Attachment 5 - Asbestos Report dated 20 Feb 26.pdf
PDF 2 MB Posted
- Attached to
- Install New FOC from ITB 910 to ITB 1365
- Solicitation number
- FA488726R0008
About this file
This is a Limited Asbestos Survey Report prepared by ProTeX for Luke Air Force Base, documenting the results of bulk material sampling and analysis conducted on February 12, 2026, at Building 1365 in Glendale, Arizona. The survey was limited in scope to suspect building materials scheduled to be impacted by a planned renovation project.
ProTeX collected twelve bulk samples of suspect building materials, which were submitted to Eurofins EMLab P&K, LLC (Phoenix, Arizona) for asbestos analysis via Polarized Light Microscopy (PLM) in accordance with EPA Methods 600/R-93/116 and 600/M4-82-020. The laboratory is approved by the Arizona Department of Health Services (ADHS No. AZ0964) and accredited by the National Voluntary Laboratory Accreditation Program (NVLAP No. 500031-0). Analysis was completed on February 18, 2026. The survey identified one asbestos-containing material (ACM): samples 2A, 2B, and 2C (black mastic beneath 1" x 1" cream ceramic tiles in the bathroom floor) containing 10% chrysotile asbestos, classified as non-friable Category II material totaling approximately 20 square feet. All other materials tested, including drywall systems (samples 1A, 1B, 1C), vinyl cove base (samples 3A, 3B, 3C), and block and mortar exterior walls (samples 4A, 4B, 4C), showed no detectable asbestos content. ProTeX recommended that any additional suspect materials discovered during renovation or demolition activities be sampled and analyzed prior to disturbance or assumed to be ACM and handled accordingly.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PHOENIX
1102 W SOUTHERN AVE., STE 4
TEMPE, ARIZONA 85282
(O) 602-272-PTX1 (7891)
DISPATCH 602-272-7890
(F) 602-272-7892
WWW.PROTEX-AZ.COM
TUCSON
916 WEST GRANT ROAD
TUCSON, ARIZONA 85705
(O) 520-352-1050
DISPATCH 520-352-0150
(F) 520-352-0150
Geot echnica l E ngineer ing • Const ruc tion Mater ia l s Test ing • Specia l Inspect ions • E nvi ronm enta l
February 20, 2026
Carl F. Moser, Jr., Civ, DAF Environmental Program Manager
56 CES/CEIEA
13970 Gillespie Drive
Luke AFB, AZ 85309
RE: Limited Asbestos Survey ProTeX Job# 17332
Luke Air Force Base
Building 1365
Glendale, Arizona 85309
Dear Mr. Moser:
In accordance with your authorization to proceed, ProTeX has conducted a limited asbestos survey of
Building 1365 located at Luke Air Force Base in Glendale, Arizona. This letter report includes sum-maries of our activities, findings, and recommendations.
PROJECT BACKGROUND
ProTeX was retained by Luke Air Force Base (AFB) Environmental Management to conduct a lim-ited asbestos survey of Building 1365 at the above referenced address. The survey was limited to the suspect building materials scheduled to be impacted by a scheduled renovation project.
ACTIVITIES
On February 12, 2026, Mrs. Sarah Ellwanger, an Environmental Protection Agency (EPA) and As-bestos Hazard Emergency Response Act (AHERA) Certified Building Inspector with ProTeX, collected twelve (12) bulk samples of suspect building materials from the site.
The samples were submitted via chain of custody protocol to Eurofins EMLab P&K, LLC of Phoe-nix, Arizona for asbestos analysis via PLM. Eurofins EMLab P&K is approved by the Arizona
Department of Health Services pursuant to Arizona Revised Statute (A.R.S.) § 36-495.02 (5) to per-form airborne and bulk asbestos fiber analysis (ADHS No. AZ0964). In addition, Eurofins EMLab
P&K is accredited by the National Voluntary Laboratory Accreditation Program (NVLAP No.
500031-0) for bulk asbestos fiber analysis. Sample analysis was conducted via Polarized Light Mi-croscopy (PLM) in general accordance with EPA Method 600/R-93/116 and/or EPA 600/M4-82-020.
