Attachment_4_Drawings.pdf
PDF 22 MB Posted
- Attached to
- Rehab Power and Cooling Systems, Pinnalces NP
- Solicitation number
- 140P8426R0002
About this file
This document is a comprehensive design and construction package for rehabilitating the off-grid photovoltaic system at Pinnacles National Park's West Side facilities in California (PMIS# 308101). The project is managed by the Department of Interior National Park Service and involves upgrading cooling and energy production systems for the Visitor Contact Station, Housing Area, and Maintenance Facility to address inadequate HVAC and power systems that allow temperatures to exceed 90 degrees Fahrenheit during summer months.
The selected Option 1A includes installation of a new 85 kW generator, 72 kW photovoltaic panels, new chillers, and new inverters, with batteries already purchased separately by the park. The design documentation spans structural, mechanical, and electrical systems with detailed specifications for solar panel mounting on both rooftop and ground-mount structures, battery storage integration, hybrid inverter systems (six 12 kW EG4 18KPV-12LV units), a 70 kVA Generac generator with sound attenuation, phase conversion equipment, and comprehensive HVAC infrastructure modifications. Key electrical components include 180 total Silfab 420-watt solar modules configured in multiple strings, 48 VDC battery system with 441 kWh capacity, 800-amp main distribution panelboard, and necessary disconnect switches with rapid shutdown capability compliant with NEC Article 690. Construction requires coordination with existing utilities, temporary power provisions during installation shutdowns, and compliance with International Building Code 2024, ASHRAE standards, seismic design criteria, and all applicable electrical codes and standards.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REHABILITATE WESTSIDE OFF GRID
PHOTOVOLTAIC SYSTEM
REHABILITATE WESTSIDE OFF-GRID PHOTOVOLTAIC SYSTEM PINNACLES
NATIONAL PARK.
THIS PROJECT WILL DESIGN AN UPGRADE TO THE COOLING SYSTEM AND ENERGY
PRODUCTION SYSTEMS THAT SERVE THE PINNACLES NATIONAL PARK WEST SIDE
VISITOR CONTACT STATION, HOUSING AREA, AND MAINTENANCE FACILITY.
CURRENTLY TEMPERATURES IN THESE FACILITIES CAN REACH INTO THE 90+ DEGREE
FAHRENHEIT RANGE DURING SUMMER DUE TO INADEQUATE HVAC AND POWER
SYSTEMS. TITLE I SERVICES TO DETERMINE THE BEST ALTERNATIVE WAS
COMPLETED BY JOSEPH CHOW AND ASSOCIATES (JCA) AND TITLE I SERVICES TO
VALIDATE THE JCA EFFORT WAS COMPLETED BY AECOM. THE CHOSEN ALTERNATIVE
IS TO DO OPTION 1A WHICH INCLUDES A NEW 85 KW GENERATOR, NEW 72 KW PV
PANELS, NEW CHILLERS, AND NEW INVERTERS. NEW BATTERIES HAVE BEEN
PURCHASED BY THE PARK AND ARE NOT PART OF THE COSTS OF THIS PROJECT.
NOTE:
1. PAD SIZE SHALL EXTEND 1'-6" MIN BEYOND THE EQUIPMENT
LAYOUT, OR AS REQUIRED BY EQUIPMENT SUPPLIER.
2. HILTI HY-200 W/ HAS ROD WAS USED AS BASIS OF DESIGN.
(4) 1/2" DIA. ADHESIVE ANCHORS
MIN. EMBEDMENT = 5"
4"
3' -0
"8" 1'
-0
#5 @ 12" OC
EW T&B
#5 @ 12" OC EF
#5 @ 12" OC EF
1'-0"
1'-0" (MIN)
COMPACTED
GRANULAR BASE
CONTRACTOR TO COORDINATE
LOCATION OF PADS TO
ACCOMODATE POSSIBLE SOUND
ATTENUATION WALLS.
(2) #4 ADDITIONAL
TIES IN THE TOP 5"
5' -6
" E M
BE
D
2'-6" DIA
(12) #7 VERT BARS
T/PIER
3" C
LR
#4 @ 8" OC
CONC PIER
PIPE AND EMBEDMENT
PER MANUFACTURER'S
RECOMMENDATIONS.
2'-6" DIA
2 1/2" CLR (TYP)
(12) #7 BARS
NOTE:
1. FOUNDATIONS HAVE BEEN DESIGNED USING TYPICAL SOLAR PANEL SYSTEM
LOADS. FINAL REACTIONS AND SELECTED SOLAR PANEL SYSTEM SHALL BE
SUBMITTED TO THE ENGINEER OF RECORD FOR REVIEW AND VERIFICATION OF THE
FOUNDATION DESIGN.
R
EF
ER
T
O S
O
LA
R
PA
N
EL
M
AN
U
FA
C
TU
R
ER
REFER TO SOLAR PANEL MANUFACTURER
CONCRETE PIER PER DETAIL 2
7' -6
12'-0" MAX ℄℄
NOTES:
1. PIER SPACING PER MANUFACTURER'S RECOMMENDATIONS. NOT TO EXCEED 12'-0".
2' -6
1'-6"
DIA.
T/PIER
(4) #5 VERT W/
(3) #4 TIES AT 1'-0"
SPACING
(2) #4 ADDITIONAL
TIES IN THE TOP 5"
PIPE STD 6
GROUT FILL PIPE
CONC FTG
2' -0
" E M
BE
D
M
EN
T
3" C
LR
2" CLR.
3' -6
3/4" = 1'-0"3 TYPICAL EQUIPMENT PAD
GENERAL CONDITIONS
1. GOVERNING BUILDING CODE: INTERNATIONAL BUILDING CODE (IBC), 2024 EDITION.
2. COORDINATE WITH ALL DRAWINGS FOR PERTINENT INFORMATION RELATED TO THE STRUCTURAL WORK. ALL CHANGES TO THE STRUCTURAL SYSTEMS SHALL BE RE-DESIGNED BY A PROFESSIONAL ENGINEER AT NO COST TO THE OWNER OR A/E AND SUBMITTED TO THE A/E FOR REVIEW. SUBMITTAL SHALL BE REVIEWED AND ACKNOWLEDGED
IN WRITING BY THE A/E BEFORE BEGINNING CONSTRUCTION.
3. EQUIPMENT FRAMING LOADS, OPENINGS AND STRUCTURE IN ANY WAY RELATED TO HVAC, PLUMBING, PROCESS, ELECTRICAL, ELEVATOR, OR ESCALATOR REQUIREMENTS ARE SHOWN FOR BIDDING PURPOSES ONLY. OBTAIN APPROVAL OF THE PERTINENT TRADES BEFORE PROCEEDING WITH SUCH PORTION OF THE WORK. EXCESS COST RELATED TO VARIATION IN THESE REQUIREMENTS SHALL BE BORNE BY THE APPROPRIATE CONTRACTOR.
4.IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE THE ERECTION PROCEDURE AND SEQUENCE TO ENSURE THE SAFETY OF THE BUILDING AND ITS COMPONENT PARTS DURING ERECTION. THIS INCLUDES, BUT IS NOT LIMITED TO, THE ADDITION OF WHATEVER TEMPORARY BRACING, GUYS OR TIE-DOWNS MAY BE NECESSARY.
5. THE STRUCTURE HAS BEEN DESIGNED FOR THE UNIFORM LOADS INDICATED IN ADDITION TO THE CONCENTRATED LOADS REQUIRED BY THE BUILDING CODE. THE STRUCTURAL DESIGN IS BASED SOLELY ON THE BUILDING IN ITS COMPLETED STATE. CONTRACTORS AND THEIR SUB-CONTRACTORS SHALL TAKE WHATEVER PRECAUTIONS ARE NECESSARY TO WITHSTAND ALL HORIZONTAL AND VERTICAL LOADINGS THAT MAY BE ENCOUNTERED DURING CONSTRUCTION PRIOR TO COMPLETION OF THE BUILDING. SUCH CONSTRUCTION LOADINGS INCLUDE (BUT ARE NOT LIMITED TO) LOADS FROM CRANES, LIFTS, DOLLIES, AND HOISTS. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE EVALUATION OF THE IMPACT OF SUCH LOADS ON THE STRUCTURE AND PROVIDING TEMPORARY SHORING, BRACING, AND REINFORCEMENT AS REQUIRED.
6. SEE THE ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS NOT SHOWN ON THE STRUCTURAL DRAWINGS. ALL DIMENSIONS AND ELEVATIONS SHOWN ON THE STRUCTURAL DRAWINGS SHALL BE VERIFIED BY THE CONTRACTOR AND SHALL CONFORM TO THOSE SHOWN ON THE ARCHITECTURAL DRAWINGS. REPORT ALL DISCREPANCIES TO THE
A/E FOR RESOLUTION BEFORE PROCEEDING.
7. FIELD VERIFY ALL EXISTING DIMENSIONS WHICH AFFECT THE NEW CONSTRUCTION PRIOR TO FINAL DETAILING AND
FABRICATION OF NEW STRUCTURAL ELEMENTS.
8. THE CONTRACTOR SHALL SUPPORT, BRACE AND SECURE EXISTING STRUCTURES AS REQUIRED. THE CONTRACTOR
IS SOLELY RESPONSIBLE FOR THE SAFETY OF EXISTING STRUCTURES DURING CONSTRUCTION.
STRUCTURAL DESIGN LOADS
1. DESIGN LIVE LOADS:
A. MECHANICAL AND ELECTRICAL EQUIPMENT = 150 PSF
2.DESIGN SNOW LOAD AND SNOW DRIFTING SHALL CONFORM WITH THE BUILDING CODE. SNOW LOAD DESIGN
PARAMETERS ARE AS FOLLOWS:
A. GROUND SNOW LOAD (Pg) = 11 PSF B. SNOW EXPOSURE FACTOR (Ce) = 0.9 C. SNOW THERMAL FACTOR (Ct) = 1.2 D. MINIMUM SNOW LOAD FOR LOW SLOPE ROOFS (Pm) = 11 PSF E. FLAT-ROOF SNOW LOAD (Pf) = 8.5 PSF
F. WINTER WIND PARAMETER = 0.25
3. DESIGN RAIN LOADS:
A. DESIGN RAINFALL INTENSITY = 2.14 IN/HR
B. DESIGN RAIN LOAD = 1.02 PSF
7. WIND DESIGN SHALL CONFORM WITH THE BUILDING CODE. WIND DESIGN PARAMETERS ARE AS FOLLOWS:
A. ULTIMATE DESIGN WIND SPEED (VULT), (3 SECOND GUST) = 92 MPH
B. NOMINAL DESIGN WIND SPEED (Vasd) = 72 MPH
C. RISK CATEGORY = II
D. WIND EXPOSURE CATEGORY = EXPOSURE C
E. INTERNAL PRESSURE COEFFICIENT = ±0.18
8. SEISMIC DESIGN SHALL CONFORM WITH SECTION 1613 OF THE BUILDING CODE. SEISMIC DESIGN PARAMETERS ARE AS
FOLLOWS:
A. SOIL SITE CLASS = DEFAULT
B. MAPPED SPECTRAL RESPONSE ACCELERATION:
a. SS = 1.50g
b. S1 = 0.60g
C. DESIGN SPECTRAL RESPONSE ACCELERATION:
a. SDS = 1.10g
b. SD1 = 1.16g
D. BUILDING RISK CATEGORY = II
E. SEISMIC DESIGN CATEGORY = D
F. SEISMIC IMPORTANCE FACTOR (Ie) = 1.0 G. ATTACHMENT OF ARCHITECTURAL, MECHANICAL, ELECTRICAL AND PROCESS SYSTEMS COMPONENTS TO COMPLY
WITH THE BUILDING CODE AND ASCE 7.
