Attachment 4 Drawings RTU.pdf
PDF 2 MB Posted
- Attached to
- Belcourt RTU & Cabinet Replacement
- Solicitation number
- 75H70126Q00007
About this file
These are 100% Construction Documents for the Indian Health Service (IHS) project located in Belcourt, North Dakota, specifically for a Rooftop Unit (RTU) and Cabinet for a CT Room. The project involves mechanical and electrical system upgrades, including installing a new AAON RQ-005-3-0-GAAY-V0-21-000-A rooftop unit (RTU-CT1) with a 140 CFM outside air capacity, 2.56 in w.g. total static pressure, and 52 MBH heating capacity. Electrical work includes demolishing existing breakers, installing a new 3-pole 50-amp breaker in Panel HCT, adding a 120VAC to 24VAC transformer for humidifier control, and routing new conduit and wiring. The mechanical scope involves installing a new steam humidifier, reconfiguring ductwork, and replacing existing HVAC components, with all work to be completed by 11/01/2024.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| B05 Amendment 4.pdf | ||
| B04 PPI Log 12.12.2025.xlsx | XLSX spreadsheet | |
| B01 Drawing A.2 Revised.pdf | ||
| B05 Amendment 3.pdf | ||
| B05 Amendment 2.pdf | ||
| B05 Amendment 1.pdf | ||
| Attachment 1 Wage Determination ND20250029.pdf | ||
| Attachment 5 Drawings Cabinetry.pdf | ||
| Attachment 2 SOW.pdf | ||
| B01 26Q00007.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
259 E. Michigan Ave., Suite 407 Kalamazoo, MI 49007 P: 269.585.2255 steelheadengineeringco.com
THE REPRODUCTION, COPYING OR OTHER USE OF THIS
DRAWING WITHOUT WRITTEN AUTHORIZATION IS PROHIBITED.
c SEVEN GENERATIONS ARCHITECTURE & ENGINEERING, LLC
SHEET NO.
SHEET TITLE
JOB NUMBER:
ISSUE DATES:
KEYPLAN
NORTH
LOCATION MAP
PROJECT TEAM DRAWING SHEET INDEXPROJECT INFORMATION
BUILDING OCCUPANCY:
CONSTRUCTION TYPE:
BUILDING HEIGHT:
FIRST FLOOR:
100% CONSTRUCTION DOCUMENTS
STEELHEAD ENGINEERING
259 E. MICHIGAN AVENUE, Ste 407
KALAMAZOO, MI 49007
PHONE: 269.585.2255
WEB: STEELHEAD.COM
ENGINEERING:
TYPE II
MIXED OCCUPANCY (SEPARATED)
9'-0"
BELCOURT, NORTH DAKOTA 58316
BELCOURT, ND 58316
241364
G000
COVER SHEET
INDIAN HEALTH SERVICE
QNBMHCF - RTU & CABINET - CT ROOM
100% CONSTRUCTION DOCUMENTS11/01/2024
Q N
BM
H
C F
R
TU
C A
BI
N
ET
C T
R O
O M
IN
D
IA
N
H
EA
LT
H
S
ER
V
IC
E
BE
LC
O
U R
T, N
O R
TH
D
A K
O
TA
Volume Number
Building Name
Sheet Classification
Sheet Discipline
Sheet Order
SHEET
NUMBER
SHEET NAME 1st Issuance
2nd Issuance
Line 1 Date
1st Issuance
MECHANICAL
70_MECHANICAL MECHANICAL 70 G000 COVER SHEET Yes No 11/01/
100%
CONSTRUCTION
DOCUMENTS
70_MECHANICAL MECHANICAL 70 M001 MECHANICAL
GENERAL INFO &
SYMBOL LEGEND
Yes No 11/01/
100%
CONSTRUCTION
DOCUMENTS
70_MECHANICAL MECHANICAL 74 M101 FIRST FLOOR
MECHANICAL
PLAN
Yes No 11/01/
100%
CONSTRUCTION
DOCUMENTS
70_MECHANICAL MECHANICAL 78 M600 MECHANICAL
SCHEDULES,
DETAILS,
CONTROLS
Yes No 11/01/
100%
CONSTRUCTION
DOCUMENTS
ELECTRICAL
80_ELECTRICAL ELECTRICAL 84 E101 ELECTRICAL PLAN Yes No 11/01/
100%
CONSTRUCTION
DOCUMENTS
EXTERIOR PERSPECTIVE
WM
M
M
CO2
CO
H
HS
NO2
S
TH
TS
T
MS
CHWS
CD
CDR
CWR
CWS
HWR
HWS
G
STM-S
(E)
CHWR CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSATE DRAINAGE
CONDENSATE RETURN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
HEATING WATER RETURN
HEATING WATER SUPPLY
NATURAL GAS
STEAM
REF-L
REF-S
REFRIGERANT-LIQUID
REFRIGERANT-SUCTION
2"
2"
4"
4"
REF-HG REFRIGERANT-HOT GAS