The analytical laboratory reports are attached to this letter report.
http://www.protex-az.com/
Limited Asbestos Survey Luke Air Force Base
Geot echnica l E ngineer ing • Const ruc tion Mater ia l s Test ing • Specia l Inspect ions • E nvi ronm enta l
FINDINGS
According to federal regulations, any material containing greater than one percent (1%) asbestos as determined by PLM is considered asbestos-containing material (ACM). Materials considered asbes-tos containing are highlighted in bold. A summary of the samples collected by ProTeX inspectors is presented in the following table:
CONCLUSIONS AND RECOMMENDATIONS
determined by PLM is considered asbestos-containing material (ACM). One (1) of the materials sampled are considered to be asbestos-containing material (ACM):
Sample Sample
Description Location
Approximate
Quantity (SF)
Friable
Y/N
Asbestos
Content
1A
Drywall System
Walls & Ceiling
-Bathroom
3,550 SF
Y ND
1B Walls & Ceiling
-Office
Y ND
1C Walls & Ceiling
-Hallway
Y ND
2A 1” x 1” Cream
Ceramic Tile with
Grout and Black
Mastic Under-neath
Bathroom Floor
20 SF
N 10% Chrysotile
(Black Mastic)
2B Bathroom Floor N 10% Chrysotile
(Black Mastic)
2C Bathroom Floor N 10% Chrysotile
(Black Mastic)
3A
Gray 4” Vinyl Cove
Base
Base of Bathroom Floor
5 SF
N ND
3B Base of Bathroom Floor N ND
3C Base of Bathroom Floor N ND
4A
Block and Mortar
Exterior Walls of
Building
8,500 SF
N ND
4B Exterior Walls of
Building
N ND
4C Exterior Walls of
Building
N ND
SF = Square Feet
ND = Non-Detect or Below Laboratory Detection Limits
Luke Air Force Base
Geot echnica l E ngineer ing • Const ruc tion Mater ia l s Test ing • Specia l Inspect ions • E nvi ronm enta l
• Samples 3A, 3B, 3C: The black mastic beneath the 1” x 1” cream ceramic tile in the bath-room of Building 1365 contains 10% chrysotile asbestos. The black mastic is a non-friable
Category II asbestos and is approximately 20 square feet in quantity.
If additional suspect building materials are discovered during renovation/demolition activities, the materials should be sampled and analyzed for asbestos content prior to disturbance or should be assumed ACM and handled as such.
LIMITATIONS
ProTeX's conclusions and recommendations, as presented in this report, are based on limited sampling and analysis. The samples collected and used for testing, and the observations made, are believed to be representative of the area(s) evaluated.
The environmental services described in this report have been conducted in general accordance with current regulatory guidelines and the standard-of-care exercised by environmental consultants per-forming similar work in the project area. No other warranty, expressed or implied, is made regarding the professional conclusions presented in this report. Variations in site conditions may exist and con-ditions not observed or described in this report may be encountered during subsequent activities.
ProTeX the PT Xperts appreciates the opportunity to provide environmental consulting services to
Luke Air Force Base and looks forward to future projects. Please contact us at (602) 272-PTX1
(7891) if you have any questions pertaining to this report.
Respectfully Submitted, ProTeX, the PT Xperts, LLC
Emily Rogers, RG
Environmental Professional
Environmental Project Manager
B.S. Geology
Figure 1 – ACM Sample Location Map
Appendix A – Personnel Certifications
Appendix B – Laboratory Reports and Chain-of-Custody
Distribution: (1) Addressee (PDF)
Sarah Ellwanger
Environmental Consultant
AHERA Building Inspector
Luke Air Force Base
Geot echnica l E ngineer ing • Const ruc tion Mater ia l s Test ing • Specia l Inspect ions • E nvi ronm enta l
FIGURE 1
ACM Sample Location Map
ProTeX Job No.17332
Scale: NTS Drawn By: SE Date: 02/18/2026
Fig. 1 (ACM Interior Sample Location) Comprehensive Asbestos Survey
Luke Air Force Base
Building 1365
Glendale, AZ
1A
3A,B,C
1B
1C
4A
4B 4C
Samples 3A, 3B, 3C: The black mastic beneath the 1” x 1” cream ceramic tile in the bath-room of Building 1365 contains
10% chrysotile asbestos. The black mastic is a non-friable Category II asbestos and is approximately 20 square feet in quantity.
