This is an as-built electrical drawings document for a federal healthcare facility, specifically providing a comprehensive legend and symbol key for electrical systems installation and design standards. The document establishes standardized identification codes, panel designation sequences, equipment symbols, wiring device specifications, and mounting height requirements for a multi-building complex that includes hospital, clinic, warehouse, parking garage, central energy plant, domiciliary, nursing home, and chapel facilities. The drawings incorporate life safety branch, critical branch, and normal branch circuits with corresponding color-coding and distinction for emergency power systems.

The document specifies detailed requirements for electrical components including automatic transfer switches (ATS), circuit breakers, disconnect switches, motor control centers, variable frequency drives, and generator distribution systems rated at 480Y/277 volts and 208Y/120 volts. It establishes conduit and conductor specifications (primarily #12 AWG conductors in 3/4" conduit), dedicated neutral conductors for each branch circuit, and prohibits neutral conductor sharing between circuits. Wiring device specifications include receptacle types (simplex, duplex, GFCI, tamper-resistant, and emergency power-connected), switch configurations (single-pole, three-way, four-way, key-operated, explosion-proof, and weatherproof), and luminaire placements with mounting heights at 18" above finished floor for receptacles and 48" for switches unless otherwise noted. The document also addresses lightning protection systems with air terminals, roof conductors, ground loop conductors buried 24" below finished grade, and bonding connections, with all materials required to comply with Underwriters Laboratories standards and the National Electrical Code.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

IDENTIFICATION CODES

SEQUENCE OF PANELS

LIFE SAFETY BRANCH

CRITICAL BRANCH

EQUIPMENT BRANCH

1,2,3 -

S - C - E -

GENERATOR DISTRIBUTIONG -

H - 480Y/277 VOLT

ZONE DESIGNATION (IF ANY)

FLOOR LEVEL (FOR MULTISTORY BUILDINGS ONLY)

C 1 A H S 1

NORMAL BRANCHN -

DISTRIBUTION PANEL (IF PRESENT)D -

UPSU -

H - HOSPITAL

C - CLINIC

W - WAREHOUSE

P - PARKING GARAGE

E - CENTRAL ENERGY PLANT

D - DOMICILIARY

N - NURSING HOME

PANEL CODE:

L - 208Y/120 VOLT

ATS - AUTOMATIC TRANSFER SWITCH

C D ATS - S 1

BUILDING IDENTIFIER

H - HOSPITAL

C - CLINIC

W - WAREHOUSE

P - PARKING GARAGE

E - CENTRAL ENERGY PLANT

D - DOMICILIARY

N - NURSING HOME

EQUIPMENT CODE:

CB - ENCLOSED CIRCUIT BREAKER

DS - DISCONNECT SWITCH

ST - COMBINATION MOTOR STARTER/DISCONNECT SWITCH

1,2,3 - SEQUENCE OF EQUIPMENT (OR EQUIPMENT SERVED)

LIFE SAFETY BRANCH

CRITICAL BRANCH

EQUIPMENT BRANCH

S - C - E -

UPSU -

FOR AUTOMATIC TRANSFER SWITCHES

ZONE DESIGNATION (IF PRESENT)

DB - BUS DUCT CIRCUIT BREAKER

BUILDING IDENTIFIER

VFD - VARIABLE FREQUENCY DRIVE

MCC - MOTOR CONTROL CENTER

SB - SWITCHBOARD

R - CHAPEL

1ALN1-

CONDUIT AND CONDUCTORS

BRANCH CIRCUIT WIRING IN CONDUIT. NO TICK MARKS INDICATE 2#12 AWG

CONDUCTORS AND 1#12 AWG GND IN 3/4" CONDUIT UNLESS OTHERWISE

NOTED. WHEN SHOWN, TICK MARKS INDICATE THE NUMBER OF #12 AWG

CONDUCTORS IN 3/4" CONDUIT. SHORT TICK MARKS INDICATED PHASE

CONDUCTORS, LONG TICK MARKS INDICATE NEUTRAL CONDUCTORS.

GROUND CONDUCTOR NOT SHOWN, PROVIDE #12 AWG GROUND IN EACH

CONDUIT UNLESS OTHERWISE NOTED. EACH BRANCH CIRCUIT SHALL BE

PROVIDED WITH A DEDICATED NEUTRAL CONDUCTOR. SHARING OF A

NEUTRAL CONDUCTOR BETWEEN TWO OR MORE BRANCH CIRCUITS IS NOT

ACCEPTABLE.

1,3,5

FEEDER SIZE, SEE FEEDER SCHEDULE ON SHEET E-EP7.001.

MOTOR BRANCH CIRCUIT SIZE, SEE MOTOR BRANCH CIRCUIT SCHEDULE

ON SHEET E-EP7.001.

CONDUIT TERMINATION, (C) CAPPED, (B) BUSHED, (G) GROUND BUSHING.

14012

14012

BRANCH CIRCUIT CONCEALED IN CEILING SPACE OR WALL.

PANELBOARD DESIGNATION.

CIRCUIT DESIGNATION. "1,3" INDICATES A TWO-POLE CIRCUIT BREAKER.

"1,3,5" INDICATES A THREE-POLE CIRCUIT BREAKER.

HOMERUN TO PANELBOARD.

LIGHTNING PROTECTION SYSTEM

AIR TERMINAL.

SUBSCRIPTS INDICATE THE FOLLOWING:

A - PARAPET MOUNTED AIR TERMINAL. REFER TO 1/E-EQ5.001 FOR DETAIL.

B - PARAPET MOUNTED AIR TERMINAL. REFER TO 2/E-EQ5.001 FOR DETAIL.

LIGHTNING PROTECTION SYSTEM ROOF CONDUCTOR.

LIGHTNING PROTECTION SYSTEM GROUND LOOP CONDUCTOR. BURY AT 24"

BELOW FINISHED GRADE.

LIGHTNING PROTECTION SYSTEM THRU-ROOF CONNECTOR. SUBSCRIPTS INDICATE

THE FOLLOWING:

THREE GROUND ROD(S), SPACED 10'-0" APART. REFER TO 7/E-EQ5.002 FOR DETAIL.

BONDING CONNECTION.

GL

C1 - AIR TERMINAL MOUNTED ON ROOFTOP EXHAUST FAN. REFER TO 3/E-EQ5.001

FOR DETAIL.

A

DN1

G

D - FLAT ROOF MOUNTED AIR TERMINAL. REFER TO 5/E-EQ5.001 FOR DETAIL.

C2 - AIR TERMINAL MOUNTED ON ROOFTOP SUPPLY FAN. REFER TO 4/E-EQ5.001 FOR

DETAIL.

E - AIR TERMINAL MOUNTED ON COOLING TOWER FAN CYLINDER. REFER TO

6/E-EQ5.001 FOR DETAIL.

DN1 - CONDUCTOR ROUTED FROM CONCRETE PARAPET DOWN TO GRADE. REFER TO

1/E-EQ5.002 FOR DETAIL.

DN2 - CONDUCTOR ROUTED FROM STEEL PARAPET DOWN TO FLAT ROOF. REFER TO

2/E-EQ5.002 FOR DETAIL.

DN3 - CONDUCTOR ROUTED FROM COOLING TOWER DOWN TO GRADE. REFER TO

3/E-EQ5.002 FOR DETAIL.

20A, 125V SIMPLEX RECEPTACLE. WALL MOUNT AT 18" AFF TO CENTER UON.

WIRING DEVICES

SUBSCRIPTS INDICATE THE FOLLOWING: (FOR ALL RECEPTACLES)

DUPLEX RECEPTACLE WITH INTEGRAL GROUND

FAULT CIRCUIT INTERRUPTER (GFCI).

MOUNT DEVICE ABOVE THE COUNTER TOP. SEE SHEET

NOTE #4 ON THIS SHEET FOR REQUIREMENTS.

TAMPER RESISTANT RECEPTACLE

MOUNT DEVICE AT 48" AFF TO CENTER. OTHER

MOUNTING HEIGHTS AS INDICATED.

G -

OC -

TR -

+48" -

20A, 125V DUPLEX RECEPTACLE FOR ENTERTAINMENT TELEVISION.

MOUNT RECEPTACLE ADJACENT TO THE CABLE TELEVISION OUTLET. SEE

COMMUNICATIONS PLANS FOR EXACT LOCATION AND MOUNTING HEIGHT.

SEE 3/E-ET5.001 FOR DETAIL.

TV

SPECIAL RECEPTACLE WITH NEMA CONFIGURATION AS INDICATED. WALL

MOUNT AT 18" AFF TO CENTER UON.

NEMA

FLUSH FLOOR BOX WITH SEPARATE POWER AND COMMUNICATIONS

COMPARTMENTS. SEE DETAIL 4/E-ET5.001.

20A, 125V SIMPLEX RECEPTACLE CONNECTED TO EMERGENCY POWER.

WALL MOUNT AT 18" AFF TO CENTER UON.

20A, 125V DUPLEX RECEPTACLE CONNECTED TO EMERGENCY POWER. WALL

MOUNT AT 18" AFF TO CENTER UON.

20A, 120/277V SINGLE POLE SWITCH. WALL MOUNT AT 48" AFF TO CENTER

UON. SUBSCRIPTS INDICATE THE FOLLOWING:

THREE WAY3 -

FOUR WAY4 -

INDICATES SWITCH LEGSa,b,c... -

FLUORESCENT DIMMING CONTROLLERFD -

KEY OPERATED SWITCHK -

EXPLOSION PROOFEXP -

WEATHER PROOF COVERWP -

FAN SPEED CONTROLLERF -

MANUAL MOTOR STARTER WITH MELTING ALLOY HEATER ELEMENTSM -

MOMENTARY CONTACT TOGGLE SWITCHMC -

SWITCH WITH PILOT LIGHTP -

WEATHERPROOF SWITCHWP -

CEILING MOUNT OR SUSPENDED FLUORESCENT LUMINAIRE (NORMAL

BRANCH)

CEILING MOUNT OR SUSPENDED FLUORESCENT LUMINAIRE (CRITICAL OR

EQUIPMENT BRANCH)

LUMINAIRES

CEILING MOUNT OR SUSPENDED FLUORESCENT LUMINAIRE (LIFE SAFETY

BRANCH)

WALL MOUNTED FLUORESCENT LUMINAIRE (NORMAL BRANCH)

WALL MOUNTED FLUORESCENT LUMINAIRE (CRITICAL OR EQUIPMENT BRANCH)

WALL MOUNTED FLUORESCENT LUMINAIRE (LIFE SAFETY BRANCH)

RECESSED DOWN LIGHT (NORMAL BRANCH)

RECESSED DOWN LIGHT (CRITICAL OR EQUIPMENT BRANCH)

RECESSED DOWN LIGHT (LIFE SAFETY BRANCH)

EXIT SIGN, CEILING OR PENDANT MOUNTED. SHADED PORTION DENOTES

FACE(S). DIRECTIONAL ARROWS AS INDICATED.

EXIT SIGN, WALL MOUNTED. SHADED PORTION DENOTES FACE(S).

DIRECTIONAL ARROWS AS INDICATED. MOUNT AT 6" ABOVE TOP OF DOOR JAMB

TO BOTTOM OF FIXTURE.