PIPING SYMBOLS
KEYNOTE
CONTINUATION SYMBOL
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
GENERAL SYMBOLS
ROOM NAME AND NUMBER
POINT WHERE DISCONNECT/DEMOLITION OCCURS
AT EXISTING
EXISTING PIPE TAG
DEMOLISHED ITEM
AREA NOT IN CONTRACT
PIPING BEING DEMOLISHED
ABOVE GROUND PIPING
PIPE SIZE TAG (DIAMETER)
PIPE RISE
PIPE DROP
PIPE TEE REDUCING 45
DEGREE TEE
45 DEGREE TEE
BELOW GROUND PIPING
PIPE INVERT ELEVATION TAG
PIPE SLOPE TAG
PG PROPANE GAS
Room
INVERT: -105' - 1"
1/8" / 12" SLOPE
18"x12"
18"/12"
(E)
18"Ø
EXHAUST AIR
OUTSIDE AIR
RELIEF AIR
RETURN AIR
SUPPLY AIR
TRANSFER AIR
GRILLES, REGISTERS & DIFFUSERS TAG
CFM
EXISTING DUCT TAG
OVAL DUCT SIZE TAG (WIDTH / HEIGHT)
SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)
HVAC SYMBOLS
RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE
RECTANGULAR RETURN/TRANSFER AIR DUCT RISE
MECHANICAL EQUIPMENT TAGS
ROUND DUCT SIZE TAG (DIAMETER)
LINEAR DIFFUSER TAG
CFM
TYPE (SEE SCHEDULE)
NUMBER OF SLOTS /
ACTIVE SLOT LENGTH (PLENUM
LENGTH) / NECK SIZE
DUCT BEING DEMOLISHED
ROUND SUPPLY/OUTSIDE AIR DUCT RISE
ROUND RETURN/TRANSFER AIR DUCT RISE
RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE
ROUND EXHAUST/RELIEF AIR DUCT RISE
DROP
DROP
DROP
DROP
DROP
DROP
GREASE EXHAUST AIR
SMOKE EXHAUST AIR
EXISTING
EQUIPMENT TO
REMAIN
EXHAUST GAS FLUE
COMBUSTION AIR
CONDITIONED OUTSIDE AIR
Ø ROUND
ABV ABOVE
AC AIR CONDITIONING
AD AREA DRAIN
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION
EFFICIENCY
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BFF BELOW FINISHED FLOOR
BLW BELOW
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER
HOUR
CAP CAPACITY
CB CATCH BASIN
CFM CUBIC FEET PER MINUTE
CLG CEILING
CO CLEAN OUT
CW COLD WATER
D DEGREE
DB DRY BULB
DIA DIAMETER
DN DOWN
DW DISTILLED WATER
EA EACH
EAT ENTERING AIR TEMPERATURE
ELEC ELECTRICAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
E/A EXHAUST AIR
EXIST EXISTING
F DEGREES FAHRENHEIT
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FL FLOOR
FO FUEL OIL
FOV FUEL OIL VENT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPM FEET PER MINUTE
FS FLOOR SINK
FT FOOT/FEET
FTR FIN TUBE RADIATION
GAL GALLON
GF GAS-FIRED
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GW GREASE WASTE
HB HOSE BIB
HP HORSE POWER
HTG HEATING
HTR HEATER
HW HOT WATER
HYD HYDRANT
ID INDIRECT
IN INCH
INV INVERT
LB POUND
LB/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LVR LOUVER
LWT LEAVING WATER
TEMPERATURE
M/A MIXED AIR
MAX MAXIMUM
MBH ONE THOUSAND BTU PER
HOUR
MCF ONE THOUSAND CUBIC FEET
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTR MOTOR
MU/A MAKE-UP/AIR
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NUMBER
NO NORMALLY OPEN
NTS NOT TO SCALE
O OXYGEN
O/A OUTSIDE AIR
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP
PIV POST INDICATOR VALVE
PLBG PLUMBING
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH
GAUGE
PWR POWER
R DUCT RISER
R/A RETURN AIR
RCP RADIANT CEILING PANEL
RD ROOF DRAIN
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RL/A RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RW RAIN WATER
SF SQUARE FOOT
S/A SUPPLY AIR
SAN SANITARY
SF SQUARE FOOT
SD SMOKE DAMPER
SM SURFACE MOUNT
SP STANDPIPE
SP STATIC PRESSURE
STM STEAM
T THERMOSTAT
TD TEMPERATURE DROP
TDR TRENCH DRAIN
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
VAC VACUUM
V VENT
VAV VARIABLE AIR VOLUME
VENT VENTILATION
