This federal contract solicitation seeks design-build services for infrastructure upgrades at the McClellan VA Medical Center in Sacramento, California. The selected contractor will provide design, construction, and commissioning services to upgrade 19 telecommunications rooms and one data center to current VA EHRM IT standards. Upgrades include installing new data cabling, fiber backbone, low-voltage systems, power and grounding, HVAC, and finishes. Some spaces will be relocated or expanded. The contractor will also extend utilities to a temporary training trailer area and remove abandoned legacy equipment. The solicitation is for the Department of Veterans Affairs Technology Acquisition Center Austin. The contractor must complete all work while maintaining operational IT services.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VISN 21 CM/PM Electronic Health

Records Modernization (EHRM) PHASE I Support Task

PO# 612C209

Northern California Health Care System Sacramento VA Medical Center

McClel lan Clinic

Ta b l e o f C o n t e n t s

Project TeamContributors

Vicinity Map/Building Addresses

Mather Campus Map/Building Information

McClellan Campus Map / Building Information

Site Infrastructure

VAMC Sacramento Fiber Distances

VAMC McClellan Fiber Distances

Door Security Requirements

Sacramento VAMC – Bldg. 645

First Floor Plan

Second Floor Plan

Sacramento VAMC – Bldg. 646

First Floor Plan

Second Floor Plan

Sacramento VAMC – Bldg. 647

First Floor Plan

Sacramento VAMC – Bldg. 649

Second Floor Plan

Sacramento VAMC – Bldg. 650

First Floor Plan – Area B

First Floor Plan – Area C

First Floor Plan – Area E

Second Floor Plan

Third Floor Plan

Sacramento VAMC – Bldg. 651

First Floor Plan

Sacramento VAMC – Bldg. 652

First Floor Plan

Sacramento VAMC – Bldg. 700

First Floor Plan

Second Floor Plan

Third Floor Plan

Fourth Floor Plan

Fifth Floor Plan

Sacramento VAMC – Bldg. 707

First Floor Plan

Identification of Network Spaces:

Sacramento VAMC

Network Spaces: (cont’d)

Sacramento VAMC – Bldg. 720

First Floor Plan

Sacramento VAMC – Bldg. 722

First Floor Plan

Sacramento VAMC – Bldg. 722A

First Floor Plan

Sacramento VAMC – Bldg. 726

First Floor Plan

Sacramento VAMC – Bldg. 727

First Floor Plan

Sacramento VAMC – Bldg. 728

First Floor Plan

Sacramento VAMC – Bldg. 730

First Floor Plan

Sacramento VAMC – Bldg. 798

First Floor Plan

Sacramento VAMC – Bldg. 799

First Floor Plan

Sacramento VAMC – Bldg. 800

First Floor Plan

Sacramento VAMC – Bldg. T8

First Floor Plan

McClellan OPC – Bldg. 29

First Floor Plan

McClellan OPC – Bldg. 88

First Floor Plan

McClellan OPC – Bldg. 98

First Floor Plan

Second Floor Plan

Identification of Network Spaces:

McClellan

VHAMACGomezM Text Box **** This package is for McClellan only. Ignore Information about Mather.

Ta b l e o f C o n t e n t s

Network Spaces: (cont’d)

Network Space Design: Sacramento

McClellan OPC – Bldg. 209

Basement

First Floor Plan

Second Floor Plan

McClellan OPC – Bldg. 949

Second Floor Plan

Bldg. 645:

Design Matrix

Enlarged Plan – Existing

Bldg. 646:

Design Matrix

Enlarged Plan - Existing

Bldg. 646:

Design Matrix

Enlarged Plan – Existing

Bldg. 649:

B203 and B205

Design Matrix

Enlarged Plan – Existing

Bldg. 650:

1A026

Design Matrix

Enlarged Plan – Existing

Bldg. 650:

1B235

Design Matrix

Enlarged Plan – Existing

Bldg. 650:

1C302

Design Matrix

Enlarged Plan – Existing

Bldg. 650:

1C900

Design Matrix

Enlarged Plan – Existing

Bldg. 650:

1E272

Design Matrix

Enlarged Plan – Existing

Bldg. 650:

2B005

Design Matrix

Enlarged Plan – Existing

Bldg. 650:

3B002

Design Matrix

Enlarged Plan – Existing

Bldg. 651:

Design Matrix

Enlarged Plan – Existing

Bldg. 652:

Design Matrix

Enlarged Plan – Existing

Bldg. 700:

1A220

Design Matrix

Enlarged Plan – Existing

Bldg. 700:

A113

Design Matrix

Enlarged Plan – Existing

Bldg. 700:

1B111

Design Matrix

Enlarged Plan – Existing

Bldg. 700:

2A112

Design Matrix

Enlarged Plan – Existing

Bldg. 700:

3A102

Design Matrix

Enlarged Plan – Existing

Bldg. 700:

4A012

Design Matrix

Enlarged Plan - Existing

Bldg. 700:

5A102

Design Matrix

Enlarged Plan – Existing

Bldg. 707:

Design Matrix

Enlarged Plan – Existing

Bldg. 720:

23A

Design Matrix

Enlarged Plan – Existing

Bldg. 726:

Design Matrix

Enlarged Plan – Existing

Bldg. 727:

Design Matrix

Enlarged Plan – Existing

Bldg. 728:

100A

Design Matrix

Enlarged Plan – Existing

Bldg. 730:

Cabinet

Design Matrix

Enlarged Plan – Existing

Bldg. 798:

Design Matrix

Enlarged Plan – Existing

Bldg. 799:

206A

Design Matrix

Enlarged Plan – Existing

Bldg. 800:

Design Matrix

Enlarged Plan - Existing

Bldg. T8:

Design Matrix

Enlarged Plan - Existing

Bldg. 29:

Design Matrix

Enlarged Plan – Existing

Bldg. 88:

1C05

Design Matrix

Enlarged Plan – Existing

Bldg. 98:

New IT Room

Design Matrix

Enlarged Plan – New Construction

Bldg. 98:

2S09B

Design Matrix

Enlarged Plan – Existing

Bldg. 209:

Design Matrix

Enlarged Plan – Existing

Bldg. 209:

Design Matrix

Enlarged Plan – Existing

Bldg. 209:

Design Matrix

Enlarged Plan – Existing

Bldg. 949:

217A

Design Matrix

Enlarged Plan – Existing

Network Space Design (cont’d)

Ta b l e o f C o n t e n t s

Network Space Design: McClellan

Appendix A – Power Installation Example

Appendix B – Compliance Requirements

Appendix C – Rack Labeling Standard

Appendix

P R O J E C T C O N TA C T D I R E C T O R Y

Concourse Federal Group

123 S. Royal Street Alexandria, Virginia 22314

Tim Hower, Project Manager ........................................................................................thower@concousefederal.com

Lorena Alvarez................................................................................................................IaIvarez@concousefederaI.com

Mike Olson ................................................................................................................... molson@concousefederal.com

Marshall Contino, Concourse A|E Vice President ....................................................... mcontino@concousefederal.com

DHE Engineering 3300 N. Central Ave. 3300 Tower Suite, 1520, Phoenix, AZ 85012

Jasper Lim, Electrical Engineer..................................................................................... jlim@dheeng.com

Kory Young, EIT, Senior Mechanical Engineer................................................................kyoung@dheeng.com

VA Northern California Health Care System

Travis Dilts (Sacramento, Chief Engineer)…………………………………………………………………Travis.Dilts2@va.gov

Jonathan Bassignani (Sacramento, Chief of Projects)……………………………………………….Jonathan.Bassignani@va.gov

V i c i n i t y M a p B u i l d i n g A d d r e s s e s

S a c r a m e n t o V A M e d i c a l C e n t e r 1 0 5 3 5 H o s p i t a l W a y M a t h e r , C A 9 5 6 5 5

M c C l e l l a n O u t p a t i e n t C l i n i c 5 3 4 2 D u d l e y B o u l e v a r d B u i l d i n g 8 8 M c C l e l l a n P a r k , C A 9 5 6 5 2

VHAMACGomezM Polygon

VHAMACGomezM

M a t h e r B u i l d i n g I n f o r m a t i o n

Bldg. # Bldg. Name

Data

Ctr Levels

650 Clinics and Administration 1 3

M a t h e r C a m p u s M a p

Bldg. # Bldg. Name TR Qty Levels

645 Outpatient GI 1 2

646 Clinics and Administration 2 2

647 ACS Specialty Clinic 0 2

649 Mental Health 1 2

650 Clinics and Administration 6 3

651 Mental Health 1 1

652 Warehouse 1 2

700 Inpatient Bed Tower 7 5

707 HRMS 1 1

720 Eye Clinic 1 1

722 ENT and Speech Pathology (Served by 720) 0 1

722A Lab 0 1

726 Clinics and Administration 1 1

727 OIF/OEF/OND Rehab 1 1

728 Center for Rehab Medicine 1 1

730 Engineering Shops 1 1

798 LMS 1 1

799 Police 1 1

800 Social Services 1 1

T-8 Medical Swing Space 1 1

VHAMACGomezM

M c C l e l l a n B u i l d i n g I n f o r m a t i o n

Bldg. # Bldg. Name TR Qty Levels

29 Warehouse 1 1

88 McClellan Dental 1 1

98 McClellan 2 2

209 Renovated Building 209 3 3

949 Mental Health and Education Building 1 3

M c C l e l l a n C a m p u s M a p

SITE INFRASTRUCTURE

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

CREATE REDUNDANT WAN PATH – ASSUME 1670’-0”

CONCRETE ENCASED 4” PVC OR HDPE WITH (4) 1” INTERDUCTS.