WALL MOUNTED LUMINAIRE (NORMAL BRANCH)

WALL MOUNTED LUMINAIRE (CRITICAL OR EQUIPMENT BRANCH)

WALL MOUNTED LUMINAIRE (LIFE SAFETY BRANCH)

FLUORESCENT STRIP OR INDUSTRIAL LUMINAIRE (LIFE SAFETY BRANCH)

FLUORESCENT STRIP OR INDUSTRIAL LUMINAIRE (CRITICAL OR EQUIPMENT

BRANCH)

FLUORESCENT STRIP OR INDUSTRIAL LUMINAIRE (NORMAL BRANCH)

POLE MOUNTED AREA LIGHT, SINGLE HEAD. (NORMAL BRANCH)

PHOTOELECTRIC CONTROLLER.

KEY NOTE SYMBOL. (SEE KEY NOTES ON INDIVIDUAL DRAWINGS).

CONDUCTOR CONNECTION

ELECTRICAL GROUND

MISCELLANEOUS

LOW VOLTAGE CABLE TRAY FOR COMMUNICATIONS SYSTEMS WIRING ONLY.

PROVIDE A MINIMUM 5" SEPARATION BETWEEN FLUORESCENT LIGHTING

FIXTURES AND CABLE TRAY. WIDTH SHALL BE 12" UNLESS OTHERWISE NOTED.

SEE 7/E-ET5.001 FOR DETAIL.

PE

BC BATTERY CHARGER, MOUNT AT 72" AFF TO TOP.

SUBSCRIPTS AS FOLLOWS:

G - BATTERY CHARGER FOR GENERATOR BATTERIES.

S - BATTERY CHARGER FOR SWITCHGEAR STATION BATTERIES.

GENERATOR SCADA SYSTEM OUTLET, SEE 8/E-ET5.001 FOR DETAIL.

S

GRAP

GENERATOR REMOTE ALARM PANEL. MOUNT AT 72" AFF TO TOP.

CLOSED CIRCUIT TELEVISION

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AUTOMATIC TRANSFER SWITCH

BELOW FINISHED GRADE

ELECTRIC UNIT HEATER

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

ELECTRICAL METALLIC TUBING

ENGINE GENERATOR SET

BELOW FINISHED CEILING

EWH

FLUOR

FA

GEN

EXP, XP

EXH

EQUIP

EWC

EUH

EMT

EF

FLUORESCENT

FIRE ALARM

EXHAUST

EXPLOSION PROOF

EXHAUST FAN

EQUIPMENT

CLG

DISC

DWG

EA

CU

CL

CAB

CCTV

CKT

BFG

CEILING

CENTERLINE

DISCONNECT(ING)

DRAWING(S)

EACH

COPPER

CABINET

CIRCUIT

CONDUIT

AFG

ATS

BFC

A

AFF

NATIONAL ELECTRICAL CODE

POLYVINYL CHLORIDE

UNLESS OTHERWISE NOTED

MANUAL TRANSFER SWITCH

WT

V

WP

VA

TEL

UON

WATER TIGHT

TELEPHONE

VOLT-AMPERES

WEATHER PROOF

VOLTAGE

MTS

PVC

PNL

RECEPT

NEC

NC

MTR

MTG

MTD

MISC

MIN

NURSE CALL

RECEPTACLE

PANEL

MINIMUM

MISCELLANEOUS

MOUNTED

MOUNTING

MOTOR

KILO-VOLTS-AMPERES

KILO-WATT-HOURS

MOTOR CONTROL CENTER

LOCAL AREA NETWORKLAN

MCC

MH

MFR

MAX

LTG

KVA

KWH

KW

KV

MANHOLE

LIGHTING

MANUFACTURER

MAXIMUM

KILO-VOLTS

KILO-WATTS

INCAND INCANDESCENT

FLA FULL LOAD AMPERES

ABOVE FINISHED CEILINGAFC

W WIRE

TYP TYPICAL

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

CURRENT TRANSFORMERSCT's

KILO-VOLTS-AMPERES REACTIVEKVAR

RGS RIGID GALVANIZED STEEL

GOVERNMENT FURNISHEDGFGI

GOVERNMENT INSTALLED

C m METER mm MILLIMETER

AIC AMPERES INTERRUPTING

CAPACITY

MCB MAIN CIRCUIT BREAKER

MDP MAIN DISTRIBUTION PANEL

SEE REFLECTED CEILING PLAN ON SHEET E-AI1.10 FOR EXACT LOCATION OF LUMINAIRES AND

CEILING MOUNTED DEVICES.

LUMINAIRES INDICATED AS FOLLOWS: UPPER CASE LETTER WITH NUMERAL DENOTES FIXTURE

TYPE (SEE LUMINAIRE SCHEDULE), LOWER CASE LETTER (IF SHOWN) DENOTES SWITCHING

ARRANGEMENT AND NUMERAL BY ITSELF (IF SHOWN) DENOTES CIRCUIT NUMBER.

WHERE DEVICES ARE INDICATED TO BE MOUNTED ABOVE A COUNTERTOP, MOUNT DEVICE

SUCH THAT BOTTOM OF COVER PLATE IS 51mm (2") ABOVE TOP OF BACK SPLASH. IF THERE IS NO BACK SPLASH, MOUNT DEVICE 51mm (2") ABOVE FINISHED COUNTER TOP SURFACE TO

BOTTOM OF DEVICE COVER PLATE.

1.

2.

3.

4.

5.

HIGH INTENSITY DISCHARGEHID

G, GND

HGT

GROUND

HEIGHT

GFP GROUND FAULT PROTECTION

NOTES:

SHEET NOTES:

AMPERES

INSTALL ALL EQUIPMENT AND DEVICES AT THE HEIGHT INDICATED ON THIS SHEET UNLESS

OTHERWISE NOTED. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS FOR SPECIAL

MOUNTING HEIGHTS AND LOCATIONS OF ELECTRICAL DEVICES. MOUNTING HEIGHTS AND

LOCATIONS INDICATED ON ARCHITECTURAL ELEVATIONS TAKE PRECEDENCE OVER

MOUNTING HEIGHTS AND LOCATIONS INDICATED ON ELECTRICAL PLANS.

WHERE MULTIPLE TOGGLE SWITCHES ARE SHOWN TO BE MOUNTED ADJACENT TO ONE

ANOTHER, MOUNT SWITCHES IN A SINGLE BOX UP TO 4-GANG (NORMAL AND EMERGENCY

CIRCUITS SHALL NOT OCCUPY THE SAME ENCLOSURE).

ABBREVIATIONS

ALL MATERIALS AND EQUIPMENT SHALL BE LISTED AS COMPLYING WITH THE

APPLICABLE STANDARDS OF UNDERWRITERS LABORATORIES, INC.

6.

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME

AMPERE TRIPAT

BARE COPPERBC

BOILER PLANT INSTRUMENTATION

PANEL

BRIP

CIRCUIT BREAKERCB, C/B

BREAKERBKR

DB DIRECT BURIED

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EXPANSION JOINTEJ

EX EXISTING

EMERGENCYEMERG

ELECTRICELEC

ELECTRIC STRIP MOLDESM

FACP FIRE ALARM CONTROL PANEL

FCU

FILM ILLUMINATORFI

FAN COIL UNIT

FIXT FIXTURE

FSCP FLAME SAFEGUARD CONTROL PANEL

FSS FUSED SAFETY SWITCH

GFI GROUND FAULT INTERRUPTER

GTB GROUND TERMINAL BOX

HH HANDHOLE

HAND-OFF-AUTOMATICHOA

JB JUNCTION BOX

LTCP LOCAL TEMPERATURE CONTROL

PANEL

LTS LIGHTS

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION

MCP MOTOR CIRCUIT PROTECTOR

MLO MAIN LUGS ONLY

MTG HGT MOUNTING HEIGHT

NON-FUSED SAFETY SWITCHNFSS

POLEP

PULL BOXPB

PREFABRICATED BEDSIDE

PATIENT POWER UNIT

PBPU

POD POWER OPERATED DAMPER

POWER TYPE ROOF VENTILATIONPTRV

POWERPWR

RGIP REMOTE GROUND INDICATOR PANEL

SIG SIGNAL

SS SAFETY SWITCH

STA STATION

TV TELEVISION

UNIT HEATERUH

VP VAPOR PROOF

W/ WITH

XFMR TRANSFORMER

HV HIGH VOLTAGE

HPS HIGH PRESSURE SODIUM

HP HORSEPOWER

NORMALLY OPENN.O.

>= GREATER THAN OR EQUAL TO

LESS THAN OR EQUAL TO<=

CEILING MOUNTED LINE VOLTAGE OCCUPANCY SENSOR. SEE

7/E-EL5.003 FOR WIRING DIAGRAM.

U a

PATTERN TYPE. SCHEDULE BELOW.

SWITCH LEG

TECHNOLOGY TYPE. SEE SCHEDULE BELOW.

SENSOR ORIENTATION

PATTERN TYPE SCHEDULE:

1 90' x 10' 2 40' x 40' 3 20' x 20'

OCCUPANCY SENSING WALL SWITCH. WITH MANUAL OVERRIDE. MOUNT AT 48" AFF TO

CENTER.

OCCUPANCY SENSORS

U

TECHNOLOGY TYPE. SEE SCHEDULE BELOW.

CEILING/WALL SENSORS

WALL SWITCHES

TECHNOLOGY TYPE SCHEDULE:

U ULTRASONIC

R INFRARED

D DUAL TECHNOLOGY(INFRARED & ULTRASONIC)

AD L

EK

N

LL

E F

S

R P

O

IS

EN

L

GI

O N A

E E

N R

EC NIL

S E

No 0052705

STATE OF

ROLF

I D A

EE

AS

M

ON

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

OFFICE OF

FACILITIES

MANAGEMENT

on e ei gh th in ch o ne fo ot

B

A

C

D

E

F th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

BUILDING IS FULLY SPRINKLERED

A NEW HOSPITAL FOR

VAMC ORLANDO, FLORIDA

Orlando, Florida

673-950

Professional Seals:

29 OCTOBER, 2009 KLM EB/RLF

CENTRAL ENERGY PLANT

E-EG0.001

ELECTRICAL LEGEND AND ABBREVIATIONS

No. Description Date

SITE WORK

A1-E1

NA1-1

T-1

MANHOLE, SEE 1/E-ES5.004 FOR DETAIL. SEE 3/E-ES5.004 FOR GROUNDING

TELECOMMUNICATIONS MANHOLE. SEE 1/E-ES5.004 FOR MANHOLE

DETAILS. SEE 3/E-ES5.0004 FOR GROUNDING DETAIL.

CONDUIT TERMINATION WITH CAP FOR FUTURE USE. EXTEND CONDUITS

DETAIL. SUBSCRIPTS INDICATES THE FOLLOWING:

N A 1 - 1

MANHOLE SEQUENCE

SWITCHGEAR SECTION (SECTION 1 OR 2)

SOURCE IDENTIFICATION ("A" SYSTEM OR "B" SYSTEM)

SERVICE IDENTIFICATION:

N - NORMAL POWER.