FOUNDATIONS, EXCAVATION AND BACKFILL
1. FOUNDATIONS HAVE BEEN DESIGNED IN ACCORDANCE WITH PRESUMPTIVE IBC VALUES. THE CONTRACTOR SHALL BECOME FAMILIAR WITH THE SURVEY PRIOR TO BIDDING AND BEFORE BEGINNING CONSTRUCTION.
2. SET FOUNDATIONS AT THE ELEVATIONS SHOWN ON THE DRAWINGS ON FIRM SUBGRADE PREPARED PER THE EARTHWORK SPECIFICATIONS. VERIFY THAT EACH FOOTING PLACED IS BEARING ON MATERIAL WITH THE DESIGN BEARING CAPACITY. FOUNDATION DESIGN VERTICAL BEARING CAPACITY PER PRESUMPTIVE IBC VALUES = 1500 PSF.
LATERAL BEARING PRESSURE CAPACITY PER PRESUMPTIVE IBC VALUES = 100PSF/FT
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN, INSTALLATION AND FINAL CLEARANCE OF ALL REQUIRED
NEEDLING, UNDERPINNING, SHORING OR BRACING OF EXISTING STRUCTURES.
4.BACKFILL BEHIND WALLS:
A. BACKFILL AGAINST BOTH SIDES OF WALLS EQUALLY UNTIL THE LOWER ELEVATION IS ATTAINED.
B. BACKFILL AGAINST WALLS SHALL NOT BE PLACED UNTIL THE FLOOR CONSTRUCTION AT THE TOP AND BOTTOM OF
THE WALL HAS BEEN COMPLETED TO BRACE THE WALL.
C. AT THE CONTRACTOR'S OPTION, WALLS MAY BE BRACED AND BACKFILL INSTALLED PRIOR TO COMPLETION OF THE
SUPPORTING FLOORS. ALL SUCH BRACING SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER, IS SOLELY THE RESPONSIBILITY OF THE CONTRACTOR, AND SHALL REMAIN IN PLACE UNTIL CONSTRUCTION OF THE SUPPORTING
FLOORS IS COMPLETED AND CONTINUOUSLY CONNECTED TO THE WALLS.
5. BUILDING EXCAVATION AND COMPACTION:
A. CARE SHALL BE TAKEN TO NOT DISTURB THE BOTTOM OF THE EXCAVATION. EXCAVATION TO FINAL GRADE SHALL
NOT BE MADE UNTIL JUST PRIOR TO PLACING CONCRETE.
B. PLACE BACKFILL AND FILL IN LIFTS OF 8" MAXIMUM LOOSE DEPTH. COMPACT EACH LIFT WITH A POWER VIBRATING
COMPACTOR OR SIMILAR EQUIPMENT TO ENSURE MAXIMUM COMPACTION OF THE MATERIAL.
C. FILL COMPACTION:
a. COMPACT COHESIVE MATERIAL FILL TO 95% OF MAXIMUM DENSITY ACCORDING TO ASTM D698.
b. COMPACT COHESIONLESS MATERIAL FILL FOR DRAINAGE TO 95% OF MAXIMUM DENSITY ACCORDING TO ASTM
D698.
D. SETTLEMENT OR WASHING OUT THAT OCCURS IN GRADED OR BACKFILLED AREAS PRIOR TO ACCEPTANCE OF THE
WORK SHALL BE REPAIRED AND GRADES RE-ESTABLISHED TO THE REQUIRED ELEVATIONS AND SLOPES.
CAST-IN-PLACE CONCRETE
1.CAST-IN-PLACE CONCRETE WORK SHALL CONFORM TO THE PROJECT MANUAL AND LATEST AMERICAN CONCRETE INSTITUTE CODES AND STANDARDS, INCLUDING, BUT NOT LIMITED TO, ACI 117, ACI 301, ACI 315 AND ACI 318.
2. MATERIALS AND PRODUCTS:
A. BAR REINFORCING STEEL: DOMESTIC DEFORMED BILLET STEEL CONFORMING TO ASTM A615, GRADE 60
B. CONCRETE:
a. CONCRETE SHALL HAVE THE FOLLOWING MINIMUM COMPRESSIVE STRENGTHS AT 28 DAYS (f'c):
· 4500 PSI FOR CONCRETE EXPOSED TO WEATHER
b. PROVIDE ENTRAINED AIR IN CONCRETE EXPOSED TO WEATHER OR WATER
3.CONTRACTION AND CONSTRUCTION JOINTS:
A. CONCRETE FOUNDATIONS, BEAMS, SLABS AND WALLS:
a. BEAMS AND SLABS SHALL BE CAST MONOLITHICALLY, EXCEPT FOR REQUIRED CONTRACTION/CONSTRUCTION
JOINTS SHOWN ON THE DRAWINGS.
b. PROVIDE VERTICAL CONTRACTION/CONSTRUCTION JOINTS IN SLABS AND HORIZONTAL
CONTRACTION/CONSTRUCTION JOINTS IN WALLS AS SHOWN ON THE DRAWINGS.
c. CONSTRUCTION JOINTS:
· WHERE CONSTRUCTION JOINTS ARE REQUIRED BUT ARE NOT INDICATED ON THE DRAWINGS, THEY SHALL
BE LOCATED AT THE MID-SPAN OF BEAMS, SLABS AND WALLS.
· AT LEAST 48 HOURS SHALL ELAPSE BETWEEN CASTING OF ADJOINING UNITS AT A CONSTRUCTION JOINT.
· UNLESS NOTED OTHERWISE OR SHOWN ON THE DRAWINGS, PROVIDE A CONTINUOUS SHEAR KEY IN SLABS
AND WALLS, AND A MINIMUM OF TWO (2) CONTINUOUS HORIZONTAL KEYS IN BEAMS AND EACH JOIST AT CONSTRUCTION JOINTS. THE MINIMUM KEY SIZE SHALL BE 1 1/2" DEEP X 1/3 THE DEPTH OR WIDTH OF THE
MEMBER.
· REINFORCEMENT SHALL BE CONTINUOUS ACROSS CONSTRUCTION JOINTS UNLESS DETAILED OTHERWISE
ON THE DRAWINGS.
· CONSTRUCTION JOINTS BELOW GRADE SHALL HAVE WATERSTOPS UNLESS BOTH SIDES OF THE JOINT ARE
EXPOSED TO EARTH.
· HARDENED CONCRETE OF HORIZONTAL CONSTRUCTION JOINTS SHALL BE DAMPENED AND THEN
THOROUGHLY COVERED WITH A COAT OF CEMENT GROUT OF SIMILAR PROPORTIONS TO THE MORTAR IN THE CONCRETE. THE FRESH CONCRETE SHALL BE PLACED BEFORE THE GROUT HAS ATTAINED ITS INITIAL
SET.
· HARDENED CONCRETE OF CONSTRUCTION JOINTS SHALL BE THOROUGHLY COATED WITH A BONDING
AGENT (SIKA ARMATEC 110 OR EQUAL).
· JOINT LOCATIONS SHALL BE SUBMITTED WITH THE ASSOCIATED REINFORCING STEEL SHOP DRAWINGS AND
ARE SUBJECT TO REVIEW BY THE A/E.
· CONTRACTOR SHALL SUBMIT ALTERNATE AND ADDITIONAL CONSTRUCTION JOINT LOCATIONS AND DETAILS
TO THE A/E FOR APPROVAL PRIOR TO CONSTRUCTION.
d. REFERENCE ACI 302 FOR GUIDELINES AND ADDITIONAL INFORMATION.
4.DOWELS IN FOOTINGS TO MATCH VERTICAL COLUMN AND WALL REINFORCING UNLESS SHOWN OTHERWISE.
5.PROVIDE 3/4" CHAMFERS ON EXPOSED CORNERS OF COLUMNS, BEAMS AND WALLS UNLESS OTHERWISE INDICATED ON THE ARCHITECTURAL DRAWINGS. MINIMUM CLEARANCES FOR REINFORCING STEEL SHALL CONFORM WITH THE
TYPICAL REINFORCING BAR CLEARANCE TABLE.
6.EMBEDDED ITEMS, SLEEVES, SLAB DEPRESSIONS, OPENINGS, ETC:
A. THE CONTRACTOR SHALL REVIEW ALL DRAWINGS FOR SIZE AND LOCATION OF EMBEDDED ITEMS, SLEEVES, SLAB
DEPRESSIONS, OPENINGS, ETC. REQUIRED BY OTHER TRADES. RECONCILE THEIR EXACT SIZES AND LOCATIONS
BEFORE PROCEEDING WITH THE WORK.
B. ALL ITEMS SHALL BE FURNISHED AND INSTALLED PRIOR TO PLACEMENT OF CONCRETE.
C. SECURE THE APPROVAL OF THE STRUCTURAL ENGINEER PRIOR TO PLACING OPENINGS NOT SHOWN ON THE
STRUCTURAL DRAWINGS.
D. NO CONDUIT SHALL BE PLACED IN CONCRETE SLABS OR BEAMS UNLESS SPECIFICALLY SHOWN ON THE
STRUCTURAL DRAWINGS.
7.REINFORCING:
A. WHERE BAR LENGTHS ARE GIVEN ON THE DRAWINGS, THE LENGTH OF ANY HOOK, IF REQUIRED, IS NOT INCLUDED.
USE STANDARD 90° BAR HOOK UNLESS NOTED OTHERWISE.
B. UNLESS INDICATED OTHERWISE, WELDING OF REINFORCING IS NOT PERMITTED.
C. LAP/SPLICE:
a. REINFORCING BAR LAP SPLICES AND ANCHORAGE LENGTHS SHALL CONFORM WITH TABLE #1, "MINIMUM LAP
SPLICE AND ANCHORAGE DIMENSION TABLE".
b. LAP WELDED WIRE FABRIC 1 SPACE (2 CROSS WIRES) + 2" AT EDGES AND ENDS OF SHEETS.
c. WHERE REINFORCING IS SHOWN THROUGH CONSTRUCTION JOINTS, MECHANICAL BAR SPLICE DEVICES MAY BE
USED.
D. REINFORCING BAR SUPPORT:
a. DETAIL AND PROVIDE REINFORCING BARS AND SUPPORT REQUIRED FOR PROPER SUPPORT OF PRINCIPAL REINFORCING WHETHER OR NOT THEY ARE INDICATED ON THE DRAWINGS. MINIMUM BAR SIZE SHALL BE #4 AND MAXIMUM SPACING SHALL BE 36" ON CENTER FOR REINFORCING THAT SUPPORTS PRIMARY REINFORCING.
DO NOT USE WELDED WIRE FABRIC FOR THE SUPPORT OF PRINCIPAL REINFORCING.
b. PROVIDE CONCRETE CUBES OR SAND PLATED CHAIRS FOR THE SUPPORT OF REINFORCING ON GRADE.
c. WELDED WIRE FABRIC SHALL BE CHAIRED TO ITS PROPER HEIGHT AND MAINTAINED AT THE PROPER LEVEL
THROUGHOUT THE CONCRETE PLACING OPERATION. LIFTING OF WELDED WIRE FABRIC WITH A HOOK DURING
CONCRETE PLACEMENT SHALL NOT BE PERMITTED.