VANCHS EHRM Power and Data For Temporary Training

Trailers (Trailers provided by follow-on project)

Power

Provide 350A 480/277V panel, 225kVA transformer, 800A 208/120V panel.

(350A 480/277V panel powered from main switchboard in the vicinity of building 702.)

Provide 1 set of (4) 250kcmil and (1) #4 ground in 2-1/2” EMT Conduit in trench from building 702 to new 350A 480/277V panel. Approximate run of feeders are estimated to be 2200ft.

Data/Fiber

Provide temporary IDF in new temporary trailer area with racks as required and Light Interface Units (LIU) as required.

Provide minimum 12 strand single mode OM2 fiber to new IDF in new temporary trailer location from closest IDF with enough fiber capacity.

If no capacity available, run fiber from existing server room approximately 2750ft away in EMT in trench.

GENERAL AREA FOR INSTALLATION OF THE TEMP POWER & DATA)

EXACT LOCATION TO BE COORDINATED WITH OWNER DURING

DESIGN.

** See Appendix D for More Information

VAMC FIBER DISTANCES

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

CREATE REDUNDANT WAN PATH – ASSUME 1670’-0”

CONCRETE ENCASED 4” PVC OR HDPE WITH (4) 1” INTERDUCTS

VAMC SACRAMENTO (MATHER)

Building Floor Room

Distance (Ft.) from Fiber Hub

Fiber Type Notes

Interior - 4" EMT

Exterior –Fiber to be pulled through existing duct loop.

(Intent is to feed each building from two (2) directions around the loop)

645 2 221 220 4120 24 strand singlemode

646 1 1031 250 4120 24 strand singlemode

646 2 2028 275 4120 24 strand singlemode

649 2 B203/B205 300 4120 24 strand singlemode

650 1 1B235 250 24 strand singlemode

650 1 MDF 1A026 275 24 strand multimode

650 1 1C900 300 24 strand multimode

650 1 1C302 325 24 strand multimode

650 1 1E272 Server Room

650 2 2B005 350 24 strand multimode

650 3 3B002 375 24 strand multimode

651 1 115 200 4120 24 strand multimode

652 1 105 200 4120 24 strand multimode

700 1 A113 200 4120 24 strand multimode

700 1 1A220 225 4120 24 strand multimode

700 1 1B111 250 4120 24 strand multimode

700 2 2A112 275 4120 24 strand multimode

700 3 3A012 300 4120 24 strand multimode

700 4 4A012 325 4120 24 strand multimode

700 5 5A012 350 4120 24 strand singlemode

707 1 119 200 4120 24 strand singlemode

720 1 23A 200 4920 24 strand singlemode

726 1 103 200 4120 24 strand singlemode

727 1 122 200 4120 24 strand singlemode

728 1 100A 200 4120 24 strand singlemode

730 1 IT Cabinet 200 4670 24 strand singlemode

731 1 200 4670 24 strand singlemode

798 1 104 200 4120 24 strand singlemode

799 1 206A 200 4200 24 strand singlemode

800 1 114 200 4200 24 strand singlemode

T8 1 141 200 4120 24 strand singlemode

VAMC FIBER DISTANCES

SACREMENTO VAMC (McCLELLAN)

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

VAMC SACRAMENTO (McCLELLAN)

Building Floor Room

Distance (Ft.) from Fiber Hub

Fiber Type Notes

Interior - 4" EMT

Exterior -Concrete

Encased 4" PVC or

HDPE with (4) 1"

Interducts

98 1 2S098 250 2000 24 strand singlemode

98 1 New IT Room 300 2000 24 strand singlemode

98 2 2S13A 325 2000 24 strand singlemode

209 BASEMENT 20 250 24 strand multimode

209 1 119 300 24 strand multimode

209 2 214 350 24 strand multimode

DOOR SECURITY REQUIREMENTS

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

I D E N T I F I C AT I O N O F N E T WO R K S PAC E S – M AT H E R

BLDG: 6 4 5

LEVEL: 1

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

N

EXISTING IT ROOM 114

RELOCATE TO 2ND FL

ROOM 221

EXISTING SPACE TO BE USED AS

GENERAL STORAGE

EXISTING TR LOCATION(S)