E - EMERGENCY POWER.

G - GENERATOR CONTROLS.

DUCT BANK. SEE DUCT BANK SCHEDULES ON SHEETS E-ES7.001, E-ES7.002

SWITCHGEAR SECTION WHERE APPLICABLE (SECTION 1 OR 2)

SOURCE IDENTIFICATION WHERE APPLICABLE ("A" SYSTEM OR "B" SYSTEM)

DUCT SEQUENCE

SERVICE IDENTIFICATION:

E - EMERGENCY POWER, SEE DUCT BANK SCHEDULE SHEET E-ES7.001.

G - GENERATOR CONTROLS, SEE DUCT BANK SCHEDULE SHEET E-ES7.002.

N - NORMAL POWER, SEE DUCT BANK SCHEDULE SHEET E-ES7.001.

T - TELECOMMUNICATIONS, SEE DUCT BANK SCHEDULE SHEET E-ES7.002.

12" BEYOND CONCRETE ENCASEMENT FOR FUTURE EXTENSION.

AND E-ES7.003 FOR REQUIREMENTS.

C

NA1-1

EXISTING MANHOLE PROVIDED UNDER A SEPARATE CONSTRUCTION PACKAGE.

DUCT BANK PROVIDED UNDER A SEPARATE CONSTRUCTION PACKAGE. SEE

DUCT BANK SHEDULES ON SHEET E-ES7.001, E-ES7.002 , AND E-ES7.003.A1-E1

TEMPORARY OVERHEAD PRIMARY POWER LINE PROVIDED UNDER A SEPARATE

CONSTRUCTION PACKAGE 1.OHP

TEMPORARY POWER POLE PROVIDED UNDER A SEPARATE CONSTRUCTION

PACKAGE 1.

UL1 UNDERGROUND SITE LIGHTING CONDUIT, SEE SCHEDULE ON SHEET E-ES7.003

FOR REQUIREMENTS.

COMBINATION VOICE/DATA OUTLET. SEE 2/E-ET6.001 FOR OUTLET CONFIGURATION.

MOUNT AT 18" AFF TO CENTER UNLESS OTHERWISE NOTED.

TELEPHONE / DATA SYSTEM

WALL MOUNTED TELEPHONE OUTLET. SEE 2/E-ET6.001 FOR OUTLET CONFIGURATION.

MOUNT 54" TO CENTER UON.

TELECOMMUNICATIONS EQUIPMENT CABINET WITH HORIZONTAL AND VERTICAL

CABLE MANAGEMENT.

COMBINATION VOICE/DATA OUTLET MOUNTED ABOVE COUNTER TOP. SEE 2/E-ET6.001

FOR OUTLET CONFIGURATION.

OC

TV

TELEVISION SYSTEM

CABLE TELEVISION OUTLET FOR FLAT PANEL MONITOR. WALL MOUNT AT 60"

AFF TO CENTER, UON. SEE 3/E-ET5.001 FOR DETAIL

AMPLIFIER.

LINE TERMINATOR.

FOUR-OUTPUT CABLE TELEVISION MULTI-TAP DEVICE WITH TAP DOWN

VALUES AS REQUIRED TO MEET PERFORMANCE CRITERIA AS INDICATED IN

THE SPECIFICATIONS.

POWER DISTRIBUTION

PANELBOARD, FLUSH MOUNTED AT 72" AFF TO TOP.

PANELBOARD, SURFACE MOUNTED AT 72" AFF TO TOP.

DISTRIBUTION PANELBOARD, SURFACE MOUNTED AT 72" AFF TO TOP.

DISCONNECT SWITCH, SEE DISCONNECT SWITCH SCHEDULE ON

SHEET E-EP7.003. MOUNT AT 72" AFF TO TOP

COMBINATION MAGNETIC STARTER/DISCONNECT SWITCH. SEE

MOTOR STARTER SCHEDULE ON SHEET E-EP7.002. MOUNT AT 72"

AFF TO CENTER.

VARIABLE FREQUENCY DRIVE. SEE VARIABLE FREQUENCY DRIVE

SCHEDULE ON SHEET E-EP7.002.

PARALLEL CONNECTED SURGE SUPPRESSOR. SEE SURGE

SUPPRESSOR SCHEDULE ON SHEET E-EP7.002.

DS1

ST-1

SS

TVSS-1

VFD

VFD-1

GENERATOR

MOTOR CONNECTION.

JUNCTION BOX OR PULL BOX

DESCRIPTION

J

G

CONNECTION TO EQUIPMENT LEADS, TERMINAL STRIPS OR CONTROL

PANEL INCLUDING ALL CONDUCTORS, CONDUIT, FLEXIBLE CONDUIT,

JUNCTION BOXES, CONNECTORS, FITTINGS, ETC. REQUIRED FOR

PROPER CONNECTION. SUBSCRIPT INDICATES EQUIPMENT

CONNECTION NUMBER. SEE EQUIPMENT CONNECTION SCHEDULE ON

SHEETE-EP7.002.

E E1

H

A

O

OVERLOAD RELAY CONTACT.

PILOT LIGHT "R" INDICATES RED, "G" INDICATES GREEN

NORMALLY CLOSED CONTACT (N.C.)

NORMALLY OPEN CONTACT (N.O.)

OL

CONTROL CIRCUIT FUSE.

OPERATING COIL

NORMALLY OPEN PUSH BUTTON.

NORMALLY CLOSED PUSH BUTTON.

NORMALLY OPEN MUSHROOM HEAD PUSH BUTTON.

CONDUCTOR CONNECTION.

HAND-OFF-AUTOMATIC SELECTOR SWITCH

NORMALLY CLOSED MUSHROOM HEAD PUSH BUTTON.

C

R

CONTROL DIAGRAM

SINGLE LINE DIAGRAM

CIRCUIT BREAKER WITH NUMBER OF POLES AND TRIP RATING AS

INDICATED. SUBSCRIPTS INDICATE THE FOLLOWING:

ELECTRONIC TRIP, SOLID STATE CIRCUIT BREAKER.

CIRCUIT BREAKER EQUIPPED WITH INTEGRAL GROUND

FAULT PROTECTION.

ET -

GFP -

CIRCUIT BREAKER WITH SHUNT TRIP COIL AND WITH NUMBER OF

POLES AND TRIP RATING AS INDICATED. SUBSCRIPTS INDICATE THE

FOLLOWING:

ELECTRONIC TRIP, SOLID STATE CIRCUIT BREAKER.

CIRCUIT BREAKER EQUIPPED WITH INTEGRAL GROUND

FAULT PROTECTION.

ET -

GFP -

DRAW-OUT TYPE CIRCUIT BREAKER WITH NUMBER OF POLES AND

TRIP RATING AS INDICATED. SUBSCRIPTS INDICATE THE FOLLOWING:

ELECTRONIC TRIP, SOLID STATE CIRCUIT BREAKER.

CIRCUIT BREAKER EQUIPPED WITH INTEGRAL GROUND

FAULT PROTECTION.

ET -

GFP -

DRY TYPE TRANSFORMER. SEE TRANSFORMER SCHEDULE ON

SHEET E-EP7.002. SEE SHEET E-EP6.006 FOR GROUNDING DIAGRAM.

AUTOMATIC TRANSFER SWITCH.

AUTOMATIC TRANSFER SWITCH WITH CENTER OFF POSITION.

MULTI FUNCTION DIGITAL POWER CIRCUIT MONITOR.

KEY INTERLOCK

SURGE ARRESTOR WITH RATINGS INDICATED.

POWER TRANSFORMER WITH DELTA CONNECTED PRIMARY, WYE

CONNECTED SECONDARY AND RATING AS INDICATED.

FEEDER CONTINUATION SYMBOL

FEEDER REFERENCE

SHEET ON WHICH FEEDER IS CONTINUED

EQUIPMENT OR PANEL TO WHICH FEEDER IS CONNECTED

PANELBOARD

WHEN PRESENT, INDICATES PANELBOARD WITH MAIN CIRCUIT

BREAKER. SEE PANEL SCHEDULE FOR SIZE. IF NOT PRESENT,

PANELBOARD WITH MAIN LUGS ONLY.

WHEN PRESENT, INDICATES PANELBOARD WITH FEED THROUGH

LUGS.

100A 3P

C 100A 3P

100A 3P

T

N E

M

K

A1

EP602

1AHNDP

1AHN1

N E

MICROPROCESSOR BASED OVERCURRENT RELAY WITH THE

FOLLOWING FUNCTIONS:

PHASE OVERCURRENT (51) ELEMENT

PHASE INSTANTANEOUS (50) ELEMENT

GROUND TIME OVERCURRENT (51G) ELEMENT

GROUND INSTANTANEOUS (50) ELEMENT

INTEGRAL POWER MONITORING LOCK-OUT RELAY (86)

1200AF

200AT52 DRAW-OUT TYPE, MEDIUM VOLTAGE, VACUUM CIRCUIT BREAKER.

FRAME RATING.

OVERCURRENT RELAY TRIP SETTING.

TC MEDIUM VOLTAGE CIRCUIT BREAKER TRIP COIL.

(3) CURRENT TRANSFORMERS WITH RATING AS INDICATED.600:5

MEDIUM VOLTAGE SWITCH WITH RATING. SUBSCRIPTS AS FOLLOWS:

SWITCH IS NORMALLY OPEN.

SWITCH IS NORMALLY CLOSED.

MEDIUM VOLTAGE FUSE WITH RATING.100A

C 200A

CIRCUIT BREAKER EQUIPPED WITH GROUND FAULT

MONITORING RELAY. BREAKER SHALL NOT TRIP ON

GROUND FAULT, BUT CAUSE ALARM ANNUNCIATION ONLY.

GFM -

CIRCUIT BREAKER EQUIPPED WITH GROUND FAULT

MONITORING RELAY. BREAKER SHALL NOT TRIP ON

GROUND FAULT, BUT CAUSE ALARM ANNUNCIATION ONLY.

GFM

CIRCUIT BREAKER EQUIPPED WITH GROUND FAULT

MONITORING RELAY. BREAKER SHALL NOT TRIP ON

GROUND FAULT, BUT CAUSE ALARM ANNUNCIATION ONLY.

GFM

MEDIUM VOLTAGE TERMINATION.

MICROPROCESSOR BASED OVERCURRENT RELAY WITH THE

FOLLOWING FUNCTIONS:

PHASE OVERCURRENT (51) ELEMENT

PHASE INSTANTANEOUS (50) ELEMENT

GROUND TIME OVERCURRENT (51G) ELEMENT (ANNUNCIATION

ONLY)

GROUND INSTANTANEOUS (50) ELEMENT (ANNUNCIATION ONLY)

INTEGRAL POWER MONITORING LOCK-OUT RELAY (86)

A

RELAY

RELAY ELECTRONIC TRIP SOLID STATE CIRCUIT BREAKER

WITH INTEGRAL POWER METERING AND BREAKER

STATUS. POWER METERING AND BREAKER STATUS

SHALL BE CONNECTED TO POWER MONITORING SYSTEM

VIA NETWORK CABLING.