TABLE 2
TYPICAL REINFORCING BAR CLEARANCE TABLE
LOCATION
CLEARANCE
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 3"
WALLS (INTERIOR FACE) 1"
WALLS (EXTERIOR FACE, #5 AND SMALLER) 1 1/2"
WALLS (EXTERIOR FACE, #6 AND LARGER) 2"
SLABS ON GRADE (BOTTOM REINFORCING) 2"
TABLE 1
MINIMUM LAP SPLICE AND ANCHORAGE DIMENSION TABLE
USE THIS TABLE FOR ASTM A615 GRADE 60-UNCOATED REINFORCING WHEN CONCRETE CLEAR COVER IS 1" OR MORE AND BAR CLEAR SPACING IS GREATER THAN OR EQUAL TO THREE (3) BAR DIAMETERS. IF CONCRETE CLEAR COVER IS LESS THAN 1", LAP AND ANCHORAGE LENGTHS SHALL BE CALCULATED PER ACI 318.
TABLES 1 NOTES:
A. FOR EPOXY COATED REINFORCING MULTIPLY THE TABLE VALUES ABOVE BY 1.31 FOR TOP BARS AND 1.5 FOR
OTHER BARS.
B. FOR LIGHTWEIGHT CONCRETE MULTIPLY THE TABLE VALUES ABOVE BY 1.3.
C. FOR BUNDLED BARS MULTIPLY THE TABLE VALUES ABOVE BY: 1.2 (3 BAR BUNDLE), 1.33 (4 BAR BUNDLE).
D. (MC) DENOTES MECHANICAL COUPLER DEVELOPING 125% OF THE BAR YIELD STRENGTH. NO OTHER SPLICE WILL
BE ACCEPTED.
E. WHEN LAPPING TWO DIFFERENT SIZE BARS, USE THE LAP DIMENSION OF THE SMALLER BAR OR THE ANCHORAGE
DIMENSION OF THE LARGER BAR. USE WHICHEVER DIMENSION IS LARGER.
F. TOP BARS SHALL BE DEFINED AS BEAM AND SLAB HORIZONTAL REINFORCEMENT SO PLACED THAT MORE THAN
12" OF FRESH CONCRETE IS CAST IN THE MEMBER BELOW THE TOP REINFORCEMENT. HORIZONTAL REINFORCING
IN WALLS SHALL BE CONSIDERED TOP BARS.
(4500 PSI CONCRETE)
TOP BARS OTHER BARS
BAR SIZE LAP ANCH LAP ANCH
#3 23" 18" 18" 14"
#4 31" 25" 25" 19"
#5 38" 30" 30" 23"
#6 46" 35" 35" 27"
STRUCTURAL ABBREVIATIONS
℄ CENTER LINE
CLR CLEAR
CONC CONCRETE
DIA DIAMETER
EA EACH
EF EACH FACE
EL ELEVATION
EOR ENGINEER OF RECORD
EW EACH WAY
FTG FOOTING
OC ON CENTER
MAX MAXIMUM
MIN MINIMUM
T&B TOP AND BOTTOM
TYP TYPICAL
T/ TOP OF
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
W/ WITH
3/4" = 1'-0"2 TYPICAL PIER DETAIL
1/8" = 1'-0"1 TYPICAL SOLAR PANEL SUPPORT PIERS PLAN
STRUCTURAL GENERAL NOTES
3/4" = 1'-0"4 TYPICAL BOLLARD DETAIL
AutoCAD SHX Text
REHABILITATE WESTSIDE
AutoCAD SHX Text
OFF-GRID PHOTOVOLTAIC SYSTEM
AutoCAD SHX Text
PINNACLES NATIONAL PARK
AutoCAD SHX Text
NATIONAL PARK SERVICE - NPS REGIONS 8,9,10,12, PACIFIC WEST REGION
AutoCAD SHX Text
DESIGN AND CONSTRUCTION
AutoCAD SHX Text
A/E FIRM
AutoCAD SHX Text
UNITED STATES
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DWG. NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DEPARTMENT OF THE INTERIOR
AutoCAD SHX Text
SUB SHEET NUMBER
AutoCAD SHX Text
TITLE OF DRAWING
AutoCAD SHX Text Mark
AutoCAD SHX Text Sheet
AutoCAD SHX Text Initial
AutoCAD SHX Text Date
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
TITLE OF PROJECT
AutoCAD SHX Text
NAME OF PARK
AutoCAD SHX Text
LOCATION WITHIN PARK
AutoCAD SHX Text
OF
AutoCAD SHX Text
AECOM 7595 TECHNOLOGY WAY SUITE 200 DENVER, CO 80237 (303)694-3946
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
JE
AutoCAD SHX Text
JK
AutoCAD SHX Text
SV
AutoCAD SHX Text S-001
AutoCAD SHX Text
STRUCTURAL NOTES, PLAN, & DETAILS
AutoCAD SHX Text 03/13/2026
AutoCAD SHX Text
50% SUBMITTAL
AutoCAD SHX Text 10/25
AutoCAD SHX Text
RG
AutoCAD SHX Text
90% SUBMITTAL
AutoCAD SHX Text 1/26
AutoCAD SHX Text
RG
AutoCAD SHX Text
100% SUBMITTAL
AutoCAD SHX Text 3/26
AutoCAD SHX Text
RG
DHW
DCW
CHWS
CHWR
GAS
OUTDOOR DESIGN CONDITIONS ARE BASED ON 2025 ASHRAE FUNDAMENTALS - CLIMATIC DESIGN CONDITIONS FOR (HOLLISTER, CA - WMO ID# 749179)
03/13/2026
EXISTING
20,000 GALLON
CHILLED
WATER AND
FIRE WATER
TANK
EXISTING
7,000 GALLON
DOMESTIC
WATER TANK
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 3" DCW
(E) AH-2
(E) AH-4
(E) AH-3
(E) AH-5
(E) AH-1
(E) FC-1
EXISTING
20,000 GALLON
CHILLED
WATER AND
FIRE WATER
TANK
EXISTING
7,000 GALLON
DOMESTIC
WATER TANK
CH-1
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 3" DCW
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
3" CHWS
3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
WEST
PINNACLES
VISITORS
CENTER
MAINTENANCE
BUILDING
HOUSING
UNIT
HOUSING
UNIT
HOUSING
UNIT
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 3" DCW
AIR-COOLED CHILLER,
SEE SHEETS M-501
AND M-601
PROPOSED
EXCAVATION AREA,
SEE SPECIFICATIONS
SECTION 312000
CONCRETE PAD, SEE
STRUCTURAL DRAWINGS
EXISTING 2.0 PSI REGULATOR, MAIN SHUTOFF VALVE
AND METER.
CONNECT EXISTING 1" PROPANE GAS FROM EXISTING
GAS MAIN DOWNSTREAM OF METER AND REGULATOR TO
NEW GENERATOR. SIZED PER 2024 IFGC SECTION 402.4.2
BRANCH LENGTH METHOD. PROVIDE SCHEDULE 40
METALLIC PIPING AND 0.5 PSI MAXITROL REGULATOR.
SEE LP GAS NOTES ON SHEET M-001.
CONNECT NEW 3" CHWS AND 3" CHWR
PIPING TO EXISTING 6" CHWS/FL PIPE IN
PUMP/PIPING ROOM. VERIFY SIZING,
LOCATION, AND POINT OF CONNECTION
IN FIELD PRIOR TO CONSTRUCTION,
SEE CHILLED WATER CONNECTION
DETAIL.
'-2
15'-10"
3'-0"
DEMOLISH EXISTINGINTAKE DUCTWORK UPTO EXTERIOR LOUVER.
DEMOLISH EXISTING EXHAUST VENT,DEMO EXISTING OPENING TO 15"X15"
EXISTING GENERATOR TO BE
DEMOLISHED, SEE ELECTRICALDRAWINGS. INSTALL TYPE 316 STAINLESS STEEL
DUCT (20 GAUGE)
MOTORIZED DAMPER (MD-1) TO BE
INTERLOCKED WITH FAN OPERATION,SEE FAN SCHEDULE
EF-1 OPEN EXHAUST DUCTWITH BIRD SCREEN
GRADE
INTERIOREXTERIORINTERIOREXTERIOR
GRADE
PROVIDE LATERAL BRACING TO
SUPPORT FAN TO STRUCTURE
NEW FAN (EF-1)
OVERHEAD, SEE SECTION
DEMOLISH EXISTINGINTAKE DUCTWORK UPTO EXTERIOR LOUVER.
DEMOLISH EXISTING EXHAUST VENT,DEMO EXISTING OPENING TO 15"X15"
EXISTING GENERATOR TO BE
DEMOLISHED, SEE ELECTRICALDRAWINGS.INSTALL TYPE 316 STAINLESS STEEL
DUCT (20 GAUGE)
MOTORIZED DAMPER (MD-1) TO BEINTERLOCKED WITH FAN OPERATION,
SEE FAN SCHEDULE
EF-1OPEN EXHAUST DUCTWITH BIRD SCREEN
GRADE
INTERIOR EXTERIOR INTERIOR EXTERIOR
GRADE
PROVIDE LATERAL BRACING TO
SUPPORT FAN TO STRUCTURE
KEY PLAN
AREA OF WORK
GENERAL NOTE:
A. IF NO NEW WORK IS SHOWN. SHEET IS FOR
REFERENCE INFORMATION ONLY.
MECHANICAL PLANS
SCALE: 1/16" = 1'-0"
(E) AH-2
(E) AH-4
(E) AH-3
(E) AH-5
(E) FC-1
CH-1
CHWSCHWS
C H
W S
CHWRCHWR
C H
W R
C H
W R
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
3" CHWS
3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
MAINTENANCE
BUILDING
HOUSING
UNIT
HOUSING
UNIT
HOUSING
UNIT
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 3" DCW
AIR-COOLED CHILLER,
SEE SHEETS M-501
AND M-601
PROPOSED
EXCAVATION AREA,
SEE SPECIFICATIONS
SECTION 312000
CONCRETE PAD, SEE
STRUCTURAL DRAWINGS
EXISTING 2.0 PSI REGULATOR, MAIN SHUTOFF VALVE
AND METER.
CONNECT EXISTING 1" PROPANE GAS FROM EXISTING
GAS MAIN DOWNSTREAM OF METER AND REGULATOR TO
NEW GENERATOR. SIZED PER 2024 IFGC SECTION 402.4.2
BRANCH LENGTH METHOD. PROVIDE SCHEDULE 40
METALLIC PIPING AND 0.5 PSI MAXITROL REGULATOR.
SEE LP GAS NOTES ON SHEET M-001.
CONNECT NEW 3" CHWS AND 3" CHWR
PIPING TO EXISTING 6" CHWS/FL PIPE IN
PUMP/PIPING ROOM. VERIFY SIZING,
LOCATION, AND POINT OF CONNECTION
IN FIELD PRIOR TO CONSTRUCTION,
SEE CHILLED WATER CONNECTION
DETAIL.