2A,B,C
Luke Air Force Base
Building 1365
Geot echnica l E ngineer ing • Const ruc tion Mater ia l s Test ing • Specia l Inspect ions • E nvi ronm enta l
APPENDIX A
PERSONNEL CERTIFICATIONS
May 19, 2025
ON-188748-9895-051925
19-May-2025
19-May-2026
Powered by TCPDF (www.tcpdf.org) http://www.tcpdf.org
Luke Air Force Base
Building 1365
Geot echnica l E ngineer ing • Const ruc tion Mater ia l s Test ing • Specia l Inspect ions • E nvi ronm enta l
APPENDIX B
LABORATORY REPORTS AND CHAIN-OF-CUSTODY
Approved by:
Approved Signatory Renee Luna-Trepczynski
Report for:
Christine McNally, CSM ProTex 1945 E Watkins Street Phoenix, AZ 85034
Regarding:
Eurofins Aerotech Built Environment Testing, LLC Project: Luke Air Force Base; Building 1365
EML ID: 4414515
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the samples as received and tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.
Eurofins Aerotech Built Environment Testing, LLC ("the Company"), a member of the Eurofins Built Environment Testing group of companies, shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Asbestos PLM: 02-18-2026
Service SOPs: Asbestos PLM (EPA 40CFR App E to Sub E of Part 763 & EPA 600/R-93-116, EBET-PLM-SOP83921) NVLAP Lab Code 500031-0
EMLab ID: 4414515, Page 1 of 6Eurofins Aerotech Built Environment Testing, LLC
Eurofins Aerotech Built Environment Testing, LLC 1501 West Knudsen Drive, Phoenix, AZ 85027
(800) 651-4802 www.eurofinsus.com/Built Client: ProTex C/O: Christine McNally, CSM Re: Luke Air Force Base; Building 1365
Date of Sampling: 02-12-2026 Date of Receipt: 02-13-2026 Date of Report: 02-18-2026
ASBESTOS PLM REPORT
Total Samples Submitted: 12 Total Samples Analyzed: 12
Total Samples with Layer Asbestos Content > 1%: 3
Location: 1A, Drywall System Lab ID-Version‡: 22149578-1
Sample Layers Asbestos Content White Compound with Paint ND
Cream Tape ND White Joint Compound ND
White Drywall with Brown Paper ND Composite Non-Asbestos Content: 15% Cellulose Sample Composite Homogeneity: Poor
Location: 1B, Drywall System Lab ID-Version‡: 22149579-1
Sample Layers Asbestos Content White Compound with Paint ND
Sample Composite Homogeneity: Good
Location: 1C, Drywall System Lab ID-Version‡: 22149580-1
Sample Layers Asbestos Content White Compound with Paint ND
Sample Composite Homogeneity: Good
EMLab ID: 4414515, Page 2 of 6Eurofins Aerotech Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
(800) 651-4802 www.eurofinsus.com/Built Client: ProTex C/O: Christine McNally, CSM Re: Luke Air Force Base; Building 1365
Date of Sampling: 02-12-2026 Date of Receipt: 02-13-2026 Date of Report: 02-18-2026
ASBESTOS PLM REPORT
Location: 2A, 1"x1" Cream CT w/ Grout w/ Black Mastic Lab ID-Version‡: 22149581-1
Sample Layers Asbestos Content Cream Ceramic Tile ND
Tan Glue Dot ND Brown Grout ND Gray Grout ND
White Mortar ND Black Mastic 10% Chrysotile
Sample Composite Homogeneity: Poor
Location: 2B, 1"x1" Cream CT w/ Grout w/ Black Mastic Lab ID-Version‡: 22149582-1
Sample Layers Asbestos Content Cream Ceramic Tile ND
Tan Glue Dot ND Brown Grout ND Gray Grout ND
White Mortar ND Black Mastic 10% Chrysotile
Sample Composite Homogeneity: Poor