VTR VENT THROUGH ROOF
W WASTE
WB WET BULB
WCO WALL CLEAN OUT
WH WALL HYDRANT
ABBREVIATIONS
48"x2 1/2"
SLB3 400
E6L1
LINEAR BAR GRILLE
LINEAR SLOT
DIFFUSER
FULL EGG-CRATE
FACE, ROUND
NECK EXHAUST
GRILLE
TYPE (SEE SCHEDULE)
R6L1
LAY-IN EGG-CRATE
FACE, ROUND
RETURN GRILLE
1 / 4' - 0" / 8"
LSD1 200
1 / 4' - 0" / 8"
LSD1 200
6' - 0"
1 / 4' - 0" / 8"
LSD1 200
SECTION TOTAL TRACK LENGTH
NEW EQUIPMENT
HEATING
COIL
FLOW
2" DOM. WM
PIPE ACCESSORY TAGS
DOMESTIC WATER METER
BALANCING VALVE
1/4 TURN BALL VALVE
CHECK VALVE
3-WAY MIXING VALVE
MOTORIZED CONTROL VALVE
3 WAY MOTORIZED CONTROL
VALVE
PRESSURE REDUCING VALVE
REFRIGERANT SOLENOID
VALVE
BUTTERFLY VALVE
2" BALANCING
2" SHUTOFF
2" CHECK
2" TMV
2" M-CONTROL
2" 3-WAY CONTROL
2" PRV
3/8" SOLENOID
2" BUTTERFLY
DATA DEVICE TAGS
VAV-XX
RTU-XX
EQUIPMENT ID
SYMBOL
SENSOR
MANUAL SWITCH
THERMOSTAT
TEMPERATURE SENSOR
TEMPERATURE & HUMIDITY SENSOR
HUMIDITY SENSOR
NITROGEN DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
HUMIDISTAT
CAP
PLUG
GWR
GWS
GEOTHERMAL WATER RETURN
GEOTHERMAL WATER SUPPLY
DEMOLISHED
EQUIPMENT
AC AIR CONDITIONING UNIT
ACCU AIR COOLING CONDENSING UNIT
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
B BOILER
CH CHILLER
CT COOLING TOWER
CUH CABINET UNIT HEATER
CHWP CHILLED WATER PUMP
DBP DOMESTIC WATER BOOSTER PUMP
DC DUCT MOUNTED COIL
DCP DOMESTIC WATER CIRCULATING
PUMP
EF EXHAUST FAN
EDC ELECTRIC DUCT COIL
ET EXPANSION TANK
EWH ELECTRIC WATER HEATER
FCU FAN COIL UNIT
FP FIRE PUMP
GI GREASE INTERCEPTOR
GRV GRAVITY ROOF
VENTILATOR
HWP HEATING WATER PUMP
HRU HEAT RECOVERY UNIT
PRV POWER ROOF VENTILATOR
RE RETURN/EXHAUST FAN
RTU ROOFTOP UNIT
SP SUMP PUMP
UH UNIT HEATER
WH WATER HEATER
EQUIPMENT ABBREVIATIONS
F S C B M D
DAMPER TAGS
MOTORIZED DAMPER
BACKDRAFT DAMPERFIRE DAMPER
SMOKE DAMPER
COMB. FIRE/SMOKE DAMPER
HVAC-CP-X
BMS CONTROL PANEL
MANUAL BALANCING DAMPER
12"x12" S/A
PANEL NAME
CONDENSATE EXHAUST AIR
18"x18" S/A
18"x18" S-O/A
18"x18" O/A
18"x18" R/A
18"x18" T/A
18"x18" E/A
18"x18" L/A
18"x18" GE/A
18"x18" CE/A
18"x18" SE/A
6"Ø FLUE
6"Ø C/A
* NOTE *
ALL GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS
IN THIS SET. THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR
MAY NOT BE USED IN THIS SET OF DRAWINGS.
POINT WHERE NEW CONNECTS TO EXISTING
(D)
(D)
TYPE (SEE SCHEDULE)
CFM
S6L1
Htg: 3.7 GPM
VAV-XX
VAV-XX
VAV-XX
VAV-XX
590 lb
RTU-XX
4.0 ton
RTU-XX
115000 Btu/h
115 CFH
RTU-XX
OPERATING
WEIGHT NOT
INCLUDING CURB
FUEL INPUT
GAS PIPE
FLOW
NOMINAL
COOLING
CAPACITY
ROOFTOP UNIT
LOUVERED FACE,
ROUND NECK
SUPPLY DIFFUSER
SYSTEM (S=SUPPLY, R=RETURN, E=EXHAUST)
NECK SIZE
FAMILY NUMBER
STYLE (L=LAY-IN, S=SURFACE)
GENERAL HVAC NOTES
1 CONTRACTOR SHALL LOCATE THERMOSTATS AND TEMPERATURE SENSORS AT
4'-0" AFF, A MINIMUM OF 8" FROM LIGHT SWITCH.
2 REFER TO HVAC DRAWINGS FOR THERMOSTAT AND TEMPERATURE SENSOR
LOCATIONS.
3 CONDENSATE DRAINS SHALL BE SUPPLIED FOR ALL COOLING EQUIPMENT.
CONTRACTOR SHALL ENSURE PROPER INSTALLATION AND DRAINAGE AS
REQUIRED BY FEDERAL CODES. CONDENSATE PIPING SHALL BE TYPE "M" COPPER.
4 ALL SUPPLY, RETURN, AND EXHAUST DUCTWORK SHALL BE RATED FOR PRESSURE
CLASS OF 2" W.G. UNLESS NOTED OTHERWISE.
5 PROVIDE DIFFUSERS AND REGISTERS WITH 4-WAY BLOW PATTERN UNLESS
OTHERWISE NOTED.
6 THIS CONTRACTOR SHALL BE REQUIRED TO REPLACE FILTERS ON HVAC
EQUIPMENT AFTER ALL DUST PRODUCING CONSTRUCTION HAS BEEN COMPLETED
AND PRIOR TO THE FINAL PUNCH.