'-2
15'-10"
3'-0"
NEW FAN (EF-1)
OVERHEAD, SEE SECTION
(E) AH-2
(E) AH-4
(E) AH-3
(E) AH-5
(E) AH-1
(E) FC-1
EXISTING
20,000 GALLON
CHILLED
WATER AND
FIRE WATER
TANK
EXISTING
7,000 GALLON
DOMESTIC
WATER TANK
CH-1
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 3" DCW
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
3" CHWS
3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
WEST
PINNACLES
VISITORS
CENTER
MAINTENANCE
BUILDING
HOUSING
UNIT
HOUSING
UNIT
HOUSING
UNIT
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 3" DCW
AIR-COOLED CHILLER,
SEE SHEETS M-501
AND M-601
PROPOSED
EXCAVATION AREA,
SEE SPECIFICATIONS
SECTION 312000
CONCRETE PAD, SEE
STRUCTURAL DRAWINGS
EXISTING 2.0 PSI REGULATOR, MAIN SHUTOFF VALVE
AND METER.
CONNECT EXISTING 1" PROPANE GAS FROM EXISTING
GAS MAIN DOWNSTREAM OF METER AND REGULATOR TO
NEW GENERATOR. SIZED PER 2024 IFGC SECTION 402.4.2
BRANCH LENGTH METHOD. PROVIDE SCHEDULE 40
METALLIC PIPING AND 0.5 PSI MAXITROL REGULATOR.
SEE LP GAS NOTES ON SHEET M-001.
CONNECT NEW 3" CHWS AND 3" CHWR
PIPING TO EXISTING 6" CHWS/FL PIPE IN
PUMP/PIPING ROOM. VERIFY SIZING,
LOCATION, AND POINT OF CONNECTION
IN FIELD PRIOR TO CONSTRUCTION,
SEE CHILLED WATER CONNECTION
DETAIL.
'-2
15'-10"
3'-0"
DEMOLISH EXISTINGINTAKE DUCTWORK UP
TO EXTERIOR LOUVER.
DEMOLISH EXISTING EXHAUST VENT,DEMO EXISTING OPENING TO 15"X15"
EXISTING GENERATOR TO BE
DEMOLISHED, SEE ELECTRICALDRAWINGS. INSTALL TYPE 316 STAINLESS STEELDUCT (20 GAUGE)
MOTORIZED DAMPER (MD-1) TO BE
INTERLOCKED WITH FAN OPERATION,SEE FAN SCHEDULE
EF-1 OPEN EXHAUST DUCTWITH BIRD SCREEN
GRADE
INTERIOREXTERIORINTERIOREXTERIOR
GRADE
PROVIDE LATERAL BRACING TOSUPPORT FAN TO STRUCTURE
NEW FAN (EF-1)
OVERHEAD, SEE SECTION
DEMOLISH EXISTINGINTAKE DUCTWORK UP
TO EXTERIOR LOUVER.
DEMOLISH EXISTING EXHAUST VENT,
DEMO EXISTING OPENING TO 15"X15"
EXISTING GENERATOR TO BE
DEMOLISHED, SEE ELECTRICALDRAWINGS.INSTALL TYPE 316 STAINLESS STEELDUCT (20 GAUGE)
MOTORIZED DAMPER (MD-1) TO BE
INTERLOCKED WITH FAN OPERATION,SEE FAN SCHEDULE
EF-1OPEN EXHAUST DUCTWITH BIRD SCREEN
GRADE
INTERIOR EXTERIOR INTERIOR EXTERIOR
GRADE
PROVIDE LATERAL BRACING TOSUPPORT FAN TO STRUCTURE
DEMOLISH EXISTING
INTAKE DUCTWORK UP
TO EXTERIOR LOUVER.
DEMOLISH EXISTING EXHAUST VENT,
DEMO EXISTING OPENING TO 15"X15"
EXISTING GENERATOR TO BE
DEMOLISHED, SEE ELECTRICAL
DRAWINGS.
INTERIOR EXTERIOR
GRADE
INSTALL TYPE 316 STAINLESS STEEL
DUCT (20 GAUGE)
MOTORIZED DAMPER (MD-1) TO BE
INTERLOCKED WITH FAN OPERATION,
SEE FAN SCHEDULE
EF-1OPEN EXHAUST DUCT
WITH BIRD SCREEN
GRADE
INTERIOR EXTERIOR
PROVIDE LATERAL BRACING TO
SUPPORT FAN TO STRUCTURE
KEY PLAN
AREA OF WORK
GENERAL NOTE:
A. IF NO NEW WORK IS SHOWN. SHEET IS FOR
REFERENCE INFORMATION ONLY.
MECHANICAL PLANS
SCALE: 1/16" = 1'-0"
MECHANICAL DEMO SECTION
SCALE: 1/4" = 1'-0"
MECHANICAL SECTION
SCALE: 1/4" = 1'-0"
(E) AH-1
(E) 6" CHWS/FL
(E) 3" CHWR
WEST
PINNACLES
VISITORS
CENTER
(E) AH-2
(E) AH-4
(E) AH-3
(E) AH-5
(E) AH-1
(E) FC-1
EXISTING
20,000 GALLON
CHILLED
WATER AND
FIRE WATER
TANK
EXISTING
7,000 GALLON
DOMESTIC
WATER TANK
CH-1
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 3" DCW
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
3" CHWS
3" CHWR
(E) 6" CHWS/FL
(E) 3" CHWR
WEST
PINNACLES
VISITORS
CENTER
MAINTENANCE
BUILDING
HOUSING
UNIT
HOUSING
UNIT
HOUSING
UNIT
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 3" DCW
AIR-COOLED CHILLER,
SEE SHEETS M-501
AND M-601
PROPOSED
EXCAVATION AREA,
SEE SPECIFICATIONS
SECTION 312000
CONCRETE PAD, SEE
STRUCTURAL DRAWINGS
EXISTING 2.0 PSI REGULATOR, MAIN SHUTOFF VALVE
AND METER.
CONNECT EXISTING 1" PROPANE GAS FROM EXISTING
GAS MAIN DOWNSTREAM OF METER AND REGULATOR TO
NEW GENERATOR. SIZED PER 2024 IFGC SECTION 402.4.2
BRANCH LENGTH METHOD. PROVIDE SCHEDULE 40
METALLIC PIPING AND 0.5 PSI MAXITROL REGULATOR.
SEE LP GAS NOTES ON SHEET M-001.
CONNECT NEW 3" CHWS AND 3" CHWR
PIPING TO EXISTING 6" CHWS/FL PIPE IN
PUMP/PIPING ROOM. VERIFY SIZING,
LOCATION, AND POINT OF CONNECTION
IN FIELD PRIOR TO CONSTRUCTION,
SEE CHILLED WATER CONNECTION
DETAIL.
'-2
15'-10"
3'-0"
DEMOLISH EXISTINGINTAKE DUCTWORK UPTO EXTERIOR LOUVER.
DEMOLISH EXISTING EXHAUST VENT,DEMO EXISTING OPENING TO 15"X15"
EXISTING GENERATOR TO BE
DEMOLISHED, SEE ELECTRICALDRAWINGS. INSTALL TYPE 316 STAINLESS STEEL
DUCT (20 GAUGE)
MOTORIZED DAMPER (MD-1) TO BE
INTERLOCKED WITH FAN OPERATION,SEE FAN SCHEDULE
EF-1 OPEN EXHAUST DUCTWITH BIRD SCREEN
GRADE
INTERIOREXTERIORINTERIOREXTERIOR
GRADE
PROVIDE LATERAL BRACING TO
SUPPORT FAN TO STRUCTURE
NEW FAN (EF-1)
OVERHEAD, SEE SECTION
DEMOLISH EXISTINGINTAKE DUCTWORK UPTO EXTERIOR LOUVER.
DEMOLISH EXISTING EXHAUST VENT,DEMO EXISTING OPENING TO 15"X15"
EXISTING GENERATOR TO BE
DEMOLISHED, SEE ELECTRICALDRAWINGS.INSTALL TYPE 316 STAINLESS STEEL
DUCT (20 GAUGE)
MOTORIZED DAMPER (MD-1) TO BEINTERLOCKED WITH FAN OPERATION,
SEE FAN SCHEDULE
EF-1OPEN EXHAUST DUCTWITH BIRD SCREEN
GRADE
INTERIOR EXTERIOR INTERIOR EXTERIOR
GRADE
PROVIDE LATERAL BRACING TO
SUPPORT FAN TO STRUCTURE
KEY PLAN
AREA OF WORK
GENERAL NOTE:
A. IF NO NEW WORK IS SHOWN. SHEET IS FOR
REFERENCE INFORMATION ONLY.
MECHANICAL PLANS
SCALE: 1/16" = 1'-0"
C H
W S
C H
W S
CHWS
C H
W R
C H
W R
CHWR
CHWR
(E) 3" CHWR
CONNECT NEW 3" CHWS AND 3" CHWR PIPING TO
EXISTING 6" CHWS/FL PIPE IN PUMP/PIPING ROOM.
VERIFY SIZING, LOCATION, AND POINT OF
CONNECTION IN FIELD PRIOR TO CONSTRUCTION,
(E) 6" CHWS/FL
(E) 3" CHWR
(E) 6" CHWS/FL
(E) 3" DCW
(E) DCWP
(E) CHWP
UNIT DATA BASIS OF DESIGN PERFORMANCE DATA MOTOR DATA GENERAL DATA
SCHEDULE NOTESTAG LOCATION FUNCTION MANUFACTURER MODEL FAN TYPE
FLOW
(CFM)
ESP
(IN WG)
DRIVE
TYPE
SOUND
RATING
(SONES) FLA
MO
CP VOLTS PHASE VFD
EMERGENCY
POWER
DAMPER
TYPE REDUNDANT
GREASE
RATED
SMOKE
RATED
WEIGHT
(LBS)
EF-1 MAINTENANCE BLDG EXHAUST GREENHECK CUE-120-VG CENTRIFUGAL 1150 0.3 DIRECT 8.4 3.8 15 115 1 No No MOTORIZED No No No 63
1.
SCHEDULE NOTES:
PROVIDE MANUFACTURER TEMPERATURE CONTROL UNIT WITH SET POINT.