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

ROOMS TO EXPAND IN

PLACE

NOTE:

ALL ABANDONED TR ROOMS ARE TO BE

REPURPOSED AS GENERAL STORAGE OR AS

INDICATED ON FLOOR PLAN. MINIMUM

REQUIREMENTS FOR TR ROOMS TO BE

ABANDONED:

• REMOVE ALL IT EQUIPMENT

• SEAL ALL PENETRATIONS IN ACCORDANCE

WITH FIRE REQUIREMENTS

• PROVIDE NEW VCT FLOORING

• REMOVE EXISTING PLYWOOD ON WALLS,

PATCH, REPAIR AND PAINT WALLS

• PROVIDE NEW DROP-IN CEILING

• PROVIDE NEW LIGHTING

LEVEL: 2

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

REMEDIATE IN PLACE

OI&T

ROOM 221

EXISTING TR LOCATION(S)

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

ROOMS TO EXPAND IN

PLACE

BLDG: 6 4 6

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

REMEDIATE IN PLACE

IT

ROOM 1031

EXISTING TR LOCATION(S)

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

REMEDIATE IN PLACE

IT

EXISTING TR LOCATION(S)

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 6 4 7

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

N

EXISTING TR LOCATION(S)

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

EXISTING IT ROOM A216

RELOCATE TO BLDG. 649

ROOM B205

EXISTING SPACE TO BE USED AS

GENERAL STORAGE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

ROOMS TO EXPAND IN

PLACE

NOTE:

ALL ABANDONED TR ROOMS ARE TO BE

REPURPOSED AS GENERAL STORAGE OR AS

INDICATED ON FLOOR PLAN. MINIMUM

REQUIREMENTS FOR TR ROOMS TO BE

ABANDONED:

• REMOVE ALL IT EQUIPMENT

• SEAL ALL PENETRATIONS IN ACCORDANCE

WITH FIRE REQUIREMENTS

• PROVIDE NEW VCT FLOORING

• REMOVE EXISTING PLYWOOD ON WALLS,

PATCH, REPAIR AND PAINT WALLS

BLDG: 6 4 9

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

N

EXPAND IN PLACE

IT

ROOM B203

EXPAND INTO

ROOM B205

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

ROOMS TO EXPAND IN

PLACE

EXISTING TR LOCATION(S)

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

BLDG: 650

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

REMEDIATE IN PLACE

MDF

ROOM 1A026

EXISTING TR LOCATION(S)

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

IT

ROOM 1B235

ROOM 1.5 WILL RELOCATE

TO 1B235

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

EXPAND IN PLACE

IT

ROOM 1C900

EXISTING TR LOCATION(S)

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

IT

ROOM 1C302

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

SCALE: 1/32” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

SERVER

ROOM 1E272

RELOCATE DATA CABLING TO IT ROOM 1A026

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 6 5 0

SCALE: 1/32” = 1’-0”

DATE: 12/22/2020

N

REMEDIATE IN PLACE

IT

ROOM 2B005

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

ROOMS TO EXPAND IN

PLACE

NOTE:

ALL ABANDONED TR ROOMS ARE TO BE

REPURPOSED AS GENERAL STORAGE OR AS

INDICATED ON FLOOR PLAN. MINIMUM

REQUIREMENTS FOR TR ROOMS TO BE

ABANDONED:

• REMOVE ALL IT EQUIPMENT

• SEAL ALL PENETRATIONS IN ACCORDANCE

WITH FIRE REQUIREMENTS

• PROVIDE NEW VCT FLOORING

• REMOVE EXISTING PLYWOOD ON WALLS,

PATCH, REPAIR AND PAINT WALLS

LEVEL: 3

SCALE: 1/32” = 1’-0”

DATE: 12/22/2020

REMEDIATE IN PLACE

IT

ROOM 3B002

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 6 5 1

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

REMEDIATE IN PLACE

IT

ROOM 115

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 6 5 2

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

REMEDIATE IN PLACE

IT

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

N

ABANDON MEZZANINE RACK.