7 SUPPLY/RETURN/EXHAUST BRANCH DUCT SIZES SHALL MATCH THE
GRILLE/DIFFUSER NECK SIZE UNLESS NOTED OTHERWISE.
GENERAL PROJECT NOTES
1 FINAL PRODUCT SHALL BE A COMPLETE AND FUNCTIONING SYSTEM, AND SHALL
CONFORM TO ALL REQUIREMENTS OF APPLICABLE FEDERAL, STATE, AND LOCAL
CODES, INCLUDING BUT NOT LIMITED TO THE INTERNATIONAL BUILDING CODE
AND INTERNATIONAL MECHANICAL CODE.
2 LOCATE EQUIPMENT REQUIRING ACCESS 2'-0" MAXIMUM ABOVE CEILING.
3 LOCATE DUCTWORK, PIPING AND MECHANICAL EQUIPMENT AWAY FROM THE
SPACE ABOVE ELECTRICAL PANELS. TRANSFORMERS AND OTHER ELECTRICAL
EQUIPMENT.
4 PENETRATIONS OF RATED ASSEMBLIES SHALL BE FIRE STOPPED. FIRE STOPPING
SHALL BE AN APPROVED MATERIAL AS PRESCRIBED IN CSFM STANDARD 43-1
AND SHALL BE U.L. LISTED.
5 PROVIDE SLEEVES AND/OR OPENINGS TO RUN PIPES AND DUCTS THROUGH
FOUNDATIONS, FLOORS, WALLS, AND ROOF.
6 MAINTAIN CLEAR ACCESS TO SERVICE EQUIPMENT AND OTHER ACCESSORIES
REQUIRING SERVICE, VISUAL INSPECTION OR HAND OPERATION. WHERE
INDICATED OR REQUIRED, PROVIDE ACCESS PANELS OF THE TYPE SELECTED TO
SUIT MATERIALS IN WHICH INSTALLED.
7 ADJUST PIPING AND DUCTWORK SIZES TO PROPERLY CONNECT TO MECHANICAL
EQUIPMENT.
8 PIPE SIZES SHOWN SHALL BE CONTINUED IN THE DIRECTION OF FLOW UNTIL
ANOTHER SIZE IS SHOWN.
9 FOR EQUIPMENT CONNECTIONS, AND PIPE SIZES NOT SHOWN ON THE PLANS,
REFER TO DETAILS, SCHEDULES, AND SPECIFICATIONS.
10 INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE RESPECTIVE
MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS, AT A LEVEL OF QUALITY
AND WORKMANSHIP CONSISTENT WITH THE SPECIFICATIONS.
11 LOCATIONS OF PIPING, DUCTWORK AND EQUIPMENT AS INDICATED ON THE
PLANS, ARE APPROXIMATE AND SUBJECT TO MINOR ADJUSTMENTS IN THE FIELD.
WORK SHALL BE COORDINATED WITH ALL OTHER TRADES TO AVOID
INTERFERENCE IN THE FIELD.
12 INSTALL EXPOSED PIPING AND DUCTWORK AS HIGH AS PRACTICAL IN ROOMS
WITHOUT CEILINGS.
13 THE CONTRACTOR'S WORK SCHEDULE SHALL BE SUBMITTED TO AND APPROVED
BY THE OWNER.
14 PRIOR TO STARTING WORK, SUBMIT SHOP DRAWINGS FOR ALL MECHANICAL
EQUIPMENT, PLUMBING FIXTURES, AND DIFFUSERS.
15 THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE
USED IN THIS SET OF DRAWINGS.
259 E. Michigan Ave., Suite 407
Kalamazoo, MI 49007
P: 269.585.2255 steelheadengineeringco.com
THE REPRODUCTION, COPYING OR OTHER USE OF THIS
DRAWING WITHOUT WRITTEN AUTHORIZATION IS PROHIBITED.
c SEVEN GENERATIONS ARCHITECTURE & ENGINEERING, LLC
SHEET NO.
SHEET TITLE
JOB NUMBER:
ISSUE DATES:
KEYPLAN
241364
Q N
B M
H C
F
R
TU
C
A B
IN
E T
C
T R
O O
M
IN
D
IA
N H
E A
LT
H
S E R
V
IC
E
B E
LC
O U
R T, N O
R
TH
D A
K O
TA
M001
MECHANICAL GENERAL
INFO & SYMBOL LEGEND
100% CONSTRUCTION DOCUMENTS11/01/2024
11/1/24
T H
TH
T
T H
TH
T
DEMO
EXISTING
HUMIDIFIER
55555555
5 5
5 5
3/4" STM-S
3/4" STM-R
/4
S
TM
-S
/4
S
TM
-R
"x
S /A
S10L1
S10L1
S10L1
S10L1
S10L1
S10L1
5 5
55555555
5 5 5
5 5
10"Ø S/A
10"Ø S/A
10"Ø S/A
10"Ø S/A
"Ø
S /A
"Ø
S /A
259 E. Michigan Ave., Suite 407
Kalamazoo, MI 49007
P: 269.585.2255 steelheadengineeringco.com
THE REPRODUCTION, COPYING OR OTHER USE OF THIS
DRAWING WITHOUT WRITTEN AUTHORIZATION IS PROHIBITED.
c SEVEN GENERATIONS ARCHITECTURE & ENGINEERING, LLC
SHEET NO.