1-2
2. PROVIDE 120V 28"x22" MOTORIZED DAMPER (MD-1) AND INTERLOCK WITH FAN OPERATION.
CHW SYS DP (AI)
OAH (AI)
CHWS T (AI)
OAT (AI)
CHW BYPV (AO)
CHW P2 (BI)
CCHW RT (AI)
CHWR T (AI)
CHW P1 (BO)
CHW P1 (BI)
CHW P2 (BO)
CHW F (AI)
CHW P1 (AO)
CH1 CHW FLW (BI)
CHW P2 (AO)
CH1 CHW DP (AI)
CH1 CHWP R (BI)
CH1 CHW ISV (BO)
CH1 CHW ISV (BI)
WEL - 42
WEL - 60
PT - 17
H - 1
T - 58
T - 1
VFD - 40
V - 73
WEL - 58
SKT - 5
P - 36
CS - 6
CHWR
T - 42
CHR - 17
T - 60
CHWS
SKT - 6
R - 5
P - 37
CS - 5
R - 6
FM - 4
SIG - 5
FS - 13
SIG - 6
VFD - 41
PT - 18
PT - 1
V - 48
POINTS LIST: COOLING PLANT SYSTEMS (CH-1)
Point Name POINTS ALARMS
G R
A
PH
IC
A
N A
LO
G
H A
R D
W A
R E
IN
PU
T (A
I) B
IN
A
R Y
H A
R D
W A
R E
IN
PU
T (B
I) A
N A
LO
G
H A
R D
W A
R E
O U
TP
U
T (A
O
B
IN
A R
Y H
A R
D W
A R
E O
U
TP
U T
(B O
SO
FT
W
A R
E
PO
IN
T
(S
FT
H
A R
D W
A R
E
IN
TE
R
LO
C
K (H
D W
W
IR
EL
ES
S
(W
LS
N
ET
W
O R
K (N
ET
H
IG
H A
N A
LO
G
L
IM
IT
LO
W A
N A
LO
G
L
IM
IT
B
IN
A
R Y
LA
TC
H D
IA
G
N O
ST
IC
SE
N
SO
R
F A
IL
C
O M
M U
N
IC
A
TI
O N
F A
IL
CHILLED WATER FLOW METER
CHW F
X X X X X
CHILLED WATER BYPASS VALVE
OUTPUT
CHW BYPV
X X
CHILLED WATER PUMP 1 START
STOP
CHW P1
X X
CHILLED WATER PUMP 1 STATUS
CHW P1
X X
CHILLED WATER PUMP 1 SPEED
CHW P1
X X
CHILLED WATER PUMP 2 START
STOP
CHW P2
X X
CHILLED WATER PUMP 2 STATUS
CHW P2
X X
CHILLED WATER PUMP 2 SPEED
CHW P2
X X
CHILLED WATER RETURN
TEMPERATURE
CHWR T
X X X X X
CHILLED WATER SUPPLY
TEMPERATURE
CHWS T
X X X X X
CHILLED WATER SUPPLY
DIFFERENTIAL PRESSURE
CHW SYS DP
X X X X
CHILLER 1 CHILLED WATER FLOW
DIFFERENTIAL PRESSURE
CH1 CHW DP
X X X X
CHILLER 1 CHILLED WATER FLOW
STATUS
CH1 CHW FLW
X X
CHILLER 1 CHILLED WATER ISO
VALVE OUTPUT
CH1 CHW ISV
X X
CHILLER 1 CHILLED WATER ISO
VALVE OPEN STATUS
CH1 CHW ISV
X X
CHILLER 1 CHILLED WATER PUMP
REQUEST FROM CHILLER
CH1 CHWP R
X X
CHILLER CHILLED WATER RETURN
TEMPERATURE
CCHW RT
X X
OUTDOOR AIR RELATIVE HUMIDITY
LOCAL
OAH
X X X
OUTDOOR AIR TEMPERATURE
LOCAL
OAT
X X X
BAS COMMUNICATION STATE
BAS COM
X X X
CHILLER PLANT ENABLE
SYS EN
X
CHILLED WATER PUMP 1 FAILURE
CHW P1 FAIL
X X X
CHILLED WATER PUMP 2 FAILURE
CHW P2 FAIL
X X X
CHILLED WATER SUPPLY
TEMPERATURE SETPOINT
CHW SUP TMP SP
X
OUTDOOR AIR TEMP ENABLE
SETPOINT
OAT ENA SP
X
J
M
M 1-PHASE MOTOR CONNECTION
3-PHASE MOTOR CONNECTION
FLOOR MOUNTED JUNCTION
BOX/EQUIPMENT CONNECTION
MAGNETIC STARTER
PANELBOARD OR OTHER ELECTRICAL
EQUIPMENT AS NOTED (SIZED TO SCALE)
GROUND ROD
UNDERGROUND OR UNDER SLAB
CONDUIT/CONDUCTOR
GROUND BAR
JUNCTION BOX / EQUIPMENT CONNECTION
ELECTRICAL PLAN SYMBOLS
NOTE: NOT ALL SYMBOLS MAY BE USED.
SYMBOL DESCRIPTION
ABOVE GRADE CONDUIT/CONDUCTOR
J
PV MODULE
NORMAL POWER DUPLEX RECEPTACLE W/ COVERPLATE,
UNLESS OTHERWISE NOTED: X INDICATES
CIRCUIT NUMBER, Y INDICATES NON-STANDARD
MOUNTING HEIGHT, AND Z INDICATES THE FOLLOWING:
G = GFCI
WP = WEATHER PROOF
XX" = MTD AT XX" AFF
X Y Z
Z X
Y
CIRCUIT BREAKER
X INDICATES FRAME
SIZE,
Y INDICATES TRIP
RATING,
Z INDICATES NUMBER
OF
POLES IF OTHER THAN
3.
Z LSI
X
Y
DRAWOUT CIRCUIT
BREAKER
X INDICATES FRAME
SIZE,
Y INDICATES TRIP
RATING,
Z INDICATES NUMBER
OF
POLES IF OTHER THAN
3.
X, Y
DISCONNECT SWITCH
X INDICATES SIZE,
Y INDICATES NUMBER
OF
POLES IF OTHER THAN 3.
Y
X, Z
FUSED SWITCH
X INDICATES SWITCH
SIZE,
Y INDICATES FUSE SIZE,
Z INDICATES NUMBER
OF
POLES IF OTHER THAN
3.
TRANSFORMER
KVA, PRI & SEC
VOLTAGE,
K-RATING, ETC. AS
INDICATED OR
SPECIFIED.
ISOLATION
TRANSFORMER
KVA, PRI & SEC
VOLTAGE,
K-RATING, ETC. AS
INDICATED OR
SPECIFIED.
TRANSFER SWITCH
AMP RATING, NUMBER
OF POLES, ETC. AS
INDICATED OR
SPECIFIED.
SURGE ARRESTER
(QUANTITY OF 3
U.N.O.)
AMMETER SWITCH
VOLTMETER SWITCH
GROUND FAULT
PROTECTOR
SURGE PROTECTIVE
DEVICE
EMERGENCY POWER
OFF
EARTH GROUND
X
CONTROL PANEL
52 X Y
MEDIUM VOLTAGE
DRAWOUT CIRCUIT
BREAKER
X INDICATES CT RATIO,
Y INDICATES FRAME
SIZE
FUSE
X INDICATES SIZE
M METER W/ SOCKET AND
TEST BLOCKS
FUSED POTENTIAL
TRANSFORMER
CURRENT
TRANSFORMER
XXX PANELBOARD
SPD
EPO
GFP
SA
AS
VS
CP
ONE-LINE DIAGRAM SYMBOLS
NOTE: NOT ALL SYMBOLS MAY BE USED.
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
NON-FUSED
DISCONNECT SWITCH
FUSED DISCONNECT
SWITCH
COMBINATION MOTOR
STARTER/DISCONNECT
PV MODULE
K KEYED INTERLOCK
DC-AC INVERTER
ELECTRICAL GENERAL NOTESABBREVIATIONS LIST:
RSD
RAPID SHUTDOWN
DEVICE
BATT BATTERY
GND
PHOTOVOLTAIC
SOLAR PANEL
BUSBAR
GENSET GENERATOR
GROUNDBAR
NEMA 5-20R, STANDARD MOUNTING HEIGHT 18" A.F.F
BUILDING CODES AND INDUSTRY STANDARDS:
· ASHRAE 90.1 2016 (AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR CONDITIONING ENGINEERS)
· EIA/TIA STANDARDS 568 & 569 (ELECTRONIC INDUSTRIES ALLIANCE/TELECOMMUNICATIONS INDUSTRY
ASSOCIATION)
· IEEE STANDARDS
· UL (FORMERLY UNDERWRITERS LABORATORIES)
· NFPA 70: NEC 2023 (NATIONAL ELECTRICAL CODE)
· IBC 2024, WITH AMENDMENTS (INTERNATIONAL BUILDING CODE)
· IEBC 2024, WITH AMENDMENTS (INTERNATIONAL EXISTING BUILDING CODE)
· IFC 2024, WITH AMENDMENTS (INTERNATIONAL FIRE CODE)
A AMPERES
ABB ABBREVIATIONS
AC ALTERNATING CURRENT
ACS ACCESS CONTROL SYSTEM
ADJ ADJUSTMENT
AF AMPERE FRAME (FOR CB) OR AMPERE
FUSE FOR DISCONNECT SWITCH)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AL ALUMINUM
AMB AMBIENT
ATS AUTOMATIC TRANSFER SWITCH
AS AMPERE SWITCH
AT AMPERE TRIP
AV AUDIO/VIDEO
AWG AMERICAN WIRE GAUGE
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
C CONDUIT
CAT CATEGORY
CB CIRCUIT BREAKER
CCT CORRELATED COLOR TEMPERATURE
CCTV CLOSED CIRCUIT TELEVISION
CL CENTERLINE
COMM COMMUNICATIONS
CU COPPER
DAS DATA ACQUISITION SYSTEM
DC DIRECT CURRENT
DCC DATA CENTER CONTINUOUS
DEG DEGREE
DISC DISCONNECT
EC EMPTY CONDUIT
EGC EQUIPMENT GROUNDING CONDUCTOR
EIA ELECTRONICS INDUSTRIES
ASSOCIATIONS
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENC ENCLOSURE
EPO EMERGENCY POWER OFF
ETC ETCETERA
(E), EX EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACU FIRE ALARM CONTROL UNIT
FBO FURNISHED BY OTHERS
FLA FULL LOAD AMPERAGE
FS FIRE STOP
FSS FUSED SAFETY SWITCH
FT FEET OR FOOT
G, GND GROUND
GALV GALVANIZED
GEC GROUNDING ELECTRODE CONDUCTOR
GEN GENERAL, GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFDI GROUND FAULT DEVICE INTERRUPTER
GFGI GOVERNMENT FURNISHED AND
GOVERNMENT INSTALLED
GFP GROUND FAULT PROTECTION
GM GROUND MOUNTED
GVEA GOLDEN VALLEY ELECTRIC
ASSOCIATION
HH HANDHOLE
HZ HERTZ
IDS INTRUSION DETECTION SYSTEM
IFC INTERNATIONAL FIRE CODE
IG ISOLATED GROUND
INV INVERTER
ISC SHORT CIRCUIT CURRENT
J-BOX JUNCTION BOX
K KILO
KCMIL THOUSAND CIRCULAR MILS
KVA KILOVOLT-AMPERES
KW KILOWATTS
KWH KILOWATT HOURS
L LENGTH
LC LIGHTING CONTACTOR
LTG LIGHTING
LPI LIGHTNING PROTECTION INSTITUTE
LV LOW VOLTAGE
MAX MAXIMUM
MCB MAIN CIRCUIT BREAKER
MBJ MAIN BONDING JUMPER
MFR MANUFACTURER
MH MANHOLE
MLO MAIN LUGS ONLY
MPPT MAX POWER POINT TRACKING
MTD MOUNTED
MTS MANUAL TRANSFER SWITCH
(N) NEW
N.C. NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
N, NEU NEUTRAL
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
N.O. NORMALLY OPEN
NTP NOTICE TO PROCEED
NTS NOT TO SCALE
OCPD OVER CURRENT PROTECTION DEVICE
OH OVERHEAD
OPGP OPERATIONS PRINCIPAL GROUND
POINT
P POLE
PLC PROGRAMMABLE LOGIC
CONTROLLER
PDU POWER DISTRIBUTION UNIT
PNL PANEL OR PANELBOARD
POE POWER OVER ETHERNET
PV PHOTOVOLTAIC
PVC POLYVINYL CHLORIDE
PWR POWER
QTY QUANTITY
REV REVERSE
RGS RIGID GALVANIZED STEEL CONDUIT
RGS-PVC PVC-COATED RIGID GALVANIZED
STEEL CONDUIT
RL RELOCATE
RM ROOM
RN REPLACE WITH NEW
RPP REMOTE POWER PANEL
RSD RAPID SHUTDOWN DEVICE
SCC SHORT CIRCUIT CONTRIBUTION
SCCR SHORT CIRCUIT CURRENT RATING
SPD SURGE PROTECTION DEVICE
SPECS CONTRACT SPECIFICATIONS
SSBJ SUPPLY-SIDE BONDING JUMPER
T TRANSFORMER
TR TELECOMMUNICATIONS ROOM
TVSS TRANSIENT VOLTAGE SURGE
SUPPRESSION
TYP TYPICAL
UFC UNIFIED FACILITIES CRITERIA
UG UNDERGROUND
UL UNDERWRITERS' LABORATORIES
UPS UNINTERRUPTIBLE POWER SUPPLY
UNO UNLESS NOTED OTHERWISE
V VOLTS
VA VOLT-AMPERES
VAC VOLTS ALTERNATING CURRENT
VD VOLTAGE DROP
VFD VARIABLE FREQUENCY DRIVE
VOC VOLTAGE OVER CURRENT
W WIRE OR WATTS
W/ WITH
WP WEATHERPROOF
WPU WEATHERPROOF WITH WHILE IN USE
COVER
XFMR TRANSFORMER
XRL EXISTING TO BE RELOCATED
Z IMPEDANCE
1. DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. CONTRACTOR SHALL FURNISH, INSTALL, AND SIZE ALL SLEEVES, HOLES, CORES, PATCHING, SLOTS, ANCHORS, BRACKETS, SUPPORTS, JUNCTION BOXES, PULL BOXES, AND OTHER APPURTENANCES NECESSARY TO EXECUTE THE CONTRACT DOCUMENTS COMPLETE.