Location: 2C, 1"x1" Cream CT w/ Grout w/ Black Mastic Lab ID-Version‡: 22149583-1
Sample Layers Asbestos Content Cream Ceramic Tile ND
Tan Glue Dot ND Brown Grout ND Gray Grout ND
White Mortar ND Black Mastic 10% Chrysotile
Sample Composite Homogeneity: Poor
EMLab ID: 4414515, Page 3 of 6Eurofins Aerotech Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 www.eurofinsus.com/Built Client: ProTex C/O: Christine McNally, CSM Re: Luke Air Force Base; Building 1365
Date of Sampling: 02-12-2026 Date of Receipt: 02-13-2026 Date of Report: 02-18-2026
ASBESTOS PLM REPORT
Location: 3A, Gray 4" VCB Lab ID-Version‡: 22149584-1
Sample Layers Asbestos Content Gray Cove Base ND
Sample Composite Homogeneity: Good
Location: 3B, Gray 4" VCB Lab ID-Version‡: 22149585-1
Sample Layers Asbestos Content Gray Cove Base ND
Tan Mastic ND Sample Composite Homogeneity: Moderate
Location: 3C, Gray 4" VCB Lab ID-Version‡: 22149586-1
Sample Layers Asbestos Content Gray Cove Base ND
Tan Mastic ND Sample Composite Homogeneity: Moderate
Location: 4A, Block + Mortar Lab ID-Version‡: 22149587-1
Sample Layers Asbestos Content White Compound with Paint ND Gray Cementitious Material ND
Sample Composite Homogeneity: Moderate
EMLab ID: 4414515, Page 4 of 6Eurofins Aerotech Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 www.eurofinsus.com/Built Client: ProTex C/O: Christine McNally, CSM Re: Luke Air Force Base; Building 1365
Date of Sampling: 02-12-2026 Date of Receipt: 02-13-2026 Date of Report: 02-18-2026
ASBESTOS PLM REPORT
Location: 4B, Block + Mortar Lab ID-Version‡: 22149588-1
Sample Layers Asbestos Content White Compound with Paint ND Gray Cementitious Material ND
Sample Composite Homogeneity: Moderate
Location: 4C, Block + Mortar Lab ID-Version‡: 22149589-1
Sample Layers Asbestos Content White Compound with Paint ND Gray Cementitious Material ND
Sample Composite Homogeneity: Moderate
EMLab ID: 4414515, Page 5 of 6Eurofins Aerotech Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 www.eurofinsus.com/Built Client: ProTex C/O: Christine McNally, CSM Re: Luke Air Force Base; Building 1365
Date of Sampling: 02-12-2026 Date of Receipt: 02-13-2026 Date of Report: 02-18-2026
ASBESTOS PLM REPORT
PROJECT ANALYST AND SIGNATORY REPORT
Project Analyst
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
Analyst: Jason Bosse
EMLab ID: 4414515, Page 6 of 6Eurofins Aerotech Built Environment Testing, LLC
PHOENIX
1102 W SOUTHERN AVE., STE 4
TEMPE, ARIZONA 85282
(O) 602-272-PTX1 (7891)
DISPATCH 602-272-7890
(F) 602-272-7892
TUCSON
916 WEST GRANT ROAD
TUCSON, ARIZONA 85705
(O) 520-352-1050
DISPATCH 520-352-0150
(F) 520-352-0150
Geot echnica l E ngineer ing • Const ruc tion Mater ia l s Test ing • Specia l Inspect ions • E nvi ronm enta l
February 20, 2026
Carl F. Moser, Jr., Civ, DAF Environmental Program Manager
56 CES/CEIEA
13970 Gillespie Drive
Luke AFB, AZ 85309
RE: Limited Asbestos Survey ProTeX Job# 17332
Luke Air Force Base
Dear Mr. Moser:
In accordance with your authorization to proceed, ProTeX has conducted a limited asbestos survey of
Building 1365 located at Luke Air Force Base in Glendale, Arizona. This letter report includes sum-maries of our activities, findings, and recommendations.