RELOCATE TO IT ROOM 105

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 7 0 0

SCALE: 1/32” = 1’-0”

DATE: 12/22/2020

EXPAND IN PLACE

IT

1A220

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

IT

1B111

REMEDIATE IN PLACE

IT

A113

(LOCATED IN NEW CATH LAB AREA)

N

IT

1A526

RELOCATE TO DATA CENTER

EXISTING SPACE TO BE USED AS

GENERAL STORAGE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

ROOMS TO EXPAND IN

PLACE

NOTE:

ALL ABANDONED TR ROOMS ARE TO BE

REPURPOSED AS GENERAL STORAGE OR AS

INDICATED ON FLOOR PLAN. MINIMUM

REQUIREMENTS FOR TR ROOMS TO BE

ABANDONED:

• REMOVE ALL IT EQUIPMENT

• SEAL ALL PENETRATIONS IN ACCORDANCE

WITH FIRE REQUIREMENTS

• PROVIDE NEW VCT FLOORING

• REMOVE EXISTING PLYWOOD ON WALLS,

PATCH, REPAIR AND PAINT WALLS

SCALE: 1/32” = 1’-0”

DATE: 12/22/2020

REMEDIATE IN PLACE

IT

2A112

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

EXISTING IT

ROOM 2A317

RELOCATE TO 2A112

EXISTING SPACE TO BE USED AS

GENERAL STORAGE

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

ROOMS TO EXPAND IN

PLACE

NOTE:

ALL ABANDONED TR ROOMS ARE TO BE

REPURPOSED AS GENERAL STORAGE OR AS

INDICATED ON FLOOR PLAN. MINIMUM

REQUIREMENTS FOR TR ROOMS TO BE

ABANDONED:

• REMOVE ALL IT EQUIPMENT

• SEAL ALL PENETRATIONS IN ACCORDANCE

WITH FIRE REQUIREMENTS

• PROVIDE NEW VCT FLOORING

• REMOVE EXISTING PLYWOOD ON WALLS,

PATCH, REPAIR AND PAINT WALLS

SCALE: 1/32” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

EXPAND IN PLACE

IT

3A012

N

NOTE:

EXPANSION WILL BE POSSIBLE AFTER

PHARMACY RELOCATES TO THE 5TH FLOOR.

IT ROOM 3A012 WILL SERVE BOTH 2ND AND

3RD FLOOR.

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

LEVEL: 4

SCALE: 1/32” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

IT

4A012

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

LEVEL: 5

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

IT

5A012

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 7 0 7

SCALE: 3/32” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

IT

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 7 2 0

SCALE: 1/32” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

IT ROOM 49

TO RELOCATE TO ROOM 23A

(EXISTING BREAKROOM)

NEW BREAKROOM TO EXPAND INTO

EXISTING HALL

NEW IT ROOM

23A

EXISTING ELEC. RM WILL

TRADE PLACES WITH THE EXISTING

BREAKROOM

N

RELOCATE EXISTING

ELECTRICAL PANELS

TO EXTERIOR OF BUILDING.

NOTE:

BUILDING 720 WILL SERVE BUILDINGS 722, 722A AND 802.

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 7 2 2

SCALE: 1/32” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

IT ROOM 126

RELOCATE TO BLDG. 720

EXISTING SPACE TO BE USED AS

GENERAL STORAGE

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

ROOMS TO EXPAND IN

PLACE

NOTE:

ALL ABANDONED TR ROOMS ARE TO BE

REPURPOSED AS GENERAL STORAGE OR AS

INDICATED ON FLOOR PLAN. MINIMUM

REQUIREMENTS FOR TR ROOMS TO BE

ABANDONED:

• REMOVE ALL IT EQUIPMENT

• SEAL ALL PENETRATIONS IN ACCORDANCE

WITH FIRE REQUIREMENTS

• PROVIDE NEW VCT FLOORING

• REMOVE EXISTING PLYWOOD ON WALLS,

PATCH, REPAIR AND PAINT WALLS

BLDG: 7 2 2 A

SCALE: 3/32” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

N

IT ROOM

RELOCATE TO BLDG. 720

EXISTING SPACE TO BE USED AS

GENERAL STORAGE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

ROOMS TO EXPAND IN

PLACE

NOTE:

ALL ABANDONED TR ROOMS ARE TO BE

REPURPOSED AS GENERAL STORAGE OR AS

INDICATED ON FLOOR PLAN. MINIMUM

REQUIREMENTS FOR TR ROOMS TO BE

ABANDONED:

• REMOVE ALL IT EQUIPMENT

• SEAL ALL PENETRATIONS IN ACCORDANCE

WITH FIRE REQUIREMENTS

• PROVIDE NEW VCT FLOORING

• REMOVE EXISTING PLYWOOD ON WALLS,

PATCH, REPAIR AND PAINT WALLS

BLDG: 7 2 6

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

IT

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 7 2 7

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

IT

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 7 2 8

SCALE: 3/32” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

IT/DATA

100A

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 7 3 0

SCALE: 3/32” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

IT

CABINET

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 7 9 8

SCALE: 1/8” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

EXPAND IN PLACE

IT

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 7 9 9

SCALE: 3/16” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

IT

206A

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 8 0 0

SCALE: 3/32” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

OI&T

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: T 8

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

SACRAMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

OI&T

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

I D E N T I F I C AT I O N O F N E T WO R K S PAC E S – M c C L E L L A N

BLDG: 2 9

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

McCLELLAN OUTPATIENT CLINIC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

IT

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 8 8

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

McCLELLAN OUTPATIENT CLINIC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

EXPAND IN PLACE

(EXTERIOR EXPANSION)