SOME OF THESE ITEMS MAY BE SHOWN ON THE DRAWINGS FOR CLARITY OR DESIGN PREFERENCE.
HOWEVER, NOT ALL OF THE ITEMS NECESSARY FOR COMPLETE EXECUTION AND INSTALLATION ARE SHOWN.
EQUIPMENT SIZES, WIRING, CONFIGURATIONS ARE BASED ON THE BASIS OF DESIGN EQUIPMENT AND THE CONTRACTOR SHALL BE RESPONSIBLE FOR ADJUSTING LAYOUTS, WIRING, AND CONFIGURATIONS TO PROVIDE A FULLY-FUNCTIONING AND OPERATIONAL SYSTEM BASED ON THE APPROVED EQUIPMENT
SUBMITTALS.
2. CONTRACTOR IS TO ENSURE THAT ALL WORK MAINTAINS THE EXISTING ARCHITECTURAL AESTHETIC AND STRUCTURAL INTEGRITY. WORK IS TO BE CONSTRUCTED, PATCHED, AND FINISHED TO MAINTAIN EXISTING
CONSTRUCTION AND FINISHES.
3. CONDUIT RUNS WHERE SHOWN, ARE DIAGRAMMATIC ONLY. INSTALL AS REQUIRED TO AVOID CONFLICTS WITH EQUIPMENT OR STRUCTURAL CONDITIONS. SEE SPECIFICATION SECTION 260519, 260543, AND OTHER
RELEVANT SECTIONS FOR ADDITIONAL REQUIREMENTS.
4. THIS IS A STANDARD LEGEND SHEET. SOME SYMBOLS OR ABBREVIATIONS APPEAR ON THIS SHEET AND NOT
ON PROJECT DRAWINGS.
5. UNLESS OTHERWISE INDICATED, MOUNTING ELEVATIONS ARE CENTERLINE ELEVATIONS.
6. MINIMUM CONDUIT SIZE SHALL BE 3/4". CONDUCTORS SHALL BE COPPER (CU) UNLESS OTHERWISE NOTED.
MINIMUM AC WIRING SHALL BE #12 WITH THHN/THWN-2 INSULATION WHERE INSTALLED INTERIOR TO BUILDINGS OR XHHW-2 WHERE INSTALLED UNDERGROUND OR EXTERIOR. MINIMUM DC WIRING SHALL BE #10 WITH TYPE PV INSULATION AND 1000V MINIMUM. VOLTAGE DROP SHALL BE LIMITED TO 5% TOTAL COMBINED
AC & DC. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
7. EXTERIOR, ABOVE-GRADE CONDUIT SUBJECT TO PHYSICAL DAMAGE SHALL BE RIGID STEEL CONDUIT.
EXTERIOR, ABOVE-GRADE CONDUIT NOT SUBJECT TO PHYSICAL DAMAGE SHALL BE EMT W/ RAINTIGHT FITTINGS. UNDERGROUND CONDUIT SHALL BE PVC SCHEDULE 40. SUBJECT TO PHYSICAL DAMAGE SHALL BE CONSIDERED TO BE FROM GRADE/FLOOR TO 8' ABOVE GRADE/FLOOR. REFER TO SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS.
8. WIRE AND CONDUIT SIZES AND QUANTITIES FOR FEEDERS AND BRANCH CIRCUITS WHICH ARE SHOWN ON
ONE-LINE DIAGRAM APPLY TO PLAN SHEETS.
9. ALL WALL AND FLOOR PENETRATIONS FOR CONDUIT INSTALLATION SHALL BE PROPERLY SEALED AND FIRE
STOPPED.
10. ENCLOSURES SHALL BE NEMA 1 INDOOR. ALL ENCLOSURES AND CONNECTIONS OUTDOOR SHALL BE
SUITABLE FOR EXTERIOR INSTALLATION AND BE NEMA 3R MINIMUM.
11. CIRCUIT IDENTIFICATION SHALL BE AS FOLLOWS:
A-2 INDICATES A CIRCUIT AT CIRCUIT 2 OF PANELBOARD A.
REFER TO PANEL SCHEDULE FOR BREAKER INFORMATION.
A-5,7 INDICATES A SINGLE PHASE, 2-POLE CIRCUIT AT CIRCUITS 5 & 7 OF PANELBOARD A.
REFER TO PANEL SCHEDULE FOR BREAKER INFORMATION.
12. CONSTRUCTION DETAILS SHOWN ON DRAWINGS SHOW TYPICAL INSTALLATION UNLESS OTHERWISE NOTED AND APPLY TO ELECTRICAL WORK INCLUDED IN THIS PACKAGE EVEN THOUGH NOT SPECIFICALLY
REFERENCED ON THE PLAN DRAWINGS.
14. THE WORD "PROVIDE" IS SYNONYMOUS WITH FURNISH AND INSTALL. THE WORD "DEMOLISH" IS SYNONYMOUS
WITH REMOVE AND DISPOSE.
15. FOR CONTROL DIAGRAMS OR INDICATED CONTROLS WIRING, THE QUANTITY AND SIZE OF WIRE/CONDUIT
REPRESENT A SUGGESTED ARRANGEMENT BASED UPON SELECTED ELECTRICAL EQUIPMENT.
MODIFICATIONS ACCEPTABLE TO THE OWNER MAY BE MADE TO ACCOMMODATE EQUIPMENT ACTUALLY PURCHASED. MAINTAIN THE BASIC SEQUENCE AND METHOD OF CONTROL INDICATED ON THE DRAWINGS
AND SPECIFICATIONS.
16. CONSIDER SECTIONS OF CONDUIT RUNS NOT MARKED, AND NOT SHOWN ON THE ONE LINE DIAGRAMS, TO BE
THE SAME AS THE HOME RUN OR THE LAST SECTION IN THE RUN THAT IS MARKED.
17. PROVIDE SUITABLE BARRIERS IN MANHOLES, HANDHOLES, PULL BOXES, AND JUNCTION BOXES TO SEPARATE INSTRUMENTATION AND COMMUNICATION CABLES FROM OTHER WIRING WHERE SEPARATE BOXES ARE NOT
SHOWN ON THE DRAWINGS.
18. ONLY MAJOR PULL BOXES ARE SHOWN. PROVIDE ADDITIONAL PULL BOXES AS REQUIRED TO MEET CODE
REQUIREMENTS AND TO PROVIDE A WORKABLE INSTALLATION.
19. VERIFY THE LOCATION OF CONDUIT ENTRANCES FOR ALL EQUIPMENT USING THE APPROVED SHOP DRAWINGS PRIOR TO INSTALLING CONDUITS AND BOXES TO SERVE THE EQUIPMENT. CONDUIT STUB-UPS
SHALL NOT BE MORE THAN 6" FROM THE CENTERLINE OF EQUIPMENT CONDUIT ENTRANCE.
20. SERIES OR CASCADED A.I.C. RATINGS ARE NOT ALLOWED UNLESS SPECIFICALLY NOTED.
23. THE PV SYSTEM SHALL COMPLY WITH NEC ARTICLES 690 AND 710. INSTALL REQUIRED LABELS AND SIGNAGE
PER THE NEC, WHETHER SHOWN ON THESE DRAWINGS OR NOT.
24. PV EQUIPMENT, CONNECTORS, AND WIRING SHALL BE UL LISTED TO 508, 1703, 1741, 4703, 6703, AND/OR 61730
AS APPLICABLE.
M
TS
3'-3"
ED102
DEMOLISH
FW-500
INVERTER
FW-1000
INVERTER
SQUARE-D HU364, 200A, 2-POLE
CIRCUIT BREAKER DISCONNECT
MIDWEST GS1202B2OUL, 200A
MANUAL TRANSFER SWITCH
SQUARE-D HU364, 200N 2-POLE
CIRCUIT BREAKER DISCONNECT
1" NIPPLE,
TYP FROM TRANSFER-
SWITCH AND DISCONNECTS
SQUARE-D HU364, 200A, 2-POLE
CIRCUIT BREAKER DISCONNECT
MIDWEST GS1202B2OUL, 200A
MANUAL TRANSFER SWITCH
SQUARE-D HU364, 200A, 2-POLE
CIRCUIT BREAKER DISCONNECT
FW-1000
INVERTER
FW-500
INVERTER
2" NIPPLE,
TYP FROM EACH
INVERTER
8"X8"X12' GUTTER
12'1'-6" 2'-2"
2'-8"
5'-1"
6'-7"
5'-5"
3'-11"
1'-8"3'-5"3'-5"2'-9"
30kW
GENERATOR
30KW GENERATOR TO BE DISCONNECTED
AND REMOVED UP TO LOUVER AND LOUVER
LEFT OR LOCKED SHUT AND POWER
DISCONNECTED IF MOTORIZED.
Generator Room
ED102
MAINT BLDG INVERTER LAYOUT
SCALE OF FEET
1 0 1 2 3
ED102
SOUTH WALL - ELEVATION VIEW
SCALE OF FEET
1 0 1 2 32
SCALE: 3/4" = 1'-0"
SCALE: 3/4" = 1'-0"
GENERAL NOTES:
1. DEMOLISH, REMOVE, AND DISPOSE OF ALL EQUIPMENT
SHOWN. SAFE OFF EQUIPMENT AND FEEDERS PRIOR TO
DEMOLITION.
2. PROVIDE TEMPORARY GENERATOR, FUEL, AND
REQUIRED TEMPORARY CONNECTIONS TO SUPPLY
POWER TO THE FACILITY DURING CONSTRUCTION
SHUTDOWNS. TEMPORARY GENERATOR MUST BE
CAPABLE OF SUPPLYING POWER FOR THE DURATION OF
THE SHUTDOWN.