ETM -

ELECTRONIC TRIP SOLID STATE CIRCUIT BREAKER

WITH INTEGRAL POWER METERING AND BREAKER

STATUS. POWER METERING AND BREAKER STATUS

SHALL BE CONNECTED TO POWER MONITORING SYSTEM

VIA NETWORK CABLING.

ETM -

ELECTRONIC TRIP SOLID STATE CIRCUIT BREAKER

WITH INTEGRAL POWER METERING AND BREAKER

STATUS. POWER METERING AND BREAKER STATUS

SHALL BE CONNECTED TO POWER MONITORING SYSTEM

VIA NETWORK CABLING.

ETM -

MOTOR CONTROL CENTER.EMCCE1

POTENTIAL TRANSFORMER

N.O N.C

AUTOMATIC POWER FACTOR CORRECTION SYSTEM.

THERMAL MAGNETIC CIRCUIT BREAKER.

MOTOR CONTROL CENTER LEGEND

MOTOR CIRCUIT PROTECTOR.MCP

NUMBER OF POLES.

CB

P

OC DEVICES (OVERCURRENT DEVICES):

STARTER:

STARTER SIZE (NEMA), "BLANK" INDICATES SIZE 0 STARTER.SIZE

TYPE OF STARTER, SEE DEFINITIONS BELOW. "BLANK"

INDICATES CIRCUIT BREAKER ONLY, NO STARTER REQUIRED.

TYPE

FULL VOLTAGE NON REVERSING STARTER.FVNR

REDUCED VOLTAGE, SOLID STATE "SOFT START" NON REVERSING STARTER.RVNR

TWO SPEED STARTER.2SPD

AD L

EK

N

LL

E F

S

R P

O

IS

EN

L

GI

O N A

E E

N R

EC NIL

S E

No 0052705

STATE OF

ROLF

I D A

EE

AS

M

ON

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

OFFICE OF

FACILITIES

MANAGEMENT

on e ei gh th in ch o ne fo ot

B

A

C

D

E

F th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

BUILDING IS FULLY SPRINKLERED

A NEW HOSPITAL FOR

VAMC ORLANDO, FLORIDA

Orlando, Florida

673-950

Professional Seals:

29 OCTOBER, 2009 KLM EB/RLF

CENTRAL ENERGY PLANT

E-EG0.002

ELECTRICAL LEGEND

O vied oF L, 3 276 5

EB

2-

1 NB

2-

B 2-

N1

NA2-

EA2-

A2- N10

A2-E11(B) A2-N11(B)

B2-N2(B)

B2-E2(B)

A2-E11(B) A2-N11(B)

OUC-13(B) OUC-22(B) OUC-23(B)

A2-E10

B 2-

E1

EH1

EH2

EH1

EH1

EH1

EH1 EH2

EH2 EH1

EH1 EH2

EH2 EH1

EH1

EH1

EH1 EH2 EH1 EH1 EH2 EH1

EH1

EH2

EH1

EH1

EH2

EH1

EX1

EX1

EX1

EX1

EX1 EX1 EX1

EX1

EX1

EX1

EX1

EH2

EH3

EH2

EH3

1A115A

1A109B 1A109A

1A109

1A101B

EH1

EH2

EH1

EH1

EH2

EH1

EH2

EH1

EH2

EH1

EH1

EH2

EH1

EH2

EH1

EH1

EH2

EH1

EH2

EH1

EH1

EH2

EH1

EH2

EH1

EH1

EH1

3a 3b b a b a a b a b a a b a b a a b a b a a b a b a

E2

MD

RE

F

LI

NE

E-

EL

1.

1B

3b a a a

2EH1

EH1

E1

ME

EH1

EH1EH2

EH2

EH1

EH2

EH1

EH2

EH1

EH1

a b a b a

3a 3b

EH4

EH1

ES3 ES3 ES3

ES3

ES3

ES3

ES3

E5 E6

EA EA

EE

E4

1A115B

EH3

EH1 EH2 EH1 EH2 EH1

EH1EH2EH1EH2EH1

EH1

EH1

EH1 EH1

EH1EH1

EH1 EH2

EH2

EH2EH2

EH2

EH1 EH1

EH1 EH2 EH1 EH1 EH2 EH1

EH1 EH2 EH1 EH1 EH2 EH1

EH2 EH2 EH1 EH1 EH2 EH1

EH1

EH1

a

4a 4b

EHS1-1

EHS1-2 EH2

EH3

EH2

EH3

EH2

EH1

EH2

EH1

EH1

EH2

EH1

EH2

EH1

EH1

EH2

EH1

EH2

EH1

EH1

EH2

EH1

EH2

EH1

EH1

b a b a a b a b a a b a b a a b a b a a b a b a

EH2

EH1

EH2

EH1

EH1

a b a b a

EH1

a

3a 3b

3b 3a4a 4b

EHS2-1

ES3

EHS2-2

4 3a

4a 3b a a a

EHS1-4

4b 3a b b b

EHE1A-1

b b b b b b b b b b a b b b b b b b

7b b

1A115

EX1

EX1

EHS1-6

EHE1A-3

EH2EH1

EH1

EH1 EH2

EH2

EH1 EH1EH2

EH2

EH1EH2 EH1

EH1

EH1

EH1 EH1

a a a a a a a a a a a a a a a a a

EHS1-5

EHE1A-2

EHS2-3

1A109

1A105

1A115B a ab

7EH1

EHS1-3

EH1 EH1

a b

EHS2-4

EH1

a

EX1

ab7

ES6 ES6 ES6 ES6ES6 ES6

EHE1A-17

1A101A

1A101

EP1EP1

10EP1 10 EP110 10

ES3

ES3

ES3

AD L

EK

N

LL

E F

S

R P

O

IS

EN

L

GI

O N A

E E

N R

EC NIL

S E

No 0052705

STATE OF

ROLF

I D A

EE

AS

M

ON

N

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

OFFICE OF

FACILITIES

MANAGEMENT

on e ei gh th in ch o ne fo ot

B

A

C

D

E

F th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

BUILDING IS FULLY SPRINKLERED

A NEW HOSPITAL FOR

VAMC ORLANDO, FLORIDA

Orlando, Florida

673-950

NOTES:

SHEET NOTES:

1/8" = 1'-0" GRAPHIC SCALE

4' 8' 24'16'

KEY PLAN

LEVEL1, AREA A

A B C

D

Professional Seals:

29 OCTOBER, 2009 KLM EB/RLF

CENTRAL ENERGY PLANT

E-EL1.1A

LIGHTING PLAN - AREA A

1 MOUNT ALL LIGHTING FIXTURES IN THIS ROOM AT 16' AFF

TO BOTTOM.

2 MOUNT ALL LIGHTING FIXTURES IN THIS ROOM AT 12' AFF

TO BOTTOM.

3 FIXTURES THAT ARE ALIGNED IN A ROW SHALL BE

MOUNTED TO A CONTINUOUS STEEL CHANNEL, SEE

5/E-EP5.005 FOR DETAIL.

4 HOMERUN VIA LIGHTING CONTACTOR "ELC-1", SEE

3/E-EL5.003 FOR WIRING DIAGRAM.

5 HOMERUN VIA LIGHTING CONTACTOR "ELC-2", SEE

1/E-EL5.003 FOR WIRING DIAGRAM. PROVIDE UNSWITCHED

PHASE CONDUCTOR CONNECTED AHEAD OF THE

CONTACTOR TO SERVE THE BATTERY BALLASTS.

6 HOMERUN VIA LIGHTING CONTACTOR "ELC-3", SEE

2/E-EL5.003 FOR WIRING DIAGRAM. PROVIDE UNSWITCHED

PHASE CONDUCTOR CONNECTED AHEAD OF THE

CONTACTOR TO SERVE THE BATTERY BALLASTS.

7 MOMENTARY CONTACT SWITCHES, SWITCH "a" CONTROLS LIGHTING CONTACTOR "ELC-2" AND SWITCH "b" CONTROLS

LIGHTING CONTACTOR "ELC-3". SEE 1/E-EL5.003 AND

2/E-EL5.003 FOR WIRING DIAGRAMS AND SWITCH

REQUIREMENTS.

8 CONTINOUSLY ILLUMINATED LIGHT FIXTURE. DO NOT

CONNECT TO SWITCH.

9 HOMERUN VIA LIGHTING CONTACTOR "ELC-6", SEE

6/E-EL5.003 FOR WIRING DIAGRAM.

10 1"C - 2 #10 + 1 #10 GND AT 24" BELOW FINISHED GRADE.

11 SEE SHEET E-EL1.1D FOR CONTINUATION.

12 COORDINATE LOCATION OF POLE WITH OUC TO VERIFY

PROPER WORKING CLEARANCES AROUND OUC

EQUIPMENT.

KEY NOTES:

A.

B.

SEE SHEETS E-EP4.005 AND E-EP4.006 FOR LOCATION OF

PANELBOARDS AND CONTACTORS SERVING THE

LIGHTING CIRCUITS IN THIS AREA.

PROVIDE "UN-SWITCHED" PHASE CONDUCTOR FOR ALL

FLUORESCENT LIGHTING FIXTURES THAT ARE EQUIPPED

WITH BATTERY BALLAST.

D. PROVIDE OPENINGS AS REQUIRED IN THE TILT-UP WALL

FOR THE EXTERIOR WALL MOUNTED LIGHT FIXTURES.

COORDINATE OPENING REQUIREMENTS WITH THE TILT-UP

WALL PROVIDER

E. ALL INTERIOR SWITCHES MOUNTED ON THE PERIMETER

TILT-UP WALLS SHALL BE SURFACE MOUNTED. ALL OTHER

SWITCHES SHALL BE FLUSHED MOUNTED

C. COORDINATE THE LOCATIONS OF ALL LIGHTING FIXTURES

WITH MECHANICAL EQUIPMENT, DUCTWORK AND PIPING.

ADJUST LOCATIONS AS REQUIRED TO SUIT THE ACTUAL

INSTALLATION.

UP

SL

EX1

EC1

EX1

EH1EH1

EH1EH1

MB

MD

E8 E9 E11E10 E12 E13 E15

RE

F

LI

NE

E-

EL

1.