IT

1C05

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 9 8

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

McCLELLAN OUTPATIENT CLINIC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

N

EXISTING IT ROOM 1B02A

RELOCATE TO NEW

TR ROOM, 1ST FLOOR

EXISTING SPACE TO BE USED FOR

LACTATION ROOM EXPANSION

EXISTING OI&T

ROOM 1A20B

RELOCATE TO 2S09B

EXISTING SPACE TO BE ADDITIONAL

STORAGE FOR WAREHOUSE USE

EXISTING IT

ROOM 1E09

RELOCATE TO NEW TR ROOM, 1ST

FLOOR

EXISTING SPACE TO BE USED AS

GENERAL STORAGE

EXISTING IT

ROOM 1Z09

RELOCATE TO 2S09B

EXISTING SPACE TO BE USED

AS GENERAL STORAGE

REMEDIATE IN PLACE

NEW IT ROOM

123 SF

NOTE: NEW TR ROOM 2S098 TO SERVE

THE NORTH (PLAN NORTH) SIDE OF FLOOR.

THE NEW TR ROOM ON THE 1ST FL.

WILL SERVE THE SOUTH (PLAN SOUTH)

SIDE OF THE FLOOR

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

ROOMS TO EXPAND IN

PLACE

NOTE:

ALL ABANDONED TR ROOMS ARE TO BE

REPURPOSED AS GENERAL STORAGE OR AS

INDICATED ON FLOOR PLAN. MINIMUM

REQUIREMENTS FOR TR ROOMS TO BE

ABANDONED:

• REMOVE ALL IT EQUIPMENT

• SEAL ALL PENETRATIONS IN ACCORDANCE

WITH FIRE REQUIREMENTS

• PROVIDE NEW VCT FLOORING

• REMOVE EXISTING PLYWOOD ON WALLS,

PATCH, REPAIR AND PAINT WALLS

BLDG: 9 8

SCALE: 1/32” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

McCLELLAN OUTPATIENT CLINIC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

EXISTING IT

ROOM 2T09A

RELOCATE TO 2S09B

EXISTING SPACE TO BE USED AS

GENERAL STORAGE

N

EXISTING OI&T

ROOM 2S13A

RELOCATE TO 2S09B

ROOM 2M20A TO BE USED

TO RUN CABLES TO THE

FIRST FLOOR

IT

2M20A

RELOCATE TO NEW TR ROOM,

LEVEL 1

EXISTING IT

ROOM 2M43

(NOT LISTED ON OCAMES)

RELOCATE TO NEW TR ROOM, LEVEL 1

EXISTING SPACE TO BE USED AS

GENERAL STORAGE

NEW TR ROOM

2S09B

NOTE: NEW TR ROOM 2S098 TO SERVE

THE NORTH SIDE OF FLOOR.

THE NEW TR ROOM ON THE 1ST FL.

WILL SERVE THE SOUTH SIDE OF THE

FLOOR

EXISTING SPACE TO BE USED AS

GENERAL STORAGE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

ROOMS TO EXPAND IN

PLACE

NOTE:

ALL ABANDONED TR ROOMS ARE TO BE

REPURPOSED AS GENERAL STORAGE OR AS

INDICATED ON FLOOR PLAN. MINIMUM

REQUIREMENTS FOR TR ROOMS TO BE

ABANDONED:

• REMOVE ALL IT EQUIPMENT

• SEAL ALL PENETRATIONS IN ACCORDANCE

WITH FIRE REQUIREMENTS

• PROVIDE NEW VCT FLOORING

• REMOVE EXISTING PLYWOOD ON WALLS,

PATCH, REPAIR AND PAINT WALLS

BLDG: 2 0 9

LEVEL: BASEMENT

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

McCLELLAN OUTPATIENT CLINIC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

(E)

IT ROOM

136 SF

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

McCLELLAN OUTPATIENT CLINIC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

(E)

COMM ROOM

85 SF

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

McCLELLAN OUTPATIENT CLINIC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

(E)

COMM ROOM

130 SF

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 9 4 9

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

EXISTING TR LOCATION(S)

McCLELLAN OUTPATIENT CLINIC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

N

EXPAND IN PLACE

IT

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

N E T WO R K S PAC E D E S I G N : SAC R A M E N TO VA M C

** See Appendix E for Excel PDF with Estimated data from initial investigation

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

OI&T

N

MATHER BLDG. 645 ROOM 221 ABSORBING RM 114, BLD 645

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated 1.5 ton ductless split HVAC unit

X Insufficient redundant power connections for network equipment.