LEGEND:
BATTERY STRING BATTERY STRINGBA
TT
ER
Y
ST
R
IN
G
BA
TT
ER
Y
ST
R
IN
G
BATTERY STRING
BA
TT
ER
Y
ST
R
IN
G
BA
TT
ER
Y
ST
R
IN
G
BATTERY
ROOM
GFCI
8"X8"X12' GUTTER
BATT
STR
BATT
STR
BATTERY
STRING
BATTERY
STRING
10' 3' 4" 5' 4" 7' 4" 10' 0" 12' 8" 15' 4" 18' 0" 0'
(9) FWPV-8 & (1) FWPV-12
COMBINER BOXES
FM80 CHARGE CONTROLLERS
8" WIDE CABLE LADDER RACK,
MTD FLAT AGAINST WALL
GS1202B2OUL BATTERY
FUSED DISCONNECTS
8" WIDE CABLE LADDER RACK,
MTD FLAT AGAINST WALL
BATTERY WIRING,
MTD ON LADDER RACK
48VDC POSITIVE BUSS,
MTD FLAT AGAINST WALL
BATTERY WIRING,
MTD ON LADDER RACK
4'X8' PLYWOOD IN FRONT OF SHEET
ROCK, 16 GAUGE PLATE BEHIND
SHEET ROCK
12" WIDE CABLE LADDER RACK WITH
TRIANGULAR RUNWAY WALL SUPPORT
48VDE NEGATIVE BUSS,
MTD FLAT AGAINST WALL
8' 0"
6' 4"
5' 6"
3' 11"
2' 10"
9' 2"
2' 6"
1' 1"
0"
3' 4"4' 0"
(end view) (side view) (side view) (end view)
ED103
COMBINER BOXES &
CHARGE CONTROLLERS
BATTERY FUSED
DISCONNECTS
12" WIDE CABLE LADDER RACK,
TYP ON THREE WALLS
8"X8"X12' GUTTER
DEMOLISH
ED103
2 0 2 4
SCALE OF FEET
2 0 2 4
SCALE OF FEET
4 0 4 8
SCALE OF FEET
ED103
NORTH WALL - ELEVATION VIEW2
SCALE: 1/2" = 1'-0"
ED103
EAST WALL - ELEVATION VIEW3
SCALE: 1/2" = 1'-0" ED103
MAINT BLDG BATTERY ROOM1
SCALE: 1/4" = 1'-0"
GENERAL NOTES:
1. DEMOLISH, REMOVE, AND DISPOSE OF ALL EQUIPMENT
SHOWN. SAFE OFF EQUIPMENT AND FEEDERS PRIOR TO
DEMOLITION.
2. PROVIDE TEMPORARY GENERATOR, FUEL, AND
REQUIRED TEMPORARY CONNECTIONS TO SUPPLY
POWER TO THE FACILITY DURING CONSTRUCTION
SHUTDOWNS. TEMPORARY GENERATOR MUST BE
CAPABLE OF SUPPLYING POWER FOR THE DURATION OF
SEE 2/ED104
32'-6" 30'-7"
27'-11"
25'- 0"
22'-4"
19'-6"
16'-10"
10'-2"
7'-6"
4'-7"
1'-11"
3' 10"
1'-4" 6"
1' 5"
2' 9"
1' 5"
3' 3"
5' 7"
CLAMP
BETWEEN
PANELS
CLAMP AT EDGE OF
OUTER PANELS
SEE DETAIL 3/ED104
FOR SIDE VIEW
DIMENSIONS ARE FROM EDGE
OF STANDING SEAM ROOF TO
CENTERLINE OF UNISTRUT
0'
1'- 4"
UNISTRUT IS ATTACHED AT EVERY
STANDING SEAM, PER DETAIL 3/ED104
7'- 8"
4'-5" 6"
DEMOLISH
MODULE MID CLAMP TO ATTACH
SOLAR PANELS
TO MOUNTING RAIL, BETWEEN PANELS
MODULE CLAMP DOES NOT NECESSARILY
ALIGN WITH STANDING SEAM METAL CLAMP,
SEE DETAIL 3/ED104 FOR CLARITY
STANDING SEAM
METAL ROOF
MODULE CLAMP
MOUNTING RAIL
FLANGE NUT
VIEW A VIEW B
MODULE CLAMP TO ATTACH
SOLAR PANELS TO MOUNTING
RAIL, AT OUTER EDGE OF
PANELS
UNIVERSAL PV STUD
(STAINLESS STEEL)
STANDING SEAM
METAL CLAMP
MODULE END CLAMP ATTACHED TO
UNISTRUT, PER DETAIL 4/ED104, VIEW B MODULE MID CLAMP ATTACHED TO UNISTRUT,
PER DETAIL 4/ED104, VIEW A
MOUNTING RAIL IS ATTACHED
AT EVERY STANDING SEAM,
PER DETAIL 4/ED104, VIEW A & B
DEMOLISH SOLAR PANELS, MOUNTING
ATTACHED TO STANDING SEAM ROOF,
AND ELECTRICAL DEVICES AND
EQUIPMENT FOR SOLAR EQUIPMENT
ED104
EXISTING MAINT BLDG ROOF PV ARRAY LAYOUT PLAN1
SCALE: 3/16" = 1'-0"
ED104
EXISTING PV MODULE - SIDE VIEW (FOR REFERENCE)3
ED104
EXISTING PV MODULE PANEL DETAIL (FOR REFERENCE)2
ED104
EXISTING PV MODULE MOUNTING AT STANDING-SEAM ROOF (FOR REFERENCE)4
NTS
NTS
LEGEND:
SCALE OF FEET
0 4 8 12
36KW STACKED INVERTERS
W/ BATTERY CHARGER W/
SURGE PROTECTION 50A, TWO
1-POLE
OUTPUT CB
TYP OF 5
80A, 1 - POLE CB,
TYP OF 10GND GND GND
GND GND GND
GND GND GND
GND GND GND
N H
N H
GND
GND
40KW SOLAR
POWER
CAPACITY
ROOF MTD
JBOXSTRING 1
STRING 2
STRING 3
STRING 1
STRING 2
STRING 3
ARRAY
9 PNLS
ARRAY
GROUP
18 PNLS
ARRAY GROUPS 2 THRU 9 ARE SIMILAR TO GROUP 1
18 PANELS EACH
ARRAY
9 PNLS
COMBINER
BOX 1
W/ FUSES
CHARGE
CONTROLLER 1 80A,
TWO 1-POLE
GFDI CB
TYP OF 5
DC BUS
POSITIVE
125A, 2-POLE
CB
TYP OF 5
COMM IN
DAISY CHAIN
COMM OUT
DAISY CHAIN
GND
VFX3648
INVERTER/CHARGER
DC
AC HOT OUT
AC NEU OUT
AC HOT IN
AC NEU IN
AC
COMM IN
DAISY CHAIN
SIMILAR FOR 8
MORE INVERTER/
CHARGER /SURGE
PROTECTION
DC GROUND BUS
15A FUSE
TYP OF 6
BUS
L1 L2
50A, TWO
1-POLE INPUT
CB TYP OF 5
AC NEU
OUT BUS
AC HOT OUT
L1 L2
BUS
PV+
PV-
BAT+
BAT-
CHARGE
CONTROLLER 2
ROOF MTD
JBOX
SIMILAR FOR
COMBINER BOXES
W/ FUSES
TYP FOR 2 THRU 9
STRING 1
ROOF MTD
JBOX
COMBINER
BOX 10
W/ FUSES
STRING 2
ARRAY
9 PNLS
ARRAY
GROUP
21 PNLS
ARRAY
12 PNLS
STRING 4
STRING 1
15A FUSE
TYP OF 7
TYP OF 10
FROM
COMBINER
BOXES
TYP OF 10
FROM
CHARGE
CONTRLRS
DC BUS
NEGATIVE
TYP OF 7
FROM
BATTERY
BANK
DC SHUNT
1/2A, 1-POLE CB
TYP OF 3
11.8K Ah (567 KWH)
BATTERY CAPACITY
BATTERY
STRING
TYP OF 7
BATT
BATT
BATT
BATT
200A, 2-POLE FUSED
DISCONNECT
200A CLASS T FUSES
TYP OF 7
TYP OF 7
WIRES FROM EACH
BATTERY STRING
25A, 1 -POLE
X-240 CB
TYP OF 3
GROUPS OF 2
150A, 2-POLE CB
30 KW/KVA (125AMPS)
240/120VAC,
1-PHASE
X-240
AUTO TRANSFORMER
TYP OF 3
GENERATOR
NORMAL
OFF
BYPASS
INV-DISC-1
200A, 2-POLE
CB DISC
TO AC
LOADS
PANEL
'MPD'
200 AMP MANUAL
TRANSFER SWITCH
INV-DISC-2
200A, 2-POLE
CB DISC
AC GROUND BUS
GROUND
TO EACH
INVERTER
MAINT. BLDG
OPERATIONS
PRINCIPAL
GROUND
POINT
GROUND WIRE TO MODULE GROUNDING POINT #8 SOLID
BARE COPPER WIRE FROM ARRAY TO DC GROUND BUS,
TYP.
PHOTOVOLTAIC PANEL (183)
MFR = SCHOTT SOLAR POLY (235 WATT)
66.341"L x 39.09"W x 2"TH, 50.6 lbs.
MEETS UL 1703
MAX POWER POINT CURRENT = 7.78 ADC
MAX POWER POINT VOLTAGE = 30.2 VDC
OPEN CIRCUIT VOLTAGE (VOC) = 37.1 VDC
SHORT CIRCUIT AMPS (ISC) = 8.42 ADC
MAX POWER = 235 W
MAX SYSTEM VOLTAGE = 600 VDC
MAX REV CURRENT = 15 ADC
TEMP COEFF (VOC) = .334 VC %/
3 PANELS PER STRING, TYP, UON.
#3/0 (CU THWN).
EXISTING KEYED NOTES (FOR REFERENCE ONLY):
OPGP #1
ROOF MTD
JBOX
1 6
9 5
14 14
GENSET
L1
NEU
L2
STRING 3
STRING 2
STRING 3
PV+
PV-
BAT+
BAT-
N H
N H
GND
GNDGND
VFX3648
INVERTER/CHARGER
DC
AC HOT OUT
AC NEU OUT
AC HOT IN
AC NEU IN
AC
3 STRINGS PER ARRAY, TYP, UON.
4 STRINGS IN ARRAY
FUSE SIZE (FOR SERIES OF 3 PANELS):
OCPD (PER NEC 690A & 690B) =
8.42 x 1.56 = 13.1 MIN OR 15A MAX
15 AMP "PV TYPE" FUSES, TYP.
FACTORY PROVIDED PV CABLE (USE-2), SINGLE
CONDUCTOR, TYP FOR ROOFTOP SERIES CONNECTIONS.
MODULE GROUNDING POINT WITH GROUNDING CLIPS,
PROVIDED WITH PANEL, TYP.
1"EMT + ALL PV WIRING, TYP.
ALL GROUND WIRES #8 (CU THHN) FROM COMBINER
BOXES, CONTROLLERS, CHASSIS GROUNDS TO DC
GROUND BUS.
#6 (CU THHN) FROM AC & DC GROUND BUS TO PRINCIPAL
GROUNDING POINT, OPGP.
2"C - 3 #3/0 + 1 #4 GND (CU THWN).
ALL WIRING #2 (CU THHN), TYP, UON.
#3/0 BATTERY CABLE, TYP.
200A, 2-POLE FUSED DISCONNECT
WITHIN 36" OF BATTERY.
#1/0 (CU THWN).
#6 GND (CU THWN).
BUS
AC HOT IN
BUS
DEMOLISH
ED601
DEMO SINGLE LINE DIAGRAM1
NTS
GENERAL NOTES:
1. DEMOLISH, REMOVE, AND DISPOSE OF ALL EQUIPMENT
SHOWN IN HATCHED AREA. SAFE OFF EQUIPMENT AND
FEEDERS PRIOR TO DEMOLITION.