1A

4a

3a

ME

EC2

EC1

EC1

ES3

EE1

EE1

EX1

E5 E6

EA

EE

EH1

EH1 EH1

EH1

EH5 EH5

EH5 EH5

2 2 2

EH1 EH1 EH1 EH1

U a a

U a U

6 6

ES3

ES1

EX1

EX1

ES1 ES1 ES1

ES3 ES3

3 3

EF2EF2

EF2 EF2a a a a a aa

EH1

EH1

EH1 EH1

EH1

EH1

EHE1A-15

3a

EF2

EHE1A-16

a

3a

EC3

EC3

EC3

EC3

EC3

EC3

3FD

EHE1A-5

E-EL4.001

1A108

1A108B

1A110A

1AC01

1A110AB

1A118

1A106B

1A102

1A106C

1A104 1A116

1A114

1A106

1A208

EH1 EH1

EC1

a

EC1

a

EX1

3a

EHE1A-4

ES3

ES3

ES3

ES3

EB1

EB1

EC1 EC1

EC1 EC1

U

U

EB1

EF1 EF1

EE2

a b aa b

EE1

EF1

EE1

a

EH1 EH1

EE1

b

U

EHE1A-6

EE2

a b b

EE1

EE1

EF1

EE1

a b

EE1

a

EE1

a

U

EF1EF1

a a

U

EHS2-5

REF LINE

E-EL1.1D

a a

EHS2-9

EHS1-7

ES3

EH1

EH1

EH1

EH1

ES3

EG1

EG1

a a a

EHS1-9

EE1

ES3

ES3

ES3

EE1

a

AD L

EK

N

LL

EF S

R P

O

IS EN

L

GI

O N A

E E

N R

EC NIL

S E

No 0052705

STATE OF

ROLF

I D A

EE AS

M

ON

N

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

OFFICE OF

FACILITIES

MANAGEMENT

on e ei gh th in ch o ne fo ot

B

A

C

D

E

F th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

BUILDING IS FULLY SPRINKLERED

A NEW HOSPITAL FOR

VAMC ORLANDO, FLORIDA

Orlando, Florida

673-950

NOTES:

SHEET NOTES:

1/8" = 1'-0" GRAPHIC SCALE

4' 8' 24'16'

KEY PLAN

LEVEL1, AREA B

A B C

D

Professional Seals:

29 OCTOBER, 2009 KLM EB/RLF

CENTRAL ENERGY PLANT

E-EL1.1B

LIGHTING PLAN - AREA B

1 UP TO LIGHT FIXTURES ON MEZZANINE LEVEL ABOVE.

SEE SHEET E-EL1.1B1 FOR CONTINUATION.

2 MOUNT LIGHTING FIXTURE TO THE UNDERSIDE OF

FINISHED CATWALK STRUCTURE. SUSPEND FIXTURE AT

12' - 0" A.F.F.

3 MOUNT LIGHTING FIXTURE TO THE UNDERSIDE OF

FINISHED MEZZANIE FLOOR. SUSPEND AT 9' - 0" AFF TO

BOTTOM.

4 OCCUPANCY SENSOR CONTROLS THE LIGHTING

FIXTURES IN CORRIDOR 1AC01, SEE 7/E-EL5.003 FOR

WIRING DIAGRAM.

5 CORRIDOR OVERRIDE SWITCH, SEE 7/E-EL5.003 FOR

WIRING DIAGRAM.

6 MOMENTARY CONTACT SWITCH CONTROLS LIGHTING

CONTACTOR "ELC-4". SEE 4/E-EL5.003 FOR WIRING

DIAGRAMS AND SWITCH REQUIREMENTS.

7 MOMENTARY CONTACT SWITCH CONTROLS LIGHTING

CONTACTOR "ELC-5". SEE 5/E-EL5.003 FOR WIRING

DIAGRAMS AND SWITCH REQUIREMENTS.

8 CONNECT TO CIRCUIT EHE1A-12. SEE SHEET E-EL1.1B1

FOR CONTINUATION.

9 HOMERUN VIA LIGHTING CONTACTOR "ELC-1", SEE

3/E-EL5.003 FOR WIRING DIAGRAM.

10 WALL MOUNT LIGHTING FIXTURE AT 8' - 0" AFF.

11 CONNECT TO OVERCOUNTER RECEPTACLE CIRCUIT IN

ROOM 1A102. REFER TO E-EP1.1B FOR CONTINUATION.

12 HOMERUN VIA LIGHTING CONTACTOR "ELC-1", SEE

3/E-EL5.003 FOR WIRING DIAGRAM.

KEY NOTES:

A.

B.

SEE SHEETS E-EP4.005 AND E-EP4.006 FOR LOCATION

OF PANELBOARDS AND CONTACTORS SERVING THE

LIGHTING CIRCUITS IN THIS AREA.

PROVIDE "UN-SWITCHED" PHASE CONDUCTOR FOR ALL

FLUORESCENT LIGHTING FIXTURES THAT ARE EQUIPPED

WITH BATTERY BALLAST.

C. COORDINATE THE LOCATIONS OF ALL LIGHTING FIXTURES

WITH MECHANICAL EQUIPMENT, DUCTWORK AND PIPING.

ADJUST LOCATIONS AS REQUIRED TO SUIT THE ACTUAL

INSTALLATION.

D. PROVIDE OPENINGS AS REQUIRED IN THE TILT-UP WALL

FOR THE EXTERIOR WALL MOUNTED LIGHT FIXTURES.

COORDINATE OPENING REQUIREMENTS WITH THE TILT-UP

WALL PROVIDER

E. ALL INTERIOR SWITCHES MOUNTED ON THE PERIMETER

TILT-UP WALLS SHALL BE SURFACE MOUNTED. ALL OTHER

SWITCHES SHALL BE FLUSHED MOUNTED

No. Description Date

1 CPR 009 08/20/10

2 CPR 018 02/18/11

SD SD SD

SDSD

SD

SD

SD

UP

UP

DN

MB

MD

E8 E9 E11E10 E12 E13 E15

ME

E5 E6

EA

EE

EH1

EH1

EH1

EH1 EH2 EH1

EH1EH1 EH1

EH1 EH1

EH2 EH1 EH1

EH1 EH1 EH2 EH1

EH1EH1

EH1EH1

EH1EH1 EH1

EH1

EH1

EH1

EH1

EH1

EH1

EH1 EH1 EH1 EH1

EH1

EH1

EH1

EH1

EH1

EH1

EH1

EH1

EH1

EH1

EH1

EH1

EH1

EH1 EH1 EH1 EH1 EH1

EH1 EH2 EH1 EH1 EH2

EH1EH1EH1EH1EH1EH1

EH1

EH1

EH1 EH1 EH1

EH1

EH1

EH1

EH1

EH1

EH1

EH1

EH1

EH1

EH2

EH1 EH1

EH1 EH1 EH2

EH1

EH1

EH1

EH1

EH1

EH1

EH1EH1EH1EH1EH1

EH1

EH1

EH1

EH1

EH1

EH1 EH1 EH1 EH1 EH1 EH1

EH1

EH1

EH1

EH1

EH1

EH1

2 2

2 2

EHE1A-8

EH1

EH1

EH1

EH1

EHE1A-9

EHE1A-10

EHE1A-11 EHE1A-12

EHS2-7

f f f ff e e e e e e

EHE1A-13

f

EHS2-6

EHE1A-7

EH1 EH1

EH1 EH1 EH1 EH1

1A208

1A112

AD L

EK

N

LL

EF S

R P

O

IS EN

L

GI

O N A

E E

N R

EC NIL

S E

No 0052705

STATE OF

ROLF

I D A

EE AS

M

ON

N

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

OFFICE OF

FACILITIES

MANAGEMENT

on e ei gh th in ch o ne fo ot

B

A

C

D

E

F th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

BUILDING IS FULLY SPRINKLERED

A NEW HOSPITAL FOR

VAMC ORLANDO, FLORIDA

Orlando, Florida

673-950

NOTES:

SHEET NOTES:

1/8" = 1'-0" GRAPHIC SCALE

4' 8' 24'16'

KEY PLAN

LEVEL 2,AREA B

A B C

D

Professional Seals:

29 OCTOBER, 2009 KLM EB/RLF

CENTRAL ENERGY PLANT

E-EL1.1B1

LIGHTING PLAN - UPPER LEVEL - AREA B

1 MOUNT AT 9' - 0" ABOVE THE FINISHED MEZZANINE FLOOR

TO BOTTOM OF FIXTURE.

2 MOUNT LIGHT FIXTURE AT 14' - 0" ABOVE THE FINISHED

MEZZANINE FLOOR TO BOTTOM OF FIXTURE.

3 MOUNT LIGHT FIXTURE AT 17' - 0" ABOVE THE FINISHED

MEZZANINE FLOOR TO BOTTOM OF FIXTURE.

4 MOUNT ALL LIGHTING FIXTURES IN THIS ROOM AT 22' - 6"

AFF TO BOTTOM OF FIXTURE.

5 FIXTURES THAT ARE ALIGNED IN A ROW SHALL BE

MOUNTED TO A CONTINUOUS STEEL CHANNEL, SEE

5/E-EP5.005 FOR DETAIL.

6 MOUNT ALL LIGHTING FIXTURES IN THIS ROOM AT 16' - 6"

AFF TO BOTTOM OF FIXTURE.

7 HOMERUN VIA LIGHTING CONTACTOR "ELC-4", SEE

4/E-EL5.003 FOR WIRING DIAGRAM.

8 HOMERUN VIA LIGHTING CONTACTOR "ELC-5", SEE

5/E-EL5.003 FOR WIRING DIAGRAM.

10 DOWN TO LIGHTING FIXTURE "EH1" IN ROOM 1A114. SEE

SHEET E-EL1.1B FOR CONTINUATION.

11 DOWN TO LIGHTING FIXTURES ON UNDERSIDE OF

CATWALK, SEE SHEET E-EL1.1B FOR CONTINUATION.

KEY NOTES:

A.

B.

SEE SHEET E-EP4.006 FOR LOCATION OF PANELBOARDS

AND CONTACTORS SERVING THE LIGHTING CIRCUITS IN

THIS AREA.

PROVIDE "UN-SWITCHED" PHASE CONDUCTOR FOR ALL

FLUORESCENT LIGHTING FIXTURES THAT ARE EQUIPPED

WITH BATTERY BALLAST.

C. COORDINATE THE LOCATIONS OF ALL LIGHTING FIXTURES

WITH MECHANICAL EQUIPMENT, DUCTWORK AND PIPING.

ADJUST LOCATIONS AS REQUIRED TO SUIT THE ACTUAL

INSTALLATION.

D. PROVIDE OPENINGS AS REQUIRED IN THE TILT-UP WALL

FOR THE EXTERIOR WALL MOUNTED LIGHT FIXTURES.

COORDINATE OPENING REQUIREMENTS WITH THE TILT-UP

WALL PROVIDER

E. ALL INTERIOR SWITCHES MOUNTED ON THE PERIMETER

TILT-UP WALLS SHALL BE SURFACE MOUNTED. ALL OTHER

SWITCHES SHALL BE FLUSHED MOUNTED

1 AMENDMENT 12/07/09

EA2-

OUC-23(B)

2-E10

UP UP

E8 E9 E11E10 E12 E13 E15

ME

E5 E6 E18 E19

EE

REF LINE

E-EL1.1B

ES5

ES5

ES5

ES5

ES5

ES5

ES5

ES5

ES5

ES5

ES5

ES5

FUTURE

COOLING

TOWER

EP2 EP2 EP2 EP2

EP1EP1EP1EP1

3/WP 3/WP

EHE1C-3,5

3 3 3 3 3

8 8 8 8 8

9 9

7 7 7 7

7 7 7

EHE1C-1

AD L

EK

N

LL

E F

S

R P

O

IS

EN

L

GI

O N A

E E

N R

EC NIL

S E

No 0052705

STATE OF

ROLF

I D A

EE

AS

M

ON

N

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

OFFICE OF

FACILITIES

MANAGEMENT

on e ei gh th in ch o ne fo ot

B

A

C

D

E

F th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

BUILDING IS FULLY SPRINKLERED

A NEW HOSPITAL FOR

VAMC ORLANDO, FLORIDA

Orlando, Florida

673-950

NOTES:

KEY NOTES:

1/8" = 1'-0" GRAPHIC SCALE

4' 8' 24'16'

KEY PLAN

LEVEL1,

A B C

D

AREA D

Professional Seals:

29 OCTOBER, 2009 KLM EB/RLF

CENTRAL ENERGY PLANT

E-EL1.1D

LlGHTING PLAN - AREA D

1 PROVIDE GALVANIZED STEEL SUPPORT STRUCTURE AS

REQUIRED FOR MOUNTING OF SWITCH. MOUNT

SWITCH AT 48" ABOVE THE ENTRY LEVEL TO THE STAIR.