PROJECT BACKGROUND
ProTeX was retained by Luke Air Force Base (AFB) Environmental Management to conduct a lim-ited asbestos survey of Building 1365 at the above referenced address. The survey was limited to the suspect building materials scheduled to be impacted by a scheduled renovation project.
ACTIVITIES
On February 12, 2026, Mrs. Sarah Ellwanger, an Environmental Protection Agency (EPA) and As-bestos Hazard Emergency Response Act (AHERA) Certified Building Inspector with ProTeX, collected twelve (12) bulk samples of suspect building materials from the site.
The samples were submitted via chain of custody protocol to Eurofins EMLab P&K, LLC of Phoe-nix, Arizona for asbestos analysis via PLM. Eurofins EMLab P&K is approved by the Arizona
Department of Health Services pursuant to Arizona Revised Statute (A.R.S.) § 36-495.02 (5) to per-form airborne and bulk asbestos fiber analysis (ADHS No. AZ0964). In addition, Eurofins EMLab
P&K is accredited by the National Voluntary Laboratory Accreditation Program (NVLAP No.
500031-0) for bulk asbestos fiber analysis. Sample analysis was conducted via Polarized Light Mi-croscopy (PLM) in general accordance with EPA Method 600/R-93/116 and/or EPA 600/M4-82-020.
The analytical laboratory reports are attached to this letter report.
Luke Air Force Base
Geot echnica l E ngineer ing • Const ruc tion Mater ia l s Test ing • Specia l Inspect ions • E nvi ronm enta l
FINDINGS
determined by PLM is considered asbestos-containing material (ACM). Materials considered asbes-tos containing are highlighted in bold. A summary of the samples collected by ProTeX inspectors is presented in the following table:
CONCLUSIONS AND RECOMMENDATIONS
determined by PLM is considered asbestos-containing material (ACM). One (1) of the materials sampled are considered to be asbestos-containing material (ACM):
Sample Sample
Description Location
Approximate
Quantity (SF)
Friable
Y/N
Asbestos
Content
1A
Drywall System
Walls & Ceiling
-Bathroom
3,550 SF
Y ND
1B Walls & Ceiling
-Office
Y ND
1C Walls & Ceiling
-Hallway
Y ND
2A 1” x 1” Cream
Ceramic Tile with
Grout and Black
Mastic Under-neath
Bathroom Floor
20 SF
N 10% Chrysotile
(Black Mastic)
2B Bathroom Floor N 10% Chrysotile
(Black Mastic)
2C Bathroom Floor N 10% Chrysotile
(Black Mastic)
3A
Gray 4” Vinyl Cove
Base
Base of Bathroom Floor
5 SF
N ND
3B Base of Bathroom Floor N ND
3C Base of Bathroom Floor N ND
4A
Block and Mortar
Exterior Walls of
Building
8,500 SF
N ND
4B Exterior Walls of
Building
N ND
4C Exterior Walls of
Building
N ND
SF = Square Feet
ND = Non-Detect or Below Laboratory Detection Limits
Luke Air Force Base
Geot echnica l E ngineer ing • Const ruc tion Mater ia l s Test ing • Specia l Inspect ions • E nvi ronm enta l
• Samples 3A, 3B, 3C: The black mastic beneath the 1” x 1” cream ceramic tile in the bath-room of Building 1365 contains 10% chrysotile asbestos. The black mastic is a non-friable
Category II asbestos and is approximately 20 square feet in quantity.
If additional suspect building materials are discovered during renovation/demolition activities, the materials should be sampled and analyzed for asbestos content prior to disturbance or should be assumed ACM and handled as such.
LIMITATIONS
ProTeX's conclusions and recommendations, as presented in this report, are based on limited sampling and analysis. The samples collected and used for testing, and the observations made, are believed to be representative of the area(s) evaluated.
The environmental services described in this report have been conducted in general accordance with current regulatory guidelines and the standard-of-care exercised by environmental consultants per-forming similar work in the project area. No other warranty, expressed or implied, is made regarding the professional conclusions presented in this report. Variations in site conditions may exist and con-ditions not observed or described in this report may be encountered during subsequent activities.