2. PROVIDE TEMPORARY GENERATOR, FUEL, AND
REQUIRED TEMPORARY CONNECTIONS TO SUPPLY
POWER TO THE FACILITY DURING CONSTRUCTION
SHUTDOWN. TEMPORARY GENERATOR MUST BE
CAPABLE OF SUPPLYING POWER FOR THE DURATION OF
BASIS OF DESIGN:
GENERAC SG070
LP VAPOR GENERATOR,
70KW/KVA 240/120VAC,
1PH, 3W, 60HZ
LEVEL 2 SOUND
ATTENUATED
ENCLOSURE
E-104
CONTRACTOR TO PROVIDE PRE-ENGINEERED
GROUND MOUNT RACKING SYSTEM. PROVIDE
FOOTINGS PER MANUFACTURER'S
ENGINEERED REQUIREMENTS.
BASIS OF DESIGN:
52 SILFAB 420-BG SOLAR PANELS ON
IRONRIDGE XR GROUND MOUNT SYSTEM,
ANGLED AT 30 DEGREES FACING SOUTH
BASIS OF DESIGN:
128 SILFAB 420-BG SOLAR PANELS ROOF MOUNTED,
MOUNTED PARALLEL TO ROOF SLOPE ON IRONRIDGE 'XR
RAIL' WITH STANDING SEEM ROOF MOUNTS
CH-1
MAINTENANCE BLDG
BASIS OF DESIGN:
PHASE PERFECT PT050
PHASE CONVERTER,
50HP, 240VAC 1PH - 240VAC 3PH, 60Hz
MCCB SERVICE DISCONNECT,
ON/OFF SWITCH
SURGE PROTECTION
BOLLARD, TYP OF 5
SEE STRUCTURAL
DRAWINGS.
E-105
200AS/200AF/3P
NEMA 3R
DISCONNECT SWITCH
MOUNT EQUIPMENT
TO FREE STANDING
UNISTRUT SUPPORT
FRAME WITH CONCRETE
FOOTINGS. REFER TO
STRUCTURAL DETAILS.
12X18 HANDHOLE, TIER 22 RATED
PV DC STRING, TYP
USE EXISTING PV CONDUIT PENETRATIONS
FROM BATTERY ROOM TO THE ROOF.
PROPANE GAS
MAIN BUILDING
ENTRY LOCATED
HERE. REFER TO
MECHANICAL
DRAWINGS.
16"x16"x10"D NEMA 3R
PULL BOX
WALL
MOUNTED
E-105
2"C - 3#3/0 + 1#6 GND
(CU, XHHW).
L=20', VD=0.19%.
E-105
(E) ROOF OVERHANG EDGE
1#6 GND BONDED TO 3/4" X 10' COPPER
CLAD GND ROD PER 4/E-105
E-104
E-105
E-105
E-105
KEY PLAN
AREA OF WORK16 0 16 32323232 48
E-101
ELECTRICAL SITE PLAN1
SCALE: 1/16" = 1'-0"
GENERAL NOTES:
1. COORDINATE FINAL EQUIPMENT LOCATIONS IN FIELD
AND ENSURE ALL WORKING SPACE REQUIREMENTS OF
NEC 110.26 ARE MET.
2. COORDINATE ALL UNDERGROUND ROUTING WITH
EXISTING UTILITIES AND ADJUST AS NECESSARY TO
AVOID OBSTRUCTION AND DAMAGE. PROVIDE
POTHOLING OR GROUND PENETRATING RADAR IF
NECESSARY.
3. ENSURE GENERATOR IS PLACED AND ROTATED SUCH
THAT THE ENGINE EXHAUST AND HOT AIR DISCHARGE
ARE NOT BENEATH THE ROOF OVERHANG. REFER TO
STRUCTURAL DRAWINGS FOR PAD REQUIREMENTS.
4. CONTRACTOR SHALL PROVIDE ALL REQUIRED MOUNTING
EQUIPMENT AND ACCESSORIES IN ACCORDANCE WITH
THE MANUFACTURER'S REQUIREMENTS TO MEET
APPLICABLE WIND AND SNOW LOADING AT THE SITE.
GROUND MOUNT SYSTEM SHALL BE PRE-ENGINEERED
BASED ON THE SITE CONDITIONS AND SUBMITTED FOR
APPROVAL.
5. DIMENSIONS AND SPACING SHOWN ARE BASED ON THE
BASIS OF DESIGN PRODUCTS. CONTRACTOR MUST
ADJUST THE LAYOUT BASED ON THE APPROVED
MANUFACTURER'S DIMENSIONS, SPACING, AND
VENTILATION REQUIREMENTS, AS WELL AS CODE
REQUIRED CLEARANCES.
6. REFER TO 2/E-105 FOR TYPICAL UNDERGROUND
CONDUIT TRENCHING DETAIL.
(2) 2"C - 2#4/0 + 1#2GND
(CU, XHHW)
L=260', VD=2.15%
(2) 1-1/4"C - 6#10 (CU, PV) + 1#6 (CU, THWN) GND. MAX L=150', VD=0.85%.
8" MIN PER MFR
Generator Room
E-102
ROUTE WIRES FROM WIREWAY ON
OTHER SIDE OF WALL TO WIREWAY
BELOW INVERTERS AND ROUTE UP
TO BOTTOM OF INVERTERS
1'-6"
5'-4"
PANEL
"INV"
BASIS OF DESIGN: SCHNIEDER
ELECTRIC 800A I-LINE DISTRIBUTION
PANELBOARD, 240VAC, 3W
INV6
(E) PANEL "MDP"
(E) CONTROL PANEL
(DATA AQUISITION
AND MANAGEMENT
SYSTEM)
GFCI
(E) MAINT. BLDG
OPERATIONS PRINCIPAL
GROUND POINT
INV5
GENERATOR REMOTE ANNUNICATOR
RSD SWITCH
INV5
BASIS OF DESIGN: SCHNIEDER
ELECTRIC, NQ30L4C, 400A, 30
SPACES, 240VAC, 3W
PANEL
"GEN"
INV4INV3INV2INV1
BASIS OF DESIGN: EG4 18KPV-12LV
HYBRID INVERTER
INV6
8" MIN PER MFR
INV4 INV3 INV2 INV1
7'-1"
(N) 8X8 WIREWAY
(N) 8X8 WIREWAY
11"
M
M
MDP-8
MDP-10
MD-1
EF-1
3/4"C - 2#12 (CU, THWN) + 1#12 (CU, THWN) GND
SCALE OF FEET
1 0 1 2 3
SCALE OF FEET
1 0 1 2 3
E-102
MAINT BLDG INVERTER LAYOUT1
SCALE: 3/4" = 1'-0"
E-102
SOUTH WALL - ELEVATION VIEW2
SCALE: 3/4" = 1'-0"
GENERAL NOTES:
1. COORDINATE FINAL EQUIPMENT LOCATIONS IN FIELD
AND ENSURE ALL WORKING SPACE REQUIREMENTS OF
NEC 110.26 ARE MET.
2. DETAILS SHOWN ARE GENERAL IN NATURE AND NOT ALL
CONDUIT MAY BE SHOWN. CONTRACTOR SHALL PROVIDE
ALL CONDUIT AND WIRING REQUIRED BY THESE PLANS
AND SPECIFICATIONS, AND ADEQUATELY SIZE AND
LOCATE WIREWAYS AND CONDUIT PER CODE,
INCLUDING DERATING.
3. DIMENSIONS AND SPACING SHOWN ARE BASED ON THE
BASIS OF DESIGN PRODUCTS. CONTRACTOR MUST
ADJUST THE LAYOUT BASED ON THE APPROVED
MANUFACTURER'S DIMENSIONS, SPACING, AND
VENTILATION REQUIREMENTS, AS WELL AS CODE
REQUIRED CLEARANCES.
4. COORDINATE NEW EQUIPMENT NAMES WITH EXISTING
NAMING CONVENTION BEFORE LABELING EQUIPMENT TO
VERIFY EQUIPMENT NAMES ARE NOT DUPLICATES OF
EXISTING EQUIPMENT.
(E)BATTERY STRING (E)BATTERY STRING
(E )B
AT
TE
R Y
ST
R
IN
G
(E )B
AT
TE
R Y
ST
R
IN
G
(E)BATTERY STRING
(E )B
AT
TE
R Y
ST
R
IN
G
(E )B
AT
TE
R Y
ST
R
IN
G
BATTERY
ROOM
GFCI
E-103
BASIS OF DESIGN:
IMO SI32-PEL64R-6
6-POLE PV DISCONNECT
(E) BATTERY FUSED
DISCONNECTS (BELOW)
(E) 12" WIDE CABLE LADDER RACK,
TYP ON THREE WALLS
E-103
PV WIRING FROM ROOF
RELOCATED (E) 8"X8"X12' GUTTER
(E) 8" WIDE CABLE LADDER RACK,
MTD FLAT AGAINST WALL
(E) GS1202B2OUL BATTERY
FUSED DISCONNECTS
(E) 8" WIDE CABLE LADDER RACK, MTD
FLAT AGAINST WALL
(E) BATTERY WIRING,
MTD ON LADDER RACK
(E) 48VDC POSITIVE BUSS,
MTD FLAT AGAINST WALL
RELOCATED (E) 8"X8"X12' GUTTER
BASIS OF DESIGN:
IMO SI32-PEL64R-6
6-POLE PV DISCONNECT
2'-6" 2'-11"
3'-11"
4'-11"
6'
7'
(E)BATT
STR
(E)BATT
STR
(E)BATTERY
STRING
(E)BATTERY
STRING
10' 3' 4" 5' 4" 7' 4" 10' 0" 12' 8" 15' 4" 18' 0" 0'
(E) BATTERY WIRING,
MTD ON LADDER RACK
(E) 4'X8' PLYWOOD IN FRONT OF
SHEET ROCK, 16 GAUGE PLATE
BEHIND SHEET ROCK
(end view) (side view) (side view) (end view)
PV WIRING FROM
GROUND MOUNTS TO BE
ROUTED TO WIREWAY
FROM OUTSIDE.
5'-4"
(E) 48VDC NEGATIVE BUSS,
MTD FLAT AGAINST WALL
1'-6"
7'-3"
INV
2 0 2 4
SCALE OF FEET
2 0 2 4
SCALE OF FEET
4 0 4 8
SCALE OF FEET
E-103
NORTH WALL - ELEVATION VIEW2
SCALE: 1/2" = 1'-0"
E-103
EAST WALL - ELEVATION VIEW3
SCALE: 1/2" = 1'-0" E-103
MAINT BLDG BATTERY ROOM1
SCALE: 1/4" = 1'-0"
GENERAL NOTES:
1. COORDINATE FINAL EQUIPMENT LOCATIONS IN FIELD
AND ENSURE ALL WORKING SPACE REQUIREMENTS
OF NEC 110.26 ARE MET.
2. DIMENSIONS AND SPACING SHOWN ARE BASED ON
THE BASIS OF DESIGN PRODUCTS. CONTRACTOR
MUST ADJUST THE LAYOUT BASED ON THE APPROVED
MANUFACTURER'S DIMENSIONS, SPACING, AND
VENTILATION REQUIREMENTS, AS WELL AS CODE
REQUIRED CLEARANCES.
PV MODULE, SEE 2/E-104
MODULE MID CLAMP TO ATTACH
SOLAR…