SHEET TITLE
JOB NUMBER:
ISSUE DATES:
KEYPLAN
241364
Q N
B M
H C
F
R
TU
C
A B
IN
E T
C
T R
O O
M
IN
D
IA
N H
E A
LT
H
S E R
V
IC
E
B E
LC
O U
R T, N O
R
TH
D A
K O
TA
M101
FIRST FLOOR
MECHANICAL PLAN
100% CONSTRUCTION DOCUMENTS11/01/2024
KEYNOTES
1 CONNECT NEW DUCTWORK TO NEW RTU
2 NEW STEAM PIPING TO NEW LP STEAM HUMIDIFIER.
3 REMOTE TEMPERATURE AND HUMIDITY SENSOR
4 DEMOLISH THE STEAM AND STEAM CONDENSATE PIPING BACK
TO THE MAIN.
5 NEW LOCATION FOR THE REINSTALLED RETURN AIR GRILLE.
6 STEAM AND STEAM CONDENSATE PIPING ROUTED TO THE
EXISTING MAIN, FIELD VERIFY THE ROUTE AND CONNECTION
REQUIREMENTS.
7 DEMOLISHED DUCTWORK AND ASSOCIATED BRANCH
DUCTWORK AND DIFFUSERS.
MECHANICAL SHEET METAL NOTES
1 THE INSTALLATION OF ALL DUCTWORK SHALL BE CLOSELY
COORDINATED WITH NEW PLUMBING, ELECTRICAL, AND
STRUCTURAL CONDITIONS. NOT ALL REQUIRED OFFSETS AND
FITTINGS ARE INDICATED ON DRAWINGS, BUT SHALL BE
PROVIDED. REFER TO ARCHITECTURAL AND STRUCTURAL PLANS
FOR CLEARANCES. ALTERNATE DUCT ROUTING SHALL BE
APPROVED BY ARCHITECT/ENGINEER BEFORE PROCEEDING IN
ORDER TO ENSURE THAT THE AVAILABLE STATIC PRESSURE
REMAINS ADEQUATE. DUCTWORK LOCATION SHALL TAKE
PRECEDENCE OVER HVAC AND FIRE PROTECTION PIPING AND
ELECTRICAL CONDUIT AND CABLE TRAY.
3 DUCTWORK, EQUIPMENT AND ACCESSORIES SUPPORTED AND
BRACED PER SMACNA GUIDELINES.
4 UNLESS OTHERWISE NOTED, ALL DUCTWORK ABOVE CEILING OR
EXPOSED IS OVERHEAD AND AS HIGH AS POSSIBLE TO THE
UNDERSIDE OF THE STRUCTURE, WITH SPACE FOR INSULATION
WHERE REQUIRED.
5 DUCTS CONNECTED TO EQUIPMENT SHALL EQUAL EQUIPMENT
CONNECTION SIZE UNLESS NOTED OTHERWISE.
6 PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS
CONNECTED TO MECHANICAL EQUIPMENT THAT REQUIRE
VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL BE
PROVIDED AT THE POINT OF CONNECTION TO THE EQUIPMENT
UNLESS OTHERWISE NOTED.
7 REFER TO DUCT DETAILS. SPIN-IN TYPE WITH SCOOPS SHALL NOT
BE ACCEPTED. A MINIMUM OF 2 FEET SHALL BE PROVIDED
BETWEEN RUNOUT TAKEOFFS FROM TRUNK DUCTS.
8 MAXIMUM LENGTH OF FLEXIBLE DUCT SHALL BE 5'-0".
9 BRANCH DUCT BALANCING DAMPERS, WHEN NOT INCLUDED IN
THE MAIN TAP SHALL BE MOUNTED AS CLOSE TO MAIN DUCT AS
POSSIBLE.
10 ROUND DUCT ELBOWS SHALL BE LONG RADIUS ELBOWS, UNLESS
SHOWN OTHERWISE.
MECHANICAL NOTES
1 CONTRACTOR SHALL PROVIDE A COMPLETE AND WORKING
SYSTEM.
2 THIS DRAWING IS DIAGRAMMATIC IN NATURE AND SHALL NOT
BE SCALED.
3 MECHANICAL EQUIPMENT LOCATED WITH UNOBSTRUCTED
ACCESS TO UNIT ACCESS PANELS, CONTROLS AND VALVING.
4 INSTALL EQUIPMENT PER MANUFACTURER'S
RECOMMENDATIONS
5 COORDINATE ALL EXTERIOR PENETRATIONS INCLUDING ROOF
PENETRATIONS WITH OTHER TRADES TO PROVIDE A COMPLETE
AND FULLY WEATHER-PROOF INSTALLATION.
6 CONTRACTOR SHALL ENGAGE A TESTING AND BALANCE FIRM
CERTIFIED BY AABC TO PERFORM TESTING AND BALANCING
PROCEDURES ON EACH SYSTEM ACCORDING TO THE
PROCEDURES CONTAINED IN AABC'S "NATIONAL STANDARDS.
FOR TESTING AND BALANCING HEATING, VENTILATION, AND AIR
CONDITIONING SYSTEMS".