2 1 1/4"C - 2 #8 + 1 #8 GND FROM UNDERGROUND PULL

BOX TO PANELBOARD. BURY AT 24" BELOW FINISHED

GRADE.

3 3/4"C - 2#10 + 1 #10 GND. CONCEAL CONDUIT TO

GREATEST EXTENT POSSIBLE ON THE UNDERSIDE OF

THE COOLING TOWER FAN DECK. CONDUIT SHALL BE

RIGID GALVANIZED STEEL. PROVIDE PULL BOXES AS

REQUIRED.

4 PROVIDE 12" X 12" X 24" DEEP (MINIMUM) POLYMER

CONCRETE OPEN BOTTOM UNDERGROUND PULL BOX

WITH COVER LOGO STATING "LIGHTING". MOUNT SUCH

THAT LID IS FLUSH WITH FINSIHED GRADE MATERIAL.

MOUNT BOX ON A 12" DEEP BED OF CRUSHED GRAVEL,

EXTEND GRAVEL 6" BEYOND BOX ON ALL SIDES.

COVER SHALL BE RATED FOR A STATIC DESIGN LOAD

OF 22,500 LBS. PROVIDE UL LISTED WATER PROOF

SPLICES IN PULL BOX.

5 3/4"C - 2#10 + 1 #10 GND FROM PULL BOX TO COOLING

TOWER AT 24" BELOW FINISHED GRADE. TRANSITION

TO RIGID GALVANIZED STEEL CONDUIT 6" BELOW

GRADE AND THEN RISE UP AND EXTEND UP COOLING

TOWER STRUCTURE TO FIXTURES AT FAN DECK

ABOVE.

6 MOUNT FIXTURE ON COOLING TOWER STRUCTURAL

COLUMN AT 7' - 6" ABOVE FAN DECK LEVEL, SEE

1/E-EL7.001 FOR DETAIL. TYPICAL FOR ALL.

7 1"C - 2 #10 + 1 #10 GND AT 24" BELOW FINISHED GRADE.

8 3/4"C - 4 #10 + 1 #10 GND. CONCEAL CONDUIT TO

GREATEST EXTENT POSSIBLE ON THE UNDERSIDE OF

THE COOLING TOWER FAN DECK. CONDUIT SHALL BE

RIGID GALVANIZED STEEL. PROVIDE PULL BOXES AS

REQUIRED.

9 3/4"C - 3 #10 + 1 #10 GND. CONCEAL CONDUIT TO

GREATEST EXTENT POSSIBLE ON THE UNDERSIDE OF

THE COOLING TOWER FAN DECK TO SWTICH. CONDUIT

SHALL BE RIGID GALVANIZED STEEL. PROVIDE PULL

BOXES AS REQUIRED.

10 SEE SHEET E-EL1.1A FOR CONTINUATION.

ME

E18 E19

EE

ES2

ES2

ES2

ES2

ES2

ES2

ES2

ES2

ES2

ES2

ES2

ES2

ES2

EHE2B-4

EHE2B-2

ES7

AD L

EK

N

LL

E F

S

R P

O

IS

EN

L

GI

O N A

E E

N R

EC NIL

S E

No 0052705

STATE OF

ROLF

I D A

EE

AS

M

ON

N

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

OFFICE OF

FACILITIES

MANAGEMENT

on e ei gh th in ch o ne fo ot

B

A

C

D

E

F th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

BUILDING IS FULLY SPRINKLERED

A NEW HOSPITAL FOR

VAMC ORLANDO, FLORIDA

Orlando, Florida

673-950

NOTES:

KEY NOTES:

1/8" = 1'-0" GRAPHIC SCALE

4' 8' 24'16'

KEY PLAN

LEVEL 2,AREA C

A B C

D

Professional Seals:

29 OCTOBER, 2009 KLM EB/RLF

CENTRAL ENERGY PLANT

E-EL1.2C

LIGHTING PLAN - WATER TANK

1 3/4" LIQUID TIGHT, FLEXIBLE METAL CONDUIT WITH 2 #10

+ 1 #10 GND. CONDUIT SHALL BE OIL AND ULTRAVIOLET

LIGHT (UV) RESISTANT. ROUTE CONDUIT ON TOP OF

DECORATIVE TRELLIS CONCEALED FROM VIEW BELOW.

2 1 1/4"C - 2 #6 + 1 #6 GND FROM UNDERGROUND PULL

BOX TO PANELBOARD. BURY AT 24" BELOW FINSHED

GRADE.

3 PROVIDE 12" X 12" X 24" DEEP (MINIMUM) POLYMER

CONCRETE OPEN BOTTOM UNDERGROUND PULL BOX

WITH COVER LOGO STATING "LIGHTING". MOUNT SUCH

THAT LID IS FLUSH WITH FINSIHED GRADE MATERIAL.

MOUNT BOX ON A 12" DEEP BED OF CRUSHED GRAVEL,

EXTEND GRAVEL 6" BEYOND BOX ON ALL SIDES.

COVER SHALL BE RATED FOR A STATIC DESIGN LOAD

OF 22,500 LBS. PROVIDE UL LISTED WATER PROOF

SPLICES IN PULL BOX.

4 3/4" C - 2 #10 +1 #10 GND FROM PULL BOX TO WATER

TOWER AT 24" BELOW FINISHED GRADE. TRANSITION

TO RIGID GALVANIZED STEEL CONDUIT 6" BELOW

GRADE, THEN EXTEND UP WATER TOWER STRUCTURE

TO FIXTURES AT DECORATIVE TRELLIS ABOVE.

5 FASTEN CONDUIT TO "STAND-OFF" BRACKETS

PROVIDED BY THE WATER TOWER MANUFACTURER.

COORDINATE THE INSTALLATION OF THE CONDUIT WITH

THE WATER TOWER MANUFACTURER.

6 MOUNT FIXTURE ON DECORATIVE TRELLIS AT THE TOP

OF THE WATER TOWER AND AIM TO ILLUMINATE THE

FACE OF THE WATER TOWER. SEE 4/E-AE5.102 FOR

MOUNTING DETAIL. COORDINATE EXACT MOUNTING

REQUIREMENTS WITH THE WATER TOWER AND TRELLIS

MANUFACTURER. TYPICAL FOR ALL.

7 MOUNT AVIATION OBSTRUCTION LIGHT ON TOP OF

WATER TOWER. ATTACHED TO BRACKET PROVIDED

WITH WATER TOWER. COORDINATE INSTALLATION

WITH WATER TOWER SUPPLIER.

8 3/4" LIQUID TIGHT, FLEXIBLE METAL CONDUIT WITH 2

#10 + 1 #10 GND. CONDUIT SHALL BE OIL AND

ULTRAVIOLET LIGHT (UV) RESISTANT. ROUTE CONDUIT

ON TOP OF WATER TOWER AND FASTEN TO BRACKETS

PROVIDED WITH THE WATER TOWER. COORDINATE

INSTALLATION WITH THE WATER TOWER SUPPLIER.

UP DN

MB

E9 E10

EF2 dEF2 d

EF2

d

EF2

d

EF2

d

EF2

d d

EHE1A-18

SUBLEVEL

MAIN LEVEL

CATWALK

LEVEL 2

CATWALK LEVEL 1

ROOF HATCH

8"

8"

8"

8"

8"

/2

3bS

3bS3cS

3cS

EF3

b

EF3

d

EF3

b

EF3

c

EF3

c

EF3

c

1 EHS2-101

AD L

EK

N

LL

E F

S

R P

O

IS

EN

L

GI

O N A

E E

N R

EC NIL

S E

No 0052705

STATE OF

ROLF

I D A

EE

AS

M

ON

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

OFFICE OF

FACILITIES

MANAGEMENT

on e ei gh th in ch o ne fo ot

B

A

C

D

E

F th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

BUILDING IS FULLY SPRINKLERED

A NEW HOSPITAL FOR

VAMC ORLANDO, FLORIDA

Orlando, Florida

673-950

NOTES:

KEY NOTES:

1/4" = 1'-0" GRAPHIC SCALE

2' 4' 12'8'0

Professional Seals:

29 OCTOBER, 2009 KLM EB/RLF

CENTRAL ENERGY PLANT

E-EL4.001

ENLARGED PLAN

1/4" = 1'-0"1

ENLARGED PLAN - SUB-BASE LEVEL 1A106D

LIGHTING

1 TYPICAL WALL MOUNTED SWITCH SERVING THE STAIR

LIGHTING FIXTURES. MOUNT 48" AFF AT THE LANDING AS

INDICATED.

2 WALL MOUNT FIXTURE AT 9'-0" AFF TO CENTER OF

FIXTURE.

3 LIGHTING FIXTURE SERVING STAIRWELL. MOUNTING

HEIGHT AS INDICATED.

4 TYPICAL LIGHTING FIXTURE TYPE, SEE LIGHTING FIXTURE

SCHEDULE ON SHEET E-EL7.001 FOR REQUIREMENTS.

5 LOWER CASE LETERS INDICATES SWITCH LEG CONTROL,

TYPICAL FOR ALL.

6 SEE SECTION 2/E-EL4.001 FOR STAIR LIGHTING.

1/4" = 1'-0"2 STAIR SECTION - LIGHTING

KEY NOTES:

A.

B.

SEE SHEET E-EP4.006 FOR LOCATION OF PANELBOARDS

SERVING THE LIGHTING CIRCUITS IN THIS AREA.

PROVIDE "UN-SWITCHED" PHASE CONDUCTOR FOR ALL

FLUORESCENT LIGHTING FIXTURES THAT ARE EQUIPPED

WITH BATTERY BALLAST.

C. COORDINATE THE LOCATIONS OF ALL LIGHTING FIXTURES

WITH MECHANICAL EQUIPMENT, DUCTWORK AND PIPING.

ADJUST LOCATIONS AS REQUIRED TO SUIT THE ACTUAL

INSTALLATION.

D. PROVIDE OPENINGS AS REQUIRED IN THE TILT-UP WALL

FOR THE EXTERIOR WALL MOUNTED LIGHT FIXTURES.