ProTeX the PT Xperts appreciates the opportunity to provide environmental consulting services to
Luke Air Force Base and looks forward to future projects. Please contact us at (602) 272-PTX1
(7891) if you have any questions pertaining to this report.
Respectfully Submitted, ProTeX, the PT Xperts, LLC
Emily Rogers, RG
Environmental Professional
Environmental Project Manager
B.S. Geology
Figure 1 – ACM Sample Location Map
Appendix A – Personnel Certifications
Appendix B – Laboratory Reports and Chain-of-Custody
Distribution: (1) Addressee (PDF)
Environmental Consultant
AHERA Building Inspector
Luke Air Force Base
Geot echnica l E ngineer ing • Const ruc tion Mater ia l s Test ing • Specia l Inspect ions • E nvi ronm enta l
FIGURE 1
ACM Sample Location Map
ProTeX Job No.17332
Scale: NTS Drawn By: SE Date: 02/18/2026
Fig. 1 (ACM Interior Sample Location) Comprehensive Asbestos Survey
Luke Air Force Base
Building 1365
Glendale, AZ
1A
3A,B,C
1B
1C
4A
4B 4C
Samples 3A, 3B, 3C: The black mastic beneath the 1” x 1” cream ceramic tile in the bath-room of Building 1365 contains
10% chrysotile asbestos. The black mastic is a non-friable Category II asbestos and is approximately 20 square feet in quantity.
2A,B,C
Luke Air Force Base
Building 1365
Geot echnica l E ngineer ing • Const ruc tion Mater ia l s Test ing • Specia l Inspect ions • E nvi ronm enta l
APPENDIX A
PERSONNEL CERTIFICATIONS
May 19, 2025
ON-188748-9895-051925
19-May-2025
19-May-2026
Powered by TCPDF (www.tcpdf.org) http://www.tcpdf.org
Luke Air Force Base
Building 1365
Geot echnica l E ngineer ing • Const ruc tion Mater ia l s Test ing • Specia l Inspect ions • E nvi ronm enta l
APPENDIX B
LABORATORY REPORTS AND CHAIN-OF-CUSTODY
Approved by:
Approved Signatory Renee Luna-Trepczynski
Report for:
Christine McNally, CSM ProTex 1945 E Watkins Street Phoenix, AZ 85034
Regarding:
Eurofins Aerotech Built Environment Testing, LLC Project: Luke Air Force Base; Building 1365
EML ID: 4414515
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the samples as received and tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.
Eurofins Aerotech Built Environment Testing, LLC ("the Company"), a member of the Eurofins Built Environment Testing group of companies, shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Asbestos PLM: 02-18-2026
Service SOPs: Asbestos PLM (EPA 40CFR App E to Sub E of Part 763 & EPA 600/R-93-116, EBET-PLM-SOP83921) NVLAP Lab Code 500031-0
EMLab ID: 4414515, Page 1 of 6Eurofins Aerotech Built Environment Testing, LLC
(800) 651-4802 www.eurofinsus.com/Built Client: ProTex C/O: Christine McNally, CSM Re: Luke Air Force Base; Building 1365
Date of Sampling: 02-12-2026 Date of Receipt: 02-13-2026 Date of Report: 02-18-2026
ASBESTOS PLM REPORT
Total Samples Submitted: 12 Total Samples Analyzed: 12
Total Samples with Layer Asbestos Content > 1%: 3
Location: 1A, Drywall System Lab ID-Version‡: 22149578-1
Sample Layers Asbestos Content White Compound with Paint ND
Cream Tape ND White Joint Compound ND
White Drywall with Brown Paper ND Composite Non-Asbestos Content: 15% Cellulose Sample Composite Homogeneity: Poor
Location: 1B, Drywall System Lab ID-Version‡: 22149579-1
Sample Layers Asbestos Content White Compound with Paint ND
Sample Composite Homogeneity: Good
Location: 1C, Drywall System Lab ID-Version‡: 22149580-1
Sample Layers Asbestos Content White Compound with Paint ND