7 REMOVE CEILING GRID TO DEMO AND REPLACE DUCTWORK.
REINSTALL CEILING GRID WHEN COMPLETE.
8 INSTALL OSHA COMPLIANT RAILING AT ROOF'S EDGE FOR FALL
PROTECTION
NORTH
SCALE: 3/8" = 1'-0"
HVAC CEILING PLAN
NORTH
SCALE: 3/8" = 1'-0"
MECHANICAL DEMOLITION PLAN
NORTH
SCALE: 3/8" = 1'-0"
MECHANICAL PIPING PLAN
SCALE: NTSM101
3D - CT Area4
UNIT CROSS SECTION
NOTE :
HUMIDIFIER IS A HOT STEAM ITEM AND IS TO BE INSULATED AS ARE CONNECTION HOT STEAM AND CONDENSATE
LINES.
COOLING COIL
DRAIN PAN
UNION,
TYPICAL
STEAM MAIN
STRAINER BY HUMIDIFIER
MANUFACTURER
ACTUATOR AND VALVE BY
HUMIDIFIER MANUFACTURER
CONDENSATE
TO DRAIN
6"MIN.
6"MIN.
F & T STEAM TRAP BY
HUMIDIFIER MANUFACTURER
STEAM DISPERSION MANIFOLD
(CROSS SECTION NOT
REPRESENTATIVE OF FINAL
PRODUCT)
HUMIDITY SENSOR: NEPTRONIC NF SHS80
STEAM DISPERSION MANIFOLD: MF SAM BE2, MANIFOLD LENGTH: 14"
1.
2.
GATE VALVE
F & T STEAM TRAP BY
HUMIDIFIER MANUFACTURER
SEPARATOR BY HUMIDIFIER
MANUFACTURER
CONTROL VALVE: SKDB0075SAM, 3/4"3.
TS
T
T
B
PROVIDE TRANSITION FROM
TERMINAL TO DUCTWORK
VAV OR CV
TERMINAL
PROVIDE A MINIMUM OF 3 DUCT
DIAMETERS OF STRAIGHT DUCT
S U
P P
LY
D
U C
T M
A
IN
LINEAR SLOT, LINEAR BAR
OR FLOW BAR DIFFUSER
SUPPLY DUCT UP
BRANCH DUCTS
TO SUPPLY AIR
OUTLETS,
TYPICAL
SUPPLY DUCT BRANCH
RIGID DUCT
FLEX DUCT
SUPPLY GRILLE/REGISTER, TYPICAL
NOTES:
1. REFER TO THE HVAC FLOOR PLANS FOR DUCT SIZES.
2. REFER TO THE SCHEDULES FOR GRILLES, REGISTERS, DIFFUSERS AND
TERMINAL SIZES AND TYPES.
3. PROVIDE A MANUAL BALANCING DAMPER FOR EACH SUPPLY OUTLET.
4. ALL DUCT RUNOUTS TO DIFFUSERS SHALL BE THE SAME SIZE AS THE
DIFFUSER NECK UNLESS OTHERWISE NOTED.
CEILING
DIFFUSER
S U
P P
LY
D
U C
T M
A
IN
RETURN/EXHAUST DUCT UP
R E
TU
R N
/E X
H A
S T
D U
C T
M A
IN
AIR CUSHION DIMENSIONS
RETURN/EXHAUST GRILLE
ON THE BOTTOM OF THE
DUCT
CEILING
GRILLE
OPEN ENDED
RETURN/EXHAUST AIR
BRANCH DUCT
1-1/2 RADIUS ELBOWS
90° ELBOWS
WITH TURNING VANES
.0
SUPPLY DUCT DOWN
ELEVATION
L=W/4, 4" MIN.
M
IN
IM
U
M
TY
P
IC
A
L
AIR CUSHION NOTES:
1. AIR CUSHION REQUIRED AT END OF
RUN FOR BRANCH TAKE OFFS
ILLUSTRATED
2. CUSHION DEPTH, D, EQUAL TO 1/2
THE GREATER OF H OR W, SUBJECT
TO 6" MINIMUM, WHERE H = HEIGHT
OF DUCT
3. SUPPLY AIR AND RETURN AIR DUCT
SHALL BE EXTERNALLY INSULATED
ONLY.
SUPPLY AIR DUCT MAIN
MANUAL
BALANCE/VOLUME
DAMPER WITH
LOCKING
QUADRANT, TYPICAL
TAKE-OFF
FITTING,
TYPICAL
DUCT TO MATCH
REGISTER FLANGE
OUTSIDE DIMENSIONS
REGISTER WITH DAMPER MANUALLY
ADJUSTABLE FROM FACE
B
W
D
B
B
B
6" MINIMUM
B
B B
B
B
.0
A P
P R
O X
IM
A
TE
LY
B L
W
HIGH EFFICIENCY TAKE-OFF
.0
ELEVATION
M
IN
IM
U
M
TY
P
IC
A
L
RIGID DUCT
FLEX DUCT
B B
90° ELBOWS
WITH TURNING
VANES
9" MINIMUM
RETURN/EXHAUST DUCT BRANCH
RETURN/EXHAUST DUCT
DOWN
B B
B
B
ROOFTOP UNIT SCHEDULE
Supply Fan Static Cooling Section Heating Section Reheat
Mark Mnf Model Type Arrangement OA Airflow Ext. Static Tot Static Motor HP Exhaust Fan Econoomizer Heating Cabinet Total Sensible Latent Total Capacity Capacity
RTU-CT1 AAON RQ-005-3-0-GAAY-V0-21-000-A Horizontal Downflow 140 CFM 2100 CFM 1.25 in 2.6 in 2 140 CFM 0.13in w.g. 0.15in w.g. 0.10in w.g. 2.56in w.g. 52 MBH 7.1 MBH 59.1 MBH 25.6MBH 49.4 MBH
Notes:
1 Rooftop Curb Adaptor: Thybar Retromate Standard Adaptor for New AAON RQ 002-006 Standard, Existing Carrier 50DJ900771 Curb
2 Electrical Rating: 460V/3ph/60hz, FLA: 42, Min Circuit Amp: 44, Max Overcurrent: 50 Provide an integral non-fused disconnect.