COORDINATE OPENING REQUIREMENTS WITH THE TILT-UP

WALL PROVIDER

E. ALL INTERIOR SWITCHES MOUNTED ON THE PERIMETER

TILT-UP WALLS SHALL BE SURFACE MOUNTED. ALL OTHER

SWITCHES SHALL BE FLUSHED MOUNTED

MOUNTING:

NOM. DIMENSIONS:

HOUSING:

REFLECTORS:

ELECTRICAL:

EFFICIENCY: 80%

120/277 VOLT BALLAST

HIGH REFLECTANCE 80% MIN. GLOSS WHITE

LOADED CATCHES. HOUSING SHALL BE CHEMICALLY TREATED

EXTRUDED ALUMINUM LENS FRAME, HINGED REMOVAL AND SPRING-

COLD ROLLED STEEL, FLANGE TO COORDINATE WITH CEILING GRID;

RECESSED

24" W X 4' L X 6" D

100% UV STABALIZED, VIRGIN ACRYLIC,SHIELDING:

BALLAST:

RECESSED CEILING MOUNTEDMOUNTING:

FOR RUST PREVENTION. SPECIFICATION GRADE TROFFER.

BALLAST SHALL BE HIGH POWER

FACTOR .95) PROGRAMMED START

CLASS P ELECTRONIC BALLAST

PRISMATIC LENS, MINIMUM AVERAGE

THICKNESS = 1/8"

WITH A SOUND RATING OF "A".

GENERAL DESCRIPTION

FEATURES

RECESSED LENSED 2'-0" x 4'-0"

FLUORESCENT TROFFER

24" NOM

1/

2" N

O M

CONTINUOUS ROW AND SINGLE UNIT PLACEMENT WITH PENDANT OR

ELECTRONIC, WITH A SOUND

PROGRAMMED START CLASS P

LIFTED BY ONE CORNER. LUMINAIRE SHALL BE CAPABLE OF

COAT FINISH. THE LUMINAIRE SHALL NOT PERMANENTLY DEFORM WHEN

WHITE, 10% UPLIGHT APERTURES. PROVIDE STIFFENING RIBS FOR RIGIDITY.

HIGH POWER FACTOR ( 0.95)

DIE-FORMED CRS HOUSING WITH WHITE ENAMEL POLYESTER POWDER

COLD ROLLED SYMMETRIC STEEL REFLECTOR/BALLAST COVER, PAINTED

INDUSTRIAL FLUORESCENT

MOUNTING:

ELECTRICAL:

REFLECTORS:

HOUSING:

120/277 VOLT BALLAST

SURFACE MOUNTING.

SUSPENDED

SHIELDING:

MOUNTING:

BALLAST:

RATING OF "A".

WIRE GUARD

SUSPENDED

GENERAL DESCRIPTION

FEATURES

A

B

C

NOMINAL DIMENSIONS :

A B C 4 7/16" 6 1/8" 11 3/4"

SPECIFICATION GRADE HEAVY DUTY TURRET INDUSTRIAL FIXTURE

STENCIL FACE LED EXIT SIGN

GENERAL DESCRIPTION

FEATURES

ELECTRICAL:

UL LISTED:

HOUSING:

MOUNTING:

NOM. DIMENSIONS:

LETTER COLOR:

MOUNTING:

SHIELDING:

11 3/8 " W X 7 7/8 " H X 1 3/4 " D

UNIVERSAL

FLAT SHEET VIRGIN ACRYLIC OVER LETTERS

GREEN

11 3/8 "

7 7/8 "

HOUSING SHALL BE DIE-CAST ALUMINUM CONSTRUCTION, WITH MATTE BLACK

ELECTROSTATIC POLYMERIC TRIM. FACEPLATES SHALL BE BRUSHED ALUMINUM

WITH CLEAR LACQUER FINISH, AND BE REMOVABLE FOR COMPARTMENT ACCESS

WITHOUT THE USE OF TOOLS. FIXTURE SHALL BE SEALED AS REQUIRED TO

PREVENT LIGHT LEAK. FIXTURE SHALL HAVE 6" HIGH GREEN ILLUMINATED

LETTERS WITH 3/4" STROKE. DIRECTIONAL ARROWS AS REQUIRED. DOUBLE OR

SINGLE FACE AS INDICATED ON PLANS. HOUSING SHALL HAVE MINIMUM 1/8"

THICK WALL.

UNIVERSAL MOUNTING, WALL OR CEILING.

120/277 VOLT, AC POWER ONLY; NO BATTERY. ILLUMINATION BY LED LAMPS,

AND OUTPUT SHALL BE UNIFORM

DAMP LOCATION

LED DOWNLIGHT

GENERAL DESCRIPTION

FEATURES

PHOSPHOR LENS ASSEMBLY

POSITIONED IN FRONT OF THE

LED ARRAY CONVERTS BLUE

LIGHT TO WHITE AND PRODUCES

A WIDE EVEN PATTERN OF

DIFFUSED WHITE LIGHT.

AS INDICATEDNOM. DIMENSIONS:

MOUNTING:

MIXING CHAMBER:

RECESSED

4-1/2"

5-3/4"ARRAY OF 16 HIGH BRIGHTNESS

ROYAL BLUE LEDs.

LED BOARD:

OPTICAL MIXING

CHAMBER

APERATURE CONE: DIFFUSE ALUMINUM CONE WITH 50 DEGREE VISUAL CUTOFF TO SOURCE AND

IMAGE. PROVIDE SELF FLANGED TRIM WITH SAME FINISH AS CONE UNLESS

NOTED OTHERWISE.

THERMAL

MANAGEMENT:

PROVIDE HEAT SINK TO MAINTAIN JUNCTION TEMPERATURE FOR CONSISTANT

RELIABLE PERFORMANCE AND 50,000 HOUR LIFETIME AT 70% LUMEN

MAINTENANCE.

MOUNTING FRAME: 18 GAUGE GALVANIZED STEEL WITH VERTICAL ADJUSTMENT MECHANISM.

INPUT WATTS: 20 WATTS.

OUTPUT LUMENS: 1000 LUMENS.

COLOR TEMP: 3000K.

FIXTURE SHALL COMPLY WITH IESNA LM79 AND LM80.

LENSED COMPACT

FLUORESCENT SHOWER LIGHT

GENERAL DESCRIPTION

FEATURES

REGRESSED WHITE SPLAY WITH GASKETED GLASS LENS, MINIMUM AVERAGE

THICKNESS = 1/8"

OPTICS:

AS INDICATED

120/277 VOLT BALLAST, HORIZONTALLY MOUNTED THERMOPLASTIC LAMP SCOKET,

TWO PIN POSITIVE LATCH

ELECTRICAL:

NOMINAL DIMENSIONS:

DIE-CAST ALUMINUM SOCKET HOUSING WITH HEAT DISSIPATING FINS

AND VENTED TOP.

BALLAST SHALL BE HIGH POWER FACTOR (>0.95) PROGRAMMED START CLASS

P ELECTRONIC BALLAST WITH A SOUND RATING OF "A."

SPUN ALUMINUM HOUSING WITH HEAT DISSIPATING FINS.

HOUSING:

MOUNTING:

BALLAST:

SHIELDING:

LENS

FIXTURE SHALL BE U.L. LISTED FOR WET LOCATIONS.MISC:

6 7/8" 7 1/2"

RECESSED IN CEILING. GALVANIZED STEEL MOUNTING BRACKET WITH 5"

VERTICAL ADJUSTMENT AND LOCKING SCREW (3/8" HEAD). GALVANIZED

STEEL MOUNTING/PLASTER FRAME.

6 1/4"

6 3/4"

FLOURESECENT WALL BRACKET

FIXTURE

GENERAL DESCRIPTION

FEATURES

100% ACRYLIC, HIGH-IMPACT, CLEAR PRISMATIC DIFFUSER.

DIE-FORMED, HEAVY-GAUGE, COLD-ROLLED STEEL WITH ENDCAPS

MADE FROM THE SAME MATERIAL AS HOUSING. PROVIDE, UP AND

DOWN LIGHTING. WHITE FINISH. SPECIFICATION GRADE FIXTURE.

ELECTRICAL: CLASS P, THERMALLY-PROTECTED, HIGH POWER FACTOR (>=0.95),

ELECTRONIC TYPE WITH SOUND RATING A. SEE SPECIFICATION OR

LIGHTING FIXTURE SCHEDULE FOR BALLAST OPTIONS AND SPECIFICS.

HOUSING:

LENS:

LAMPS: FLUORESCENT. SEE FIXTURE SCHEDULE FOR WATTAGE.

CERTIFICATION: UL LISTED AND LABELED.

7" NOMINAL

4" N

O M

IN

AL

LENS

LENS

FLUORESCENT UNDER-CABINET

TASK LIGHT

SECTION

(MINIMUM 85%), BAKED WHITE ENAMEL FINISH.

BALLAST SHALL BE HIGH POWER

FACTOR (> 0.95) PROGRAMMED

START, CLASS P, THERMALLY

PROTECTED, ELECTRONIC BALLAST

WITH A SOUND RATING OF "A." SEE

SPECIFICATIONS FOR BALLAST

OPTIONS AND SPECIFICS.

MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITH HIGH REFLECTANCE

SURFACE MOUNTED, UNDER CABINETS.

100% ACRYLIC, CLEAR PRISMATIC WITH LINEAR RIBS FOR EVEN ILLUMINATION.

MINIMUM AVERAGE THICKNESS = 1/8".

5 1/4" W X 1 13/16" D. FIXTURE TYPE

DICTATES LENGTH:

DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FOR

RIGIDITY. ENDCAPS SECURED WITH TABS, SCREWS, OR RIVETS.

ELECTRICAL: 120V BALLAST.

NOM. DIMENSIONS:

HOUSING:

MOUNTING:

FINISH:

LAMPS:

LENS:

LINEAR FLUORESCENT T8, WITH WATTAGES AS INDICATED. SEE LIGHTING

FIXTURE SCHEDULE.

BALLAST:

EG1 - 3' LENGTH.

CERTIFICATION: UL LISTED AND LABELED.

5 1/4" NOMINAL

/1 6"

N O

M

IN

AL

GENERAL DESCRIPTION

FEATURES

SURFACE MOUNTED VANDAL

RESISTANT FLUORESCENT FIXTURE

GENERAL DESCRIPTION

FEATURES

SECTION

UV-STABILIZED POLYCARBONATE

PRISMATIC CLEAR LENS WITH HIGH-

REFLECTANCE WHITE PAN REFLECTOR

SYSTEM

BALLAST SHALL BE HIGH POWER

FACTOR ( 0.95) PROGRAMMED

START CLASS P ELECTRONIC

BALLAST WITH A SOUND RATING

WHITE POLYESTER POWDER FINISH

SURFACE WALL

HIGH-REFLECTANCE WHITE PAN REFLECTOR SYSTEM

48"

CONSTRUCTED OF MARINE-GRADE EXTRUDED ALUMINUM SIDE RAILS AND

BACK RAILS, PRECISION DIE-CAST, MARINE-GRADE ALUMINUM END CAPS.

NOM. LENGTH:

HOUSING:

MOUNTING:

FINISH:

ELECTRICAL:

REFLECTORS:

120/277 VOLT BALLAST

MOUNTING:

SHIELDING:

BALLAST:

SURFACE WALL

OF "A".