Sample Composite Homogeneity: Good
EMLab ID: 4414515, Page 2 of 6Eurofins Aerotech Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 www.eurofinsus.com/Built Client: ProTex C/O: Christine McNally, CSM Re: Luke Air Force Base; Building 1365
Date of Sampling: 02-12-2026 Date of Receipt: 02-13-2026 Date of Report: 02-18-2026
ASBESTOS PLM REPORT
Location: 2A, 1"x1" Cream CT w/ Grout w/ Black Mastic Lab ID-Version‡: 22149581-1
Sample Layers Asbestos Content Cream Ceramic Tile ND
Tan Glue Dot ND Brown Grout ND Gray Grout ND
White Mortar ND Black Mastic 10% Chrysotile
Sample Composite Homogeneity: Poor
Location: 2B, 1"x1" Cream CT w/ Grout w/ Black Mastic Lab ID-Version‡: 22149582-1
Sample Layers Asbestos Content Cream Ceramic Tile ND
Tan Glue Dot ND Brown Grout ND Gray Grout ND
White Mortar ND Black Mastic 10% Chrysotile
Sample Composite Homogeneity: Poor
Location: 2C, 1"x1" Cream CT w/ Grout w/ Black Mastic Lab ID-Version‡: 22149583-1
Sample Layers Asbestos Content Cream Ceramic Tile ND
Tan Glue Dot ND Brown Grout ND Gray Grout ND
White Mortar ND Black Mastic 10% Chrysotile
Sample Composite Homogeneity: Poor
EMLab ID: 4414515, Page 3 of 6Eurofins Aerotech Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 www.eurofinsus.com/Built Client: ProTex C/O: Christine McNally, CSM Re: Luke Air Force Base; Building 1365
Date of Sampling: 02-12-2026 Date of Receipt: 02-13-2026 Date of Report: 02-18-2026
ASBESTOS PLM REPORT
Location: 3A, Gray 4" VCB Lab ID-Version‡: 22149584-1
Sample Layers Asbestos Content Gray Cove Base ND
Sample Composite Homogeneity: Good
Location: 3B, Gray 4" VCB Lab ID-Version‡: 22149585-1
Sample Layers Asbestos Content Gray Cove Base ND
Tan Mastic ND Sample Composite Homogeneity: Moderate
Location: 3C, Gray 4" VCB Lab ID-Version‡: 22149586-1
Sample Layers Asbestos Content Gray Cove Base ND
Tan Mastic ND Sample Composite Homogeneity: Moderate
Location: 4A, Block + Mortar Lab ID-Version‡: 22149587-1
Sample Layers Asbestos Content White Compound with Paint ND Gray Cementitious Material ND
Sample Composite Homogeneity: Moderate
EMLab ID: 4414515, Page 4 of 6Eurofins Aerotech Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 www.eurofinsus.com/Built Client: ProTex C/O: Christine McNally, CSM Re: Luke Air Force Base; Building 1365
Date of Sampling: 02-12-2026 Date of Receipt: 02-13-2026 Date of Report: 02-18-2026
ASBESTOS PLM REPORT
Location: 4B, Block + Mortar Lab ID-Version‡: 22149588-1
Sample Layers Asbestos Content White Compound with Paint ND Gray Cementitious Material ND
Sample Composite Homogeneity: Moderate
Location: 4C, Block + Mortar Lab ID-Version‡: 22149589-1
Sample Layers Asbestos Content White Compound with Paint ND Gray Cementitious Material ND
Sample Composite Homogeneity: Moderate
EMLab ID: 4414515, Page 5 of 6Eurofins Aerotech Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 www.eurofinsus.com/Built Client: ProTex C/O: Christine McNally, CSM Re: Luke Air Force Base; Building 1365
Date of Sampling: 02-12-2026 Date of Receipt: 02-13-2026 Date of Report: 02-18-2026
ASBESTOS PLM REPORT
PROJECT ANALYST AND SIGNATORY REPORT
Project Analyst
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
Analyst: Jason Bosse
EMLab ID: 4414515, Page 6 of 6Eurofins Aerotech Built Environment Testing, LLC
| Attachment 5 - Asbestos Report dated 20 Feb 26 |
| Attachment 12 - Asbestos Report for Bldg 1365 dated 20 Feb 26 |