METAL CLAMP
SEE NOTE 6
SEE NOTE 7
SEE NOTE 7
LONG
RADIUS
ELBOW AS
INIDICATED
INSULATED FLEXIBLE DUCT, A MAXIMUM OF 5'-0"
LONG, SECURE INNER LINER WITH STAINLESS STEEL
METAL HOSE CLAMP, SECURE THE OUTER JACKET
WITH A NYLON ZIP TIE/STRAP
NOTES:
1. SUPPORT DUCTWORK AS REQUIRED.
2. BAND FLEX TO COLLAR 1/2" MINIMUM FROM
OUTBOARD END OF COLLAR.
3. INSTALL SPIN COLLAR DAMPER IN OPEN POSITION;
FINAL ADJUSTMENT BY TAB CONTRACTOR.
4. PULL FLEXIBLE DUCT INSULATION UP TO END OF
SPIN COLLAR AT EDGE OF RECTANGULAR
DUCTWORK; SEAL VAPOR BARRIER WITH TAPE TO
PREVENT MOISTURE MIGRATION.
5. PROVIDE EXTENSION RODS TO ACCOMMODATE
INSULATION, PULL TO EDGE OF DUCTWORK AS
REQUIRED AND SEAL VAPOR BARRIER.
6. SHEET METAL SCREWS, MINIMUM 3 EACH AT 120
DEGREE INTERVALS, CONNECTING TO COLLAR.
ENSURE SCREWS DO NOT INTERFERE WITH DAMPER.
7. TAPE AND SEAL ALL JOINTS TO PREVENT LEAKAGE.
8. INSTALL LOCKING QUADRANT AND HANDLE ON
BOTTOM OF DUCT FOR EASY SERVICE (SHOWN ON
TOP FOR CLARITY ONLY).
3" MINIMUM
BRANCH DUCT
TAKE-OFF
SEAL JOINT
SEE NOTE 5 AND 8
DUCTWORK RECTANGULAR,
ROUND, OR OVAL
SINGLE BLADE
BALANCING DAMPER APPROX. 6
DUCT SUPPORT
PROVIDE A MINIMUM OF ONE DUCT DIAMETER OF
STRAIGHT DUCT TO THE INLET OF THE DIFFUSER, OR
PROVIDE AN EQUALIZING GRID AT THE DIFFUSER INLET
259 E. Michigan Ave., Suite 407
Kalamazoo, MI 49007
P: 269.585.2255 steelheadengineeringco.com
THE REPRODUCTION, COPYING OR OTHER USE OF THIS
DRAWING WITHOUT WRITTEN AUTHORIZATION IS PROHIBITED.
c SEVEN GENERATIONS ARCHITECTURE & ENGINEERING, LLC
SHEET NO.
SHEET TITLE
JOB NUMBER:
ISSUE DATES:
KEYPLAN
241364
Q N
B M
H C
F
R
TU
C
A B
IN
E T
C
T R
O O
M
IN
D
IA
N H
E A
LT
H
S E R
V
IC
E
B E
LC
O U
R T, N O
R
TH
D A
K O
TA
M600
MECHANICAL
SCHEDULES, DETAILS,
CONTROLS
100% CONSTRUCTION DOCUMENTS11/01/2024
SCALE: NTSM600
SPIN COLLAR FLEXIBLE DUCT CONNECTOR WITH DAMPER AND WITH
LONG RADIUS ELBOW3
SCALE: 1/8" = 1'-0"M600
DUCT MOUNTED STEAM GRID HUMIDIFIER PIPING2
SCALE: NO SCALEM600
DUCTWORK INSTALLATION DIAGRAM1
GRILLES, REGISTERS AND DIFFUSERS SCHEDULE
MARK DESCRIPTION MANUFACTURER MODEL
FACE
SIZE
INSTALLATION/
FRAME TYPE MATERIAL FINISH
MAX
AIRFLOW
CFM
TOTAL
PRESSURE
NECK THROW
DISTANCE
(A) NC (B) NOTESDIAMETER WIDTH HEIGHT
LAY-IN
S10L1 LOUVERED FACE, ROUND NECK
SUPPLY DIFFUSER
TITUS TDC-AA 24x24 LAY-IN ALUMINUM WHITE
ENAMEL
400 CFM 0.09 in-wg 10" 15' - 0" 22 --
GENERAL NOTES:
A. THROW AT 50 FEET PER MINUTE VELOCITY.
B. "-" NC RATING IS LOW ENOUGH TO NOT REGISTER IN THE MANUFACTURER'S DATA.
J
T H
TH
T 1
NEW LP STEAM HUMIDIFIER
EXISTING
DISCONNECT
EXISTING
TRANSFORMER
EXISTING
PANEL
HCT
EXISTING
PANEL
LCT
NEW RTU-CT1
LOCATED ON ROOF
ROOF LEVEL
MAIN LEVEL FINISH FLOOR
CT ELECTRICAL ROOMEXTERIOR INTERIOR
[1] 1” CONDUIT WITH 3 - #6 AND 1 - #10 GROUND.
FEEDER SCHEDULE
RISER LEGEND
NEW FEEDER
EXISTING FEEDER
DEMOLISHED FEEDER
NEW EQUIPMENT
EXISTING EQUIPMENT
DEMOLISHED
EQUIPMENT
INTEGRAL DISCONNECT
SWITCH PROVIDED WITH
RTU-CT1
EX. PANEL
HCT
RTU-CT1
259 E. Michigan Ave., Suite 407
Kalamazoo, MI 49007
P: 269.585.2255 steelheadengineeringco.com
THE REPRODUCTION, COPYING OR OTHER USE OF THIS
DRAWING WITHOUT WRITTEN AUTHORIZATION IS PROHIBITED.
c SEVEN GENERATIONS ARCHITECTURE & ENGINEERING, LLC
SHEET NO.
SHEET TITLE
JOB NUMBER:
ISSUE DATES:
KEYPLAN
241364
Q N
B M
H C
F
R
TU
C
A B
IN
E T
C
T R
O O
M
IN
D
IA
N H
E A
LT
H
S E R
V
IC
E
B E
LC
O U
R T, N O
R
TH
D A
K O
TA
E101
ELECTRICAL PLAN
100% CONSTRUCTION DOCUMENTS11/01/2024
KEYNOTES
1 DEMOLISH BREAKER AND ASSOCIATED BRANCH CIRCUITRY
SERVING EXISTING RTU.
2 HOMERUN CIRCUITRY, 3-#6 AND 1-#10 GROUND IN A 1"
CONDUIT, ROUTED TO A NEW 3-POLE 50-AMP BREAKER FED IN
PANEL HCT.
3 120VAC TO 24VAC TRANSFORMER FOR HUMIDIFIER
ACTUATOR CONTROL. HOMERUN CIRCUITRY, 3-#12 AND
1-#12 GROUND IN A 3/4" CONDUIT, ROUTED TO A NEW 1-POLE
20 A BREAKER IN PANEL LTC, FIELD VERIFY LOCATION AND
CONNECTION REQUIREMENTS.
SCALE: NTSE101
ELECTRICAL DEMOLITION PLAN1
SCALE: NTSE101
ELECTRICAL POWER PLAN2
SCALE: NTSE101
3D - CT Area - Electrical4
GENERAL POWER NOTES
1 WIRE COUNTS FOR CIRCUIT CONDUCTORS ARE NOT SHOWN.
PROVIDE PROPER NUMBER OF CONDUCTORS TO ACHIEVE
CIRCUIT AND SWITCHING CONNECTIONS SHOWN.
2 SINGLE PHASE BRANCH CIRCUITS SHALL NOT SHARE NEUTRALS.
3 PROVIDE THE REQUIRED POWER FOR ALL MECHANICAL OR
PLUMBING EQUIPMENT SPECIFIED IN THE CONTRACT
DOCUMENTS, EVEN IF NOT SHOWN ON THE POWER PLANS.
4 THE CONTRACTOR SHALL FIELD VERIFY THE POWER
REQUIREMENTS OF ALL MECHANICAL AND PLUMBING
EQUIPMENT, WITH THE EQUIPMENT SUPPLIERS, PRIOR TO
PREPARING SUBMITTALS OR ORDERING ANY SWITCHGEAR OR
EQUIPMENT. SUPPLIED PLUMBING AND/OR MECHANICAL
EQUIPMENT MAY VARY FROM EQUIPMENT SPECIFIED IN THE
PLANS.
5 FOR EACH THERMOSTAT, TEMPERATURE SENSOR OR WALL
MOUNTED HVAC CONTROL DEVICE PROVIDE A JUNCTION BOX,
WITH A SINGLE GANG MUD RING, AT 48” ABOVE THE FINISH
FLOOR WITH A ¾” CONDUIT (WITH A PULL STRING) TO ABOVE
THE CEILING FOR THE HVAC CONTROLS. HVAC CONTROLS
WIRING AND DEVICES INSTALLED BY MECHANICAL CONTROLS
CONTRACTOR.
SCALE: NTSE101
ELECTRICAL RISER DIAGRAM3
| Sheets |
| E101 - ELECTRICAL PLAN |
| G000 - COVER SHEET |
| M001 - MECHANICAL GENERAL INFO & SYMBOL LEGEND |
| M101 - FIRST FLOOR MECHANICAL PLAN |
| M600 - MECHANICAL SCHEDULES, DETAILS, CONTROLS |