4" NOM

1/

8" N

O M

AD L

EK

N

LL

E F

S

R P

O

IS

EN

L

GI

O N A

E E

N R

EC NIL

S E

No 0052705

STATE OF

ROLF

I D A

EE

AS

M

ON

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

OFFICE OF

FACILITIES

MANAGEMENT

on e ei gh th in ch o ne fo ot

B

A

C

D

E

F th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

BUILDING IS FULLY SPRINKLERED

A NEW HOSPITAL FOR

VAMC ORLANDO, FLORIDA

Orlando, Florida

673-950

Professional Seals:

29 OCTOBER, 2009 KLM EB/RLF

CENTRAL ENERGY PLANT

E-EL5.001

LIGHTING FIXTURE DETAILS

NOT TO SCALE

1 FIXTURE TYPE "EC1 & EC2"

NOT TO SCALE

2 FIXTURE TYPE "EH1, EH2, EH3, EH4, & EH5"

NOT TO SCALE

3 FIXTURE TYPE "EX1"

NOT TO SCALE

4 FIXTURE TYPE "EE1"

NOT TO SCALE

5 FIXTURE TYPE "EE2"

NOT TO SCALE

6 FIXTURE TYPE "EF1"

NOT TO SCALE

8 FIXTURE TYPE "EG1"

NOT TO SCALE

7 FIXTURE TYPE "EF2 & EF3"

WALL MOUNTED AREA LIGHT

GENERAL DESCRIPTION

FEATURES

HINGED DOOR FRAME WITH CLEAR TEMPERED GLASS LENS.

DIE CAST ALUMINUM CONSTRUCTION. SPUN ALUMINUM BASE COVER.

STAINLESS STEEL HARDWARE. FIXTURE HOUSING SHALL BE GASKETED.

ELECTRICAL: 277V

HOUSING:

LENS:

LAMPS: COMPACT FLUORESCENT. REFER TO FIXTURE SCHEDULE FOR WATTAGE.

CERTIFICATION: UL LISTED FOR WET LOCATIONS. MEETS FULL CUT OFF REQUIREMENTS.

FIXTURE SHALL BE MOUNTED WITH WALL MOUNTING BOX ACCESSORY.MOUNTING:

SILVER POLYESTER POWDER FINISH.FINISH:

SIDE

BALLAST: BALLAST SHALL BE HIGH POWER FACTOR ( 0.95) PROGRAMMED START

CLASS P ELECTRONIC BALLAST WITH A SOUND RATING OF "A".

FRONT

10" NOM. 11-1/2" NOM.

5- 8-

7/ 8"

N O

M

FLOOD LIGHT

GENERAL DESCRIPTION

FEATURES

SPUN ALUMINUM SILIVER-ANODIZED REFLECTOR WITH NEMA 2 NARROW OPTIC

DISTRIBUTION.

REFLECTOR:

FIXTURE SHALL BE U.L. LISTED FOR WET LOCATIONS.MISC:

METAL HALIDE PULSE

START BALLAST

AS INDICATED

HOUSING:

NOM. DIMENSIONS:

BALLAST:

MOUNTING: SURFACE

15.5'' NOM.

" N

O M

SURFACE

GASKETED

" N

O M

6" NOM.

DIE CAST ALUMINUM MOUNTED TO DIE CAST ALUMINUM BRACKET WITH

STAINLESS STEEL FASTENERS. HORIZONTAL FIELD ADJUSTMENTS TO

360 DEGREES.

ASSEMBLY: DIE CAST ALUMINUM ATTACHED TO LAMP HOUSING WITH STAINLESS

STEEL ROLL PIN. DIE CAST ALUMINUM LATCHES ALLOW FOR TOOL

LESS ENTRY INTO THE LAMP HOUSING. CLEAR FLAT TEMPERED GLASS.

NATURAL ALUMINUM FINISHFINISH:

PERFORATED

EXTERIOR

DIFFUSER WITH

WHITE INTERIOR

ACRYLIC WHITE

DIFFUSER

REFLECTOR

WHITE ACRYLIC INTERIOR

PERFORATED STEEL WHITE

BALLAST SHALL BE HIGH POWER

FACTOR ( .95) PROGRAMMED

START CLASS P ELECTRONIC

BALLAST WITH A SOUND RATING

BAKED ON LOW GLOSS WHITE POWDER COATED POLYESTER-EPOXY.

RECESSED CEILING MOUNTED

DIE-FORMED HIGH REFLECTANCE PAINTED STEEL.

24" W X 48" L X 6" D

COLD ROLLED STEEL, FLANGE TO COORDINATE WITH CEILING GRID;

MECHANICALLY ATTACHED DIE-FORMED STEEL PERFORATED

DIFFUSER. HOUSING SHALL BE CHEMICALLY TREATED FOR RUST

RECESSED DIRECT/INDIRECT

FLUORESCENT TROFFER

EFFICIENCY: 60%

NOM. DIMENSIONS:

HOUSING:

MOUNTING:

FINISH:

ELECTRICAL:

REFLECTORS:

GENERAL DESCRIPTION

120/277 VOLT BALLAST

PREVENTION. SPECIFICATION GRADE TROFFER.

FEATURES

SHIELDING:

BALLAST:

OF "A".

PERFORATED EXTERIOR

DIFFUSER WITH WHITE INTERIOR

ACRYLIC WHITE DIFFUSER.

SECTION

BALLAST REFLECTOR

DECORATIVE WALL MOUNTED AREA

LIGHT

GENERAL DESCRIPTION

FEATURES

IESNA FULL CUTOFF WITH WIDE DISTRIBUTION PATTERN. 86% MINIMUM

REFLECTIVITY SPECULAR ANODIZED ALUMINUM SEGMENTED REFLECTOR.

OPTICAL

SYSTEM:

FIXTURE SHALL BE U.L. LISTED FOR WET LOCATIONS.MISC:

HEAT AND IMPACT RESISTANT TEMPERED GLASS LENS WITH SILICON

RUBBER GASKET.

METAL HALIDE PULSE

START BALLAST

AS INDICATED

HOUSING:

LENS:

NOM.

DIMENSIONS:

BALLAST:

MOUNTING: SURFACE WALL MOUNT

DIE CAST ALUMINUM HOUSING. CONSTRUCTED TO IP54.

POLESTER POWDER COAT, SATIN ALUMINUM.FINISH:

9.

" N O

M

9.13" NOM. 18.13" NOM.

ELECTRONIC, WITH A SOUND

PROGRAMMED START CLASS P

HIGH POWER FACTOR ( 0.95)

HAZARDOUS ENCLOSED

INDUSTRIAL FLUORESCENT

MOUNTING:

LENS:

CHASSIS:

WALL MOUNTED. PROVIDE 45° ADJUSTABLE STAINLESS STEEL QUADRANT BRACKETS.

MOUNTING:

BALLAST:

RATING OF "A".

WALL MOUNTED

GENERAL DESCRIPTION

FEATURES

NOMINAL DIMENSIONS :

A B C D 5-9/32" 7-5/16" 9-23/32" 53-3/4"

C

B

D

A

NON-CORROSIVE ONE-PIECE SEAMLESS MOLDED FIBERGLASS

REINFORCED POLYESTER COMPOSITE BODY SUITABLE FOR 40 °C AMBIENT

TEMPERATURE.

WIREWAY: FULL-LENGTH RIGIDLY FORMED WIREWAY COVER WITH ALL ELECTRICAL

COMPONENTS RETAINED TO BODY WITH TWO MACHINE SCREWS AND

LOCKWASHERS WITHIN THE FIXTURE BODY.

3/16" THICK TEMPERED GLASS WITH STAINLESS STEEL, NON CORROSIVE STEEL

16-GAUGE FRAME GASKETED WITH SILICONE, SECURELY ATTACHED TO FRAME.

HINGES BOTH SIDES WITH STAINLESS SPRING STEEL TOGGLE CLAMPS.

REFLECTORS: PHOSPHATE PRIMED, BAKED WHITE ACYLIC ENAMEL WITH 86% MINIMUM

REFLECTIVITY.

LABELS: PROVIDE UL LISTED FOR WET LOCATION AND UL-LISTED CLASS I, DIVISION 2,

GROUPS A,B,C AND D LOCATIONS.

SECTION VIEW

TOP VIEW

POLE TOP METAL HALIDE AREA LIGHT

GENERAL DESCRIPTION

FEATURES

NOM. DIMENSIONS:

HOUSING:

MOUNTING:

FINISH:

LAMP ACCESS:

MOUNTING:

REFLECTORS:

BALLAST: 8.

5"

N O

M

SURFACE ARM MOUNT . PROVIDE

SINGLE ARM.

FULL CUTOFF , MULTI-FACETED

SEGMENTED REFLECTORS MADE OF

ANODIZED ALUMINUM

HIGH POWER FACTOR PULSE

START MAGNETIC BALLAST

AS INDICATED

DIE-CAST ALUMINUM SURFACE ARM MOUNT

DIE-CAST ALUMINUM WITH CORROSION RESISTANT HARDWARE.

SPRING LOADED LATCH AT UPPER SIDE OF HOUSING.

ELECTROSTATICALLY APPLIED POLYESTER POWDER COAT TEXTURED SATIN

ALUMINIUM FINISH

24" DIAMETER

LENS: FULLY TEMPERED INVERSE CONICAL GLASS LENS AND COLIMATING OPTIC

LENS.

UL LISTING: WET LOCATION

DISTRIBUTION: FULL CUTOFF WITH ASYMMETRIC DISTRIBUTION.

EXTERNAL HOUSE

SIDE SHIELD WHERE

INDICATED

1' - 6"±

5" OUTSIDE DIAMETER ROUND STRAIGHT

ALUMINUM POLE. WALL THICKNESS SHALL

BE 3/16" MINIMUM.

WIRING HANDHOLE MIN. 2-1/2" X 5" (CLEAR OPENING)

WITH COVER AND STAINLESS STEEL SCREWS.

PROVIDE INTERNAL GROUNDING LUG.

TERMINATE CONDUITS INTERNALLY.

ALUMINUM ANCHOR BASE COVER.

CONCRETE BASE - SEE DETAIL 8/E-EL5.002.

14'

DIRECT DRILL ARM MOUNT TO POLE. SEE

MANUFACTURERS RECOMMENDATION FOR

ARM MOUNT DRILL TEMPLATE.

PROVIDE POLE WITH WIND VELOCITY RATING OF 110

MPH WITH 1.3 GUST FACTOR FOR SINGLE MOUNTED

LUMINAIRE.

NOTES:

1.

2.

POLE DETAIL

PROVIDE TEXTURED SATIN ALUMINUM FINISH.

16" DIA.CONCRETE AS

SPECIFIED.

LEGEND

POLE. REFER TO 7/E-EL5.002 FOR

DETAIL.

PVC CONDUIT STUBBED UP

ADJACENT TO WIRING HANDHOLE,

NUMBER AND SIZE AS

REQUIRED.

SET TOP OF CONCRETE

FOUNDATION 4" ABOVE

GRADE.

COPPER EQUIP. GND

C. ATTACH TO

GROUND LUG

INTERNAL TO POLE.

EQUIP. GND C. SHALL

BE SAME SIZE AND

TYPE AS SUPPLY

CONDUCTOR.

CIRCUIT CONDUCTORS