Provide 30A, 208V, 5 wire NEMA

L21-30R receptacle, from a normal power source, mounted near the equipment rack.

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

X Piping over equipment Relocate piping or pipe trough X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

Remote Controlled battery thermostat Wired thermostat

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

200 Approximate total cable length

= 33000'.

Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

Inadequate rack space for new equipment Provide new rack as required.

X

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

IT

N

MATHER BLDG. 646 ROOM 1031

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate

Lower temp set point of dedicated

HVAC unit. If temp issue is not corrected then replace with new 1.5 ton ductless split HVAC unit

Insufficient redundant power connections for network equipment.

Provide 30A, 208V, 5 wire NEMA

L21-30R receptacle, from a normal power source, mounted near the equipment rack.

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

Piping over equipment Relocate piping or pipe trough X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

Remote Controlled battery

Thermostat Wired thermostat

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

TBD Approximate total cable length

= TBD

Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

Inadequate rack space for new equipment Provide new rack as required.

SCALE: 1/16” = 1’-0”

DATE: 12/22/2020

IT

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

N

MATHER BLDG. 646 ROOM 2028

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated 1.5 ton ductless split HVAC unit

X Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA

L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

Piping over equipment Relocate piping or pipe trough X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

Remote Controlled battery thermostat Wired thermostat

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

TBD Approximate total cable length

= TBD

Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

Inadequate rack space for new equipment

BLDG: 6 4 9

SCALE: 1/4” = 1’-0”

DATE: 12/22/2020

N

B203 & B205

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

IT ROOM B203

123 SF

REMOVE EXISTING

WALL BETWEEN

ROOM B203 AND

B205. EXPAND TR

ROOM B203

NEW WALL

ROOM B205

MATHER BLDG. 649 ROOM B205 ABSORBING ROOM A216 FROM BLD 647

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Needs dedicated 1.5 ton ductless split HVAC unit

X Insufficient redundant power connections for network equipment.

Provide 30A, 208V, 5 wire NEMA

L21-30R receptacle, from a normal power source, mounted near the equipment rack.

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

X Piping over equipment Relocate piping or pipe trough X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

Remote Controlled battery thermostat Wired thermostat X

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

400. Approximate total cable length

= 66000'

X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

X Inadequate rack space for new equipment Provide 5 new racks.

SCALE: 1/4” = 1’-0”

DATE: 12/22/2020

1A026

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

IT

1A026

Data cabling from 1E272 is

Being moved to this room.

MATHER BLDG. 650 ROOM 1A026 (MDF) UNSURVEYED

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Needs dedicated 1.5 ton ductless split HVAC unit

X Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA

L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

Insufficient Central UPS power backup.

Design Build contractor to determine size of Central UPS.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

X Missing Telecom Main Ground Bar

(TMGB)

Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from

BMS

X Inadequate grounding connections to metal objects in date canter.

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

X Piping over equipment If water piping is overhead then relocate piping or add pipe trough

X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X No redundant fiber optic cable feeds entering the building on opposite faces.

Install new as required

Remote Controlled battery thermostat Wired thermostat

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

TBD Approximate total cable length

= TBD'

X Micro condensate pump Commercial condensate pump Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

Inadequate rack space for new equipment Provide new rack as required.

XXX

SCALE: 1/4” = 1’-0”

DATE: 12/22/2020

1B235

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

IT

1B235

NOTE: ROOM 1.5 WILL

RELOCATE TO 1B235

MATHER BLDG. 650 ROOM 1B235 ABSORBING ROOM 1.5

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate

Absorbing room 1.5. Needs dedicated 1.5 ton ductless split

HVAC unit

X Insufficient redundant power connections for network equipment.

Provide 30A, 208V, 5 wire NEMA

L21-30R receptacle, from a normal power source, mounted near the equipment rack.

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

Piping over equipment Relocate piping or pipe trough X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

Remote Controlled battery thermostat

Wired thermostat X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

200 Approximate total cable length

= 33000'.

X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

Inadequate rack space for new

SCALE: 1/4” = 1’-0”

DATE: 12/22/2020

1C302

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

REMEDIATE IN PLACE

IT

ROOM 1C302IT

1C302

NOTE: REMOVE STORAGE SHELVING FROM IT ROOM

TO PROVIDE ADDITIONAL SPACE FOR CERNER RACKS

MATHER BLDG. 650 ROOM 1C302

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Needs dedicated 1.5 ton ductless split HVAC unit

X Insufficient redundant power connections for network equipment.

