존합니다.
-도색작업
년 1회정압기및도시가스배관에대하여도색작업을실시합니다.
-긴급점검
정압기의긴급한문제점이나조치가어려운점은군산도시가스에연락하고긴급점검을
실시합니다.
4.3정압기필터청소요령
1)필터(Filter)분해점검및 Element교체
필터의분해점검시정압기주라인의후단밸브(저압측밸브)를서서히닫아줍니다.
이제주라인으로도시가스가완전히차단된상태입니다.
필터상단의볼트를풀어줍니다.
필터뚜껑을열고 Element를새제픔으로교체합니다..
(Element 교체후역순으로다시조립한후누설검사를
시행합니다.)
4.4누설점검및밸브점검
4.4.1누설점검
-후렌지등접합부위를가스누설검지기를이용하여누설여부를점검합니다.
-도시가스누설시검지기는소리가발생합니다.
<검지기를이용한누설점검>
4.5기타사항
-압력(Pressure)
2차압력: 70 Kpa (0.07Mpa)-미군부대정압기에서각빌딩조정로공급되는압력
5.가스사용시설일일점검일지 (Daily Inspection Log)
-점검일지의해당사항을점검하고,일일점검일지를작성후보관한다.
도시가스일일점검일지 결 관리원 책임자 총괄자
특 기 사 항
- 기타
- 누설여부
-통풍상태
-보정기작동상태
- GAS METER작동상태
- 조정기후단압력 Kpa
- REGULATER작동상태
- FILTER후단압력 Kpa
조 정 기
- FILTER전단압력 Mpa
- 기타
- 밸브상태
- 배관도색상태
- 노후,손상에누설우려여부
- 연결부위상태
- 고정상태
배 관 및
후 렉 시 블
- 누설여부
- 기타
- 누설여부
- 통풍상태
-보정기작동상태
- GAS METER작동상태
- 정압기후단압력 Kpa
- REGULATER작동상태
- FILTER후단압력 Kpa
정 압 기
- FILTER전단압력 Mpa
점검항목 점검 내용 점검결과 조치 내용
2022년 월 일 요일 ●양호,ⅹ불량, ▲정비요
재
File details come from the government source that posted it. Updated .