Provide 30A, 208V, 5 wire NEMA

L21-30R receptacle, from a normal power source, mounted near the equipment rack.

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

X Piping over equipment Relocate piping or pipe trough X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

Remote Controlled battery thermostat Wired thermostat

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

TBD Approximate total cable length

= TBD

X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

X Inadequate rack space for new equipment Provide 2 new racks.

SCALE: 1/4” = 1’-0”

DATE: 12/22/2020

1C900

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

IT

1C900

126 SF

REMOVE EXISTING

WALL BETWEEN

ROOM 1C900 AND

1C700A. EXPAND

IT ROOM INTO

1C700A

NEW WALL

RELOCATE

EXISTING DOOR.

INFILL OPENING.

PATCH AND

REPAIR AS

NEEDED

EXISTING OFFICE

1C700A

NEW DOOR

LOCATION.

REMOVE

PORTION OF

WALL FOR NEW

DOOR.

MATHER BLDG. 650 ROOM 1C900

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Needs dedicated 1.5 ton ductless split HVAC unit

X Insufficient redundant power connections for network equipment.

Provide 30A, 208V, 5 wire NEMA

L21-30R receptacle, from a normal power source, mounted near the equipment rack.

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

X Piping over equipment Relocate piping or pipe trough X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

Remote Controlled battery thermostat Wired thermostat

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

TBD Approximate total cable length

= TBD

X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

X Inadequate rack space for new equipment Provide new rack.

SCALE: 1/4” = 1’-0”

DATE: 12/22/2020

1E272

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

SERVER

1E272

NOTE:

RELOCATE DATA

CABLING TO IT

ROOM 1A026

MATHER BLDG. 650 ROOM 1E-272

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated 1.5 ton ductless split HVAC unit

X Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA

L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insufficient Central UPS power backup.

Design Build contractor to determine size of Central UPS.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

X Missing Telecom Main Ground Bar

(TMGB)

Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs three (3) new temperature monitoring sensors and humidity sensors per rack.

Provide controls from BMS

X Inadequate grounding connections to metal objects in date canter.

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

Piping over equipment Relocate piping or pipe trough

UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X No redundant fiber optic cable feeds entering the building on opposite faces.

Install new as required

Remote Controlled battery thermostat Wired thermostat

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

TBD Approximate total cable length

= TBD'

Micro condensate pump Commercial condensate pump Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

Inadequate rack space for new equipment Provide new rack as required.

X

SCALE: 1/4” = 1’-0”

DATE: 12/22/2020

2B005

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

IT

2B005

MATHER BLDG. 650 ROOM 2B005

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated 1.5 ton ductless split HVAC unit

X Insufficient redundant power connections for network equipment.

Provide 30A, 208V, 5 wire NEMA

L21-30R receptacle, from a normal power source, mounted near the equipment rack.

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

Piping over equipment Relocate piping or pipe trough X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

Remote Controlled battery thermostat

Wired thermostat Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

TBD Approximate total cable length

= TBD

Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

Inadequate rack space for new equipment

SCALE: 1/4” = 1’-0”

DATE: 12/22/2020

3B002

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

IT

3B002

NOTE:.

REMOVE LEGACY PHONE SYSTEM

MATHER BLDG. 650 ROOM 3B002

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Needs dedicated 1.5 ton ductless split HVAC unit

X Insufficient redundant power connections for network equipment.

Provide 30A, 208V, 5 wire NEMA

L21-30R receptacle, from a normal power source, mounted near the equipment rack.

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

Piping over equipment Relocate piping or pipe trough X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

Remote Controlled battery thermostat

Wired thermostat Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

TBD Approximate total cable length

= TBD

X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

Inadequate rack space for new equipment

BLDG: 6 5 1

SCALE: 1/4” = 1’-0”

DATE: 12/22/2020

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

IT

MATHER BLDG. 651 ROOM 115

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated 1.5 ton ductless split HVAC unit

X Insufficient redundant power connections for network equipment.

Provide 30A, 208V, 5 wire NEMA

L21-30R receptacle, from a normal power source, mounted near the equipment rack.

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

X Piping over equipment Relocate piping or pipe trough X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

Remote Controlled battery thermostat Wired thermostat

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

TBD Approximate total cable length

= TBD

Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

Inadequate rack space for new equipment

BLDG: 6 5 2

SCALE: 1/4” = 1’-0”

DATE: 12/22/2020

SACREMENTO VAMC

NORTHERN CALIFORNIA HEALTH CARE SYSTEM

ELECTRICAL ROOM

NOTE: CABINET AT

MEZZANINE TO RELOCATE

TO ROOM 105

MATHER BLDG.